N April. 22, 2010 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555 Zion Nuclear Power Station, Unit 1 and 2 Facility Operating License Nos. DPR-39 and DPR-48 NRC Docket Nos. 50-295 and 50-304
Subject:
Radioaet-ive Effluent Release Report for 2009 and Offsite Dose Calculation Manual for 2009 In accordance with 10 CFR 50.36a, "Technical specifications on effluents from nuclear power plants," and pursuant to Technical Specification 5.7.3, "Radioactive Effluent Release Report,"
for Zion Nuclear Station, Units 1 and 2, this is the submittal of a Radioactive Effluent Release Report for the year 2009. The report is required to be submitted by April 30, 2010 and is provided as 1st Attachment to this letter. A listing of commitments contained in this submittal is provided as 2nd Attachment.
Pursuant to 10 CFR 50.4, there were no changes made to the Exelon Nuclear Offsite Dose Calculation Manual (ODCM) during the period of January through December 2009.
Technical Specification 5.6.1 for the Zion Nuclear power station requires a copy.of the entire ODCM be submitted to the NRC as part of, or concurrent with, the Radioactive Effluent Release Report. This must be submitted prior to May 1. A copy of the entire Exelon ODCM, current as of December 31, 2009 is provided as an Attachment.
If you have any questions about this submittal please contact Mr. Ken Greenlee at 847-379-2700.
Respeý Ronald J. chuster Plant Manager Zion Nuclear Station K:\\RP\\effluent\\09AER\\AERO9_cvrltr.doc qD)5 O.
lk
-4.
554
Attachments
- 1.
Radioactive Effluent Release Report
- 2.
List of Regulatory Commitments
- 3.
Summary of Changes to the ODCM
- 4.
Exelon ODCM Copy to:
Regional Administrator-NRC Region III K:\\ARP\\effluent\\09AER\\AER09 'cvr ltr.doc
Exelon* Generation, LLC Zion Station 101 Shiloh Blvd Zion, 11. 60099 C,
ZION NUCLEAR POWER STATION 2009 RADIOACTIVE EFFLUENT RELEASE REPORT
" UNIT I & 2 (DOCKET Numbers 50-295 & 50M304)
EXECUTIVE
SUMMARY
A review of 2009 effluent data indicates that the activity released from the station was far below any regulatory limit. There was no noble gas released in 2009. This trend can be attributed to the shutdown of both units since late September 1997.
Airborne Dose to Maximally Exposed Receptor from Unit 1 Dose to Maximally Exposed Receptor from Unit 2 a
Gamma Air 0 mrad 0 mrad Beta Air 0 mrad 0 mrad Total Body 1.31 E-05 mrem 1.31 E-5 mrem (Child)
(Child)
Skin 0 mrem 0 mrem Organ 1.49E-05 mrem 1.49E-05 mrem (Adult GI)
(Adult GI)
There was NO Aquatic release of radioactivity from Zion Station for 2009.
Aquatic Dose to Maximally Exposed Receptor (Any) f
" I
+ I Dose to Maximally Exposed Receptor (Any)
T -* I I.,;+ 0 IIU III HI I II II 1 HI IL*
Total Body 0 mrem 0 mrem Organ 0 mrem 0 mrem I. K:\\RP\\EFFLUENT\\09AER\\AER2009exec sum
A ttachment 2:
To the Zion Nuclear Power Station, Units, 1 and 2, 2009 Radioactive Effluent Release Report.
The following identifies those actions committed to by Exelon Nuclear in this document. Any other actions discussed in this submittal represent intended or planned actions by Exelon Nuclear. They are described to the NRC for the NRC's information, and are not Regulatory Commitments.
Commitment:
None Word\\K\\EFFLUENT\\AER NRC Commit
ZION STATION 2009 Unit I 10CFR20 Compliance Assessment
- 1.
10CFR 20.1301 (a) (1) Compliance Total Effective Dose Equivalent 10 CFR 20r-1301 (a) (1) limit
% of the limit
- 2.
Compliance.Summary 10CFR20 1st Qtr.
2 nd Qtr.
3rc MDE 0
2.80E-05 0
2.80E-05 mrem/year 100 mrem/year 0.00000028 Qtr.
4th Qtr 0
% of Limit 0.00000028 TE K:\\RP\\EFFLUENT\\09AER\\AER_ 10CFRCompliance_09.doc
ZION STATION 2009 Unit 2 IOCFR20 Compliance Assessment 1.
10CFR 20.1301 (a) (1) Compliance Total Effeetive Dose Equivalent 10 CFR 20.1301 (a) (1) limit
% of the limit 2.80E-05 mrerm/year 100 mrem/year 0.00000028
- 2.
Compliance Summary 10CFR20 1St Qtr.
2 Qtr.
3 rd Qtr.
TEDE 0
2.80E-05 0
4th Qtr 0
% of Limit 0.00000028 K:\\RP\\EFFLUENT\\09AER\\AERI OCFR_Conmpliance_09.doc
RETDAS V3.6.3
<ZI0>
VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT LIQUID DOSE
SUMMARY
Report for: 2009 Unit Range -
From:
1 To: 2 PERIOD DOSE BY ORGAN AND AGE GROUP (mrem)
Agegrp Bone Liver Thyroid Kidney Lung Liquid Receptor QUARTER 1 GI-LLI Skin TB SITE DOSE LIMIT ANALYSIS Quartr -
Limit Qtr 1 Admin.
Any Organ Qtr 1 Admin. Total Body Age Group Dose Organ (mrem)
UARTER I Limit (mrem)
- 0. 00E+0(
- 1. 13E+0C Max % of Limit 0.00E+00 0.00E+00
- 0. OOE+00 0.00E+00 ADULT TBODY Qtr 1 T.Spc. Any Organ Critical Pathway:
Major Contributors (
0% or greater to total)
Nuclide Percentage Qtr 1 T.Spc. Total Body ADULT TBODY Critical Pathway: Potable Water (PWtr)
Major Contributors (
0% or greater to total)
Nuclide Percentage 0.00E+00 3.75E+00 0.OOE+00 0.OOE+00 1.50E+00 0.OOE+00
PETDAS v3.6.3
<ZIO>
VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT LIQUID DOSE
SUMMARY
Report for: 2009 Unit Range -
From:
1 To:
2 Liquid Receptor PERIOD DOSE BY ORGAN AND AGE GROUP (mrem)
QUARTER 2 Agegrp Bone Liver Thyroid Kidney Lung GI-LLI Skin TB SITE DOSE LIMIT ANALYSIS Quartr -
Limit Qtr 2 Admin. Any Organ Qtr 2 Admin.
Total Body QUARTER 2
Age Dose Limit Max % of Group Organ (mrem)
(mrem)
Limit 0.OOE+00 5.OOE+00 0.OOE+00 ADULT TBODY 0.OOE+00 1.13E+00 0.OOE+00 Qtr 2 T.Spc. Any Organ Critical Pathway:
Major Contributors (
0% or greater to total)
Nuclide Percentage Qtr 2
- T.Spc. Total Body ADULT TBODY Critical Pathway: Potable Water (PWtr)
Major Contributors (
0% or greater to total)
Nuclide Percentage 0.00E+00 3.75E+00 0.00E+00 0.OOE+00 1.50E+00 0.OOE+00
RETDAS v3.6.3
<ZIO>
VSSI 40CFR190 URANIUM FUEL CYCLE DOSE REPORT LIQUID DOSE
SUMMARY
Report for: 2009 Unit Range -
From: 1 To:
2 PERIOD DOSE BY ORGAN AND AGE GROUP (mrem)-------
Agegrp Bone Liver Thyroid Kidney Lung Liquid Receptor QUARTER 3
GI-LLI Skin TB
=== SITE DOSE LIMIT ANALYSIS Quartr - Limit Qtr 3 Admin. Any Organ Qtr 3 Admin. Total Body Age Group ADULT QUARTER 3
Dose Limit Organ (mrem)
(mrem) 0.OOE+00 5.00E+00 TBODY 0.OOE+00 1.13E+00 Max % of Limit
- 0. OOE+00
- 0. ooE+00 Qtr 3
- T.Spc. Any Organ Critical Pathway:
Major Contributors (
0% or greater to total)
Nuclide Percentage Qtr 3
- T.Spc. Total Body ADULT TBODY Critical Pathway: Potable Water (PWtr)
Major Contributors (
0% or greater to total)
Nuclide Percentage 0.OOE+00 3.75E+00 0.00E+00 0.OOE+00 1.50E+00 0.OOE+00
RETDAS v3.6.3
<ZIO>
VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT LIQUID DOSE
SUMMARY
Report for: 2009 Unit Range -
From: 1 To: 2 Liquid Receptor PERIOD DOSE BY ORGAN AND AGE GROUP (mrem)
QUARTER 4 Agegrp Bone Liver Thyroid Kidney Lung GI-LLI Skin TB SITE DOSE LIMIT ANALYSIS Age Dose Quartr - Limit Group Organ (mrem)
QUARTER 4 Limit (mrem)
)0 5.OOE+C
)0 1.13E+C Max % of Limit 10 0.OOE+00 10 0.00E+00 Qtr 4 Qtr 4 Admin.
Any Organ Admin. Total Body
- 0. OOE+0
- 0. 00E+
ADULT TBODY Qtr 4 T.Spc. Any Organ Critical Pathway:
Major Contributors C 0% or greater to total)
Nuclide Percentage Qtr 4 T.Spc. Total Body ADULT TBODY Critical Pathway: Potable Water (PWtr)
Major Contributors
(
0% or greater to total)
Nuclide Percentage a
0.OOE+00 3.75E+00 0.OOE+00 0.00E+00 1.50E+00 0.OOE-i00
RETDAS v3.6.3
<ZIO>
VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT LIQUID DOSE SUMM4ARY Report for: 2009 Unit Range From: 1 To:
2 Liquid Receptor PERIOD DOSE BY ORGAN AND AGE GROUP (mrem)
ANNUAL 2009----------
Agegrp Bone Liver Thyroid Kidney Lung GI-LLI Skin TB SITE DOSE LIMIT ANALYSIS ANNUAL 2009 Age Dose Limit Annual - Limit Group Organ (mrem)
(mrem) 2009 Admin. Any Organ 0.OOE+00 5.00E+00 2009 Admin. Total Body ADULT TBODY 0.OOE+00 2.25E+00 Max % of Limit
- 0. OOE+00 0.00]E+00 2009 T.Spc.
Any Organ Critical Pathway:
Major Contributors (
0% or greater to total)
Nuclide Percentage 2009 T.Spc. Total Body ADULT TBODY Critical Pathway: Potable Water (PWtr)
Major Contributors (
0% or greater to total)
Nuclide Percentage 0.OOE+00 7.50E+00 0.OOE+00 0.OOE+00 3.OOE+00 0.OOE+00
RETDAS v3.6.3
<ZIO>
VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Report for: 2009 Unit Range -
From:
1 To: 2
==I&P DOSE LIMIT ANALYSIS Quartr -
Limit Qtr 1 Admin.
Any Organ Qtr 1 Admin. Total Body Age Group Organ QUARTER 1 Dose Limit (mrem)
(mrem)
- 0. OOE+00
- 0. OOE+00
- 1. OOE+01
- 1. OOE+01 Max % of Limit
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00 Qtr 1 T.Spc. Any Organ Receptor:
0 Distance:
-(meters)
Compas Critical Pathway:
Major Contributors
(
0% or greater to total)
Nuclide Percentage Qtr 1
- T.Spc. Total Body Receptor:
0 Distance:
(meters)
Compas Critical Pathway:
Major Contributors
(
0% or greater to total)
Nuclide Percentage 0.OOE+/-00 l.OOE+/-03l s Point:
0.OOE+00 1.OOE+01
- 0. 00E+00 s Point.:
RETDAS v3.6.3
<ZIO>
VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Report for: 2009 Unit Range -
From: 1 To: 2 NG DOSE LIMIT ANALYSIS Quartr - Limit Qtr 1 Admin.
Gamma Qtrl Admin.
Beta
-====-
QUARTER 1 Dose Limit Max % of (mrad)
(mrad)
Limit 0.OOE+00 1.OOE+01 0.OOE+00 0.OOE+00 1.OOE+01 0.OOE+00 0.OOE+00 1.00E+01 0.00E+00 Qtr 1
- T.Spc.
Gamma Receptor:
0 Distance:
.(,meters)
Nuclide P*.centage Qtr 1
- T.Spc. Beta Receptor:
0 Distance:
(meters)
Nuclide Percentage Compass Point:
e 0.00E+/-00 1.OOE+/-01 0.OOE+/-00 Compass Point:
RETDAS v3.6.3
<ZIO>
VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Report for: 2009 Unit Range -
From: 1 To: 2
== &P DOSE LIMIT ANALYSIS
=-
Quartr - Limit Age Group ADULT CHILD Qtr 2 Qtr 2 Organ GILLI TBODY Dose (mre 2. 97 2.62 QUARTER 2 Limit m)
(mrem)
E-05 5.63E+0 E-05 5.25E+0 Max % of Limit 0
5.28E-04 0
4.99E-04 Admin.
Any Organ Admin. Total Body Qtr 2
- T.Spc. Any Organ ADULT GILLI 2.97E-05 7.50E+00 3.96E-04 Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00-(meters)
Compass Point: NA Critical Pathway: Gropd Plane Deposition (GPD)
Major Contributors (
0% or greater to total)
Nuclide Percentage a
- 1. 00E+02 Qtr 2 T.Spc. Total Body CHILD TBODY 2.62E-05 7.50E+00 3.49E-04 Receptor: 5 Composite Crit. Receptor -
IP Distance:
0.00 (meters),
Compass Point: NA Critical Pathway: Ground Plane Deposition (GPD)
Major Contributors (
0% or greater to total)
Nuclide Percentage CO-60 I.OOE+02
RETDAS v3.6.3
<ZIGO>
VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Report for: 2009 Unit Range -
From:
1 To:
2 NG DOSE LIMIT ANALYSIS QUARTER 2 Dose Limit Quartr -
Limit (mrad)
(mrad)
Qtr 2 Admin.
Gamma 0.OOE+00 7.50E+00 Qtr 2. -
Admin.
Beta 0.OOE+00 7.50E+00 Max % of Limit
- 0. OOE+00
- 0. OOE+00 Qtr 2
- T.Spc.
Gamma 0.00]
Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00-(meters)
Compass Point: NA Nuclide P~centage Qtr 2 T.Spc. Beta 0.00]
Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 (meters)
Compass Point: NA Nuclide Percentage E+00 7.50E,+00 0.OOE+00 0
E+00 7.50E+00 0.OOE+-00
RETDAS v3.6.3 VSSI S40CFRI90 URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Report for: 2009 Unit Range -
From:
1 To: 2
=== I&P DOSE LIMIT ANALYSIS Quartr -
Limit Age Grou p Org QUARTER 3 Dose Limit an (mrem)
(mrem) 0.0-E+00 7.50E+00 0.00E+00 7.50E+00 Max % of Limit
- 0. 00E+00
- 0. OOE+00 Qtr 3 Admin. Any Organ Qtr 3 Admin. Total Body Qtr 3 T.Spc. Any Organ Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00U(meters)
Compas Critical Pathway:-
Major Contributors
(
0% or greater to total)
Nuclide Percentage Qtr 3 T.Spc. Total Body Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 (meters)
Compas Critical Pathway:
Major Contributors (
0% or greater to total)
Nuclide Percentage 0.00E+00 7.50E+00 0.00E+00 s Point: NA
.0 0.00E+00 7.50E+00 0.OOE+00
- s Point: NA
RETDAS v3.6.3
<ZIU>
VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Report for: 2009 Unit Range -
From:
1 To: 2 NC DOSE LIMIT ANALYSIS QUARTER 3
Dose Limit Max % of Quartr - Limit (mrad)
(mrad)
Limit Qtr 3 Admin.
Gamma 0.00E+00 7.50E+00 0.OOE+00 Qtr 3 Admin.
Beta 0.OOE+00 7.50E+00 0.00E+00 Qtr 3
- T.Spc. Gamma 0.OOE+00 7.50E+00 0.OOE+00 Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 Umeters)
Compass Point: NA Nuclide Percentage Qtr 3
- T.Spc. Beta 0.OOE+00 7.50E+00 0.OOE+00 Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 (meters)
Compass Point: NA Nuclide Percentage
RETDAS v3.6.3
<ZIO>
VSSI 40CFRl90 URANIUM FUEL CYCLE DOSE REPORT GASEOUS----DO--E-------A--
GASEOUS DOSE
SUMMARY
Report for: 2009 Unit Range -
From:
1 To: 2 I&P DOSE LIMIT ANALYSIS Quartr - Limit Qtr 4 Admin. Any Organ Qtr 4 Admin. Total Body Age Group QUARTER 4 Dose Limit Max % of Organ (mrem)
(mrem)
Limit 0.00E+00 7.50E+00 0.00E---00 0.OOE+00 7.50E+00 0.00E+00 Qtr 4 T.Spc. Any Organ 0.001 Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00_jmeters)
Compass Point: NA Critical Pathway:-
Major Contributors
(
0% or greater to total)
Nuclide Percentage Qtr 4
- T.Spc. Total Body 0.001 Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 (meters)
Compass Point: NA Critical Pathway:
Major Contributors (
0% or greater to total)
Nuclide Percentage E+00 7.50E+00 0.00E+00 a
E+00 7.50E+00 0.00E+00
RETDAS v3.6.3
<ZTO; VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT GASEOUS. DOSE
SUMMARY
Report for: 2009 Unit Range -
From: 1 To: 2
==NG DOSE LIMIT ANALYSIS Quartr Limit QUARTER 4 Dose Limit (mrad)
(mrad)
Qtr 4 Qtr 4 Admin.
Gamma Admin.
Beta 0.00E.+00
- 0. 00E+00
- 7. 50E+00 7.50E+00 Qtr 4
- T.Spc.
Gamma 0.00E+00 7.50E+00 Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 (meters)
Compass Point: NA Nuclide Percentage Qtr 4
- T.Spc. Beta O.OOE+00 7.50E+00 Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 (meters)
Compass Point: NA Nuclide r'
Percentage Max % of Limit
- 0. OOE+00
- 0. 00E+00
- 0. OOE+00
- 0. OOE+00
RETDAS v3.6.3
<ZIO>
VSSI 40CFR190 URANIUM FUEL CYCLE DOSE REPORT' GASEOUS-----DOSE-----U-----
GASEOUS DOSE
SUMMARY
Report for: 2009 Unit Range-From: 1 To: 2
- == I&P DOSE LIMIT ANALYSIS Annual -
Limit 2009 Admin.
Any Organ 2009 Admin. Total Body ANNUAL 2009 Age Dose Limit Group Organ (mrem)
(mrem)
ADULT GILLI 2.97E-05 1.13E+01 CHILD TBODY 2.62E-05 1.05E+01 Max % of Limit
- 2. 64E-04
- 2. 49E-04
- 1. 98E-04 2009
- T.Spc. Any Organ ADULT GILLI 2.97]
Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00-(meters)
Compass Point: NA Critical Pathway: Gro~nd Plane Deposition (GPD)
Major Contributors
(
0% or greater to total)
Nuclide Percentage CO-60 1.00E+02 2009
- T.Spc. Total Body CHILD TBODY 2.621 Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 (meters)
Compass Point: NA Critical Pathway: Ground Plane Deposition (GPD)
Major Contributors (
0% or greater to total)
Nuclide Percentage Co-60 1.00E+02 E-05 1.50E+01
.0*
E-05 1.50E+01 1.74E-04
RETDAS v3.6.3
<ZIO>
VSSI 40CFRI90 URANIUM FUEL CYCLE DOSE REPORT GASEOUS DOSE
SUMMARY
Report for: 2009 Unit Range-From: 1 To: 2 NG DOSE LIMIT ANALYSIS.
Annual -
Limit 2009 Ad--in.
Gamma 2009 Admin. Beta ANNUAL 2009 Dose Limit (mrad)
(mrad) 0.00E+00 1.50E+01 0.OOE+00 1.50E+01 Max % of Limit
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00
- 0. OOE+00 2009 T.Spc. Gamma 0.OOE+00 1.50E+01 Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00-(ometers)
Compass Point: NA Nuclide Pkrcentage 2009 T.Spc. Beta 0.OOE+00 1.50E+01 Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 (meters)
Compass Point: NA Nuclide Percentage C
RETDAS v3.6.3 VSSI 40CFR190 URANIUM FUEL CYCLE DOSE REPORT Report for: 2009 Unit Range -
From:
1 To:
2 MAXIMUM DOSE ANALYSIS ANNUAL 2009 Age Dose Dose Type Group Organ (mrem)
Any Organ ADULT GILLI 2.97E-05 Liquid Receptor:
NA Gaseous Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 (meters)
Compass Point: NA Liquid Dose.:
Critical Pathway:
Major Contributors Nuclide Gaseous Dose:
Critical Pathway:
Major Contributors Nuclide CO-60 0.OOE+00
% of Total: 0.00E+00 Potable Water (PWtr)
.4-0% or greater to total)
Pecentage 2.97E-05
% of Total: 1.00E+02 Ground Plane Deposition (GPD) 0% or greater to total)
Percentage 1.00E+02 MAXIMUM DOSE ANALYSIS ANNUAL 2009----------
Age Dose Dose Type Group Organ (mre]
Total Body CHILD TBODY 2.62:
Liquid Receptor:
NA Gaseous Receptor:
5 Composite Crit. Receptor -
IP Distance:
0.00 (meters)
Compass Point: NA E-05 Liquid Dose:
Critical Pathway:
Major Contributors Nuclide Gaseous Dose:
Critical Pathway:
Major Contributors Nuclide CO-60 0.OOE+00
% of Total: 0.OOE+00 Potable Water (PWtr) 0% or greater to total)
Percentage 2.62E-05
% of Total: 9.99E+01 Ground Plane Deposition (GPD)
.0% or greater to total)
Percentage 1.00E+02
Zion Nuclear Power Station Annual Radioactive Release Report for 2009 Unit 1 (Docket Number 50-295)
Infant Receptor 4
Yearly Limit 10CFR 50 Appendix I Total dose (mrad, mrem)
% of Yearly Limit Maximum Qtr. Dose (mrad, mrem)
A. Airborne QTR Obj. 1st Qtr.
2nd Qtr.
3 Qtr.
4 Qtr.
Gamma Air 5.0 mrad 0.00Eb00
+
0.E+00 0.00E+00 0.00E+00 Beta Air 10.0 mrad 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 Total Bod 7.5 mrem 0OOE+00 0.OOE+00 0 OOE+/-00 0.00E+00 Skin 7.5 mrem 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Organ 7.5 mrem OIOOE+00 [0OOE+00 0.OOE+00 0-OOE+00 Critica Oran NA NA B. Aquatic Total Bod.
1.5 mrem 0-O*E+00-01OOE+00 0-OOE+O-j 0 OOE+00 Internal Organ 15.0 mrem 0.OOE+001 0 00E+001 OOOE+001 0 00E+001
=
U 10.0 mrad 0.00E+00 0
20.0 mrad O.OOE+00 0
15.0 mrem O.OOE+00 0
15.0 mrem O.OOE+00 0
15.0 mrem O.OOE+00 0
3.0 mrem 0.0E+00 0.00E+00 1.0.mren. 0OOE+00.
OOE+00 NA Critical Organ SNA I
NA I
NA I
NA K:\\RP\\effluent\\09AER\\AER receptors 09.xls A I I
Zion Nuclear Power Station Annual Radioactive Release Report for 2009 Unit 1 (Docket Number 50-295)
Child Receptor I
4 Yearly Limit 10CFR 50 Appendix I Total dose (mrad, mrem)
% of Yearly Limit Maximum Qtr. Dose (mrad, mrem)
A. Airborne QTR Obi. 1st Qtr.
2nd Qtr.
3 Qtr.
4 Qtr.
Gamma Air 5.0 mrad 0.00E+00 0+ 0E+00 0.00E+00 0.00E+00 Beta Air 10.0 mrad 0.00E+00 0.00E+00 0.00E+00 0.00E+00 Total Bod 7.5 mrem 0:OOE+00 1.31 E-05 0.00E+00 0.00E+00 Skin 7.5 mrem 0.00E+00 0.OOE+00 0.00E+00 0.00E+00 Organ 7.5 mrem 0.00E+00 0.00E+00 0.00E+00 0.00E+00 Critical Organ NA NA NA NA B. Aquatic Total Ba 11.5 mrem I OOE0 0OOE+001 OOOE+00 1
0.0 OO+0 lInternal Organ J5.0 mrem I O.OE+001 0 005+001 0 OOE+0%0
.OOE+00 1
(-
10.0 mrad 0.00E+00 0
20.0 mrad
.OOE+00 0
15.0 mrem 1.31E-05 8.70E-05 15.0 mrem 0.OOE+00 0
15.0 mrem O.OOE+00 0
NA 3.mrem 0005+00 00 100 mrem 0.00E+00 0001 NA Critical Organ L_ýýýýNAý
ýNAý K:\\RP\\effluent\\09AER\\AER receptors 09.xls I
Zion Nuclear Power Station Annual Radioactive Release Report for 2009 Unit 1 (Docket Number 50-295)
Teen Receptor Yearly Limit 10CFR 50 Appendix I Total dose (mrad, mrem)
% of Yearly Limit Maximum Qtr. Dose (mrad, mrem)
A. Airborne QTR Obj. 1st Qtr.
2nd.Qtr.
3 Qtr.
4 Qtr.
Gamma Air 5.0 mrad 0.00E+00 0.00E+00 0..00E+00 0.00E+00 Beta Air 10.0 mrad O.OOE+00 0. 00_E+00 0.0OE+0_
0..0E+/-00 Total Bad 7.5 mrem 0.00E+00 0.00E+00 0.000E+00 0.00E+00 Skin 7.5 mrem 0.00E+00 0.OOE+00 0.00E+00 0.00E+00 Or an 7.5 mrem 0.00E+00 0.OOE+00 0.00E+00 0.00E+00 Critical ogan NA NA NA NA B. Aquatic ITotal Bad 1 mem O.OE+001 0.OOE+00 0. OOE+00 0.00
+OE00 jInternal Organ 15.0 mrem O.OE+001 0.OOE+001 000E+00O.'0 E-+00j 100mrad OO0E+00 0
20.0 mrad 0.OOE+00 0
15.0 mrem O.OOE+00 0
15.0 mrem O.OOE+00 0
15.0 mrem O.OOE+00 0
- 3. mem-"r OOOE+00 0.00 10 lOmremO.OOE+00 0.00 NA I
Critical Organ I
NA INA I,NA INA~j K:\\RP\\effluent\\09AER\\AER receptors 09.xis I
Zion Nuclear Power Station Annual Radioactive Release Report for 2009 Unit 1 (Docket Number 50-295)
Adult Receptor I
Yearly Limit 10CFR 50 Appendix I Total dose (mrad, mrem)
% of Yearly Limit Maximum Qtr. Dose (mrad, mrem)
A. Airborne QTR Obj. 1st Qtr.
2nd Qtr.
3 Qtr.
4 Qtr.
Gamma Air
- 5. 0 rad 0.0.
.+..
+..
+
+..........
Beta Air 10.0 mrad 0.00E+00 0.OOE+00 0.OOE+00 0.00E+00 Total Body 7.5 mrem 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 Skin 7.5 mrem 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Organ 7E5 mrem 0.OOE+00 1.49E-05 0.OOE+00 0.OOE+00 Critical Organ NA GI NA B. Aquatic iTotal Body 1.5 mrem 0.OE+00
+
OOE+o-
.o+0-
.5E+66 Intrnl rgn J5.0 mrem 0 OOE+/-00 O.OOE+00 O.OOE+00 000OE+0]
10.0mrad 000E+00 0
20.0 mrad O.OOE+00 0
lmrm O.OOE+/-00 0
15.0 mrem O.OOE+00 0
15.0 mrem. 1.49E-05 9.93E-05 H f3 0Tmrem 0.00E+00 0
10.0 mrem O.OOE+00 0
NA Critical Organ NA NA NA NA K:\\RP\\effluent\\09AER\\AER receptors 09.xls I
Zion Nuclear Power Station Annual Radioactive Release Report for 2009 Unit 2 (Docket Number 50-304)
Infant Receptor Yearly Limit 10CFR 50 Appendix I Maximum Qtr. Dose (mrad, mrem)
Total dose (mrad, mrem)
% of Yearly Limit A. Airborne QTR Obi. 1st Qtr.
2nd Qtr.
3 Qtr.
4 Qtr.
Gamma Air 5.0 mrad 0.00E+00 0.00E+00 0.00E+00 0.00E+00 Beta Air 10.0 mrad 0.00E+00 0.00E+00 0.OOE+00 0.OOE+00 Total Bod 7.5 mrem 0.00E+00 0.00E+00 0.00E+00 O0.0E+00 Skin 7.5 mrem [.OOE+00 O.OOE+00
.0-0E+00 OOOE+00 Organ 7.5 mrem 0.00E+00 0.OOE+00 0.00E+00 0.00E+00 Critical Organ NA NA NA NA B. Aquatic nTotal Body 1.5 mre OOOE+00 0. O.E+0010.E+00 0 OOE+00 lnenlOrgan 15.0 mremn O.OE+001 0 OOE+001 0 OOE+001 0 OOE+00 10.0 mrad 0.OOE+00 0
20.0 mrad O.OOE+00 0
15.0 mrem O.OOE+00 0
15.0 mrem O.OOE+00 0
15.0 mrem O.OOE+00 0
N==A i3.0 mrem 0.O0E+00,O.0OE+00 10.0 mrem O.O-E+00 o.OOE+00 NA Critical Organ I1 NA U
NA 1
NA i
NA I
BL
- [.......................
l..................
rl K:\\RP\\effluent\\09AER\\AER receptors 09.xls I
Zion Nuclear Power Station Annual Radioactive Release Report for 2009 Unit 2 (Docket Number 50-304)
Child Receptor Yearly Limit 10CFR 50 Appendix Total dose (m rad, mrem)
% of Yearly Limit Maximum Qtr. Dose (mrad, mrem)
A. Airborne QTR Obi.
1st Qtr.
2nd Qtr.
3 Qtr.
4 Qtr.
Gamma Air 5.0 mrad 0.00E+00 0.00E+00 0-0-E+00 0.0E+00 Beta Air 10.0 mrad 0.00E+00 0.OOE+00 0.00E+00 0.OOE+00 Total Bodx 7.5 mrem 0.OOE+00 1.31 E-05 0.OOE+00 0.OOE+00 Skin 7.5 mrem 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Oruan 7.5 mrem 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Critical Organ NA NA NA NA B. Aquatic nTotal BodX 11 5 mrem I OOE+00 0_OOE+0 O0O0OE+00O.O0OE_+o_0T IlnenlOr an 05.0 mrem I O.OOE+001 O.OOE+001 0 OOE+001 0 00E+00 10.0 mrad 0.00E+00 0
20.0 mrad 0.OOE+00 0
15.0 mrem 1.31E-05 8.70E-05 15.0 mrem O.OOE+00 0
15.0 mrem O.OOE+00 0
NA 3.0 mrem
- 0.
+
0.00
- 1. me NA0 0 0.00 Critical Organ j
NA I
NA I
NA I
NA K:\\RP\\effluent\\09AER\\AER receptors 09.xis I
Zion Nuclear Power Station Annual Radioactive Release Report for 2009 Unit 2 (Docket Number 50-304)
Teen Receptor 4
Yearly Limit 10CFR 50 Appendix I Total dose (mrad, mrem)
% of Yearly Limit Maximum Qtr. Dose (mrad, mrem)
A. Airborne QTRObj. lstQtr.
2nd Qtr.
3 Qtr.
4 Qtr..
Gamma Air 50mrad OO+0 0O+00 O+00 00+0 Beta Air 10.0 mrad 0.OOE+00 0-.0E+00 0.00E+00 O 00E+00 Total Bod 7.5mrem. 00E+00 0.00E+00 o.OOE+00.000E+00 Skin 7.5 mrem 0.OOE+00 0.00E+00 0.00E+00 0.00E+00 Organ 7.5 mrem 0.OOE+00 0.00E+00 0.00E+00 0.00E+00 Critical Organ NA NA NA A
B. Aquatic ITotal Boda 15 7 mrem
+
0 00E+00 0 00E+00j 00E+00 0.00E+00 lInternal Organ 15.0 mrem IO.OOE-I-OOOEj 0 O.OOE+000.OOE+00I 10.0 mrad 0.00E+00 0
20.0 mrad O.OOE+00 0
15.0 mrem 7.00E+00 0
15.0 mrem O.OOE+00 0
15.0 mrem O.OOE+00 0
S3.0 mrem 0.00E+00 I.0 100 mrem OOOE+00 0
NA Critical Organ NA NA_
I NA I
NA I
K:\\RP\\effluent\\09AER\\AER receptors 09.xls I
Zion Nuclear Power Station Annual Radioactive Release Report for 2009 Unit 2 (Docket Number 50-304)
Adult Receptor M
Yearly Limit 10CFR 50 Appendix I Total dose (mrad, mrem)
% of Yearly Limit Maximum Qtr. Dose (mrad, mrem)
A. Airborne QTR Obj. 1st Qtr.
2nd Qtr.
3 Qtr.
4 Qtr.
eamma Air 5.0 mrad 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Beta Air 10.0 mrad 0.00E+00 0.00E+00 0.00E+00 0.00E+00 Total Body 7.5 mrem 0.OOE+00 0.00E+00 0.OOE+00 0.00E+00 Skin 7.5 mrem 0.OOE+00 0.OOE+00 0.OOE+00 0.00E+00 Organ 7.5 mrem 0.00E+00 1.49E-05 0.00E+00 0.00E+00 Critical Organ NA GI.
NA I
N B. Aquatic Tota B.d 1 5E m
Z.
+00 0.00 +00 0.00 +00 OOOOE+OO H
Onterna g
Organ.5.
0mrem 0 -OOE+00 0 OE+OO0OOE+00 0.00E+00 10.0 mrad 0.00E+00 0
20.0 mrad 0.00E+00 0
15.0 mrem O.OOE+00 0
15.0 mrem 0.OOE+00 0
15.0 mrem 1.49E-05 9.93E-05 3.0 mrem 0.00E+00 0
10.0 mrem 0.OOE+00 0
NA Critical Organ NA NA NA NA K:\\RP\\effluent\\09AER\\AER receptors 09.xls
Zion Nuclear Power Station Annual Effluent Release Report Gaseous Effluent Lower Limit of Detection Isotope Alpha H-3 Kr-85 Mn-54
- Co-58 ZN-65 Sr-89 Sr-90 Mo-99 Cs-134 Cs-1 37 iCe-141 uCi/cc 1.OOE-11 1.OOE-06 1.OOE-06 1.00E-11 1.OQE-11 1.00E-11 1.00E-1 1.00E-11 1.00E-11 1.00E-11 1.0 E-1 1.00E-11 1.00E-1 1 1.O0E-11 Liquid Effluents Lower Limit of Detection Entrained Gases Isotope uCi/mI Kr-85m 1.00E-05 Kr-85m 1-O-E*05 Kr-88 1.O0E-05 jAr-41 1.O0E-05 Xe-131 m 1.00E-05 Xe-133m 1.O0E-05 Xe-133 1.00E-05 Xe-135m 1.O0E-05 X X1e-135m 1.o00E-05 Principle C Isotope Alpha Sr-89 Sr-90 Fe-55 Mn-54 Co-58 Co-60 Zn-65 Mo-99 Cs-134 Cs-137 Ce-141 Ce-144 amma Emmiters uCi/ml 1.OOE-07 1.00E-05 5.00E-08 5.00E-08
[.0OE-06 5.00E-07 5.00E-07 5.00E-07 5.00E-07 5.00E-07 5.00E-07 5.00E-07 5.00E-07
.5.00E-07 K:RP\\EFFLUENT\\09AER\\LLDsO9.xls
ZION NUCLEAR POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT FOR 2009 UNIT I & 2 (Docket Numbers 50-295 & 50-304)
ADDENDUM 1'.
Offsite Dose Calculation Manual (ODCM)
Changes to the ODCM are required by Zion Station Permanently Defueled Technical Specification 5.6.1. and ODCM Section 12.6.3 to be submitted as part of, or concurrent with, the Annual Radioactive Effluent Release Report.
A summary of changes made to the ODCM during 2009 and an entire copy of the ODCM, current as of December 31,2009.
- 2.
Gaseous and Liquid Wasie Treatment Systems and Process Control Program Zion Station ODCM Section 12.6.4 requires major changes to the Gaseous and Liquid Waste Treatment Systems to be reported in the Anmual Radioactive Effluent Release Report.
The Waste Gas Hold-up System was permanently vented. In Zion's defueled configuration this system is no longer applicable.
In Zion's defueled configuration, the charcoal iodine removal system is no longer applicable.
Due to radioactive decay and no means of production, radioactive iodine is not a concern at Zion.
- 3.
Limiting Conditions of Operation (LCOs)
Zion Station ODCM Section 12.7.2 requires explanation as to why the inoperability of liquid or gaseous monitoring instrumentation was not corrected within the time specified in the ODCM to be submitted with the Annual Radioactive Effluent Release Report.
- 4.
Liquid Holdup Tanks and Gas Storage Tanks Zion Station ODCM Section 12.7.2 requires a description of events leading to liquid holdup tanks or gas storage tanks exceeding technical specification limits to be included in the Annual Radioactive Effluent Release Report.
There was no activity present in any gas decay tanks during 2009. The Gas Decay Tanks have been abandoned in place.
No liquid holdup tanks exceeded the limits of Permanently Defueled Technical Specifications 5.6.3 during 2009.
.. K:RP\\EFFLUENT\\O9AER\\ADDENDUMO9.doc
ZION NUCLEAR POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT FOR 2009 ADDENDUM
- 5.
Estimates of Total Error The following is an estimate of the total error associated with certain total values in the Annual Radioactive Effluent Release Report. The Total error, is determined by calculating the square root of the sum of the squares of the individual errors.
- a.
Gaseous Effluents Sampling Error 5%
Calibration Error 10%
Counting Statistics Error 17%
Sample Volume Error 10%
Total Error 23%
- b.
Liquid Effluents Sampling Error 5%
Calibration Error 10%
Counting Statistics Error 16%
Sample Volume Error 2%
Total Error 20%
K: RP\\EFFLUENT\\O9AER\\ADDENDUMO9. doe
ZION NUCLEAR POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT FOR 2009 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS A. SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (Not irradiated fuel)
- 1. Type of waste and 2. Estimate of major nuclide composition
- b.
Dry compressible waste, contaminated equipment, etc.
Waste Volume Activity Estim. Error Class (m
- 3)
(Ci) in Activity A
7.25E+01 0.OOE+00 2.50E+01%
Nuclide
' Percent Activity Name Abundance (Ci)
H-3 0.OOE+00% 0.00E+00 C-14 0.OOE+00% 0.OOE+00 Cr-51 0.OOE+00%
0.OOE+00 Mn-54 0.00E+00% 0.OOE+00 Fe-55 0.00E+00% 0.00E+00 Fe-59 0.00E+00% 0.00E+00 Co-57 0.00E+00%
0.00E+00 Co-58 0.OOE+00%
0.OOE+00 Co-60 0.00E+00%
0.OOE+00 Ni-59 0.OOE+00%
0.OOE+00 Ni-63 0.00E+00%
0.OOE+00 Sr-89 0.00E+00%
0.00E+00 Sr-90 0.OOE+00%
0.OOE+00 Zr-95 0.OOE+00%
0.OOE+00 Nb-95 0.00E+00%
0.OOE+00 Tc-99 0.00E+00% 0.OOE+00 Ag-110m 0.OOE+00%
0.OOE+00 Sn-113 0.00E+00%
0.00E+00 Sb-125 0.00E+00%
0.00E+00 1-129 0.00E+00%
0.00E+00 Cs-134 0.OOE+00%
0.00E+00 Cs-137 0.OOE+00%
0.00E+00 Ce-144 0.00E+00%
0.00E+00 Pu-238 0.00E+00%
0.00E+00 Pu-239 0.00E+00% 0.000+00 Pu-241 0.00E+00%
0.00E+00 Pu-242 0.00E+00% 0.00E+00 Am-241 0.00E+00% 0.00E+00 Cm-242 0.00E+00% 0.00E+00 Cm-243 0.00E+00% 0.00E+00 Zn-95 0.00E+00%
0.00E+00 Waste Volume Activity Estim. Error Class (m
- 3)
(Ci) in Activity B
0.00E+00 0.OOE+00 0.00E+00%
Nuclide Percent Activity Name Abundance (Ci)
H-3 0.00E+00%
0.00E+00 C-14 0.00E+00%
0.00E+00 Cr-51 0.00E+00%
0.00E+00 Mn-54 0.00E+00%
0.00E+00 Fe-55 0.00E+00%
0.00E+00 Fe-59 0.00E+00%
0.00E+00 Co-57 0.00E+00%
0.00E+00 Co-58 0.00E+00%
0.00E+00 Co-60 0.00E+00%
0.00E+00 Ni-59 0.00E+00%
0.000+00 Ni-63 0.00E+00%
0.00E+00 Sr-89 0.00E+00%
0.00E+00 Sr-90 0.00+E00%
0.00E+00 Zr-95 0.00E+00%
0.00E+00 Nb-95 0.00E+00%
0.00E+00 Tc-99 0.00E+00%
0.00E+00 Ag-110m 0.OOE+00%
0.00E+00 Sn-113 0.00E+00%
0.00E+00 Sb-125 0.00E+00%
0.00E+00 1-129 0.00E+00%
0.00E+00 Cs-134 0.00E+00%
0.00E+00 Cs-137 0.00E+00%
0.00E+00 Ce-144 0.00E+00%
0.00E+00 Pu-238 0.00E+00%
0.00E+00 Pu-239 0.00E+00%
0.00E+00 Pu-241 0.00E+00%
0.00E+00 Pu-242 0.00E+00%
0.00E+00 Am-241 0.00E+00%
0.00E+00 Cm-242 0.00E+00%
0.00E+00 Cm-243 0.00E+00%
0.00E+00 Zn-95 0.00E+00%
0.00E+00 Waste Volume Activity Estim. Error Class (m
- 3)
(Ci) in Activity C
0.00E+00 0.00E+00 0.00E+00%
Nuclide Percent Activity Name Abundance (Ci)
H-3 0.00E+00%
0.00E+00 C-14 0.00L+00%
0.000+00 Cr-51
.00E+00%
0.00E+00 Mn-54 I000E+00% 0.00E+00 Fe-55 0.00E+00% 0.00E+00 Fe-59 0.OOE+00%
0.00E+00 Co-57 0.00E+00% 0.00E+00 Co-58 0.00E+00%
0.00E+00 Co-6S 0.00E+00%
0.00E+00 Ni-59 0.00E+00%
0.00E+00 Ni-63 0.00E+00% 0.00E+00 Sr-89 0.00E+00%
0.00E+00 Sr-90 0.00E+00%
0.00E+00 Zr-95 0.00E+00%
0.00E+00 Nb-95 0.00E+00%
0.00E+00 Tc-99 0.00E+00%
0.00E+00 Ag-110m 0.00E+00%
0.00E+00 Sn-113 0.00E+00%
0.00E+00 Sb-125 0.00E+00%
0.00E+00 1-129 0.00E+00%
0.00E+00 Cs-134 0.00E+00%
0.00E+00 Cs-1 37 0.00E+00%
0.OOE+00 Ce-144 0.00E+00%
0.00E+00 Pu-238 0.00E+00%
0.00E+00 Pu-239 0.00E+00%
0.00E+00 Pu-241 0.OOE+00%
0.00E+00 Pu-242 0.00E+00%
0.00E+00 Am-241 0.00E+00%
0.00E+00 Cm-242 0.00E+00%
0.00E+00 Cm-243 0.00E+00%
0.00E+00 Zn-95 0.00E+00%
0.00E+00 Waste Volume Activity Estim. Error Class (mW)
(Ci) in Activity All 7.25E+01 0.000+00 2.50E+01%
Nuclide Percent Activity Name Abundance (Ci)
H-3 0.00E+00%
0.00E+00 C-14 0.00E+00%
0.00E+CO Cr-51 0.00E+00%
0.00E+00 Mn-54 0.00E+00%
0,00E+00 Fe-55 0.00E+00%
0.00E+00 Fe-59 0.00E+00%
0.00E+00 Co-57 0.00E+00%
0.00E+00 Co-58 0.00E+00%
0.00E+00 Co-60 O.OOE+00%
O.OOE+00 Ni-59 0.00E+00%
0.00E+00 Ni-63 0.00E+00%
0.00E+00 Sr-89 0.00E+00%
0.00E+00 Sr-90 0.00E+00%
0.00E+00 Zr-95 0.00E+00%
0.00E+00 Nb-95 0.00E+00%
0.00E+00 Tc-99 0.00E+00%
0.00E+00 Ag-110m 0.00E+00%
0.00E+00 Sn-113 0.00E+00%
0.00E+00 Sb-125 0.00E+00%
0.00E+00 1-129 0.00E+00%
.000E+00 Cs-134 0.00E+00%
0,00E+00 Cs-137 0.00E+00%
0.00E+00 Ce-144 0.00E+00%
0.00E+00 Pu-238 0.00E+00%
0.00E+00 Pu-239 0.00E-+00%
0.00E+00 Pu-241 0.00E+00%
0.00E+00 Pu-242 0.00E+00%
0.00E+00 Am-241 0.00E+00%
0.00E+00 Cm-242 0.00E+00%
0.00E000 Cm-243 0.00E+00%
0.00E+00 Zn-95 O.00E+00%
0.00E+00
ZION NUCLEAR POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT FOR 2009 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS A. SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (Not irradiated fuel)
- 1. Type of waste and 2. Estimate of major nuclide composition
- a.
Spent resins, filter sludges, evaporator bottoms, etc.
Waste Volume Activity Estim. Error Class n(m
- 3)
(Ci) in Activity A
0.00E+00 0.OOE+00 2.50E+01%
Nuclide Percent Activity Name Abundance (Ci)
H-3 0.OOE+00% 0.OOE+00 C-14 0.OOE+00% 0.OOE+00 Cr-51 0.OOE+00% 0.OOE+00 Mn-54 0.OOE+00% 0.00E+00 Fe-55 0.00E+00% 0.OOE+00 Fe-59 0.OOE+00% 0.OOE+00 Co-57 0.OOE+00% 0.OOE+00 Co-58 0.OOE+00% 0,00E+00 Co-60 0.00E+00% 0.00E+00 Ni-59 0.OOE+00%
0.OOE+00 Ni-63 0.OOE+00% 0.00E+00 Sr-89 0.00E+00% 0.ODE+00 Sr-90 0.OOE+00% 0.O0E+00 Zr-95 0.OOE+00% D.OOE+00 Nb-9S 0.OOE+00% 0.00E+00 Tc-99 0.0OE+00% 0.OOE+00 Ag-110m 0.00E+00% 0.OOE+00 Sn-113 0.00E+00% 0.O0E+00 Sb-125 0.00E+00% 0.OOE+00 1-129 0.OOE+00% 0.00E+00 Cs-1 34 0.OOE+00%
D.OOE+00 Cs-1 37 0.OOE+00% 0.00E+00 Ce-144 0.OOE+00% 0.OOE+00 Pu-238 0.00E+00% 0.OOE+00 Pu-239 0.00E+00% 0.OOE+00 Pu-241 0.OOE+00% 0.OOE+00 Pu-242 0.00E+00% 0.00E+00 Am-241 0.OOE+00% 0.005+00 Cm-242 0.OOE+00% 0.00E+00 Cm-243 0.OOE+00% 0.OOE+00 Zn-95 0.00E+00% 0.OOE+00 Waste Volume Class (m3)
B 0.00E+00 Activity Estim. Error (Ci) in Activity 0.00E+00 2.50E+01%
Waste Class C
Volume (m3) 0.00E+00 Activity (Ci) 0.OOE+00 Estim. Error in Activity 2.50E+01%
Waste Volume Class (M
3)
All 0.00E+00 Activity (Ci) 0.00E+00 Estim. Error in Activity 2.50E+01%
Nuclide Percent Activity Name Abundance (Ci)
H-3 0.00E+00% 0.00E+00 C-14 0.00E+00% 0.OOE+00 Cr-51 0.00E+00% 0.00E+00 Mn-54 0.00E+00% 0.00E+00 Fe-55 0.00E+00% 0.00E+00 Fe-59 0.00E+00% 0.00E+00 Co-57 0.00E+00% 0.00E+00 Co-58 0.00E+00% 0.00E+00 Co-6S 0.00E+00% 0.00E+00 Ni-59 0.00E+00% 0.00E+00 Ni-63 0.00E+00% 0.00E+00 Sr-89 0.00E+00% 0.00E+00 Sr-90 0.00E+00% 0.00E+00 Zr-95 0.00E+00% 0.00+E00 Nb-95 0.00E+00% 0.00E+00 Tc-99 0.00E+00% 0.00E+00 Ag-110m 0.00E+00% 0.00E+00 Sn-113 0.00E+00% 0.00E+00 Sb-125 O.00E+00% 0.00E+00 1-129 0.00E+00% 0.00E+00 Cs-134 0.00E+00% 0.00E+00 Cs-1 37 0.00E+00% 0.00E+00 Ce-144 0.00E+00% 0.00E+00 Pu-238 0.00E+00% 0.00E+00 Pu-239 0.00E+00% 0.00E+00 Pu-241 0.00E+00% 0.00E+00 Pu-242 O.OOE+00%
0.00E+00 Am-241 0.00E+00% 0.00E+00 Cm-242 0.00E+00% 0.00E+00 Cm-243 0.00E+00% 0.00E+00 Zn-95 0.00E+00% 0.00E+00 Nuclide Percent Activity Name Abundance (Ci)
H-3 0.00E+00% 0.00E+00 C-14 o.oEi0oo% o.O0E+00 Cr51 fO0E+O0% O.OOE+O0 Mn-54 0.00E+00% 0.00E+00 Fe-55 0.00E+00% 0.00E+00 Fe-59 0.00E+00% 0.00E+00 Co-57 0.00E+00% 0.00E+00 Co-58 0.00E+00% 0.00E+00 Co-60 0.00E+00% 0.00E+00 Ni-59 0.00E+00% 0.00E+00 Ni-63 0.00E+00% 0.00E+00 Sr-89 0.OOE+00% 0.00E+00 Sr-90 0.00E+00% 0.00E+00 Zr-95 0.00E+00% 0.00E+00 Nb-9O 0.00E+00% 0.00E+00 Tc-99 0.00E+00% 0.00E+00 Ag-110m 0.00E+00% 0.00E+00 Sn-113 0.00E+00% 0.00E+00 Sb-125 0.00E+00% 0.00E+00 1-129 0.00E+00% 0.00E+00 Cs-1 34 0.00E+00% 0.00E+00 Cs-137 0.00E+00% 0.00E+00 Ce-144 0.00E+00% 0.00E+00 Pu-238 0.00E+00% 0.00E+00 Pu-239 0.00E+00% 0.00E+00 Pu-241 0.00E+00% 0.00E+00 Pu-242 0.00E+00% 0.00E+00 Am-241 0.00E+00% 0.00E+00 Cm-242 0.00E+00% 0.00E+00 Cm-243 0.00E+00% 0.00E+00 Zn-95 0.00E+00% 0.00E+00 Nuclide Percent Activity Name Abundance (Ci)
H-3 0.00E+00% 0.00E+00 C-14 0.00E+00% 0.00E+00 Cr-51 0.00E+00% 0.00E+00 Mn-54 0.00E+00% 0.00E+00 Fe-55 0.00E+00% 0.00E+00 Fe-59 0.00E+00% 0.00E+00 Co-57 0.00E+00% 0.00E+00 Co-58 0.00E+00% 0.OOE+00 Co-60 0.00E+00% 0.00E+00 Ni-59 0.00E+00% 0.00E+00 Ni-63 0.00E+00% 0.00E+00 Sr-89 0.00E+00% 0.00E+00 Sr-90 0.00E+00% 0.00E+00 Zr-95 0.00E+00% 0.00E+00 Nb-95 0.00E+00% 0.00E+00 Tc-99 0.00E- 00% 0.00E+00 Ag-110m 0.OOE+00% 0.00E+00 Sn-113 0.00E+00% 0.00E+00 Sb-125 0.00E+00% 0.00E+00 1-1 20 0.00E+00% O.00E+00 Cs-134 0.00E+00% 0.00E+00 Cs-137 0.OOE+00% 0.OOE+00 Ce-144 0.OOE+00% 0.00E+00 Pu-238 0.00E+00% 0.00E+00 Pu-239 0.00E+00% 0.00E+00 Pu-241 0.00E+00% 0.005+00 Pu-242 0.00E+00% 0.00E+00 Am-241 0.00E+00% 0.00E+00 Cm-242 0.00E+00% 0.00E+00 Cm-243 0.OOE+00% O.00E+00 Zn-95 0.0+/-E+00% 0.09E+00 I
ZION NUCLEAR POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT FOR 2009 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Radioactive Waste Shipments for 2009 Shipment Date Shipment Number Waste Class Container Solidification Type Agent Activity (Ci)
Volume Media Receiver (mn 3)
(if3)
(M3)
(ft) 1 st Quarter:
Sub totals:
0 0.0000000 0.000 0.00 2nd Quarter:
M Sub totals:
0 0.0000000 0.000 0.00 3rd Quarter:
Sub totals:
0 0.0000000 0.000 0.00 4th Quarter:
Sub totals:
0 0.0000000 0.000 0.00 Totals:
1 O.OOE+00 0.000 0.00 Number of Shipments Activity (Ci)
Volume (M3)
Class A Class B Class C 0
0 0
0.00E+00 0.00E+00 0.OOE+00 0.00E+00 0.00E+00 0.OOE+00
ZION NUCLEAR POWER STATION ANNUAL RADIOACTIVE EFFLUENT REPORT FOR 2009 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS A. SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (Not irradiated fuel)
- 3. Solid Waste Disposition Number of Shipments 0
Mode of transportation none MDestination none B. IRRADIATED FUEL SHIPMENTS No irradiated fuel shipments were performed during 2009.
C. IRRADIATED COMPONENTS, CONTROL RODS, ETC.
No irradiated material shipments were performed during 2009.
I
Zion Nuclear Station Period of Record: January -
March 2009 Stability Class - Extremely Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable Total 1-3 0
0 0
0 0
0 0
0~
0 0
0 0
0 0
0 0
0 0
4-7 8-12 13-18 19-24 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0
> 24 Total 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2 2
0 0
0 0
0 0
0 0
0 0
0 0
0 0
4 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 0
stability class:
0 all stability classes:
4
Zion Nuclear Station Period of. Record: January -
March 2009 Stability Class -
Moderately Unstable Winds Measured at 3!
- 250Ft-33Ft Delta-T (F) 5 Feet Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable Total 1-3 4-7 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
C
=
8-12 13-18 19-24
> 24 Total 2
Hours of calm in this stability class:
0 Hours of missing wind measurements in this stabili Hours of missing stability measurements in all sta ty class:
0 bility classes:
4
Zion Nuclear Station Period of Record: January -
March 2009 Stability Class Slightly Unstable Winds Measured at 35 250Ft-33Ft Delta-T (F)
Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
4-7 0
0 0
3 0
1 2
0 0
0 0
0 0
0 0
0 0
8-12 13-18 19-24
> 24 Total 0
1 0
0 0
0 0
0 0
0 0.
0 6
2 0
0 0
0 0
0 0
0 0
0 0
2 2
4 0
2 Total 0
6 9
9 0
0 24 Hours of calm in Hours of missing Hours of missing this stability class:
0 wind measurements in this stability class:
0 stability measurements in all stability classes:
4
Zion Nuclear Station
'Period of Record: January -
March 2009 Stability Class - Neutral.
250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
0 2
4 12 NNE NE ENE E
1 1
0 2
2 5
25 4
6 11 16 9
8 9
3 3
9 0
7 17 2
22 2
9 5
13 5
7 3
2 7
7 6
0 0
0 0
0 0
0 S
SSW 0
0 0
0 0
2 0
18 0
36 0
34 0
18 0
18 0
23 0
28 0
31 0
18 0
26 0
52 0
43 0
88 0
73 0
76 0
38 C
SW WSW W
WNW NW NNW Variable Total 7
20 16 0
12 20 11 0
13 57 1.6 0
12 50 10 0
15 48 13 0
10 14 14 9
0 2
1 0
0 0
14 0
0 0
325 0
149 0
0 8
124 0
620 Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
34 Hours of missing stability measurements in all stability classes:
4
Zion Nuclear Station Period of Record: January -
March 2009 Stability Class - Slightly Stable Winds Measured at 250Ft-33Ft Delta-T (F) 35 Feet Wind Speed (in mph)
Wind Directio N
NNE NE ENE E
WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24
> 24 Total 0
2 5
2 4
2 4
2 5
7 5
5 13 12 10 2
0 12 10 4
6 2
9 18 15 48 40 24 30 67 58 82 22 0
9 11 20 2
5 7
28 35 25 32 32 31 86 62 67 15 0
467 9
3 3
2 8
2 12 14 2
15 17 2
15 5
17 8
0 37 30 32 12 19 20 62 68 80 94 80 69 185 137 176 47 0
-C Total 80 447 134 20 0
1148 Hours of calm in this stability class:
3 Hours of missing wind measurements in this stability class:
23 Hours of missing stability measurements in all stability classes:
4
Zion Nuclear Station Period of Record: January -
March 2009 Stability Class -
Moderately Stable Winds Measured at Wind Speed 250Ft-33Ft Delta-T (F) 35 Feet (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24
> 24 Total 1
3 0
1 1
2 1
1 3
13 9
7 3
6 4
0 0
5 5
2 1
2 2
4 8
19 10 4
6 26 16 7
1 0
5 1
1 0
2 2
3 13 5
1 0
0 0
0 0
1 0
34 11 9
3 2
5 6
9 24 29 25 13 13 29 22 11 2
0 S
Total 55 118 5
1 0
213 8
Hours of calm in this stability class:
1 Hours of missing wind measurements in this stability class:
Hours of missing stability measurements in all stability classes:
4
Zion Nuclear Station Period of Record: January -
March 2009 Stability Class -
Extremely Stable
- 250Ft-33Ft Delta-T (F)
Winds Measured at 35'Feet Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
2 3
0 0
0 0
5 NNE 1
0 0
0 0
0 1
NE 0
0 0
0 0
0 0
ENE 3
0 0
0 0
0 3
E 1
0 0
0 0
0 1
ESE 1
0 0
0 0
0 1
SE 0
1 0
0 0
0 1
SSE 0
2 3
2 0
0 7
S 1
27 1
0 0
0 29 SSW 4
3 1
0 0
0 8
SW 6
1 0
0 0
0 7
WSW 2
2 0
0 0
0 4
W 4
0 0
0 0
0 4
WNW 0
1 0
0 0
0 1
NW 1
0 0
0 0
0 1
NNW 1
0 0
0 0
0 1
Variable 0
0 0
0 0
0 0
Total 27 40 5
2 0
0 74 Hours of calm in this stability class:
2 Hours of missing wind measurements in this stability class:
0 Hours of missing stability measurements in all stability classes:,
4
Zion Nuclear Station Period of Record: January -
March 2009 Stability Class Wind Direction N
NNE NE ENE E
WNW NW NNW Variable Total
- Extremely Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Sbeed (in mph)
-3 4-7 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 8-12 13-18 19-24
> 24 0
0 0
0 1
1 0
0 0
2 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 o
o 0
0o 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0
- 0.
0 0
0 Total 0
2 2
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 I
3 0
0 4
Hours of calm in this stability class:
Hours of missing wind measurements in this Hours of missing stability measurements in 0
stability class:
all stability cl 0
asses:
4
Zion Nuclear Station Period of Record: January -
March 2009 Stability Class - Moderately Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Direction N
NNE NE ENE E
WNW NW NNW Variable Total Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24.
> 24 Total 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0
.0 0
0 0
0 0
.0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0
.0 0
0 0
0 0
0 0
0
~0 0
0 0
0 a
2 Hours of calm in this stability class:
Hours of missing wind measurements in this Hours of missing stability measurements in 0
stability class:
0 all stability classes:
4
Zion Nuclear Station Period of Record: January -
March 2009 Stability Class -
Slightly Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Direction N
NNE NE ENE E
WNW NW NNW Variable Wind Speed (in mph) 8-12 13-18 19-24 1-3 4-7
> 24 Total 0
3 1
4 0
C Total 0
1 9
4 10 0
24 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 0
stability class:
all stability cl 0
asses:
4
Zion Nuclear Station Period of Record: January -
March 2009 Stability Class -
Neutral 250Ft-33Ft Winds Measured at 250 Feet Delta-T (F)
Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 4-7 1
7 3
5 4.
4 0
0 1
4 6
5 2
5 6
0 8-L12 13-18 19-24
> 24 3
2 13 5
14 17 9
3 5
15 14 2
5 3
3 0
4 3
4 0
3 7
4 2
14 10 10 2
12 6
5 0
4 9
8 0
8 9
4 3
6 11 13 14 11 16 7
5 24 36 21 7
19 31 20 1
19 31 22 1
10 10 10 4
0 0
0 0
Total 24 44 43 14 16 20 40 24 21 25 48 45 93 73 78 40 0
a Total 1
54 161 216 167 49 648 Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
6 Hours of missing stability measurements in all stability classes:
4
Zion Nuclear Station Period of Record: January -
Mardh 2009 Stability Class - Slightly Stable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Direction Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE E
WNW NNW Variable 0
0 0
0 2
2 2
0 0
0 1
0 0
2 0
0 1
2 2
0 1
3 4
3 16 3
3 3
7 6
6 10 4
0 8
6 10 6
1 4
14 17 24 21 17 18 22 28 31 35 0
11 10 14 5
3 12 9
19 31 48 28 26 71 56 90 24 0
457 7
1 6
1 2
6 19 16 9
9 16 14 59 44 38 12 0
14 4
0 2
5 7
21 5
0 12 12 2
9 4
9 1
0 42 23 30 15 16 35 68 73 67 93 77 67 167 140
.178 76 1
C Total 10 73 262 259 107 1168 6
Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
Hours of missing stability measurements in all stability classes:
4
Zion Nuclear Station Period of Record: January -
March 2009 StabilityClass
- Moderately Stable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE E
0 1
0 0
0 2
0 0
2 5
0 0
1 0
0 0
5 1
3 0
2 2
3 4
3 0
0 0
1 1
1 0
0 4
3 2
2 2
1 3
4 3
0 0
0
- 7.
2 7
8 6
11 4
11 0
1 3
1 0
0 1
7 4
1 0
0 1
0 0
1 0
0 4
3 5
a 7
0 12 3
0 9
0 12 4
3 18 5
31 0
24 0
18 0
12 0
14 0
22 0
13 0
15 4
- 10 1
19 W
WNW NW NNW Variable 3
8 3
11 2
0 4
0 0
0 7
b Total 11 26 54 98 20 13 222 Hours of calm in Hours of missing Hours of missing this stability class:
0 wind measurements in this stabili stability measurements in all sta ty class:
0 bility classes:
4
Zion Nuclear Station Period of Record: January -
March 2009 Stability Class -
Extremely Stable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Direction N
NNE NE ENE E
ESE SE SSE Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24 0
0 0
0 0
0 0
0 0
0 0
S 0
0 2
0 1
0 0
3 1
2 0
0 0
0 0
0 0
0 2
0 0
1 1
4 4
6 0
0 0
0 0
0 0
6 8
0 0
0 0
0 0
0 2
24 0
0 0
0 0
0 2
2 a
1 6.
1 16 0
16 0
20 Total 0
2 2
13 0
W 0
WNW NW NNW Variable Total 0
0 0
0 0
2 1
1 1
0 0
0 3
0 1
0 1
0 0
0 0
0 0
0 0
0 6
1 2
1 1
0 0
9 26 32 3
76 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 0
stability class:
all stability cl 0
asses:
4.J,
Zion Nuclear Station Period of Record: April -
June 2009 Stability Class - Extremely Unstable Winds Measured at 250Ft-33Ft Delta-T (F) 35 Feet Wind Direction Wind Speed (in mph) 8-12 13-18 1-3 4-7 19-24 24 Total N
NNE NE ENE E
WNW NW NNW VariablE 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
0 0
2 13 0
0 0
0 0
-0 0
1 2
3 9
12 2
0 0
3 20 4
1 4
2 3
0 0
1 3
6 18 17 5
0 0
a Total 1
23 44 19 0
0 87 0
Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
Hours of missing stability measurements in all stability classes:
7
Zion Nuclear Station Period of Record: April - June 2009 Stability Class - Modedately Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
4-7 1
2 2
1 0
2 0
0 0
0 0
0 0
3 2
0 0
8-12 13-1-8 19-24
> 24 0
Total 3
0 16 5
2.
0 0
Total 0
13 28 21 0
0 62 0
Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
Hours of missing stability measurements in all stability classes:
7
Zion Nuclear Station Period of Record: April Stability Class - Slightly Unstable June 2009 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Direction 1-3 N
0 NNE 0
NE 1
ENE 1
E 0
ESE 0
SE 0
SSE 0
S 0
SSW 0
SW 0
WSW 0
W 0
WNW 0
NW 0
NNW 0
Variable 0
Wind Speed (in mph) 4-7 8-12 13-18 1
14 1
1 2
5 2
3 0
0 0
0 0
3 4
0 0
7 15 4
0 0
0 1
4 0
2 6
8 12 6
0 0
0 19-24 3
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
> 24 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
Total 19 31 7
2 2
5 3
7 0
3 8
10 12 12 6
0 0
Total 2
36 65 21 3
0 127 Hours of calm in this stability class:
0 Hours of missing wind measurements in this stabili Hours of missing stability measurements in all sta ty class:.
. 1.
bility classes:
7
Zion Nuclear Station Period of Record: April -
June 2009 StAbility Class.-
Neutral 250Ft-33Ft Del]ta-T (F)
Winds Measured at 35 Feet Wind Speed (in mph)
Wind Direction 1-3 4 -7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE E
13 46 24 2
30 48 14 4
21 1
4 2
5 6
7 5
5 0
1 1
5 3
0 0
0 7
1 0
0 0
0 4
15 2
1 7
13 S
3 4
SSW 0
0 5
11 6
10 0
2 5
9 8
0 SW WSW W
WNW NW NNW 0
10 15 0
18 22 0
0 0
0 2
1 0
0 0
0 0
94 0
95 0
35 0
1.4 0
10 0
10 0
20 0
22 0
10 0
21 0
25 0
35 0
41 0
62 0
42 0
14
.0
.1 22 28 11 0
16 13 13 1
0 7
0 4
0 2
0 Variable 0
0 Total 26 191 226 96 11 0
550 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 0
stability class:
all stability cl 0
asses:
.,7
Zion Nuclear Station Period of Record: April -
June 2009 Stability Class Slightly Stable Winds Measuredat 250Ft-33Ft'Delta-T (F) 35 Feet Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 4-7 8-1-2 1-3-18 19-24
> 24 Total 13 14 10 8
7 3
7 7
1 5
2 4
5 4
5 8
0 35 50 30 16 15 11 24 22 14 19 8
21 22 14 21 16 0
338 80 41 11 19 4
1 3
22 17 16 17 6
26 12 10 3
0 34 4
5 3
2 0
1 6
1 10 13 1
0 0
0 4
0 2
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
170 112 57 47 28 15 35 58 33 55 41 32 53 30 36 31 0
Total 103 288 84 18 2
833 Hours of calm in this stability class:
1 Hours of missing wind measurements in this stability class:
1 Hours of missing stability measurements in all stability classes:
7
Zion Nuclear Station Period of Record: April Stability Class - Moderately Stable Winds Measured at June 2009
- 250Ft--33Ft Delta-T (F) 35 Feet Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 1-9-24 24 Total N
NNE NE ENE E
WNW NW NNW VariablE Total 13 3
6 5
5 5
10 2
8 9
17 14 5
4 17 7
0 130 7
8 11 3
2 4
6 17 14 13 6
13 19 10 12 4
0 149 1
1 0
5 4
3 1
16 6
0 2
1 0
0 0
0 0
40 21 12 17 15 11 12 18 35 29 22 25 28 24 14 29 11 0
0 323 Hours of calm in this stability class:
Hours of missing wind measurements in this Hours of missing stability measurements in 2
stability class:
0 all stability classes:
7
Zion Nuclear Station Period of Record: April -
June 2009 Stability Class - Extremely Stable Winds Measured at 250Ft-33Ft 35 Feet Delta-T (F)
Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE E
WNW NW NNW VariablE 2
3 1
2 2
1 1
3 9
19 21 11 13 9
4 3
e0 0
8 0
0 2
5 5
5 9
3 5
15 7
0 1
0 0
2 11 1
2 5
6 10 14 28 22 26 26 20 9
5 3
0 a
Total 104 65 18 3
0 0
190 Hours of calm in this stability class:
0 Hours of missing wind measurements in this stabili Hours of missing stability measurements in all sta ty class:>
0 bility classes:
7
Zion Nuclear Station Period of Record: April -
June 2009 Stability Class -
Extremely Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Direction N
NNE NE ENE E
WNW NW NNW Variable Wind Speed (in mph) 8-12 13-18 1-3 4-7 19-24
> 24 Total 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1 11 3
0 2
1 0
0 0
0 0
0 0
1 0
0 I
0 0
0 0
0 0
0 0
0 1
2 11 0
0 0
3 20 4
2 3
4 1
0 0
1 2
5 19 20 3
0 0
Total 0
11 20 25 26 5
87 Hours of calm in Hours of missing this stability class:
0 wind measurements in this stability class:
0 Hours of missing stability measurements in all stability classes:
Zion Nuclear Station Period of Record: April -. June 2009 Stability Class - Moderately Unstable 250Ft--33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE E
WNW NW NNW VariablE 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
4 15 5
1 0
2 1
2 0
4 4
6 9
7 2
0 0
Total 0
1 17 24 18 2
62 Hours of calm in this stability class:
Hours of missing wind measurements in this Hours of missing stability measurements in 0
stability class:
0 all stability classes:
7
Zion Nuclear Station Period of Record: April - June 2009 Stability Class -
Slightly Unstable
- 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Directic N
NNE NE ENE E
WNW NW NNW Variabl(
Wind Speed (in mph) n 1-3 4-7 8-12 13-18 19-24
> 24 Total 1
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
5 11 3
0 1
3 5
1 2
0 0
3 0
4 2
0 0
26 25 7
0 3
5 5
4 2
3 7
11 12 12 6
0 0
Total 1
8 40 52 23 4
128 Hours of calm in this Hours of missing wind stability class:
0 measurements in this stability class:
0 Hours of missing stability measurements in all stability classes:
7
Zion Nuclear Station Period of Record: April - June 2009 Stability Class - Neutral 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet.
Wind Speed (in mph)
Wind Direction N
1-3 I
4-7 8-12 13-18 19-24
> 24 Total 4
22 31 43 15 116 NNE NE ENE E
SSW 1
17 19 30 0
0 1
1 6
9 4
3 6
2 4
2 8
10 4
3 1
1 3
9 2
6 8
9 4
3 1
0 0
0 2
6 6
1 0
7 4
80 1
21 1
18 0
11 0
22 0
24 1
0 0
7 1
1 1
7 2
5 9
2 9
SW WSW 0
0 0
0 1
- 6 10 2
15 26 W
1 19 4
28 9
31 1
45, 0
65 1
40 0
14 WNW 2
19 24 20 0
9 16 14 NW NNW Variable 0
0 0
1 0
6 0
4 0
3 0
0 0
Total 6
67 143 178 117 39 550 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 0
stability class:
0 all stability classes:
7
Zion Nuclear Station Period of Record: April - June 2009 Stability Class - Slightly Stable 25OFt-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Direction Wind Speed (in mph) 8-12 13-18 19-24
> 24 1-3 4-7 Total N
0 NNE 1
NE 3
ENE 4
E 2
ESE 2
SE 0
SSE 1
S 0
SSW 0
SW 0
WSW 0
W 0
WNW 1
NW 0
NNW 1
Variable 0
6 18 11 12 12 10 10 13 4
4 0
2 6
0 1
1 0
29 29 11 9
8 8
16 17 2
7 7
5 6
3 12 9
0 178 53 46 16 10 5
6 10 12 16 27 18 15 33 19 23 7
0 316 44 10 7
12 9
0 2
12 4
6 20 4
13 1
1 4
0 29 2
4 2
6 2
1 3
0 13 4
0 0
0 0
1 0
161 106 52 49 42 28 39 58 26 57 49 26 58 24 37 23 0
S.
Total 15 110 14"9 67 835 Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
0 Hours of missing stability measurements in all stability classes:
7
Zion Nuclear Station Stability Cla Period of Record: April -
June 2009
.ss -
Moderately Stable 250Ft-33F Winds Measured at 250 Feet t Delta-T (F)
Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
0 0
4 16 NNE NE ENE 6
9 3
2 2
0 1
10 2
E 1
9 6
9 7
5 2
3 5
1 1
1 5
0 3
10 12 23 S
0 1
1 4
10 W
WNW NW NNW Variable Total 0
0 2
0 0
2 3
1 4
4 0
2 0
1 4
3 9
9 5
4 0
0 0
1 2
3 0
7 3
0 2
0 3
0 1
0 0
0 7
18 3
0 22 0
17 1
15 1
19 7
19 2
20 1
18 2
57 0
26 0
12 0
15 C
9 0
32 0
16 0
21 9
5 13 2
0 2
0 0
0 6
0 13 81 90 104 22 14 324 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 1
stability class:
0 all stability classes:
7
Zion Nuclear Station Period of Record: April - June 2009 Stability Class -
Extremely Stable 250Ft-33Ft Winds Measured at 250 Feet Delta-T (F)
Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE 0
2 2
1 3
2 1
0 2
4 2
2 3
0 3
0 0
0 0
1 0
0 1
0 0
0 0
0 1
0 0
0 0
1 1
3 7
8 3
5 5
E 1
0 a
WNW NW NNW Variable 2
4 1
10 5
11 14 4
7 11 4
13 1
22 2
37 0
25 0
15 0
16 3
1 0
2 1
3 0
4 1
4 3
3 0
6 8
3 5
1 1
0 0
6 0
11 0
0 0
5 8
0 Total 21 36 45 63 15 9
189 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in I
stability class:
0 all stability classes:
7
Zion Nuclear Station Period of Record: July -
September 2009 Stability Class -
Extremely Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Speed (in mph)
Wind Direction N
1-3 4-7 8-12 13-18 19-24
> 24 Total 0
4 4
0 0
0 8
NNE 0
26 36 NE 1
40 6
7 0
0 0
ENE E
35 0
33 1
39 0
14 2
4 6
4 0
3 0
0 0
0 5
2 0
0 0
0 0
0 0
8 1
3 0
0 0
0 0
0 0
0 0
0 0
0 0
0 62 0
47 0
42 0
35 0
44 0-20 0
0 0
0 9
2 3
3 12 WSW W
WNW NW NNW Variable Total 0
9 19 0
11 17 0
20 15 1
8 15 0
0 0
0 0
0 23 0
29 0
31 0
35 0
24 0
0 3
0 2
0 0
0 5
0 0
0 3
252 152 12 0
0 419 0
Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
Hours of missing stability measurements in all stability classes:
0
Zion Nuclear Station Period of Record: July -
September 2009 Stability Class -
Moderately Unstable
- 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Speed (in mph)
Wind Direction N
1-3 0
4-7 3
8-12 13-18 19-24
> 24 Total 1
0 0
0 4
NNE NE ENE 0
11 0
14 E
ESE SE 8
5 5
3 7
7 0
2 4
7 e
SSE S
0 10 WNW 0
0 NW 2
8 4
0 NNW Variable 0j 3
1 0
0 0
0 0
0 0
0 0
0 Total 7
49 32 2
0 90 Hours of calm in Hours of missing Hours of missing this stability class:
0 wind measurements in this stability class:
0 stability measurements in all stability classes:
0
Zion Nuclear Station Period of Record: July -
September 2009 StabilityClass
- Slightly Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Speed. (in mph)
Wind Direction 1-3 4 -7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE E
WNW NW NNW Variable 0
0 3
4 0
3 1
0 0
0 0
0 0
1 1
1
- .0 8
9 3
2 7
5 13 6
1 2
4 5
7 9
7 1
0 4
1 1
1 1
1 0
6 0
3 11 3
1 8
2 1
0 12 10 7
8 9
14 12 18 5
18 8
11 18 10 3
0 e
Total 14 89 44 6
0 0
153 0
Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
Hours of missing stability measurements in all stability classes:
0
Zion Nuclear Station Period of Record: July -
Stability Class -
Neutral Winds Measured at Wind Speed Wind September 2009 250Ft-33Ft Delta-T (F) 35 Feet (in mph)
Direction 1-3 4-7 8-12 13-18 1.9-24
> 24 Total N
NNE NE ENE E
WNW NW NNW VariablE 5
7 10 4,
2 5
1 2
3 3
2 5
8 5
7 4
0 30 26 11 9
17 27 16 26 20 12 14 14 31 40 18 15 0
17 11 4
4 5
6 4
21 5
17 43 6
8 6
13 7
0 177 0
0 Q
2 0
0 0
3 0
1 7
0 12 3
6 0
0 34 52 44 25 19 24 38 21 52 28 33 67 25 59 54 44 26 0
a Total 73 326 1
0 611 Hours of calm in Hours of missing this stability class:
0 wind measurements in this stability class:
0 Hours of missing stability measurements in all stability classes:
0
Zion Nuclear Station Period of Record:
July September 2009 Stability Class Slightly Stable 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet
- Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable Total 1-3 4--7 8-1-2 13-18 19-24
> 24 Total 16 6
6 4
7 3
6 3
10 17 11 10 9
19 12 9
0 148 35 14 10 9
2 4
8 17 31 17 17 18 33 13 19 10 0
257 2
3 1
0 0
0 2
14 3
7 5
1 4
3 1
0 0
46 53 23 17 1-3 9
7 16 36 44 41 33 29 46 35 32 19 0
0 453 Hours of calm in this stability class:
Hours of missing wind measurements in this Hours of missing stability measurements in 8
stability class:
all stability cl 0
asses:
0
Zion Nuclear Station Period of Record: July -
Stability Class -
Moderately Stable Winds Measured at Wind Speed Wind September 2009 250Ft-33Ft Delta-T (F) 35 Feet (in mph)
Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24
> 24 Total 4
1 0
0 1
3 2
10 21 25 34 13 17 20 22 0
5 0
0 1
0 3
6 1
1.4 4
5 6
25 10 7
13 0
9 1
0 1
1 4
9 5
24 25 30 40 38 27 27 35 0
Total 174 100 2
0 0
0 276 Hours of calm in Hours of missing this stability class:
2 wind measurements in this stability class:
0 Hours of missing stability measurements in all stability classes:
0
Zion Nuclear Station Period of Record: July Stability Class -
Extremely Stable Winds Measured at September 2009 250Ft-33Ft 35 Feet Delta-T (F)
Wind Speed (in mph)
Wind Direction N
NN E ME ENE E
SSW SW 1-3 4-7 8-12 13-18 19-24
> 24 Total 0
1 0
1 1
0 0
1 2
7 17 23 0
0 0
0 0
0 0O 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
0 1
1 C
0 2
4 2
7 WSW W
WNW NW 7
37 17 36 26 5
1 0
132 8
0 0
62 0
0 0
0 0
0 1
0 17 0
30 0
54 0
62 0
13 0
0 1
0 Variable Total 0
195 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 1
stability class:
0 all stability classes:
0
Zion Nuclear Station Period of Record: July -
September 2009 Stability Class - Extremely Unstable 250Ft-33FL Delta-T (F)
Winds Measured at 250 Feet Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24
> 24 0
2 3
6 0
0 0
14 33 1-8 0
0 0
18 17 5
0 0
0 23 12 7
0 0
0 18 8
2 0
0
.0 21 26 2
0 0
0 3
13 8
1 0
0 1
5 1
0 0
0 0
0 0
0 0
0 0
0 1
0 0
0 1
1 11 7
0 0
1 12 10 7
0 0
2 15 12 6
2 0
5 15 15 1
0 1
0 13 8
0 0
0 3
2 1
0 0
0 0
0 0
0 0
Total 11 65 40 42 28 49 25
.7 0
1 20 30 37 36 22 6
0 Total 1
112 175 107 22 2
419 Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
0 Hours of missing stability measurements in all stability classes:
0
Zion Nuclear Station Period of Record: July -
September 2009.
Stability Class - Moderately Unstable 250Ft Winds Measured at 250 Feet 33Ft De].ta-T (F)
Wind Speed (in mph)
Wind Direction 1-3 N
NNE NE ENE E
1 1
3 3
2 2-1 0
0 0
1 8-12 4
7 3
1 3
2
.1 4
0 0
1 2
13-18 1
1 19-24 0
0 2 '
0
> 24 Total 1
0 2
1 2
0 1
1 2
4 1
5 0
0 0
0 0
0 0
0 1
2 1
4 1
0 0
0 9
8 9
8 5
6 6
4 7
0 2
4 6
W WNW NW NNW Variable Total 0
0 0
0 0
1 0
2 1
0 2
1 1
2 0
0 11 0
0 0
0 3
8 3
0 2
21 34 24 0
90 Hours of calm inthis stability class:
0 Hours of missing-wind measurements in this stabi Hours of missing stability measurements in all s
lity class:
0 tability classes:
0
Zion Nuclear-Station Period of Record: July -
September 2009 Stability Class - Slightly Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Speed (in mph)
Wind Direction 1-3 4 -7 8-12 1.3-18 19-24
> 24 Total N
0 NNE NE ENE E
WNW NW 0
0 0
1 0
1 5
1 6
5 6
4 3
2 3
2 2
7
.0 0
5 0
0 0
0 0
0 1
0 0
1 0
8 0
0 1
2 2
0 0
3 1
0 0
0 1
0 0
1 0
0 0
0 5
1 0
3 1
0 0
0 10 0
10 0
0 0
0 12 0
14 5
9 9
0 0
0 8
1 2
3 5
7 5
1 0
4 2
9 0
1 0
0 20 0
10 3
11 0
19 0
0 0
9 4
0 Variable Total 3
42 55 38 12 3
153 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 0
stability class:
0 all stability classes:
0
Zion Nuclear Station Period of Record: July 7 September 2009 Stability Class -
Neutral 250Ft-33Ft Winds Measured at 250 Feet Delta-T (F)
Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE E
10 18 22 0
8 19 16 1
0 0
2 14 6
6 5
2 5
3 0
0 4
1 7
20 0
0 9
15 12 6
13 9
0
- 14 17 13 S
0 0
1 0
1 0
4 16 2
2 3
5 12 3
41 2
1 4
2 1
22 5
8 1
9 0
0 0
55 0
43 0
22 0
18 0
33 0
38 0
29 0
48 0
24 1
21 4
74 0
25 9
58 2
61 2
42 0
20 a
2 13 5
4 26 10 3
36 19 3
11 17 NW NNW 0
0 0
1 13 Variable Total 0
0 6
0 196 0
0 5
84 245 63 18 611 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 0
stability class:
0 all stability classes:
0
Zion Nuclear Station Period of Record: July -
September 2009 Stability Class -
Slightly Stable 250Ft-33Ft Winds Measured at 250 Feet Delta-T (F)
Wind Direction Wind Speed (in mph) 8-12 13-18 19-24 1-3 4-7
> 24 Total N
0 3
14 15 NNE NE ENE E
WNW 1
11 21 0
0 5
14 3
6 1
10 11 7
5 4
2 5
2 9
0 2
0 0
0 0
0 0
0 0
0 0
6 8
7 4
0 0
2 0
0 2
4 6
2 3
1 1
3 2
7 15 0
32 0
40 0
26 0
13 0
24 0
20 0
20 0
37 0
41 0
30 0
32 0
30 0
36 0
37 0
20 0
23 6
19 14 4
6 17 1
9 21 4
16 9
1 9
23 1
20 14 2
9 9
NNW Variable Total 0
10 13 0
0 0
26 0
0 0
169 0
0 4
72 190 0
461 Hours of calm in Hours of missing Hours of missing this stability class:
.wind measurements in this stability measurements in 0
stability class:
0 all stability classes:
0
Zion Nuclear Station Period of Record: July -
September 2009 Stability Class
- Moderately Stable 250Ft Winds Measured at 250 Feet 33Ft Delta-T (F)
Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE E
3 10 0
. 12 12 0
1 1
1 0
0 8
4 8
2 8
3 7
5 1
1 2
3 8
3 0
0 1
0 0
0 S
1 5
13 11 9
13 13 0
0 0
0 0
3 1
0 0
0 0
1 4
2 0
0 0
0 1
12 0
6 0
21 0
27 0
15 0
10 0
11 C
WNW 1
1 0
0 4
10 1
5 8
7 0
30 0
36 0
23 0
14 0
28 0
20 0
11 NW 0
0 0
2 0
1 0
0 NNW 2
7 0
6 16 7
11 8
0 0
0 0
7 0
Variable 0
Total 6
70 104 86 11 1
278 Hours of calm in Hours of missing Hours of missing this stability~class:
0 wind measurements in this stability class:
0 stability measurements in all stability classes:
0
Zion Nuclear Station Period of Record: July -
September 2009 Stability Class -
Extremely Stable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW
.Variable 1-3 4-7 8-12 13-18 19-24
> 24 Total 4
4 5
0 2
1 0
1 0
0 2
2 1
0 2
0 8
13 2
2 0
2 2
3 2
4 2
3 1
2 1
3 0
14 0
0 0
0 1
1 9
8 6
5 5
4 9
0 0
0 0
0 0
0 0
0 2
9 7
2 7
7 12 2
0 26 21 8
2 2
3 4
5 5
22 19 13 14 16 17 16 0
C Total 25 50 67 48 I
2 193 Hours of calm in Hours of missing this stability class:
3 wind measurements in this stability class:
.0 Hours of missing stability measurements in all stability classes:
0
Zion Nuclear Station Period of Record: October - December2009 Stability Class -
Extremely Unstable 250Ft-33Ft winds measured at 35 Feet Delta-T (F)
Wind Speed (in mph)
Wind Direction N
NNE 1-3 4-7 8-12 13-18 19-24
> 24 Total 0
0 0
0 ENE E
WNW NW NNW 0
0 0
0 0
0 0
0 0
0 0
0 0
2 1
2 1
4 4
0 0
2 7
0 9
0 10 1
1 1
0 4
0 0
0 3
1 0
0 0
0 6
0 0
0 0
0 0
0 0
12 0
11 0
0 0
0 5
1 1
0 Variable Total 0
13 34 0
53 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 0
stability class:
0 all stability classes:
5
Zion Nuclear Station Period of Record: October -
December2009 Stability Class - Moderately Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Speed (in mph)
Wind Directic N
NNE NE ENE E
)n 1-3 0
0 0
0 0
0 0
0 4-7 0
0 0
0 0
2 1
1 0
0 0
1 0
2 2
1 0
8-12 13-18 19-24
> 24 Total 0
0 0
0 0
0 0
0 0
0 0
3 0
2 0
1 S
WNW 0
0 0
0 0
0 0
0 0
0 4
6 9
2 0
0 0
0 NW 0
0 2
NNW 0
0 0
4 0
Variable 0
0 Total 0
10 22 1
0 0
33 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 0
stability class:
1 all stability classes:
5
Zion Nuclear Station Period of Record: October - December2009 Stability Class -
Slightly Unstable 250Ft-33Ft Winds Measured at 35 Feet Wind Speed (in mph)
Wind Delta-T (F)
Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24
> 24 Total 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
2 3
4 4
10 4
0 4
9 9
18 11 4
3 0
Total 0
32 42 12 0
0 86 3
Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
Hours of missing stability measurements in all stability classes:
5
Zion Nuclear Station Period of Record: October - December2009 Stability Class -
Neutral
- 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24
> 24 Total 3
1 0
2 3
5 4
5 8
4 6
2 11 8
8 0
6 14 5
1 10 27 33 17 29 34 27 43 56 32 21 26 0
14 9
22 13 10 24 25 37 11 19 37 49 57 30 25 15 0
4 2
14 12 29 5
14 20 0
3 20 17 19 7
9 3
0 27 26 42 30 71 65 77 86 45 64 88 116 136 80 63 52 0
Total 71 381 397 178 36 5
1068 Hours of calm in this stability class:
Hours of missing wind measurements in this 0
stability class:
85 Hours of missing stability measurements in all stability classes:
5
Zion Nuclear Station Period of Record: October -
Decermber2009 Stability Class - Slightly Stable 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Speed (in mnph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE E
WNW NW NNW Variabl(
8 3
1 0
0 2
7 16 17 4
14 15 4
9 0
11 8
1 2
0 3
15 4
23 55 37 36 31 35 32 21 0
9 7
3 1
5 3,
22 10 15 25 30 13 13 13 6
10 0
0 0
0 0
18 8
0 4
0 0
0 0
0 0
0 0
0 29 18 6
4 34 30 44 28 50 98 84 55 58 63 42 42 0
a Total 101 314 185 52 30 3
685 Hours of calm in Hours of missing this stability class:
1 wind measurements in this stability class:
8 Hours of missing stability measurements in all stability classes:
5
Zion Nuclear Station Period of Record: October - December2009 Stability'Class -
Moderately Stable 250Ft-33Ft Delta-T (F)
Winds Measured at 35 Feet Wind Speed (in mphl)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
NNE NE ENE E
WNW NW NNW VariablE 0
1 0
0 0
2 1
0 1
4 2
10 11 2
3 4
0 11 0
0 1
0 3
0 2
15 1
5 20 4
4 2
0 11 2
0 0
1 2
5 3
3 20 3
15 31 6
7 6
0 Total 41 69 5
0 0
0 115 Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
0 Hours of missing stability measurements in all stability classes:
5
Zion Nuclear Station Period of Record:.October Stability Class Extremely Stable Winds Measured at Wind Speed Wind December2009 250Ft-33Ft Delta-T (F) 35 Feet (in mph)
Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24
> 24 Total 0
0 1
0 0
4 1
0 0
1 0
7 7
6 4
2 0
2 0
0 0
0 2
1 0
2 1
2 4
11 3
1 1
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
2 0
1 0
0 6
2 0
4 2
2 11 18 9
5 3
0 Total 33 30 2
0 0
0
\\N 65 Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
0 Hours of missing stability measurements in all stability classes:
5
Zion Nuclear Station Period of Record: October -
Decemdber2009 Stability Class -
Extremely Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Direction N
NNE NE ENE E
WNW NW NNW Variable Wind Speed (in mph) 1-3 4-7 8-1-2 13-18 19-24
> 24 Total 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 2
2 1
1 7
0 0
1 7
11 12 6
1 1
0 C
Total 0
3 19 24 Hours of calm in this stability class:
0" Hours of missing wind measurements in this stabili 6
1 53 Hours of missing stability measurements in all sta ty class:
0 bility classes:
5
Zion Nuclear Station Period of Record: October -
December2009 Stability Class -
Moderately Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
ESE sE SSE S
WNW
-NW NNW Variable 1-3 4-7 8-12 13-18 19-24
> 24 Total 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 1
2 0
0 0
0 a
Total 0
2 12 17 3
0 34 0O Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
Hours of missing stability measurements in all stability classes:
.5
Zion Nuclear Station Period of Record: October - December2009 Stability Class -- Slightly Unstable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Direction N
NNE NE ENE E
WNW NW NNW Variable Wind Speed (in mph) 1-3 4-7 8-12 13-18 19-24
> 24 Total 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
1 2
2 4
4 3
8 6
1 2
9 10 19 10 5
3 0
- a.
Total 0
14 29 32 11 3
89 Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
0 Hours of missing stability measurements in all stability classes:
5
Zion Nuclear Station Period of Record: October - December2009 Stability Class - Neutral 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Speed (in mph)
Wind Direction N
NNE NE ENE E
WNW NW NNW Variable 1-3 4-7 8-12 13-18 19-24
> 24 Total 1
0 0
0 1
1 2
0 3
2 1
0 1
0 3
1 0
2 3
2 3
5 8
14 6
11 10 12 7
7 11 9
8 0
10 8
7 2
6 15 13 23 19 25 25 30 47 35 16 16 0
9 8
17 11 13 16 19 30 17 17 29 41 53 17 34 26 0
3 12 14 19 19 11 14 7
14 6
16 18 20 18 14 4
0 2
0 16 22 25 16 8
12 2
2 7
12 15 0
3 0
0 27 31 56 57 6.9 67 70 78 66 62 90 108 143 81 79 55 0
C Total 16 118 297 357 209 142 1139 14 Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
Hours of missing stability measurements in all stability classes:
5 N
Zion Nuclear Station Period of Record: October - December2009 Stability Class
- Slightly Stable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Speed (in mph)
Wind Direction 1-3 4-7 8-12 13-18 19-24
> 24 Total N
3 3
7 6
2 0
21 NNE 4
2 6
19 2
0 33 NE 1
1 0
7 1
1 11 ENE 3
1 2
2 2
0 10 E
I I
1 0
6 14 23 ESE 0
.2 2
1 2
21 28 SE 0
1 5
0 4
8 18
- SSE, 1
3 7
8 6
9 34 S
0 1
19 36 17 2
75 SSW 2
7 29 35 14 0
87 SW 0
6 26 38 15 0
85 WSW 0
4 22 22 3
1 52 W
2 3
21 27 3
1 57 WNW 0
1 9
19 10 0
39 NW 1
2 8
35 1
0 47 NNW 3
6 17 25 3
0 54 Variable 0
0 0
0 0
0 0
Total 21 44 181 280 91 57 674 Hours of calm in this stabilityclass:
0 Hours of missing.wind measurements in this stability class:
20 Hours of missing stability measurements in all stability.classes:
5
Zion Nuclear Station Period of Record: October -
December2009 Stability Class -
Moderately Stable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Direction Wind Speed (in mph) 1-3 4-7 8-12 18 19-24
> 24 Total N
0 NNE 0
NE 1
ENE 0
E 0
ESE 0
SE 0
SSE 0
S 1
SSW 1
SW 0
WSW 0
W 0
WNW 0
NW 0
NNW
.0 Variable 0
1 0
3 7
1 0
3 7
6 3
4 14 17 2
0 0
2 10 7
1 1
1 0
.7 17 11 6
8 17 19 6
2 0
a Total 3
12 34 65 1
0 115 0
Hours of calm in this stability class:
0 Hours of missing wind measurements in this stability class:
Hours of missing stability measurements in all stability classes:
5
Zion Nuclear Station Period Stability Class -
Wind Direction 1-3 of Record: October - December2009
- Extremely Stable 250Ft-33Ft Delta-T (F)
Winds Measured at 250 Feet Wind Speed (in mph) 8-12 13-1.8 19-24
> 24 4-7 Total N
0 NNE NE ENE E
WNW NW NNW Variable 2
9 2
5 0
Total 3
17 28 13 4
0 65 Hours of calm in Hours of missing Hours of missing this stability class:
wind measurements in this stability measurements in 0
stability class:
.0 all stability classes:
5
Letter lo 'Fcl Date: October 2, 2009 Subject-Zion Station 30-Day Return to Service Letter for ORT-PR25 On September 4, 2009 0RT-PR25 was declared out of service clue to false high radiation alarms.
Zion Radiation Protection ODCM table 12.2-1 requires ORT-PR25 to be returned to service within 30 days. If the mopitor is not returned to service within 30 days the station is to conlduct a station review to determine the plan to return the monitor to an operable status.
Troubleshooting has-been performed over the last 28 days to determine the cause of the high radiation alarms. Rie alarms occurred primarily within 20 minutes of sunset when perimeter lighting was activated, The frequency of the alarms has decreased since September 23, 2009. The plan is to continue monitoring until October 16, 2009. The Corporate Subject Matter Expert will perform an independent review of the data the week of October 5, 2009. The estimated date for resolution decision is October 16, 2009.
ILX 0 Ken Greenlee RadChem Manager K'eno~netli L. Kinig Maintenance Manager ames Ashley 6" Regulatory As ralanc*
Terry Printz Operations / Engineering Manager JL6n-ý ej?
Date Da e Date Date K: / RP / EFFLUENT / 09AER
Letter to File 1¢.-
Date: October 1.5, 2009
Subject:
Zion Station 30-Day Return to Service Letter for ORT-PR25, Revision I On Septemnber 4, 2009 0RT-PR25 was declared out of service due to false high radiation alarms.
Zion Radiation Protection ODCM table 12.2-1 requires ORT-PR25 to be returned to service within 30 days. If the monitor is not returned to service within 30 days the station is to conduct a station review to determine the plan to return tei monitor to an operable status.
Troubleshooting has been performed over the last 44 days to determine the cause of the high radiation alarms. The alarms occurred 28 times primarily within 20 minutes of sunset when outdoor 7ghting was automatically activated. The plan is to continue monitoring and troubleshooting efforts. The Corporate Radiation Monitor Subject Matter Expert has been contacted as well as other sites and the manufacturer. Additional time is required to fully investigate both lighting issues and vendor recommendations related to potential causes. The estimated return to service date is no later than November 30, 2009.
.0 0,
Ken Greenlee RadChem Manager Kenneth L. K~ing Maintenance Manager
/ames Ashley Regulatory Assuri. ceý.
Terry Printz Operations / Engineering Manager rZ¢,YS -o Date Date 16-,1/2E- ` 7 Date Date
/
~'.~A')
Letter to File Date: October 15, 2009
Subject:
Zion Station 30-Day Return to Service Letter for ORT-PR30A On September 16, 2009 ORT-PR30A was declared out of service due to a monitor fail condition that could not be remedied. ORT-PR30A is the Fuel Building noble gas effluent monitor.
Zion Radiation Protection ODCM table 12.2-3, Surveillance 10, requires ORT-PR30A to be returned to service within 30 days. If the monitor is not returned to service within 30 days the station is to conduct a station review to determine the plan to return the monitor to an operable status.
Troubleshooting has been ongoing to determine the cause of the monitor problem. The manufacturer has been= contacted to assist in troubleshooting efforts. The plan is to replace the existing detector module and alter the sample collection method. Following replacement, the system will be monitored for a period of time prior to returning it to service. The estimated return to service date is no later than October 31, 2009.
41 1.-1..,.zf~z f-t, Ken Greenfee RadChem Manager
/& -./S-O, Date Kenneth L. King Maintenance Manager me Asle
/ Regulatoryy As cc*
Terry Printz Operations / Engineering Manager
/Dt /
Date Date Date
uot"r W (F1 1(,
D)ale: October 30, 2009 SuLbject: Zioii Station 30-Day Return to Service Letter for OR.'"-PR30A On September 16, 2009 ORT-PR30A was declared out of service due to a monitor fail condition that could not be remedied. OR'IT-PR30A is the Fuel Building noble gas effluent monitor.
Zioni, Radiation Protection ODCM table 12.2-3, Surveillance 10, requires ORT-PR30A to be returned to service within 30 days. If the monitor is not returned to service within 30 days th-te station is to conduct a station review to determine the plan to return the monitor to an operable status.
Troubleshooting has Ien ongoing to determine the cause of the monitor problem. The manufacturer has been contacted to assist in troubleshooting efforts. A functional detector module has been installed and. the monitor tubing has been reconfigured. The system is currently being monitored and will continue through the week of November 9, 2009 with an expected return to service date no later than November 13, 2009.
Ken Greenlee RadChern Manager Kenneth L. King Maintenance Manager Date Date Date Date Operations / Engineering Manager K: / RP / EFFLUENT / 09AER
2009 Summary of changes made to the ODCM :
For the year 2009 the-e were no changes made to the Zion Station ODCM.
.0
,K
. K:RPNEFFLUENT\\M9AER\\AER Summary of,changes09.doc