ML092800358
| ML092800358 | |
| Person / Time | |
|---|---|
| Site: | Surry |
| Issue date: | 09/30/2009 |
| From: | Price J Dominion, Virginia Electric & Power Co (VEPCO) |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| 09-455B | |
| Download: ML092800358 (40) | |
Text
VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 September 30, 2009 1 OCFR50.90 U. S. Nuclear Regulatory Commission Serial No.
09-455B ATTN: Document Control Desk SPS/LIC/CGL R2 Washington, D. C. 20555 Docket Nos.
50-280/281 License Nos.
DPR-32/37 VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)
SURRY POWER STATION UNITS 1 AND 2 PROPOSED LICENSE AMENDMENT REQUEST ONE-TIME ALTERNATE REPAIR CRITERIA FOR STEAM GENERATOR TUBE INSPECTION/REPAIR FOR UNITS 1 AND 2 A July 28, 2009 Dominion letter (Serial No.09-455) requested a license amendment to revise the Surry Power Station Units 1 and 2 Technical Specifications (TS).
The proposed change requested revision of the inspection scope and repair requirements of TS 6.4.Q, "Steam Generator (SG) Program," and the reporting requirements of TS 6.6.A.3, "Steam Generator Tube Inspection Report." The proposed change requested approval of permanent alternate repair criteria (PARC) to exclude portions of the tube below the top of the steam generator tube sheet from periodic steam generator tube inspections. Westinghouse WCAP-17092-P, Revision 0, "H*: Alternate Repair Criteria for the Tubesheet Expansion Region in Steam Generators with Hydraulically Expanded Tubes (Model 51F)," was included as Attachment 5 in the July 28, 2009 letter and provides the basis for the proposed change. The license amendment request (LAR) also included proposed revisions to TS 3.1.C and TS 4.13, which are both titled "RCS Operational Leakage," to delete a primary to secondary leakage limitation that was included as part of the modified interim alternate repair criteria previously approved for the Surry Unit 1 B SG. Associated revisions to the Bases for TS 3.1.C and TS 4.13 were also included for the NRC's information.
On August 14, 2009, an NRC request for additional information (RAI) was communicated to Dominion regarding the Model 51F Westinghouse WCAP-17092-P and the Surry PARC LAR transmitted by the July 28, 2009 letter. Dominion provided the response to the RAI by a September 16, 2009 letter (Serial No. 09-455A).
On September 2, 2009, during a teleconference between NRC and industry personnel, the NRC Staff indicated that Staff concerns with eccentricity of the tube sheet tube bore in normal and accident conditions (RAI Question 4) have not been adequately resolved to justify a permanent, generic application of the WCAP. The Staff further indicated that there was insufficient time to resolve their concerns to support approval of the permanent amendment request for plants with fall 2009 refueling outages. As such, Dominion is proposing to revise the proposed permanent change contained in the July 28, 2009 LAR to be a one-time change to TS 4.13, TS 6.4.Q and TS 6.6.A.3 for Surry Unit 2 during the fall 2009 Refueling Outage 22 and the subsequent operating Apx
[4Za
Serial No. 09-455B Docket Nos. 50-280/50-281 Page 2 of 3 cycle and to TS 3.1.C, TS 4.13, TS 6.4.Q and TS 6.6.A.3 for Unit 1 during the fall 2010 Refueling Outage 23 and the subsequent operating cycle. The justification for this one time alternate repair criteria license amendment using the permanent H* value is provided in Attachment 1.
The marked-up TS and Bases pages are provided in, and the proposed TS and Bases pages are provided in Attachments 3 and 4 for Surry Units 2 and 1, respectively, due to their differing implementation dates.
The requested one-time change does not expand the scope of the request originally transmitted.
The one-time change also does not affect the conclusion of the no significant hazards consideration discussion provided in our July 28, 2009 letter and as published by the NRC in the Federal Register (Accession No. ML092020471).
Dominion requests approval of the proposed license amendments contained herein by October 16, 2009 with a 30-day implementation period to support the Surry Unit 2 Refueling Outage (fall 2009). The one-time change will be implemented on Unit 2 prior to the startup following the fall 2009 Unit 2 Refueling Outage 22 and on Unit 1 prior to the startup following the fall 2010 Unit 1 Refueling Outage 23.
Dominion also requests that the NRC Staff provide the specific questions remaining to be resolved with respect to the eccentricity of the tube sheet tube bore in normal and accident conditions (RAI Question 4) and that the review of the permanent alternate repair criteria license amendment request continue.
If you have any questions or require Mr. Gary D. Miller at (804) 273-2771.
additional information, please contact Sincerely, J. la rice V ePesident-Nuclear Engineering COMMONWEALTH OF VIRGINIA COUNTY OF HENRICO
))
)
The foregoing document was acknowledged before me, in and for the County and Comm'onwrealth aforesaid, today by J. Alan Price, who is Vice President - Nuclear Engineering, of Virginia, Electric and Power Company. He has affirmed before me that he is duly authorized to execute and file the foregoing document in behalf of that Company, and that the statements in the document are true to the best of his knowledge and belief.
Acknowledged before me this ' _day of_-4ý*
4*,2009.
My Commission Expires:
-'-Gt".-' 2S P/Z_
Notary Public
" ::""" 7 " -:,,'A..
Serial No. 09-455B Docket Nos. 50-280/50-281 Page 3 of 3 Commitments made in this letter: See Attachment 5 - List of Regulatory Commitments Attachments:
- 1. Justification for One-Time Alternate Repair Criteria Using the Permanent H* Value
- 2. Marked-up of Technical Specifications and Bases Pages
- 3. Proposed Unit 2 Technical Specifications Pages (Implement Fall 2009)
- 4. Proposed Unit 1 Technical Specifications and Bases Pages (Implement Fall 2010)
- 5. List of Regulatory Commitments cc:
U.S. Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW Suite 23T85 Atlanta, Georgia 30303 NRC Senior Resident Inspector Surry Power Station State Health Commissioner Virginia Department of Health James Madison Building - 7th Floor 109 Governor Street Room 730 Richmond, Virginia 23219 Ms. K. R. Cotton NRC Project Manager U. S. Nuclear Regulatory Commission One White Flint North Mail Stop 16 E15 11555 Rockville Pike Rockville, Maryland 20852-2738 Dr. V. Sreenivas NRC Project Manager U. S. Nuclear Regulatory Commission One White Flint North Mail Stop 8 H4A 11555 Rockville Pike Rockville, Maryland 20852-2738
Serial No. 09-455B Docket Nos. 50-280/50-281 ATTACHMENT 1 JUSTIFICATION FOR ONE-TIME ALTERNATE REPAIR CRITERIA USING THE PERMANENT H* VALUE VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)
SURRY POWER STATION UNITS I AND 2
Serial No. 09-455B Docket Nos. 50-280/50-281 Page 1 of 1 JUSTIFICATION FOR ONE-TIME ALTERNATE REPAIR CRITERIA USING THE PERMANENT H* VALUE The permanent H* submittal in Dominion's July 28, 2009 letter (Serial No.09-455) is based on maintaining structural and leakage integrity in the event of an accident.
From a structural perspective, the 16.7 inch value of H* ensures that tube rupture or tube pull out from the tube sheet will not occur in the event of an accident over the life of the plant.
Even in the event that all tubes in the steam generator have a 360 degree sever at 16.7 inches, structural integrity of the steam generator tube bundle will be maintained.
This assumption bounds the current status of the Surry Units 1 and 2 steam generators with significant margin.
At Surry, tube flaw indications within the tube sheet have only been found at the hot leg tube ends.
Approximately 24,725 tube ends have been recently inspected at Surry.
Two hundred sixteen (216) flaw indications have been reported.
These indications were located within 1 inch of the tube end and are associated with residual stress conditions at the tube ends. Twelve (12) tubes in Unit i and six (6) tubes in Unit 2 were plugged for tube end cracks.
In addition, over 50% of the overexpansion/bulge indications within the tubesheet have been inspected in both Unit 1 and Unit 2 with no degradation found.
Based on these inspections, no indications of a 360 degree sever have been detected in any steam generator at Surry.
Consequently, the level of degradation in the Surry steam generators is very limited compared to the assumption of "all tubes severed" that was utilized in the development of the permanent H* value. Thus, structural integrity will be assured for this one-time interim alternate repair criteria for the operating period between inspections allowed by TS 6.4.Q, "Steam Generator (SG) Program."
From a leakage perspective, projections of accident induced steam generator tube leakage are based on leakage rate factors applied to leakage detected during normal operation. The multiplication factor used for Surry bounds the expected increased leakage in the event of an accident at Surry. The projected accident induced leakage remains the same for both this one-time request and the permanent H* amendment request.
No primary to secondary steam generator tube leakage has been detected during the current operating cycles at Surry.
For Surry, the number. of tubes identified with flaws within the tubesheet is small in comparison to the input assumptions used in the development of the permanent H* value.
Consequently, significant margin exists between the current state of the Surry steam generators and the conservative assumptions used as the basis for the permanent H* value.
Structural and leakage integrity will continue to be assured for the operating period between inspections allowed by TS 6.4.Q, "Steam Generator (SG) Program," with the implementation of this proposed one-time alternate repair criteria using the permanent H* value.
Serial No. 09-455B Docket Nos. 50-280/50-281 ATTACHMENT 2 MARKED-UP TECHNICAL SPECIFICATIONS AND BASES PAGES VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)
SURRY POWER STATION UNITS 1 AND 2
TS 3.1-13 "9-&779-..
C.
RCS Operational LEAKAGE Applicability The following specifications are applicable to RCS operational LEAKAGE whenever Tavg (average RCS temperature) exceeds 200'F (200 degrees Fahrenheit).
Specificatiouis
- 1. RCS operational LEAKAGE shall be limited to:
- a. No pressure boundary LEAKAGE,
- b. 1 gpm unidentified LEAKAGE,
- c. 10 gpm identified LEAKAGE, and
- d. 150 gallons per day primary to secondary LEAKAGE through any one steam Spe~rati' cy]23.---
2.a. If RCS operational LEAKAGE is not within the limits of 3.l.C. I for reasons other than pressure boundary LEAKAGE. or primary to secondary LEAKAGE, reduce LEAKAGE to within the specified limits within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
- b. If the LEAKAGE is not reduced to within the specified limits within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, the unit shall be brought to HOT SHUTDOWN within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDOWN withffi the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
- 3.
If RCS pressure boundary LEAKAGE exists, orf primary to secondary LEAKAGE is not within the limit specified in 3.1.C..d,.the unit shall be brought toHOT SHUTDOWN within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
Amendment Nos.
and 250
TS 3,1-14a This LCO deals with protection of the reactor coolant pressure boundary (RCPB) from degradation and th6 core from inadequate cooling. in addition to preventing the accident analyses radiation release assumptions from being exceeded. The consequences of violating this LCO include the possibility of a loss of coolant accident (LOCA).
APPLICABLE SAFETY ANALYSES - Except for primary to secondary LEAKAGE, the safety analyses do not address operational LEAKAGE. However, other operational LEAKAGE is related to the safety analyses* for LOCA; the amount.of leakage can affect the probability of such an event. The safety analysis for an event resulting in steam discharge to the atmosphere assumes that
.primary to secondary. LEAKAGE from alt steam generators (SGs) Is I gpm or increases to I gpm as a result of accident induced conditions. The LCO requirement to limit primary to secondary LEAKAGE through any one SG to less than or equal to 150 gallons per day is significantly less than the conditions assumed in the safety analysis 'ii tO t cperme ility vaaion in ication n th njif JA Stea geeaorf d dun ýg Ref ling tae 1opfi. ry to sy ondar cak aNte fr Zat se enator /irited j6 20 ga*ns o e/day forOperatdt Cycle Primary to secondary LEAKAGE is a factor in the dose releases outside containment resulting from a main steam line break (MSLB) accident. Other accidents or transients involve se~ondary steam. release to the.atmosphere, such as a steam generator tube rupture (SGTR.). The leakage contaminates the secondary fluid.
'Te UFSAR (Ref, 2) analysis for SOTR assumes the contaminated secondary fluid is released via power operated relief valves or safety v.alves. The source term in the primary system coolant is transported to the affected (ruptured) steam generator by the break flow. The affected steam generator discharges steam to-th6 environment for 30 minutes until the generator is manually isolated. The I gpm primary 0o secondary LEAKAGE transports the source term to the unaffected steam generators. Releases continue through the unaffected steam generators until the Residual Heat Removal System is placed in service.
The MSLB is less limiting for site radiation releases than the SGTR, The safety analysis for the MSLB accident assumes I gpm total primary. to secondary LEAKAGE, including 500 gpd leakage into the faulted generatpr, The dose consequ.ences resulting from the MSLB and the SGTR accidents are within the limits defined in the plant licensing basis.
The RCS operational LEAKAGE satisfies Criterion 2 of 10 CFR 50.36(c)(2)(ii).
LIMITING CONDITIONS FOR OPERATION - RCS operational LtAKAGE shall be limited to:
- a. Pressure Boundary LEAKAG3E No pressure boundary LEAKAGE is allowed, being indicative of material deterioration.
LEAKAGE of this type is unacceptable as the leak itself could cause further deterioration, resulting in higher LEAKAGE. Violation of this LCO could result in continued degradation of the RCPB. LEAKAGE past seals and gaskets is not pressure boundary
- LEAKAGE, Amendment NOS..
and 250
TS 3.1-14b
- b. Unidentified LEAKAGE One gallon per minute (gpm) of unidpntified LEAKAGE is allowed as a reasonable minimum detectable =nount that the containment airmonitoring and coptainment sumnp level monitoring equipment can detect within a reasonable time period. Violation of this LCO could result in confinued degradation of the RCPB, if the LEAKAGE is from the pressure boundary.
- c. Identified LEAKAGE Up to 10 gpm of identified LEAKAGE is considered allowable because LEAKAGE is from known sources that do not interfere with detection of unidentified LEAKAGE and is well within the capability of the RCS Makeup System. Identified LEAKAGE includes LEAKAGE (o the containment from specifically known and located sources, but does not include pressure boundary LEAKAGE or controlled reactor coolant pump (RCP) seal leakoff (a normal function not considered LEAKAGE). Violation of this LCO could result in continued degradation of a component or system.
- d. Primary to Secondary LEAKAGE through Any One SG The limit of 150 gallons per day pe' SG'is based on the operational LEAKAGE performance criterion in NBI 97-06, Steam Oenerator Program Guidelines (Ref. 3). The Steam Generator Program operational LEAKAGE performance criterion in NEI 97-06 states, "The RC*S operational primary to secondary leakage through any one SG shall be limited to 150 gallons per day." The linMt is based on operating experience with SG tube, degradation mechanisms that result in tube leakage. The operational leakage rate criterion in conjunction with the implementation of the Steam Generator Program is an effective measure for minimizing the.frequency of steam. generator tube ruptures.!me toie pe, cabi vy ation *dicatio s in th Unit I/ stea genera ir fount/dwir Refe ng tage 2, th prim to se ndary rat for th steam/neratis li..tedto 0 galo sper, ay-for'peradn Gyc 23 APPLICABILITY - In REtACTOR OPERATION conditions Where Tavg exceeds 2000F, the potential for RCPB LEAKAGB is greatest when the RCS'is pressurized.
In COLD SHUTDOWN and REFUELING SHUTDOWN, LEAKAGE limits are not required because the reactor coolant pressure is far lower, resulting in lower stresses and reduced potentials for LEAKAGE.
LCO 3.1.C.5 measures leakage through each individual pressure isolation valve (PIV) and can impact this LCO. Of the two PIVs in series in each isolated 'line, leakage measured through one PIV does not result in RCS LEAKAGE when the other is leaktight. If both valves leak and result in a loss of mass from the RCS, the loss must be included in the allowable identified LEAKAGE.
Amendment Nos.
4 and 250
TS 4.13-1 4.13 RCS OPERATIONAL LEAKAGE Applicability The following specifications are applicable to RCS operational LEAKAGE whenever Tavg (average RCS temperature) exceeds 200*F (200,degrees Fahrenheit).
Objective To verify that RCS operational LEAKAGE is maintained within the allowable limits.
Specifications A.
Verify RCS operational LEAKAGE is within the limits specified in TS 3.1.C by performance of RCS water inventor balance once every 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />s1'12 1B. Verify primary to secondary LEAKAGE is :5 150 gallons per day through any one LE 4A0Y for th/Unit I ste 9-4 raor ill b e rifle/ to be -5 gallo e
Notes:
I.
Not required to be completed until 12hou after establishment of steady state operation.
, -tlr I
H'
- 2.
Not applicable to primary to secondary LEAKAGE.' pS vi*y i-".e-AkA iF-o 4
BlASES -
ný ~d v i v, Sa)a I -I-hL.
SURVEILLANCE REQUMRMENTS (SR) pwY\\~oS.Y
~
1A SR4.13.A
,ssucnda )ke V,;n-Saf c'V 'if-1\\
Verifying RCS LEAKAGE to be within the Limiting Condition for Operation (LCO) limits ensures the integrity.of the reactor coolant pressure boundary (RCPB) is maintained. Pressure boundary LEAKAGE would at first appear as unidentified LEAKAGE and can only be positively identified by inspection. It should be noted that LEAKAGE past seals and gaskets is not pressure boundary LEAKAGE. Unidentified LEAKAGE and identified LEAKAGE are determined by performance of an RCS water inventory balance.
The RCS water inventory balance must be performed with the reactor at steady state operating conditions (stable pressure, temperature, power level, pressurizer and makeup tank levels, makeup and letdown, and RCP seal injection and return flows). The surveillance is modified by two notes.
Note I states that this SR is not required to be complcted until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after establishing steady state operation. The 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> allowance provides sufficient time to collect and process all necessary data after stable unit comiditions are established.
Amendment Nos.)and*
TS 4.13-2 Steady state operation is required to perform a proper inventory balance since calculations during maneuvering are not useful. For RCS operational LEAKAGE determination by water inventory balance, steady state is defined as stable RCS pressure., temperature, power level, pressurizer and makeup tank levels, makeup and letdown; and RCP seal injection and ritura flows.
An early warning of pressure boundary LEAKAGE or unidentified LEAKAGE is provided by the automatic systems that monitor the containment atmosphere radioactivity and the containment sumnp level.-It should be noted that LEAKAGE past seals andgaskets-is not pressure boundary LEAKAGE. These leakage detection systems am specified in the TS 3.1.C Bases.
Note 2 States that this SR is not applicable to primary to secondary LEAKAGE because LEAKAGE of 150 gallons per day cannot be measured accurately by an RCS water inventory balance.
The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> frequency is a reasonable interval to trend LEAKAGE and recognizes the importance of early leakage detecti.on in the prevention of accidents.
SR 4,13.3 This SR verifies that primary to scondary LEAKAGE is less than or equal to 150 gallons rda through any ono SG, IW the,* owj g ec ti.,m e prioary toD onda' LEAKAX for tt LJit
- Ystc*.gonq*ator ill bimit Ito 2
alo er d durinn Oerati C
23.
a ing the primary to secondary LEAKAGE limit ensures that the operational LEAKAGE performance criterion in the Steam Generator Program is met. If this SR is not met, compliance with LCO 3.1.H, "Steam Generator Thbe Integrity,' should be evaluated, The 150 gallons per day limit is measured at room temperature as described in Reference 4, The-operational LEAKAGE rate limit applies to LEAKAGE through any one SG.
If it is not practical to assign the LEAKAGE to an individual SP, all the primary to secondary LEAKAGE should be conservatively assumed to be from one SG$ or it i jatJo Yagecoul
- ,*af~me/(0 e6ougK the2*-stearr/grne.*tor fo*Oprrag ýy/_e 23.[Th-e surveillance is--
modified by a Note, which states-that the Surveillance is not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after establishment of steady state operation. For RCS primary to secondary LEAKAGE determination, steady state is defined as stable, RCS pressure, temperature, power level, pressuriz*r and makeup tank levels, makeup and letdown, and RCP seal injection and return flows.
The surveillance frequency of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is a reasonable interval to trend primary to secondary LEAKAGE and recognizes the importance of early leakage detection in the prevention of accidents. The primary to secondary LEAKAGE is determined using continuous process radiation monitors or radiochemicl grab sampling in accordanice with the BPRI gui.delines (Ref. 4).
Amendment Nos. 264 and 250
TS 6.4-12
- c. The operational LEAKAGE performance criterion is specified in TS 3.1.C and 4.13, "RCS Operational LEAKAGE."
- 3. Provisions for SG tube repair criteria. Tubes found by inservice inspection to contain flaws with a depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged.
The following alternate tube repair criteria shall be applied as an alternative to the 40% depth-based criteria:
[INSERT*"]
2
- a. ForUnit2 eueifgO age an esu seque opera c, u eswit flaws ing a circu erential c ponent les an or equal 203 degrees fou in the port of the tub low 17 in es from the p of the tub ct a
above 1 i from the ttomn of the besheet do t require plu ging.
bes wi aws havin a circumfere al compone greater than 3 degrees found i he portion the tube bel 17 inches ram the top o -e tubesheet and ova I incl ram the botto of the tube eet shall be r oved from s
ice.
Tubes
- service-ind ad flaws I td within the gion fromn the tof the tube aet to 17 inc s below the p of the tubesh t shall be rem ed from s
ice. Tubes
- service-n ced axial crac found in the tion of the ube below inches from e top of the tu Sheet do not re uire plugging.
When ore than one w with circum rential compo nts is found in a
por n of the tube. low 17 inches uon the top of a tubesheet an above inch from the ttom of the tu h
- et with the otal of the circu erential components eater than 20 egrees and an jal separation i tance of less than In
, then the tub all be remove rom service.
en the circu erential corn nents of each of e flaws are ad dit is accep le, to co t the overla ad portions only oc in the total circumferen i I omponents.
When o or more flaws wi circumferenti components found in th port n of the u wt inch from the ottom of the esheet, and t total these circurnferent' components eeds gr
, then the tu shall be removed from ser ce. When one more flaws w! circufre.'ae components ar ound in the pa ion of the tube ithin 1 inch om the bott m of the tubes eat and within nch axial Sepa on distanc of a flaw ab e 1 inch fro the bottom of t tubesheet an he total of es circumfer ntial Amendment Nos.>
INSERT 1 For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, tubes with service-induced flaws located greater than 16.7 inches below the top of the tubesheet do not require plugging. Tubes with service-induced flaws located in the portion of the tube from the top of the tubesheet to 16.7 inches below the top of the tubesheet shall be plugged upon detection.
V TS 6.4-13 comp ents oxceed egr~ees, eni T ru.~ edial] be removed ro service.
W n the cit-e erential co iponents of ach of the flaws ar added, it is ceptable. t count the vorlapped ortions only ono n~ the total of circumfer tial compo nts.
For U I Refucli Outage 22 d the subsequent ' crating cycle tube fla having a roumferentj compoiient less - an or equal to 203; esre-es fnd in ale rtion of -th be below 17 inc s from the. top of the besheet and abo v Iinch fro e bottom of the ibe~heet do not r
're plugging.
Trubes idi flaws ha rig a circumferen I I component great an 203 degrebs fou in the por
- n of the tube be 17 inches from top of the tubesh tabov I i oh from the bo m of the tubesh shall be remove rom service.
'rubes ith service-in cod flaws locat ithin the region fr the to p of fte tub.heeL to.17 in es be,]ow th6 to 1 the, tubesheet s be removed from rvice. Tube.
ith service-ind d axial cracks fo d in the poition of the tube below inches from tb op of the tiubesh onot require pluggin When ore than one f with circurrfer tial components Is f d
din the po 'on of the tube ow 17 inches fro the top of the tubes tand above I ch from the
-torn of the tube eet with the total of. -
circuraferenti' I component.'
cater than 203 ees and an axial se ration distance ess than I1' ch, then the t a shell be remove row ser~vice.
en the circ ferential cop ntof each of the s are added, i t i acceptable to ont the overl ed portions only cc in the total circumferentl I components.
When e or more flaws wi circumferentia oraponents are nd in the por ni of the tube within inch from the tomn of the tubes t, and the, total
- these circumferment components ee ees 94 dogreeos, en the tube 4hala removed from' rvice. When e or more flaw with circumfc atl,ý,
components e foud in the rtion of the tube hin I inch fEm a~ bottom of th esh, und
-in1inh axialsep tion distance o flaw abov1 inc rmtebt oftoubesheet id the total of t o circumferent' I mponenls ex eds 94 degrees, t thetbshlbreodfoms i.
When the 'cumferential. coi onents of each the flaws are a ed, it is Zaccept le to count the vet-lapped port-ns only onc= i c total of.
cir fercatial camp rits.
C.
or Ulnit 1 Refue i g Outage 22 an e subsequent op ting cycle, tu in the B steam ge ator with per-me ity variation ind' Lions that may ask flaws in the b ow one inch of tubosheet do not quire plugging.
AmndemNos N d2
TS 6.4-13a
- 4. Provisions for SG tube inspections. Periodic SG tube inspections shall be performed. The number and portions of the tubes inspected and methods of inspection shall be performed with the' objective of detecting flaws of any type (e.g., volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube repair criteria.L'he tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of 4.a, 4.b, and 4.c below, the inspection scope, inspection methods, and inspection intervalsshall be such as to ensure that SG tube integrity is maintained until the next SG inspection. An assessment of degradation shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.
- b. Inspect 100% of the tubes at sequential periods of 120, 90, and, thereafter, 60 effective full power months. The first sequential period shall be considered to begin after the first inservice inspection of the SGs. In addition, inspect 50% of the tubes by the refueling outage nearest the midpoint of the period and the remaining 50% by the refueling outage nearest the end of the period. No SG shall operate for more than 48 effective full power months or two refueling outages (whichever is less) without being inspected.
- c. If crack indications are found in then the next inspection for each of.b e
SG for the degradation mechanism that caused the crack indication shall not 4,_,
e-n 0 -_F.exceed 24 effective full power months or one refueling outage (whichever is less). If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack.
- 5. Provisions for monitoring operational primary to secondary LEAKAGE.
Amendment No. 263/258
INSERT 2 For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, portions of the tube greater than 16.7 inches below the top of the tubesheet are excluded from this requirement.
TS 6.6-3
- b. The results of specific activity analysis in which the primary coolant exceeded the limits of Specification 3.1.D.4. In addition, the information itemized in Specification 3.1.D.4 shall be included in this report.
- 3. Steam Generator Tube Inspection Report A report shall be submitted within 180 days after Tavg exceeds 200'F following completion of an inspection performed in accordance with the Specification 6.4.Q, Steam Generator (SG) Program. The report shall include:
- a. The scope of inspections performed on each SG,
- b. Active degradation mechanisms found,
- c. Nondestructive examination techniques utilized for each degradation mechanism,
- d. Location, orientation (if linear), and measured sizes (if available) of service induced indications,
- e. Number of tubes plugged during the inspection outage for each active degradation mechanism,
- f. Total number and percentage of tubes plugged to date,
- g. The results of condition monitoring, including the results of tube pulls and in-situ testing, ei-d-
- h. The effective plugging percentage for all plugging in each SGC N E
- i.
Follo ng comp tion of a U it 2 inspecilon peorfon in Refuel' g Outage 2
and any spections erformed the subse bunt operati cycle), th number findicatio and locat' n, size, or' ntation, wh her initiate on pri ary or seconry side fo ach service nduced fla within the t ihkness of the tubes et, and th otal of the rcumferent I compones and any circumf ential over p below 17j ches from e top of th tubeshee as deter mined in a'c dance with T 6.4.Q.3.a, Amendment Nos.->-$*
INSERT 3
- i. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, the primary to secondary LEAKAGE rate observed in each SG (if it is not practical to assign the LEAKAGE to an individual SG, the entire primary to secondary LEAKAGE should be conservatively assumed to be from one SG) during the cycle preceding the inspection which is the subject of the report, and
- j.
For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during-Refueling Outage 23 and the subsequent operating cycle, the calculated accident induced LEAKAGE rate from the portion of the tubes below 16.7 inches from the top of the tubesheet for the most limiting accident in the most limiting SG.
In addition, if the calculated accident induced LEAKAGE rate from the most limiting accident is less than 2,03 times the maximum operational primary to secondary LEAKAGE rate, the report should describe how it was determined.
- k. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, the results of the monitoring for tube axial displacement (slippage). If slippage is discovered, the implications of the discovery and corrective action shall be provided.
TS 6.6-3a
- j. Fýlio.g completi n of a Unit 2 npccon perrmed in RefucH g Outage 21 nd any ins ections perfo ed in the an sequont operatg cycle), the imary to S ndary LEA GE rate obs ed in each stea generator (if it is not prac ' at to ass-ign akage to a ndividual SG, entire primary second y LBAKAG should bo c servatively assu d to be from one earn gen ator) durin e cycle prec ing the inspectio which is the sub' ct of the r ort, and k.Following ompletion of Unit 2 inspectio performed in
-fueling Outage 21 (an any inspeci' ns performed in t subsequent orating cycle), the cale uted accide leakage rate from e portion of t etube below 17 inche low the top f the tube*heet the moist Ii "ing accident in the ost limiting stea generator.
- 1. Pollowi completion of a,nit I inspeci performed in Refn ing Outage 22- ( d any inspection performed in e subsequent oper ng cycle), the n nber of indicatio s and loeatio, size, orientation, wether initiated on primary or secon try side for eservice-induced ftI within the thickne of the tubes et, and the to of the circurnfer tial components a abny circumnfer ntial overlap low 17 inches fr.
the top of the tub, heet as deter `bed in accorda ce with TS 6.4.Qr3 i'n. Fowing comple o*n of a Unit I in ection performed in cfueling Outage 22 (and any i pections perdfo din the subseqpent perating cycle),
e primrn~y t ecoondary LEA Erate observed in e steam generator fit is not p tical to assign I ~kage to an individ I SO, the entire imary to ondary LEAKAG should be conserva' ely assumed tobe, om one steam generator) durin e cycle. preceding e inspection which' the subject of tI
- report,
- n. Followi completion of a U t I inspection pert med in Refiuelin utage 22 nd any inspections rformed in the su equent operatin ycle), the alculated accident le age rate from the p t'on of the tube, I inches below the, top of the tub ect for the most Hi iting accident in e most limiting steam generator and Amendment Nos.X4 and.(%
TS 6.6-3b
- o.
Fol wing co pletion of nit 1 ins ction peifo
.d in Refueli,
Outage 22 and any o er inspec ns perfor d in the sub quent oparat g cycle), for e
B ste generato ah nurnbe of permeab. ty variation i ications ine ding loc ion and to 1 circumfe etiall eextenn t~
Amendment Nos.
Serial No. 09-455B Docket Nos. 50-280/50-281 ATTACHMENT 3 PROPOSED UNIT 2 TECHNICAL SPECIFICATIONS PAGES (IMPLEMENT FALL 2009)
VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)
SURRY POWER STATION UNITS 1 AND 2
TS 4.13-1 4.13 RCS OPERATIONAL LEAKAGE Applicability The following specifications are applicable to RCS operational LEAKAGE whenever Tavg (average RCS temperature) exceeds 200'F (200 degrees Fahrenheit).
Objective To verify that RCS operational LEAKAGE is maintained within the allowable limits.
Specifications A.
Verify RCS operational LEAKAGE is within the limits specified in TS 3.1.C by performance of RCS water inventory balance once every 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />'1' 2 B.
Verify primary to secondary LEAKAGE is < 150 gallons per day through any one SG once every 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, with the following exception. The primary to secondary LEAKAGE for the Unit 1 B steam generator will be verified to be < 20 gallons per day during Operating Cycle 23.1 If it is not practical to assign the LEAKAGE to an individual SG, all the primary to secondary LEAKAGE should be conservatively assumed to be from one SG.
Notes:
- 1. Not required to be completed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after establishment of steady state operation.
- 2.
Not applicable to primary to secondary LEAKAGE.
BASES SURVEILLANCE REQUIREMENTS (SR)
SR 4.13.A Verifying RCS LEAKAGE to be within the Limiting Condition for Operation (LCO) limits ensures the integrity of the reactor coolant pressure boundary (RCPB) is maintained. Pressure boundary LEAKAGE would at first appear as unidentified LEAKAGE and can only be positively identified by inspection. It should be noted that LEAKAGE past seals and gaskets is not pressure boundary LEAKAGE. Unidentified LEAKAGE and identified LEAKAGE are determined by performance of an RCS water inventory balance.
The RCS water inventory balance must be performed with the reactor at steady state operating conditions (stable pressure, temperature, power level, pressurizer and makeup tank levels, makeup and letdown, and RCP seal injection and return flows). The surveillance is modified by two notes.
Note 1 states that this SR is not required to be completed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after establishing steady state operation. The 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> allowance provides sufficient time to collect and process all necessary data after stable unit conditions are established.
Amendment Nos. 264 and
TS 6.4-12
- c. The operational LEAKAGE performance criterion is specified in TS 3.1.C and 4.13, "RCS Operational LEAKAGE."
- 3. Provisions for SG tube repair criteria. Tubes found by inservice inspection to contain flaws with a depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged.
The following alternate tube repair criteria shall be applied as an alternative to the 40% depth-based criteria:
- a. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, tubes with service-induced flaws located greater than 16.7 inches below the top of the tubesheet do not require plugging. Tubes with service-induced flaws located in the portion of the tube from the top of the tubesheet to 16.7 inches below the top of the tubesheet shall be plugged upon detection.
Amendment Nos. 251 and
TS 6.4-13
- b.
For Unit I Refueling Outage 22 and the subsequent operating cycle, tubes with flaws having a circumferential component less than or equal to 203 degrees found in the portion of the tube below 17 inches from the top of the tubesheet and above 1 inch from the bottom of the tubesheet do not require plugging.
Tubes with flaws having a circumferential component greater than 203 degrees found in the portion of the tube below 17 inches from the top of the tubesheet and above 1 inch from the bottom of the tubesheet shall be removed from service.
Tubes with service-induced flaws located within the region from the top of the tubesheet to 17 inches below the top of the tubesheet shall be removed from service. Tubes with service-induced axial cracks found in the portion of the tube below 17 inches from the top of the tubesheet do not require plugging.
When more than one flaw with circumferential components is found in the pdrtion of the tube below 17 inches from the top of the tubesheet and above 1 inch from the bottom of the tubesheet with the total of the circumferential components greater than 203 degrees and an axial separation distance of less than 1 inch, then the tube shall be removed from service. When the circumferential components of each of the flaws are added, it is acceptable to count the overlapped portions only once in the total of circumferential components.
When one or more flaws with circumferential components are found in the portion of the tube within 1 inch from the bottom of the tubesheet, and the total of these circumferential components exceeds 94 degrees, then the tube shall be removed from service. When one or more flaws with circumferential components are found in the portion of the tube within 1 inch from the bottom of the tubesheet and within 1 inch axial separation distance of a flaw above I inch from the bottom of the tubesheet, and the total of these circumferential components exceeds 94 degrees, then the tube shall be removed from service.
When the circumferential components of each of the flaws are added, it is acceptable to count the overlapped portions only once in the total of circumferential components.
- c.
For Unit 1 Refueling Outage 22 and the subsequent operating cycle, tubes in the B steam generator with permeability variation indications that may mask flaws in the bottom one inch of the tubesheet do not require plugging.
Amendment Nos. 264 and
TS 6.4-13a
- 4. Provisions for SG tube inspections. Periodic SG tube inspections shall be performed. The number and portions of the tubes inspected and methods of inspection shall be performed with the objective of detecting flaws of any type (e.g., volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube repair criteria. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, portions of the tube greater than 16.7 inches below the top of the tubesheet are excluded from this requirement. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of 4.a, 4.b, and 4.c below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. An assessment of degradation shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.
- b. Inspect 100% of the tubes at sequential periods of 120, 90, and, thereafter, 60 effective full power months. The first sequential period shall be considered to begin after the first inservice inspection of the SGs. In addition, inspect 50% of the tubes by the refueling outage nearest the midpoint of the period and the remaining 50% by the refueling outage nearest the end of the period. No SG shall operate for more than 48 effective full power months or two refueling outages (whichever is less) without being inspected.
- c. if -crack indications are found in the portions of the SG tube not excluded above, then the next inspection for each SG for the degradation mechanism that caused the crack indication shall not exceed 24 effective full power months or one refueling outage (whichever is less). If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack.
- 5. Provisions for monitoring operational primary to secondary LEAKAGE.
Amendment Nos. 263 and
TS 6.6-3
- b. The results of specific activity analysis in which the primary coolant exceeded the limits of Specification 3. 1.D.4. In addition, the information itemized in Specification 3.1.D.4 shall be included in this report.
- 3. Steam Generator Tube Inspection Report A report shall be submitted within 180 days after Tavg exceeds 200'F following completion of an inspection performed in accordance with the Specification 6.4.Q, Steam Generator (SG) Program. The report shall include:
- a. The scope of inspections performed on each SG,
- b. Active degradation mechanisms found,
- c. Nondestructive examination techniques utilized for each degradation mechanism,
- d. Location, orientation (if linear), and measured sizes (if available) of service induced indications,
- e. Number of tubes plugged during the inspection outage for each active degradation mechanism,
- f. Total number and percentage of tubes plugged to date,
- g. The results of condition monitoring, including the results of tube pulls and in-situ testing,
- h. The effective plugging percentage for all plugging in each SG,
- i. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, the primary to secondary LEAKAGE rate observed in each SG (if it is not practical to assign the LEAKAGE toan individual SG, the entire primary to secondary LEAKAGE should be conservatively assumed to be from one SG) during the cycle preceding the inspection which is the subject of the report, and
- j.
For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, the calculated accident induced LEAKAGE rate from the portion of the tubes below 16.7 inches from the top of the tubesheet for the most limiting accident Amendment Nos. 251 and
TS 6.6-3a in the most limiting SG. In addition, if the calculated accident induced LEAKAGE rate from the most limiting accident is less than 2.03 times the maximum operational primary to secondary LEAKAGE rate, the report should describe how it was determined.
- k. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, the results of the monitoring for tube axial displacement (slippage). If slippage is discovered, the implications of the discovery and corrective action shall be provided.
- 1. Following completion of a Unit I inspection performed in Refueling Outage 22 (and any inspections performed in the subsequent operating cycle), the number of indications and location, size, orientation, whether initiated on primary or secondary side for each service-induced flaw within the thickness of the tubesheet, and the total of the circumferential components and any circumferential overlap below 17 inches from the top of the tubesheet as determined in accordance with TS 6.4.Q.3,
- m. Following completion of a Unit 1 inspection performed in Refueling Outage 22 (and any inspections performed in the subsequent operating cycle), the primary to secondary LEAKAGE rate observed in each steam generator (if it is not practical to assign leakage to an individual SG, the entire primary to secondary LEAKAGE should be conservatively assumed to be from one steam generator) during the cycle preceding the inspection which is the subject of the
- report,
- n. Following completion of a Unit 1 inspection performed in Refueling Outage 22 (and any inspections performed in the subsequent operating cycle), the calculated accident leakage rate from the portion of the tube 17 inches below the top of the tubesheet for the most limiting accident in the most limiting steam generator, and Amendment Nos. 264 and
TS 6.6-3b 05-07-09
- o.
Following completion of a Unit 1 inspection performed in Refueling Outage 22 (and any other inspections performed in the subsequent operating cycle), for the B steam generator, the number of permeability variation indications including location and total circumferential extent.
Amendment Nos. 264/---
Serial No. 09-455B Docket Nos. 50-280/50-281 ATTACHMENT 4 PROPOSED UNIT 1 TECHNICAL SPECIFICATIONS AND BASES PAGES (IMPLEMENT FALL 2010)
VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)
SURRY POWER STATION UNITS 1 AND 2
TS 3.1-13 C.
RCS Operational LEAKAGE Applicability The following specifications are applicable to RCS operational LEAKAGE whenever Tavg (average RCS temperature) exceeds 200'F (200 degrees Fahrenheit).
Specifications
- 1. RCS operational LEAKAGE shall be limited to:
- a. No pressure boundary LEAKAGE,
- b. I gpm unidentified LEAKAGE,
- c. 10 gpm identified LEAKAGE, and
- d. 150 gallons per day primary to secondary LEAKAGE through any one steam generator (SG).
2.a. If RCS operational LEAKAGE is not within the limits of 3.1.C.1 for reasons other than pressure boundary LEAKAGE or primary to secondary LEAKAGE, reduce LEAKAGE to within the specified limits within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
- b. If the LEAKAGE is not reduced to within the specified limits within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />, the unit shall be brought to HOT SHUTDOWN within the next.6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
- 3.
If RCS pressure boundary LEAKAGE exists, or primary to secondary LEAKAGE is not within the limit specified in 3.1.C.l.d, the unit shall be brought to HOT SHUTDOWN within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
Amendment Nos.
and 250
TS 3.1-14a This LCO deals with protection of the reactor coolant pressure boundary (RCPB) from degradation and the core from inadequate cooling, in addition to preventing. the accident analyses radiation release assumptions from being exceeded. The consequences of violating this LCO include the possibility of a loss of coolant accident (LOCA).
APPLICABLE SAFETY ANALYSES - Except for primary to secondary LEAKAGE, the safety analyses do not address operational LEAKAGE. However, other operational LEAKAGE is related to the safety analyses for LOCA; the amount of leakage can affect the probability of such an event. The safety analysis for an event resulting in steam discharge to the atmosphere assumes that primary to secondary LEAKAGE from all steam generators (SGs) is 1 gpm or increases to I gpm as a result of accident induced conditions. The LCO requirement to limit primary to secondary LEAKAGE through any one SG to less than or equal to 150 gallons per day is significantly less than the conditions assumed in the safety analysis.
Primary to secondary LEAKAGE is a factor in the dose releases outside containment resulting from a main steam line break (MSLB) accident. Other accidents or transients involve secondary steam release to the atmosphere, such as a steam generator tube rupture (SGTR). The leakage contaminates the secondary fluid.
The UFSAR (Ref. 2) analysis for SGTR assumes the contaminated secondary fluid is released via power operated relief valves or safety valves. The source term in the primary system coolant is transported to the affected (ruptured) steam generator by the break flow. The affected steam generator discharges steam to the environment for 30 minutes until the generator is manually isolated. The 1 gpm primary to secondary LEAKAGE transports the source term to the unaffected steam generators. Releases continue through the unaffected steam generators until the Residual Heat Removal System is placed in service.
The MSLB is less limiting for site radiation releases than the SGTR. The safety analysis for the MSLB accident assumes 1 gpm total primary to secondary LEAKAGE, including 500 gpd leakage into the faulted generator. The dose consequences resulting from the MSLB and the SGTR accidents are within the limits defined in the plant licensing basis.
The RCS operational LEAKAGE satisfies Criterion 2 of 10 CFR 50.36(c)(2)(ii).
LIMITING CONDITIONS FOR OPERATION - RCS operational LEAKAGE shall be limited to:
- a. Pressure Boundary LEAKAGE No pressure boundary LEAKAGE is allowed, being indicative of material deterioration.
LEAKAGE of this type is unacceptable as the leak itself could cause further deterioration, resulting in higher LEAKAGE. Violation of this LCO could result in continued degradation of the RCPB. LEAKAGE past seals and gaskets is not pressure boundary LEAKAGE.
Amendment Nos.
and 250
TS 3.1-14b
- b. Unidentified LEAKAGE One gallon per minute (gpm) of unidentified LEAKAGE is allowed as a reasonable minimum detectable amount that the containment air monitoring and containment sump level monitoring equipment can detect within a reasonable time period. Violation of this LCO could result in continued degradation of the RCPB, if the LEAKAGE is from the pressure boundary.
- c. Identified LEAKAGE Up to 10 gpm of identified LEAKAGE is considered allowable because LEAKAGE is from known sources that do not interfere with detection of unidentified LEAKAGE and is well within the capability of the RCS Makeup System. Identified LEAKAGE includes LEAKAGE to the containment from specifically known and located sources, but does not include pressure boundary LEAKAGE or controlled reactor coolant pump (RCP) seal leakoff (a normal function not considered LEAKAGE). Violation of this LCO could result in continued degradation of a component or system.
- d. Primary to Secondary LEAKAGE through Any One SG The limit of 150 gallons per day per SG is based on the operational LEAKAGE performance criterion in NEI 97-06, Steam Generator Program Guidelines (Ref. 3). The Steam Generator Program operational LEAKAGE performance criterion in NEI 97-06 states, "The RCS operational primary to secondary leakage through any one SG shall be limited to 150 gallons per day." The limit is based on operating experience with SG tube degradation mechanisms that result in tube leakage. The operational leakage rate criterion in conjunction with the implementation of the Steam Generator Program is an effective measure for minimizing the frequency of steam generator tube ruptures.
APPLICABILITY - In REACTOR OPERATION conditions where Tavg exceeds 200°F, the potential for RCPB LEAKAGE is greatest when the RCS is pressurized.
In COLD SHUTDOWN and REFUELING SHUTDOWN, LEAKAGE limits are not required because the reactor coolant pressure is far lower, resulting in lower stresses and reduced potentials for LEAKAGE.
LCO 3.1.C.5 measures leakage through each individual pressure isolation valve (PIV) and can impact this LCO. Of the two PIVs in series in each isolated line, leakage measured through one PIV does not result in RCS LEAKAGE when the other is leaktight. If both valves leak and result in a loss of mass from the RCS, the loss must be included in the allowable identified LEAKAGE.
Amendment Nos.
and 250
TS 4.13-1 4.13 RCS OPERATIONAL LEAKAGE Applicability The following specifications are applicable to RCS operational LEAKAGE whenever Tavg (average RCS temperature) exceeds 200'F (200 degrees Fahrenheit).
Objective To verify that RCS operational LEAKAGE is maintained within the allowable limits.
Specifications A.
Verify RCS operational LEAKAGE is within the limits specified in TS 3.1.C by performance of RCS water inventory balance once every 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. 1,2 B.
Verify primary to secondary LEAKAGE is < 150 gallons per day through any one SG once every 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. If it is not practical to assign the LEAKAGE to an individual SG, all the primary to secondary LEAKAGE should be conservatively assumed to be from one SG.
Notes:
- 1.
Not required to be completed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after establishment of steady state operation.
- 2.
Not applicable to primary to secondary LEAKAGE.
BASES SURVEILLANCE REQUIREMENTS (SR)
SR 4.13.A Verifying RCS LEAKAGE to be within the Limiting Condition for Operation (LCO) limits ensures the integrity of the reactor coolant pressure boundary (RCPB) is maintained. Pressure boundary LEAKAGE would at first appear as unidentified LEAKAGE and can only be positively identified by inspection. It should be noted that LEAKAGE past seals and gaskets is not pressure boundary LEAKAGE. Unidentified LEAKAGE and identified LEAKAGE are determined by performance of an RCS water inventory balance.
The RCS water inventory balance must be performed with the reactor at steady state operating conditions (stable pressure, temperature, power level, pressurizer and makeup tank levels, makeup and letdown, and RCP seal injection and return flows). The surveillance is modified by two notes.
Note 1 states that this SR is not required to be completed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after establishing steady state operation. The 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> allowance provides sufficient time to collect and process all necessary data after stable unit conditions are established.
Amendment Nos.
and 250
TS 4.13-2 Steady state operation is required to perform a proper inventory balance since calculations during maneuvering are not useful. For RCS operational LEAKAGE determination by water inventory balance, steady state is defined as stable RCS pressure, temperature, power level, pressurizer and makeup tank levels, makeup and letdown, and RCP seal injection and return flows.
An early warning of pressure boundary LEAKAGE or unidentified LEAKAGE is provided by the automatic systems that monitor the containment atmosphere radioactivity and the containment sump level. It should be noted that LEAKAGE past seals and gaskets is not pressure boundary LEAKAGE. These leakage detection systems are specified in the TS 3.1.C Bases.
Note 2 states that this SR is not applicable to primary to secondary LEAKAGE because LEAKAGE of 150 gallons per day cannot be measured accurately by an RCS water inventory balance.
The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> frequency is a reasonable interval to trend LEAKAGE and recognizes the importance of early leakage detection in the prevention of accidents.
SR 4.13.B This SR verifies that primary to secondary LEAKAGE is less than or equal to 150 gallons per day through any one SG. Satisfying the primary to secondary LEAKAGE limit ensures that the operational LEAKAGE performance criterion in the Steam Generator Program is met. If this SR is not met, compliance with LCO 3.1.H, "Steam Generator Tube Integrity," should be evaluated.
The 150 gallons per day limit is measured at room temperature as described in Reference 4. The operational LEAKAGE rate limit applies to LEAKAGE through any one SG.
If it is not practical to assign the LEAKAGE to an individual SG, all the primary to secondary LEAKAGE should be conservatively assumed to be from one SG. The surveillance is modified by a Note, which states that the Surveillance is not required to be performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after establishment of steady state operation. For RCS primary to secondary LEAKAGE determination, steady state is defined as stable RCS pressure, temperature, power level, pressurizer and makeup tank levels, makeup and letdown, and RCP seal injection and return flows.
The surveillance frequency of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is a reasonable interval to trend primary to secondary LEAKAGE and recognizes the importance-of early leakage detection in the prevention of accidents. The primary to secondary LEAKAGE is determined using continuous process radiation monitors or radiochemical grab sampling in accordance with the EPRI guidelines (Ref. 4).
Amendment Nos.
and 250
TS 6.4-12
- c. The operational LEAKAGE performance criterion is specified in TS 3.1.C and 4.13, "RCS Operational LEAKAGE."
- 3. Provisions for SG tube repair criteria. Tubes found by inservice inspection to contain flaws with a depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged.
The following alternate tube repair criteria shall be applied as an alternative to the 40% depth-based criteria:
- a. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, tubes with service-induced flaws located greater than 16.7 inches below the top of the tubesheet do not require plugging. Tubes with service-induced flaws located in the portion of the tube from the tubesheet to 16.7 inches below the top of the tubesheet shall be plugged upon detection.
Amendment Nos.
TS 6.4-13
- 4. Provisions for SG tube inspections. Periodic SG tube inspections shall be performed. The number and portions of the tubes inspected and methods of inspection shall be performed with the objective of detecting flaws of any type (e.g., volumetric flaws, axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube repair criteria. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit I for Refueling Outage 23 and the subsequent operating cycle, portions of the tube greater than 16.7 inches below the top of the tubesheet are excluded from this requirement. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of 4.a, 4.b, and 4.c below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. An assessment of degradation shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.
- b. Inspect 100% of the tubes at sequential periods of 120, 90, and, thereafter, 60 effective full power months. The first sequential period shall be considered to begin after the first inservice inspection of the SGs. In addition, inspect 50% of the tubes by the refueling outage nearest the midpoint of the period and the remaining 50% by the refueling outage nearest.the end of the period. No SG shall operate for more than 48 effective full power months or two refueling outages (whichever is less) without being inspected.
- c. If crack indications are found in the portions of the SG tube not excluded above, then the next inspection for each SG for the degradation mechanism that caused the crack indication shall not exceed 24 effective full power months or one refueling outage (whichever is less). If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s), then the indication need not be treated as a crack.
- 5. Provisions for monitoring operational primary to secondary LEAKAGE.
Amendment Nos.
TS 6.6-3
- b. The results of specific activity analysis in which the primary coolant exceeded the limits of Specification 3.1.D.4. In addition, the information itemized in Specification 3.1.D.4 shall be included in this report.
- 3. Steam Generator Tube Inspection Report A report shall be submitted within 180 days after Tavg exceeds 200°F following completion of an inspection performed in accordance with the Specification 6.4.Q, Steam Generator (SG) Program. The report shall include:
- a. The scope of inspections performed on each SG,
- b. Active degradation mechanisms found,
- c. Nondestructive examination techniques utilized for each degradation mechanism,
- d. Location, orientation (if linear), and measured sizes (if available) of service induced indications,
- e. Number of tubes plugged during the inspection outage for each active degradation mechanism,
- f. Total number and percentage of tubes plugged to date,
- g. The results of condition monitoring, including the results of tube pulls and in-situ testing,
- h. The effective plugging percentage for all plugging in each SG,
- i. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, the primary to secondary LEAKAGE rate observed in each SG (if it is not practical to assign the LEAKAGE to an individual SG, the entire primary to secondary LEAKAGE should be conservatively assumed to be from one SG) during the cycle preceding the inspection which is the subject of the report, and Amendment Nos.
TS 6.6-3a
- j. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit 1 during Refueling Outage 23 and the subsequent operating cycle, the calculated accident induced LEAKAGE rate from the portion of the tubes below 16.7 inches from the top of the tubesheet for the most limiting accident in the most limiting SG. In addition, if the calculated accident induced LEAKAGE rate from the most limiting accident is less than 2.03 times the maximum operational primary to secondary LEAKAGE rate, the report should describe how it was determined.
- k. For Unit 2 during Refueling Outage 22 and the subsequent operating cycle and for Unit I during Refueling Outage 23 and the subsequent operating cycle, the results of the monitoring for tube axial displacement (slippage). If slippage is discovered, the implications of the discovery and corrective action shall be provided.
Amendment Nos.
Serial No. 09-455B Docket Nos. 50-280/50-281 ATTACHMENT 5 LIST OF REGULATORY COMMITMENTS VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)
SURRY POWER STATION UNITS 1 AND 2
Serial No. 09-455B Docket Nos. 50-280/50-281 Page 1 of 1 LIST OF REGULATORY COMMITMENTS The following table identifies those actions committed by Dominion for Surry Power Station Units 1 and 2 with respect to the one-time alternate repair criteria for steam generator tube repair.
These commitments, which supersede those in our July 28, 2009 permanent alternate repair criteria license amendment request letter (Serial No.09-455), are a restatement of the commitments reflected in our September 16, 2009 permanent alternate repair criteria RAI response letter (Serial No. 09-455A).
Commitment Due Date/Event Dominion commits to monitor for tube slippage as part of Starting with Unit 2 the SG tube inspection program for Unit 1 and Unit 2.
Refueling Outage 22 and during subsequent Unit 1 and Unit 2 SG inspections Dominion commits to perform a one-time verification of Prior to the startup the tube expansion to locate any significant deviations in following Unit 2 the distance from the top of tubesheet to the beginning of Refueling Outage 22 expansion transition. If any significant deviations are and Unit 1 Refueling found, the condition will be entered into the plants Outage 23 corrective action program and dispositioned. Additionally, Dominion commits to notify the NRC of significant deviations.
Dominion commits to plug eleven Unit 2 tubes that have During the Unit 2 been identified as not being expanded within the Refueling Outage 22 tubesheet in either the hot leg or cold leg.
Dominion commits to plug three Unit 1 tubes that have During the Unit 1 been identified as not being expanded within the Refueling Outage 23 tubesheet in either the hot leg or cold leg.
Dominion commits to the following:
For the Condition For every operating Monitoring assessment, the component of operational cycle following leakage from the prior cycle from below the H* distance Unit 2 Refueling will be multiplied by a factor of 2.03 and added to the total Outage 22 and accident leakage from any other source and compared to Unit 1 Refueling the allowable accident induced leakage limit.
For the Outage 23 Operational Assessment, the difference between the allowable accident induced leakage and the accident induced leakagefrom sources other than the tubesheet expansion region will be divided by 2.03 and compared to the observed operational leakage.
An administrative operational leakage limit will be established to not exceed the calculated value.