Evaluation of Relief Requests S2-I2-RR-B01 and S2-I2-RR-C01
ML081260365
Person / Time
Site: Salem PSEG icon.png
Issue date: 06/02/2008
From: Chernoff H
NRC/NRR/ADRO/DORL/LPLI-2
To: Levis W
Public Service Enterprise Group
Ennis R, NRR/DORL, 415-1420
References
S2-I2-RR-B01, S2-I2-RR-C01, TAC MD5977, TAC MD5978
Download: ML081260365 (33)


Text

June 2, 2008 Mr. William Levis President & Chief Nuclear Officer PSEG Nuclear LLC - N09 Post Office Box 236 Hancocks Bridge, NJ 08038

SUBJECT:

SALEM NUCLEAR GENERATING STATION, UNIT NO. 2 - EVALUATION OF RELIEF REQUESTS S2-I2-RR-B01 AND S2-I2-RR-C01 (TAC NOS. MD5977 AND MD5978)

Dear Mr. Levis:

By letter dated June 27, 2007, as supplemented by letter dated December 14, 2007, PSEG Nuclear LLC (PSEG) submitted relief requests S2-I2-RR-B01 and S2-I2-RR-C01 which requested relief from certain requirements specified in Section XI of the American Society of Mechanical Engineers Boiler and Pressure Vessel Code (ASME Code) for the inservice inspection (ISI) of Class 1 and Class 2 components at Salem Nuclear Generating Station (Salem), Unit No. 2. PSEG stated that it had conducted examinations as part of the second ten-year ISI interval to the extent practical. However, coverage for certain weld examinations was less than required by the ASME Code.

The U.S. Nuclear Regulatory Commission (NRC) staff, with technical assistance from its contractor, the Pacific Northwest National Laboratory, has completed its review of relief requests S2-I2-RR-B01 and S2-I2-RR-C01 as documented in the enclosed Safety Evaluation. The NRC staff concludes that the ASME Code examination coverage requirements are impractical for the subject welds listed in the relief requests. Based on the volumetric and/or surface coverage obtained, it is also concluded that, if significant service-induced degradation were occurring, there is reasonable assurance that evidence of it would have been detected by the examinations that were performed. As such, the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed. Therefore, the NRC staff is granting PSEGs requests for relief pursuant to 10 CFR 50.55a(g)(6)(i), for the second 10-year ISI interval at Salem Unit No. 2.

Granting relief pursuant to 10 CFR 50.55a(g)(6)(i) is authorized by law and will not endanger life or property, or the common defense and security, and is otherwise in the public interest given due consideration to the burden upon the licensee that could result if the requirements were imposed on the facility.

All other ASME Code,Section XI requirements for which relief was not specifically requested and approved in the subject requests for relief remain applicable, including third-party review by the Authorized Nuclear Inservice Inspector.

If you have any questions concerning this matter, please contact the Salem Project Manager, Mr. Richard Ennis, at (301) 415-1420.

Sincerely,

/ra/

Harold K. Chernoff, Chief Plant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-311

Enclosure:

As stated cc w/encl: See next page

If you have any questions concerning this matter, please contact the Salem Project Manager, Mr. Richard Ennis, at (301) 415-1420.

Sincerely,

/ra/

Harold K. Chernoff, Chief Plant Licensing Branch I-2 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-311

Enclosure:

As stated cc w/encl: See next page DISTRIBUTION PUBLIC RidsOgcRp TMcLellan, DCI/CVIB LPL1-2 R/F RidsAcrsAcnw&mMailCenter JWhite, Region I RidsNrrDorlLpl1-2 RidsRgn1MailCenter TOHara, Region I RidsNrrLAABaxter RidsNrrOd RidsNrrPMREnnis RidsNrrAdes SWilliams, EDO Region I DNaujock, DCI/CPNB Accession No.: ML081260365 OFFICE LPL1-2/PM LPL1-2/LA CVIB/BC CPNB/BC OGC LPL1-2/BC NAME REnnis ABaxter MMitchell TChan JBielecki HChernoff DATE 5/29/08 5/8/08 5/12/08 5/15/08 5/28/08 6/2/08 OFFICIAL RECORD COPY

Salem Nuclear Generating Station, Unit Nos. 1 and 2 cc:

Mr. Thomas Joyce Senior Vice President - Operations PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Dennis Winchester Vice President - Nuclear Assessment PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Robert Braun Site Vice President - Salem PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Carl Fricker Vice President - Operations Support PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. George Gellrich Plant Manager - Salem PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. James Mallon Manager - Licensing PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Steven Mannon Manager - Salem Regulatory Assurance PSEG Nuclear P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Jeffrie J. Keenan, Esquire PSEG Nuclear - N21 P.O. Box 236 Hancocks Bridge, NJ 08038 Township Clerk Lower Alloways Creek Township Municipal Building, P.O. Box 157 Hancocks Bridge, NJ 08038 Mr. Paul Bauldauf, P.E., Asst. Director Radiation Protection Programs NJ Department of Environmental Protection and Energy CN 415 Trenton, NJ 08625-0415 Mr. Brian Beam Board of Public Utilities 2 Gateway Center, Tenth Floor Newark, NJ 07102 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Senior Resident Inspector Salem Nuclear Generating Station U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, NJ 08038 Mr. William Levis President and Chief Nuclear Officer PSEG Nuclear, LLC P.O. Box 236 Hancocks Bridge, NJ 08038

Enclosure SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO RELIEF REQUESTS S2-I2-RR-B01 AND S2-I2-RR-C01 PSEG NUCLEAR LLC SALEM NUCLEAR GENERATING STATION, UNIT NO. 2 DOCKET NO. 50-311

1.0 INTRODUCTION

By letter dated June 27, 2007, as supplemented by letter dated December 14, 2007, (Agencywide Documents Access and Management System (ADAMS) Accession Nos.

ML071900437 and ML073620370, respectively), PSEG Nuclear LLC (PSEG or the licensee) submitted relief requests S2-I2-RR-B01 and S2-I2-RR-C01 which requested relief from certain requirements specified in Section XI of the American Society of Mechanical Engineers Boiler and Pressure Vessel Code (ASME Code) for the inservice inspection (ISI) of Class 1 and Class 2 components at Salem Nuclear Generating Station (Salem), Unit No. 2. PSEG stated that it had conducted examinations as part of the second ten-year ISI interval to the extent practical. However, coverage for certain weld examinations was less than required by the ASME Code.

2.0 REGULATORY EVALUATION

The ISI of ASME Code Class 1, 2, and 3 components is to be performed in accordance with Section XI of the ASME Code and applicable edition and addenda as required by Title 10 of the Code of Federal Regulations (10 CFR) Section 50.55a(g), except where specific relief has been granted by the Nuclear Regulatory Commission (NRC or Commission) pursuant to 10 CFR 50.55a(g)(6)(i). Pursuant to 10 CFR 50.55a(a)(3), alternatives to the requirements of paragraph (g) may be used, when authorized by the NRC, if the licensee demonstrates that:

(i) the proposed alternatives would provide an acceptable level of quality and safety, or (ii) compliance with the specified requirements would result in hardship or unusual difficulty without a compensating increase in the level of quality and safety.

Pursuant to 10 CFR 50.55a(g)(4), ASME Code Class 1, 2, and 3 components (including supports) must meet the requirements, except the design and access provisions and the preservice examination requirements, set forth in the ASME Code,Section XI, ARules for Inservice Inspection of Nuclear Power Plant Components,@ to the extent practical within the limitations of design, geometry, and materials of construction of the components. The regulation requires that inservice examination of components and system pressure tests conducted during the first 10-year interval, and subsequent intervals, comply with the requirements in the latest edition and addenda of Section XI of the ASME Code incorporated by reference in

10 CFR 50.55a(b) 12 months prior to the start of the 120-month interval, subject to the limitations and modifications listed therein. The Salem Unit No. 2 second ten-year ISI interval began May 10, 1992, and ended on November 23, 2003. The ISI Code of record for Salem Unit No. 2 for the second 10-year ISI interval was the ASME Code Section XI, 1986 Edition, with no addenda.

The subject relief requests were originally submitted by PSEG by letter dated March 21, 2006 (ADAMS Accession No. ML060950206). The NRC staff requested additional information (RAI) in a letter dated December 20, 2006 (ADAMS Accession No. ML063340284). The licensee was unable to provide the requested information in a timely manner, and based on discussions with the NRC staff, PSEG withdrew its request in a letter dated March 26, 2007 (ADAMS Accession No. ML070930448). PSEGs request dated June 27, 2007, resubmitted the original requests and incorporated the responses to the NRC staffs RAIs. As discussed in an NRC inspection report dated August 14, 2007 (ADAMS Accession No. ML072260460), a severity Level IV violation of 10 CFR 50.55a(g)(5)(iii) and 10 CFR 50.55a(g)(5)(iv) was identified since PSEG had not submitted the subject relief requests within 12 months following the completion of the second 10-year ISI interval for Salem Unit No. 2 (i.e., the subject relief requests should have been submitted by November 23, 2004). PSEGs letter dated September 13, 2007 (ADAMS Accession No. ML072680855), provided the licensees response to the NRCs notice of violation.

3.0 TECHNICAL EVALUATION

The NRC staff, with technical assistance from its contractor, the Pacific Northwest National Laboratory (PNNL), evaluated the information provided by PSEG in support of the subject relief requests. For clarity, the licensees request has been evaluated in several parts according to ASME Code Examination Category.

3.1 Request for Relief S2-I2-RR-B01 (Part A), Examination Category B-A, Items B1.12, B1.22, and B1.40, Pressure Retaining Welds in Reactor Pressure Vessel ASME Code Requirement ASME Code,Section XI, Examination Category B-A, Item B1.12 requires essentially 100 percent volumetric examination, as defined by Figure IWB-2500-2, of the length of one longitudinal reactor pressure vessel (RPV) shell weld during successive operating intervals 2 through 4. Item B1.22 requires essentially 100 percent volumetric examination of the accessible length of head welds, as defined by Figure IWB-2500-3.

Item B1.40 requires essentially 100 percent volumetric and surface examination of the head-to-flange weld, as defined by Figure IWB-2500-5. Essentially 100%, as clarified by ASME Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, is greater than 90 percent coverage of the examination volume, or surface area, as applicable. ASME Code Case N-460 has been approved for use by the NRC in Regulatory Guide (RG) 1.147, Revision 14, Inservice Inspection Code Case Acceptability.

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required 100 percent volumetric examination of Class 1 RPV welds 2-RPV-3442A, 2-RPV-3442B, and 2-RPV-3442C which are lower shell longitudinal welds at 60°, 180°,

and 300°, respectively, 2-RPV-1443C which is a head meridional weld at 30°, and 2-RPVCH-6446A which is a head-to-flange weld.

Licensees Basis for Relief Request (as stated)

Full [ASME] Code-required coverage is impractical for the identified subject components since the Reactor Pressure Vessel (RPV) would require design modifications that would impose a significant burden to PSEG. PSEG has examined the subject components to the extent practical and has determined them to be acceptable with no observed signs of degradation. In addition, other RPV welds have been examined to the extent required by the Code and also found to be acceptable with no observed signs of degradation. Also, VT-2 visual examinations performed in conjunction with system pressure testing after each refueling outage found these welds to be acceptable with no leakage observed.

Licensees Proposed Alternative Examination (as stated)

Where the component would not allow an ultrasonic angle beam examination from both sides of the weld, the following were performed using the best available technology at the time and as applicable, demonstrated through the [Electric Power Research Institute] EPRI [Performance Demonstration Initiative] PDI program:

Similar metal welds were examined to the extent practical using personnel and techniques qualified and demonstrated through the EPRI PDI, as applicable.

System pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires essentially 100 percent volumetric examination of the accessible length of the subject ASME Code Class 1 RPV welds. However, the geometry of the welds, along with interference from appurtenances such as core barrel supports and in-core instrumentation tubes located in close proximity to the welds, limits access for full volumetric examination. To gain access for examination, the RPV would require design modifications. Imposing this requirement would create a significant burden on the licensee; therefore, the ASME Code-required 100 percent volumetric examinations are impractical.

As shown on the sketches and technical descriptions included in the licensees submittals, examinations of the subject welds have been performed to the extent practical; with the licensee obtaining substantial volumetric coverage from approximately

79 percent to 88 percent. All of the subject examinations were performed using equipment, personnel and procedures qualified through the EPRI PDI.

In the case of RPV Welds 2-RPV-3442A, 2-RPV-3442B, and 2-RPV-3442C, which are lower shell course longitudinal welds at 60°, 180°, and 300°, respectively, integrally welded core barrel support lugs located adjacent to these welds limited ultrasonic scanning such that only 81 percent of the ASME Code-required coverage could be obtained. Weld 2-RPV-1443C is a head meridional weld located at 30° where nearby core instrumentation tubes restricted scanning and limited the ASME Code-required volumetric coverage to 88 percent. For Weld 2-RPVCH-6446A, an upper head-to-flange weld, only 79 percent volumetric coverage was obtained due to the outside surface transition which limited scans near this flange weld.

The licensee has shown that it is impractical to meet the ASME Code-required 100 percent volumetric examination coverage for the subject welds due to their design and proximity to other RPV components. Based on the substantial volumetric examination coverages obtained, it is concluded that if significant service-induced degradation were occurring, there is reasonable assurance that evidence of it would have been detected. As such, the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed.

3.2 Request for Relief S2-I2-RR-B01 (Part B), Examination Category B-B, Items B2.11 and B2.12, Pressure Retaining Welds in Vessels Other than Reactor Vessels ASME Code Requirement ASME Code,Section XI, Examination Category B-B, Items B2.11 and B2.12 require essentially 100 percent volumetric examination, as defined by Figures IWB-2500-1 and -2, respectively, of the circumferential shell-to-head weld and one foot of the intersecting longitudinal weld on the pressurizer. Essentially 100%, as clarified by ASME Code Case N-460, is greater than 90% coverage of the examination volume, or surface area, as applicable. ASME Code Case N-460 has been approved for use by the NRC in RG 1.147.

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required 100 percent volumetric examination of circumferential shell-to-head Weld 2-PZR-CIRC DUH, and one foot of intersecting longitudinal weld 2-PZR-LONG D on the pressurizer.

Licensees Basis for Relief Request (as stated)

Full [ASME] Code-required coverage is impractical for the subject components since these vessels would require design modifications that would impose a significant burden to PSEG. PSEG has examined these component welds to the extent practical and determined them to be acceptable with no observed signs of

degradation. In addition, other similar vessel welds have been examined to the extent required by the [ASME] Code and also found to be acceptable with no observed signs of degradation. Also, VT-2 visual examinations performed in conjunction with system pressure testing after each refueling outage found these welds to be acceptable with no leakage observed.

Licensees Proposed Alternative Examination (as stated)

Where the component will not allow an ultrasonic angle beam examination from both sides of the weld, the following were performed using the best available technology at the time and as applicable, demonstrated through the EPRI PDI program:

Similar metal welds were examined to the extent practical using personnel and techniques qualified and demonstrated through the EPRI PDI, as applicable.

System pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires essentially 100 percent volumetric examination of the accessible length of the subject pressurizer welds. However, for Welds 2-PZR-CIRC DUH and 2-PZR-LONG D, insulation supports restrict access for volumetric examinations. To gain access for complete examination, the vessel insulation supports would have to be removed and modified. Imposing this requirement would create a significant burden on the licensee; therefore, the ASME Code-required 100 percent volumetric examinations are impractical.

As shown on the sketches and technical descriptions included in the licensees submittals, examinations of the subject welds have been performed to the extent practical with the licensee obtaining volumetric coverage of approximately 74 percent for one foot of longitudinal Weld 2-PZR-LONG D and 37 percent for shell-to-upper head Weld 2-PZR-CIRC DUH. An insulation support ring clamped on the outside of the pressurizer head just above Weld 2-PZR-CIRC DUH severely restricts access to ultrasonic scans such that only approximately 140-degrees of the total 360-degree weld length could be volumetrically examined. For Weld 2-PZR-LONG D, a permanently installed insulation support bracket limited access for further volumetric examination.

The examinations were performed using personnel and techniques qualified and demonstrated through the industrys PDI, as administered by EPRI. No unacceptable indications were noted during the subject examinations.

The licensee has shown that it is impractical to meet the ASME Code-required 100 percent volumetric examination coverage for the subject welds due to their design and proximity of other components. However, based on the examinations performed, in combination with examination of ASME Code-required volumes in other welds on the pressurizer, it is concluded that if significant service-induced degradation were occurring, there is reasonable assurance that evidence of it would have been detected. As such,

the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed.

3.3 Request for Relief S2-I2-RR-B01 (Part C), Examination Category B-D, Item B3.120, Full Penetration Welds of Nozzles in Vessels ASME Code Requirement ASME Code,Section XI, Examination Category B-D, Item B3.120 requires 100 percent volumetric examination, as defined by Figures IWB-2500-7(a) through (d), as applicable, of nozzle inside radius sections on the pressurizer. ASME Code Case N-460, as an alternative approved for use by the NRC in RG 1.147, states that a reduction in examination coverage due to part geometry or interference for any ASME Code, Class 1 and 2 weld is acceptable provided that the reduction is less than 10 percent (i.e., greater than 90 percent examination coverage is obtained).

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required 100 percent volumetric examination of the pressurizer safety nozzle inside radius section designated as 4-PSN-1231-IRS.

Licensees Basis for Relief Request (as stated)

Full [ASME] Code required coverage is impractical for the subject components since the nozzles identified within the table would require design modifications that would impose a significant burden to PSEG. PSEG has examined these component welds to the extent practical and determined them to be acceptable with no observed signs of degradation. In addition, other similar vessel welds have been examined to the extent required by the [ASME] Code and also found to be acceptable with no observed signs of degradation. Also, VT-2 visual examinations performed in conjunction with system pressure testing after each refueling outage found these welds to be acceptable with no leakage observed.

Licensees Proposed Alternative Examination (as stated)

Where the component will not allow an ultrasonic angle beam examination from both sides of the weld or upon the nozzle inner radius section, the following were performed using the best available technology at the time and as applicable, demonstrated through the EPRI PDI program:

Similar metal welds and inner radius sections were examined to the extent practical using personnel and techniques qualified and demonstrated through the EPRI PDI, as applicable.

System pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires 100 percent volumetric examination of full penetration welded nozzles and inside radius sections in Class 1 vessels. However, examination of pressurizer safety nozzle inside radius section, designated as 4-PSN-1231-IRS by the licensee, is limited by the design of the component which includes an integral manufacturing identification stamp located in close proximity to the weld on the vessel head. To gain access for further examination, the vessel stamp would have to be removed. Removal of the vessel stamp would create a significant burden on the licensee; therefore, the ASME Code-required 100 percent volumetric examination is impractical.

As shown on the sketches and technical descriptions included in the licensees submittal, examination of the subject nozzle inside radius section has been performed to the extent practical with the licensee obtaining volumetric coverage of approximately 50 percent. A permanent, raised manufacturing identification stamp integrally cast into the upper head in close proximity to the nozzle-to-shell weld restricted ultrasonic transducer placement; thus, no additional scans could be performed to achieve the ASME Code-required coverage of the safety nozzle inside radius section. The examination was performed using personnel and techniques qualified and demonstrated through EPRI PDI. No unacceptable indications were noted during the examination.

The licensee has shown that it is impractical to meet the ASME Code-required 100 percent volumetric examination coverage for the subject nozzle inside radius section due to the design of the vessel. Specifically, limited scans were caused by a cast-in manufacturing identification stamp. Based on the examination performed, along with the full examination of ASME Code-required volumes in other nozzle inside radius sections, it is concluded that if significant service-induced degradation were occurring, there is reasonable assurance that evidence of it would have been detected. As such, the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed.

3.4 Request for Relief S2-I2-RR-B01 (Part D), Examination Category B-F, Item B5.40, Pressure Retaining Dissimilar Metal Welds in Vessel Nozzles ASME Code Requirement ASME Code,Section XI, Examination Category B-F, Item B5.40, requires 100 percent volumetric and surface examination, as defined by Figure IWB-2500-8, for dissimilar metal nozzle-to-safe end butt welds 4-inch nominal pipe size (NPS), and greater, in diameter on the pressurizer. ASME Code Case N-460, as an alternative approved for use by the NRC in RG 1.147, states that a reduction in examination coverage due to part geometry or interference for any Class 1 and 2 weld is acceptable provided that the reduction is less than 10 percent (i.e., greater than 90 percent examination coverage is obtained).

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required 100 percent volumetric examination of pressurizer relief nozzle-to-safe end Weld 6-PR-1203-1.

Licensees Basis for Relief Request (as stated - in part)

Required [ASME] Code coverage is impractical for the subject welds since the components would require design modifications that would impose a significant burden to PSEG. PSEG has examined these welds to the extent practical and determined them to be acceptable with no observed signs of degradation. In addition, other similar piping welds have been examined to the extent required by the

[ASME] Code and also found to be acceptable with no observed signs of degradation. Also, VT-2 visual examinations performed in conjunction with system pressure testing after each refueling outage found these welds to be acceptable with no leakage observed.

Licensees Proposed Alternative Examination (as stated)

Where the component will not allow an ultrasonic angle beam examination for axial scans (upstream and downstream), the following were performed using the best available technology as demonstrated through the EPRI PDI program:

Similar metal welds were examined in at least one axial direction and two circumferential scans adjacent to the weld and upon the weld using personnel and techniques qualified and demonstrated through the EPRI PDI program for single sided access relating to the material type to be examined, as applicable.

Austenitic-to-lnconel dissimilar metal welds were examined in at least one axial direction and two circumferential scans adjacent to the weld and upon the weld using personnel and techniques qualified and demonstrated through the EPRI PDI program for single sided access relating to the material type to be examined, as applicable.

The [ASME] Code required surface and system pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires 100 percent volumetric and surface examination of pressurizer relief nozzle-to-safe end dissimilar metal butt Weld 6-PR-1203-1. However, complete volumetric examination is restricted by the outside diameter (OD) surface configuration of the subject weld. To gain access for examination, the weld would require extensive design modifications or replacement. Imposition of this requirement would create a significant burden on the licensee; therefore, the ASME Code-required 100 percent volumetric examination is impractical.

As shown on the sketches and technical descriptions included in the licensees submittal, examinations of the subject weld have been performed to the extent practical with the licensee obtaining significant volumetric coverage of approximately 86 percent. Surface curvature in the axial pipe direction limited ultrasonic scanning access to this weld.

Additionally, 100 percent of the ASME Code-required surface examination was performed. No unacceptable indications were observed during the performance of these examinations.

The licensee has shown that it is impractical to meet the ASME Code-required volumetric examination coverage for the subject weld due to the OD surface features of the piping and nozzle. However, based on the 86 percent volumetric coverage obtained, along with the full surface examination performed, it is concluded that if significant service-induced degradation were occurring, there is reasonable assurance that evidence of it would have been detected. As such, the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject weld based on the examinations that have been performed.

3.5 Request for Relief S2-I2-RR-B01 (Part E), Examination Category B-J, Items B9.11, B9.21, and B9.40, Pressure Retaining Welds in Piping ASME Code Requirement ASME Code,Section XI, Examination Category B-J, Item B9.11, requires essentially 100 percent volumetric and surface examinations, as defined by Figures IWB-2500-8, for piping circumferential welds 4-inch NPS, and greater, in diameter. Items B9.21 and B9.40 require essentially 100 percent surface examinations, as defined in Figure IWB-2500-8, of piping circumferential welds less than four-inch [nominal pipe size] NPS in diameter and socket welds. Essentially 100%, as clarified by ASME Code Case N-460, is greater than 90 percent coverage of the examination volume, or surface area, as applicable. ASME Code Case N-460 has been approved for use by the NRC in RG 1.147.

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required 100 percent volumetric examination of the ASME Code, Class 1 piping welds shown in Table 3.5.1.

Table 3.5.1 - Examination Category B-J ASME Code Item Weld ID Weld Type B9.11 29-RC-1230-3 Pipe to Pipe B9.11 10-SJ-1221-21 Elbow to Pipe B9.11 8-SJ-1262-10 Pipe to Pipe B9.11 6-SJ-1241-18 Elbow to Pipe B9.11 4-PR-1200-7 Pipe to Tee

Table 3.5.1 - Examination Category B-J ASME Code Item Weld ID Weld Type B9.11 4-PS-1231-20 Valve 2PS28 to Pipe B9.11 4-PS-1231-21 Pipe to Valve 2PS3 B9.11 8-SJ-1252-9 Pipe to Pipe B9.11 6-SJ-1242-2 Elbow to Valve 24SJ43 B9.11 6-SJ-1232-12 Pipe to Tee B9.11 6-SJ-1212-2 Valve 21SJ43 to Pipe B9.11 27.5-RC-1230-1 Pump to Pipe B9.11 6-RH-1231-16 Elbow to Valve 23SJ156 B9.21 3-CV-1241-13 Valve 2CV80 to Elbow B9.21 3-CV-1231-14 Pipe to Valve 2CV274 B9.21 3-CV-1241-14 Elbow to Branch Connection B9.40 2-CV-1275-43 Valve 2CV76 to Pipe B9.40 2-CV-1275-44 Pipe to Branch Connection Licensees Basis for Relief Request (as stated)

Required [ASME] Code coverage is impractical for the subject welds since the components would require design modifications that would impose a significant burden to PSEG. PSEG has examined these welds to the extent practical and determined them to be acceptable with no observed signs of degradation. In addition, other similar piping welds have been examined to the extent required by the

[ASME] Code and also found to be acceptable with no observed signs of degradation. Also, VT-2 visual examinations performed in conjunction with system pressure testing after each refueling outage found these welds to be acceptable with no leakage observed.

[ASME] Code required volumetric examinations are conducted by ultrasonic examination from both the upstream and downstream directions of piping welds.

Ultrasonic examination of certain terminal ends and structural discontinuities are considered to be impractical due to their configuration and material acoustic properties.

The EPRI PDI is in agreement with the NRC's September 22, 1999 Final Rule regarding single side access for piping. The Final Rule requires if access is available, austenitic steel welds shall be scanned in each of the four directions (parallel and perpendicular to the weld) where required. PDI has not been able to qualify a single side examination procedure technique that is capable of demonstrating equivalency for a two-sided examination procedure technique on austenitic piping welds. Current or past technology is not capable of reliably detecting or sizing flaws on the far side of an austenitic weld for configurations

common to nuclear applications. Ultrasonic examination of ferritic steel welds requires scanning in the two axial scan directions. Circumferential scanning is required in the remaining two directions only when axial indications were noted during preservice inspections. Coverage credit may be taken for single side exams on ferritic piping. However, for austenitic piping, a procedure must be qualified with flaws on the inaccessible side of the weld.

To demonstrate that the best available technology was applied for austenitic welds, PDI provides a best effort qualification instead of a complete single sided qualification. PDI Performance Demonstration Qualification Summary (PDQS) austenitic piping certificates list the limitation that single side examination is performed on a best effort basis. When performing single side access of austenitic stainless steel piping welds the best available techniques are used from the accessible side of the weld, as qualified through the PDI.

When the examination area is limited to one side of an austenitic weld, examination coverage does not comply with 10 CFR 50.55a(b)(2)(xv)(A) or the ASME [Code]

Section XI requirements and proficiency demonstrations do not comply with 10 CFR 50.55a(b)(2)(xvi) and full coverage credit may not be claimed. Based upon the qualification efforts of the PDI program, PSEG considers austenitic piping welds examined from a single side to be fully examined to the extent practical. This is considered true for examinations performed prior to and after the PDI in that it has been confirmed by the PDI that the configuration and material acoustic properties of austenitic piping prevents full two-sided access for examination.

Licensees Proposed Alternative Examination (as stated)

Where the component will not allow an ultrasonic angle beam examination for axial scans (upstream and downstream), the following were performed using the best available technology at the time and as applicable, demonstrated through the EPRI PDI program:

Similar metal welds were examined in at least one axial direction and two circumferential scans adjacent to the weld and upon the weld using personnel and techniques qualified and demonstrated through the EPRI PDI program for single sided access relating to the material type to be examined, as applicable.

Austenitic-to-lnconel dissimilar metal welds were examined in at least one axial direction and two circumferential scans adjacent to the weld and upon the weld using personnel and techniques qualified and demonstrated through the EPRI PDI program for single sided access relating to the material type to be examined, as applicable.

The [ASME] Code-required surface and system pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires essentially 100 percent volumetric and/or surface for selected Examination Category B-J pressure retaining welds in piping. Full ASME-required 100 percent surface examinations were conducted for all of the subject welds. However, as shown in Table 3.5.2, complete volumetric examinations are restricted by several factors, including valve configurations and branch connections. These conditions preclude the licensee obtaining full volumetric examinations for these welds. To gain access for examination, the welds would require design modifications. Imposition of this requirement would create a significant burden on the licensee; therefore, the ASME Code-required 100 percent volumetric examinations are impractical.

Table 3.5.2 - ASME Code,Section XI, Examination Category B-J Limitations Weld ID Limitation Description/Interference Coverage 29-RC-1230-3 The ultrasonic examination was limited due to branch connections.

90%

ultrasonic test (UT) 100%

penetrant test (PT) 10-SJ-1221-21 The ultrasonic examination was limited due to a shortened inner radius of the elbow.

83% UT 100% PT 8-SJ-1262-10 The ultrasonic examination was limited due to an installed pipe support.

82% UT 100% PT 6-SJ-1241-18 The ultrasonic examination was limited due to an adjacent weld.

90% UT 100% PT 4-PR-1200-7 The ultrasonic examination was limited due to a tee to valve configuration.

59% UT 100% PT 4-PS-1231-20 The ultrasonic examination was limited due to the valves OD configuration.

59% UT 100% PT 4-PS-1231-21 The ultrasonic examination was limited due to the valves OD configuration.

55% UT 100% PT 8-SJ-1252-9 The ultrasonic examination was limited due to two permanently welded pipe supports.

86% UT 100% PT 6-SJ-1242-2 The ultrasonic examination was limited due to the valves OD configuration.

62% UT 100% PT 6-SJ-1232-12 The ultrasonic examination was limited due to the tees OD configuration.

61% UT 100% PT 6-SJ-1212-2 The ultrasonic examination was limited due to the valves OD configuration.

61% UT 100% PT 27.5-RC-1230-1 The ultrasonic examination was limited due to the OD configuration of the pump nozzle and a branch connection.

49% UT 100% PT

Table 3.5.2 - ASME Code,Section XI, Examination Category B-J Limitations Weld ID Limitation Description/Interference Coverage 6-RH-1231-16 The ultrasonic examination was limited due to the valves OD configuration.

50% UT 100% PT 3-CV-1241-13 The ultrasonic examination was limited due to the valves OD configuration.

75% UT 100% PT 3-CV-1231-14 The ultrasonic examination was limited due to the valves OD configuration.

75% UT 100% PT 3-CV-1241-14 The ultrasonic examination was limited due to the OD configuration of a branch connection.

75% UT 100% PT 2-CV-1275-43 The ultrasonic examination was limited due to the close proximity of a socket weld.

50% UT 100% PT 2-CV-1275-44 The ultrasonic examination was limited due to the close proximity of a socket weld.

50% UT 100% PT As shown on the sketches and technical descriptions included in the licensees submittal, examinations of the subject welds have been performed to the extent practical with the licensee obtaining volumetric coverage from approximately 49 percent to 90 percent.

Various scan limitations were caused by the configuration of the welds and adjacent components (see Table 3.5.2). No unacceptable indications were observed during the performance of these examinations. It was noted that for branch connection welds on the Chemical and Volume Control System, the ASME Code requires surface examination only. However, as part of an augmented inspection program, the licensee elected to perform additional ultrasonic examinations on these welds; thus they have been included in the request for relief.

The licensee has shown that it is impractical to meet the ASME Code-required volumetric examination coverage for the subject welds due to the design of the welds and proximity of other components. Considering the examinations performed, along with the examination of other pressure retaining piping welds, it is concluded that if significant service-induced degradation were occurring in the subject welds, there is reasonable assurance that evidence of it would have been detected. As such, the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed.

3.6 Request for Relief S2-I2-RR-B01 (Part F), Examination Category B-K-1, Item B10.10, Welded Integral Attachments ASME Code Requirement ASME Code, Examination Category B-K-1, Item B10.10 requires essentially 100 percent surface or volumetric examinations, as defined by Figures IWB-2500-13, -14, or -15, as applicable, of the length of integrally welded attachments to piping. Essentially 100%,

as clarified by ASME Code Case N-460 is greater than 90 percent coverage of the examination volume, or surface area, as applicable. ASME Code Case N-460 has been approved for use by the NRC in RG 1.147.

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required 100 percent surface examination of piping support integrally welded attachments designated as 4-PS-1231-11PS-1 through 4 on the pressurizer spray line.

Licensees Basis for Relief Request (as stated)

Full [ASME] Code-required coverage is impractical for the subject welds since the integral attachment would require design modifications and would impose a significant burden to PSEG Nuclear. The piping and pumps have a permanently welded support structure that interfered with the exam upon the lower portion of the integrally welded attachments. Removal of the piping or pump support structure to access the obstructed area would result in the need to redesign the system's configuration. PSEG has examined these welds to the extent practical and determined them to be acceptable with no observed signs of degradation. In addition, other similar welds have been examined to the extent required by the

[ASME] Code and also found to be acceptable with no observed signs of degradation. VT-2 visual examinations performed in conjunction with system pressure testing after each refueling outage found these welds to be acceptable with no leakage observed.

Licensees Proposed Alternative Examination (as stated - in part)

These examinations were performed in accordance with the requirements of ASME

[Code] Section XI 1986 Edition to the extent practical. System pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires essentially 100 percent surface examination of the length of the subject piping integrally welded attachments on the pressurizer spray line. However, complete examinations were restricted by interference from a permanently fixed pipe clamp adjacent to the attachment welds. To gain access for examination, the piping and support clamp would require design modifications. Imposition of this requirement would

create a significant burden on the licensee; therefore, the ASME Code-required 100 percent surface examinations are impractical.

As shown on the sketches and technical descriptions included in the licensees submittal, examinations of the subject welds have been performed to the extent practical with the licensee obtaining surface coverage of approximately 50 percent. The liquid penetrant examinations on the integrally welded attachments were obstructed due to a permanently installed pipe clamp located over the bottom half of the welds. No unacceptable indications were observed during the performance of these examinations.

The licensee has shown that it is impractical to meet the ASME Code-required surface examination coverage for the subject integrally welded attachments due to the proximity of a permanently installed piping support clamp. Based on the examinations performed, it is concluded that if significant service-induced degradation were occurring in the subject welds, there is reasonable assurance that evidence of it would have been detected. As such, the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed.

3.7 Request for Relief S2-I2-RR-C01 (Part A), Examination Category C-A, Items C1.10, C1.20, and C1.30, Pressure Retaining Welds in Pressure Vessels ASME Code Requirement ASME Code,Section XI, Examination Category C-A, Items C1.10, C1.20 and C1.30 require essentially 100 percent volumetric examinations of the length of Class 2 pressure vessel shell circumferential, head circumferential, and tubesheet-to-shell welds, as defined by Figures IWC-2500-1, or IWC-2500-2, respectively. The examinations may be limited to one vessel among the group of vessels performing a similar function.

Essentially 100%, as clarified by ASME Code Case N-460, is greater than 90 percent coverage of the examination volume, or surface area, as applicable. ASME Code Case N-460 has been approved for use by the NRC in RG 1.147.

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required 100 percent volumetric examination of Class 2 vessel welds shown in Table 3.7.1.

Table 3.7.1 - Examination Category C-A Code Item Weld ID Weld Type C1.10 2-RCF-2 Flange-to-Shell C1.10 2-LHEX-1 Flange-to-Shell C1.10 2CVE-18-SWIJ-1

  1. 21 Seal Water Injection Filter Flange to Shell C1.20 2CVE-18-SWIJ-2
  1. 21 Seal Water Injection Filter Shell to Lower Head

Table 3.7.1 - Examination Category C-A Code Item Weld ID Weld Type C1.20 2-RCF-3 Shell to Lower Head C1.20 2-BIT-A Lower Head C1.20 21-STG-SDUH Shell D-to-Upper Head C1.30 2-RHE-2 Shell-to-Tubesheet C1.30 2-RHE-3 Shell-to-Tubesheet Licensees Basis for Relief Request (as stated)

Full [ASME] Code-required coverage is impractical for the subject welds since the vessels would require design modifications that would impose a significant burden to PSEG. PSEG has examined these welds to the extent practical and determined them to be acceptable with no observed signs of degradation. In addition, other similar vessel welds have been examined to the extent required by the Code and also found to be acceptable with no observed signs of degradation. In addition, VT-2 visual examinations performed in conjunction with system pressure testing have found these welds to be acceptable with no leakage observed.

Licensees Proposed Alternative Examination (as stated)

Where the component will not allow an ultrasonic angle beam examination from both sides of the weld, the following were performed using the best available technology at the time and as applicable, demonstrated through the EPRI PDI program.

Similar metal welds, 100 percent of the required volume was examined to the extent practical using personnel and techniques qualified and demonstrated through the EPRI PDI, as applicable.

The [ASME] [C]ode required system pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires essentially 100 percent volumetric examination of the length of the subject Class 2 vessel welds. However, as shown in Table 3.7.2, complete examinations are restricted by several factors, including the geometric configuration of the nozzles, adjacent interferences from support plates, and the proximity of nozzle and flange welds. To gain access for examination, the Class 2 vessels would require design modifications. Imposing this requirement would create a significant burden on the licensee; therefore, the ASME Code-required 100 percent volumetric examinations are impractical.

Table 3.7.2 - ASME Code,Section XI, Examination Category C-A Limitations Weld ID Limitation Description/Interference Coverage 2-RCF-2 A davit welded attachment pad on the side of coolant filter.

61%

2-LHEX-1 Proximity of nozzle and flange welds.

42%

2CVE-18-SWIJ-1 Permanently installed welded attachment and identification plate as well as the flange configuration.

61%

2CVE-18-SWIJ-2 Permanently installed welded attachment and an inlet nozzle.

69%

2-RCF-3 Tank leg support plates welded to the lower section of the reactor coolant filter tank.

53%

2-BIT-A Tank leg support plates welded to boron injection tank.

85%

21-STG-SDUH Insulation support plates and welded pads attached to the steam generator.

87%

2-RHE-2 Component support and hanger connected to the regenerative heat exchanger.

44%

2-RHE-3 Component support and hanger connected to the regenerative heat exchanger.

33%

As shown on the sketches and technical descriptions included in the licensees submittal, examinations of the subject welds have been performed to the extent practical with the licensee obtaining volumetric coverage of approximately 33 percent to 87 percent.

Various scan limitations were caused by the configuration of the welds and adjacent components (see Table 3.7.2). No unacceptable indications were noted during the performance of these examinations.

The licensee has shown that it is impractical to meet the ASME Code-required volumetric examination coverage for the subject welds due to the design and proximity of other components. Based on the examinations performed, along with the examination of pressure retaining welds in other ASME Code,Section XI, Class 2 vessels, it is concluded that if significant service-induced degradation were occurring in the subject welds, there is reasonable assurance that evidence of it would have been detected. As such, the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed.

3.8 Request for Relief S2-I2-RR-C01 (Part B), Examination Category C-B, Item C2.21, Pressure Retaining Nozzle Welds in Vessels ASME Code Requirement ASME Code,Section XI, Examination Category C-B, Item C2.21 requires 100 percent volumetric and surface examinations, as defined by Figures IWC-2500-4(a) or (b), as applicable, of nozzle-to-shell (or head) welds in Class 2 vessels greater than 1/2-inch nominal thickness. ASME Code Case N-460, as an alternative approved for use by the

NRC in RG 1.147, states that a reduction in examination coverage due to part geometry or interference for any ASME Code,Section XI, Class 1 and 2 weld is acceptable provided that the reduction is less than 10 percent (i.e., greater than 90 percent examination coverage is obtained).

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required 100 percent volumetric examination of nozzle-to-head Welds 2-BIT-1 and 2-BIT-2 on the boron injection tanks, and nozzle-to-shell Weld 21-RHRHEX-IN on the Residual Heat Removal (RHR) heat exchanger.

Licensees Basis for Relief Request (as stated)

Full [ASME] Code-required coverage is impractical for the subject welds since the vessels would require design modifications and would impose a significant burden to PSEG. PSEG has examined these welds to the extent practical and determined them to be acceptable with no observed signs of degradation. In addition, other similar vessel welds have been examined to the extent required by the [ASME] Code and also found to be acceptable with no observed signs of degradation. In addition, VT-2 visual examinations performed in conjunction with system pressure testing have found these welds to be acceptable with no leakage observed.

Licensees Proposed Alternative Examination (as stated)

Where the component will not allow an ultrasonic angle beam examination from both sides of the weld, the following were performed using the best available technology at the time and as applicable, demonstrated through the EPRI PDI program:

Similar metal welds, 100 percent of the required volume was examined to the extent practical using personnel and techniques qualified and demonstrated through the EPRI PDI, as applicable.

The [ASME] [C]ode required system pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires 100 percent volumetric and surface examination of the subject pressure retaining nozzle-to-head and nozzle-to-shell welds. However, the OD surface configurations, interference from adjacent supports, and a nearby flange weld limit access for full volumetric examination. To gain access for examination, the vessels would require design modifications. Imposing this requirement would create a significant burden on the licensee; therefore, the ASME Code-required 100% volumetric examinations are impractical.

As shown on the sketches and technical descriptions included in the licensees submittal, examinations of the subject welds have been performed to the extent practical with the

licensee obtaining volumetric coverage of only 25 percent for Weld 21-RHRHEX-IN due to the presence of integrally welded support plates and the close proximity of a bolted flange-to-head weld on the RHR heat exchanger. For boron injection tank nozzle-to-head welds 2-BIT-1 and 2-BIT-2, the OD surface caused by the blend radius of the nozzles limited ultrasonic scans to the head side of the welds only, resulting in volumetric coverage of 31 percent and 63 percent, respectively. All the examinations were performed using personnel and techniques qualified and demonstrated through the EPRI PDI, as applicable. In addition, the licensee performed the ASME Code-required surface examinations with no limitations. No unacceptable indications were noted during the examinations performed.

The licensee has shown that it is impractical to meet the ASME Code-required 100 percent volumetric examination coverage for the subject nozzle-to-head/shell welds due to their design and proximity of the nozzles to other support components and welds.

Based on the examinations performed, along with the examination of other pressure retaining Class 2 nozzle welds, it is concluded that if significant service-induced degradation were occurring in the subject welds, there is reasonable assurance that evidence of it would have been detected. As such, the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed.

3.9 Request for Relief S2-I2-RR-C01 (Part C), Examination Category C-C, Item C3.20, Integral Attachments for Vessels, Piping, Pumps and Valves ASME Code Requirement ASME Code,Section XI, Examination Category C-C, Item C3.20 requires 100 percent surface examinations, as defined by Figure IWC-2500-5, of integral attachment welds in Class 2 piping systems. ASME Code Case N-460, as an alternative approved for use by the NRC in RG 1.147, states that a reduction in examination coverage due to part geometry or interference for any Class 1 and 2 weld is acceptable provided that the reduction is less than 10 percent (i.e., greater than 90 percent examination coverage is obtained).

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required 100 percent surface examinations of piping integrally welded attachments 14-BF-2211-Trunnions 11PL-11 and 11-PL-12, weld integral pipe support attachments 32-MS-2231-1PS-2, 32-MS-2221-1PS-2, 32-MS-2211-1PS-2, pipe lugs 32-MS-2211-2PL-1 through 3, and pipe supports 14-BF-2221-3PL-1 through 8. These supports are located in various Class 2 piping systems.

Licensees Basis for Relief Request (as stated)

Full [ASME] Code required coverage is impractical for the subject welds since the integral attachment would require design modifications and would impose a significant burden to PSEG. PSEG has examined these welds to the extent practical

and determined them to be acceptable with no observed signs of degradation. In addition, other similar welded attachments have been examined to the extent required by the [ASME] Code and also found to be acceptable with no observed signs of degradation. Also, VT-2 visual examinations performed in conjunction with system pressure testing after each refueling outage found these welds to be acceptable with no leakage observed.

Licensees Proposed Alternative Examination (as stated - in part)

These examinations were performed in accordance with the requirements of ASME

[Code] Section XI 1986 Edition to the extent practical. System pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires 100 percent surface examination of the subject integrally welded attachments. However, the welded lug design configurations and adjacent pipe supports severely limit access to the welds. These conditions preclude full surface examinations to the extent required by the ASME Code for these piping integrally welded attachments. Substantial portions of various plant piping systems would have to be redesigned to enable better access to these welded attachments. This would place a significant burden on the licensee; therefore, the ASME Code-required 100 percent surface examinations are impractical.

As shown on the sketches and technical descriptions included in the licensees submittal, examinations of the subject welds have been performed to the extent practical, with the licensee obtaining surface examination coverage from approximately 50 percent to 84 percent. In the case of piping welded attachment 14-BF-2211-Trunnions 11PL-11 and 11-PL-12, the surface examination was limited to 80 percent of the ASME Code-required coverage due to the close proximity of an adjacent pipe support which did not allow proper placement of the magnetic particle (MT) yoke to obtain full coverage. For integral pipe support attachments 32-MS-2231-1PS-2, 32-MS-2221-1PS-2, and 32-MS-2211-1PS-2, surface coverage of 50% was obtained because welded lug configurations precluded magnetization in two orthogonal directions as required by ASME Code. For piping welded lugs 32-MS-2211-2PL-1 through 3, the coverage was limited to 84 percent of the ASME Code requirement due to the lug configuration. For pipe supports 14-BF-2221-3PL-1 through 8, coverage was limited to 79 percent of that required by the ASME Code required coverage because permanently installed components prevented sufficient access to magnetize the weld in two orthogonal directions. No unacceptable indications were noted during the examinations performed.

The licensee has shown that it is impractical to meet the ASME Code-required 100 percent surface examination coverage for the subject piping integral attachment welds due to their design and proximity of other components. Based on the surface coverage obtained, it is concluded that if significant service-induced degradation were occurring in the subject welds, there is reasonable assurance that evidence of it would have been detected by the examinations that were performed. As such, the NRC staff

further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed.

3.10 Request for Relief S1-RR-C01 (Part D), Examination Category C-F-1, Item C5.11 and Item C5.21, Pressure Retaining Welds in Austenitic Stainless Steel or High Alloy Piping ASME Code Requirement ASME Code,Section XI, Examination Category C-F-1, Items C5.11 and C5.21 require 100 percent volumetric and surface examinations, as defined by Figure IWC-2500-7, of selected Class 2 austenitic stainless steel or high alloy piping welds. ASME Code Case N-460, as an alternative approved for use by the NRC in RG 1.147, states that a reduction in examination coverage due to part geometry or interference for any Class 1 and 2 weld is acceptable provided that the reduction is less than 10 percent (i.e., greater than 90 percent examination coverage is obtained).

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required volumetric examinations of the high alloy piping welds shown in Table 3.10.1.

Table 3.10.1 -ASME Code,Section XI, Examination Category C-F-1 Code Item Weld ID Weld Type A-E<3/8 8-CS-2227-5 Valve 21CS2 to Pipe C5.11 8-RH-2216-4R1 Flange to Valve 21RH10 C5.11 8-RH-2273-18 Valve 21RH12 to Tee C5.21 3-CV-2255-9 Valve 2CV70 to Pipe C5.21 4-CV-2257-16 Valve 2CV53 to Elbow C5.21 3-CV-2259-14R1 Valve 2CV55 to Pipe C5.21 3-CV-2256-6 Pipe to Valve 2CV73 C5.21 3-CV-2255-12 Pipe to Valve 2CV72 Licensees Basis for Relief Request (as stated)

Required [ASME] Code coverage is impractical for the subject welds since the piping system would require design modifications to achieve additional coverage and would impose a significant burden to PSEG. PSEG has examined these welds to the extent practical and determined them to be acceptable with no observed signs of degradation. In addition, other similar piping welds have been examined to the extent required by the Code and also found to be acceptable with no observed signs of degradation. Further, VT-2 visual examinations performed in conjunction with system pressure testing have found these welds to be acceptable with no leakage observed.

[ASME] Code-required volumetric examinations are conducted by ultrasonic examination from both the upstream and downstream directions of piping welds.

Ultrasonic examination of certain terminal ends and structural discontinuities are considered to be impractical due to their configuration and material acoustic properties.

The EPRI Performance Demonstration Initiative (PDI) is in agreement with the NRCs September 22, 1999 Final Rule regarding single side access for piping. The Final Rule requires that if access is available, austenitic steel weld shall be scanned in each of the four directions (parallel and perpendicular to the weld) where required.

PDI has not been able to qualify a single side examination procedure technique that is capable of demonstrating equivalency for a two-sided examination procedure technique on austenitic piping welds. Current or past technology is not capable of reliably detecting or sizing flaws on the far side of an austenitic weld for configurations common to nuclear applications. Ultrasonic examination of ferritic steel welds requires scanning in the two axial scan directions. Circumferential scanning is required in the remaining two directions only when axial indications were noted during preservice inspections. Coverage credit may be taken for single side exams on ferritic piping. However, for austenitic piping, a procedure must be qualified with flaws on the inaccessible side of the weld.

To demonstrate that the best available technology was applied to austenitic welds, PDI provides a best effort qualification instead of a complete single sided qualification. PDI Performance Demonstration Qualification Summary (PDQS) austenitic piping certificates list the limitation that single side examination is performed on a best effort basis. When performing single side access of austenitic stainless steel piping welds the best available techniques are used from the accessible side of the weld, as qualified through the PDI.

When the examination area is limited to one side of an austenitic weld, examination coverage does not comply with 10 CFR 50.55a(b)(2)(xv)(A) or the ASME [Code]

Section XI requirements and proficiency demonstrations do not comply with 10 CFR 50.55a(b)(2)(xvi) and full coverage credit may not be claimed. Based upon the qualification efforts of the PDI program, PSEG considers austenitic piping welds examined from a single side to be fully examined to the extent practical. This is considered true for examinations performed prior to and after the PDI in that it has been confirmed by the PDI that the configuration and material acoustic properties of austenitic piping prevents full two-sided access for examination.

Licensees Proposed Alternative Examination (as stated)

Where the component would not allow an ultrasonic angle beam examination for axial scans (upstream and downstream), the following were performed using the best available technology at the time and as applicable, demonstrated through the EPRI PDI program:

For similar metal welds, 100 percent of the required volume was examined by ultrasonic examination in at least one axial direction and two circumferential

scans adjacent to the weld and upon the weld using personnel and techniques qualified and demonstrated through the EPRI PDI program for single sided access relating to the material type to be examined, as applicable.

For dissimilar metal welds, 100 percent of the required volume was examined by ultrasonic examination in at least one axial direction and two circumferential scans adjacent to the weld and upon the weld using personnel and techniques qualified and demonstrated through the EPRI PDI program for single sided access relating to the material type to be examined, as applicable.

The [ASME] [C]ode-required surface and system pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires 100 percent volumetric and surface examination of the subject pressure retaining high alloy ASME Code,Section XI, Class 2 piping welds. Full coverage ASME Code-required surface examinations were performed for all of the subject welds. However, as shown in Table 3.10.2, complete volumetric examinations are restricted by several factors, including nozzle, valve or pipe fitting configurations (e.g., valve-to-valve or elbow-to-pipe). To gain access for examination, substantial portions of various piping systems and plant structural components would need to be redesigned and modified. Imposition of this requirement would create a significant burden on the licensee; therefore, the ASME Code-required 100 percent examinations are impractical.

Table 3.10.2-ASME Code,Section XI, Examination Category C-F-1 Limitations Weld ID Limitation Description/Interference Coverage 8-CS-2227-5*

The ultrasonic examination was limited to the pipe side due to the valve OD configuration.

39.8% - UT 100% - PT 8-RH-2216-4R1 The ultrasonic examination was limited due to flange and valve OD configurations which prohibited scanning from either side of the weld.

22% - UT 100% - PT 8-RH-2273-18 The ultrasonic examination was limited due to the tee and valves OD configurations.

51% - UT 100% - PT 3-CV-2255-9 The ultrasonic examination was limited to the pipe side due to the nozzle OD configuration.

31% - UT 100% - PT 4-CV-2257-16 The ultrasonic examination was limited to the pipe side due to the valve OD configuration.

38% - UT 100% - PT 3-CV-2259-14R1 The ultrasonic examination was limited to the pipe side due to the valve OD configuration.

39% - UT 100% - PT

Table 3.10.2-ASME Code,Section XI, Examination Category C-F-1 Limitations Weld ID Limitation Description/Interference Coverage 3-CV-2256-6 The ultrasonic examination was limited to the pipe side due to the valve OD configuration.

50% - UT 100% - PT 3-CV-2255-12 The ultrasonic examination was limited to the pipe side due to the valve OD configuration.

50% - UT 100% - PT

  • Note: PSEG indicated Weld 8-CS-2227-5 is not required to be examined by ASME Code since the wall thickness of the piping is less than 3/8-inch. Therefore, no applicable ASME Item number exists for this weld. As part of the second 10-year interval inservice inspection plan, PSEG committed to perform augmented volumetric examinations of a 71/2% sample of Class 2 welds in the containment spray system that are otherwise not selected based on wall thickness (i.e., less than 3/8-inch wall thickness). This weld is part of the augmented examination population and therefore included in the submittal as the licensee has chosen to use ASME Section XI for inspection requirements and acceptance criteria.

As shown on the sketches and technical descriptions included in the licensees submittal, examinations of the subject welds have been performed to the extent practical, with the licensee obtaining volumetric examination coverage from approximately 22 percent to 90 percent. Severe limitations caused by flange, valve, or nozzle OD surface configurations prevent the necessary access to achieve additional volumetric coverage (see Table 3.10.2). The limitations for these restricted examinations cannot be overcome without entirely redesigning the subject piping welds or components and portions of the associated structural and piping systems. All the examinations were performed using personnel and techniques qualified and demonstrated through the EPRI PDI program, as applicable. No unacceptable indications were noted during the performance of these examinations.

The licensee has shown that it is impractical to meet the ASME Code-required 100 percent volumetric examination coverage for the subject welds due to ultrasonic scan limitations caused by the OD surface design of connected components. Based on the examinations performed, along with examinations completed on other pressure retaining welds in high alloy piping, it is concluded that if significant service-induced degradation were occurring in the subject welds, there is reasonable assurance that evidence of it would have been detected. As such, the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed.

3.11 Request for Relief S1-RR-C01 (Part D), Examination Category C-F-2, Item C5.51, Pressure Retaining Welds in Carbon or Low Alloy Steel Piping ASME Code Requirement ASME Code,Section XI, Examination Category C-F-2, Item C5.51, requires 100 percent volumetric and surface examinations, as defined by Figure IWC-2500-7, of selected Class 2 carbon steel or low alloy piping welds. ASME Code Case N-460, as an alternative approved for use by the NRC in RG 1.147, states that a reduction in examination coverage due to part geometry or interference for any Class 1 and 2 weld is acceptable provided that the reduction is less than 10 percent (i.e., greater than 90 percent examination coverage is obtained).

Licensees ASME Code Relief Request In accordance with 10 CFR 50.55a(g)(5)(iii), the licensee requested relief from the ASME Code-required volumetric examinations of the low alloy main steam piping welds shown in Table 3.11.1.

Table 3.11.1 - ASME Code,Section XI, Examination Category C-F-2 Code Item Weld ID Weld Type C5.51 30-MS-2211-9 Pipe to Elbow C5.51 34-MS-2241-2 Pipe to Valve 24MS167 C5.51 6-MS-2211-13 Tee to Pipe C5.51 32-MS-2241-3 Elbow to Pipe C5.51 32-MS-2231-3 Elbow to Pipe C5.51 34-MS-2231-1 Pipe to Pipe C5.51 32-MS-2221-3 Elbow to Pipe C5.51 32-MS-2211-3 Elbow to Pipe C5.51 34-MS-2211-1 Pipe to Pipe C5.51 6-MS-2246-3 Pipe to Valve 24MS9 Licensees Basis for Relief Request (as stated)

Required [ASME] Code coverage is impractical for the subject welds since the piping system would require design modifications to achieve additional coverage and would impose a significant burden to PSEG. PSEG has examined these welds to the extent practical and determined them to be acceptable with no observed signs of degradation. In addition, other similar piping welds have been examined to the extent required by the Code and also found to be acceptable with no observed signs of degradation. Further, VT-2 visual examinations performed in conjunction with system pressure testing have found these welds to be acceptable with no leakage observed.

[ASME] Code-required volumetric examinations are conducted by ultrasonic examination from both the upstream and downstream directions of piping welds.

Ultrasonic examination of certain terminal ends and structural discontinuities are considered to be impractical due to their configuration and material acoustic properties.

The EPRI Performance Demonstration Initiative (PDI) is in agreement with the NRCs September 22, 1999 Final Rule regarding single side access for piping. The Final Rule requires that if access is available, austenitic steel weld shall be scanned in each of the four directions (parallel and perpendicular to the weld) where required.

PDI has not been able to qualify a single side examination procedure technique that is capable of demonstrating equivalency for a two-sided examination procedure technique on austenitic piping welds. Current or past technology is not capable of reliably detecting or sizing flaws on the far side of an austenitic weld for configurations common to nuclear applications. Ultrasonic examination of ferritic steel welds requires scanning in the two axial scan directions. Circumferential scanning is required in the remaining two directions only when axial indications were noted during preservice inspections. Coverage credit may be taken for single side exams on ferritic piping. However, for austenitic piping, a procedure must be qualified with flaws on the inaccessible side of the weld.

To demonstrate that the best available technology was applied to austenitic welds, PDI provides a best effort qualification instead of a complete single sided qualification. PDI Performance Demonstration Qualification Summary (PDQS) austenitic piping certificates list the limitation that single side examination is performed on a best effort basis. When performing single side access of austenitic stainless steel piping welds the best available techniques are used from the accessible side of the weld, as qualified through the PDI.

When the examination area is limited to one side of an austenitic weld, examination coverage does not comply with 10 CFR 50.55a(b)(2)(xv)(A) or the ASME [Code]

Section XI requirements and proficiency demonstrations do not comply with 10 CFR 50.55a(b)(2)(xvi) and full coverage credit may not be claimed. Based upon the qualification efforts of the PDI program, PSEG considers austenitic piping welds examined from a single side to be fully examined to the extent practical. This is considered true for examinations performed prior to and after the PDI in that it has been confirmed by the PDI that the configuration and material acoustic properties of austenitic piping prevents full two-sided access for examination.

Licensees Proposed Alternative Examination (as stated)

Where the component will not allow an ultrasonic angle beam examination for axial scans (upstream and downstream), the following were performed using the best available technology at the time and as applicable, demonstrated through the EPRI PDI program:

For similar metal welds, 100 percent of the required volume was examined by ultrasonic examination in at least one axial direction and two circumferential

scans adjacent to the weld and upon the weld using personnel and techniques qualified and demonstrated through the EPRI PDI program for single sided access relating to the material type to be examined, as applicable.

For dissimilar metal welds, 100 percent of the required volume was examined by ultrasonic examination in at least one axial direction and two circumferential scans adjacent to the weld and upon the weld using personnel and techniques qualified and demonstrated through the EPRI PDI program for single sided access relating to the material type to be examined, as applicable.

The [ASME] [C]ode-required surface and system pressure test examinations were performed per ASME [Code] Section XI requirements.

NRC Staff Evaluation

The ASME Code requires 100 percent volumetric and surface examination of the subject pressure retaining carbon steel or low alloy piping welds. Full coverage ASME Code-required surface examinations were performed for all of the subject welds. However, as shown in Table 3.11.2, complete volumetric examinations are restricted by several factors, including OD surface component configurations, or adjacent permanently installed structural and pressure-retaining components. To gain access for examination, substantial portions of the piping systems and plant structural components would need to be redesigned and modified. Imposition of this requirement would create a significant burden on the licensee; therefore, the ASME Code-required 100 percent examinations are impractical.

Table 3.11.2-ASME Code,Section XI, Examination Category C-F-2 Limitations Attachment ID Limitation Description/Interference Coverage 30-MS-2211-9 The ultrasonic examination was limited due to a branch connection.

90% - UT 100% - MT 34-MS-2241-2 The ultrasonic examination was limited due to multiple branch connections located on the main steam header.

85% - UT 100% - MT 6-MS-2211-13 The ultrasonic examination was limited due to the OD configuration of the tee fittings blend radius areas on the upstream side.

73% - UT 100% - MT 32-MS-2241-3 The ultrasonic examination was limited due to a permanently installed welded pipe support.

85% - UT 100% - MT 32-MS-2231-3 The ultrasonic examination was limited due to a welded pipe support partially covering upstream side of the weld.

87% - UT 100% - MT 34-MS-2231-1 The ultrasonic examination was limited due to a welded pipe support.

40% - UT 100% - MT

Table 3.11.2-ASME Code,Section XI, Examination Category C-F-2 Limitations Attachment ID Limitation Description/Interference Coverage 32-MS-2221-3 The ultrasonic examination was limited due to pads and a pipe support.

87% - UT 100% - MT 32-MS-2211-3 The ultrasonic examination was limited due to a permanent restraint and branch connection.

82% - UT 100% - MT 34-MS-2211-1 The ultrasonic examination was limited due to seven pipe restraint bars partially covering the weld.

51% - UT 100% - MT 6-MS-2246-3 The ultrasonic examination was limited due to the valves OD configuration.

79% - UT 100% - MT As shown on the sketches and technical descriptions included in the licensees submittal, examinations of the subject welds have been performed to the extent practical with the licensee obtaining volumetric coverage from approximately 22 percent to 90 percent.

Severe limitations caused by flange and valve configurations, adjacent supports and OD surface features prevent the necessary access to achieve additional examination coverage (see Table 3.11.2). The limitations for these restricted examinations cannot be overcome without entirely redesigning the subject piping welds or adjacent components and portions of the associated structural and support systems. All the examinations were performed using personnel and techniques qualified and demonstrated through the EPRI PDI program, as applicable. No unacceptable indications were noted during the performance of the examinations.

The licensee has shown that it is impractical to meet the ASME Code-required volumetric examination coverage for the subject welds due to ultrasonic scan limitations caused by their design and proximity of other components. Based on the examinations performed, along with examinations completed on other pressure retaining welds in low alloy piping, it is concluded that if significant service-induced degradation were occurring in the subject welds, there is reasonable assurance that evidence of it would have been detected. As such, the NRC staff further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed.

4.0 CONCLUSION

The following summarizes the NRC staff conclusions based on the technical evaluation discussed above in Safety Evaluation Section 3.1 through 3.11.

The NRC staff, with technical assistance from its contractor, the PNNL, has reviewed the licensee's submittal and concludes that ASME Code examination coverage requirements are impractical for the subject welds listed in relief requests S2-I2-RR-B01 and S2-I2-RR-C01.

Based on the volumetric and/or surface coverage obtained, it is also concluded that, if significant service-induced degradation were occurring, there is reasonable assurance that evidence of it would have been detected by the examinations that were performed. As such, the NRC staff

further concludes that there is reasonable assurance of structural integrity of the subject welds based on the examinations that have been performed. Therefore, the NRC staff is granting PSEGs requests for relief pursuant to 10 CFR 50.55a(g)(6)(i), for the second 10-year ISI interval at Salem Unit No. 2.

Granting relief pursuant to 10 CFR 50.55a(g)(6)(i) for is authorized by law and will not endanger life or property, or the common defense and security, and is otherwise in the public interest given due consideration to the burden upon the licensee that could result if the requirements were imposed on the facility.

All other ASME Code,Section XI requirements for which relief was not specifically requested and approved in the subject requests for relief remain applicable, including third-party review by the Authorized Nuclear Inservice Inspector.

Principal Contributors: T. McLellan D. Naujock Date: