ML093000573
| ML093000573 | |
| Person / Time | |
|---|---|
| Site: | Summer (NPF-012) |
| Issue date: | 11/05/2009 |
| From: | Martin R Plant Licensing Branch II |
| To: | South Carolina Electric & Gas Co |
| Martin R, NRR/DORL, 415-1493 | |
| References | |
| GL-04-002, TAC MC4721 | |
| Download: ML093000573 (125) | |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 November 5, 2009 LICENSEE; SOUTH CAROLINA ELECTRIC &GAS COMPANY FACILITY:
VIRGIL C. SUMMER NUCLEAR STATION, UNIT 1
SUBJECT:
SUMMARY
OF SEPTEMBER 14, 2009, PUBLIC CONFERENCE CALL TO DISCUSS RESPONSES TO GENERIC LETTER 2004-02 REQUESTS FOR ADDITIONAL INFORMATION (TAC NO. MC4721)
On September 14, 2009, a conference call was held between representatives of South Carolina Electric & Gas Company (the licensee) at the Virgil C. Summer Nuclear Station, Unit 1 (VCSNS) site and the U.S. Nuclear Regulatory Commission (NRC) staff in Rockville, Maryland. The purpose of the meeting was for the NRC staff and licensee to exchange information regarding the staff's requests for additional information (RAls) associated with Generic Letter 2004-02 dated February 3, 2009, (Agencywide Documents Access and Management System (ADAMS)
Accession No ML090270927).
A list of attendees is provided in Enclosure 1.
The licensee provided draft RAI responses for the discussions (see Enclosure 2).
The meeting was held to allow the NRC staff to inform the licensee on which proposed RAI responses appeared adequate, and which responses were either insufficient (Le., require further explanation or additional detail) or failed to fully address the staffs concern. The results of the discussion are provided below.
(1)
The NRC staff determined that the licensee's responses to the following RAls were adequate, in that the staff did not foresee any significant concerns:
Question 1 Question 2 Question 5 Question 7 Question 8 Question 9 Question 12 Question 13 Question 14 Question 15 Question 16 Question 17 Question 18 Question 19 Question 20 Question 21 Question 23 (2)
The licensee will provide additional information to either address specific NRC staff concerns or enhance its response for the following RAI:
Question 10: The staff asked the licensee to clarify the information on the flashing evaluation for a large break loss-of-coolant accident (LOCA), and discuss why flashing is not a concern for a small break LOCA.
(3)
The NRC staff informed the licensee that it still had concerns with the following RAI responses, and that these items would be discussed at a public meeting:
- 2 Question 3:
The NRC staff would like to see the licensee's basis for the erosion because the total percentage appears low.
Question 4:
The NRC staff questioned the tumbling velocity and the size categories used by the licensee, and would like to discuss them further.
Question 6:
The NRC staff questioned the basis for the debris generation, and would like to discuss it further.
Question 11: The NRC staff would like additional details of the licensee's bypass determination.
Question 22: The NRC staff requested additional details on how the topical report data was used in the licensee's calculations.
Questions 24 to 26:
The NRC staff did not find the licensee's arguments that there would be no chemical effects for VCSNS to be convincing and concluded that chemical effects should be addressed for the VCSNS.
Prior to concluding the meeting, it was agreed that an additional conference call can be held to discuss items (3), (4), (6), (11), and (22), above, and to determine if the proposed responses adequately address the staffs concerns or whether additional information is still required.
/LJl/J)11~~
f RObe~~~artin, Sen(or Project Manager Plant Licensing Branch 11-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-395
Enclosures:
- 1. List of Attendees
- 2. Draft Responses to NRC Request for Additional Information Distribution via ListServ
LIST OF ATTENDEES SEPTEMBER1~2009CONFERENCECALLTO DISCUSS RESPONSES TO GENERIC LETTER 2004-02 REQUEST FOR ADDITIONAL INFORMATION NRC South Carolina Electric & Gas Company Others Stewart Bailey B. Thompson KMcNamee, Westinghouse John Lehning G. Robertson KKarcher, Progress EnerQV Ervin Geiger K Leonelli C. Moffett Steve Smith W. Stuart Paul Klein Bob Martin
NRC RAI #1 Please identify which reactor coolant loop was used to evaluate the postulated crossover leg break and describe how it was ensured that the break selection maximized the generation of TempMat debris.
SCE&G Response Break selection consists of determining the size and location of the HELBs that produce debris and potentially challenge the performance of the sump strainer.
The break selection methodology for determining the worst case maximum generation of TempMat debris is outlined in the V.C. Summer Debris Generation Analysis.
Since the limiting break location was not known prior to the evaluation, the break selection process evaluated a number of break locations to identify the location that produces the largest quantity of debris and/or the combination of debris types likely to present the greatest challenge to post-accident sump performance. The debris inventory and the transport path were considered when making this determination.
Sections 3.3.4.1 and 4.2.1 of the SER recommend that a sufficient number of breaks bounding variations in debris size, quantity, and type be identified [Ref. 11]. Per the guidance of the SER, the following break locations were considered:
Breaks in the RCS with the largest potential for debris Large breaks with two or more different types of debris Breaks in the most direct path to the sump Large breaks with the largest potential particulate debris to fibrous insulation ratio by weight Breaks that generate a "thin bed" - high particulate with 1/8" fiber bed A comprehensive approach was taken at V.C. Summer for break selection which accounted for the overall placement and target density of TempMat insulation. Specific break locations were selected by modeling the various lOis along the RCS piping and maximiZing the debris generated by those lOis. LBLOCAs were postulated at multiple RCS locations to ensure the most limiting break was evaluated.
All three reactor coolant loops were evaluated and considered in the debris generation process.
Then all three reactor coolant loops were evaluated in the Debris Transport Analysis.
Subsequently, the combination of debris generation and debris transport for each reactor coolant loop was then evaluated and the design basis loads were based on the worst case results.
The Loop "A" reactor coolant loop was used to evaluate the postulated crossover leg break as this loop resulted in the greatest amount of destroyed TempMat (11.75 ft3). The Loop "C" break does result in some smaller amount of destroyed TempMat (8.09 ft\\ but is bounded by the Loop "A" quantity. The total volume of TempMat destroyed for each loop was determined by volume analysis of a CAD model as shown in an example below and in detail in Attachment E of Reference 1. The Debris Generation Analysis also determined that the Loop "B" reactor coolant loop crossover line break does not result in any destroyed TempMat.
Draft 8/17/2009
The SBLOCAs that involve piping located inside the bio-shield walls were evaluated in the Debris Generation Analysis and the small break ZOls are bounded by the LBLOCA results.
Analyzing the Loop "Au crossover break in the Debris Transport Analysis ensures the maximum amount of TempMat debris is evaluated.
Draft 8/17/2009 2
Figure 1-1 CAD Modeling a Spherical ZOI for TempMat Debris Generation Loop A showing a RCS Cross-over Line Break 3.7D & 11.7D (Temp-mat) Zones of Influence Draft 8/17/2009 3
NRC RAI #2 Please identify the insulating materials installed on the reactor vessel. If the material is other than reflective metal insulation, please provide the amount of material damaged by various breaks and size distribution for the damaged insulation.
SCE&G Response The reactor vessel has all Reflective Metal Insulation (RMI). The break location at the Reactor Vessel Cold Leg nozzle presented in Table 5 of the supplemental response letter RC-08-0031 shows the debris generation which includes the Reactor Vessel insulation.
Draft 8/17/2009 4
NRC RAI #3 Please provide the following additional information needed to support the assumption of 10%
erosion of fibrous debris pieces in the containment pool.
- a. Please demonstrate the similarity of the flow conditions (velocity and turbulence), chemical conditions, and fibrous material present in the erosion tests to the analogous conditions applicable to the plant condition.
- b. Please identify the length of the erosion tests and how the results were extrapolated to the sump mission time.
SCE&G Response The ten percent erosion of fibrous debris pieces in the containment pool assumption is based on erosion tests that were performed at generic incipient tumbling velocity metrics. The incipient tumbling velocity is the velocity at which the debris would start moving and this velocity bounds the greatest velocity that a piece of insulation lying in the containment pool would experience without being carried to the sump strainer. Therefore, it is considered the velocity that would produce the most insulation fines that would travel to the sump strainer while the piece of insulation itself would remain stationary in the pool. In the generic testing, the sample flow erosion velocities were not based on V.C. Summer specific pool analysis, but rather the incipient tumbling velocity. If the V.C. Summer containment floor pool velocities do not reach the incipient tumbling velocity, then the erosion that was observed during testing will be bounding. If the pool velocities exceed the incipient tumbling velocity, then the insulation debris will be transported to the sump strainers, and its flow erosion will be irrelevant.
The incipient tumbling velocities that were used to model debris transport in the V.C. Summer Computational Fluid Dynamics (CFD) Analysis were 0.12 tUs for small pieces of TempMat, and 0.90 ft/s for large pieces of TempMat. The Alion generic testing velocities were 0.50 tUs for small pieces of TempMat and 0.90 tUs for large pieces of TempMat. Therefore, the tested small piece TempMat incipient tumbling velocity metric significantly bounded the plant's analyzed value and the tested large piece TempMat incipient tumbling velocity metrics are equal.
Since the testing covered a velocity range four times larger than the modeled plant specific velocity, it is reasonable to assume that any turbulence variations are encompassed sufficiently in the test data taken at the higher velocity. If turbulence is high enough to not allow settling, then the insulation debris will be transported to the sump strainers and its flow erosion is not a factor. The test results from the cases that were performed in different test apparatus for the same duration and sample size, showed no preference for test apparatus despite varying turbulence levels, indicating that turbulence is not a significant contributor to flow erosion.
With respect to chemical conditions, the erosion tests were performed in tap water and not buffered or borated water that would be present in the V.C. Summer containment pool.
However, the lack of containment recirculation chemicals and neutral pH of the tap water would have little effect on the flow erosion mechanism. Tap water lacks containment pool chemicals such as aluminum, boron, or pH buffers.
These chemicals may affect the individual fiber characteristics in a debris clump, but do not affect the flow erosion of individual fibers from the clump. TempMat high density fiberglass does not use a chemical binder like NUKON@ and, therefore, there are no binder associated chemical effects for TempMat.
Draft 8/17/2009 5
The fibrous material tested was NUKON@ low density fiberglass and TempMat high density fiberglass, these materials compare well to V.C. Summer insulation materials listed in the Debris Generation Analysis.
The Debris Generation Analysis indicates that V.C. Summer contains two types of fiberglass that are subject to erosion; TempMat and Kaowool M-board.
The generic erosion testing covered high density fiberglass, TempMat, and low density fiberglass, NUKON. The high density fiberglass resulted in much lower erosion values, all 0.8 percent or less, as compared to the low density fiberglass erosion values, ranged from 1 percent to 18 percent. The low density fiberglass erosion numbers were conservatively applied to all of the V.C. Summer specific types of fiberglass, which only includes high density fiberglass.
The generic testing analysis is based on a mission time of 30 days. However, the V.C. Summer mission time is 40 days.
Although the analysis is based on 30 days, the data can be extrapolated to a 40 day mission time without any additional erosion increase, due to several factors. The generic testing was performed at a number of different durations, up to approximately 30 days and the erosion factor of ten percent was based on the average of all of the small sample erosion values regardless of test duration, so it was not time-based. The generic testing data trends indicate that the large majority of the erosion occurred in the beginning hours of the testing.
Finally, the low density fiberglass value of ten percent was conservatively applied to high density fiberglass TempMat V.C. Summer.
Draft 8/17/2009 6
NRC RAI #4 Please provide the methodology used to calculate the tumbling velocity metrics used for paint chips that are listed in Table 8 of the supplemental response. Please also identify the test data from NUREG/CR-6916 from which the velocity metrics are derived, and justify how the methodology used to derive the calculated velocity metrics accounts for the differences between the paint chips that were tested and the paint chips predicted to be formed under actual post LOCA conditions for the plant.
SCE&G Response The methodology used to calculate the tumbling velocity metrics used for paint chips is located in the Computational Fluid Dynamics calculation (included as Attachment 4-1), which contains an analysis of paint chip transport metrics based on the testing described in NUREG/CR-6916.
The paint chip transport metrics appendix analyzes the raw data from NUREG/CR-6916, to develop a curve fit of the data trend. The specific chip data is then normalized to compare the various chip types with each other and then identify data trends that can be used to interpolate settling velocities for chips with different size and density properties. The resulting transport metrics are listed below.
Debris Type Size Terminal Settling Velocity (ftls)
Minimum TKE Required to Suspend (ft2/sec2)
Flow Velocity Associated with Incipient Tumbling (ftls) 1/8" 6 mil chips (94 Ib/ft3 )
0.15 3.5E-02 1.08 I
Unqualified Epoxy Paint 2" 6 mil chips (94 Ib1ft3) 0.23 7.8E-02 1.76 Chips Curled 1.5" 6 mil chips 0.22 7.2E-02 0.12 (94 Ib/ft3)
Draft 8/17/2009 7
ATTACHMENT 4-1 Paint Tumbling Metrics Calculation 13 Pages Draft 8/17/2009 8
(A>
V.c. Sum mer Reactor Building GSJ-191 CFD Analysis Calculation A L I 0 N Document No: ALION-CAL-SCEG-28I 0-04 I Rev: 5 Page: 5-1 of 5-13 1~11';:,[
A;WO tlU*1.. ~H.":H.T I
APPENIlIX :;
This appendix contains an analysis of paint chip transport mt'lrics based on the testing described in NUREG/CR-69 16. Table 5-1 shows the raw data from NUREGICR-69 16. Note tlwt the settling and tumbling velocity data for curled chips was not included in this table since the ti)l'ces and drag coefficient on a curled chip would be significantly different than for a flat chip.
- l)e.-
I'
. d T II 'i I NURECICR 6916 pamt c liP transport metric :Ita J
Coating Typl' Al kyd (olle coal)
AI kycl (one COal)
Alkyd (one COal)
Zillc-Epoxy (0111.' coat e,l(;h)
Zinc-Epoxy (one cml( eHch)
Epoxy ([wo coan Epoxy (two coat. cured 2 days)
Epoxy (two coat, cured 14 clays)
E[lOxy (two coat)
Epoxy t!wo coat)
Epoxy (six coa11 E~IOXY (six cont. clln~d :2 days)
E[IOXY tsJ.\\ roat, cured I~ days)
E[lOXY (six coa\\i Epoxy Isix coat)
Epoxy (three component)
Epoxy (thme compone1lt, cured
- 2 davs)
E[IOXY (three component. cured 14 daYs)
Epoxy (three wmponent)
Epoxy Itlll\\'e wmponent)
Chip Length (in)
I [02 J/8 to 1/4 11M to 1/32 1/8 [0 1/-1 I/Mw 1/32 I lO2 I to 2 I to2 lIS to 11-1 11M [0 1/32 I to 2 I to :2 1 to2 lIS to 1/4 1164 to 1/32 I w2 I to 2 1 to :2 1/8 to 1/-1 11M 10 1/32 i\\leasurl'd t\\I casII red Hulk Sl'llling Chip Coating Tumhling V ('1 oci I)'
I >Cnsit)*l Thicknl'ss Vclol'ily (fils)
(Ibn/H))
(mill (fils) 0.1)')
2.2 718 0.46 (J08 2.2 7U:\\
0.85
'} ')
0,92 71.8 0.04 0,21 7.l 161. t 1.3~
7.1 161.1 0.26 l.36 8,6 0.22 0.85 111.1 8.3 107.~
0.18 108.6 8.1 0.17 8.6 Ill.!
0.15 1.19 O.I.~
8.6 IlLl 1.01 110.5 0.32 no 1.36
- 2~.3 108.0 0.28 21.9 109.9 0.21 02~
23.0 110.5 l.15 no 110.5 0.16 0.77 25.0 115.5 0.29 LO\\
117.4 0.24 23.4 0.31 23.5 11~.9 1.28 25.0 115.5 0.24 0.98 115.5 0.16 25.0 I The coating densities used in this analysis were taken from the measured coating densities reported in NUREGiCR-6916 with the exception of the alkyd coatings. The density measured for these coatings was 62.4 Ibm/fe. Since this density is the same as water, it it were correct, the chips would be neutrally buoyant. Since the chips are shown to settle, however, the manufacturer density of 71.8 Ibn/If was judged to be a more realistic density.
Draft 8/17/2009 I
9
(j)
V.c. Summer Re.:lctor Bui Iding GS[- 191 CFD Analysis Calculation A L I 0 N Document No: ALlON-CAL-SCEG-28 10-04 I Rev: 5 Page: 5-2 of 5-13 lur,Hl..... u !f.<<hdl'O".
I The forces acting on a given chip as it settles nre the \\veight of the chip. the buoyancy of the chip. and the drag force. The..veight and buoyancy can be directly calculated using the chip size.
thickness, and density. The drag force, however, is,I function both of the chip area and the drag coefficient. Since the orientation of settling paint chips is not stable (i.e. the chips nre free to rotate in uny direction ns they fall). the drag coefficient and the effective drag area are not known. However. the chip data shown in Table 5-1 can be normalized to compare the various chip types with each other and then identify dnta trends that can be used to interpolate settling velocities for chips with different size and density properties. One way to normalize the data would be to calculate the effective weight (weight minus buoyancy) of each chip. Since the effective weigllt is a function of the chip area, this term would implicitly contain all of the physical parameters that affect transport. Note, however, that for the chips shown in Table 5-1.
only the chip thickness and density are directly measured. The chip length varies because a group of chips within a given size range was tested. Therefore, if one were to Ctllculate the chip area by assuming that on average the chips were square. the uncertainty in the area would be significantly greater thnn the uncertainty in the length since the uncertainty in the}ength is being squnred (i.e. a I to 2 inch chip has a length of 1.5 in +/- 33% and an area of 2.25 in- +7SS{-/-56%).
For this reason. the chips were not normalized by calculating the weight, but were instead normalized using the following equation:
x = L* t. (P.Il'!, - P t )
Equation 5-1 where:
x =Normalization parameter L =Average chip length (in) t =Chip thickness Imil)
P,II;" =Chip density (Ibllllft 1
)
PI =Fluid density (Ibll/fr 1
)
It was assumed that the density of the water during the testing was approximalely 62.4 Ibn/ft3.
The normalization parameter is shown for each chip type and size tested in Table 5-2.
Draft 8/17/2009 10
Qi)
V.c. Summer Re:lctor Building GSI-191 CFD Analysis Calculation A L I 0 N Document No: ALION-CAL-SCEG-281 0-04 Rev: 5 Page: 5-3 of 5-13 I
I
~ (I r... r r ",.. r., t, M" ();. () r; ~
T~lble 5 NOfIn;dized paint chip transport metric d:lta Chip Measlired l\\leasUl1'd N()I'I1l<llization Settling Hulk Chip Coating Pa raul('1(')"
Tumhling Cuafing TJpl' Length Thkklll'ss Density lin-mil-VdodtJ
'\\/l'Iodty lin)
(mil)
(Ih,.ln~)
Ihll/UJ )
(fils)
(ft!s)
Al kyd iOlJe coa1l I to :2 2.2 71.8 31.0 0.09 OA6 Alkyd (olle coat)
Jl8 to l/~
') ')
718 3.9 0.08 0.85 Alkyd (one coal) l/6~ to 2.2 71.8 0.5
().O~
0.92 1/32 Zinc-Epuxy (One 1/8 (0 1/4 7.1 16U UtA 0.21 U~
coal e;lCl1)
Zitlc-Epoxy IOfJe l/6~1()
7.1 161.1 16A 0.26 1..\\6 coat e:1cl1) 1/32 EpllXY (two coat) t to :2 8.6 lll.l 628.2 0.22 0.85 Epoxy ((wo coat.
I 102 8.3 107A 56(1.3 0.18 cured 2 days)
Epoxy (two CO;lt.
I 102 8.1 108.6 561.3 0.17 cured 1~ days)
Epoxy (twocu;lll lI8 III l/~
86 Ill. I 78.5 OIS 1.19 Epoxy (1\\\\0 cDat) 1/64 10 8.6 1111 9.8 013 1.01 1/32 Epoxy (SIX CO,ll)
I to:2 2HJ IIO.S 1,6595 0.32 1.16 Epoxy (six coal, I to 2 24.3 108.0 1,662.1 0.28 cured :2 davs)
Epoxy (SIX coat.
1102 2l.9 109.9 1.560A 027 cured [4 days)
Epoxy Isix coal) 1/8 t.O 1/4 23.0 110.5 207.4 0.24 1.15 Epoxy (six cLlal) 1/64 10 23.0 110.5 25.9 0.16 077 1/32 Epoxy (three I to 2 25.0 115.5 1,l)l)1.3 0.29 1.01 component I Epoxy (three COlllpOfl('nl. cured 2 I tLl2 2-'.4 117.4 1.9:10.5
():2~
days)
Epoxy (three component, l'ur(>d I to 2 23.5 114.9 1,850.6 0.:11 I~davsl Epoxy (three 1/8 to 1/4 25.0 115.5 2~(\\.9 0.24 1.28 component)
Epoxy (three 1/64 to 25.0 115.5
- ILl 0.16 0.98 component) 1/32 Figl1l'~ 5-I shows a plot of the settl ing velocity v~rsus th~ normal ization parameter. As shown in this figure. a logarithmic curv~ with the following equation provides a reasonably good fit to the data:
Draft 8/17/2009 11
(,i)
V.c. Summer Reactor Building GSI-191 CFD Analysis Calculation A L I 0 N Document No: ALION-CAL-SCEG-28 10-04 I Rev: 5 I Page: 5-4 of 5-13 H.lt~l.l "ItO rl';'t;,i!H~Hd v, = 0.0274. (nO>' ) +0.065 Equation 5-2 where:
V,= Settling velocity (I'tIS)
X =Normalization parameter =L x t X (PC/HI' - Pr)
L =Average chip length (in)
I =Chip thickness (mil)
Pc"ip =Chip density (Ibn,1ft3) p,= Fluid density (lbm/ft')
Note that the data SC<ltter in this plot is most likely due predominantly to variations in the characteristic length of the chips tested.
Settling Velocity 0.35 0.30 I
- p.
~~
{
m i
0.25 y = 0.0274Ln(x) + 0.065 R2 = 0.6943
~
'u 0.20 o
<Ii
.~ 0,15
~ i l/l 0.10 i
0.05 0.00.1 i
i i
i o
500 1.000 1.500 2,000 2,500 Normalization Patllmeter (in.mil*lbm 11t3)
Figun> 5 Paint chip settling velocity versus normalization parameter Figure 5-2 shows a plot of the bulk tumbling velocity versus the normalization parameter, but does not indicate any clear trend.
Draft 8/17/2009 12
V.c. Summer Reactor Building GSI-191 CFD Analysis Calculation
/1 L I 0 N Document No: ALION-CAL-SCEG-2810-04 I Rev: 5 Page: 5-5 of 5-13
,(....r [
~ 110 1 t r. ~ I ~ rl; <:l.. ~
I Bulk Tumbling Velocity 2.500 2.000 1,500 1.000 500 I
mI iii iii i
ill I
II I
i j
0.20 0.40 0.00 o
- 8 E
~ 0.60
,:,t;
~
~
'0 1.00 o
0> 0.80 c:
1.60
<n 1.20 1.40 Normalization Parameter (in*mil.lb,,!ft3)
Figure 5 Paint chip bulk tumbling velocity versus normalization parameter In order to slidl~ a chip along a floor. the drag and shear forces acting on the chip must exceecllhe friclion force. The Reynolds number can be used in order to determine whether the drag force or she:!r force is dominant since drag force is dominant at high Reynolds numbers and shear force is dominant at 1m\\' Reynolds I\\\\unbers (-I). The folJowing c:l1culations show the minimum alld maximum Reynolds llumbers based on the dala in Table 5-1:
jJfVL Re=--
Equation 5-3 j.J where:
Re =Reynolds number Pr= Fluid density
\\1= Velocity Draft 8/17/2009 13
V.c. Summer Reactor Building GSI-191 CFD Analysis Calculation A L I 0 N Document No: ALJON-CAL-SCEG-28I 0-04 I Rev: 5 I Page: 5-6 of 5-13
'c It.. : r.\\loIO lr{ H"'n*, Q& ~
L =Average chip length
}I =Fluid viscosity
' \\'O.023ill'j' (62,4/h ft' )*(0.77 (IS)'
'II
\\
12inji Equation 5-4 Re min
=120 (2.:HxIO-//~f*s.fr)*(32.2fr s-'/hffilhf )
(62.4/h", ji1HI.36/rs).[ 1..5ill
'J'
\\ 12/11 II,
' 4 Equation 5-5 Re m" =
',' = I.4 x IU (2.34xIO-fbl*s ji")*(32.2.fi s* */b,.fb/)
Shear force is dominant at low Reynolds numbers (-I) and drag force is dominant at high Reynolds numbers. Therefore. since the range of Reynolds numbers are fairly high, it is expected that the drag force is dominant.
The friction and drag forces are defined as shown in the followi ng equations:
F
= c!,' N Equation 5-6 r
N = 111,_. g Equation 5-7 Ill, = A. dll". r. (P,llll' - PI)
Equation 5-8 I
I*J = -::" Cd. Ad.P,. \\.-
Equation 5-9 when::
Ij= Friction force C,,= Coefficient of friction lv' =Normal force III = Effective mass (including the effects of buoyancy)
A,'1111' =Chip area I =Chip thickness pdllj, =Chip density g =gmvity Fd = Drag force Cd =Drag cL)efficient Ad=Projected frontal area associated with the drag coeffici~~l1t Pr = Fluid density r =Fluid velocity Setting the friction and drag forces equal yields the following equation:
Draft 8/17/2009 14
V.c. Summer Reactor Building GSI-191 CFD Analysis Calculation A L 10 N Document No: ALION-CAL-SCEG-28 10-04 I Rev: 5 Page: 5-7 of 5-13 ILI~"l~f
~MD rtCtHUlL_'~L(
I Equation 5-10 Both the coefficient offriction and the drag coefficient in these equ,ltions are unknown. The coefficient of friction between the chips and the floor is reason<lbly judged to be a constant value for aII of the chips. The drag coefficient is also judged to be a constant for chips that are the same size. Solving for these two terms gives the following equation:
Cd 2*.'1,1111'. ( * (P"llIl' - P; I' g Equation 5-J I e'l Ad,p.r,\\,2 Note that the projected frontal area is also somewhat of an unknown. However, since the chips are flat. and sit flat on the floor, the projected area can be reasonably estimated as the characteristic chip length times the chip thickness.
As discllssed previously, calculating the area of the chips based on the average ctHu'acteristic chip length has significant ul1cert'linty. However, in order to estimate the drag/friction coefficient, it will be assumed that the chips are square 011 average with each side having a length equal to the average characteristic length.
Draft 8/17/2009 15
Q;J V.c. Summer Reactor Building GSI-191 CFD Analysis Calculation A L I 0 N Document No: A LlON-CAL-SCEG-28 10-04 I Rev: 5 Page: 5-8 of 5-1."\\
\\<:.11.;;(.(..... 11 n(~hHH_';;~Y I
Table 5 Calculated paint chip drag/friction coeffkient data Chill I\\leasun'c1 J\\Je:lsun*d Bulk Cakulated Chip Coating Tumbling I)raglFl'ict inn Coating Type IA'ngth Thickness IknsH" Vdodt)
CoetTicienl (inl (mil)
(Ihll/rth
( rtlS)
(C,,",cul AI kyJ (Olk~ coat i 1102 2.2 62.4 0.46 3804 Alkyd (Olle coal) 1/8 to 1/4 2.2 62.4 0.85 1.39 Alkyd lone coal) 1/64 hi 1/32
'1 "1 62.4 0.92 (tIS Zinc-Epoxy (OIW COill 1/810 114 7.1 161.1 1.34 1.45 each)
Zinc-Epox y (on" coat I/M 101/32 7.1 161.1 1.36 0.18 each)
Epoxy ((wo coat) 1102 8.6 11 1.1 0.85 19.84 Epoxy (two coat, cured Itu 2 8.3 107.4 2 davs)
Epoxy (lwo CO:H. cured 1102 8.1 lO8.6 14 days)
Epoxy (two coal) 1/8 to 1/4 8.6 II 1.1 1.19 1.27 Epoxy Itwo coal) 1/64 to 1/32 8.6 JIl.l 1.0 I 0.22 Epoxy Isix coat) 1102 23.11 110.5 1.36 7.71 Epoxy Isix,'oat. cured I to 2 24.3 108.0 2 days)
Epox y (six coat, cured I to 2 21.9 109.9 14davs)
Epoxy Isix coat) 1/810 1/4 23,0 110.5 115 1.35 Epoxy (six coat) 1/(-... to 1/32 23.11 110.5 11.77 0.38 Epoxy (three I 10 :2 25.0 115.5 LUI 14.61 component)
Epoxy Ililfee cOIn pone nl. Clll'l'd :2 lto 2
- DA J17.4 lbVSl Epoxy Ilhft'(~
(omponent. cured 14 I 10 2 23.5 114.9 dayS!
Epoxy (three 1/8 to 1/4 25.0 115.5 US 1.14 component)
Epoxy ilhree li64 to 1/32 25.n 115.5 0.98 0.24 component.)
Figure 5-3 shows the calculated bulk tumbling velocity drag/friction coeftlcicnt for each of the paint chips. As shown in Figure 5-4. wht'n the data is plotted on a logarithmic scale. it shows a linear trend.
Draft 8/17/2009 16
(J>
A L ION V.c. Sununer Reactor BuiJding GSI-J91 CFD Analysis Calculation Document No: ALION-CAL-SCEG-281 0-04 I Rev: 5 I Page: 5-9 of 5-13 Calculated Bulk Velocity Drag/Friction Coefficient 10.0
=.
t.l 9.0
~:o
-£.
8.0 E
Q)
'(3
!l:
7.0 Q) 8 6.0
- c 0.=
5.0
() ;t m 4.0 0
"tI 3.0 "5
2.0
()
"is 1.0 "A
0.0 I
I I
I
.1 to 2 Inch
~ 1.'8 to 1.'4 inch 1/64 to 1.'32 inch i
I I I
I I.
I 0
500 1,000 1,500 2.000 2.500 Normalization Parameter (in* mil* Ib,dft3)
Figure 5 Calculated bulk tumbJ ing velocity drag/ftiction coefficient versus nOl1l1alization parameter (linear scale)
Draft 8/17/2009 17
V.c. Summer Reactor Building GSI-191 CFD Analysis Calculation A L I 0 N Document No: ALION-CAL-SCEG-28 10-04 I Rev: 5 I
Page: 5-1 () of 5-J3 lunH_~
~ijll n-:r1.... l..~~1 Calculated Bulk Velocity Drag/Friction Coefficient 10
'J
~
1::
III
'13
- =
8
<)
c 0
'is
'1:
~
15 "tl oS!...
"3
~ 8 0.1 0.01 0.1 10 100 1000 10000 Normalization Parameter (in*mil*lbrn/ff) y = 0.0376x0647 I R2 = 0.6726 Figure 5--+ - Calculated bulk tumbling velocity draglfJiction coefficient versus normalizatioll parameter (logarithmic scale)
Figure 5-4 shows that the re lationship of the drag/fliction coefticient to the normalization parameter can be estimated using the following equation:
Cd /c!, = (HJ376* X()*o~71 Equation 5-12 where:
Cd= Drag coefficient ell =Coefficient of friction X=Normalization parameter =L x t X (Pd'ip - PrJ L =Average chip length (in) t =Chip thickness (mil)
Pchip =Chip density (lbn/ft 1
)
Pi =Fluid density (lbm/f!')
Draft 8/17/2009 18
V.C. Summer Reactor Building GST-19 I CFD Analysis Calculation A L I 0 N Document No: ALlON-CAL-SCEG-28 10-04 I Rev: 5 I Page: 5-11 of 5-13 I Lit.. L I '" ~ 1I 1 r ': i"<" (] ~ -J ~ y RearTanging Equation 5-10 to solve for the tumbling velocity yields the following:
Equation 5-13
\\vhere:
Vr =Tumbling velocity Adll/' =Chip area t =Chip thickness pclri/, =Chip density PI =Fluid density g =gnlvity Ad= Projected frontal area associated with the drag: coefticient Cd= Drag coeft1cient c" =Coefficient of friction This equation can be used along with the drag/friction coefficient calculated by Equation 5-12 to determine the tumbling velocity for plant specific chips.
For (~urled chips, NUREG/CR-6916 shows that the settling velocity is slightly higher inmost cases than for an equivalent flat chip. Therefore. the selliing velocity calculated using Equation 5-2 can be conservatively used for curled chips. Table 5-4 shows the tumbling velocities for the curled chips. Note thnt the calculnted normalization parllmeter in this tllble does not include the characteristic chip length since all of the curled chips tested were the same length:
Eqlllltion 5-14 where:
Xcur/cd =Normalization parameter for curled chips t =Chip thickness (mil) pc/rip =Chip density <Ibll/,ftJ)
PI =Fluid density (lbm/ft')
Draft 8/17/2009 19
(j)
V.c. Slimmer Reactor Building GSI-19l CFD Analysis Calculation A L I 0 N Document No: ALiON-CAL-SCEG-28I 0-04 I Rev: 5 Page: 5-12 of 5-13
~t:.lpnl
"'~!J ![.,r-t.. -tH'*'(,Y I
TLI ale -'\\4 - NonllarIzed curIecI pamt cI'lJp trans )Ort met nc Cata Coating Type Zinc-Epoxy (Olle coat each)
Epoxy (two coat)
Epoxy (SIX coat)
Chil> Ll'ngth (in) l\\leaslIrcd Chip Thickness (mil)
Curled l to 2 7.1 Curled l 102 8.6 Curled l to 2 23.0 l\\h'<\\slJrcd Coating J)ensit v (lb,,/(l\\)
161.1 Ill,l Il 0,5 1'\\ ()I"nullizatinn Bulk I
Parmnl'lcr TlJmhlin~
Vc1ncity (ft/S)
I (mil* lbll/fr',
700.8 0.43 0,27 418.8 0,69 1.1 063 Figure 5-5 shows that tumbling velocity for curled chips versus the normalization parameter is linear and the following equation provides a good fitta the data:
\\/,,'Jrled = 0.00062* X,'uri.,,, = 0.00062, f ' (Pc"'!) - Pf)
EqU:ltion 5-J5 where:
VI.t"u.rled =Tumbling velocity for curled chips (rUs)
XCII/h'd =Normalization parameter for curled chips =t x (Pchip - p/)
t =Chip thickness (mil)
Pchip =Chip density (lbn/ttJ )
Pr= Fluid density (Ibn/fl')
Draft 8/17/2009 20
A L f$J,0 N V.c. Summer Reactor Building GSI-191 CFD Analysis Calculation Document No: ALION-CAL-SCEG-28 10-04 I Rev: 5 I
Page: 5-].3 of 5-13
\\ [ I f.* ~. (... r; It (d":: l,jl,"
Curled Chip Bulk Tumbling Velocity 0.90 0.80 0.70 Q)
~
0.60
'0 o
~ 0.50 Ol
.E:0 0.40 E
- J
~ 0.30
- i ell 0.20 y = 0.00062x
- 0.99860
/
R2 I
/
/
I
/
/
i I
I Y
I I
I I
i i I 0.10 0.00 o
200 400 600 800 1,000 1.200 1.400 Curled Normalization Parameter (mil.lbm'lf)
Figure 5 Curled chip bulk tumbling velocity venms curled chip normalization parameter Draft 8/17/2009 21
NRC RAI #5 Transport testing performed for Unresolved Safety Issue A-43 was used as a basis for the tumbling velocity metrics assumed for small and large pieces of TempMat. Please provide the following information concerning the assumed velocity metrics:
- a. Please identify the specific tests from NUREG/CR-2982 that were used as a basis.
- b. Please identify the sizes of the test debris pieces for which these metrics were derived and justify why they are conservative or prototypical.
SCE&G Response The small piece tumbling velocity metric for TempMat has subsequently been revised to conservatively use the NUKON@ small piece tumbling velocity metric and no longer relies on the use of regularly shaped, scissor cut debris piece data.
The large piece tumbling velocity metric for TempMat is unchanged and justified based on the staff's acceptance of the use of that metric at other utilities for Mineral Wool insulation. Use of the Mineral Wool velocity metric is conservative as Mineral Wool has a lower density than TempMat and a lower density requires a lower tumbling velocity. Reduction of the tumbling velocity metric for TempMat results in a conservatively higher transport fraction.
NUREG/CR-2982 tested three types of fiberglass; including mineral wool, Burlglass (a high density fiberglass approximately 10 Ibs/ft\\ and covered Burlglass. The transport test results for individual large pieces (up to two feet on the side) are summarized as having a velocity range of 0.9 to 1.5 ftlsec. The 0.9 fUsec value was conservatively selected as it is the lowest velocity value of all of the specific large piece tests.
Draft 8/17/2009 22
NRC RAI #6 It was not clear that the testing covered the full range of potential fibrous debris loading for the strainer. Please provide information that shows that the following issues were considered in the evaluation and shows how the issues were bounded by the head loss testing that was conducted.
- a. The surge line break that results in fine Kaowool debris was not tested.
- b. It was not clear that Test 2 included any fibrous debris to represent the TempMat prior to the introduction of the "additional fiber loading."
SCE&G Response to 6a The surge line break that results in fine Kaowool debris is bound by the TempMat fiber quantities developed in the LBLOCA Case 1 scenario. The Debris Generation Analysis justifies the use of a K-Wool size distribution for the Kaowool debris and subsequent calculations have been revised to include the Kaowool size distribution listed in Table 6a-1 below.
6a-1 T emplMtDb'S e rlS ource T Case 1 LBLOCA T bl a
e a
erm -
Large Pieces Amount Intact Destroyed Blankets 4.0 fe 11.75fe (34%)
Large Pieces Amount Intact Destroyed Blankets oft3 1.48 fe (0%)
0.13 ft3 0.34 ft3 (39%)
Exposed Blankets 3.76 fe (32%)
Small Pieces 3.17 fe (27%)
I Db' S T bl a e 6a-2: Kaowoo e rlS ource Term-Exposed Blankets oft3 (0%)
0.13 ft3 (37%)
Small Pieces 1.18 (80%)
fe 0.06 (19%)
ft3 Fines Amount Density Size 0.82 (7%)
fe 162lbm/fe 2.95 ft.
E-05 14" Pressurlzer S urge L'me Break Fines Amount 0.30 ft3 (20%)
0.02 ft3 (5%)
Density Size 160lbm/fe 2.95 ft.
E-05 1601bm/ft3 2.95 ft.
E-05 This size distribution applied to the break that destroys Kaowool is bound by the quantity of fiber generated in the loop break Case 1 scenario.
SCE&G Response to 6b Test 2 did not include TempMat as a part of the design basis debris loading. The design basis debris loading for Test 2 was an all particulate case (all coatings assumed to fail as particulate) for a break location that generates Marinite XL debris.
There are no break locations that generate both TempMat debris and Marinite XL debris.
The debris load cases for the Marinite XL are presented on Tables 11 and 12 in the SCE&G supplemental response letter RC-08-0031.
The debris loading assumes 100% transport of the Marinite XL as particulate and fiber. The total Marinite XL debris is 8.58 fe. Test 2 used an equivalent loading of 30.2 ft3 of Marinite XL based This is 3.5 times the design Marinite XL loading.
on an early debris generation evaluation.
Draft 8/17/2009 23
After the design basis debris loading test was complete, Test 2 was continued to evaluate the onset of thin bed formation. Additional fiber was added in the form of TempMat as a means of demonstrating that the design basis fiber loading at V.C. Summer is below thin bed.
The TempMat was added in equivalent 1/16" theoretical bed thickness.
The test is based on a surface area of 2229 ft2, so each TempMat fiber addition is equivalent to 11.6 ft3.
This is compared to conservative TempMat fiber load of 1.47 ft3 as detailed in response to RAI #5a.
The second TempMat addition was again an equivalent 1/16" load. The total fiber loads are summarized below.
Design Design Test After First After Second Value Value TempMat TempMat Latent 16 Ibs 16 Ibs 161bs 161bs Marinite XL 19.81bs 69.51bs 69.5 Ibs 69.5 Ibs TempMat Olbs Olbs 136.91bs 273.81bs Total Fiber 35.8 Ibs 85.5 Ibs Notes: TempMat bulk density is 11.8 Ib/ft3 222.4 Ibs 359.3 Ibs (11.8 x 11.6 = 136.9 Ibs)
Marinite Density is 46 Ib 1ft3 (46 x 8.58 = 395 Ibs)
(46 x 30.2 = 13891bs)
Marinite XL is 5% fiber by mass (395 Ibs x 5% = 19.8 Ibs)
Marinite I used in test is 5%* fiber by mass (1389 x 5% = 69.5 Ibs)
- confirmation of 5% or more fiber in Marinite I test material is planned The only conclusions that may be drawn from the TempMat additions is that V.C. Summer strainer design is well below the onset of thin bed formation. The Templ\\l1at additions were significantly greater than the design condition. Total design basis fiber loading is approximately 36 Ibs. The total fiber added during the test was approximately 360 Ibs. The increase in head loss following the TempMat additions is based on the significant increase in fiber loading and approach to thin bed. The test does not indicate a different bed formation when TempMat is added. It indicates an order of magnitude increase in fiber loading results in approach to thin bed.
As discussed during several teleconferences between SCE&G and the NRC, the testing for V.C.
Summer is based on the design limiting Marinite XL loading. The Marinite XL loading case is limiting based on the following points.
- 1. The total mass of fiber in the Marinite XL debris loading case is greater than TempMat.
The limiting break for Marinite XL conservatively results in 8.58 ft3 of debris at the sump strainer location. The density of Marinite is 46 Ib/ft3with 5% fiber content by mass. The total Marinite XL fiber loading is 19.8 Ibs. Total latent debris fiber loading is 16 Ibs for a total of 35.8 Ibs. This could be for either the A strainer or B strainer. Since the strainer surface areas are different, loading for the TempMat cases are strainer specific.
A summary of the loading is as follows.
Draft 8/17/2009 24
Marinite XL Strainer B TempMat Strainer A Case TempMat Strainer B Case Test 2 Particulate Test 3 Paint Chip Latent Fiber 16 Ibs 161bs 161bs 161bs 161bs Marinite XL Fiber 19.81bs oIbs oIbs 69.51bs 19.81bs TempMat Fiber (vol) oftJ 2.33 ftJ 1.47 ft3 oft3 oft3 TempMat Fiber (mass) oIbs 27.451bs 16.781bs Olbs Olbs Total Fiber 35.81bs 43.451bs 32.781bs 85.51bs 35.81bs Strainer Surface Area 2379 ft£ 2939 ft2 2379 ft2 2379 ft2 2379 ft2 Sacrificial Area 150 ft2 150 ft2 150 ftz 150 ftz 150 ft2 Total Area Available 2229 ft2 2789 ft2 2229 ft2 2229 ft2 2229 ftz Fiber Loading 0.0161 Ib/ft2 0.01561b/ft2 0.01471b/ft2 0.0384 Ib/ftz 0.0161 Ib/ftz Flow Rate 7500 gpm 7600 gpm 7500 gpm 7500 Qpm 7500 gpm Velocity 0.0075ft1sec 0.0061 ftlsec 0.0075ft1sec 0.0075ft1sec 0.0075ft1sec The fiber loading for the Marinite XL (0.0161 Ib/ft2) is limiting for all cases. Additional margin for the Strainer A case is provided in the lower approach velocity at the strainer surface due to the large size of Strainer A.
- 2. The TempMat fiber diameter is given as 9 microns in NEI 04-07. The Scanning Electron Microscope (SEM) completed on the Marinite I powder used in the actual test determined a fiber diameter of 8.5 microns (Ref AECL report V. C. Summer-34325-TN 001).
Based on NUREG/CR-6224 correlations, smaller diameter fibers yield a higher head loss when forming a debris bed.
The Marinite I fibers used in the testing are limiting in terms of head loss.
- 3. The Marinite XL fiber length was questioned by the NRC during the July 27, 2009 teleconference. The average fiber length in the Marinite I test powder was determined to be 37 microns.
No specific concerns with regard to fiber length could be found in industry or regulatory documents. Any concerns regarding short fibers bypassing the strainer are addressed by the bypass testing completed. As further detailed in response to RAI #11, the maximum bypass was 1.4% early in Test 2. All other bypass measurements were less than 1% and decreased with time indicating the Marinite I fibers must be part of the debris bed on the strainer surface. The length of the Marinite I fibers used in the test does not adversely affect the tests.
- 4. The SEM photos provided with response to RAI #12 clearly show fiber release from the Marinite I particulate. There is no concern the fibers were not available to form a debris bed.
Draft 8/17/2009 25
Based on review of relevant data and technical resources, the Marinite XL design basis case is the limiting head loss case for the sump strainers and the Marinite I powder used in the tests bound the TempMat debris loading cases.
Draft 8/17/2009 26
NRC RAI #7 The licensee did not verify that the fibrous debris that was added to the testing was prepared sufficiently finely. Because most fibrous debris for this plant is latent, and the majority of the other fibrous debris that transports is fine, almost all fibers should have been individual or easily suspendable. The use of fibrous shreds for the Summer test cases could prevent the potential formation of a thin bed because sufficient fines would not be available to cover the strainer.
Because the fibrous debris predicted to arrive at the strainer is a relatively small amount and it is added directly on top of the strainer, the results of the test are likely strongly dependent upon the preparation and introduction of the debris. Please provide information that shows that the size distribution of debris in each test matches the debris size predicted to reach the strainer by the transport calculation for that case.
Alternately verify that the debris was prepared conservatively fine.
SCE&G Response Three large-scale strainer tests were performed by AECL using debris loads specified by SCE&G. In Tests 1 and 2, PCI Nukon and TemplV1at fiberglass were used; in Test 3, only PCI Nukon was used to simulate latent fiber. The procured fibrous insulations were cut into pieces of approximately 6 inches by 6 inches. A leaf shredder was used to break down the debris further. The fibrous debris weighed out for testing is shown in Figure 7-1 and Figure 7-2. As can be seen from these photos, the fibrous debris became small and fluffy after shredding.
The measured fibrous debris was added into a plastic tub and wetted with water. A water jet from a pressure washer was used to separate the fibers.
Particulate debris for each batch addition was also added into the tub and mixed with fibrous debris by using a water jet (approximately 2000 psi) and a rake. The debris mixture was then added from the tub to the test tank through a submerged sludge pump, shown in Figure 7-3. It was almost impossible to add large fibrous shreds into the test tank through the pump. As shown in Figure 7-4, after being pumped into the test tank, the fibers had become separated into individual filaments. Any floating debris was skimmed out into a bucket and added into the test tank again.
The debris preparation method was the same as in the Dominion chemical effects tests, which was approved by the NRC during a field trip to AECL in May 2008. The debris preparation and addition to the test tank were conservative as compared to the plant situation.
Another source of fibrous debris that could contribute to the debris bed head loss is the Marinite I debris addition. As explained in for RAI 12, the Marinite I powder contains fiber. SEM analysis performed by AECL indicated that fiber release from Marinite I powder had an average diameter of 8.5 microns and an average length of 37 microns. Marinate I debris was added in Tests 2 and 3. Prior to the debris addition, Marinite I powder was mixed with fibrous debris in a plastic hub.
The mixture was then pressure washed and pumped to the test tank.
The debris preparation process adopted by AECL ensured that fibrous debris was separated into single fines.
Thin debris bed photos shown in Figure 7-5 and Figure 7-6 supported the above statements.
Draft 8/17/2009 27
Figure 7-1 Fibrous Debris Used in V.C. Summer Tests 1 and 2 [4]
Figure 7-2 Fibrous Debris Used in V.C. Summer Test 3 [5]
Fjgure 7-3 Debris Mixture Being Pumped from the Tub to the Test Tank Draft 8/17/2009 28
Figure 7-4 Fibers Being Separated into Individual Filament Draft 8/17/2009 29
Figure 7-5 Thin Debris Bed Formed in V.C. Summer Test 2 Figure 7-6 Thin Debris Bed Formed in V.C. Summer Test 3 Draft 8/17/2009 30
NRC RAI #8 It was not clear that the debris was diluted sufficiently to prevent agglomeration of debris during testing. Please provide information that shows that non-conservative agglomeration of debris did not occur during testing.
SCE&G Response For debris preparation, the fiber batts were cut into pieces of approximately 6 in. by 6 in. The pieces of fiber were further broken into smaller pieces using a leaf shredder. Particulate debris, including walnut shell flour and Marinite I powder, were procured in powder form. SEM analysis indicated that Marinite I powder had an average particle size less than 10 IJm.
The measured fibrous and particulate debris were mixed in a plastic tub. A high-pressure water jet (approximately 2000 psi) was used to separate fiber shreds and thoroughly mix the debris.
The slurry of mixed debris was then pumped from the plastic tub to the test tank. The gratings of the submerged pump prevented any large pieces from being added to the tank.
Figure 8-1 shows a technologist agitating the debris slurry in the plastic tub using a rake while the submerged pump was turned on. Debris was sufficiently diluted and finely separated before it was pumped into the test tank.
Debris bed photo shown in Figure 7-6 also indicated that debris agglomeration did not happen during the testing.
By strictly following the debris preparation procedure developed for the V.C. Summer tests, debris agglomeration was prevented in all stages of the testing.
Draft 8/17/2009 31
Figure 8-1 Debris Slurry Prepared in a Plastic Tub Figure 8-2 Thin Debris Bed Formed in V.C. Summer Test 3 32 Draft 8/17/2009
NRC RAJ #9 The supplemental response stated that the test results were viscosity corrected based on the decrease of water viscosity with increasing temperature. The presence of bore holes or lack of a continuous bed could result in turbulent flow conditions across at least part of the strainer that would invalidate the use of a straight viscosity correction for head loss. Please state whether flow sweeps were conducted to ensure that bore holes or other pressure driven phenomenon did not occur during testing. Provide the results of the flow sweeps. Provide the methodology used for the viscosity correction. If flow sweeps were not conducted, justify the method used to perform the viscosity correction.
SCE&G Response Flow sweeps were not conducted for V. C. Summer large-scale tests. At the time these tests were performed (from September 2006 to July 2007), the information that the NRC would accept, head loss behaving linearly with a change in flow rate as a demonstration of lack of boreholes, was not available. Instead, a defensive method was used. After the test, debris bed on each fin was carefully checked and photos were taken to demonstrate that the debris bed was complete and boreholes did not exist.
After Test 3, photos of debris bed that indicating possible boreholes were carefully examined as shown in Figure 9-1 and Figure 9-2.
Figure 9-1 Spider Web Features between the Corrugations 33 Draft 8/17/2009
Figure 9-2 Spider Web with hole in top valley.
Draft 8/17/2009 34
Close-up photos indicate that those apparent holes did not extend through the debris bed, only through the fluffy "web" joining adjacent corrugations as shown in Figure 9-3 and Figure 9-4.
Figure 9-3 Blow-up of the Spider Web in Upper Valley.
Draft 8/17/2009 35
Figure 9-4 Close-up of Another Similar Feature.
Note in Figure 9-4 that the bottom of the hole in the spider web stops at the top of the main part of the debris bed. Paint chips are white and the gray is due to the zinc powder. (The yellow tinge is due to the overhead lighting.)
In addition, the fact that the head loss vs. time plot for Test 3 did not exhibit sudden drops in pressure also indicated that there were no boreholes, because if boreholes were forming, then sudden drops in pressure would accompany the formation of such holes.
The total test module surface area was 357 ft2. With a test flow rate of 1201 gpm, the flow approach velocity to the test module was calculated to be 0.0075 ftls.
Under the test temperature (104°F) and flow condition, the Reynolds Number of the flow was below 5. Hence, we would expect laminar flow. Referring to NUREG/CR-6224, for laminar flow, the debris bed head loss is proportional to fluid viscosity.
Draft 8/17/2009 36
NRC RAI #10 The basis for combining the head loss results for one paint chip addition (from test 3) with the results of the head loss from the fiber and particulate case (test 2) was not clear.
If it is anticipated that paint chips will transport to the strainer, thereby reducing the effective area for debris to collect, the chips should be added to the limiting case. A simple addition of the results may not produce a conservative result. Please provide a justification for combining the two test results instead of performing an integrated test.
SCE&G Response Test 2 was run to bound the sump strainer head loss with an all particulate debris load (all coatings assumed to fail as particulate). The test used a Marinite XL debris load of 30.2 fe, which has based on the original analysis for the initial GL 2004-02 response in September 2004.
Test 3 was run with the refined design basis Marinite XL debris load of 8.58 fe, but with an excess of paint chips (3436 ff compared with a 747 fe design load). The use of the Test 3 total head loss was overly conservative with 4.5 times the design basis paint chips used. Therefore, a combination of the Test 2 and Test 3 results was developed to define an appropriately conservative design basis head loss for the sump strainer.
Based on several teleconferences, the NRC suggested that the head loss be based on a single bounding test. To that ends the head loss will be based on Test 3 with paint chips. Table 10-1 presents the measured pressure drop after each debris addition.
Table 10-1 Test 3 Pressure Drop During Debris Addition Debris Addition kPa psi Clean 0.13 0.02 1/3 Fiber/Particulate 0.31 0.05 1/3 Chips 0.68 0.10 1/3 Fiber/Particulate 6.33 0.92 1/3 Chips 10.02 1.45 1/3 Fiber/Particulate 21.73 3.15 1/3 Chips (peak) 27.35 3.97 Stabilized final 23.92 3.47 The design head loss for the strainer was chosen as the pressure drop after the third fiber addition, but before the third (and final) paint chips addition. The pressure drop was measured at 3.15 psi at 104°F test conditions.
The 3.15 psi is bounding based on the following points.
- 1. The entire fiber and particulate load is included in the test.
This includes both the Marinite I and latent fiber.
Marinite I (test material) fiber content is planned to be confirmed to meet or bound the 5% fiber content of Marinite XL (actually installed).
Draft 8/17/2009 37
- 2. The paint chip loading is 1145.3 fe x 2 = 2290.6 fe. This is approximately 3 times the analysis paint chip loading of 747 fe. Comparing the particulate test (Test 2) and the paint chip test (Test 3) the significant impact of increasing paint chip loading is clearly established. The excess paint chip load provides a significant margin in the test results.
An additional concern is the termination criteria for the test. The mission time for the V.C.
Summer GSI-191 resolution has been established at 40-days based on the Environmental Qualification temperature restraints. Since strainer tests are not run for the full mission time, the concern is that pressure drop may increase over time. Acceptable means of qualifying a test run have been an equivalent number of turnovers or demonstrate that the head loss is stable or decreasing.
The stable or decreasing head loss can be demonstrated for Test 3 after the final paint chip addition as discussed in response to RAI #13. The peak pressure drop is clearly conservative for Test 3.
Using the intermediate test data point from Test 3 does not allow for this type of analysis. The following arguments are provided for the 3.15 psi being a conservative limiting head loss that bounds the expected debris loads.
- 1. The evaluation of the head loss after the third paint chip addition shows the debris bed was formed and stable (RAI #13).
The paint chips block additional screen surface, increasing head loss across the strainer. There are no changes to the fiber bed. If the fiber bed was formed and stable after the last paint chip addition, then the fiber bed was formed and sable before the last paint chip addition.
- 2. Head loss stabilized at 3.47 psi from a peak of 3.97 psi after the last paint chip addition.
This means the stable head loss with an additional paint chip load is only 0.32 psi greater than 3.15 psi being used.
- 3. Table 10-2 provides a comparison of Test 2 (no paint chips) and the Design Case with 747 ft2 of paint chips. The NRC SE on the GSI-191 methodology approved a value of 75% blockage of the strainer surface for debris (tape, placards, signage, etc..). Applying that same 75% to the paint chips would reduce the free strainer surface area to 1668.75 ft2 for the design case. With a known fiber load and surface area, the fiber loading per square foot of strainer is calculated. Test 2 has a higher fiber loading than the design case. Figure 10-1 shows the pressure drop plot for Test 2. The pressure drop increases linearly with each debris addition. This indicates head loss varies linearly with fiber load within the debris loading margins at V.C. Summer. The head loss for the Design Case may be estimated by a simple ratio based on fiber load.
Design Case Pressure Drop
= 1.92 psi x (0.021414/0.03834)
= 1.07 psi The blockage of the screen by paint chips also increases the velocity of flow through the strainer. The velocity increase will increase pressure drop. The strainer design is within the laminar flow region with a Reynold's Number of 5. This means that pressure drop will vary linearly with velocity. The pressure drop for the Design Case is then Design Case Pressure Drop (Linear) = 1.07 psi x (0.01001 0.00750)
= 1.43 psi Draft 8/17/2009 38
If the strainer flow rates were in the turbulent flow regime, the pressure drop would vary with the square of velocity.
Since velocity is increasing, this is a more conservative approach.
Design Case Pressure Drop (Square) = 1.07 psi x (0.01001 0.00750)2
=1.91 psi This analytical approach is based on approved methods and test data. This assessment further confirms that the use of 3.15 psi for the pressure drop conservatively bounds expected strainer performance in a post-LOCA event.
Table 10-2 Comparison of Test Fiber Loading Test 2 Design Case Strainer Surface Area 2379 fe 2379 fe Sacrificial Area 150 ff 150 ff I
Free Strainer Surface Area ft2 Paint Chip Area 2229 fe 2229 ft2 ft2 Percent Blockage 0
747 75%
75%
Sacrificial Area for ft2 ft2 0
Paint Chips 560.25 Total Strainer Free ft2 ft2 2229 Surface Area 1668.75 16 Ib Maritie Volume Latent fiber 16 Ib 30.2 Ib 8.58 Ib Marinite Density 46 Ib Marinite lVIass 46 Iblfe 1389.2 Ib 394.68 Iblfe
% Fiiber in Marinite 5%
Ib Marinite Fiber 5%
19.734 Ib Total Fiber 69.46 Ib 35.734 Ib 85.46 Ib 0.021414 Iblft2 Pressure Drop 0.03834 Iblfe Fiber Loading 1.92 psi 7500 gpm 7500 gpm Flow Rate Flow Rate (1) 16.71 ft 3/sec 16.71 ft 3/sec Approach Velocity 0.00750 ftlsec 0.01001 ftlsec Draft 8/17/2009 39
Figure 10-1 Pressure Drop for Test 2 - All Particulate Case
'JJ
- J SJ
~
7J
<\\l 2..
&J t
Q.
E...
<\\l 5,:J
~
1~1
'J
....:lcllloo J
Test VCS-2
-~---.-.-,-------i---T
-:------Ti**
I I
Flow rate I
I I
~ -
I
\\
~ -
~ - it
~~.~~~~~~\\~ ---- ~t_ -- ---=ri'"~." ---~"--+=~
I I
I I
I U
I I
PDT-2 I
I I
I I
I I
"Tni!C I:
:-------¥~N~(~;~:,~f_'t---r '\\'r--------:---MrJl:"'**:r~
I "I]' l
,..,'A
"".A.A,,"./.~
I I
~
teL. j
- -~, ------ f...rrr-** cu-'.,...., - - -- -"~-I - -,- -7U4\\!#-*\\--r";1~.,.
I I
. Ij b.'/~'-; ',.. \\. I ~"j
~#""i~ J?l;1 I
I J
l' V'f~ \\
"\\
I I
I I
I
- 1 I
- - - - - - --------+--------- -i - - i- - - - - - - - -----+--.;.
-i ~-
- )
PDT-l:
-...- __JL---~.l.--~_._,.,._-l L...--......--~
J 1
I
~
I I
I I
Seca'lj t
I' I
I I
- l:iliM_ I 1
I I
Flo'HRate FT-1 I
- - - ~ - - - - - - _1- __*....
L
.J - - -
L __
i T'
I I**** T.empe'at"re TE-1 I I
,ewpeI;W.a-e I
I
_____ ~7'.rl~
-'--i-1-
~ ___
Head LOSS POT-1 ~ __
c" J
I I
I
.....- Head '"-ass POT-2 I
__ ~l
~
-1:-
~-------- ~
~--
/
I I
I I
I I
/
I I
I I
I I
I I
I I
I I
ro
~
- 'C.
'c
t-----...s.,t-------t-------t------t-------t---'-J t'3.'Ct1t6 1'S'lE
\\
nllle (standard)
Draft 8/17/2009 40
The increase is design pressure from 2.72 psi in the Supplement Response to 3.15 psi at 104°F has been incorporated into the Net Positive Suction Head (NPSH) calculations for both the RHR Pumps and the Reactor Building Spray Pumps. This is included in the response to RAI #16.
The evaluation of flashing is based on the submergence of the strainer fin, pressure inside the reactor building, vapor pressure of the sump water and the pressure drop across the sump strainer.
The vapor pressure and pressure drop are both temperature dependent.
If the pressure inside the strainer falls below the vapor pressure, then flashing would occur.
Ps = PRB - LlPT+ Z X (PT /144 in2/ff)
Where Ps is the pressure inside the strainer (psia)
PRB is the reactor building pressure (psia)
LlPT is the pressure drop at Temperature (T) of interest (psi)
Z is the submergence (ft)
PT is the water density at Temperature (T) of interest (Ib/ft3)
If the water vapor pressure equals the reactor building pressure, this reduces to a comparison between submergence and pressure drop.
The Reactor Building saturation temperature is based on initial Reactor Building conditions established by Technical Specification 3.6.1.4 which limits pressure to -0.1 and +1.5 psig.
Therefore, a saturation temperature of 212°F was evaluated for flashing. No credit is taken for subcooling at or above this temperature.
Subcooling is credited for lower temperatures.
Several sump temperatures were evaluated to confirm the limiting temperature was selected.
The strainer pressure drop was adjusted to the appropriate temperature based on water viscosity.
Temperature Strainer Pressure Drop Level I\\/Iargin 70°F 4.72 psi 25.5 ft 104°F 3.15 psi 27.6 ft 130°F 2.46 psi 26.7 ft 212°F 1.37 psi 0.3 ft The design basis strainer head loss is also within the strainer design allowable pressure drop of 6.5 psid. Therefore, the design strainer head loss of 3.15 psid at 104°F is acceptable for system operation.
Draft 8/17/2009 41
NRC RAI #11 The section of the supplemental response that describes bypass fraction testing states that samples for bypass fraction were taken for all three tests at 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> intervals. The supplemental response also states that the quantity of fiber bypass decreased exponentially over time. It is not clear when the first grab sample was taken. It also appears that more frequent sampling near the beginning of the test may be appropriate. Please provide the schedule upon which samples were taken. Considering that the bypass decreases exponentially with time, provide the methodology used to determine the total bypass.
SCE&G Response Test 1 was a RMI blockage test.
The first batch of debris addition started at 1415 h, September 6, 2006 and the last batch of debris addition finished at 1736 h, three hours later.
The first bypass sample was taken at 1800 h. A total of 11 bypass samples were taken at 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> intervals. Test 1 will not be discussed further since it included large amounts of Reflective Metal Insulation (RI\\I1I) debris. The bypass fraction was substantially lower and not applicable to the V.C. Summer final strainer design basis.
Test 2 was a thin bed test. The first batch of latent fiber and particulate mixture addition started at 1940 h I Oct 3, 2006. A total of 7 batches were added to the test during a period of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.
Following these 7 batches, a second and then third addition consisting of TempMat fiber only was added to the test at 2219 h, Oct 3 and 1300 h, Oct 4, 2006 respectively. These TempMat additions were beyond the strainer design basis and were not included in the bypass sampling.
The first bypass sample (Sample 2) was taken at 2135 h after the latent fiber and Marinite I were added to the test.
Bypass sampling for Test 3 started after completion of the fiber/particulate and paint chips additions and continued until the test was terminated. A detailed bypass sample schedule for all three tests is listed in Table 11-1.
Draft 8/17/2009 42
Table 11-1 V.C. Summer Large-Scale Strainer Tests Bypass Sample Schedule Sample Time Test 1 Test 2 Test 3 1
2006 Sep. 26 1800 h Test clean water sample 2007 Jul. 24 1700 h 2
2000 h 2006 Oct. 3 2135 h 1900 h 3
2200 h 2335 h 2100 h 4
2400 h 2006 Oct. 4 0135 h 2300 h 5
2006 Sep. 27 0200 h 0335 h 2007 Jul. 25 0100 h 6
0400 h 0535 h 0300 h 7
0600 h 0735 h 0500 h 8
0800 h 1325 h 0700 h 9
1000 h
/
/
10 1200 h
/
/
11 1400 h
/
/
For Test 2, fiber bypass was measured via SEM analysis of Samples 2, 3, 5, 7 and 8 (see Table 11-1). Individual fiber lengths were measured from SEM micrographs of filtered portions of these samples. Most of the fibers (90%) were less than 0.039 in. (1.0 mm) in length. The volumes and masses of fiber bypass were calculated from the measured fiber lengths. Fiber concentrations calculated in this fashion are plotted versus time in Figure 11-1. The greatest observed fiber bypass of 5.3 mg/L from Sample 2 corresponds to a bypass fraction of 1.4%).
This assumes a minimum Marinite I fiber content of 4% by mass. The quantity of fiber bypass decreased over time. An exponential least-squares trend line fits the measurements reasonably well. From the curve equation, the maximum fiber concentration of 3.5 mg/L was obtained by setting the time to zero.
For Test 3, the first bypass sample was taken at 1700 h, 2007 July 24.
Fiber bypass was measured via SEM analysis of Samples 1, 2, 4, 6 and 8 (see Table 11-1).
Individual fiber lengths were measured from SEM micrographs of filtered portions of these samples. Most of the fibers (95%) were less than 0.039 in. (1.0 mm) in length. The volumes and masses of fiber bypass were calculated from the measured fiber lengths. The calculated fiber concentrations Draft 8/17/2009 43
are plotted versus time in Figure 11-2Figure. The greatest observed fiber bypass of 0.7 mg/L from Sample 1 corresponds to a bypass fraction of 0.42%.. This assumes a minimum Marinite I fiber content of 4% by mass. The quantity of fiber bypass decreased over time. An exponential least-squares trend line fits the measurements reasonably well. From the curve equation, the maximum fiber concentration of 0.42 mg/L was obtained by setting the time to zero.
Bypass testing started just after the design basis debris additions were completed.
The samples were then repeated at two hours intervals.
The sampling showed a consistent exponential decline in bypass for both tests. The peak bypass was calculated to be 1.4%. This is 3 times higher than other samples.
As stated in the Supplemental Response, the fiber bypass fraction for downstream effects is set at 5% to bound the test data.
The 5% bypass will be used for the incore downstream effects when WCAP-16793-f\\lP is approved. Fiber bypass plays a negligible role in component and piping downstream effects when compared to the particulate loading which assumes 100% bypass.
Draft 8/17/2009 44
VCS-2 -- Thin Bed Test 5
VCS-2 Exponential Best Fit 2"4 Cl E-c: o
~
'E 3 a> u c: o y = 3.522e-O.1725x U
L a>
R2 = 0.8721
,g 2
- u.
1 O+-------,---------,----------.----------j o
4 8
12 16 Time (h) (from 2006 Oct. 3 @ 21 :35 h)
Figure 11-1 Fiber Concentration vs Time - Test V.C. Summer-2 Draft 8/17/2009 45
0.800 Test 3
-- Paint Chip Test I
Exponential Best Fit I 0.600
- J'-
tn E-c:
y= 0.4152e-00338x 0
~
R2 = 0.3796 l'J....... 0.400 c:
(J)
(.)
c:
0 0...
(J)
.0
- u.
0.200 0.000 +1----,-----,------,-------,--------,----
a 5
10 15 20 25 30 Time (h) (from 2007 Jul. 24 @ 15: 19 h)
Figure 11-2 Fiber Concentration vs Time - Test V.C. Summer-3 Draft 8/17/2009 46
NRC RAI #12 It was not clear that the properties of Marinite sawdust were equivalent to the predicted crushed Marinite.
Please provide a justification for the use of Marinite sawdust instead of crushed Marinite.
SCE&G Response The Marinite I debris used in the V.C. Summer tests was procured in the powder form as shown in Figure 12-1 The Marinite powder is sander dust collected from sanding Marinite boards with 53" wide, fiberglass reinforced sand paper belts imbedded with 24 to 50 grit silicon carbide particles. The Marinite I powder contains 4% to 16% fiber by mass according to manufacturer's Material Safety Data Sheet (MSDS).
A sample of Marinite I powder was analyzed using SEM. The following SEM photos (Figure 12 2 and Figure 7) clearly show that Marinite I debris used in the tests is a very fine powder and that the majority of the particles are less than 10 ~m. Also fiber release is clearly showed in the photos.
SEM analysis performed by AECL indicated that fiber release from Marinite I powder had an average diameter of 8.5 microns and an average length of 37 microns. The number of SEM samples was limited to confirm fiber release and size. An additional effort is planned to be under taken to increase the sampling size so that actual fiber content (mass fraction) of the test material can be quantified. Marinite XL (installed at V.C. Summer) has a manufacturer's fiber content of 5%. Given the Marinite I fiber content range of 4% to 16% there is a high level of confidence that 5% is met or exceeded. Any fiber content above 5% provides additional margin in the test results.
Draft 8/17/2009 47
Figure 12-1 Marinite I Powder Used in V.C. Summer Tests Draft 8/17/2009 48
e) X 500 f) X 500 Figure 12-2 SEM Photos of Marinite Powder Fiber Release Draft 8/17/2009 49
b) X 500 e) X 3,000 Figure 7 SEM Photos of Marinite Powder Particle Size Draft 8/17/2009 50
NRC RAI #13 It was not stated that the test results were extrapolated to the strainer mission time. Results were not provided in a format that showed that the head loss was steady or decreasing at test termination. Please provide any extrapolation of test results to the mission time. If the results were not extrapolated provide a justification for the lack of extrapolation. Provide head loss graphs for tests 2 and 3 showing debris additions, test termination, and noting other significant events during the tests.
SCE&G Response For Test 2, the design basis debris load of latent fiber and particulate debris was added in seven increments starting at approximately 1940 h on October 3, 2006 and continuing over a 2-h period. The head loss increased linearly, stopping when the addition of the last increment was completed as shown in Figure 13-1. The head loss remained stable at 1.9 psid (13 kPa) for 42 min after the addition of the last increment was completed. The test stability criterion was 36 min. (12 turnovers). The next two additions (TempMat debris only) were beyond the latent fiber load and were only intended to determine the maximum fiber accommodation of the sump strainer (i.e. approach to thin bed formation).
As shown in Figure 13-2, the best-fit curve of head loss after the first addition has a negative slope, which means head loss was in a decreasing trend.
For Test 3, as shown in Figure 13-3, after the debris addition, head loss quickly peaked at 3.97 psi (27 kPa). After reaching the peak value, head loss was in a decreasing trend even though two tank floor sweeps were performed. Figure 13-4 shows the best-fit trend of head loss curve has a negative slope, which indicates that the head loss was decreasing.
In both Tests 2 and 3, since the peak head loss was used for strainer performance evaluation and the best-fit head loss trend had a negative slope, there was no need to run the test for the whole mission time.
Draft 8/17/2009 51
Test VCS-2
'DO 90 Flow rate 70 60 SO PDT-2 Third 50
~
70
~
E E 60 Addition Ii CI> c.
40 a.
E
~
III
~
III 50
.2 "0...
3D
~
CI>
~
40 J:
0::
Second Flow Rate FT-1 Addition
~
0 3D u::
Temperature TE-1 20 Temperature Head Loss PDT-1 20
,- Head Loss PDT-2 10 First 10 Addition 0 +---__-+-
~----~----~-----~----__.__-..J.O 03/DeV0619'26 03/DeV0622:,9 04/OcV06 ':'2 041OcV064:04 04/DcV066:57 04/DeV06 9:50 04/DcV06 1243 Time (standard)
Figure 8 Test Parameters vs. Time for Test 2 Draft 8/17/2009 52
ves Test 2 Head loss Extrapolation 13..,-----...... ----- ----- -----------..--- -.--.-.-----
12 "ii' Q.::.
y =-15.34x + 598162 II)
II)
Head Loss (kPa) 0 11
...J Linear (Head Loss (kPa))
"'C IV III
- x:
10 9+----,-----,-----,----,-----.----+-----;
03/0cV2006 03/0cV2006 03/0cV2006 03/0cV2006 03/0cV2006 03/0cV2006 03/0cV2006 03/0cV2006 21:59 22:01 22:04 22:07 22:10 22:13 22:16 22:19 Time Figure 13-2 Least-Square Trend Line of Head Loss Curve for Test 2 after the First Debris Addition Draft 8/17/2009 53
90 81 72 u
~
~
- J
~
Gl Co E
Gl I
63 54 45
~
~
36
~
~
0 u:::
27 18 Debris addition 9
o
\\
Test 3 (Coating Failure as Particles/Chips Test)
Swept~oor Swept floor Flow rate (LIs)
Temperature (Oe)
I ~~....~ Head loss (PDT-1)
Head loss (PDT-2) 28 25.2 22.4 19.6 16.8 14 11.2 l?
a.::.
VI VI
..!2
"'C l'Cl Gl J:
8.4 5.6 2.8 0
24/Jul/0 24/Jul/0 24/Jul/0 24/Jul/0 24/Jul/0 24/Jul/0 25/Jul/0 25/Jul/0 25/Jul/0 25/Jul/0 25/Jul/0 25/Jul/0 712:28 714:24 716:19 718:14 720:09 722:04 70:00 71:55 73:50 75:45 77:40 79:36 Time Figure 13-3 Test Parameters vs. Time for Test 3.
Draft 8/17/2009 54
Test 3 (Coating Failure as Particles/Chips Test) 28 25.2 22.4 19.6 y =-3.8616x + 151738 Ii Q.
16.8
~
l/I l/I0 14
..J "tl Head loss (PDT-1)
Q) 11.2 J:
Head loss (PDT-2)
Linear (Head loss (PDT-2))
8.4 5.6 2.8 O+-----.------.----,-------r-----,-------r-----,---.------i 24/Jul/07 24/Jul/07 24/Jul/07 24/Jul/07 25/Jul/07 25/Jul/07 25/Jul/07 25/Jul/07 25/Jul/07 25/Jul/07 16:19 18:14 20:09 22:04 0:00 1:55 3:50 5:45 7:40 9:36 Time Figure 13-4 Least-Square Trend Line of Head Loss Curve for Test 3.
Draft 8/17/2009 55
NRC RAI #14 It was not clear that the refueling water storage tank (RWST) volume credited in the water level evaluation was based on a Technical Specification minimum RWST level. Please verify that the mass of water credited from the RWST is based on a minimum Tech Spec level.
SCE&G Response Yes, the mass of water credited from the RWST is based on a minimum Tech Spec level. The water level evaluation is discussed in Section 3g.3 of the V.C. Summer supplemental response provided in letter RC-08-0031. The RWST minimum injected mass credited is 2,763,276 Ibs; which is equivalent to a volume of 44,518.7 te or 333,023 gallons. This volume is derived from the Technical Specification RWST minimum contained volume of 453,800 gallons. As stated in the supplemental response, instrument uncertainty and instantaneous swap over from injection to recirculation were modeled, thus reducing the injected flow.
Draft 8/17/2009 56
NRC RAI #15 The amount of holdup in the refueling canal was not clearly specified.
Please specify the amount of holdup in the refueling canal and its drain line.
Provide a justification for the assumption that the refueling canal cannot be blocked by debris (as stated in the Upstream Section of the supplemental response).
SCE&G Response The Reactor Building minimum flood level calculation was updated to incorporate a water hold up volume for the Refueling Canal floor, the increase in RB Spray Pump flow rate (discussed in response to RAI #16) and remove a simplification that resulted in an over conservatism in the RB spray transit holdup volume. The Refueling Canal floor holdup was calculated to be 6978 Ibs. The net effect of these three changes was no change in RB sump minimum flood level.
Large Break LOCA 3.42ft Small Break LOCA 2.60 ft Blockage of the Refueling Cavity was addressed in the supplemental response in Section 31.4 and is provided below.
"3/.4 Refueling Cavity The Refueling Cavity is drained by an 8 inch diameter pipe. The drain opening into the pipe is located on the floor level in the cavity at elevation 423 feet, 5.25 inches. The centerline line of the pipe outlet into the normal RB sump (at a location away from the recirculation sump strainers) is 409 feet, 2 inches. There are no valves in the line. During refueling operation, a blind flange is installed to block the drain flow path. Based on the assessment summarized below, a debris interceptor for the Refueling Cavity drain is not required.
A continuous two inch curb is provided around the Refueling Cavity at the 463 ft operating deck elevation. During post-LOCA conditions, this curb prevents water collected on the operating deck (from the spray flow) from entering the refueling cavity. This limits the amount of water that must drain from the refueling cavity through the 8 inch pipe. The curb also prevents wash down of any debris from the operating deck into the Refueling Cavity.
V.C. Summer containment is highly compartmentalized. The shield wall around the S/Gs extends up to the 475 ft, 5 inch elevation on the side facing the Refueling Cavity.
The limiting design break at the S/G outlet is at the 431 ft elevation. Debris large enough to block the 8 inch diameter drain is not expected to be carried up and over this elevation difference.
If it were postulated that large debris were to dislodge from the top of the S/G and fall laterally into the Refueling Cavity, it would then have to transport to the 8 inch drain line. The insulation on the S/Gs is reflective metal cassettes. The failure mechanism for cassette located near the top of the S/G is for the cassette Draft 8/17/2009 57
buckle to fail and the cassette to break open as it impacts the floor.
The Refueling Cavity drain line is located near the containment wall in the fuel transfer canal.
This is well away from the S/Gs. Testing has shown that water readily flows through a pile of crumpled reflective metal insulation debris."
Based on teleconferences with the NRC staff a more detailed discussion with an explanation of the layout is needed.
The fibrous debris for V.C. Summer is TempMat used to insulate the Steam Generator Wide Range Level instrument tubes in Loop A and C S/G compartments. The TempMat is located at approximately the 439 ft elevation and above.
A review of each loop compartment was completed to detail the grating and tortuous path that large pieces of TempMat would encounter.
The Diamond Power Reflective Metal Insulation (RMI) on the steam generators must also be addressed.
The insulation cassettes are very heavy and not expected to be transported vertically. However, the Diamond Power RMI has a very low destruction pressure. The failure mechanism is the latch coming open and the cassette falling to the ground and bursting open.
In discussions with the NRC staff on the July 6, 2009 complete blockage of a drain is not expected due to RMI debris, but additional water hold up due to increase flow resistance should be addressed if RMI can get to the drain.
The following sections detail the review of the refueling cavity for potential debris introduction and drain blockage.
Drain and refueling cavity layout Steam generator A TempMat, grating and tortuous path Steam generator C TempMat, grating and tortuous path RMI Debris Transport and potential for additional water holdup Drain Location and Size The Refueling Cavity drain is an 8" -150 Ib flange located on the 423 ft, 5 % inch elevation in the north section of the Reactor Building. Figure 15-1 is a 3D CAD rendering of the Reactor Building with the Refueling Cavity drain, steam generators and TempMat locations denoted.
For debris to enter the drain location, it would have to fall into the Refueling Cavity and be transported to the drain location. The Refueling Crane is stationed directly above the drain location making it unlikely that anything could fall directly into the drain. This is shown in Figure 15-3.
As discussed in the supplemental response, the Refueling Cavity is surrounded by a two inch curb. There will be no wash down into the cavity.
Draft 8/17/2009 58
Figure 15 3D CAD Rendering of Reactor Building with Refueling Cavity Drain Denoted TempMat Locations indicated with a star.
Draft 8/17/2009 59
Steam Generator A Loop Compartment TempMat The TempMat in Loop A is located on the bio-shield wall, opposite the refueling canal. There is a vertical run starting at approximately the 439 ft elevation. It extends up to the 457 ft with a horizontal run at that elevation. This is shown (approximately) in Figure 15-2.
To exit Loop A, the TemplVlat would have to transport up and then around the Steam Generator and out into the canal.
Figure 15-3 provides a photo of S/G A loop compartment as seen from the Loop B compartment.
The lowest wall elevation of the S/G A cubicle is at the 475 ft elevation. There is a platform across the opening as shown in Figure 15-4. The next platform elevation is at the 482 ft elevation. This is shown in Figure 15-5. The top platform is on the 488 ft elevation. This platform completely encircles the S/G and is shown in Figures 15-6a, 15-6b, 15-6c and 15-6d. There is approximately a 19" to 46" gap between this 488 ft platform and the bio-shield wall (this is the west wall opposite the Refueling Cavity) as shown in Figure 15-6b.
S/G Loop A is also provided with a solid platform at the 457 ft elevation would restrict flow up S/G cubicle on the Refueling Cavity side.
There are two additional platforms on each side of S/G A at the 466 ft 11 inch elevation. Figure 15-7 provides photo of these platforms from below (436 ft elevation) along the north wall of the S/G A cubicle.
The platform and concrete wall on the S/G A cubicle are shown in Figures 15-8a and 15-8b. The location of the TempMat is also included. For a large piece of TempMat to exit the S/G A loop cubicle to the Refueling Cavity it would have to lift vertically to between the 475 ft and 488 ft elevation, then move horizontally around the steam generator. The other path would be to hug the bio-shield wall up through the opening at the 488 ft elevation grating and then move horizontally.
These tortuous paths will restrict the transport of large TempMat to the Refueling Cavity and significantly limit the potential for Refueling Cavity drain blockage.
Draft 8/17/2009 60
Figure 15 A Loop TempMat Approximate Location (Note that Loop walls only shown to 463 ft elevation Draft 8/17/2009 61
Figure 15 Photo of S/G A Loop Compartment and Location of Refuel Crane Refueling Crane parked over the drain location inhibiting direct deposition of debris Draft 8/17/2009 62
Draft 8/17/2009 63
Draft 8/17/2009 64
ure 15-6c - S/G Loop A - 488 ft - South Wall Draft 8/17/2009 65
Draft 8/17/2009 66
Figure 15-8a - Platform Elevation Section for Loop A - Looking North 488 ft 482 ft 475 ft 467 ft 457 ft Refueling Cavity Draft 8/17/2009 67
Figure 15-8b - Platform Elevation Section for Loop A - Looking West from Refueling Cavity 488 ft 482 ft 475 ft 467ft 457 ft
..,...----l TempMat from 439 ft to 457 ft Draft 8/17/2009 68
Steam Generator C Loop Compartment TempMat The TempMat location of the C Loop is on the bio-shield wall, opposite the refueling canal.
There is a horizontal run at approximately the 439 ft elevation. Then there is a vertical run up to locations outside the Zone of Influence. This is shown (approximately) in Figure 15-9.
Figure 15-10 provides a picture of the 443 ft platform directly above the horizontal section of the TempMat.
To exit the S/G C loop compartment, the TempMat would have to transport up and then around the Steam Generator and out into the cavity.
Figure 15-11 a provides a photo of S/G C loop compartment as seen from the Loop A compartment.
The Loop C compartment wall along the Refueling Cavity goes up to the 488 ft elevation and then angles even higher on the southern portion of the wall. Figure 15-11 b provides a photo of S/G C Loop compartment as seen from the 463 ft operating deck, just north of the compartment. The wall which projects out over the 463 operating deck goes up to the 475 ft elevation.
Figure 15-12 shows a small platform at the 467 ft elevation.
Though not directly over the TempMat, it does provide another barrier to vertical transport. Figure 15-13a and 15-13b show a large platform at the 488 ft elevation. Figure 15-13a shows the platform directly against the wall over the TempMat installation. Figure 15-13b shows the platform from the bottom, blocking TempMat vertical transport. Another small platform at the 488 ft elevation along the west side is also provided. This can be seen on Figure 15-11 a.
The S/G loop C is also provided with a snubber access platform at the 457 ft elevation. This solid platform would restrict flow up S/G cubicle southern side of the compartment.
This is clearly seen in Figure 15-14 showing the platform form the 443 ft elevation.
The platform and concrete wall on the S/G C compartment are shown in Figures15-15a and 15 15b. The location of the TempMat is also included. For a large piece of TempMat to exit the S/G C compartment to the Refueling Cavity it would have to lift vertically to between the 467 ft and 488 ft elevation, then move horizontally south around the steam generator, then lift vertically again above the top of the steam generator wall around the 500 ft elevation and move west horizontally out to the Refueling Cavity. Any TempMat that moved north horizontally and exited the compartment at the 475 ft elevation to the north would fall to the 463 ft operating deck and not enter the Refueling Cavity. These tortuous paths will restrict the transport of large TempMat to the Refueling Cavity and significantly limit the potential' for Refueling Cavity drain blockage.
Draft 8/17/2009 69
Figure 15 S/G Loop C Approximate TempMat Locations (Note that concrete wall elevations are onl shown to the 463 ft elevation for clarit )
Draft 8/17/2009 70
Draft 8/17/2009 71
~
~
/
Draft 8/17/2009 72
Draft 8/17/2009 73
Figure 15-13a - C Loop - 488 ft Elevation - East Wall (above TempMat Location, opposite the RF cavit Draft 8/17/2009 74
Figure 15 Loop C - 457 ft Snubber Platform seen from below T
~ :;
Draft 8/17/2009 75
Figure 15-15a - Platform Elevation Section for Loop C - Looking South 488 ft 475 ft 467ft 463 ft 457 ft 443 ft Refueling Cavity Draft 8/17/2009 76
Figure 15-15b Platform Elevation Section for Loop C -
Looking East from Refueling Cavity 488 ft 467 ft 457 ft 443 ft Draft 8/17/2009 77
RMI Evaluation The Diamond Power Reflective Metal Insulation (RMI) has a large Zone of Influence, so theoretically RI\\/II cassettes could be dislodged from the Steam Generator at elevations above the loop compartment walls. Each loop is considered separately for the potential of cassettes and RI\\/II debris from entering the refueling cavity.
For Loop A, the wall to the north as shown in Figure 15-3 is above the steam generator and RMI and would preclude RMI cassettes from falling towards the drain location. For an RMI cassette to enter the refueling canal it would have to fall over the loop compartment.
The loop compartment projects about 5 to 6 feet away from the steam generator. If the RMI cassette cleared the loop compartment, it could fall into the refueling canal, but at a location well away from the 8" drain line.
For Loop B, the compartment is on the south end of the Reactor Building. The RMI debris would again have to clear the loop compartment and project out horizontally. The reactor head missile shield would provide an impediment for debris transport. Also, the flow rate on the floor at this location is minimal since it is the furthest from the drain location, as shown on Figure 15
- 1.
For Loop C, the wall facing the refueling cavity is at a higher elevation as shown in Figure 15 11 a. This leaves only a small section at the 488 ft elevation (52 feet above the break location) that RMI debris could theoretically leave the loop compartment. Again, the RMI cassette would have to project out horizontally approximately 5 to 6 feet to clear the loop compartment wall.
RMI cassettes from Loop C would not fall into the refueling canal. There is a 9 ft 6 in wide platform at the 463 ft elevation between the Loop C compartment and the refueling canal. RMI cassettes would fall to this area from Loop C. There is a 2" curb as noted in the supplemental response that will preclude RMI debris from entering the refueling canal.
There is a low probability RMI debris will enter the refueling cavity. If by some unlikely chance a cassette projected out over the Loop A compartment, from here the RMI would have to transport based on water in the cavity (at that location) due to spray flow.
From this location, large stainless steel pieces of RMI adequate to block off the 8" drain line are not expected to transport. Smaller pieces of RMI may transport depending on the water depth in the refueling canal. If the small pieces of RMI transport to the 8" drain, they would not block flow at the drain opening by themselves. The RMI debris would fall into the drain piping. Small RMI debris have been shown to transport at less than 0.5 ftIsec.
The drain line has two horizontal runs (at the 422 ft and 409 ft elevations) and no high points or goose necks that could trap RMI debris. The flow in the 8 inch drain line pipe is 712.8 gpm or 1.59 fe/sec. The flow velocity is 4.6 ftIsec. This is more than adequate to sweep the small RMI pieces through the drain line.
The drain line empties into the normal reactor building sump at the 409 ft elevation. The top of the normal reactor building sump is on the 412 ft floor elevation.
The normal reactor building sump is 5 ft x 5 ft with the bottom at the 401 ft elevation. Small RMI debris would fall to the bottom of the sump. The volume beneath the refueling cavity drain line is approximately 187 ft3 (5 ft x 5 ft x [408.5 ft - 401 ftl). This is depicted in Figure 15-16.
Draft 8/17/2009 78
The volume is converted to area of 2.5 mil stainless steel foil based on the Utility Resolution Guidance (URG) Volume 2, Appendix B (Ref. 15-1).
Area =Volume / Kt From Table B-2 (Ref. 15-1), the Kt factor is 0.015, so 187 fe is equivalent to 12,467 fe of RMI debris for 2.5 mil foil. From Table 3 of the V.C. Summer supplemental response, a total of 47,577 fe of RMI debris may be generated from the limiting Loop A break. The only theoretical RMI debris source for the Refueling Cavity is the Loop A Steam Generator above the 475 ft elevation, facing the cavity.
This is less than Y4 of the Steam Generator surface and substantially less than Y4 of the total RMI generation.
Based on this discussion, a debris interceptor or cage over the refueling cavity drain is not required for RMI debris. Any RMI that reaches the drain will be swept through the pipe into the normal RB sump pit. There will be no additional holdup in the refueling cavity due to increased flow resistance.
References for RAI #15 15-1 Utility Resolution Guidance for ECCS Suction Strainer Blockage, Volume 2, October 1998 (Appendix B)
Draft 8/17/2009 79
Figure 15-16 Normal RB Sump Showing Refuel Cavity Drain Line Grating
~sump Pump Support Plate
~
412 ft 409 ft- --------------
I Drain Line Area Available for Small RMI Debris Deposits 401 ft Draft 8/17/2009 80
NRC RAI #16 A technical basis for the pump flow rates was not provided. Please provide the basis for the flow rates used in the net positive suction head (NPSH) evaluation. For example, are the flow rates based on pump runout or are they based on a calculated value?
If the value was calculated, please provide the methodology, assumptions, and inputs used in the evaluation.
SCE&G Response The pump flow rates used in the Debris Transport analysis and NPSH calculations are discussed in Supplement Response Section 3g.2. The flows are repeated here for clarity.
RHR Pump Flow Rates Single Train Operation Analytical Maximum NPSH Flow Assumption (Ref. 2)
(Ref. 3)
RHR Pump A 4290 gpm 4500 gpm RHR Pump B 4196 Qpm 4500 Qpm Two Train Operation Analytical Maximum Debris Transport Flow (Ref. 1)
Assumption (Ref. 4)
RHR Pump A 3669 gpm 4288 gpm RHR Pump B 3590 Qpm 4288 Qpm The RB Spray Pumps have separate spray headers. The pumps do not interact when both trains are operating. The individual pump flow rate is the same for one pump and two pump operation. The maximum RB Spray Pump flow is 3000 gpm per operating pump.
The total recirculation flow rate used in the Debris Transport for two trains operating is 14576 gpm (4288 + 4288 + 3000 + 3000). The total recirculation flow rate used in the NSPH calculation for a single sump strainer is 7500 gpm (4500 + 3000).
The maximum RHR Pump recirculation flow rate calculation was completed in 2006 by Westinghouse using the Fathom computer code. Pertinent modeling and design input are
- 1. The model development used current piping isometrics and component data.
- 2. For the maximum flow rates, the model was bench marked against startup test data.
This conservatively lowers system resistance to maximize flow.
- 3. The RHR Pump maximum allowable performance curve was used.
RHR Pump performance within this allowable maximum is confirmed via surveillance testing in support of Technical Specification requirements.
- 4. The Reactor Coolant System and Reactor Building pressure are equal.
- 5. The Reactor Building sump water level is set to a maximum depth (420 ft elevation).
- 6. Head loss across the sump strainer is assumed to be 0 psig to conservatively reduce system resistance.
In summary, the RHR Pump maximum flow rates for post-LOCA recirculation were calculated with the same conservative bounding methodologies used for RHR Pump performance in FSAR Chapters 6 and 15 analyses.
Draft 8/17/2009 81
During the course of the RAI resolution, a difference between the RB Spray Pump curve used in the system design calculation and the vendor certified calculation was noted.
Further investigation identified a historical calculation which increased maximum RB Spray Pump flow rate during post-LOCA recirculation (due to the pump curve change) that was not reflected in the historical NPSH calculation. The maximum RB spray Pump flow rate during post-LOCA recirculation has now been appropriately documented (as described below) and has increased from 3000 gpm to 3300 gpm. The impact of this flow increase is also addressed in this RAI response.
The maximum Reactor Building Spray Pump flow rate calculation was recently updated. The calculation does not rely on computer hydraulic modeling.
The system resistance curve is plotted against the Reactor Building Spray Pump maximum performance curve, accounting for elevation differences.
The curve intersection yields the flow rate.
Pertinent modeling and design input are
- 1. Pipe, piping fitting and valve head losses were reduced by 20% to allow for conservatisms in the literature values.
- 2. The Reactor Building Spray Pump maximum allowable performance curve was used.
Reactor Building Spray Pump performance within this allowable maximum is confirmed via surveillance testing in support of Technical Specification requirements.
- 4. Head loss across the sump strainer is assumed to be 0 psig to conservatively reduce system resistance.
In summary, the Reactor Building Spray Pump maximum flow rates for post-LOCA recirculation were calculated with the same conservative bounding methodologies used for Reactor BUilding Spray Pump performance in FSAR Chapters 6 and 15 analyses.
This Reactor Building Spray Pump flow rate increase is within the margin included in both the strainer testing program and the Debris Transport calculations. The strainer tests were carried out at 7500 gpm to reflect single train operation which increases RHR Pump flow rate. The maximum calculated flow through each strainer is shown below (note that RHR Pump flow rates are rounded up for simplification)
Train A 4300 m
3300 m
7600 m
Train B 4200 m
3300 m
7500 m
The Train B strainer is significantly smaller and was used for the test scaling. The approach velocity for each strainer and the test module are shown below Train A Train B Test Module Total Flow Rate 7600 gpm 7500 gpm 1201 gpm Total Flow Rate 16.93 fe/sec 16.71 ft3/sec 2.68 ft3/sec Total Surface Area 2939 ft2 2379 ft2 357 ft2 Sacrificial Area 150 W 150 ft2 oft2 Total Flow Area 2789 ff 2229 ff 357 ff Draft 8/17/2009 82
I_F_lo_w_v_e_lo_c_ity"--__I_o_.0_0_6_0_7_ftl_s_ec_-LI_O_.0_0_7_5_ftl_s--,-e_c__I 0.0075 ftlsec The flow velocity through the strainer fins for both trains stays within the flow velocity used in the strainer test.
The Computational Fluid Dynamics (CFD) Model calculation total flow rate is 14,576 gpm or 7288 gpm per train assuming two trains operating to maximize flow rate and transport velocities.
A comparison of the CFD flows and the update flow is as follows.
Pump Used in the CFD Model Updated Flow Rate Difference Percent Difference RHR Pump A (Break Flow) 4287.5 gpm 3669 gpm
-1,316 gpm
-15.3%
RHR Pump B (Break Flow) 4287.5 gpm 3590 gpm Spray Pumps 6000 qpm 6600 Qpm 600 qpm 10.0%
Total Flow 14,575 qpm 13,859 qpm
-716qpm
-4.9%
The increase in Spray Pump flow is offset in all areas by the decrease in Break Flow except for possibly wash down of some debris types from upper containment. (Note: The transport of fines from upper containment is 100% regardless of spray flow rate or location.) Three wash down locations are modeled as shown on Figure 16-1 (Note this was Figure 2 in the Supplement Response).
- 2. The eastern stairwell is well outside the flow stream to the sump strainers (which are located in the southern and western portions of the containment).
The transport fraction is zero and will remain zero.
- 3. The equipment hatch is located in the south eastern side of the Reactor Building.
Increasing the spray flow rate increases the drain down flow and, therefore, increases the localized turbulence.
- a. For small fiber clumps and curled paint chips there is no impact since Debris Transport is already 100% from the equipment hatch.
- b. For large fiber, reflective metal insulation, 2" flat paint chips and 1/8" flat paint chips there is no impact. These debris types have a large quiet area with no transport between the equipment hatch and sump area. Debris will continue to settle out before reaching the strainer.
- c. For 1/64" flat paint chips, there is a mix of results. For a break modeled in the A loop, the transport fraction is 100% from the equipment hatch.
For breaks modeled in the Band C loops, the transport fraction is 0%. However, the quiet zone of no transport is relatively small. For conservatism, the Debris Transport fraction is set to 100% for 1/64" flat paint chips for all three loop break locations to account for the increase in spray flow. There is no net impact on debris loading at the Train A strainer. The A Loop break location continues to bound the Band C Loop break location debris loadings.
The NPSH calculations for both the RB Spray Pumps and the RHR Pumps were updated to reflect the change in the flows. The following table supersedes Table 17 of Section 3g.4 of the Draft 8/17/2009 83
supplemental response. Also note that the strainer pressure drop was updated to 3.15 psi at 104of as covered in response to RAI #10 NPSH Margin - No Credit for Subcooling of sump water Pump Flow rate NPSH Required NPSH Available NPSH Margin Temperature RHR Pump A 4300 gpm 17 ft 18.8 ft 1.8 ft 70°F RHR Pump A 4300 gpm 17 ft 26.4 ft 9.4 ft 212°F RHR Pump B 4200 Qpm 16 ft 19.4 ft 3.4 ft 70°F RHR Pump B 4200 Qpm 16 ft 27.0 ft 11.0 ft 212°F Spray Pump A 3300 gpm 17 ft 20.7 ft 3.7 ft 70°F Spray Pump A 3300 gpm 17 ft 28.3 ft 11.3 ft 212°F Spray Pump B 3300 gpm 17 ft 20.2 ft 3.2 ft 70°F Spray Pump B 3300 l::JPm 17 ft 27.8 ft 10.8 ft 212°F The increase in Reactor Building Spray Pump maximum flow rate during post-LOCA recirculation was captured in the Corrective Action Program to ensure all impacts are evaluated and documented.
Draft 8/17/2009 84
Figure 16-1 CAD Model with Spray Drainage, Break Locations ad Sump Locations Stoam Cenerator and Peripheral N
---..:r=rt=-~~_~,.:Oralnage t
Draft 8/17/2009 85
NRC RAI #17 A technical basis for the NPSH required (NPSHr) for each pump was not provided. Please provide the basis for the NPSHr values used in the evaluation (e.g., is the NPSHR based on a 3% decrease in discharge head or some other acceptance criterion?).
SCE&G Response The NPSH required (NPSHr) for the RHR Pumps is taken directly from the vendor certified performance curves which covered a range of data points up to 4500 gpm.
Procurement specifications for RHR Pump NPSH testing invoked the Hydraulic Institute guidelines.
The NPSH required test for the Containment Spray Pumps was similarly based on the Hydraulic Institute guidelines, but was only tested at one data point (2520 gpm design flow) as required by the Procurement Specification (SP-594).
The NPSH required is 9.4 ft (Train A) and 10.1 ft (Train B).
The required NPSH at 3300 gpm is based on comparison with the vendor characteristic curve for the pump and impeller size.
Flow Rate Train A Train B Characteristic Curve Difference 2520 gpm 9.4 ft 10.1 ft 14.5 ft 4.4 ft 3300 gpm 17 ft 17 ft 20.3 ft 3.3 ft Based on this comparison, 17 ft is used for the NPSH required at 3300 gpm for both RB Spray Pumps.
Draft 8/17/2009 86
NRC RAI #18 An evaluation of NPSH margin during hot leg recirculation was not provided. If the maximum flow rate is not based on pump runout, please provide the maximum flow rate during hot leg recirculation. Include the methodology, assumptions, and inputs used to determine the flow rate.
SCE&G Response V.C. Summer initially aligns the Safety Injection System for recirculation with the RHR Pumps and Charging Pumps delivering flow to the Reactor Coolant System cold legs. These flows are presented on Table 16 of the Supplemental Response (4290 gpm for Train A and 4196 gpm for Train B). At approximately 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> following switchover from injection from the RWST to Cold Leg Recirculation for the sump, the system is realigned for simultaneous Hot Leg and Cold Leg recirculation. Two system alignments are possible. The preferred alignment included in the Emergency Operating Procedures is for the Charging pumps to deliver flow to the hot legs and the RHR Pumps to remain aligned to the cold legs. The calculated flows for this alignment are 4148 gpm (Train A) and 4134 gpm (Train B) assuming only one RHR Pump and one Charging Pump are operating). These flows are slightly less than those presented in Table 16 of the Supplemental Response for Cold Leg recirculation. The alternative alignment is for the RHR Pumps to deliver to the Reactor Coolant System hot legs and the Charging Pump to deliver to the cold legs.
This alignment is not specifically proceduralized, but is allowable under engineering guidance during post-LOCA long term cooling. The RHR Pumps are only provided with two 6 inch hot leg injection lines (as opposed to three 6 inch cold leg injection lines). The RHR flows were not specifically calculated for this alternate alignment; however, with the discharge header resistance significantly higher (only 2 injection lines instead of 3), the pump flow will be lower. In all cases, the Cold Leg recirculation flow rates presented in Table 16 of the Supplemental Response are bounding.
Draft 8/17/2009 87
NRC RAI #19 The 2004 Edition of the ASME Code is not currently endorsed by the Code of Federal Regulations. Please provide justification and/or re-evaluation for discrepancies, if any, between the applicable portions of the 2004 Edition of the ASME Code which were used in the analysis and the respective Code Editions which are currently endorsed by the NRC in 10CFR50.55a.
SCE&G Response 10CFR50.55a currently endorses the 2004 Edition of the ASME Code.
The analysis used portions of the ASME Code,Section III, Subsection NF (Class 3), 2004 edition with 2005 addenda. For the portions of Subsection NF used in the analysis, there are no discrepancies between the 2004 edition and the 2005 addenda.
Draft 8/17/2009 88
NRC RAI #20 The licensee's submittal stated that current VCSNS LOCA dose calculations are required to assume the passive failure of a high head safety injection pump seal at 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after the event with isolation of the leak in 30 minutes. To eliminate the need for assuming a pump seal failure, Section 3p of the licensee's supplemental response stated that the licensee would be preparing an Alternate Source Term (AST) dose analysis and would be submitting an AST license amendment. The licensee stated that if it could avoid the assumption of a high head safety injection pump seal failure at 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, there would be no need to replace the pump's carbon/graphite disaster bushing. A March 18, 2008 letter from the South Carolina Electric and Gas Company to the Nuclear Regulatory Commission confirmed the licensee's commitment to submit the AST amendment, and the licensee verbally informed the NRC Project manager that the amendment would actually be submitted in March 2009 (a December 10, 2008 letter from the licensee updated this to a projected time frame of February, 2009). The licensee should either (1) obtain NRC approval of an AST amendment, or (2) satisfactorily address the radiological effects of failure of the high head safety injection pump seal, potentially through replacement of that pump's carbon/graphite disaster bushing.
SCE&G Response SCE&G submitted the LAR for AST on February 17, 2009 in our letter RC-09-0004.
Draft 8/17/2009 89
NRC RAI #21 The licensee stated that the debris loading expected during post-LOCA conditions may cause the high head safety injectiohl pump seals to exceed the accepted 50 gpm leak rate and that the carbon/graphite disaster bushings in the pump seals may also not limit pump seal leakage to 50 gpm if the primary seal fails. The submittal stated that a more robust replacement pump seal assembly is not available.
- a.
Please confirm that the expected seal leakage does not diminish the pump(s) capacity below that required to accomplish the pumps design function.
- b. Please confirm that the expected pump seal leakage is accounted for in the compartment flooding evaluation.
SCE&G Response to 21a Each of the six pumps circulating post-LOCA sump water is provided with two seals.
The primary seal of each pump has been demonstrated to meet the 40-day mission time for V.C.
Summer based on the methodologies contained in WCAP-16406-P.
The second seal is a backup seal with carbon-graphite bushings. The backup seal is provided to limit seal leakage to 50 gpm if the primary seal were to fail. As covered in WCAP-16406-P, these bushings could not be demonstrated to meet a post-LOCA mission time. However, the backup seal is not relied upon unless there is a primary seal failure.
The licensing basis for post-LOCA recirculation is either one Active Failure or one Passive Failure. Assuming the Passive Failure is a pump primary seal, that pump may leak more than 50 gpm. With the failure of the primary seal, the operators would stop the pump once the leak was identified. The redundant pump, which is already running and is 100% capacity, would meet the analysis flows. Reduced performance of a pump with a fail seal is not a concern.
SCE&G Response to 21 b The RHR pumps and Reactor Building Spray pumps are located on the 374 foot elevation of the Auxiliary Building. Each pump is within its own room with an 8.5 inch curb across the door way.
The maximum calculated flood level on the Auxiliary Building 374 foot elevation is 9.4 inches.
This is based on a Feedwater line rupture at a higher elevation that flows down to the 374 foot elevation. The flow rate of this rupture is over 10,000 gpm and bounds any potential leakage out a failed pump seal for both the RHR pump and Reactor Building spray pump.
The Charging pumps are located on the 388 foot elevation of the Auxiliary Building (drawing 001-002, Rev. 36). Each Charging pump is in its own room with a 6 inch curb in the door way.
A postulated pipe rupture within the Charging pump cubicle results in the maximum flood level of 6 inches.
The flood level in the general floor area of the 388 foot elevation of the Auxiliary BUilding is 4.7 inches.
This is based on 2862 fe draining from a higher elevation.
This represents a pipe rupture leak rate of over 700 gpm. This bounds any potential leakage out a failed pump seal for the Charging pump which has a run out flow of 688 gpm.
Note that a pipe rupture considered for flooding is not assumed to occur simUltaneously with a LOCA and post-accident long term recirculation. The pipe rupture leakage rate is not added with a failed seal leakage rate.
Draft 8/17/2009 90
As noted in response to RAI #21 a, the primary seals meet the 40-day mission time for V.C.
Summer. Therefore, only one primary pump seal failure need be postulated based on the single failure criteria for evaluating flood levels.
Draft 8/17/2009 91
NRC RAI #22 The licensee used coating abrasion data extracted from WCAP-16571-P, "Test of Pump and Valve Surfaces to Assess the Wear from Paint Chip Debris Laden Water," Revision 0, to supplement erosion data in the erosion calculations. The NRC has not evaluated this WCAP.
Please submit data extracted from WCAP-16571-P pertinent to the wear evaluations, including information used to support the validity of the data.
SCE&G Response
Background
In Generic Safety Issue GSI-191, "Assessment of Debris Accumulation on PWR Sump Performance," the NRC required licensees to address the effects of ingesting debris into the Emergency Core Cooling (ECC) and Containment Spray (CS) systems following the post accident realignment of those systems to recirculate coolant from the containment sump. The effects of debris on equipment and components downstream of the sump screen are referred to as "downstream effects" and the evaluation of those components is referred to as "downstream effects evaluations."
Abrasive wear is the removal of material due to particles that move between two surfaces that are in close proximity and in relative motion.
This type of wear affects certain components within pumps, such as wear rings, internal bearings, etc. On the other hand, erosive wear is the wear associated with particles striking a fixed surface.
In general, the abrasive wear rate is greater than the erosive wear rate for a given concentration of debris.
A method of evaluating downstream effects was described in WCAP-16406-P (Reference 22-1).
Components exposed to debris can wear in two ways: pump running clearance wear by abrasion and valve, orifice and heat exchanger wear by erosion.
Abrasive and erosive wear models were described in Reference 22-1. The models were based on available data generated from early equipment testing of original equipment supplied to plants, and literature data based on slurry transport. Specifically, wear testing of components with entrained debris (Reference 22-1) included the following debris mix:
- 1. Abrasives: sand, concrete, and glass
- 2. Fibers
- 3. Protective coatings 1\\10 attempt was made in the tests to characterize the wear behavior by debris type. Thus, all of the debris types were treated as being equally abrasive.
Debris generation and transport evaluations performed by and for licensees to address GSI-191 have shown that protective paint coatings debris is generally a major contributor to the debris source term that is passed through the containment sump screen. The concentration of paint coatings debris usually dominates the other debris mix or constituents and consequently contributes significantly to the wear of components using the Reference 22-1 model. While paint coatings debris is not thought to be as abrasive or erosive as sand, concrete or glass, there is minimal data available to Westinghouse to demonstrate the actual abrasive or erosive Draft 8/17/2009 92
properties of paint coatings debris. To confirm our intuition, Westinghouse developed a test program to obtain abrasive and erosive wear data associated with protective paint coatings debris. The results of this test program are documented in WCAP-16571-P (Reference 22-2),
and summarized below.
Summary of WCAP-16571-P WCAP-16571-P documents testing performed on paint coatings to establish the wear characteristics of paint coatings. Below is the test summary:
- A test loop was constructed that circulated paint chip laden water in a closed pumped loop.
This debris loading also had an approximately even split between large and small particles, as defined by Reference 22-1. The debris mix is highly dominated by IOZ and epoxy, and has a low concentration of acrylic paint coatings (less than 0.5% of the total). A constant debris concentration was maintained for the tests.
- To accelerate the wear test, the test specimens were fabricated from pure aluminum of known hardness and stainless steel 300 series of known hardness to determine wear when exposed to debris laden fluid. The fixtures included simulated pump wear rings and a flat plate orifice plate.
- The duration of each test was approximately 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
The amount of wear measured for the aluminum fixture was far less than would be predicted using the Reference 22-1 model, showing that the wear due to the softer paint coatings is less than other typical debris materials such as glass, concrete and fiber.
- Applying the methodology of Reference 22-1 on the measured wear, a paint coating specific model was developed. This is documented in Reference 22-2.
In WCAP-16571-P, it is shown that wear from paint coatings is not as erosive as sand, concrete or glass, which was the basis of the wear model in Reference 22-1. From the test data, a wear model was developed in Reference 22-2 for the erosive effects of paint coatings, which is patterned after the wear model in Reference 22-1. The resultant paint coatings wear model could then be used for the erosive effects of paint coatings in debris laden fluid, separately from the Reference 22-1 model, which is to be used for all other types of debris. By taking credit for the testing that was performed, the Reference 22-2 erosive wear model is an enhanced version of the Reference 22-1 wear model that takes into account the diminished erosive effects of paint coatings as compared to sand, concrete and glass. The Reference 22-2 erosive wear model utilized the same equation as Reference 22-1, except that the exponents on the concentration and hardness are adjusted to diminish the effects from those variables.
Draft 8/17/2009 93
Applicability of WCAP-16571-P to V.C. Summer In February of 2008, an evaluation (Reference 22-3) was performed for V.C. Summer to determine the erosive effects of debris laden fluid on valves in the ECC and CS systems. In this evaluation, it was determined that the critical valves are the ECC system injection line throttle valves, due to the fact that these valves are typically partially closed, causing high velocities through the close clearances of the valve internals. For the erosive wear models in References 22-1 and 22-2, velocity is a squared term, so high velocities through the valve would tend to increase the wear rate of the surfaces exposed to a debris laden fluid.
In the Reference 22-3 evaluation, the debris loading that is assumed to be introduced to the ECCS system and used for the calculations in the evaluation is highly dominated by paint coatings (:::: 85% of total debris). For this reason, it was determined that it was appropriate to use the Reference 22-2 model to calculate the wear rate due to paint coatings, and use the Reference 22-1 model for the remainder of the debris loading (:::: 15%).
In reviewing References 22-1, 22-2 and 22-3, it was determined that the use of the Reference 22-2 wear rate model for paint coatings for the V.C. Summer downstream effects evaluations is justifiable for reasons outlined in Table 1.
References for RAI #22 22-1 WCAP-16406-P-A Revision 1, "Evaluation of Downstream Sump Debris Effects in Support GSI-191," March 2008.
22-2 WCAP-16571-P Revision 0, "Test of Pump and Valve Surface to Assess the Wear from Paint Chip Debris Laden Water For Wolf Creek & Callaway Nuclear Power Plants," July 2006 [Proprietary Class 2].
22-3 CI\\J-CSA-05-104 Revision 2, "V.C. Summer (CGE) Sump Debris Downstream Effects Evaluation for ECCS Valves," February 2008.
Draft 8/17/2009 94
NRC RAI #23 The NRC staff considers in-vessel downstream effects to not be fully addressed at VCSNS, as well as at other PWRs. The licensee's supplemental response refers to WCAP-16406-P which is not recognized by the NRC for addressing in-vessel downstream effects. Westinghouse has prepared WCAP-16793-NP, "Evaluation of Long-Term Cooling Considering Particulate, Fibrous, and Chemical Debris in the Recirculating Fluid" to address in-vessel downstream effects.
Further, the NRC staff has not issued a final safety evaluation (SE) for WCAP-16793-NP.
Therefore, the licensee may demonstrate that in-vessel downstream effects issues are resolved for VCSNS by showing that the licensee's plant conditions are bounded by the final WCAP 16793-NP and the corresponding final NRC staff SE, and by addressing the conditions and limitations in the final SE. The licensee may alternatively resolve this item by demonstrating, without reference to WCAP-16793-NP or the staff SE, that in-vessel downstream effects have been addressed at VCSNS. In any event, the licensee should report how it has addressed the in-vessel downstream effects issue within 90 days of issuance of the final NRC staff SE on WCAP-16793-NP. The NRC staff is developing a Regulatory Issue Summary to inform the industry of the staffs expectations and plans regarding resolution of this remaining aspect of GSI-191.
SCE&G Response SCE&G is a part of the WOG program developing WCAP-16793-NP and has supplied debris loading to Westinghouse. SCE&G will demonstrate that in-vessel downstream effects issues are resolved for V.C. Summer by showing that V.C. Summer conditions are bounded by the final WCAP-16793-NP and the corresponding final NRC staff SE, and by addressing the conditions and limitations in the final SE. This response will be supplied within 90-days of the NRC SE on the WCAP-16793-N P.
Draft 8/17/2009 95
NRC RAI #24 Provide a detailed technical basis to support the conclusion that aluminum hydroxide is not expected to precipitate in the VCSNS sump water. This information should include the assumed post-LOCA temperature profile as a function of time. Indicate why the assumed temperature profile is the most limiting when considering the amount of dissolved aluminum in the sump water and the solubility of aluminum as a function of temperature at the assumed pH.
SCE&G Response:
Due to the similarity of the topics, a single set of References is provided for RAI #24, #25 and
- 26. These are provided following RAI #26.
Aluminum hydroxide (AI(OHh) may exist in an amorphous form or as one of three crystalline forms: gibbsite, bayerite, or nordstrandite1.
Various forms of AIOOH (boehmite, diaspore, or pseudoboehmite) could also precipitate, but gibbsite is thermodynamically most stable and other metastable phases can be changed to gibbsite through aging. The precipitation of these aluminum crystalline phases depends on their solubility in solution.
The solubility of gibbsite in non-borated water as a function of temperature at various pH values (Figure 24-1) was calculated from thermodynamic data reported by Wesolowski [6] [1992]. The solubility of gibbsite under these conditions is a weak function of temperature, decreasing by a factor of about 10 as the temperature is decreased from 100°C to 25°C at pH 10. However, the solubility of gibbsite is a very strong function of pH. For example, at 50°C, the solubility drops by a factor of -300 when the pH is lowered from 10 to 6.5.
The temperature and pH dependencies of the solubilities of bayerite, diaspore and boehmite
[Benezeth et aI., 2001[7]; Apps et aI., 1988[8)) are similar to that of gibbsite although bayerite has the highest solubility relative to the other three aluminium phases at the same pH (Figure ).
The solubilities of all of these compounds in non-borated water are very low; for example, at pH 7 and below 100°C, the solubilities of all four compounds are less than 0.1 mg/L below.
The solubility of amorphous aluminum hydroxide is much higher than that of the crystalline forms. Park et al. [9] [2006] reported a Ksp value2 of 8.0x10*13 for the amorphous phase at 25°C; this value is approximately 400 times larger than the solubility of gibbsite at the same temperature, which is consistent with the high measured aluminum concentrations in ICET Test
- 1.
I There is a fourth, rare polymorph, doyleite, that has a slightly different structure than the other three forms, but is not considered important in this context..
2 This value was taken from Van Straten and de Bruyn [10] [1984].
Draft 8/17/2009 96
100 10 t)l)
.:c t)l) a
'-' =
.S
~
0.1
.t: =
<lJ
'" =
0 0.01
~
0.001 0.0001
<> pH 6.5
- pH 7.0 t::.pH 8.0
- pH 9.0
- pH 10.0
'" pH 11.0 t::.
t::.
t::.
t::.
t::.
~
t::.
~
t::.
~
t::.
t::.
~
t::.
t::.
~
t::.
t::.
t::.
t::.
t::.
~ *
- 0 20 40 60 80 100 temperature(OC)
Figure 24-1 Solubility of gibbsite as a function of temperature at various pH values.
0025
- Gibbsite
- Boehmite 0.020
.Bayerite j
... Diaspore biJ
!. 0.015
=
'E
'=... 0.010
'" =
e 0.005 0.000 20 30 40 50 60 70 80 90 100 temperature (0C)
Figure 24-2 Solubility of gibbsite, boehmite, bayerite and diaspore as a function of temperature at pH 7.0 Draft 8/17/2009 97
The amphoteric property of aluminum hydroxide makes it dissolve readily in strong acids and bases. Figure 24-3 shows the dissolved species of gibbsite as a function of pH at 50°C. In acidic solutions, the dominant species of aluminum hydroxides is AI 3 +. Over the pH range 4 to 9, a small change in pH towards the neutral point results in rapid and voluminous precipitation of colloidal aluminum hydroxide, which readily forms a gel containing considerable excess water and variable amounts of anions. The gel composition and properties depends largely on the method of preparation and can crystallize on aging.
Above pH 9, the dominant aluminum species in solution is hydrated aluminum ion, AI(OHk.
2
-~._-
1 0
-1 C)
,:;(.
-2 0
E
-3
~ -4 C) 0 -5 Neutral
-6 AI(OHh
-7
-8 2
3 4
5 8
9 10 11 l
6 7
pH(50°C)
Figure 24-3 Logarithm of the molality of monomeric aluminum hydrolysis species, AI(OH)/'Y in equilibrium with gibbsite as a function of pH at 50°C and infinite dilution3 Precipitation of Aluminum Hydroxide The precipitation of aluminum hydroxide phases from supersaturated aluminate solutions has been studied by a number of groups (e.g., Van Straten and De Bruyn [10] [1984; Vermeulen
[11] [1975]). Wesolowski [6] [1992] noted that approach to equilibrium from supersaturated aluminum solutions can be very slow (15-90 days); the formation of a metastable surface or bulk phase with a higher solubility than gibbsite was suggested.
Van Straten and De Bruyn [10] [1984] reported that when a suspension of aluminum hydroxide in water is aged at a pH of 7 or higher, it undergoes a two-step aging process: amorphous 3 The thick solid curve is the total solubility of gibbsite.
Draft 8/17/2009 98
aluminum hydroxide transforms into poorly ordered boehmite (pseuoboehmite), which in turn transforms into bayerite, the stable polymorph.
It has also been shown that supersaturated aluminate solutions form the most-soluble phase first, become saturated with that phase, and sUbsequently form the next soluble phase. This process follows the Ostwald rule of stages4.
For example, in a solution supersaturated with respect to amorphous AI(OHh, pseudoboehmite, and bayerite (phases in order of decreasing solubility), amorphous AI(OHh will form first, then pseudoboehmite, and finally bayerite. Upon aging of the precipitate, amorphous AI(OHh will convert first to pseudoboehmite, which will subsequently convert to bayerite. In experiments in which solutions of aluminate ions were titrated with acids at various rates, they found that the formation of a crystalline phase was favoured by very low titration rates, with amorphous phases being favoured at high titration rates. They also noted that an amorphous phase was formed immediately once a critical value of the supersaturation was reached and if the titration speed was quite rapid. The degree of supersaturation in these tests was (pAl - pOH :os; -1.9). Based on this conclusion, the supersaturated aluminum concentration required for precipitation should be greater than 2.1 mg/kg at pH 7 and 25°C, which is 100 times higher than the solubility of crystalline aluminum hydroxides (Figure 24-2).
Anions present during aluminum hydroxide precipitation can be absorbed by the aluminum hydroxide gel and may stabilize or destabilize the colloid.
Studies have shown that the crystallization of gibbsite from amorphous aluminum hydroxide can be greatly inhibited by the presence of sulfate, silicic acid, and citric acid [Klasky et aI., 2006 [12)). It has been reported that nitrate has a rather weak effect, and perchlorate has no effect at all [Klasky et aI., 2006
[12)).
There is significant data in the literature to indicate a strong interaction between boron and aluminum, which can lead to a significant increase in the solubilities of both gibbsite and boehmite (up to factors of 6) [Klasky et aI., 2006 [12)). One study of the adsorption of boron onto aluminum hydroxide surfaces found that the boron present in the aluminum hydroxide gel was held predominantly on the surface as a specifically absorbed ion. Aging studies showed that the adsorption of boron onto the aluminum surface precluded crystallization.
Kinetic experiments using pressure-jump-relaxation have also shown that boron adsorbs as an inner sphere complex on aluminum oxide via a ligand exchange of borate with surface hydroxyl groups [Toner and Sparks, 1995 [13)). The point-of-zero-charge5 (pzc) for the AI(OHh free of any specifically adsorbed anions was 9.72, whereas for the boron-containing gel, the pzc was found to be 7.57-8.14.
As a result, the presence of boron may significantly change the flocculation behaviour of the aluminum hydroxide or oxyhydroxide. For tests carried out in the pH range 7.5-10.0, close to the pzc of AI(OHh, the behaviour of the precipitate will be a strong function of pH, and the adsorption of borate ion could promote flocculation. Klasky et al. [12]
recommended that equilibrium calculations for the ICET test conditions consider the aluminum borate complex in order to properly assess the effects of the presence of borate ion in the test solution on aluminum solubility.
While boron was identified as a constituent of some of the precipitates, it was unclear whether the boron was present as part of an aluminum-boron compound, or adsorbed on the surface of an aluminum hydroxide or oxyhydroxide. If the latter is the case, then the presence of boron may have significantly changed the flocculation behaviour of the aluminum hydroxide or oxyhydroxide, and the surface chemistry of the precipitates must be considered.
For tests 4 The Ostwald rule of stages predicts that the thermodynamically least stable phase should form first, followed by the more thermodynamically stable phases.
5 pH at which a colloid particle surface has no net charge.
Draft 8/17/2009 99
carried out near the pzc, the behaviour of the precipitate will be a strong function of pH, and the adsorption of borate ion could promote or prevent flocculation.
Most of the studies of aluminum hydroxide precipitation carried out under (PWR) post-LOCA sump water conditions have shown that the solubility of aluminum in these solutions is higher than the reported solubilities of the crystalline phases. Aluminum concentrations in solution under simulated PWR sump water chemistry conditions can be as much as three magnitudes higher than the solubility of crystalline phases. This is probably due to the slow precipitation kinetics and the presence of dissolved boron species or other impurities in the solutions. The resulting supersaturated aluminum solutions are most likely to precipitate amorphous phases under PWR sump water chemistry conditions.
Table 24-11 summarizes most of the available AI solubility data under PWR post-LOCA sump water conditions, as a function of solution pH. The graph (Figure 24-5) has been divided into a "Precipitation" and a "No Precipitation" region based on the data. The data strongly suggest that, at a given pH, precipitation does not occur at AI concentrations in the "No Precipitation" zone.
Draft 8/17/2009 100
Table 24-1 Summary of Relevant AI Solubility data Under PWR post-LOCA Sump Water Conditions Source
[B]
(mg/L)
Temperature (DC) pH Solubility (mg/L)
CR-6915 pg 74 2800 60 9.3 126 CR-6915 pg 74 2800 60 8.7 80 ICET 1 3120 60 10 380 ICET 5 (max) 2860 60 8.5 54 ICET 5 (min) 2860 60 8.5 34 CR-6913 C5 2800 60 10 260 CR-6913 C5 2800 60 9.8 115 CR-6913 C5 2800 60 9.5 60 CR-6913 pg 63 2800 60 9.6 53 CR-6913 pg 63 2800 60 9.6 35 CR-6913 pg 63 2800 60 9.6 49 Feb 152007 4500 38 8.4 50 AECL 2800 25 7
20 WCAP-16785 2500 60 8.14 98.4 The initial ANL head loss testing of aluminum hydroxide precipitates were performed with surrogates proposed by industry or by forming precipitates in-situ using aluminum nitrate, AI(N03h. as the source of dissolved AI. In a post-LOCA environment, however, the precipitates would be formed in-situ with the source of the AI being dissolution of AI by corrosion of AI metal.
In this respect, sodium aluminate is a much more representative aluminum source in alkaline solutions, as the aluminum ions released by corrosion would hydrolyse. Nitrate ions would not likely be present at concentrations comparable to those obtained when AI(N0 3h is the source of dissolved AI. Recently, ANL performed a series of head loss tests in which the source of AI being corrosion from AI alloy plates Bahn et aI., 2008d [14]. Tests were performed using Alloy 1100 and Alloy 6061. The objective of these tests was to compare the head loss resulting from precipitates formed from aluminum coupon corrosion with the head loss resulting from the use of precipitates prepared using the methodology presented in WCAP-16530-NP [Lane et aI.,
2006 [15)) or precipitates formed in-situ as a result of chemical injection.
Draft 8/17/2009 101
Post-test examination of the glass fiber bed and bench top test results showed that Fe-Cu enriched intermetallic6 particles were released by corrosion of the alloys and captured in the bed during the loop test. Differences in head loss behavior associated with the intermetallic particles were attributed to differences in the sizes of the intermetallic particles in Alloy 6061 and Alloy 1100. The AI corrosion vertical head loss loop tests in which the source of aluminum was the corrosion of Alloy 6061 and Alloy 1100 AI plates suggested that the solubility of aluminum in these tests was lower than that measured in tests where the source of aluminum was chemical addition. It was suggested that this was due to heterogeneous nucleation of AI hydroxide on intermetallic particles and/or on the surfaces of pre-existing AI hydroxide precipitates. It was concluded that the potential for corrosion of an AI alloy to result in increased head loss may be dependent on its microstructure, Le., the size distribution and number density of intermetallic particles, as well as on the AI release rate.
The solubilities were obtained from the available data on AI solubility in borated water presented by Bahn et aL [2008d [14)). This map of precipitation space is similar to the one developed by Guzonas [16], but the data are represented as pH + p[AI], allowing the two variables, pH and AI concentration, to be plotted against temperature in a single graph.
In the figure, a filled symbol indicates AI hydroxide precipitation was observed at that condition and an open symbol indicates AI hydroxide precipitation was not observed. The following data are included:
Data from ANL's long-term AI solubility bench top test data [Bahn et aL, 2008a [17));
Some room temperature data points from the previous ANL report [Park et aL, 2006 [9] ];
- The stable AI concentrations observed in ICET-1 and 5 [Dallman et aL, 2005a; Dallman et aL, 2005b [18));
Solubility test data by Westinghouse at 140 and 200°F; ANL bench top test data in sodium tetraborate solution [2008b [19] ];
The previous ANL head loss test data associated with AI hydroxide precipitates [Park et aL, 2006 [9]; Bahn et aL 2008c [20] ] including the two AI plate tests described in the report [Bahn et aL, 2008d [14] ] are designated as diamond symbols.
The observed decrease of pH + p[AI] as a function of temperature in Figure is a consequence of the dominant equilibrium:
AI(OHk = AI(OHh(s) + OH-.
(1 )
The equilibrium constant of the reaction can be expressed as K
[OH-]
(2) 14 -
[Al(OH)~]
Since AI(OHk is the dominant dissolved aluminum species in alkaline solution, the overall aluminum concentration is equal to [AI(OH)41 Therefore, pH + p[AI] =logK14 + pKw,
(3) 6 The intermetallic particles are primarily (FeSiAI) ternary compounds ranging in diameter from a few tenths of a micrometer to 10 !-Lm.
Draft 8/17/2009 102
and pH + p[AIJ represents the sum of logK14 and pKw.
Recently, Bahn et al. (2008) reported bounding estimates of aluminum solubility in alkaline environments containing boron [36].
Their most conservative curve, which bounds all the available data, is reproduced in Figure 24-6, along with the predicted aluminum concentrations for the three V.C. Summer cases examined. At pH 8.5, the predicted aluminum concentrations in the V.C. Summer sump are a factor of 7 to 10 lower than the most conservative solubility estimate, and no precipitation is expected. At pH 7.5, the predicted aluminum concentration lies just below the most conservative solubility estimate.
As both the calculated aluminum concentration and the solubility limit are considered conservative, precipitation is unlikely.
275 250 E 225 l!!
~ 200*
w
~ 175 -l-..w~JJllll--l...l.J.
150 -l-f-H-+HIH 125..JJ-H+f+l.11I 100.j=ttt.Ullll:+/-t 10" ICP 10'
, 0' lOS 10' 10" TlJ.lE (SECONDS)
ViRGIl C. SUMMER "uo.EAR STAYIO" lH'2H'8 SHEET 7-6 f'.EVlSION I' W'iJ4101 Figure 24-2 Post-LOCA temperature evolution of V.C. Summer sump.
Draft 8/17/2009 103
12.5 12.0 0
No precipitation
.8 11.5 0
~
0 aD 0
.0 0
8 00
~ 11.0 0
~
- c.
0
+
- r
- c. 10.5 10.0 0
0
- non-flocculation pre~itation 0
8 lilt lilt 9.5 flocculated precipitation ED 9.0 o No PPT
- ANL Loop PPT OANL Loop No PPt
- PPT. non-flocculated AANL, STB Benchtop
- PPT flocculated o ICET-1&5 x WCAP-16785
.VC Summer 60 80 100 120 140 160 180 200 220 Temperature (F)
Figure 24-5 pH + p[AI] as a function of temperature for amorphous aluminum hydroxide in borated alkaline water The calculated AI concentrations for the three V.C. Summer cases are also plotted on the graph.
Draft 8/17/2009 104
100
- J 0>
-S 10
~
~
0.1 +---..----,--.--------,----,--.--------,-------i 6
6.5 7
7.5 8
8.5 9
95 10 pH Figure 24-6 Solubility limit at 136.8 F based on the bounding estimates of aluminum solubility in alkaline environments containing boron presented by Bahn et al. (2008). The three V.C. Summer cases have been added.
Draft 8/17/2009 105
NRC RAI #25 Provide a table showing, for each of the VCSNS plant specific solubility cases evaluated, the following plant parameters: pH, temperature, amount of dissolved aluminum, and the assumed aluminum solubility.
SCE&G Response Table 25-1 lists the pH, temperature, submerged surface area, dissolved aluminum concentration and the solubility of aluminum inferred from the relevant literature data (borated alkaline water).
Table 25-1 Calculated AI concentrations in V.C. Summer post-LOCA sump water after 40 days.
pH Temp (F)"
Submerged Dissolved Assumed..
areas (fe)
Solubility
[AI]
0-2 Oh 40 d 2 h - 40 d (mg/kg)
(mg AI/kg) h Case 1 10.5 120 136.7 417.6 10.0 127 8.5 127 Case 2 10.5 8.5 120 136.7 212 5.1 120 136.7 417.6 6.27 12.7 Case 3 10.5 7.5
. Temperature evolution is shown in Error! Reference source not found..
.. Solubility of amorphous AI(OHh inferred from FiQure 24-5 at Day 40.
The submerged area for Case 1 and 3 is includes 6.3 fe on aluminum know to be submerged, 219.5 fe of aluminum without a specified location within the Reactor Building and 191.8 ft2 of operating margin for future application. Case 2 covers the more realistic scenario where the aluminum without a specific location and the operating margin are reduced by one half. This is reasonable since the submerged level is 8 ft above the floor while the Reactor Building extends over 180 ft above the floor level.
Draft 8/17/2009 106
27$ -
250 E 225 +-++J-Hl+!II-++
!200 -- =.
w
~ 175 125 100 10" 10 10' 10' 10' TIUE (SECONDS)
IrtAG It C. SUMMeIl NUClEAA STATlON lHl;!I*Ol~ SHEET 1*B AEVlSION II cr.v[}~l Figure 25-1 Post-LOCA temperature evolution of V.C. Summer sump 12.5 12.0 0
0 No precipitation
.8 11.5 0
0 0
.0
[J])
0 8
00 l
[
11.0 0
)
Co
+
0
~
- non-flocculation pre~itation
- I:
Co 10.5 Ci) 10.0 1/11 1/11 "
0 9.5 flocculated precipitation 1/11 9.0 60 80 100 120 140 160 180 200 Temperature (F)
PPT Loop PPT oANL Loop No PPt e PPT. non-flocculated
.6.ANL, STB Benchtop
- PPT flocculated o ICET-1&5 x WCAP-16785 eVC Summer 220 Figure 25-2 pH + p[AI] as a function of temperature for amorphous aluminum hydroxide in borated alkaline water The calculated AI concentrations for the three V.C. Summer cases are also plotted on the graph.
Draft 8/17/2009 107
NRC RAI #26 To account for plant-specific chemical effects, licensees have used a number of approaches including: adding pre-mixed chemical precipitate to integrated head loss tests; inducing precipitation in the head loss test loop; or performing longer term tests in simulated post-LOCA environments. For those licensees using pre-mixed chemical precipitate, i.e., the WCAP 16530-NP methodology, the NRC staff has accepted the assumption of three specific precipitates based on the predicted amount and properties of these precipitates bounding other precipitates that could form following a LOCA. Given that the VCSI\\lS analysis assumes no impact from chemical effects based solely on the assumption that aluminum hydroxide is not expected to form, please provide the technical basis that shows why precipitates other than aluminum hydroxide could not form in a post-LOCA environment and affect head loss across the sump strainer.
SCE&G Response In a sodium hydroxide plant, two precipitates have typically been considered to have the potential to form in the post-LOCA sump water: aluminum hydroxide (or oxyhydroxide) and some type (usually sodium) aluminosilicate.
Table 26-1 summarizes the major precipitates identified in the ICET tests; no aluminosilicate species were reported. This fact was recognized by the group that carried out the thermodynamic modeling [Jain et aI., 2006 [21)); they later repeated their modeling with the formation of aluminosilicates suppressed, as discussed below.
Table 26-2 lists the precipitates formed by the cooling of various simulated sump water solutions in the Westinghouse Owners Group (WOG) single tests [Lane, 2006 [22)). They reported the formation of aluminosilicates in three tests in which fiberglass was the starting material and the pH was 12.
This is perhaps not surprising as the starting material, fiberglass, is itself an aluminosilicate; cooling a solution of its high temperature dissolution products might be expected to reprecipitate an aluminosilicate.
There was little corrosion of any of the other alloys included in the ICET tests, and it can therefore be concluded that for sodium hydroxide plants there is little likelihood that precipitates involving these metals (e.g., iron, zinc) will form.
Table 26-1 Summary of Chemical Phases Identified during ICET Tests 1,4, and 5 (non-TSP tests).
Test ID Deposit Formula 1
tincalonite l\\Ia2B40 y*5H2O borax l\\la2B40s(OH)4'8H20 unknown Compound containing AI, B, Na, CO/
unknown Compound containing l\\la, B, AI 4
tobermorite Ca2.2S(SbOys(0 H)1s)(H2O) calcite CaC0 3 5
unknown Compounds containing 0, Na, AI, C, Ca Mg and Si Draft 8/17/2009 108
Table 26-2 Precipitates Formed by the Cooling of Various Simulated Sump Water Solutions in the mg'e ec s t
PWOG S*
I Eft t Tes s.
Type of Test and Conditions Precipitate (as identified by SEM)
Precipitation from cooling, AI at pH 4 Hydrated AIOOH Precipitation from cooling, AI at pH 8 Hydrated AIOOH Precipitation from cooling, AI at pH 12 Hydrated AIOOH Precipitation from cooling, other fiberglass, pH 12 NaAISi30 a with minor calcium aluminum silicate Precipitation from cooling, concrete, pH 4 Calcium aluminum silicate - AI rich Precipitation from cooling, mineral wool, pH 4 Hydrated AIOOH Precipitation from cooling, FiberFrax at pH 4 Hydrated AIOOH Precipitation from cooling, FiberFrax at pH 12 NaAISi30 a Precipitation from cooling, galvanized steel, pH 12 ZnSi04with Ca and AI impurities Calcium phosphate and a silicate Mixture of TSP and cal-sil Mixture of TSP and powdered concrete Calcium phosphate with AIOOH pH 12, 265 fiberglass with high calcium from pH 4 cal-sil Sodium calcium aluminum silicate Attempts have been made to use thermodynamic modeling [e.g., Jain et aI., 2005 [23)) to predict the possible chemical species that could precipitate in the post-LOCA sump water. For example, the results of Jain et al. suggested that sodium aluminosilicate with the composition of the naturally occurring mineral analbite, NaAISi30 a would be one of the dominant precipitating phases.
However, NaAISi30 a was not detected in the ICET tests (Table), although it was observed in the PWOG single effects testing (Table 26-2).
It was noted that, while these silicates are the thermodynamically stable phases, their formation is kinetically slow.
As an example of a typical thermodynamic prediction, we can consider the potential formation of fully disordered? albite, NaAISi30 s. Under the chemistry conditions expected in V.C. Summer post-LOCA sump water (a weakly alkaline solution), the dissolved aluminum and silicon are present as AI(OHk and Si(OH)4°:
NaAISi30 s + 8 H20 =Na+ + AI(OH)4- + 3 H4Si04° (1)
The thermodynamically calculated equilibrium constant for equation (1) for fully disordered albite, NaAlSi30 s can be expressed as [Arnorsson and Stefansson, 1999 [24)):
logK = -97.275 + 306.?65 _ 3313.51 _ 28.622x 10-6T 2 + 35.851x logT T
T where 7 The disordered form is expected to be less stable than the ordered form.
Draft 8/17/2009 109
and [Na+], AI(OH)4-and H4Si04 are the equilibrium concentrations.
At 60°C, the calculated equilibrium constant from equation (1) is K=1.11x10-20 or log (K) = -19.96. Table 24-1 lists the values of the logarithm of the concentration product, log (Q) for the ICET tests.
From Table, the logarithm of log (Q) in the ICET tests are between -10 and -14, which are greater than log (K). Thermodynamically, NaAISi30 4 should precipitate from these solutions, however, none of the tests observed the precipitation of sodium aluminosilicates including NaAISi30 4at 60°C and 25°C, probably due to kinetic factors.
Table 26-3
+
Concentrations of Na,AI(OH)4' and Si(OH)40 and log (Q) values from the ICET Tes ts.
Test ID
[Na+]
(molll)
[AI(OH)4] (molll)
[Si(OH)/]
(mol/l) log (Q)
Test 1 0.2391 1.41 x10-2 3.03x 10-4
-13.03 Test 2 0.0391 2.04x1O-4 3.21x10*3
-12.58 Test 3 0.0870
- 3. 70x 10-6 3.57x 10-3
-13.83 Test 4 0.5000 2.04x10-4 6.43x 10-3
-10.57 Test 5 0.0609 2.00x10-3 4.29x 10-4
-14.02 To clarify the apparent contradiction between experimental results and modeling results, AECl reviewed the published solubility and kinetics data on the formation of some relevant aluminosilicates. These data have been used to assess the likelihood that aluminosilicates will precipitate under post-lOCA sump water chemistry conditions.
Thermodynamic considerations When metallic aluminum and aluminum oxide or other salts dissolve in alkaline solutions, aluminum hydroxide can be produced. The amphoteric property of aluminum hydroxide makes it dissolves readily in strong acids and bases as shown in Figure 26-1Error! Reference source not found..
In the absence of any species that can form complexes with aluminum, the dominant aluminum species is AI(OHh between pH 7 and 9, while above pH 9, the dominant aluminum species in solution is hydrated aluminum ion, AI(OH)4-, with a regular tetrahedron structure when the concentration of aluminum is well below 0.1 molll [Arson, 1982 [25)).
As silicates or silica dissolve in water, various silicon species can be present depending on the pH of the solutions:
H4Si04 = H3Si04- + H+
(1 )
H3Si04' = H2SiO/- + H+
(2) 3 H2SiO/- = HSi04 - + H+
(3) 3 4
HSi04 - = Si04 - +H+
(4) 2H4Si04 = H6Si20 7 + H2O (5) 4 6
H20 +2Si04- = Si20 7 - + 2 OH-(6)
Draft 8/17/2009 110
Over the pH range 6.8 to 9.3 at 25°C, the dissolved silicon species are dominantly H4Si04
[Wilkin and Barnes, 1998 [26)).
Like AI(OH)4", the basic structure of the silicon species is tetrahedral.
7 T
a:::
6 UJ
-J.
5 w
-J 0
~
4
...J
..J
~
3
(.)
z 0
(.)
2
- I:
0
- J
<[
o o I 2
3 4
5 6
7 a 9 10 II 12 Figure 26-1 Solubility of AI(OHh as a function of pH [Wefers and Bell, 1972 [27)).
When aluminum and silicon species are both present in aqueous solution, polymerization of aluminum and silicon similar to the polymerization of silicon species shown in Equations (5) and (6) can occur to form various aluminosilicates. Depending on the AI/Si ratio and the pH of the solution, aluminosilicates such as feldspars, nepheline and zeolites can be produced, in which the molar ratio of AI/Si ranges from 0 to 1. The molar ratio of AI/Si in aluminosilicates usually follows Loewenstein's law [Loewenstein, 1954 [28)), which states that an AIO/- tetrahedron 5
cannot be connected with another AI04 - tetrahedron by a common oxygen atom. Hence, the maximum AI/Si ratio in aluminosilicates is 1: 1, and the silicon and aluminum tetrahedra alternate to form an ordered framework.
The solubilities of aluminosilicates depend on various factors including material structures, pH, temperature, Si/AI ratio and ionic strength. In alkaline solutions, a high pH generally increases the solubility of aluminosilicates; in acidic solutions, increasing acid concentration destroys the framework of aluminosilicates and increases the solubility. Figure 26-2 shows the solubility of nepheline (NaAISi04) glass at 25°C as a function of pH. Near neutral pH, nepheline has the lowest solubility; this behavior is also observed from the solubility data for jadeite and albite glasses [Hamilton, 2001 [29)). The effect of temperature on the solubility of aluminosilicates appears to be not well understood.
Both positive and negative temperature coefficients of solubility have been reported, even for the same type of material.
Draft 8/17/2009 111
500,--.-----..----
450
~ 400
~Si
'0 E 350
- .---AI
'b 300
..--Na
~ 250
~ 200
- g 150
~ 100 50 o+---.----,-:.=----,-:---.-...1--....---....----.----1 o
2 4
10 12 14 Figure 26-2 Solubility of nepheline glass as a function of pH at 25°C.
120.,----------------------------,
100
...J
/0
~Si
'0 80 E
E 0/
.~
60 AI 0
..c
~o*
0
'0
- I 40 Ul 20 0+----,-----,---,---,----,----,-----1 o
20 40 60 80 100 120 140 Figure 26-3 Solubility of amorphous sodium aluminosilicate NaAISi04 in 3 M NaOH as a function of temperatures. Squares are from Mensah et al. [2004] [30]; Circles are from Ejaz and Jones [1999] [31].
Kinetics Of Aluminosilicate Precipitation The post-LOCA sump water in a PWR is not an equilibrium system; the physical and chemical conditions change over the strainer mission time. Therefore, predictions based on equilibrium thermodynamics are unlikely to give accurate predictions concerning the formation of precipitates due to chemical effects.
Instead, precipitate formation will be dominated by processes such as supersaturation, heterogeneous nucleation, colloid stabilization, and gel Draft 8/17/2009 112
formation, leading to the formation of amorphous or poorly crystalline phases [Torres, 2006
[32)). These phases are far more soluble than the thermodynamically most stable phases for the specified conditions. Typically, the nucleating phase possesses the lowest interfacial free energy of all candidate phases, with recrystallization to form more stable phases taking place over timescales longer than the period of coolant recirculation. These mechanisms must be taken into account when attempting to understand the behavior of chemical species in post LOCA sump water.
The crystalline aluminosilicates generally have very low solubilities in water, while the solubilities of the corresponding amorphous materials are much higher.
For example, the solubility of amorphous sodium aluminosilicate is about six times that of crystalline zeolite A in 3 M NaOH solutions at 25°C [Mensah et aI., 2004 [30)) although both have same chemical formula, NaAISi04. The solubility data for amorphous phases are important in understanding and predicting the formation of crystalline aluminosilicates and zeolites because amorphous phases usually form first, and these gradually transform to crystalline phases.
The mixing of alkaline aluminate and silicate solutions at particular concentrations typically results in the formation of aluminosilicate gels, which, upon heating in contact with the supernatant solution, are converted to aluminosilicates or zeolites. Gelation or precipitation may be delayed for long periods depending on the AI and Si concentration, pH, temperature and the nature of the cation.
Generally, the chosen synthesis conditions are far away from the equilibrium state, and supersaturated AI and Si solutions are commonly used to speed up the nucleation during the preparation of aluminosilicates.
The relation between supersaturation ratio and induction time find, i.e., time elapsed between mixing the aluminate and silicate solutions and the first visible sign (if any) of gel or precipitation formation, can be expressed empirically by the equation:
loge! ) = A + __B__
(8)
,nd T J (lOg(S)2 where A and B are dimensionless empirical constants; T is absolute temperature; S is supersaturation ratio, defined as (9) or s = [Si]
(10)
[Silq where [AI] and lSi] are the total concentrations of aluminum and silicon species in solution, respectively, and [AI]eq and [Si]eq are the total concentrations of aluminum and silicon species at the equilibrium state, respectively. It has been found that increasing the temperature and supersaturation ratio decreases the induction time for aluminosilicate formation.
The effect of pH appears to have two opposite effects on the precipitation of sodium aluminosilicate. Thermodynamically, lowering the pH decreases the solubility and increases the Draft 8/17/2009 113
supersaturation ratio. On the other hand, kinetic experiments show that sodium aluminosilicate solutions with relatively low [AI] and or lSi] concentrations (0.05 mol/kg) and low alkalinity (2 M) exhibited an extreme longevity with respect to precipitation [North et aI., 2001 [33)). This is one of the reasons that high alkaline concentrations are generally used to shorten the crystallization time of aluminosilicates [Ejaz and Jones, 1999 [31)).
In the ICET tests, the low alkaline concentrations (pH < 12) probably make sodium aluminosilicates difficult to precipitate.
Mensah et al. [2004] [30] measured the solubility of amorphous sodium aluminosilicate and crystalline zeolite at different aluminum concentrations. They found that increasing the aluminum concentration decreases the solubility of aluminosilicates (Error! Reference source not found. 26-4).
140
- J 120 "0 E 100 c:
0
+:i SO III D
c:
60 Q)
CJ c:
0 40 CJ en 20 0
0 0.1 0.2 0.3 0.4 0.5 AI concentration (mol/L)
Figure 26-4 Solubility of amorphous sodium aluminium silicate (NaAISi04) as a function of aluminium concentration at 30 and 65°C. The base solution contains 4.0 M of NaOH, 1.0 M NaN03 and 1.0 M NaN02 [Mensah et al. 2004].
(
Park and Englezos [2001] [34] measured the concentrations of AI and Si in various equilibrium states and constructed a useful solubility map to predict the precipitation conditions for sodium aluminosilicates (Figure 26-5). It can be seen that the concentration of aluminum decreases with increasing concentration of silicon in the solution, and vice versa.
It should be noted that the pH ([OH-]= 0.S9 1V1) in Figure 26-5 is greater than that of the ICET tests; a high pH increases the solubility of aluminosilicates. However, the dependence of the solubility of aluminosilicates on pH is weak at low hydroxide concentration ([OH-] < 1 M)
[Gasteiger et aI., 1992 [35]; Mensah et al. 2004 [30)).
Preliminary modeling, carried out before the first ICET results were available, used input values from peer-reviewed literature (corrosion/dissolution rates) and the ICET test plan (surfaces areas, water composition) [Jain et aI., 2005 [23)). It was assumed that the system was in thermodynamic equilibrium; no kinetic information was included. The most oversaturated phase was allowed to precipitate. The reactions were limited to those materials used in the ICET tests and excluded the uptake of CO2 from air. At pH 10, various amounts of silicate species were Draft 8/17/2009 114
predicted to form over time; the species predicted included CaSi03, Ca2MgsSis0 22(OHh, ZnSi04, Si02, NaAISi30 s, Fe3Si0401Q(OHb Ca3FeSi030 12, and ZnFe304.
However, silicate phases were not observed to form in the ICET tests. It was noted that, while these silicates are the thermodynamically stable phases, their formation is kinetically slow. Aluminum hydroxide was also not detected in the ICET tests, only aluminum oxyhydroxides. Hence the simulations were repeated with the formation of silicates and aluminum hydroxide suppressed. When the revised simulations were run for ICET Test 1 [Jain et aI., 2006 [21], reasonable predictions of the AI and Ca concentrations in solution were obtained for the first 720 h, after which the model overpredicted the concentrations of AI and Ca.
The concentrations of selected elements measured in the five Integrated Chemical Effects Tests (ICET) carried out by Los Alamos Laboratory at the University of New Mexico are listed in Table. Based on Figure 26-5 and the data in Table, it is expected that there should have been no sodium aluminosilicate precipitation in these tests, as observed.
Table 26-4 Concentration of Selected Elements in Water Samples taken from the ICET Tests.
Test 10 pH AI Fe Maximum concentration in water samples (mg/L)
Ni Cu Zn Mg Si Ca 1\\1 a P
Test 1 10 380 Nr nr 1.2 1.8 nr 8.5 15 5500 nr (no TSP)
Test 4 10 bd bd nr 0.3 bd bd 180 50 11500 nr (no TSP)
(5.5)
(0.3)
Test 5 8.5 54 bd nr 0.9 0.8 1
12 34 1400 nr (borax)
- below detection
- not reported Using the calculated aluminum concentration of V.C. Summer (about 2 to 10 mg AI/kg) and Figure 26-5, a silicon concentration greater than 0.1 mol/kg or 2800 mg/kg would be required for sodium aluminosilicate to precipitate. Such a high silicon concentration is unlikely in the V.C.
Summer sump water since the dissolved silicon concentration resulting from dissolution of the various types of debris in alkaline solution is typically below 200 mg Silkg H20. Hence, the precipitation of sodium aluminum silicates is unlikely to occur in the V.C. Summer post-LOCA sump water.
Draft 8/17/2009 115
-1.0 precipitation
-1.5
-2.0
~
'0 E -2.5
~
no precipitation 8'
-3.0
-3.5
-4.0 +----..-----.-------,------.-----,-----1
-4.0
-3.5
-3.0
-2.5
-2.0
-1.5
-1.0 log[Si] mol/kg Figure 26-5 Precipitation zones for sodium aluminosilicates at 25°C and 0.89 M hydroxide [Park and Englezos, 2001 [34)).
Precipitation Of Carbonates Under V.C. Summer Water Chemistry Conditions In general, many metal ions M2 + and M3 + can react with C0 3 2-to form carbonate precipitates, M(II)C03 or M(IIIh(C03h such as CaC03 and Gd2(C0 3h However, the precipitations of carbonates under V. C. Summer sump water chemistry condition (pH 7-10) are not issues because of following reasons.
(1) The solubility of CO2 in water is low, e.g., 6.64x10-6 mol/l at 50°C. As the temperature increases, the solubility of carbon dioxide decreases. For example, the solubility of CO 2 in water at 50°C is about half of that at 25°C while at 125°C the solubility of CO 2 is only 25%
of the value at 25°C. The evaporation of large amounts of water can form a thick layer of steam to further prevent the dissolution of CO2 from atmosphere. It is expected that the concentration of the dissolved CO 2 in V.C. Summer water is much lower than the solubility of CO2 at similar temperature.
(2) Under V.C. Summer sump water chemistry, bicarbonate ion (HC0 3-), not carbonate ion, cot, is the major dissolved carbon species in weakly alkaline solution (Figure 26-6). For example, more than 70% of the dissolved inorganic carbon species are present as bicarbonate at pH 10, while below pH 9, almost all of the dissolved inorganic carbon is bicarbonate.
Draft 8/17/2009 116
100 90 80 III Ql 70
'0 Ql Q.
III 60 l::
0
.c I'll 50 0-H2C03 0
l::
40 0
~
0 l!!
30
- u.
20 10 0
0 2
4 6
8 10 12 14 pH Figure 26-6 Inorganic carbon species distribution as a function of pH at 298 K.
(3) AI3(C03h and Fe2(C03h if present in water, are rapidly hydrolysed to form the hydroxides (AI(OHh or Fe(OHh) due to their much low solubility.
(4) The possibility of the precipitation of other carbonates such as Mg2+ and Ca2+ carbonates was considered. It was concluded that these precipitates are not issue for V.C. Summer, based on the following calculations.
Using pH =7.0 (25°C) as an example, we have the following:
Solubility of CO2 is 6.65x 10.6 at 50°C The use of the Ksp for CaC03 at 38.8°C (only available data) instead of 50°C should not effect the conclusion because the temperature change, and hence the Ksp change, in going from 38.8 to 50°C is not large. All Ksp values are from Martel [1964].
Draft 8/17/2009 117
Based on the distribution in Figure 26-6, the calculated carbonate concentration at pH 7 is The required minimum [Ca2+] for CaC03 precipitation is:
The required minimum [Mg 2+] for MgC03 precipitation is
[Mg 2+] = KW '[C0 3 2-] = 2.09 x10-s/1.31x10-8 = 1.59x103 M. Similar calculations can be carried out at pH 7.5 and 8.5, the pH values of the three V.C. Summer cases examined. The results are reported in Table.
Table 26-5 pH 7
7.5 8.5 M" "
MIg'2+
d C 2+ concen ra Ions
" 't f Inlmum an a
t f for preclpl a Ion 0 fM191CO3 andCaCO3*
[CO/OJ (M)
[Ca L+]
[Mg L +]
1.59x103 1.59x102 1.59 0.289 1.31 x1 0-8 0.0289 1.31 x10-7 1.31 x10-5 2.89xlO-4 At pH 7.5, it is not possible for the [Ca2+] and [Mg 2+] in the V.C. Summer sump to reach the required values, and precipitations of CaC03 and MgC03 is not expected. For pH 8.5, the precipitation of MgC03 is impossible because the dissolved magnesium concentration in the V.C. Summer sump water cannot reach the required value. However, the dissolved calcium concentration required for precipitation at pH 8.5 is only 2.89x 10-4 mol/kg or 16 mg/kg.
Particulate CaC03 precipitation was observed in ICET Test 3; however, the precipitated calcite was from the cal-sil samples used in the test. Typically, for precipitation of calcium carbonate to occur, an empirical law requires that the supersaturation degree is greater than 10, i.e., the concentration of Ca2 + should be greater than 160 mg/kg. Based on the materials used in V.C.
Summer, such a high concentration of calcium is unlikely. Hence, the precipitation of calcium concentration in V.C. Summer is unlikely to happen.
Draft 8/17/2009 118
Reference List for Chemical Effects RAI #24, #25 and #26
[1]
Virgil C. Summer Nuclear Station (VCSNS), Docket No. 50/395, Operating License No.
NPF-12, Supplemental Response to NRC Generic Letter 2004-02: Potential Impact of Debris Blockage on Emergency Recirculation During Design Basis Accident at Pressurized -Water Reactors. February 29, 2008
[2]
US NRC, V.C. Summer, Request for Additional Information, Supplemental Response Dated 2/29/2008 to Generic Letter (GL) 2004-02.
[3]
AECL Proposal No. GNP-700844-006, "NRC Requests for Additional Information (RAI) on Supplemental Response Dated 2/29/2008 to Generic Letter (GL) 2004-02",
2009 April.
[4]
Fisher, N.J., Cheng, Q., Haque, Z., "Large-Scale Testing for Replacement Passive Design Sump Strainers - Reflective Metal Insulation Blockage and Thin Bed Tests",
AECL Test Report V.C. Summer-34325-TR-001 Rev. 1,2007 November.
[5]
Cheng, Q., Fisher, N.J., "Large-Scale Testing for Replacement Passive-Design Sump Strainers - Coating Failure as Particles/Chips Test", AECL Test Report V.C.
Summer-34325-TR-002 Rev. 0, 2007 September.
[6]
Wesolowski, D.J. (1992) Aluminum Speciation and Equilibria in Aqueous Solutions: I.
The Solubility of Gibbsite in the System Na-K-CI-OH-AL(OH)4 from 0 to 100°C.
Geochim Cosmochim Ac 1992; 56: 1065-1092.
[7]
Benezeth, P., Palmer, D.A., Wesolowski, D.J. (2001) Aqueous High Temperature Solubility Studies. II. The Solubility of Boehmite at 0.03 m Ionic Strength as a Function of Temperature and pH as Determined by In-situ Measurements. Geochim Cosmochim Ac 2001; 65: 2097.
[8]
Apps, JA, Neil, ~I.M., Jun, C.H. (1998) Thermochemical Properties of Gibbsite, Bayerite, Boehmite, Diaspore and the Aluminate Ion between 0 and 350°C. Berkeley, CA: Lawrence Berkeley National Laboratory; 1988. Report No.: LBL-21482.
[9]
Park, J.H., Kasza, K., Fisher B, Oras J., Natesan K., Shack, W.J. (2006) Chemical Effects Head-loss Research in Support of Generic Safety Issue 191. Washington: US NRC; 2006. Report No.: NUREG/CR-6913.
[10]
Van Straten, H.A., De Bruyn, P.L. (1984) Precipitation from Supersaturated Aluminate Solutions. II. Role of Temperature. J Colloid Interf Sci 1984 ; 102: 260-277.
[11]
Vermeulen, A.C. (1975) Hydrolysis-precipitation Studies of Aluminum (III) Solutions 1.
Titration of Acidified Aluminum Nitrate Solutions. J Colloid Interf Sci 1975; 51: 449.
[12]
Klasky, M., Zhang, J., Ding, M., Letellier, B. (2006) Aluminum Chemistry in a Prototypical Post-Loss-of-Coolant-Accident, Pressurize-Water-Reactor Containment Environment. Los Alamos, NM: Los Alamos National Laboratory; 2006 December.
Report No.: LA-UR-05-4881, NUREG/CR-6915.
[13]
Toner, C.V., Sparks, D.L. Chemical Relaxation and Double Layer Model Analysis of Boron Adsorption on Alumina. Soil Sci Soc Am J 1995; 59: 395.
Draft 8/17/2009 119
[14]
Bahn, C.B., Kasza, K.E., Shack, W.J., Natesan, K. (2008d) Technical Letter Report on Evaluation of Head Loss by Products of Aluminum Alloy Corrosion. Argonne, IL:
Argonne National Laboratory; 2008 August.
[15]
Lane, A.E., Andreychek, T.S., Byers WA, Jacko, R.J., Lahoda, E.J., Reid, R.D.
(2006) Evaluation of Post-accident Chemical Effects in Containment Sump Fluids to Support GSI-191. Westinghouse; 2006 February 28. Report No.: WCAP-16530-NP, Rev. O.
[16]
Guzonas D. (2007) AECL Approach to Chemical Effects - Assessment and Bench-top Testing. Presented at the Public Meeting with Nuclear Energy Institute, Pressurized Water Reactor Owners Group, Licensees, and Sump Strainer Vendors to Discuss the Resolution of Generic Safety Issue 191; 2007 October 24. ADAMS Accession Number ML072980661.
[17]
Bahn, C.B., Kasza, K.E., Shack, W.J., Natesan, K. (2008a) Technical Letter Report on Evaluation of Long-term Aluminum Solubility in Borated Water Following a LOCA.
Argonne, IL: Argonne National Laboratory; 2008 February. ADAMS Accession Number ML081550043.
[18]
Dallman J, Letellier B, Garcia J, Madrid J, Roesch W, Chen D, Howe K, Archuleta L, Sciacca F, Jain BP. (2005b) Integrated Chemical Effects Test Project: Test #5 data report. Los Alamos, NM: Los Alamos National Laboratory; 2005. Report No.: LA-UR 05-9177.
[19]
Bahn, C.B., Kasza, K.E., Shack, W.J. (2008b) Technical Letter Report on Follow-on Studies in Chemical Effects Head-loss Research; Studies on WCAP Surrogates and Sodium Tetraborate Solutions. Washington: US NRC; 2008 February. ADAMS Accession Number ML070580086.
[20]
Bahn, C.B., Kasza, K.E., Shack, W.J., Natesan, K. (2008c) Technical Letter Report on Evaluation of Chemical Effects: Studies on Precipitates used in Strainer Head Loss Testing. Washington: US NRC; 2008 January. ADAMS Accession Number ML080600180.
[21]
Jain, B.P., Jain, V., McMurry, J., He, Z., Pan, Y.-M., Pabalan, R., Pickkett, D., Yang. L.
and Chiang, K. [2006]. Chemical Speciation Prediction: Technical Program and Results, slides for presentation during ARCS Thermal-Hydraulics Subcommittee Meeting, 2006 February 14-16.
[22]
Lane, A. [2006]. Evaluation of Post-Accident Chemical Effects in Containment Sump Fluids, presentation at the US NRC Public Meeting Regarding the PWR Sump Blockage Issues, 2006 February 9.
[23]
Jain, V., He, X. and Pan, Y.-M. [2005]. Corrosion Rate Measurements and Chemical Speciation of Corrosion Products using Thermodynamic Modeling of Debris Components to Support GSI-1 91 ", NUREG/CR-6873.
[24]
Arnorsson S. and Stefansson, A. [1999]. Assessment of Feldspar Solubility Constants in Water in the range OOto 350°C at Vapour Saturation Pressures, American Journal of Science, 299, 173-209.
[25]
Arnson, T.R. [1982]. The Chemistry of Aluminum Salts in Papermaking. TAPPI J. 65, 125.
Draft 8/17/2009 120
[26]
Wilkin, RT. and Barnes, H.L. [1998]. Solubility and Stability of Zeolites in Aqueous Solution: I. Analcime, Na, and K-clinoptilolite, Amer. Mineral, 83, 746.
[27]
Wefers, K. and Bell, G.M. [1972]. Oxides and Hydroxides of Aluminum. Technical Paper no. 19, Alcoa Research Laboratories.
[28]
Lowenstein, W., The Distribution of Aluminium in the Tetrahedra of Silicates and Aluminates, Amer. Mineral., 1954,39,92.
[29]
Hamilton, ~I.P., Brantley, S.L., Pantano, C.G., Criscenti, L.J. and Kubicki, J.D. [2001].
Dissolution of Nepheline, Jadeite, and Albite Glasses: Toward Better Models for Aluminosilicate Dissolution. Geochimica et Cosmochimica Acta, 65, 3683.
[30]
Mensah, J.A, Li, J., Rosencrance, S., and Wilmarth, W. [2004]. Solubility of Amorphous Sodium Aluminosilicate and Zeolite A Crystals in Caustic and Nitrate/Nitrite
-Rich Caustic Aluminate Liquors. J. Chem. Eng. Data, 49, 1682.
[31]
Ejaz, T. and Jones, AG. [1999]. Solubility of Zeolite A and its Amorphous Precursor under Synthesis Conditions. J. Chern. Eng. Data, 44, 574.
[32]
Peer Review of GSI-191 Chemical Effects Research Program, P.A Torres, NUREG 1861, 2006.
[33]
North, M.R, Fleischer, A and Swaddle, T.W. [2001]. Precipitation from Alkaline Aqueous Aluminosilicate Solution. Can. J. Chem. 79, 75.
[34]
Park, H. and Englezos, P. [2001]. Precipitation Conditions of Aluminosilicate Scales in the Recovery Cycle of Kraft Pulp Mills. Pulp &Paper Canada, 102, 20.
[35]
Gasteiger, H.A, Frederick, W.J., Streisel, RC. [1992]. Solubility of Aluminosilicates in Alkaline Solutions and a Thermodynamic Equilibrium Model. Ind. Eng. Chem. Res., 31, 1183.
[36]
C. B. Bahn, K. E. Kasza, W. J. Shack, and K. Natesan, Aluminum Solubility in Boron Containing Solutions as a Function of pH and Temperature, September 19, 2008, Argonne National Laboratory.
[37]
Martel, AE. [1964]. Stability constants of metal-ion complexes, the Chemical Society, Burlington House.
[38]
Cobble, J.W. and Lin, S.W. [1989]. Chemistry of steam cycle solutions: properties in the ASME Handbook on Water Technology for Thermal Power Systems, edited by P.
Cohen, The American Society of Mechanical Engineers, l\\Iew York.
Draft 8/17/2009 121
- 2 Question 3:
The NRC staff would like to see the licensee's basis for the erosion because the total percentage appears low.
Question 4:
The NRC staff questioned the tumbling velocity and the size categories used by the licensee, and would like to discuss them further.
Question 6:
The NRC staff questioned the basis for the debris generation, and would like to discuss it further.
Question 11: The NRC staff would like additional details of the licensee's bypass determination.
Question 22: The NRC staff requested additional details on how the topical report data was used in the licensee's calculations.
Questions 24 to 26:
The NRC staff did not find the licensee's arguments that there would be no chemical effects for VCSNS to be convincing and concluded that chemical effects should be addressed for the VCSNS.
Prior to concluding the meeting, it was agreed that an additional conference call can be held to discuss items (3), (4), (6), (11), and (22), above, and to determine if the proposed responses adequately address the staffs concerns or whether additional information is still required.
Members of the public did not participate in this conference call.
IRA!
Robert E. Martin, Senior Project Manager Plant Licensing Branch 11-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-395
Enclosures:
- 1. List of Attendees
- 2. Draft Responses to NRC Request for Additional Information Distribution via ListServ DISTRIBUTION PUBLIC LPL2-1 R/F RidsAcrsAcnw_MailCTR Resource RidsNrrDorlDpr Resource RidsNrrDorlLpl2-1 Resource RidsNrrDRA Resource RidsNrrLASRohrer Resource RidsNrrPMSummer Resource RidsOgcMailCenler RidsRgn2MailCenler Resource DDiaz-Toro, EDO R*II SBailey, NRR RidsNrrDorl CTucci RidsNrrDsslSSIB ADAMS Accession Number' ML093000573 NRC-001 OFFICE LPL2-1/PM LPL2-1/LA NRRlDSS/SSIB/BC LPL2-1/BC NAME RMartin SRohrer MScott (SBailey for)
GKulesa DATE 10/29/09 10/29/09 11/2109 11/5/09 OFFICIAL RECORD COPY