RBG-46883, Unit 1, Supplement to License Amendment Request, Application for Technical Specification Change to Adopt NRC Approved Generic Changes TSTF-163, -222, -230 and 306
| ML090280215 | |
| Person / Time | |
|---|---|
| Site: | River Bend (NPF-047) |
| Issue date: | 01/23/2009 |
| From: | Roberts J Entergy Operations |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| RBF1-09-0012, RBG-46883 | |
| Download: ML090280215 (4) | |
Text
Entergy Operations, Inc.
River Bend Station 5485 U. S. Highway 61N St. Francisville, LA 70775 Tel 225 381 4149 En tergyFax 225 635 5068 jrober3@entergy.com Jerry C. Roberts Director, Nuclear Safety Assurance January 23, 2009 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555
Subject:
Supplement to License Amendment Request (LAR)
River Bend Station - Unit 1 Docket No. 50-458 License No. NPF-47
Reference:
LAR 2009-01, dated January 21, 2009 (Letter No. RBG-46763)
Application for Technical Specification Change to Adopt NRC Approved Generic Changes TSTF-163, -222, -230, and 306 File No.:
G9.5 RBF1-09-0012 RBG-46883
Dear Sir or Madam:
On January 21, 2009, Entergy Operations, Inc. submitted a request to amend the Technical Specifications (TS) for River Bend Station as described in the referenced letter (LAR 2009-01). During subsequent on-site processing of the proposed change, it was noticed that two pages of that letter contained a grammatical error. Specifically, pages 7 and 9 of Attachment 4 contain inserts indicating proposed changes to Surveillance Requirements in TS 3.8.1, "AC Sources - Operating." The word "and" was inadvertently omitted from those inserts. Copies of the original pages are attached to this letter, and have been annotated to indicate the needed correction.
If you have any questions, please contact Danny Williamson at 225-381-4279.
I declare under penalty of perjury that the foregoing is true and correct. Executed on January 23, 2009.
Sincerely,
" Jerry C. Roberts Director - Nuclear Safety Assurance
Supplement to License Amendment Request RBG-46883 January 23, 2009 Page 2 of 2 Attachments
- 1. Att. 4 to RBG-46763, page 7 of 11
- 2. Att. 4 to RBG-46763, page 9, of 11 cc:
U. S. Nuclear Regulatory Commission Region IV 612 East Lamar Blvd., Suite 400 Arlington, TX 76011-4125 NRC Senior Resident Inspector P. 0. Box 1050 St.' Francisville, LA 70775 U. S. Nuclear Regulatory Commission Attn: Mr. Carl F. Lyon Washington, DC 20555-0001 Mr. Jeffrey P. Meyers Louisiana Dept. of Environmental Quality Attn: OEC-ERSD P. O. Box 4312 Baton Rouge, LA 70821-4312 RBG-46763 Page 7 of 11 INSERT 3 Verify each DG starts and achieves:
- 1. In _510 seconds for DG 1A and DG 1B and *_13 seconds foi voltage _Ž3740 V and frequency Ž_58.8 Hz.
4
- 2. Steady state voltage Ž_3740 V and _<4580 V and frequency
!-61.2 Hz.
DG 1C
(
RBG-46763 Page 9 of 11 INSERT 4 Verify, when started simultaneously from standby condition, each DG achieves:
- 1. In <10 seconds for DG 1A and DG 1B and _s13 seconds for DG 1C voltage Ž_3740 V and frequency L-58.8 Hz.,,q
- 2. Steady state voltage >_3740 V and *<4580 V and frequency _Ž58.8 Hz and
- s61.2 Hz.