Text

ADAMS Accession No.: ML100680420 REQUESTS FOR ADDITIONAL INFORMATION Prairie Island Nuclear Generating Plant, Units 1 and 2 Alternative Source Term (AST) License Amendment Request (LAR) dated October 27, 2009 Docket Nos. 50-282 and 50-306 TAC Nos. ME2609 and ME2610 Office of Nuclear Reactor Regulation Division of Engineering Electrical Engineering Branch Please provide the following information for the NRC staff to continue its review:

1. Provide the changes in the emergency diesel generator (EDG) loading due to this LAR.

Provide the EDG loads for Units 1 and 2 pre-and post-AST, and confirm that adequate margin exists post-AST. Confirm that EDG testing envelopes the loading requirements due to this LAR.

2. Confirm that no credit has been taken for non-safety related system(s) due to this LAR.

If yes, then a) describe the impact on the EDG loading due to these systems, b) describe how electrical and physical separation, and single failure criteria, have been met, and c) describe how the operators will be notified (e.g., control room annunciators) in the event that these systems become inoperable.

3. Confirm that there are no changes to the environmental qualification (EQ) program due to this LAR.