ah tJ'Hr..,w14, Hnpflr flAV 12 2~

J2 RESEARCH & DEVELOPMENT CENTER Report No.:

10, 519 Date:

April 16, 1981'

Subject:

OZONE RESISTING SILICONE RUBER CABLE TESTS FOR CONSOLIDATED EDISON CO.

I...

SPECIAL TESTI,G PROGRAM ON "4A'WG 600 VOLT SILICONE RUBBER CABLE AS PROVIDED BY CONSOLIDATED EDISON CO.

REQ. 4N845-0-0025-00, DATED 12/18/80 I

~

.1

SUMMARY

Consolidated Edison furnished samples of service-aged 600 volt cable taken from their Indian-Point Nuclear Generating Station. All samples passed current industry standards, ICEA S-19-81, for this class of insulation.

For: Application Engineering Conducted by:

Mat(

Written by:

J.

N Approved:

S.

Approved:

F.

1 Approved:

H.

8202090348 B20204 PDR ADOCK 05000286 P

.PDR 0rials Laboratory Personnel -

Mr.

E.

Smith o Doepken, Jr Distribution:

Messrs. S. Allam J.

Fitzger:.

F. A. Teti Original -

R&D File L -_ -

/

,CONSOLIDATED EDISONJ CO.

/

ZO IE RESTST].NG STLICO:-

RUPTIER CABLE TESTS estin -Period: March 1981

.Cable

Description:

04 AWG, I/C, Copper Conductor, 85 mils silicone rubber insulation, polyester film separator helically applied,.saturated asbestos braid covering overall.

The Testing program was divided into two (2) groups as follow s:

Groun I Three (3)*forty (40) foot samples were involved each sample containing one (1) field installed splice. The sample identifications are as follows:

No. 2 - Dried, Not Rinsed.

No. 4 -

Unconditioned.

NO.

C, -wasnea and Dried.

Group 11 Two (2) samples were tested, one thirty (30) foot and ona (1) forty (40) doot in length. The thirty (30) foot length had two (2) splices nstalled at the Phelps Dodge facility by Con Ed personnel under the s§ e

_on of the Raychem Co. personnel, the splice supplier. The forty (40) foot sample was used as a control and tested in the "as received" condition.

Test Procedures All tests were performed strictly in accordance with ICEA Pub. No. S-19-81 (sixth edition) titled "Rubber Insulated Wire and Cable for the Transmissi:.

and Distribution of Electrical Energy".

The ioilowing tests comprised the testing program:

Physical and Aging Requirements per Section 3.17.1 Accelerated Water Absorption per Section 3.17.3.2 Voltage Tests per Section 3.17.2.1 Insulation Resistance Tests per Section 3.17.2.2 A) Group. I samples were first tested to determine IR at 60°F with and after removal of the splice from each sample.

Next, all samples (splices removed) were subjected to the AC and DC voltage withstand test.

The samples were then removed Sfrom the room temperature bath and placed into a 750 C water bath.

After a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> soaking period (no voltage) the IR at 750C was measured.

./0 0

CONSOLIDATED EDISON CO.

OZONE RESISTING ILICONE RUBBER CABLE TESTS PAGE NO. 2/

The E14-60 (at 75 C) test completed the testing procedure.

General Observations - Group I Samples With the exception of the IR measurement on the samples containing the splices and the DC withstand test on sample No.'s 4 and 6, the cables met all applicable current requirements of ICEA S-19-81 for this class of insulation.

  • The unusually low IR values obtained on the samples with splices are attributed to. improper installation of splices.

. The DC voltage failures experienced on sample No.'s 4 and 6 may have been the result of mechanical damage due to handling. llcwever,'

examination of faulted areas revealed no obvious evidence of mechanical damage.

13)

Group I-sample testing, IR at 606F, DC and AC withstand, met applicable current requirements of ICEA S-19-81 for this crass of insulation. This was true for both the spliced and unspliced samples. The IR measurements at 75C indicate good quality 600 volt insulation as evidenced by converting the 60OFeK factcr of 4000 to a 750C K factor of 25.

. 2,..'.'.'.'

OZONE SAMPLE IDENTIFICATION Testing Sequence ICEA S-19-81 Test Method CONSOLIDATEDI

'-SISTING SILICONE GROUP I r

f"4 UNCONDITIONED ISON CO.

RUBlER IC

  1. 6 WASHEE ILR TESTS 4-i--

p p

& DRY

  1. 2 DRIED NOT RINSED CURRENT

-ICEA S-19-81

  • SEC. 3.17 REQUIREMENTS I-IR at 60OF '

f, (With Splice) 6.25 Sample length 32 Ft.

-32 Ft 40 Ft.

M,:eg ohms A

4.5 19.0 29.0 (3.17.2.2)

, Factor RK.

6.

4 8.

" -1>

4000 2-Pemove Snlice 6.25"Yes es.s 3-IR at 600 F 6.25 Sample Length I

30 Ft 28 Ft.

38 Ft.

mcg ohms j

3.0x10 6 3.2xi 6 3,4x0 6

(3.17.2.2)

K Factor 370,000

> 4000 4-DC Withstand Table 3-2 at Room Temn.

6.24.3.

Failed At 13kV Fa*1ea kt 5!V ase

(.kV']5 Mi 5-Cut Out Failure _

Yes Ys V

6-AC Withstand Table 3-2 At Poo-i Temp.

6.24.2

-!i3 Passed Passel Passed 6,0kV-5 Min 7-Retest "Table 3-2 DC Withstand 6.24.3 Passed passe.

8.0kV-15 ni 8-IR at 750c (24 11r. Soak) 6.25 For Engineer Sample Length 10 Ft.

10 Ft.

38 Ft.

Information Meg ohms 102x10 3 101xl)3' 32xi0 3 K Factor 4211.

"4170 150_21_._

9-Accelerated Water Absorption 1-60'(75Oc)

I Aging Requirements Tensile Elongation A ino 6.9.2 Table 1 6.4.13.3 6.14.13.5 AA A

Tablel 2 Table 3 Sec. 3.17.3.

(Listed on Tab Table 4 Table 5 Table 6 Scc. 3.17.1

-(Listed on Tab

.LI.

I I

i;

A COVISOLIDATDTSON CO.

NERSINGSLCONE

.t13RCA13LE

SUBJECT:

ON 3/26/81 CON GROUP II ED Air RAYCHEM PE'SONNEL INSTALLED TWO (2) SPLICES ON 600V CABLr SMPTLr SAMPLE IDENTIFICATION TESTING SEQUENCE I

T ~

-~---------------.---.-.----.-

ICEA i-19-81 TEST I:ETHOD SAMPLE #1 CABLE AND 2 SPLICES SAMPLE h2 CABLE ONLY CURRENT.

ICEA S-19-81 SECo 3.17 REQUIREMENTS 1-IR at 60°F

6.

ISec.

3.17.2.2 Sample Length 30 Ft.

41 Ft.

Meg ohms 4.5x10 6 3.5xi0 6 1< Factor 557,000 592,000 4000 2-Dc Uithstand Table 3-2 At Room Temo.

6..3 "

Passed 18kV 15 Min.

3-AC ':ithstand Table 3-2 At Room Temp.

Passed Passed 6kV -5 Min.

4-Iz At 750c (24 I!r. Soak)

6. -5 ist Day Meg ohms 8.7x10 3 21x10 3 For X Factor 1078 3555 Engineering 7tn uay Meg ohms 11.2 x 103 19.75 x 103 Information K

K Factor 1387 3343

  • 14th Day

- 3 Meg ohms 12.0 x 10 19.70 x 10 K Factor..

1486 3335

  • a::

~

I CONSOLIDATED FDT.SO:! CO.

(' NI.' RESISTING s!LICO[I!

RU!: !:R CAPLE TABLE Ri

/ P4.;-.-

!v~~iind 60 PIz

.5, 7.,:

(ICEA S-19-81 6.9.2) 40 V/M 4 DyS 7 Days 3.4 iavu SIC 3.16 3.24 3.24

%IPF 2.10 1.99 2.0 SIC 3.17 3.24 3.24 Chance in S.T.C.

i4 Days

+

o00 80 V/M

% PF 2.18 2.08 2.10 Current ICEA Requirements Sec. 3.17.3.2 10.0%

3. 0%

Stability Factor

+

.08

+

.09

+

.1 1 Dav 7 Dt. ":"

PIIELPS DODGE CABLE & WIRE COMPANY CONSOLIDATED EDISON CO.

O ZONE RESISTI.N:G !;ILiCONE RUIBER CAILE

/

~~TABLE

.",2 j

SAMPLE 96 -Washed and dried.

60 Hz @ 750 C (ICEA S-19-81 6.9.2)

"1 Day 7 Days 14 Days SiC 3.17 3.19 3.20 40 V/M

% PF 2.67 2.33 2.40 SIC 3.17 3.20 3.21 1-14 Days

  • 7-14 Days

%'Change in S.I.C.

+ 1.26%

+

o31%

Stability Factor

1. Day 7 Days 14 Days Current ICEA Requirements Sec. -3.17. 3.,2 10%

+

.13

+

.. 12

~'

~

.~.

80 V/,

% PF 2.77 2.46 2.52

  • PIEhPS DODGE CABLE & WIRE COMPANY CONSOLIDATED EDISON CO.

OZONE RESISTING SILICONE RUB'BER CABLE TABLE 93 SAMPLE N2 -

JUST DRIED NOT RINSED.

60 Hz @ 750 C -

(ICEA S-19-81 6.9.2) 40 V/M SIC 3.44 3.20 3.23

% PF 6.75 2.06 2.02 SIC 3.46 3.20 3.24 80 V/M

% PF 6.81 2.15 2.16 1-14*Days

.7-14 Days I Day*

7 Days 14 Days Change in SIC

-6.3%

+ 1.25%

Stability Factor

+

.06

+

.09

+

.14 Current ICEA.

Requirements Sec. 3.17.3.2 30%

3..0%

-~......

  • 6' I Day 7 Days 14 Days

I-.E~.s.

0*

0 A

CONSOLIDATED EDISON CO.

O..NI: RESISTI NG SILICO'!E r. un.B.,R CABLE TABLE H,4 ff4 v Unconditionoed.

original Tensile & Elong.

Ten.-ile 1

1150 2

800 3

1000 4

1025 5

13.100 6

1075 1025 Elong.

300 270 320 310 330 310 306.6, After Aging 7 Days @ 200 0 C Air Oven.

1' 950 2

800 3

950 92 5

5 900 905 (88.2% Ret) 266%

(86.7% Ret)

Current ICEA S-19-81 Requirements.

ec.3.17.1 Tensile 800 Min.

Elongation at RujLure 250% Min.

Aging

.ensile Elongation 500 Min.

at Rupture 280 250 260 290 250 125% Min.

DODGE CABLE & WIRE COIMPANY 9j CONSOLIDATED EDISON CO.

OZONE RESISTIN:G SILICONE RUtFER CABLE TABLE _ 5 116 Washed Dried Original Tensile & Elong.

Tensile 1

950 2 1025 3

900 4 1000 5 1000 After Aging - 7 Days @ 200 0 C Air Oven.

1 900 L2 900 3

850 4

975 5

850 895 (91.7% Ret) 250%

(92.5% Ret)

.. ~...... -..........................

ICEA Req.

Tensile, PSI

% Elongation Orictinal 800 Min.

250 Min.

After Acing 500 Min.

125 Min.

Elong.

250 280 250 290 280 270%~

250 240 230 280 250

IIELPS DODGE CA13LE: & WIRE COMIPANY

/

CONSOLIDATED EDISON CO.

OZONE PESISTING SILICON": PUBBER CAPLE TABLE 46

  1. 12 Sample - Just Dried not Rinsed.

Original Tensile & Elong.

Tensile 1 1075 2 1000

-4 975 5 1025

.1030

% Elon@'

290 270 290 290 290 286%

After Aging - 7 Days @ 2000C Air Oven.

1 800 2

950 3

850 4

900 5

950 890 (86.4,1 Ret) 250 260 230 290 210 248%

(86.7% Ret)

S-....-.-......,......-.

.Wh;~..

ICEA Req.

Tensile PSI

% Elong.

Orig.

800 Min.

250 Min.

After Aging 500 Min.

125 Min.

rl

.r.

/

It