ML11348A110

From kanterella
Jump to navigation Jump to search
TRM1, Technical Requirements Manual, Unit 1
ML11348A110
Person / Time
Site: Susquehanna Talen Energy icon.png
Issue date: 12/01/2011
From:
Susquehanna
To: Gerlach R
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML11348A110 (40)


Text

Dec.

01, 2011 Page 1

of 2

MANUAL HARD COPY DISTRIBUTION DOCUMENT TRANSMITTAL 2011-66949 USER INFORMATION:

GERLACH*ROSE M EMPL#:028401 CA#:

0363 Address: NUCSA2 Phone#:

254-3194 TRANSMITTAL INFORMATION:

TO:

GERLACH*ROSE M 12/01/2011 LOCATION:

USNRC

  • FROM:

NUCLEAR RECORDS DOCUMENT CONTROL CENTER (NUCSA-2)

THE FOLLOWING CHANGES HAVE OCCURRED TO THE HARDCOPY OR ELECTRONIC MANUAL ASSIGNED TO YOU.

HARDCOPY USERS MUST ENSURE THE DOCUMENTS PROVIDED MATCH THE INFORMATION ON THIS TRANSMITTAL.

WHEN REPLACING THIS MATERIAL IN YOUR HARDCOPY MANUAL, ENSURE THE UPDATE DOCUMENT ID IS THE SAME DOCUMENT ID YOU'RE REMOVING FROM YOUR MANUAL.

TOOLS FROM THE HUMAN PERFORMANCE TOOL BAG SHOULD BE UTILIZED TO ELIMINATE THE CHANCE OF ERRORS.

ATTENTION:

"REPLACE" directions do not affect the Table of Contents, Therefore no TOC will be issued with the updated material.

TRMl -

TECHNICAL REQUIREMENTS MANUAL UNIT 1 REMOVE MANUAL TABLE OF CONTENTS DATE: 11/24/2011 ADD MANUAL TABLE OF CONTENTS DATE: 11/30/2011 CATEGORY:

DOCUMENTS TYPE: TRM1 ADO(

Dec.

01, 2011 Page 2

of 2

ID:

TEXT 3.7.3.8 REMOVE:

REV:8 ADD:

REV:

9 CATEGORY:

DOCUMENTS TYPE: TRM1 ID:

TEXT B3.7.3.8 REMOVE:

REV:I ADD:

REV:

2 CATEGORY:

DOCUMENTS TYPE:

TRM1 ID:

TEXT LOES REMOVE:

REV:68 ADD:

REV:

69 ANY DISCREPANCIES WITH THE MATERIAL PROVIDED, CONTACT DCS @ X3107 OR X3136 FOR ASSISTANCE.

UPDATES FOR HARDCOPY MANUALS WILL BE DISTRIBUTED WITHIN 3 DAYS IN ACCORDANCE WITH DEPARTMENT PROCEDURES.

PLEASE MAKE ALL CHANGES AND ACKNOWLEDGE COMPLETE IN YOUR NIMS INBOX UPON COMPLETION OF UPDATES.

FOR ELECTRONIC MANUAL

USERS, ELECTRONICALLY REVIEW THE APPROPRIATE DOCUMENTS AND ACKNOWLEDGE COMPLETE IN YOUR NIMS INBOX.

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 Table Of Contents Issue Date:

I Procedure Name TEXT LOES

Title:

LIST OF EF 1/30/2011 Rev 69 FECTIVE SECTIONS Issue Date 11/30/2011 Change ID Change Number TEXT TOC

Title:

20 08/23/2011 TABLE OF CONTENTS TEXT 1.1 0

11/18/2002

Title:

USE AND APPLICATION DEFINITIONS TEXT 2.1 1

02/04/2005

Title:

PLANT PROGRAMS AND SETPOINTS PLANT PROGRAMS TEXT 2.2 9

01/13/2011

Title:

PLANT PROGRAMS AND SETPOINTS INSTRUMENT TRIP SETPOINT TABLE LDCN 4414 TEXT 3.0 A

05/23/2008

Title:

TECHNICAL REQUIREMENT FOR OPERATION (TRO)

APPLICABILITY & SURVEILLANCE (TRS)

APPLICABILITY TEXT 3.1.1 1

11/09/2007

Title:

REACTIVITY CONTROL SYSTEMS ANTICIPATED INJECTION (ATWS-ARI)

INSTRUMENTATION TEXT 3.1.2 0

11/18/2002

Title:

REACTIVITY CONTROL SYSTEMS CONTROL ROD TEXT 3.1.3 5

04/16/2009

Title:

REACTIVITY CONTROL SYSTEMS CONTROL ROD TEXT 3.1.4 0

11/18/2002

Title:

REACTIVITY CONTROL SYSTEMS CONTROL ROD CHECK VALVE TEXT 3.2.1 12 01/25/2011

Title:

CORE OPERATING LIMITS REPORT (COLR)

TRANSIENT WITHOUT SCRAM ALTERNATE ROD DRIVE (CRD)

HOUSING SUPPORT BLOCK INSTRUMENTATION SCRAM ACCUMULATORS INSTRUMENTATION &

Pagel' of 16 Report Date: 12/01/11 Page 1 '

of

.16 Report Date: 12/01/11

SSES MANUALJ Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 3.3.1 0

11/18/2002

Title:

INSTRUMENTATION RADIATION MONITORING INSTRUMENTATION TEXT 3.3.2 3

03/31/2011

Title:

INSTRUMENTATION SEISMIC MONITORING INSTRUMENTATION TEXT 3.3.3 2

'11/09/2007

Title:

INSTRUMENTATION METEOROLOGICAL MONITORING INSTRUMENTATION TEXT 3.3.4 6

07/09/2010

Title:

INSTRUMENTATION TRM POST-ACCIDENT MONITORING INSTRUMENTATION TEXT 3.3.5 0

11/18/2002

Title:

INSTRUMENTATION THIS PAGE INTENTIONALLY LEFT BLANK TEXT 3.3.6 3

01/13/2011

Title:

INSTRUMENTATION TRM ISOLATION ACTUATION INSTRUMENTATION TEXT 3.3.7 1

11/09/2'007

Title:

INSTRUMENTATION MAIN TURBINE OVERSPEED PROTECTION SYSTEM TEXT 3.3.8 1

10/22/2003

Title:

INSTRUMENTATION TRM RPS INSTRUMENTATION TEXT 3.3.9 3

04/17/2008

Title:

OPRM INSTRUMENTATION CONFIGURATION TEXT 3.3.10 1

12/14/2004

Title:

INSTRUMENTATION REACTOR RECIRCULATION PUMP MG SET STOPS TEXT 3.3.11 1

10/22/2003

Title:

INSTRUMENTATION MVP ISOLATION INSTRUMENTATION TEXT 3.3.12 0

04/16/2009

Title:

WATER MONITORING INSTRUMENTATION Page 2 of 16 Report Date: 12/01/11 Page2 of 16 Report Date: 12/01/11

SSES MANUAL

.i Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 3.4.1

Title:

REACTOR TEXT 3.4.2

Title:

REACTOR TEXT 3.4.3

Title:

REACTOR TEXT 3.4.4

Title:

REACTOR TEXT 3.4.5

Title:

REACTOR TEXT 3.4.6

Title:

REACTOR TEXT 3.5.1 1

04/26/2006 COOLANT SYSTEM REACTOR COOLANT SYSTEM CHEMISTRY 1

04/16/2009 COOLANT SYSTEM STRUCTURAL INTEGRITY 1

11/09/2007 COOLANT SYSTEM HIGH/LOW PRESSURE INTERFACE LEAKAGE MONITORS 2

04/17/2008 COOLANT SYSTEM REACTOR RECIRCULATION FLOW AND ROD LINE LIMIT 1

04/26/2006 COOLANT SYSTEM REACTOR VESSEL MATERIALS 1

06/15/2010 RECIRCULATION SINGLE LOOP OPERATION SLO FLOW RATE RESTRICTION 02/04/2005

Title:

EMERGENCY CORE COOLING AND RCIC ADS MANUAL INHIBIT TEXT 3.5.2 1

11/09/2007

Title:

EMERGENCY CORE COOLING AND RCIC ECCS.AND RCIC SYSTEM MONITORING INSTRUMENTATION TEXT 3.5.3 0

11/18/2002

Title:

EMERGENCY CORE COOLING AND RCIC LONG TERM NITROGEN SUPPLY TO ADS I

TEXT 3.6.1 0

11/18/2002

Title:

CONTAINMENT VENTING OR PURGING TEXT 3.6.2 1

08/23/2011

Title:

SUPPRESSION CHAMBER TO DRYWELL VACUUM BREAKER POSITION INDICATION TEXT 3.6.3 0

11/18/2002

Title:

CONTAINMENT SUPPRESSION POOL ALARM INSTRUMENTATION Page 3 of 16 Report Date: 12/01/11 Page 3 of 16 Report Date: 12/01/11

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 3.6.4 0

11/18/2002

Title:

CONTAINMENT PRIMARY CONTAINMENT CLOSED SYSTEM BOUNDARIES TEXT 3.7.1

Title:

PLANT TEXT 3.7.2

Title:

PLANT TEXT 3.7.3.1

Title:

PLANT TEXT 3.7.3.2

Title:

PLANT TEXT 3.7.3.3

Title:

PLANT 0

11/18/2002 SYSTEMS EMERGENCY SERVICE WATER SYSTEM (ESW)

SHUTDOWN 0

11/18/2002 SYSTEMS ULTIMATE HEAT SINK (UHS)

AND GROUND WATER LEVEL 2

04/16/2009 SYSTEMS FIRE SUPPRESSION WATER SUPPLY SYSTEM 3

04/16/2009 SYSTEMS SPRAY AND SPRINKLER SYSTEMS 3

SYSTEMS C02 SYSTEMS 04/16/2009 04/16/2009 TEXT 3.7.3.4

Title:

PLANT SYSTEMS 2

HALON SYSTEMS TEXT 3.7.3.5

Title:

PLANT TEXT 3.7.3.6

Title:

PLANT TEXT 3.7.3.7

Title:

PLANT TEXT 3.7.3.8

Title:

PLANT TEXT 3.7.4

Title:

PLANT 2

04/16/2009 SYSTEMS FIRE HOSE STATIONS 2

04/16/2009 SYSTEMS YARD FIRE HYDRANTS AND HYDRANT HOSE HOUSES 1

04/26/2006 SYSTEMS FIRE RATED ASSEMBLIES 9

11/30/2011 SYSTEMS FIRE DETECTION INSTRUMENTATION LDCN 1

04/26/2006 SYSTEMS SOLID RADWASTE SYSTEM 3503 Page 4

.~of. 16 Report Date: 12/01/11 Page 4 ý _

of, 1_6 Report Date: 12/01/11-

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 3.7.5.1 0

11/18/2002

Title:

PLANT SYSTEMS MAIN CONDENSER OFFGAS HYDROGEN MONITOR TEXT 3.7.5.2 01,

.11/18/2002

Title:

PLANT SYSTEMS MAIN CONDENSER OFFGAS EXPLOSIVE GAS MIXTURE TEXT 3.7.5.3 1

04/26/2006.

Title:

PLANT SYSTEMS LIQUID HOLDUP TANKS TEXT 3.7.6 2

06/27/2008.

Title:

PLANT SYSTEMS ESSW PUMPHOUSE VENTILATION TEXT 3.7.7 2

09/05/2008

Title:

PLANT.SYSTEMS MAIN CONDENSER OFFGAS PRETREATMENT LOGARITHMIC RADIATION MONITORING TEXT 3.7.8 4

06/21/2007

Title:

PLANT SYSTEMS SNUBBERS TEXT 3.7.9 1

08/28/2006

Title:

PLANT SYSTEMS CONTROL STRUCTURE HVAC TEXT 3.7.10 1

12/14/2.004

Title:

PLANT SYSTEMS SPENT FUEL STORAGE POOLS (SFSPS)

TEXT 3.7. 11 0

.04/16/2009

Title:

STRUCTURAL INTEGRITY TEXT 3.8.1 2

04/05/2010

Title:

ELECTRICAL POWER PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TEXT 3.8.2.1 2

11/09/2007

Title:

ELECTRICAL POWER MOTOR OPERATED VALVES (MOV)

THERMAL OVERLOAD PROTECTION CONTINUOUS D

TEXT 3.8.2.2 2

12/14/2004

Title:

ELECTRICAL POWER MOTOR OPERATED VALVES (MOV)

THERMAL OVERLOAD PROTECTION AUTOMATIC Page 5 of

.16 Report Date: 12/01/11

SSES MANUAL Manual Name:

TRM1 Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 3.8.3

Title:

ELECTRICAL TEXT 3.8.4

Title:

ELECTRICAL TEXT 3.8.5

Title:

ELECTRICAL TEXT 3.8.6

Title:

ELECTRICAL TEXT 3.8.7 1

04/05/2010 POWER DIESEL GENERATOR (DG)

MAINTENANCE ACTIVITIES 0

11/18/2002 POWER 24 VDC ELECTRICAL POWER SUBSYSTEM o

11/18/2002 POWER DEGRADED VOLTAGE PROTECTION 0

11/18/2002 POWER EMERGENCY SWITCHGEAR ROOM COOLING 1

06/15/2009

Title:

BATTERY MAINTENANCE AND MONITORING-PROGRAM TEXT 3.9.1 0

11/18/2002-

Title:

REFUELING OPERATIONS DECAY TIME TEXT 3.9.2 0

11/18/2002

Title:

REFUELING OPERATIONS COMMUNICATIONS TEXT 3.9.3 0

11/18/2002

Title:

REFUELING OPERATIONS REFUELING PLATFORM' TEXT 3.10.1 1

04/26/2006

Title:

MISCELLANEOUS SEAL SOURCE CONTAMINATION TEXT 3.10.2 2

08/08/2006

Title:

MISCELLANEOUS SHUTDOWN MARGIN TEST RPS INSTRUMENTATION TEXT 3.10.3 2

06/15/201:0

Title:

MISCELLANEOUS INDEPENDENT SPENT FUEL STORAGE INSTALLATION (ISFSI)

TEXT 3.10.4 2

04/17/2008

Title:

MISCELLANEOUS LEADING EDGE FLOW METER (LEFM)

Page 6 16 Report Date: 12/01/11 Page 6 of 16 Report Date: 12/01/11

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 3.11.1.1

Title:

RADIOACTIVE TEXT 3.11.1.2

Title:

RADIOACTIVE TEXT 3.11.1.3

Title:

RADIOACTIVE TEXT 3.11.1.4

Title:

RADIOACTIVE TEXT 3.11.1.5

Title:

RADIOACTIVE TEXT 3.11.2.1

Title:

RADIOACTIVE TEXT 3.11.2.2

Title:

RADIOACTIVE TEXT 3.11.2.3

Title:

RADIOACTIVE FORM TEXT 3.11.2.4

Title:

RADIOACTIVE TEXT 3.11.2.5

Title:

RADIOACTIVE TEXT 3.11.2.6

Title:

RADIOACTIVE TEXT 3.11.3

Title:

RADIOACTIVE EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS 1

04/26/2006 LIQUID EFFLUENTS CONCENTRATION 1

04/26/2006 LIQUID EFFLUENTS DOSE 1

04/26/2006 LIQUID WASTE TREATMENT SYSTEM 1

12/14/2004 LIQUID RADWASTE-EFFLUENT MONITORING.INSTRUMENTATION 2

05/02/2007 RADIOACTIVE LIQUID. PROCESS MONITORING INSTRUMENTATION' 3

04/26./2006 DOSE RATE 1

04/26/2006 DOSE -

NOBLE GASES 1

04/26/2006 DOSE -

IODINE, TRITIUM, AND RADIONUCLIDES IN PARTICULATE 0

11/18/2002, GASEOUS RADWASTE TREATMENT SYSTEM 3

11/14/2006 VENTILATION EXHAUST TREATMENT SYSTEM 4

09/16/2009 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION 1

04/26/2006 TOTAL DOSE Page 1 of 16 Report Date: 12/01/il Page.1 of 16 Report Date: i2/01/11

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 3.11.4.1 4

08/08/2006

Title:

RADIOACTIVE EFFLUENTS MONITORING PROGRAM TEXT 3.11.4.2 2

04/26/2006

Title:

RADIOACTIVE EFFLUENTS LAND USE CENSUS TEXT 3.11.4.3 1

04/26/2006

Title:

RADIOACTIVE EFFLUENTS INTERLABORATORY COMPARISON PROGRAM TEXT 3.12.1 0

11/19/2002:

Title:

LOADS CONTROL PROGRA M CRANE TRAVEL-SPENT FUEL POOL STORAGE POOL TEXT 3.12.2 4

04/17/2008

Title:

LOADS CONTROL PROGRAM HEAVY LOADS REQUIREMENTS TEXT 3.12.3 0

11/19/2002

Title:

LOADS CONTROL PROGRAM LIGHT LOADS REQUIREMENT TEXT 4.1

Title:

TEXT 4.2

Title:

TEXT 4.3

Title:

TEXT 4.4

Title:

TEXT 4.5

Title:

TEXT 4.6

Title:

0 CONTROLS ADMINISTRATIVE ADMINISTRATIVE CONTROLS 0

CONTROLS ADMINISTRATIVE 08/31/1998 ORGANIZATION 08/31/1998 REPORTABLE EVENT ACTION 08/31/1998 SAFETY LIMIT VIOLATION 12/18/2008 PROCEDURES & PROGRAMS 08/31/1998 REPORTING REQUIREMENTS 08/31/1998 RADIATION PROTECTION PROGRAM ADMINISTRATIVE CONTROLS 0

ADMINISTRATIVE CONTROLS 0

ADMINISTRATIVE CONTROLS Page 8 of 16 Report Date: 12/01/11 Page 8 of 16 Report Date: 12/01/11

SSES MANUAL Manual Name:

TRM1 Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT 4.7 0

08/31/1998

Title:

ADMINISTRATIVE CONTROLS TRAINING TEXT B3.0 4

05/23/2008

Title:

APPLICABILITY BASES TECHNICAL REQUIREMENT FOR OPERATION (TRO)

APPLICABILITY, TEXT B3.1.1 1

11/09/2007

Title:

REACTIVITY CONTROL SYSTEMS BASES ANTICIPATED TRANSIENT WITHOUT SCRAM ALTERNATE ROD INJECTION (ATWS-ARI)

INSTRUMENTATION TEXT B3.1.2 0

11./19/2002

Title:

REACTIVITY CONTROL SYSTEMS BASES CONTROL ROD DRIVE (CRD)

HOUSING SUPPORT TEXT B3.1.3 3

03/31/2006

Title:

REACTIVITY CONTROL SYSTEMS, BASES CONTROL ROD BLOCK INSTRUMENTATION, TEXT B3.1.4 0

11/19/2002

Title:

REACTIVITY CONTROL SYSTEMS BASES CONTROL ROD SCRAM ACCUMULATORS INSTRUMENTATION AND CHECK VALVE TEXT B3.2.1 0

1i/19/*2002

Title:

CORE OPERATING LIMITS BASES CORE OPERATING LIMITS REPORT (COLR)

TEXT B3.3.1

Title:

INSTRUMENTATION TEXT B3.3.2

Title:

INSTRUMENTATION TEXT B3.3.3

Title:

INSTRUMENTATION TEXT B3.3.4

Title:

INSTRUMENTATION TEXT B3.3.5

Title:

INSTRUMENTATION 0

11/19/2002 BASES RADIATION MONITORING INSTRUMENTATION 2

. 03/31/2011 BASES SEISMIC MONITORING INSTRUMENTATION 3

12/18/2008 BASES METEOROLOGICAL MONITORING INSTRUMENTATION 4

07/09/2010 BASES TRM POST ACCIDENT MONITORING (PAM)

INSTRUMENTATION 2

11/09/2007 BASES THIS PAGE INTENTIONALLY LEFT BLANK Page 9 of 16 Report Date: 12/01/11 Page 9 of 16 Report Date: 12/01/11

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT B3.3.6 4

01/13/2011

Title:

INSTRUMENTATION BASES TRM ISOLATION ACTUATION INSTRUMENTATION TEXT B3.3.7 1

11/09/2007

Title:

INSTRUMENTATION BASES MAIN TURBINE OVERSPEED PROTECTION SYSTEM TEXT B3.3.8 1

10/22/2003

Title:

INSTRUMENTATION BASES TRM REACTOR PROTECTION SYSTEM (RPS)

INSTRUMENTATION TEXT B3.3.9 3

04/17/2008

Title:

OPRM INSTRUMENTATION TEXT B3.3.10 3

08/09/2010

Title:

INSTRUMENTATION BASES REACTOR RECIRCULATION PUMP MG SET STOPS TEXT B3.3.11 1

10/22/2003

Title:

INSTRUMENTATION BASES MVP ISOLATION INSTRUMENTATION TEXT B3.3.12 0

04/16/2009

Title:

WATER MONITORING INSTRUMENTATION TEXT B3.4.1 0

11/19/2002

Title:

REACTOR COOLANT SYSTEM BASES REACTOR COOLANT SYSTEM CHEMISTRY TEXT B3.4.2 1

04/16/2009

Title:

REACTOR COOLANT SYSTEM BASES STRUCTURAL INTEGRITY TEXT B3.4.3 1

11/09/2007

Title:

REACTOR COOLANT SYSTEM BASES HIGH/LOW PRESSURE INTERFACE LEAKAGE MONITOR TEXT B3.4.4 0

11/19/2002

Title:

REACTOR COOLANT SYSTEM BASES REACTOR RECIRCULATION FLOW AND ROD LINE LIMIT TEXT B3.4.5 0

11/19/2002

Title:

REACTOR COOLANT SYSTEM BASES REACTOR VESSEL MATERIALS 4

Page 10 of 16 ReportDate: 12/01/11

SSES MANUJAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT B3.4.6 1-06/15/2010

Title:

REACTOR RECIRCULATION SINGLE LOOP OPERATION SLO FLOW RATE RESTRICTION TEXT B3.5.1 0

11/19/2002

Title:

ECCS AND RCIC BASES ADS MANUAL INHIBIT TEXT B3.5.2 1

11/09/2007

Title:

ECCS AND RCIC BASES ECCS AND RCIC SYSTEM MONITORING INSTRUMENTATION TEXT B3.5.3 1

11/09/2007

Title:

ECCS AND RCIC BASES LONG TERM NITROGEN SUPPLY TO ADS TEXT B3.6.1 0

11/19/2002

Title:

CONTAINMENT BASES VENTING OR PURGING TEXT B3.6.2 0

11/19/2002

Title:

CONTAINMENT BASES SUPPRESSION CHAMBER-TO-DRYWELL VACUUM BREAKER POSITION INDICATION TEXT B3.6.3 2

04/17/2008'

Title:

CONTAINMENT BASES SUPPRESSION POOL ALARM INSTRUMENTATION LDCN 3933 TEXT B3.6.4 1

12/14/2004

Title:

CONTAINMENT BASES PRIMARY CONTAINMENT CLOSED SYSTEM BOUNDARIES TEXT B3.7.1 0

11/19/2002

Title:

PLANT SYSTEMS BASES EMERGENCY SERVICE WATER SYSTEM (SHUTDOWN)

TEXT B3.7.2 0:

11/19/2002

Title:

PLANT SYSTEMS BASES ULTIMATE HEAT SINK (UHS)

GROUND WATER LEVEL TEXT B3.7.3.1 3

06/15/2010

Title:

PLANT SYSTEMS BASES FIRE SUPPRESSION WATER SUPPLY SYSTEM S TEXT B3.7.3.2 2

04/26/2006

Title:

PLANT SYSTEMS BASES SPRAY AND SPRINKLER SYSTEMS Page 11 of 16 Report Date: 12/01/11

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT B3.7.3.3

Title:

PLANT TEXT B3.7.3.4

Title:

PLANT TEXT B3.7.3.5

Title:

PLANT TEXT B3.7.3.6

Title:

PLANT TEXT B3.7.3.7

Title:

PLANT TEXT B3.7.3.8

Title:

PLANT TEXT B3.7.4

Title:

PLANT TEXT B3.7.5.1

Title:

PLANT TEXT B3.7.5.2

Title:

PLANT TEXT B3.7.5.3

Title:

PLANT TEXT B3.7.6

Title:

PLANT 0

11/19/2002 C02 SYSTEMS SYSTEMS BASES 1

04/26/2006 SYSTEMS BASES HALON SYSTEMS 1

04/26/2006 SYSTEMS BASES FIRE HOSE STATIONS 1

04/26/2006 SYSTEMS BASES YARD FIRE HYDRANTS AND HYDRANT HOSE HOUSES 0

11/19/2002 SYSTEMS BASES FIRE RATED ASSEMBLIES 2

11/30/2011 SYSTEMS BASES FIRE DETECTION INSTRUMENTATION 0

11/19/2002 SYSTEMS BASES SOLID RADWASTE SYSTEM 0

11/19/2002 SYSTEMS BASES MAIN CONDENSER OFFGAS HYDROGEN MONITOR 0

11/19/2002 SYSTEMS BASES MAIN CONDENSER OFFGAS EXPLOSIVE GAS MIXTURE 0

11/19/2002 SYSTEMS BASES LIQUID HOLDUP TANKS 2

06/27/2008 SYSTEMS BASES ESSW PUMPHOUSE VENTILATION 2

01/31/2008 TEXT B3.7.7

Title:

PLANT SYSTEMS BASES MAIN CONDENSER OFFGAS PRETREATMENT LOGARITHMIC RADIATION MONITORING INSTRUMENTATION Page 12 of 16 Report Date: 12/01/11

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT I TEXT B3.7.8

Title:

PLANT TEXT B3.7.9

Title:

PLANT TEXT B3.7.10

Title:

PLANT TEXT B3.7.11 3

06/21/2007 SYSTEMS BASES SNUBBERS 1

12/14/2004, SYSTEMS BASES CONTROL STRUCTURE HVAC 1

12/.14/2004.

SYSTEMS BASES SPENT FUEL STORAGE POOLS 1

04/14/2010

Title:

STRUCTURAL INTEGRITY TEXT B3.8.1

Title:

ELECTRICAL PROTECTIVE TEXT B3.8.2.1

Title:

ELECTRICAL CONTINUOUS TEXT B3.8.2.2

Title:

ELECTRICAL AUTOMATIC TEXT B3.8.3

Title:

ELECTRICAL TEXT B3.8.4

Title:

ELECTRICAL TEXT B3.8.5

Title:

ELECTRICAL TEXT B3.8.6

Title:

ELECTRICAL TEXT B3.8.7 2

.031101/2010.

POWER BASES PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT DEVICES 0

.11/19/2002.

POWER BASES MOTOR OPERATED VALVES (MOV)

THERMAL OVERLOAD PROTECTION -

1 09/,17/2004 POWER BASES MOTOR OPERATED VALVES (MOV)

THERMAL OVERLOAD 0

11/19/2002 POWER BASES DIESEL GENERATOR (DG)

MAINTENANCE ACTIVITIES

ý0 11/19/2002.,

POWER BASES 24 VDC ELECTRICAL POWER SUBSYSTEM 0

11/19/2002 POWER BASES DEGRADED VOLTAGE PROTECTION 1

02/0.4/2005 POWER BASES EMERGENCY SWITCHGEAR ROOM COOLING 1i 06/15/2009.,

PROTECTION -

Title:

BATTERY MAINTENANCE AND MONITORING PROGRAM Page 21 of 16 Report Date: 12/01/11 Page 13 of 16 Report Date: 12/01/11

SSES MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT B3.9.1 0

Title:

REFUELING OPERATIONS BASES 11/19/2002 DECAY TIME TEXT B3.9.2 0

11/19/2002

Title:

REFUELING OPERATIONS BASES COMMUNICATIONS TEXT B3.9.3 0

11/19/2002

Title:

REFUELING OPERATIONS BASES REFUELING PLATFORM TEXT B3.10.1 0

Title:

MISCELLANEOUS BASES SEALED 11/19/2002 SOURCE CONTAMINATION TEXT B3.10.2 1

03/31/2006

Title:

MISCELLANEOUS BASES SHUTDOWN MARGIN TEST RPS INSTRUMENTATION TEXT B3.10.3 0

11/19/2002

Title:

MISCELLANEOUS BASES INDEPENDENT SPENT FUEL STORAGE INSTALLATION (ISFSI)

TEXT B3.10.4 1

04/17/2008

Title:

MISCELLANEOUS BASES LEADING EDGE FLOW METER (LEFM)

TEXT B3.11.1.1

Title:

RADIOACTIVE TEXT B3.11.1.2

Title:

RADIOACTIVE TEXT B3.11.1.3

Title:

RADIOACTIVE TEXT B3.11.1.4

Title:

RADIOACTIVE 0

11/19/2002 BASES LIQUID EFFLUENTS CONCENTRATION EFFLUENTS EFFLUENTS EFFLUENTS EFFLUENTS 0

BASES 0

BASES 11/19/2002 LIQUID EFFLUENTS DOSE 11/19/2002 LIQUID WASTE TREATMENT SYSTEM 0

11/19/2002 BASES LIQUID RADWASTE EFFLUENT MONITORING INSTRUMENTATION TEXT B3.11.1.5

Title:

RADIOACTIVE EFFLUENTS INSTRUMENTATION 0

11/19/2002 BASES RADIOACTIVE LIQUID PROCESS MONITORING Page 14 of 16 Report Date: 12/01/11 Page 14 of 16 Report Date: 12/01/11

SSES MANUJAL Manual Name:

TRM1 Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT B3.11.2.1

Title:

RADIOACTIVE EFFLUENTS TEXT B3.11.2.2

Title:

RADIOACTIVE EFFLUENTS TEXT B3.11.2.3

Title:

RADIOACTIVE EFFLUENTS PARTICULATES FORM TEXT B3.11.2.4

Title:

RADIOACTIVE EFFLUENTS TEXT B3.11.2.5

Title:

RADIOACTIVE EFFLUENTS TEXT B3.11.2.6

Title:

RADIOACTIVE EFFLUENTS INSTRUMENTATION TEXT B3.11.3

Title:

RADIOACTIVE EFFLUENTS TEXT B3.11.4.1

Title:

RADIOACTIVE EFFLUENTS 1

12/14/2004 BASES DOSE RATE 0

11/19/2002 BASES DOSE -

NOBLE GASES 0

11/19/2002 BASES DOSE -

IODINE, TRITIUM, AND RADIONUCLIDES IN 0

11/1.9/2002 BASES GASEOUS RADWASTE TREATMENT SYSTEM 4

BASES 1 1 BASES 11/14/2006 VENTILATION EXHAUST 01/27/2004 RADIOACTIVE GASEOUS TREATMENT SYSTEM EFFLUENT MONITORING 0

  • 11/19/2002 BASES TOTAL DOSE 3

07/09/2010 BASES MONITORING PROGRAM TEXT B3.11.4.2 0

11/19/2002

Title:

RADIOACTIVE EFFLUENTS BASES LAND USE CENSUS TEXT B3.11.4.3 0

11/19/2002

Title:

RADIOACTIVE EFFLUENTS BASES INTERLABORATORY COMPARISON PROGRAM TEXT B3.12.1 1

10/04/2007

Title:

LOADS CONTROL PROGRAM BASES CRANE TRAVEL-SPENT FUEL STORAGE POOL TEXT B3.12.2 1

Title:

LOADS CONTROL PROGRAM BASES 12/03/2010 HEAVY LOADS REQUIREMENTS Page i~.

of ii Report Date: 12/01/11 Page 1_5 of 16 Report Date: 12/01/11

9SSE MANUAL Manual Name:

TRMI Manual

Title:

TECHNICAL REQUIREMENTS MANUAL UNIT 1 TEXT B3.12.3 0

11/19/2002

Title:

LOADS CONTROL PROGRAM BASES LIGHT LOADS REQUIREMENTS Pane 16 of 16 Report Date: 12/01/11 Page 16 of 16 Report Date: 12/01/11

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 69 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date TOC TABLE OF CONTENTS 1.0 2.0 USE AND APPLICATION Pages TRM / 1.0-1 through TRM / 1.0-3 PLANT PROGRAMS Page 2.0-1 Pages TRM / 2.0-2 and TRM / 2.0-3 Page TRM / 2.0-4 Page TRM / 2.0-5 Page TRM / 2.0-6 Page TRM / 2.0-7 Pages TRM / 2.0-8 and TRM / 2.0-9 Page TRM / 2.0-10 Page TRM / 2.0-11 Page TRM / 2.0-12 Pages TRM / 2.0-13 and TRM / 2.0-14 Page TRM / 2.0-15 3.0 APPLICABILITY Page TRM / 3.0-1 Page TRM / 3.0-2 Page TRM / 3.0-3 Page TRM / 3.0-4 08/11/2011 10/04/2002 08/31/1998 01/28/2005 06/25/2002 04/02/1999 03/27/2008 05/15/2008 01/07/2011 02/02/2010 11/15/2004 03/27/2008 11/15/2004 11/15/2005 04/14/2008 04/12/2007 03/15/2002 11/30/2005 10/31/2007 08/31/1998 03/22/2006 04/07/2009 03/27/2008 02/18/1999 02/18/1999 07/07/1999 01/20/2011 07/16/1999 10/31/2007 03/10/2011 10/31/2007 08/31/1998 06/30/2010 3.1 3.2 REACTIVITY CONTROL SYSTEMS Page TRM / 3.1-1 Pages TRM / 3.1-2 through TRM / 3.1-5 Page TRM / 3.1-6 Page TRM / 3.1-7 Page TRM / 3.1-8 Pages TRM / 3.1-9 and TRM / 3.1-9a Page TRM / 3.1-10 CORE OPERATING LIMITS REPORT Page TRM / 3.2-1 Pages TRM / 3.2-2 through TRM / 3.2-54 INSTRUMENTATION Pages TRM / 3.3-1 through TRM / 3.3-3 Page TRM / 3.3-4 and TRM / 3.3-5 Page TRM / 3.3-6 Page TRM / 3.3-7 Page 3.3-8 Pages TRM / 3.3-9 and TRM / 3.3-9a 3.3 SUSQUEHANNA - UNIT I TRM / LOES-1 EFFECTIVE DATE 11/24/2011 SUSQUEHANNA - UNIT 1 TRM / LOES-1 EFFECTIVE DATE 11/24/2011

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 69 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date 3.4 Page TRM / 3.3-10 Pages TRM / 3.3-11 and TRM / 3.3-11 a Page TRM / 3.3-12 Page TRM / 3.3-13 Page TRM / 3.3-14 Pages TRM / 3.3-15 and TRM / 3.3-16 Page TRM / 3.3-17 Page TRM / 3.3-18 Pages TRM / 3.3-19 through TRM / 3.3-21 Page TRM / 3.3-22 Page TRM / 3.3-22a Pages TRM / 3.3-22b through TRM / 3.3-22d Page TRM / 3.3-23 Pages TRM / 3.3-24 and TRM / 3.3-25 Page TRM / 3.3-26 Pages TRM / 3.3-27 and TRM / 3.3-28 REACTOR COOLANT SYSTEM Page TRM / 3.4-1 Pages 3.4-2 through 3.4-5 Pages TRM / 3.4-6 through TRM / 3.4-8 Page TRM / 3.4-9 Page TRM / 3.4-10 Page TRM / 3.4-11 Page TRM / 3.4-12 Page TRM / 3.4-13 Pages TRM / 3.4-14 and TRM / 3.4-15 EMERGENCY CORE COOLING AND RCIC Page TRM / 3.5-1 o Pages 3.5-2 and 3.5-3 Pages TRM / 3.5-4 and TRM / 3.5-5 Pages 3.5-6 and 3.5-7 CONTAINMENT Page 3.6-1 Pages TRM / 3.6-2 and TRM / 3.6-2a Page 3.6-3 Page TRM / 3.6-4 Page 3.6-5 Pages TRM / 3.6-6 through TRM / 3.6-8 10/31/2007 06/30/2010 03/30/2001 01/07/2011 12/14/1998 01/07/2011 06/14/2002 10/31/2007 10/22/2003 03/27/2008 11/15/2004 03/22/2006 12/03/2004 05/16/2003 10/22/2003 04/07/2009 03/31/2006 10/23/1998 04/01/2009 08/31/1998 10/31/2007 08/31/1998 03/27/2008 03/31/2006 06/10/2010 01/28/2005 08/31/1998 10/31/2007 08/31/1998 08/31/1998 08/11/2011 08/31/1998 01/07/2002 08/31/1998 12/31/2002 3.5 3.6 SUSQUEHANNA

- UNIT 1 TRM / LOES-2 EFFECTIVE DATE 11/24/2011 SUSQUEHANNA - UNIT 1 TRM / LOES-2 EFFECTIVE DATE 11/24/2011

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 69 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date 3.7 PLANT SYSTEMS Pages 3.7-1 through 3.7-3 Page TRM / 3.7-4 Pages TRM / 3.7-5 Pages TRM / 3.7-6 through TRM / 3.7-8 Pages TRM / 3.7-9 and TRM / 3.7-10 Page TRM / 3.7-11 Page TRM / 3.7-12 Page TRM / 3.7.13 Page TRM / 3.7-14 Pages TRM / 3.7-15 and TRM / 3.7-16 Page TRM / 3.7-17 Page TRM / 3.7-18 Page TRM / 3.7-19 Pages TRM / 3.7-20 through TRM / 3.7-22 Page TRM / 3.7-23 Page TRM / 3.7-24 Pages TRM / 3.7-25 and TRM 3.7-26 Page TRM 3.7-27 Page TRM / 3.7-28 Page TRM / 3.7-29 Page TRM / 3.7-30 Pages TRM / 3.7-31 and TRM / 3.7-32 Page TRM / 3.7-33 Page TRM / 3.7-34 Page TRM / 3.7-34a Page TRM / 3.7-35 Pages TRM / 3.7-36 and TRM / 3.7-37 Pages 3.7-38 and 3.7-39 Page TRM / 3.7-40 Page TRM / 3.7-41 Page TRM / 3.7-41a Page TRM / 3.7-42 Page TRM / 3.7-43 Pages TRM / 3.7-44 through TRM / 3.7-46 Page TRM / 3.7-47 Page TRM / 3.7-48 Page TRM / 3.7-49 Page TRM / 3.7-50 Page TRM / 3.7-51 Page TRM / 3.7-52 Page TRM / 3.7-53 Page TRM / 3.7-54 Pages TRM / 3.7-55 through TRM / 3.7-57 08/31/1998 03/31/2006 04/07/2009 08/02/1999 04/07/2009 12/29/1999 08/02/1999 04/07/2009 08/09/2005 08/02/1999 04/07/2009 08/02/1999 04/07/2009 08/02/1999 04/07/2009 03/31/2006 08/02/1999 11/24/2011 11/29/2006 08/09/2005 01/13/2010 11/16/2001 09/16/2010 11/16/2001 10/05/2002 03/31/2006 02/01/1999 08/31/1998 03/31/2006 02/14/2005 06/20/2008 09/04/2008 08/31/1998 10/05/2006 06/07/2007 10/05/2006 06/07/2007 03/09/2001 08/16/2006 12/03/2004 04/15/2003 07/29/1999 04/01/2009 SUSQUEHANNA

- UNIT 1 TRM/LOES-3 EFFECTIVE DATE 11/24/2011 SUSQUEHANNA - UNIT 1 TRM / LOES-3 EFFECTIVE DATE 11/24/2011

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 69 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date 3.8 ELECTRICAL POWER Page TRM / 3.8-1 Page TRM / 3.8-2 Pages TRM / 3.8-3 and TRM /3.8-4 Pages TRM / 3.8-5 and TRM / 3.8-6 Page TRM / 3.8-7 Pages TRM / 3.8-8 through TRM / 3.8-10 Page TRM / 3.8-11 Page TRM / 3.8-12 Page TRM / 3.8-13 Page TRM / 3.8-14 Pages TRM / 3.8-15 through TRM / 3.8-17 Page 3.8-18 Page TRM / 3.8-19 Page 3.8-20 Pages TRM / 3.8-21 through TRM / 3.8-23 Pages 3.8-24 and 3.8-25 Page TRM / 3.8-26 Page TRM / 3.8-27 Pages TRM / 3.8-28 and TRM / 3.8-29 3.9 REFUELING OPERATIONS Pages 3.9-1 through 3.9-3 04/02/2002 01/28/2005 03/25/2010 04/02/2002 10/31/2007 12/03/2004 09/03/2004 12/03/2004 03/25/2010 08/31/1998 04/02/2002 08/31/1998 04/02/2002 08/31/1998 06/06/1999 08/31/1998 05/28/2009 11/29/2006 05/28/2009 08/31/1998 03/31/2006 08/31/1998 08/31/1998 08/01/2006 03/22/2006 06/10/2010 03/31/2006 08/31/1998 03/31/2006 08/31/1998 03/31/2006 08/31/1998 12/03/2004 08/31/1998 04/12/2007 3.10 3.11 MISCELLANEOUS Page TRM / 3.10-1 Pages 3.10-2 and 3.10-3 Pages 3.10-2 and 3.10-3 Page TRM / 3.10-4 Pages TRM / 3.10-5 and TRM / 3.10-6 Page TRM / 3.10-7 RADIOACTIVE EFFLUENTS Page TRM / 3.11-1 Pages 3.11-2 and 3.11-3 Page TRM / 3.11-4 Page 3.11-5 Page TRM / 3.11-6 Pages TRM / 3.11-7 through TRM / 3.11-9 Page TRM / 3.11-10 Pages 3.11-11 and 3.11-12 Page TRM / 3.11-13 SUSQUEHANNA - UNIT 1 TRM / LOES-4 EFFECTIVE DATE 11/24/2011

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 69 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date Page TRM / 3.11-14 Pages 3.11-15 and 3.11-16 Page TRM / 3.11-17 Page 3.11-18 Page TRM / 3.11-19 Pages TRM / 3.11-20 and TRM /3.11-21 Page TRM / 3.11-22 Page TRM / 3.11-23 Page TRM / 3.11-24 Page TRM / 3.11-25 Pages TRM / 3.11-26 and TRM / 3.11-27 Page TRM / 3.11-28 Page TRM / 3.11-29 Pages TRM / 3.11.30 through TRM / 3.11.32 Page TRM / 3.11-33 Page 3.11-34 Page TRM / 3.11-35 Pages TRM / 3.11-36 through TRM / 3.11-39 Pages 3.11-40 through 3.11-43 Page TRM / 3.11-44 Page TRM / 3.11-45 Page 3.11-46 Page TRM / 3.11-47 LOADS CONTROL PROGRAM Pages TRM / 3.12-1 through TRM / 3.12-3 Page TRM / 3.12-4 Page TRM / 3.12-5 ADMINISTRATIVE CONTROLS Pages TRM / 4.0-1 through TRM / 4.0-3 Page TRM / 4.0-4 Pages TRM / 4.0-5 through TRM / 4.0-8 12/03/2004 09/01/1998 03/31/2006 08/31/1998 08/15/2005 03/31/2006 04/02/2002 11/14/2006 05/13/2005 04/12/2007 01/21/2004 09/08/2009 12/03/2004 01/21/2004 03/31/2006 08/31/1998 03/31/2006 11/30/2005 08/31/1998 08/01/2006 03/31/2006 08/31/1998 03/31/2006 02/05/1999 03/14/2008 02/05/1999 08/31/1998 12/11/2008 08/31/1998 3.12 4.0 SUSQUEHANNA

- UNIT I TRM/LOES-5 EFFECTIVE DATE 11/24/2011 SUSQUEHANNA - UNIT 1 TRIM / LOES-5 EFFECTIVE DATE 11/24/2011

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 69 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date B 3.0 APPLICABILITY BASES Pages TRM / B 3.0-1 through TRM / B 3.0-3 Page TRM / B 3.0-4 Page TRM / B 3.0-5 Page TRM / B 3.0-6 Page TRM / B 3.0-7 Pages TRM / B 3.0-8 through TRM / B 3.0-10 Pages TRM / B 3.0-11 and TRM / B 3.0-12 Pages TRM / B 3.0-13 and TRM / B 3.0-14 Page TRM / B 3.0-15 B 3.1 REACTIVITY CONTROL SYSTEMS BASES Page TRM / B 3.1-1 Pages TRM / B 3.1-2 and TRM / B 3.1-3 Page B 3.1-4 Page TRM / B 3.1-5 Pages TRM / B 3.1-6 and TRM / B 3.1-7 Page TRM / B 3.1-8 B 3.2 CORE OPERATING LIMITS BASES Page B 3.2-1 08/31/1998 01110/2007 04/14/2008 08/31/1998 04/12/2007 08/31/1998 03/15/2002 11/30/2005 03/15/2002 07/13/1999 10/31/2007 08/31/1998 11/15/2005 03/22/2006 02/18/1999 08/31/1998 04/07/2000 03/10/2011 10/31/2007 12/11/2008 10/31/2007 06/30/2010 05/30/2006 06/30/2010 10/30/2007 06/30/2010 10/31/2007 01/07/2011 06/25/2002 10/31/2007 10/31/2007 10/22/2003 03/22/2006 03/22/2006 03/27/2008 B 3.3 INSTRUMENTATION BASES Page TRM / B 3.3-1 Page TRM / B 3.3-2 Page TRM / B 3.3-2a Page TRM / B 3.3-3 Page TRM / B 3.3-3a Page TRM / B 3.3-4 Page TRM / B 3.3-5 Page TRM / B 3.3-6 Page TRM / B 3.3-7 Page TRM / B. 3.3-8 Page TRM / B 3.3-9 Pages TRM / B 3.3-10 through TRM / B 3.3-13 Page TRM / B 3.3-14 Page TRM / B 3.3-14a Page TRM / B 3.3-14b Pages TRM / B 3.3-15 and TRM / B 3.3-16 Page TRM / B 3.3-17 Pages TRM / B 3.3-17a through TRM / B 3.3-17c Page TRM / B 3.3-17d SUSQUEHANNA - UNIT 1 TRM / LOES-6 EFFECTIVE DATE 11/24/2011

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 69 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date B 3.4 B 3.5 B 3.6 Pages TRM / B 3.3-17e and TRM / B 3.3-17f Pages TRM / B 3.3-18 and TRM / B 3.3-19 Page TRM / B 3.3-20 Page TRM / B 3.3-21 Pages TRM / B 3.3-22 and TRM / B 3.3-23 REACTOR COOLANT SYSTEM BASES Page B 3.4-1 Pages TRM / B 3.4-2 and TRM / B 3.4-3 Pages TRM / B 3.4-4 and TRM / B 3.4-4p Page TRM / B 3.4-5 Page B 3.4-6 Pages TRM / B 3.4-7 and TRM / B 3.4-8 ECCS AND RCIC BASES Pages B 3.5-1 and B 3.5-2 Pages TRM / B 3.5-3 through TRM / B 3.5-5 CONTAINMENT BASES Page TRM / B 3.6-1 Page TRM / B 3.6-2 Page B 3.6-3 Page TRM / B 3.6-4 Page TRM / B 3.6-5 Page TRM / B 3.6-6 Pages B.3.6-7 through TRM / B 3.6-11 PLANT SYSTEMS BASES Pages B 3.7-1 and B 3.7-2 Page TRM / B 3.7-3 Page TRM / B 3.7-3a Page TRM / B 3.7-4 Page TRM / B 3.7-5 Page TRM / B 3.7-6 Pages TRM / B 3.7-7 and TRM / B 3.7-7a Page TRM / B 3.7-8 Page TRM / B 3.7-9 Page TRM / B 3.7-10 Page TRM / B 3.7-1Oa Page TRM / B 3.7-11 Page TRM / B 3.7-1 la Pages TRM / B 3.7-12 through TRM / B 3.7-14 Page TRM / B 3.7-14a 03/22/2006 08/03/2010 10/22/2003 05/16/2003 04/07/2009 08/31/1998 04/01/2009 10/31/2007 10/15/1999 08/31/1998 06/10/2010 08/31/1998 10/31/2007 07/26/2001 02/01/1999 08/31/1998 03/27/2008 04/04/2007 12/03/2004 12/31/2002 08/31/1998 06/10/2010 12/27/2007 03/31/2006 08/02/1999 03/31/2006 08/02/1999 08/02/1999 03/31/2006 08/02/1999 03/31/2006 08/02/1999 03/31/2006 08/02/1999 08/02/1999 B 3.7 SUSQUEHANNA - UNIT 1 TRM / LOES-7 EFFECTIVE DATE 11/24/2011

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 69 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date Page TRM / B 3.7-14b Pages TRM / B 3.7-15 and TRM / B 3.7-16 Pages B 3.7-17 through B 3.7-20 Page TRM / B 3.7-21 Page TRM / B 3.7-21a Page TRM / B 3.7-22 and TRM / B 3.7-23 Pages TRM / B 3.7-24 through TRM / B 3.7-28 Pages TRM / B 3.7-29 and TRM / B 3.7-30 Pages TRM / B 3.7-30a and TRM / B 3.7-30b Page TRM / B 3.7-31 Page TRM / B 3.7-32 Page TRM / B 3.7-33 Page TRM / B 3.7-34 Page TRM / B 3.7-35 Pages TRM / B 3.7-36 through TRM / B 3.7-39 Page TRM / B 3.7-40 ELECTRICAL POWER BASES Page TRM / B 3.8-1 Pages TRM / B 3.8-2 and TRM / B 3.8-2 Page TRM / B 3.8-2a Page TRM / B 3.8-3 Page TRM / B 3.8-3a Page TRM / B 3.8-4 Page TRM / B 3.8-4a Page TRM / B 3.8-5 Pages TRM / B 3.8-6 through TRM / B 3.8-16 Page TRM / B 3.8-17 Pages TRM / B 3.8-18 through TRM / B 3.8-20 Pages TRM / B 3.8-21 through TRM / B 3.8-24 REFUELING OPERATIONS BASES Pages B 3.9-1 through B 3.9-7 B 3.8 B.3.9 11/24/2011 02/01/1999 08/31/1998 02/14/2005 06/20/2008 01/30/2008 10/05/2006 06/07/2007 10/05/2006 12/03/2004 03/09/2001 04/15/2003 12/03/2004 07/05/2000 04/01/2009 04/08/2010 04/02/2002 01/28/2005 03/01/2010 04/02/2002 04/02/2002 08/10/2004 04/02/2002 08/31/1998 04/02/2002 01/28/2005 11/29/2006 05/28/2009 08/31/1998 08/31/1998 03/22/2006 08/23/1999 B 3.10 MISCELLANEOUS BASES Page B 3.10-1 Pages TRM / B 3.10-2 and TRM / B 3.10-3 Pages TRM / B 3.10-4 and TRM / B 3.10-5 SUSQUEHANNA

- UNIT 1 TRM / LOES-8 EFFECTIVE DATE 11/24/2011 SUSQUEHANNA - UNIT 1 TRM / LOES-8 EFFECTIVE DATE 11/24/2011

SUSQUEHANNA STEAM ELECTRIC STATION PPL Rev. 69 LIST OF EFFECTIVE SECTIONS (TECHNICAL REQUIREMENTS MANUAL)

Section Title Effective Date B 3.11 RADIOACTIVE EFFLUENTS BASES Pages B 3.11-1 through B 3.11-9 Page TRM / B 3.11-10 Pages TRM/B 3.11-11 and TRM/B 3.11-11a Pages TRM/B 3.11-12 and TRM/B 3.11-13 Page TRM / B 3.11-14 Page TRM / B 3.11-15 Pages B 3.11-16 through B 3.11-19 Page TRM / B 3.11-20 Page TRM / B 3.11-20a Page TRM / B 3.11-21 Pages TRM / B 3.11-22 and TRM / B 3.11.23 Page TRM / B 3.11.23a Pages TRM / B 3.11-24 and TRM / B 3.11-25 Pages B 3.11-26 and B 3.11-27 Pages TRM / B 3.11-28 and TRM / B 3.11-29 Page TRM / B 3.11-30 Pages B 3.11-31 and B 3.11-32 Page TRM / B 3.11-33 Pages TRM / B 3.11-34 and TRM / B 3.11-35 Page TRM / B 3.11-36 B.3.12 LOADS CONTROL PROGRAM BASES Page TRM / B 3.12-1 Page TRM / B 3.12-2 Page TRM / B 3.12-3 08/30/1998 02/01/1999 04/07/2000 02/01/1999 12/03/2004 02/01/1999 08/30/1998 04/02/2002 04/02/2002 05/13/2005 11/14/2006 05/13/2005 01/21/2004 08/30/1998 11/30/2005 06/30/2010 08/30/1998 06/30/2010 08/30/1998 02/12/1999 09/19/2007 11/29/2010 02/05/1999 TRMI text LOES 11/28/11 SUSQUEHANNA

- UNIT I TRM / LOES-9 EFFECTIVE DATE 11/24/2011 SUSQUEHANNA - UNIT 1 TRM / LOES-9 EFFECTIVE DATE 11/24/2011

Fire Detection Instrumentation 3.7.3.8 PPL Rev. 9 3.7.3 Fire Protection 3.7.3.8 Fire Detection Instrumentation TRO 3.7.3.8 APPLICABILITY:

The fire detection instrumentation for each fire detection zone shown in Table 3.7.3.8-1 shall be OPERABLE.

Whenever equipment protected by the fire detection instrument is required to be OPERABLE.

ACTIONS NOTE

1. Separate condition entry is allowed for each instr CONDITION REQUIRED ACTION COMPLETION TIME A. The number of OPERABLE A.

Establish an hourly fire 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> fire detection instruments watch patrol less than the Minimum Instruments Operable AND requirement of Table 3.7.3.8-1 A.2.1 Inspect the accessible Once per hour zone(s) with inoperable instrument(s)

OR A.2.2 Inspect the affected area Once per hour surrounding any inaccessible zones SUSQUEHANNA - UNIT 1 TRM / 3.7-26 EFFECTIVE DATE 08/02/1999

Fire Detection Instrumentation PPL Rev. 9 3.7.3.8 TECHNICAL REQUIREMENT SURVEILLANCE SURVEILLANCE FREQUENCY NOTE When a detector is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and required Actions may be delayed for up to 15 minutes to allow for the individual detector trip to clear.

TRS 3.7.3.8.1 Perform CHANNEL FUNCTIONAL TEST on 12 months accessible fire detection instruments.

TRS 3.7.3.8.2 Verify that the supervised circuits supervision 12 months associated with the detector alarms of each of the fire detection instruments listed in Table 3.7.3.8-1 are OPERABLE.

TRS 3.7.3.8.3 Perform CHANNEL FUNCTIONAL TEST on Prior to startup from each inaccessible fire detection instruments.

COLD SHUTDOWN exceeding 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> unless performed in the previous 12 months TRS 3.7.3.8.4 Perform CHANNEL FUNCTIONAL TEST on 12 months heat detectors fixed-temperature, non-restorable line type fire detection instrument.

SUSQUEHANNA - UNIT 1 TRM / 3.7-27 EFFECTIVE DATE 11/24/2011

Fire Detection Instrumentation 3.7.3.8 PPL Rev. 9 TABLE 3.7.3.8-1 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION:

INSTRUMENT OPERABLE FIRE HEAT IONIZATIN PHTOEECTRIC ZONE ROOM OR AREA ELV.

OAL[

TOTAL TOAN VIN OA MIN.

a.

- Con~trol Buidin 0-21A Common Equipment Room Elevator Lobby 656'-0" NA NA 1

1 NA NA Chem Lab 0F135 High Temp. Alarm 687'-10" 2

1 NA NA NA NA Chem Lab DS-021 687'-10" 2

1 NA NA NA NA Chem Lab 0F138 High Temp. Alarm 687-1 0" 2

1 NA NA NA NA Chem Lab DS-022 687-10" 2

1 NA NA NA NA 0-22A Chem Lab 0F141 High Temp. Alarm 687'-10" 2

1 NA NA NA NA Chem Lab DS-023 687T-10" 2

1 NA NA NA NA Chem Lab 0F144 High Temp. Alarm 687T-10" 2

1 NA NA NA NA Chem Lab DS-024 687'-10" 2

1 NA NA NA NA 0-22A Above Ceiling/Filter Area 687'-8" NA NA 10 5

NA NA 0-22A Elevator Lobby 676'-0" NA NA 1

1 NA NA 0-23 Egress Corridor to South Stairwell 686'-6" NA NA 1

1 NA NA 0-24B Corridor 698'-0" NA NA 3

2 NA NA 0-24B Corridor Elevator Lobby 698'-0" NA NA 1

1 NA NA 0-24C UPS Panel Room U-1 698'-U' 4

2 2

1 NA NA U-1 Lower Relay Room 1 U704 697-0" 11 6

6 3

NA NA PGCC Halon Panel Division II.

1 U705 697'-0" 11 6

6 3

NA NA 0-24D 1 U706 697'-0" 11 6

6 3

NA NA 1 U731 697'-0" 10 5

6 3

NA NA 1 U732 697'-0" 11 6

6 3

NA NA 0-24D U-1 Lower Relay Room 698'-9' 4

2 4

2 NA NA 0-24E Computer Room 698'-U' NA NA 6

3 NA NA 0-24E Computer Room (Above Ceiling) 698'-0" 12 6

4 2

NA NA Computer Room 1 U720 697'-0" NA NA 4

2 NA NA PGCC Underfloor 1 U722 697'-0" NA NA 4

2 NA NA 0-24E 1 U724 697'-0" NA NA 4

2 NA NA 1 U726 697"-0" NA NA 4

2 NA NA SUSQUEHANNA - UNIT 1 TRM / 3.7-28 EFFECTIVE DATE 11/29/2006

Fire Detection Instrumentation 3.7.3.8 PPL Rev. 9 TABLE 3.7.3.8-1 FIRE DETECTION INSTRUMENTATION I NSTRU MENT LOCAT.I.ON_

INSTRUMENT OPERABL FIRE 1HEA~T

]

IONIZATION J H r

CRIC ZONE ROOM OR AREA

]

ELEV.

TOTAL MKIN TOTAL MIN. JTOTAL [MIN.

Computer Room 2U721 697'-0" NA NA 4

2 NA NA PGCC Underfloor 2U723 697-0" NA NA 4

2 NA NA 0-24E 2U725 697'-0" NA NA 4

2 NA NA 2U727 697'-0" NA NA 4

2 NA NA 0-24F Computer Maintenance Rm and Office 698'-0" NA NA 2

1 NA NA 0-24J South Cable Chase 698'-0" 1

1 NA NA NA NA 0-24L Center Cable Chase 698'-0" 1

1 NA NA NA NA 0-24M North Cable Chase 698'-0" 1

1 NA NA NA NA 0-25A U-2 Lower Cable Spreading Room 714!-0" 20 10 6

3 NA NA 0-25B South Cable Chase 714'-0" 1

1 NA NA NA NA 0-25C Center Cable Chase 714'-0" 1

1 NA NA NA NA 0-25D North Cable Chase 714'-0" 1

1 NA NA NA NA 0-25E U-1 Lower Cable Spreading Room 714'-0" 26 13 5

3 NA NA 0-25E U-1 Lower Cable Spreading Room Elevator 714'-0" NA NA 1

1 NA NA Lobby 0-26A Copy Room 729'-1" NA NA 1

1 NA NA 0-26B South Cable Chase 729'-1" NA NA 1

1 NA NA 0-26C Center Cable Chase 729'-1" NA NA 1

1 NA NA 0-26D North Cable Chase 729'-1" NA NA 1

1 NA NA 0-26E Locker Room 729'-1" NA NA 1

1 NA NA 0-26F Vestibule Elevator Lobby 729'-1" NA NA 1

1 NA NA 0-26F Vestibule (Under Floor) 728'-1" NA NA 1

1 NA NA 0-26G Shift Office 729'-1" NA NA 1

1 NA NA 0-26G Shift Office (Under Floor) 728'-1" NA NA 2

1 NA NA 0-26H Control Room (Under Floor Unit 1) 728'-1" NA NA 15 8

NA NA 0-26H Control Room (Under Floor Unit 2) 728'-1" NA NA 12 6

NA NA 0-26H Control Room 729'-1" NA NA 10 5

NA NA 0-26H Control Room (Above Ceiling) 729'-1" NA NA 9

5 NA NA 0-261 Operational Support Center 729'-1" NA NA 1

1 NA NA SUSQUEHANNA - UNIT 1 TRM / 3.7-29 EFFECTIVE DATE 08/09/2005

Fire Detection Instrumentation 3.7.3.8 PPL Rev. 9 TABLE 3.7.3.8-1 FIRE DETECTION INSTRUMENTATION INSTRUMENT LO6CATION

-NRUM ENT OPERABLE FIRE HETIONIZATION PHOTO E ECTRiC~

ZONE JROOM OR AREA ELEV.

TOTAL.

-111N.4 TOTAL M~IN. TOTAL M~IN.

0-261 Operational Support Center (Under Floor) 728'-1" NA NA 2

1 NA NA 0-26J Vestibule (Under Floor) 728'-1" NA NA 1

1 NA NA 0-26J Vestibule 729'-1" NA NA 1

1 NA NA 0-26K Technical Support Center 741'-1" NA NA NA NA 10 5

0-26K Technical Support Center Elevator Lobby 741'-1" NA NA 1

1 NA NA 0-26K Technical Support Center (Above Ceiling) 741'-1" NA NA 5

3 NA NA 0-26L Conference Room 741'-1" NA NA NA NA 6

3 0-26L Conference Room (Above Ceiling) 741'-1" NA NA 2

1 NA NA 0-26M U-1 TSC Soffit 729'-1" NA NA 2

1 NA NA 0-26M U-1 TSC Soffit 741'-1" NA NA 2

1 NA NA 0-26N U-1 Control Room Soffit 741'-1" NA NA 2

1 NA NA 0-26P U-2 Control Room Soffit 741'-1" NA NA 2

1 NA NA 0-26R U-2 TSC Soffit 729'-1" NA NA 2

1 NA NA 0-26R U-2 TSC Soffit 741'-1" NA NA 2

1 NA NA 0-26S South Cable Chase 741'-1" 1

1 NA NA NA NA 0-26T Center Cable Chase 741'-1" 1

1 NA NA NA NA 0-26V North Cable Chase 741-1" 1

1 NA NA NA NA 0-27B U-2 Upper Cable Spreading Room 753'-0" 24 12 5

3 NA NA 0-27C U-1 Upper Cable Spreading Room 753'-0" 23 12 7

4 NA NA 0-27C U-1 Upper Cable Spreading Room Elevator 753'-0' NA NA 1

1 NA NA Lobby 0-27D Electrician's Office 754'-0" 2

1 1

1 NA NA 0-27E U-1 Upper Relay Room 754-0" 4

2 2

1 NA NA SUSQUEHANNA - UNIT 1 TRM / 3.7-30 EFFECTIVE DATE 01/13/2010

Fire Detection Instrumentation 3.7.3.8 PPL Rev. 9 TABLE 3.7.3.8-1 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCAT,ION INSTRUMENT OPERABLE FIRE HEAT IONIZATIO PHT LECTRIC ZOEROOM~

OR AREA ELEV.

TOTA IVN TOTAL MIN.

TOTAL

MIN, U-i Upper Relay Room 1 U700 753'-0" 11 6

6 3

NA NA PGCC Halon Panel Division 1 U701 753'-0" 11 6

6 3

NA NA 0-27E 1 U702 753'-0" 11 6

6 3

NA NA 1 U703 753'-0" 11 6

6 3

NA NA 1 U730 753'-0" 11 6

6 3

NA NA 0-27F South Cable Chase 754'-0" 1

1 NA NA NA NA 0-27G Center Cable Chase 7541-0" 1

1 NA NA NA NA 0-27H North Cable Chase 754'-0" 1

1 NA NA NA NA 0-28A-I Equipment Room 771'-0" NA NA 1

1 NA NA 0-28A-11 Equipment Room 771'-0" NA NA 3

2 NA NA 0-28B-I Equipment Room 771'-0" NA NA 1

1 NA NA 0-28B-11 Equipment Room 771'-0" NA NA 2

1 NA NA 0-28B-11 Equipment Room Elevator Lobby 771'-0" NA NA 1

1 NA NA 0-28C Battery Room 771'-0" NA NA 1

1 NA NA 0-28D Battery Room 771'-0" NA NA 1

1 NA NA 0-28E Battery Room 771 '-0" NA NA 1

1 NA NA 0-28F Battery Room 771'-0" NA NA 1

1 NA NA 0-28G Battery Room 771'-0" NA NA 1

1 NA NA 0-28H Repair Shop 771'-0" NA NA 2

1 NA NA 0-281 Battery Room 771'-0" NA NA 1

1 NA NA 0-28J Battery Room 771'-0" NA NA 1

1 NA NA 0-28K Battery Room 771 '-0" NA NA 1

1 NA NA 0-28L Battery Room 771'-0" NA NA 1

1 NA NA 0-28M Battery Room 771'-0" NA NA 1

1 NA NA 0-28N Battery Room 771'-0" NA NA 1

1 NA NA 0-28P South Cable Chase 771'-0" 1

1 NA NA NA NA 0-28Q Center Cable Chase 771'-0" 1

1 NA NA NA NA 0-28R North Cable Chase 771'0" 1

1 NA NA NA NA 0-28T Battery Room 771'-0" NA NA 1

1 NA NA 0-29A Elevator Vestibule 783'-0" NA NA 1

1 NA NA 0-29B H&V Equipment Room 783'-0" NA NA 10 5

NA NA SUSQUEHANNA - UNIT 1 TRM / 3.7-31 EFFECTIVE DATE 11/16/2001

Fire Detection Instrumentation 3.7.3.8 PPL Rev. 9 TABLE 3.7.3.8-1 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION INSTRUMENT OPIERABLE FIRE ROMOHAE EY O

AT IN IONIZATION PHOTO ELECTRIC ZOEROIRAE LV OA]MN TOTAL MIN.

TOTAL MIJN.

0-30A HVAC Equipment Room 806'-0" NA NA 19 10 NA NA 0-30A Freight Elevator Lobby 806'-0" NA NA 1

1 NA NA 0-30A CREOASS 0F125A High Temp. Alarm 806'-0' 7

4 NA NA NA NA 0-30A CREOASS DS-091 806'-0" 7

4 NA NA NA NA 0-30A CREOASS 0F125B High Temp. Alarm 806'-0" 7

4 NA NA NA NA 0-30A CREOASS DS-092 806'-0" 7

4 NA NA NA NA O-30A SGTS - OF 69A High Temp. Alarm 806'-0" 1

1 NA NA NA NA 0-30A SGTS - DS-093 806'-0" 1

1 NA NA NA NA 0-30A SGTS - OF1 69B High Temp. Alarm 806'-0" 1

1 NA NA NA NA 0-30A SGTS - DS-094 806'-0" 1

1 NA NA NA NA b

React~orBuilding~~'-

0-6G Surge Tank Vault 779'-4" NA NA 2

1 NA NA 0-8A Refueling Floor 818'-1" NA NA NA NA 60 30 0-8A Refueling Floor Elevators 818'-1" NA NA 2

1 NA NA 1-1A Core Spray Pump Room 645-0" NA NA 7

4 NA NA 1-1B Core Spray Pump Room 645'-0" NA NA 5

3 NA NA 1 -1,B Elevator Lobby 645-0" NA NA 1

1 NA NA 1-1c HPCl Pump Room 645'-0" 2

1 NA NA 7

4 1-1D RClC Pump Room 645'-0" 2

1 NA NA 5

3 1-1E RHR Pump Room 645-0" NA NA NA NA 13 7

1-1F RHR Pump Room 645-0" NA NA NA NA 15 8

1-IG Sump Room 645'-0" NA NA 2

1 NA NA 1-11 NW Stairway and Elevator Vestibule 676'-0" NA NA 1

1 NA NA 1-2A Access Area 670'-0" NA NA 7

4 NA NA 1-2B Access Area 670'-0" NA NA 9

5 NA NA 1-2B Access Area Elevator Lobby 670'-0" NA NA 1

1 NA NA 1-2D Remote Shutdown Panel Room 670'-0" NA NA 2

1 NA NA 1-3A Access Area 683'-0" NA NA 9

5 NA NA 1-36-N Equipment Removal Area - North 683'-0" NA NA 8

4 NA NA 1-3B-N Equipment Removal Area Elevator Lobby 683'-0" NA NA 1

1 NA NA SUSQUEHANNA - UNIT 1 TRM / 3.7-32 EFFECTIVE DATE 11/16/2001

Fire Detection Instrumentation 3.7.3.8 PPL Rev.9 TABLE 3.7.3.8-1 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION INSTRUMENT OPERABLE FIR HET IONIZOAltTION PHOTO ELECTRIC ZONE ROOM OR AREAj ELEV.

TOTAL M1N jMN.

TOTAL M

!IN.

TMN 1-3B-S Equipment Removal Area - South 683-0" NA NA 1

1 NA NA 1-3B-W Equipment Removal Area - Wraparound 683'-0" NA NA 2

1 NA NA 1-3C-N Equipment Access Area - North 683'-0" NA NA NA NA 4

2 1-3C-S Equipment Access Area - South 683'-0" NA NA NA NA 4

2 1-3C-W Equipment Access Area - Wraparound 683'-0" NA NA NA NA 5

3 1-4A-N Containment Access Area - North 719'-0" NA NA 11 6

4 2

1-4A-N Containment Access Area Elevator Lobby 719'-0" NA NA 1

1 NA NA 1-4A-S Containment Access Area - South 719'-0" NA NA 10 5

NA NA 1-4A-W Containment Access Area -Wraparound 719'-0" NA NA 6

3 NA NA 1-4B Pipe Penetration Room 719'-l" NA NA 1

1 NA NA 1-4C Switchgear Room 719'-1" NA NA 2

1 NA NA 1-4D Switchgear Room 719'-1" NA NA 2

1 NA NA 1-4G Main Steam Pipeway 719'-1" NA NA NA NA 4

2 1-4G Exhaust Fan Room (Note: these detectors 799'-1" NA NA NA NA 2

1 also cover el. 749'-1")

1-5A-N General Access Area - North 749'-1" NA NA 5

3 1

1 1-5A-N General Access Area Elevator Lobby 749'-1" NA NA 1

1 NA NA 1-5A-S SLC / Chiller Area - South 749'-1" NA NA 15 8

7 4

1-5A-W Access Corridor - Wraparound 749'-1" NA NA 7

4 NA NA 1-5B Valve Access Area 761'-10" NA NA NA NA 2

1 1-51 RWCU Pumps & Heat Exchangers 749'-1" NA NA NA NA 10 5

1-5E Penetration Room 749'-1" NA NA NA NA 2

1 1-5F Load Center Room 749'-1" NA NA 2

1 NA NA 1-5G Load Center Room 749'-1" NA NA 2

1 NA NA 1-5H Instrument Repair Shop/Sample Station 749'-1" NA NA 1

1 NA NA 1-6A Access Area 779'-1" NA NA 9

5 NA NA 1-6A Access Area Elevator Lobby 779'-1" NA NA 1

1 NA NA 1-61 Load Center Room 779'-1" NA NA 4

2 NA NA 1-6C Electrical Equipment Room 779'-1" NA NA 2

1 NA NA 1--6D H&V Equipment Room 779'-1" NA NA 12 6

NA NA SUSQUEHANNA - UNIT 1 TRM / 3.7-33 EFFECTIVE DATE 09/16/2010

Fire Detection Instrumentation PPL Rev. 9 3.7.3.8 TABLE 3.7.3.8-1 FIRE DETECTION INSTRUMENTATION I NSTRUM ENT LOCATION{

INSTRUMENT OPERABLE FIR HEAT

] IiAION PHOTO ELECTRIC ZONE JROOMv OR AREA ELEV.

TOAW~I~TTL IIN.

J OTAL MvIN.

1-6E Recirculation Fans Area 779'-1" NA NA 2

1 NA NA 1-61 Fuel Pooling Holding Pump Room 779'-1" NA NA NA NA 2

1 1-7A H&V Fan & Filter Rooms 799'-1" NA NA 15 8

NA NA 1-7A HVAC Filter 1F257A High Temp. Alarm 799'-1" 7

4 NA NA NA NA 1-7A HVAC Filter 1 F257A DS-1 81 799'-1" 7

4 NA NA NA NA 1-7A HVAC Filter 1F257B High Temp. Alarm 799'-1" 7

4 NA NA NA NA 1-7A HVAC Filter 1 F257B DS-182 799'-1" 7

4 NA NA NA NA 1-7A HVAC Filter 1F217A High Temp. Alarm 799'-1" 5

3 NA NA NA NA 1-7A HVAC Filter 1 F217A DS-1 83 799'-1" 5

3 NA NA NA NA 1-7A HVAC Filter 1F217B High Temp. Alarm 799'-1" 5

3 NA NA NA NA 1-7A HVAC Filter 1 F217B DS-184 799'-1" 5

3 NA NA NA NA

c.

ESWPu R

o useo6 5 -

NNA3N 0-51 Pump Room 685'-6" NA NA 6

3 NA NA 0-52 Pump Room 685'-6' NA NA 6

3 NA NA

d.

Diesel Generator Building

____ T

-:INFRA-4R ELECTRI.C 0-41A Diesel Generator "A" Bay 660'-0" 2,

677'-0" 22 11 2

1 15 8

710'- 9" N/A N/A N/A N/A 8

4 0-41B Diesel Generator "B" Bay 660'-0" &

677'-0" 23 12 2

1 15 8

710'-9" N/A N/A N/A N/A 9

5 0-41 C Diesel Generator "C" Bay 660'-0"&

22 11 2

1 15 8

677-9' 710'-9 N/A N/A N/A N/A 8

4 0-41 D Diesel Generator "D" Bay 660'-0" &

22 11 2

1 15 8

677'-0" 710'9" N/A N/A N/A N/A 8

4 0.-~

DieselGienerator E B bilding'

-~A HEA Tm fINFRA-REb:

fibNiaidki 0-41 E Diesel Generator Rooms 656'-6" &

1 1

NA NA 21 11 675'-6" &

NA NA 6

3 3

2 708'-0" NA NA 4

2 NA NA SUSQUEHANNA - UNIT 1 TRM / 3.7-34 EFFECTIVE DATE 11/16/2001

Fire Detection Instrumentation 3.7.3.8 PPL Rev. 9 TABLE 3.7.3.8-1 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION[

INSTRUMENT OPERABLE

.vZFIRE HEAT____

IONIZATION PHOTO ELECTRIC sPHOTO

f.

Outside Area HEAT IOfVIZA TIO'N 7ELEECTRIC 0-00 Startup Transformer (0X103)

DS-014 NA 10 5

NA NA NA NA 0-00 Startup Transformer (0X104)

DS-015 NA_

12 6

NA NA NA NA 0-00 ESS Transformer - DS-01 6 0X201 NA 6

3 NA NA NA NA OX 213 NA 6

3 NA NA NA NA 0-00 ESS Transformer - DS-01 7 0X203 NA 6

3 NA NA NA NA 0X211 NA 6

3 NA NA NA NA SUSQUEHANNA - UNIT 1 TRM / 3.7-34a EFFECTIVE DATE 10/05/2002

Fire Detection Instrumentation PPL Rev. 2 B 3.7.3.8 B 3.7.3.8 Fire Detection Instrumentation BASES TRO OPERABILITY of the fire detection instrumentation ensures that adequate warning capability is available for the prompt detection of fires. This capability is required in order to detect and locate fires in their early stages.

Prompt detection of fires will reduce the potential for damage to safety-related equipment and is an integral element in the overall facility fire protection program.

The basis for the detection instrumentation included within the scope of this TRO includes both Safety Related and Safe Shutdown System protection.

Fire Detection Instrumentation associated with building elevators are listed as separate line items in Table 3.7.3.8-1 due to their specific function and their layout being in a vertical string.

ACTIONS The Actions are defined to ensure proper corrective measures and compensatory actions are taken in response to the inoperable systems or components.

In the event that a portion of the fire detection instrumentation is inoperable, establishing hourly firewatch patrols in the affected areas is required to provide detection capability until the inoperable instrumentation is restored to OPERABILITY.

Inaccessible Fire Detection Instrumentation can affect the compensatory actions for inoperable Fire Rated Assemblies (Ref. TRO 3.7.3.7 and B3.7.3.7).

Hourly Firewatch Patrols shall be completed once each clock hour.

Individual zones on the hourly firewatch patrol shall be toured at intervals (i.e., zone A and back to zone A) of sixty minutes with a margin of fifteen minutes.

A continuous Firewatch must remain in the specified area at all times and must patrol the required fire zones in the specified area at least once per fifteen minutes with a margin of five minutes.

SUSQUEHANNA - UNIT 1 TRM / B 3.7-14 EFFECTIVE DATE 08/02/1999

Fire Detection Instrumentation PPL Rev. 2 B 3.7.3.8 B 3.7.3.8 Fire Detection Instrumentation BASES ACTIONS The specified area can be as small as one fire zone or as large as a (continued) firewatch can reasonably patrol within the fifteen minute time period. The specified area is limited to two floors of the Control Structure or Reactor Buildings. The floors must be adjacent or served by an operable elevator.

Areas exist Within the plant where the posting of a firewatch does not provide acceptable radiological ALARA practices. For these inaccessible areas, alternate measures should be taken to assure an adequate level of fire protection is maintained.

TRS The TRSs are defined to be performed at the specified Frequency to ensure that the Fire Detection Instrumentation is maintained OPERABLE.

The Surveillances are modified by a ****Note**** to indicate that when a detector is placed in an inoperable status solely for performance of required Surveillances, entry into associated Conditions and Required Actions may be delayed for up to 15 minutes for each detector. Upon completion of each detector test, or expiration of the 15 minute allowance, the detector must reset and alarm must clear, or the applicable Condition entered and Required Action taken. This note is based on the assumption of time to perform a detector test. Under normal conditions, it is expected that the detector would reset and alarm clear within minutes after detector test initiation. It is recognized that while the detector being tested is in the tripped condition, other alarms originating on the string of detectors being tested will be masked.

TRS 3.7.3.8.1 / TRS 3.7.3.8.2 The surveillance frequency of 12 months is based on NFPA 72-1996, National Fire Alarm Code.

(continued)

SUSQUEHANNA - UNIT 1 TRM / B 3.7-14a EFFECTIVE DATE 08/02/1999

Fire Detection Instrumentation PPL Rev. 2 B 3.7.3.8 B 3.7.3.8 Fire Detection Instrumentation BASES TRS TRS 3.7.3.8.3 (continued)

Fire Detection Instrumentation that is inaccessible during unit operation is defined as those fire detection instruments that are located within high radiation areas or where access is limited due to operating conditions, AND remote testing capability (i.e., smoke tubes) does not exist. Inaccessible Fire Detection Instruments need only be tested when the Unit is in cold shutdown for longer than 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />, unless it has been tested in the previous 12 months. Inaccessible Fire Detection Instrumentation must then be surveilled during the cold shutdown prior to startup. Inaccessible Fire Detection Instrumentation remains OPERABLE during Unit operation even though the surveillance frequency for accessible Fire Detection Instrumentation may have been exceeded.

TRS 3.7.3.8.4 Fire Detection Instruments that are Fixed-Temperature, non-restorable line type shall be surveilled by measuring the loop resistance from the control panel to the detector and back to the panel. Changes from the acceptance criteria shall be investigated. The acceptance criterion is identified at time of Fire Detection Instrument installation.

REFERENCES

1. FPRR Section 4.12 SUSQUEHANNA - UNIT 1 TRM / B 3.7-14b EFFECTIVE DATE 11/24/2011