ENCLOSURE 2 Joseph M. Farley Nuclear Plant Annual Radioactive Effluent Release Report for 2006

SOUTHERN NUCLEAR OPERATING COMPANY FARLEY NUCLEAR PLANT UNIT NO.

ONE LICENSE NO.

NPF-2 AND FARLEY NUCLEAR PLANT UNIT NO.

TWO LICENSE NO.

NPF-8 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT CALENDAR YEAR 2006

FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT SECTION TITLE PAGE 1.0 LIQUID EFFLUENTS 1

1.1 Regulatory Requirements 1

1.1.1 Concentration Limits 1

1.1.2 Dose Limits 1

1.2 Effluent Concentration Limit (ECL) 1 1.3 Measurements and Approximation 2

of Total Radioactivity 1.3.1 Total Radioactivity Determination 2

1.3.2 Total Error Estimation 3

1.4 Liquid Effluents -

Release Data 3

1.5 Radiological Impact Due to Liquid Releases 3

1.6 Liquid Effluents -

Batch Releases 3

1.7 Liquid Effluents - Abnormal Releases 4

2.0 GASEOUS EFFLUENTS 36 2.1 Regulatory Requirements 36 2.1.1 Dose Rate Limits 36 2.1.2 Air Doses Due to Noble Gases in 36 Gaseous Releases 2.1.3 Doses to a Member of the Public 37 2.2 Measurements and Approximation 37 of Total Radioactivity 2.2.1 Sample Collection and Analysis 37

FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT SECTION TITLE PAGE 2.2.2 Total Quantities of Radioactivity, Dose 38 Rates and Cumulative Doses 2.2.2.1 Fission and Activation Gases 38 2.2.2.2 Radioiodine, Tritium and Particulate 38 Releases 2.2.2.3 Gross Alpha Release 39 2.2.3 Total Error Estimation 40 2.3 Gaseous Effluent Release Data 40 2.4 Radiological Impact Due to Gaseous 41 Releases 2.5 Gaseous Effluents - Batch Releases 41 2.6 Gaseous Effluents -

Abnormal Releases 41 3.0 SOLID WASTE 77 3.1 Regulatory Requirements 77 3.1.1 Solid Radioactive Waste System 77 3.1.2 Reporting Requirements 77 3.2 Solid Waste Data 77 4.0 DOSES TO MEMBERS OF THE PUBLIC 83 INSIDE THE SITE BOUNDARY 4.1 Regulatory Requirements 83 4.2 Demonstration of Compliance 83

FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT SECTION TITLE PAGE 5.0 TOTAL DOSE FROM URANIUM FUEL 90 CYCLE (40CFR190) 5.1 Regulatory Requirements 90 5.2 Demonstration of Compliance 90 6.0 METEOROLOGICAL DATA 90 7.0 PROGRAM DEVIATIONS 90 7.1 Inoperable Liquid or Gaseous Effluent.

90 Monitoring Instrumentation 7.1.1 Regulatory Requirements 90 7.1.2 Description of Deviations 90 7.2 Effluent Sample Analysis Exceeding 91 Minimum Detectable Concentration (MDC) 7.2.1 Regulatory Requirements 91 7.2.2 Description of Deviations 91 7.3 Incorrect Compositing of Liquid 91 or Gaseous Effluent Samples 7.3.1 Regulatory Requirements 91 7.3.2 Description of Deviations 91 8.0 CHANGES TO THE PLANT FARLEY ODCM 91 8.1 Regulatory Requirements 91 8.2 Description of Changes 92

FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT SECTION TITLE PAGE 9.0 MAJOR CHANGES TO LIQUID,

GASEOUS, OR 92 SOLID RADWASTE TREATMENT SYSTEMS 9.1 Regulatory Requirements 92 9.2 Description of Major Changes 92

FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT LIST OF TABLES TABLE 1-IA PAGE 1-lB Liquid Effluents -

All Releases, Unit 3 and 4)

Liquid Effluents -

All Releases, Unit 3 and 4)

Liquid Effluents -

All Releases, Site 3 and 4)

Summation of 1 (Quarters 1,2, Summation of 2 (Quarters 1,2, Summation of (Quarters 1,2, 5

7 1-iC 9

I-2A 1-2B 1-2C I-3A Liquid Effluents, Unit 1 (Quarters 1,2, 3 and 4)

Liquid Effluents, Unit 2 (Quarters 1,2, 3 and 4)

Liquid Effluents, Site (Quarters 1,2, 3 and 4)

Doses to a MEMBER OF THE PUBLIC Due to Liquid Releases, Unit 1 (Quarters 1,2,3 and 4)

Doses to a MEMBER OF THE PUBLIC

  • Due to Liquid Releases, Unit 2 (Quarters 1,2,3 and 4)

Minimum Detectable Concentration -

Liquid Sample Analyses Liquid Effluents -

Batch Release Summary, Unit 1 Liquid Effluents -

Batch Release Summary, Unit 2 II1 15 19 23 25 27 28 30 1-3B 1-4 I-5A I-SB

FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT TABLE LIST OF TABLES PAGE 1-6A Liquid Effluents -

Abnormal Release 32 Summary, Unit 1 1-6B Liquid Effluents -

Abnormal Release 34 Summary, Unit 2 2-1A Gaseous Effluents -

Summation of 42 All Releases, Unit 1 (Quarters 1,2, 3 and 4) 2-1B Gaseous Effluents -

Summation of 44 All Releases, Unit 2 (Quarters 1,2, 3 and 4) 2-1C Gaseous Effluents -

Summation of 46 All Releases, Site (Quarters 1,2, 3 and 4) 2-2A Gaseous Effluents - Mixed Mode 48 Level Releases, Unit 1 (Quarters 1,2, 3 and 4) 2-2B Gaseous Effluents -

Mixed Mode 50 Level Releases, Unit 2 (Quarters 1,2, 3 and 4) 2-2C Gaseous Effluents - Mixed Mode 52 Level Releases, Site (Quarters 1,2, 3 and 4) 2-3A Gaseous Effluents Ground 54 Level Releases, Unit 1 (Quarters 1,2, 3 and 4) 2-3B Gaseous Effluents -

Ground 56 Level Releases, Unit 2 (Quarters 1,2, 3 and 4) 2-3C Gaseous Effluents -

Ground 58 Level Releases, Site (Quarters 1,2, 3 and 4)

FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT TABLE LIST OF TABLES PAGE 2-4A Air Doses Due to Noble Gases in 60 Gaseous Releases., Unit 1 (Quarters 1,.2, 3 and 4) 2-4B Air Doses Due to Noble Gases in 62 Gaseous Releases, Unit 2 (Quarters 1,2, 3 and 4) 2-5A Doses to a MEMBER OF THE PUBLIC 64 Due to Radioiodines, Tritium, and Particulates in Gaseous Releases, Unit 1 (Quarters 1,2,3 and 4) 2-5B Doses to a MEMBER OF THE PUBLIC 66 Due to Radioiodines, Tritium, and Particulates in Gaseous Releases, Unit 2 (Quarters 1,2,3 and 4) 2-6 Minimum Detectable Concentration -

68 Gaseous Effluent Analyses 2-7A Gaseous Effluents -

Batch Release 69 Summary, Unit 1 2-7B Gaseous Effluents -

Batch Release 71 Summary, Unit 2 2-8A Gaseous Effluents - Abnormal Release 73 Summary, Unit 1 2-8B Gaseous Effluents - Abnormal Release 75 Summary, Unit 2 3-1 Solid Waste and Irradiated 78 Fuel Shipments 4-1 Doses to a MEMBER OF THE PUBLIC 84 Due to Activities Inside the Site Boundary, Site

1.0 LIQUID EFFLUENTS This section contains applicable ODCM limits for liquid effluents as well as the quantities of radioactive liquid effluents released during 2006. These quantities are summarized on a quarterly basis and include any unplanned releases.

A tabulation of the total body and organ doses which were calculated in accordance with ODCM 2.4 are presented to show conformance with the limits of ODCM 2.1.3.

1.1 Regulatory Requirements 1.1.1 Concentration Limits Technical Specifications 5.5.4.b and 5.5.4.c state that the concentration of radioactive material released in liquid effluents to UNRESTRICTED AREAS (see ODCM Figure 10-1) shall be limited at all times to ten times the concentrations specified in

10CFR20, Appendix B, Table 2, Column 2 for radionuclides other than dissolved or entrained noble gases. For dissolved or entrained noble gases, the concentration shall be limited to i.OE-04 uCi/ml total activity.

1.1.2 Dose Limits Technical Specifications 5.5.4.d and 5.5.4.e state that the dose or dose commitment to a MEMBER OF THE PUBLIC from radioactive materials in liquid effluents released, from each unit, to UNRESTRICTED AREAS (see ODCM Figure 10-1) shall be limited:

a.

During any calendar quarter to less than or equal to 1.5 mrem to the total body and to less than or equal to 5 mrem to any organ, and

b.

During any calendar year to less than or equal to 3 mrem to the total body and to less than or equal to 10 mrem to any organ.

1.2 Effluent Concentration Limit (ECL)

ECL values used in determining allowable liquid radwaste release rates and concentrations, for principal gamma emitters, 1-131, tritium, Sr-89, Sr-90 and Fe-55, are taken from 10CFR Part 20, Appendix B, Table 2, Column 2.

A tolerance factor of up to 10 is utilized to allow flexibility in establishing practical monitor setpoints which can accommodate effluent releases at concentrations higher than the ECL values stated in

10CFR20, Appendix B, Table 2, Column 2.

For dissolved or entrained noble gases in liquid radwaste, the ECL is 1.OE-04 uCi/ml total activity.

For gross alpha in liquid radwaste, the ECL is 2.OE-09 uCi/ml.

I

Furthermore, for all the above radionuclides, or categories of radioactivity, the overall ECL fraction is determined in accordance with 10CFR Part 20, Appendix B.

1.3 Measurements and Approximation of Total Radioactivity The radionuclides listed below are considered when evaluating liquid effluents:

MN-54 CS-134 FE-59 CS-137 CO-58 CE-141 C0-60 CE-144 ZN-65 MO-99 SR-89 FE-55 SR-90 H-3 1-131 1.3.1 Total Radioactivity Determination Batch Releases: Representative pre-release grab samples are obtained and analyzed in accordance with ODCM Table 2-3.

Isotopic analyses are performed using the computerized pulse height analysis system utilizing high resolution germanium detectors. Isotopic values thus obtained are used for release rate calculations as specified in the ODCM.

Only those nuclides that are detected are used in the calculations. All Strontium and Iron-55 samples are sent offsite to the Georgia Power Environmental Laboratory for analysis. Gross beta and gross alpha determinations are made using 2 pi gas flow proportional counters. Tritium determinations are made using liquid scintillation techniques. Dissolved gases are determined employing grab sampling techniques and then counting on the pulse height analyzer.

The sample analyses results are used along with the ECL values to determine the ECL fraction for the planned release. The ECL fraction is then used, with the appropriate safety factors, and the expected dilution stream flow, to calculate the maximum permissible release rate and a liquid effluent monitor setpoint.

The monitor setpoint is calculated to assure that the limits of the ODCM are not exceeded. A monitor reading in excess of the calculated setpoint will result in automatic termination of the liquid radwaste discharge.

Radionuclide concentrations, safety factors, dilution stream flow rate, and liquid effluent radiation monitor calibration factors are used by the computer to generate a pre-release printout. If the release is not permissible, appropriate warnings will be displayed on the computer screen and on the printout. If the release is permissible, it is approved by a Chemistry Technician.

The release permit is transferred from the Chemistry Department to the Operations Department for release. When the release is completed, the actual release data are provided to the Chemistry 2

Department.

These release data, including release rate and release duration, are input into the computer and a post-release printout is generated. This printout contains the actual release rates, radionuclide concentrations and quantities, dilution flow, and calculated doses to an individual.

Continuous Releases: Continuous releases are analogous to batch releases except that they are analyzed on a weekly composite basis in accordance with ODCM Table 2-3.

Typically achieved liquid effluent sample analyses minimum detectable concentrations are reported in Table 1-4.

1.3.2 Total Error Estimation The maximum error associated with volume and flow measurements, based upon plant calibration practice is estimated to be + or -

10%.

The average error associated with counting is estimated to be less than + or -

15%.

1.4 Liquid Effluent Release Data Summaries of all radioactive liquid effluents released from Units 1 and 2 during 2006 are presented in accordance with Regulatory Guide 1.21 Tables 2A and 2B. Information required by Table 2A is found in this report in Tables 1-lA, 1-1B, and I-IC; Table 2-B information is presented in Tables 1-2A, 1-2B, and 1-2C.

Data is presented on a quarterly basis as required by Regulatory Guide 1.21 for all four quarters.

1.5 Radiological Impact Due to Liquid Releases The total body and organ doses for Units 1 and 2 are provided in the following tables in order to show conformance with the limits of ODCM 2.1.3:

Unit 1 2006 Doses to a Member of the Public due to Liquid Releases: Table 1-3A Unit 2 2006 Doses to a Member of the Public due to Liquid Releases: Table 1-3B 1.6 Liquid Effluents -

Batch Releases Batch release information for Units 1 and 2 is summarized in the following tables:

Unit 1 2006 Liquid Effluents -

Batch Release Summary: Table 1-5A Unit 2 2006 Liquid Effluents -

Batch Release Summary: Table 1-SB 3

1.7 Liquid Effluents - Abnormal Releases There were no abnormal releases during 2006.

Abnormal release information for Units 1 and 2 is summarized in the following tables:

Unit 1 2006 Liquid Effluents -

Abnormal Release Summary: Table 1-6A Unit 2 2006 Liquid Effluents-Abnormal Release Summary: Table 1-6B 4

TABLE 1-lA Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents -

Summation of All Releases Unit: 1 Starting :

l-Jan-2006 Ending : 30-Jun-2006 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE (NOT INCLUDING
TRITIUM, GASES, ALPHA)

CURIES 2.94E-02 5.30E-02 1.80E+01

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.86E-09 3.57E-09

3.

PERCENT OF APPLICABLE LIMIT B.

TRITIUM

1. TOTAL RELEASE CURIES 1.82E+02 2.14E+01 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.15E-05 1.44E-06

3.

PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1. TOTAL RELEASE CURIES 1.36E-02 3.97E-03 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 8.61E-l0 2.68E-10

3.

PERCENT OF APPLICABLE LIMIT D.

GROSS ALPHA RADIOACTIVITY

1. TOTAL RELEASE CURIES 5.46E-06 1.65E-05 1.80E+01 E.

WASTE VOL RELEASED(PRE-DILUTION)

LITERS 2.30E+06 2.94E+07 1.OOE+01 F.

VOLUME OF DILUTION WATER USED LITERS 1.58E+10 1.48E+10 1.00E+01 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

5

TABLE 1-lA Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents - Summation of All Releases Unit: 1 Starting :

l-Jul-2006 Ending : 31-Dec-2006 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE (NOT INCLUDING
TRITIUM, GASES, ALPHA)

CURIES 1.28E-02 1.45E-02 1.80E+01

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 8.07E-10 9.66E-10

3.

PERCENT OF APPLICABLE LIMIT B.

TRITIUM

1. TOTAL RELEASE CURIES 6.79E+01 1.17E+02 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 4.28E-06 7.79E-06

3.

PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1. TOTAL RELEASE CURIES 5.02E-04 4.06E-06 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 3.17E-11 2.70E-13

3.

PERCENT OF APPLICABLE LIMIT D.

GROSS ALPHA RADIOACTIVITY

1. TOTAL RELEASE CURIES 4.42E-05 0.OOE+00 1.80E+01 E.

WASTE VOL RELEASED(PRE-DILUTION)

LITERS 5.30E+07 1.77E+07 1.OOE+01 F.

VOLUME OF DILUTION WATER USED LITERS 1.58E+10 1.50E+10 1.OOE+01 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

6

TABLE 1-lB Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents -

Summation of All Releases Unit: 2 Starting :

l-Jan-2006 Ending : 30-Jun-2006 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2.

EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE (NOT INCLUDING
TRITIUM, GASES, ALPHA)

CURIES 2.93E-02 3.54E-02 1.80E+01

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 2.25E-09 2.07E-09

3.

PERCENT OF APPLICABLE LIMIT B.

TRITIUM

1. TOTAL RELEASE CURIES 1.14E+02 2.33E+01 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 8.77E-06 1.36E-06

3.

PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1. TOTAL RELEASE CURIES 8.46E-03 3.64E-03 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 6.51E-10 2.13E-10

3.

PERCENT OF APPLICABLE LIMIT D.

GROSS ALPHA RADIOACTIVITY

1. TOTAL RELEASE CURIES 3.37E-06 2.40E-05 1.80E+01 E.

WASTE VOL RELEASED(PRE-DILUTION)

LITERS 1.40E+06 1.89E+07 1.00E+01 F.

VOLUME OF DILUTION WATER USED LITERS 1.30E+10 1.71E+10 1.OOE+01 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

7

TABLE 1-lB Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents -

Summation of All Releases Unit: 2 Starting :

l-Jul-2006 Ending : 31-Dec-2006 TYPE OF EFFLUENT UNITS QUARTER 3

QUARTER 4 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE (NOT INCLUDING
TRITIUM, GASES, ALPHA)

CURIES 3.91E-02 1.03E-02 1.80E+01

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 2.30E-09 6.87E-10

3.

PERCENT OF APPLICABLE LIMIT B.

TRITIUM

1. TOTAL RELEASE CURIES 1.10E+02 1.67E+02 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 6.46E-06 1.lIE-05

3.

PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1. TOTAL RELEASE CURIES 3.05E-04 3.10E-04 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.79E-11 2.07E-ll

3.

PERCENT OF APPLICABLE LIMIT D.

GROSS ALPHA RADIOACTIVITY

1. TOTAL RELEASE CURIES 1.28E-05 0.00E+00 1.80E+01 E.

WASTE VOL RELEASED(PRE-DILUTION)

LITERS 1.73E+07 1.10E+06 1.00E+01 F.

VOLUME OF DILUTION WATER USED LITERS 1.70E+10 1.50E+10 1.OOE+01 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

8

TABLE 1-IC Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents -

Summation of All Releases Unit: Site Starting :

l-Jan-2006 Ending : 30-Jun-2006 TYPE OF EFFLUENT UNITS QUARTER 1

QUARTER 2 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE (NOT INCLUDING
TRITIUM, GASES, ALPHA)

CURIES 5.87E-02 8.84E-02 1.80E+01

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 2.04E-09 2.78E-09

3.

PERCENT OF APPLICABLE LIMIT B.

TRITIUM

1. TOTAL RELEASE CURIES 2.96E+02 4.47E+01 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.03E-05 1.40E-06

3.

PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1. TOTAL RELEASE CURIES 2.20E-02 7.62E-03 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 7.64E-10 2.39E-10

3.

PERCENT OF APPLICABLE LIMIT D.

GROSS ALPHA RADIOACTIVITY

1. TOTAL RELEASE CURIES 8.83E-06 4.05E-05 1.80E+01 E.

WASTE VOL RELEASED(PRE-DILUTION)

LITERS 3.70E+06 4.83E+07 1.OOE+01 F.

VOLUME OF DILUTION WATER USED LITERS 2.88E+10 3.18E+10 1.OOE+01 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

9

TABLE 1-IC Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents -

Summation of All Releases Unit: Site Starting :

l-Jul-2006 Ending : 31-Dec-2006 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE (NOT INCLUDING
TRITIUM, GASES, ALPHA)

CURIES 5.18E-02 2.48E-02 1.80E+01

2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.58E-09 8.26E-10

3.

PERCENT OF APPLICABLE LIMIT B.

TRITIUM

1. TOTAL RELEASE CURIES 1.78E+02 2.84E+02 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 5.42E-06 9.46E-06

3.

PERCENT OF APPLICABLE LIMIT C.

DISSOLVED AND ENTRAINED GASES

1. TOTAL RELEASE CURIES 8.07E-04 3.14E-04 1.80E+01
2.

AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 2.46E-11 1.05E-11

3.

PERCENT OF APPLICABLE LIMIT D.

GROSS ALPHA RADIOACTIVITY

1. TOTAL RELEASE CURIES 5.69E-05 0.OOE+00 1.80E+01 E.

WASTE VOL RELEASED(PRE-DILUTION)

LITERS 7.03E+07 1.88E+07 1.00E+01 F.

VOLUME OF DILUTION WATER USED LITERS 3.28E+10 3.OOE+I0 1.OOE+01 Applicable limits are expressed in terms of dose.

See Tables 1-3A and 1-3B of this report.

10

TABLE 1-2A*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: 1 Starting :

l-Jan-2006 Ending : 30-Jun-2006 I CONTINUOUS MODE I

BATCH MODE NUCLIDE I

UNIT IQUARTER 1

[QUARTER 2 IQUARTER 1 IQUARTER 2 I

CURIES I 0.OOE+00 I 0.OOE+00 1.82E+02 I 2.14E+01 I H-3 FISSION & ACTIVATION PRODUCTS AG-108M AG-IIOM AS-76 BE-7 CE-144 CO-58 CO-60 CR-51 CS-134 CS-137 EU-154 FE-55 FE-59 1-131 1-132 1-133 MN-54 NB-95 NB-97 NI-56 PR-144 RH-105 RU-103 SB-124 SB-125 SN-113 CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES 0. OOE+00 0 OOE+00 0 00E+00

0. 00E+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00 0.OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0 OOE+00 0 OOE+00 0 OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0 OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00
0. OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
7. 93E-05
0. OOE+00
6. 17E-06
2. 94E-06 9.24E-04
2. 16E-03
5. 18E-04
1. 56E-06
4. 99E-05
1. 29E-06 1.70E-03
0. OOE+00 2.44E-05
0. OOE+00 2.61E-05 1.96E-05
4. 80E-05 2.35E-05
2. 13E-05 0. OOE+00
0. OOE+00
0. OOE+00 1.73E-06 3.36E-04
0. OOE+00 5.94E-05 3.62E-04 1.18E-06
0. OOE+00
0. OOE+00 5.38E-03
2. 94E-03 2.33E-03 1.16E-05 5.14E-05
0. OOE+00 4.60E-04 2.31E-06
0. OOE+00 5.28E-05 6.38E-06 1.21E-04
6. 05E-04 0.OOE+00
1. 68E-05
2. 84E-04 9.60E-05 2.24E-05 3.87E-05 6.12E-04 4.09E-05 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

11

TABLE 1-2A*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: 1 Starting :

l-Jan-2006 Ending : 30-Jun-2006 CONTINUOUS MODE BATCH MODE NUCLIDE I

UNIT IQUARTER 1 IQUARTER 2 IQUARTER 1 IQUARTER 2 1

FISSION & ACTIVATION PRODUCTS SN-117M CURIES 0.OOE+00 0.OOE+00 2.84E-04 2.07E-04 SR-90 CURIES 0.OOE+00 0.OOE+00 6.28E-06 8.99E-06 TC-104 CURIES 0.OOE+00 0.OOE+00 9.97E-07 0.OOE+00 TC-99M CURIES 0.OOE+00 0.OOE+00 1.71E-05 0.OOE+00 TE-125M CURIES 0.OOE+00 0.OOE+00 2.22E-02 3.33E-02 TE-129 CURIES 0.OOE+00 0.OOE+00 1.41E-05 6.75E-04 TE-129M CURIES 0.OOE+00 0.00E+00 0.OOE+00 8.21E-04 TE-132 CURIES 0.OE+00 0.OOE+00 0.OE+00 3.33E-05 TE-133M CURIES 0.OE+00 0.OOE+00

.OOE+00 2.16E-06 TE-134 CURIES 0.OOE+00 0.OOE+00 0.OOE+00 3.39E-06 Y-88 CURIES 0.OE+00 0.OOE+00 1.18E-06 0.OOE+00 Y-91M CURIES 0.OOE+00 0.OOE+00 2.22E-06 0.OOE+00 ZN-65 CURIES 0.00E+00 0.OOE+00 9.82E-04 4.18E-03 ZR-95 CURIES 0.OE+00 0.OOE+00 9.05E-06 2.52E-04 TOTALS CURIES I 0.OOE+00 I 0.00E+00 I 2.94E-02 I 5.30E-02 DISSOLVED AND ENTRAINED GASES AR-41 CURIES 0.OOE+00 I 0.OOE+00 3.68E-05 0.OOE+00 XE-133 CURIES I 0.OOE+00 I 0.OOE+00 9.96E-03 I 3.34E-03 XE-133M CURIES 0.OOE+00 j0.OOE+00 2.89E-03 I 2.56E-05 XE-135 I

CURIES 0.OOE+00 I 0.OOE+00 1.51E-05 I 8.34E-05 XE-138 CURIES 0.OOE+00 I 0.OOE+00 6.59E-04 5.26E-04 TOTALS I

CURIES I 0.OOE+00 I 0.OOE+00 I 1.36E-02 I 3.97E-03 I

G-ALPHA I

CURIES I 0.OOE+00 I 1.65E-05 I 5.46E-06 I 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

12

TABLE 1-2A*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: 1 Starting :

l-Jul-2006 Ending : 31-Dec-2006 I CONTINUOUS MODE I

BATCH MODE I

NUCLIDE I

UNIT IQUARTER 3 QUARTER 4 IQUARTER 3 IQUARTER 4 1

I CURIES I 0.OOE+00 I 0.OOE+00 I 6.79E+01 I 1.17E+02 I

H-3 FISSION & ACTIVATION PRODUCTS AG-11OM BA-141 CO-58 CO-60 CR-51 CS-137 FE-55 1-133 LA-142 MN-54 NB-95 ND-149 NI-56 RH-105 SB-125 SN-117M SR-85 SR-89 SR-90 TA-182 TC-101 TC-99M CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES

0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00 3.71E-03 0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00 0. OOE+00 O.OOE+00
0. OOE+00 O.OOE+00
0. OOE+00 O.OOE+00 7.49E-04 0. OOE+00 0. OOE+00 O.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 3.77E-05 0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00 0. OOE+00
0. OOE+00 7.61E-06
0. 00E+00
0. OOE+00
0. OOE+00
0. OOE+00
3. 88E-06
0. OOE+00
2. 48E-04
4. 06E-04
4. 42E-06
6. 47E-05
4. 21E-04
5. 67E-07
1. 80E-06
6. 59E-06 4 37E-05 2 69E-06 2 21E-06 2 33E-06 7 03E-05
1. 71E-05
5. 34E-07
0. OOE+00
6. 73E-06
1. 24E-06
5. 60E-07
4. 71E-07 2.77E-06 1.55E-06 1.36E-04
4. 13E-04
0. OOE+00 3.32E-05
2. 89E-04 2.61E-07
0. OOE+00
0. OOE+00 2.76E-06
0. OOE+00
4. 71E-06
0. OOE+00
1. 13E-04 1.22E-05
0. OOE+00
0. OOE+00 3.97E-06
0. OOE+00
0. OOE+00
0. OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

13

TABLE 1-2A*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT 2006 Liquid Effluents Unit: 1 Starting :

l-Jul-2006 Ending : 31-Dec-2006 I CONTINUOUS MODE BATCH MODE I

NUCLIDE I

UNIT IQUARTER 3

QUARTER 4 QUARTER 3 IQUARTER 4 1 FISSION & ACTIVATION PRODUCTS TE-125M CURIES 0.OOE+00 0.OOE+00 6.36E-03 1.32E-02 TE-127 CURIES 0.OOE+00 0.OOE+00 0.OOE+00 3.83E-05 ZN-65 CURIES 0.OOE+00 0.OOE+00 6.20E-04 2.29E-04 ZR-95 CURIES 0.OOE+00 0.OOE+00 1.57E-05 0.OOE+00 TOTALS CURIES 4.46E-03 I 4.53E-05 I 8.30E-03 1.45E-02 DISSOLVED AND ENTRAINED GASES AR-41 CURIES 0.OOE+00 0.OOE+00 2.46E-06 0.OOE+00 KR-85 CURIES 0.OOE+00 0.OOE+00 1.18E-04 0.OOE+00 XE-133 CURIES 0.OOE+00 0.OOE+00 3.80E-04 4.06E-06 XE-135 CURIES 0.OOE+00 0.OOE+00 4.81E-07 0.OOE+00 TOTALS CURIES 0.OOE+00 I 0.OOE+00 I 5.02E-04 I 4.06E-06 G-ALPHA I CURIES 3.79E-05,1 0.OOE+00 I 6.26E-06 I 0.00E+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

14

TABLE 1-2B*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: 2 Starting :

l-Jan-2006 Ending : 30-Jun-2006 I CONTINUOUS MODE I

BATCH MODE NUCLIDE I

UNIT IQUARTER 1 IQUARTER 2 IQUARTER 1 IQUARTER 2 H-3 I

CURIES I 0.OOE+00 I 0.00E+00 I 1.14E+02 I 2.33E+01 FISSION.................................--.............................7 AIAOPDC FISSION & ACTIVATION PRODUCTS AG-108M AG-IIOM CE-146 CO-57 CO-58 CO-60 CR-51 CS-137 CS-138 FE-55 1-132 MN-54 NB-95 NB-97 NI-56 RH-105 RU-103 CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES

0. OOE+00 0.OOE+00
0. 00E+00
0. OOE+00
0. OOE+00 0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+.00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00 0.OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00 0.OOE+00
0. OOE+00 5.06E-05
4. 75E-06 6.06E-07 8.23E-04
1. lIE-03
9. 08E-04
1. 82E-05
5. 83E-06
9. 73E-04 0. OOE+00
1. 61E-05
1. 50E-04
1. IOE-05
3. 61E-05
1. 55E-05
0. OOE+00
3. 04E-05
2. 07E-04 0.OOE+00
0. OOE+00
2. 19E-03
1. 76E-03 1.38E-03 1.17E-05
5. 83E-06
4. 55E-04 2.17E-05
2. 01E-05 2.73E-04
0. OOE+00 1.55E-05 6.02E-05 9.44E-06 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

15

TABLE 1-2B*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: 2 Starting :

l-Jan-2006 Ending : 30-Jun-2006 I CONTINUOUS MODE I

BATCH MODE NUCLIDE I

UNIT IQUARTER 1 IQUARTER 2 IQUARTER 1 QUARTER 2 FISSION & ACTIVATION PRODUCTS SB-12 4 SB-125 SN-113 SN-117M SR-92 TC-99M TE-125M TE-129 TE-129M TE-132 TE-133 TE-134 ZN-65 ZR-95 CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES

0. 00E+00 0 OOE+00 0 00E+00 0 00E+00
0. 00E+00
0. 00E+00
0. 00E+00
0. OOE+00
0. OOE+00
0. OOE+00 0.00E+00 0.00E+00
0. OOE+00
0. 00E+00
0. 00E+00 0 OOE+00 0 00E+00
0. 00E+00
0. 00E+00
0. OOE+00
0. OOE+00
0. 00E+00
0. 00E+00
0. OOE+00
0. 00E+00
0. OOE+00
0. 00E+00
0. 00E+00
7. 81E-06 2.04E-04 4.32E-06
3. 10E-04 0. OOE+00 1.33E-06 2.36E-02
0. OOE+00
0. OOE+00
0. OOE+00
0. 00E+00 3.71E-06 9.65E-04
7. 53E-05 3.41E-06 2.57E-04 1.83E-05
1. 45E-04 2.03E-05
0. 00E+00 2.62E-02 3.38E-04 4.25E-04
2. 47E-05
3. 01E-06
0. OOE+00 1.41E-03
1. 28E-04 TOTALS CURIES 0.OOE+00 I 0.00E+00 I 2.93E-02 I 3.54E-02 DISSOLVED AND ENTRAINED GASES XE-133 CURIES 0.00E+00 0.OOE+00 8.31E-03 3.59E-03 XE-133M CURIES 0.00E+00 0.OOE+00 1.22E-04 4.41E-06 XE-135 CURIES 0.00E+00 0.00E+00 5.38E-06 4.85E-05 XE-138 CURIES 0.00E+00 0.OOE+00 2.04E-05 0.00E+00 TOTALS I CURIES I 0.OOE+00 0.00E+00 I 8.46E-03 I 3.64E-03 G-ALPHA CURIES I 0.00E+00 I 2.40E-05 3.37E-06 0.00E+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

16

TABLE l-2B*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: 2 Starting :

l-Jul-2006 Ending : 31-Dec-2006 I CONTINUOUS MODE I

BATCH MODE NUCLIDE I

UNIT IQUARTER 3 QUARTER 4 QUARTER 3 QUARTER 4 1 H-3 I

CURIES I 0.OOE+00 I 0.00E+00 I 1.10E+02 I 1.67E+02 I FISSION & ACTIVATION PRODUCTS AG-IIOM AS-76 BE-7 CD-109 CO-57 CO-58 CO-60 CR-51 CS-137 CS-138 FE-55 NB-95 NI-56 RH-105 SB-125 SN-117M SR-90 TE-125M TE-129M TE-133 TE-134 Y-91M ZN-65 CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES

0. OOE+00 0. OOE+00
0. OOE+00
0. 00E+00
0. OOE+00 0 OOE+00
0. OOE+00 0 00E+00 0 00E+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0 OOE+00 0 OOE+00 0 OOE+00 0. OOE+00 0. OOE+00 0 OOE+00 0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00 0 OOE+00
0. OOE+00 0. OOE+00 0 OOE+00
1. 53E-05 3.28E-06 1.26E-05
4. 69E-05
1. 26E-05
1. 68E-04
9. 66E-03
3. 25E-05
9. 14E-04
0. OOE+00 1.14E-03
8. 49E-06
9. 76E-06 4.95E-06
6. 61E-04 5.40E-05
0. OOE+00 2.57E-02 2.43E-05
0. OOE+00
2. 45E-06
0. OOE+00
6. 1OE-04 3.98E-06
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 3 92E-05
1. 67E-03 0 OOE+00
1. 14E-04
2. 48E-06 2 61E-04
0. OOE+00
2. 92E-06
0. OOE+00
1. 06E-04 7 75E-06 5.34E-06
8. 02E-03
0. OOE+00
2. 73E-06
0. OOE+00
1. 19E-06
8. 93E-05 TOTALS CURIES I 0.OOE+00 0.OOE+00 I 3.91E-02 I 1.03E-02 I Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

17

TABLE 1-2B*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: 2 Starting :

l-Jul-2006 Ending : 31-Dec-2006 I CONTINUOUS MODE I

BATCH MODE I

NUCLIDE I

UNIT IQUARTER 3 QUARTER 4 QUARTER 3 IQUARTER 4 1

DISSOLVED AND ENTRAINED GASES AR-41 CURIES 0.00E+00 0.OOE+00 0.OOE+00 2.01E-06 KR-87 CURIES 0.00E+00 0.OE+00 1.30E-06 0.OOE+00 XE-131M CURIES 0.OOE+00 0.OE+00 1.30E-05 0.OOE+00 XE-133 CURIES 0.OOE+00 0.OOE+00 2.90E-04 5.55E-06 XE-135 CURIES 0.OOE+00 0.OE+00 6.06E-07 5.20E-07 XE-138 CURIES 0.OOE+00 0.OE+00 0.OOE+00 3.02E-04 TOTALS I CURIES I 0.OOE+00 0.OOE+00 3.05E-04 I 3.10E-04 I G-ALPHA CURIES I 3.84E-06 I 0.OOE+00 8.93E-06 I 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

18

TABLE 1-2C*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: Site Starting :

l-Jan-2006 Ending : 30-Jun-2006 I CONTINUOUS MODE BATCH MODE NUCLIDE I

UNIT IQUARTER 1 IQUARTER 2 QUARTER 1 IQUARTER 2 I CURIES 0.OOE+00 0.OOE+00 I 2.96E+02 4.47E+01 H-3 FISSION & ACTIVATION PRODUCTS AG-108M AG-I1OM AS-76 BE-7 CE-144 CE-146 CO-57 CO-58 CO-60 CR-51 CS-134 CS-137 CS-138 EU-154 FE-55 FE-59 1-131 1-132 1-133 MN-54 NB-95 NB-97 NI-56 PR-144 R14-105 RU-103 SB-124 SB-125 SN-113 CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES 0.OOE+00

0. OOE+00
0. OOE+00 0.OOE+00 0.OOE+00
0. OOE+00
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00
0. OOE+00
0. 00E+00
0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00 0.OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0.OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 1.30E-04 0.OOE+00
6. 17E-06
2. 94E-06
4. 75E-06
6. 06E-07 1.75E-03
3. 27E-03
1. 43E-03
1. 56E-06 6.82E-05
5. 83E-06
1. 29E-06 2.67E-03
0. OOE+00 2.44E-05
0. OOE+00
2. 61E-05 3.56E-05 1.98E-04
3. 45E-05 5.74E-05
0. OOE+00
1. 55E-05 0.00E+00
9. 54E-06 5.40E-04 4.32E-06 8.97E-05
5. 70E-04 1.18E-06 0.OOE+00 0.OOE+00 0. OOE+00
0. OOE+00 7.58E-03
4. 70E-03
3. 71E-03 1.16E-05 6.31E-05
5. 83E-06
0. OOE+00
9. 15E-04 2.31E-06 0. OOE+00
7. 45E-05 6.38E-06 1.42E-04
8. 77E-04
0. OOE+00 3.23E-05 2.84E-04
1. 56E-04
3. 19E-05 4.21E-05
8. 69E-04 5.92E-05 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

19

TABLE 1-2C*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: Site Starting :

l-Jan-2006 Ending : 30-Jun-2006 I CONTINUOUS MODE I

BATCH MODE NUCLIDE I

UNIT IQUARTER 1 IQUARTER 2 QUARTER 1 IQUARTER 2 FISSION & ACTIVATION PRODUCTS SN-117M CURIES 0.00E+00 0.OOE+00 5.95E-04 3.52E-04 SR-90 CURIES 0.OE+00 0.OOE+00 6.28E-06 8.99E-06 SR-92 CURIES 0 00E+00 0.OOE+00 0.OOE+00 2.03E-05 TC-104 CURIES 0.OOE+00 0.OOE+00 9.97E-07 0.OOE+00 TC-99M CURIES 0.OOE+00 0.OOE+00 i.85E-05 0.OOE+00 TE-125M CURIES 0.OE+00 0.OOE+00 4.57E-02 5.95E-02 TE-129 CURIES 0.OE+00 0.OOE+00 1.41E-05 1.01E-03 TE-129M CURIES 0.OE+00 0.00E+00 0.OE+00 1.25E-03 TE-132 CURIES 0.OOE+00 0.OOE+00 0.OE+00 5.80E-05 TE-133 CURIES 0.OOE+00 0.OOE+00 0.OOE+00 3.01E-06 TE-133M CURIES 0.OOE+00 0.OOE+00 0.OOE+00 2.16E-06 TE-134 CURIES 0.OOE+00 0.OOE+00 3.71E-06 3.39E-06 Y-88 CURIES 0.00E+00 0.OOE+00 1.18E-06 0.OE+00 Y-91M CURIES 0.OE+00 0.OOE+00 2.22E-06 0.OE+00 ZN-65 CURIES 0.OE+00 0.OOE+00 i.95E-03 5.59E-03 ZR-95 CURIES 0.00E+00 0.OOE+00 8.43E-05 3.80E-04 TOTALS CURIES I 0.OOE+00 1 0.OOE+00 I 5.87E-02 I 8.84E-02 DISSOLVED AND ENTRAINED GASES AR-41 CURIES-0.OOE+00 0.OOE+00 3.68E-05 0.OOE+00 XE-133 CURIES 0.OOE+00 0.OOE+00 1.83E-02 6.93E-03 XE-133M CURIES 0.OOE+00 0.OOE+00 3.02E-03 3.01E-05 XE-135 CURIES 0.OOE+00 0.OOE+00 2.05E-05 1.32E-04 XE-138 CURIES 0.OOE+00 0.OOE+00 6.79E-04 5.26E-04 TOTALS CURIES 0.I00-E+00 I 0.OOE+00 I 2.20E-02 I 7.62E-03 G-ALPHA I

CURIES 0.I00-E+00 I 4.05E-05 8.83E-06 I 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

20

TABLE 1-2C*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: Site Starting :

l-Jul-2006 Ending : 31-Dec-2006 I CONTINUOUS MODE I

BATCH MODE NUCLIDE I

UNIT IQUARTER 3 IQUARTER 4 QUARTER 3 IQUARTER 4 H-3 I

CURIES 0.OOE+00 I 0.OOE+00 I 1.78E+02 I 2.84E+02 I FISSION & ACTIVATION PRODUCTS AG-11OM AS-76 BA-141 BE-7 CD-109 CO-57 CO-58 CO-60 CR-51 CS-137 CS-138 FE-55 1-133 LA-142 MN-54 NB-95 ND-149 NI-56 RH-105 SB-125 SN-117M SR-85 SR-89 SR-90 TA-182 TC-101 TC-99M TE-125M TE-127 TE-129M CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES CURIES

0. 00E+00
0. 00E+00
0. OOE+00
0. OOE+00 0. 00E+00
0. OOE+00 0 OOE+00 0 OOE+00 0 00E+00 0 OOE+00
0. OOE+00
3. 71E-03
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0 OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 7 49E-04 0 OOE+00 0 OOE+00
0. OOE+00 0 OOE+00 0 OOE+00 0 OOE+00 0 OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 3.77E-05
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00
0. 0OE+00
0. OOE+00 0 OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 7 61E-06
0. OOE+00
0. OOE+00
0. OOE+00
0. OOE+00 0. OOE+00
0. OOE+00
0. OOE+00
1. 92E-05 3.28E-06 0 OOE+00
1. 26E-05
4. 69E-05
1. 26E-05
4. 16E-04
1. 01E-02 3 69E-05
9. 79E-04
0. OOE+00
1. 56E-03
5. 67E-07
1. 80E-06
6. 59E-06
5. 22E-05
2. 69E-06
1. 20E-05
7. 28E-06
7. 32E-04
7. lE-05
5. 34E-07
0. OOE+00
6. 73E-06
1. 24E-06
5. 60E-07
4. 71E-07
3. 21E-02
0. OOE+00
2. 43E-05 6.75E-06 0. OOE+00 1 55E-06 0. OOE+00 0 OOE+00
0. OOE+00
1. 75E-04
2. 08E-03
0. OOE+00 1.47E-04
2. 48E-06 5 50E-04.

2 61E-07

0. OOE+00
0. OOE+00
2. 76E-06 0. OOE+00 7 62E-06 0 OOE+00
2. 19E-04
1. 99E-05 0 OOE+00
0. OOE+00
9. 31E-06 0 OOE+00
0. OOE+00
0. OOE+00
2. 12E-02
3. 83E-05
0. OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

21

TABLE 1-2C*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Unit: Site Starting :

l-Jul-2006 Ending : 31-Dec-2006 I CONTINUOUS MODE I

BATCH MODE I

NUCLIDE I

UNIT IQUARTER 3 IQUARTER 4 IQUARTER 3 IQUARTER 4 1

FISSION & ACTIVATION PRODUCTS TE-133 CURIES 0.OOE+00 I 0.OOE+00 0.OOE+00 I 2.73E-06 TE-134 CURIES 0.OOE+00 I 0.00E+00 2.45E-06 I 0.OOE+00 Y-91M CURIES 0.OOE+00 I 0.OOE+00 0.00E+00 1.19E-06 ZN-65 CURIES 0.OOE+00 I 0.OOE+00 1.23E-03 I 3.18E-04 ZR-95 CURIES 0.OOE+00 0.OOE+00 1.57E-05 I 0.OOE+00 TOTALS I CURIES I 4.46E-03 I 4.53E-05 4.74E-02 I 2.48E-02 DISSOLVED AND ENTRAINED GASES AR-41 CURIES 0.OOE+00 0.OOE+00 2.46E-06 2.01E-06 KR-85 CURIES 0.OOE+00 0.OOE+00 1.18E-04 0.OE+00 KR-87 CURIES 0.00E+00 0.OE+00 1.30E-06 0.OE+00 XE-131M CURIES 0.00E+00 0.OOE+00 1.30E-05 0.OOE+00 XE-133 CURIES 0.OE+00 0.OE+00 6.71E-04 9.61E-06 XE-135 CURIES 0.OOE+00 0.OE+00 1.09E-06 5.20E-07 XE-138 CURIES 0.OE+00 0.OE+00 0.OOE+00 3.02E-04 TOTALS I

CURIES I 0.OOE+00 I 0.OOE+00 I 8.07E-04 I 3.14E-04 I G-ALPHA I

CURIES I 4.18E-05 I O.OOE+00 I 1.52E-05 I O.OOE+O0 I

Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 1-4 for typically achieved minimum detectable concentrations.

22

TABLE 1-3A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 1 Starting: 01-Jan-2006 Ending: 30-Jun-2006 Cumulative Doses per Quarter Organ ODCM Units Quarter

% of Quarter

% of Limit 1

ODCM 2

ODCM Limit Limit Bone 5.0 mrem 8.90E-03 1.78E-01 1.31E-02 2.62E-01 Liver 5.0 mrem 4.83E-03 9.65E-02 5.36E-03 1.07E-01 TBody 1.5 mrem 2.73E-03 1.82E-01 2.31E-03 1.54E-01.

Thyroid 5.0 mrem 3.93E-03 7.86E-02 4.00E-03 8.00E-02 Kidney 5.0 mrem 3.54E-02 7.09E-01 5.20E-02 1.04E+00 Lung 5.0 mrem 3.27E-03 6.54E-02 2.79E-03 5.57E-02 GILLI 5.0 mrem 3.57E-02 7.15E-01 5.41E-02 1.08E+00 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 10.0 mrem 2.20E-02 2.20E-01 Liver 10.0 mrem 1.02E-02 1.02E-01 TBody 3.0 mrem 5.04E-03 1.68E-01 Thyroid 10.0 mrem 7.93E-03 7.93E-02 Kidney 10.0 mrem 8.74E-02 8.74E-01 Lung 10.0 mrem 6.06E-03 6.06E-02 GILLI 10.0 mrem 8.98E-02 8.98E-01 23

TABLE 1-3A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 1 Starting: 01-Jul-2006 Ending: 31-Dec-2006 Cumulative Doses per Quarter Organ ODCM Units Quarter

% of Quarter

% of Limit 3

ODCM 4

ODCM Limit Limit Bone 5.0 mrem 4.08E-03 8.16E-02 5.46E-03 1.09E-01 Liver 5.0 mrem 2.19E-03 4.38E-02 2.92E-03 5.84E-02 TBody 1.5 mrem 1.15E-03 7.67E-02 1.68E-03 1.12E-01 Thyroid 5.0 mrem 1.27E-03 2.54E-02 2.47E-03 4.93E-02 Kidney 5.0 mrem 1.08E-02 2.16E-01 2.23E-02 4.47E-01 Lung 5.0 mrem 1.21E-03 2.42E-02 1.49E-03 2.99E-02 GILLI 5.0 mrem 1.12E-02 2.23E-01 2.21E-02 4.43E-01 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 10.0 mrem 3.15E-02 3.15E-01 Liver 10.0 mrem 1.53E-02 1.53E-01 TBody 3.0 mrem 7.87E-03 2.62E-01 Thyroid 10.0 mrem 1.17E-02 1.17E-01 Kidney 10.0 mrem 1.21E-01 1.21E+00 Lung 10.0 mrem 8.76E-03 8.76E-02 GILLI 10.0 mrem 1.23E-01 1.23E+00 24

TABLE 1-3B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 2 Starting: 01-Jan-2006 Ending: 30-Jun-2006 Cumulative Doses per Quarter Organ ODCM Units Quarter

% of Quarter

% of Limit 1

ODCM 2

ODCM Limit Limit Bone 5.0 mrem 9.94E-03 1.99E-01 9.58E-03 1.92E-01 Liver 5.0 mrem 4.77E-03 9.54E-02 3.83E-03 7.65E-02 TBody 1.5 mrem 2.41E-03 1.61E-01 1.60E-03 1.07E-01 Thyroid 5.0 mrem 3.86E-03 7.71E-02 3.01E-03 6.03E-02 Kidney 5.0 mrem 4.03E-02 8.06E-01 3.87E-02 7.73E-01 Lung 5.0 mrem 2.21E-03 4.41E-02 1.32E-03 2.64E-02 GILLI 5.0 mrem 4.02E-02 8.04E-01 3.95E-02 7.91E-01 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 10.0 mrem 1.95E-02 1.95E-01 Liver 10.0 mrem 8.60E-03 8.60E-02 TBody 3.0 mrem 4.01E-03 1.34E-01 Thyroid 10.0 mrem 6.87E-03 6.87E-02 Kidney 10.0 mrem 7.90E-02 7.90E-01 Lung 10.0 mrem 3.53E-03 3.53E-02 GILLI 10.0 mrem 7.98E-02 7.98E-01 25

TABLE l-3B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 2 Starting: 01-Jul-2006 Ending: 31-Dec-2006 Cumulative Doses per Quarter Organ ODCM Units Quarter

% of Quarter

% of Limit 3

ODCM 4

ODCM Limit Limit Bone 5.0 mrem 1.09E-02 2.19E-01 3.02E-03 6.04E-02 Liver 5.0 mrem 6.06E-03 1.21E-01 2.36E-03 4.72E-02 TBody 1.5 mrem 3.41E-03 2.27E-01 1.69E-03 1.13E-01 Thyroid 5.0 mrem 3.70E-03 7.41E-02 1.96E-03 3.91E-02 Kidney 5.0 mrem 4.06E-02 8.12E-01 1.24E-02 2.48E-01 Lung 5.0 mrem 4.29E-03 8.58E-02 1.66E-03 3.33E-02 GILLI 5.0 mrem 4.25E-02 8.50E-01 1.27E-02 2.53E-0l Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 10.0 mrem 3.35E-02 3.35E-01 Liver 10.0 mrem 1.70E-02 1.70E-01 TBody 3.0 mrem 9.11E-03 3.04E-01 Thyroid 10.0 mrem 1.25E-02 1.25E-01 Kidney 10.0 mrem 1.32E-01 1.32E+00 Lung 10.0 mrem 9.48E-03 9.48E-02 GILLI 10.0 mrem 1.35E-01 1.35E+00 26

TABLE 1-4 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 MINIMUM DETECTABLE CONCENTRATION -

LIQUID SAMPLE ANALYSES The values in this table represent a priori Minimum Detectable Concentrations (MDC) that are typically achieved in laboratory analyses of liquid radwaste samples.

Nuclide MDC(uCi/ML)

MN-54 3.14E-08 CO-58 4.92E-08 FE-59 7.19E-08 CO-60 4.77E-08 ZN-65 8.11E-08 MO-99 1.29E-07 1-131 2.53E-08 CS-134 3.51E-08 CS-137 4.28E-08 CE-141 5.41E-08 CE-144 1.95E-07 27

TABLE l-5A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents -

Batch Release Summary Unit: 1 Starting :

l-Jan-2006 Ending : 30-Jun-2006 LIQUID RELEASES NUMBER OF BATCH RELEASES TOTAL TIME PERIOD FOR BATCH RELEASES MAXIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE TIME PERIOD FOR BATCH RELEASES MINIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE STREAM FLOW DURING PERIODS OF RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM 251 25036.67 136.00 99.75 66.00 MINUTES MINUTES MINUTES MINUTES 8.43E+03 CFS *

  • Average River Flow Rate, taken at Walter F.

George Lock and Dam, located 30.7 miles above Farley Nuclear Plant.

28

TABLE 1-5A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents -

Batch Release Summary Unit: 1 Starting :

l-Jul-2006 Ending : 31-Dec-2006 LIQUID RELEASES NUMBER OF BATCH RELEASES TOTAL TIME PERIOD FOR BATCH RELEASES MAXIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE TIME PERIOD FOR BATCH RELEASES MINIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE STREAM FLOW DURING PERIODS OF RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM 105 11564.55 130.00 110.14 90.00 MINUTES MINUTES MINUTES MINUTES 3.18E+03 CFS *

  • Average River Flow Rate, taken at Walter F.

George Lock and Dam, located 30.7 miles above Farley Nuclear Plant.

29

TABLE 1-5B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents - Batch Release Summary Unit: 2 Starting :

l-Jan-2006 Ending : 30-Jun-2006 LIQUID RELEASES NUMBER OF BATCH RELEASES TOTAL TIME PERIOD FOR BATCH RELEASES MAXIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE TIME PERIOD FOR BATCH RELEASES MINIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE STREAM FLOW DURING PERIODS OF RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM 182 18692.33 275.00 102.71 3.00 MINUTES MINUTES MINUTES MINUTES 8.43E+03 CFS *

  • Average River Flow Rate, taken at Walter F.

George Lock and Dam, located 30.7 miles above Farley Nuclear Plant.

30

TABLE 1-5B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents -

Batch Release Summary Unit: 2 Starting :

l-Jul-2006 Ending : 31-Dec-2006 LIQUID RELEASES NUMBER OF BATCH RELEASES TOTAL TIME PERIOD FOR BATCH RELEASES MAXIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE TIME PERIOD FOR BATCH RELEASES MINIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE STREAM FLOW DURING PERIODS OF RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM 167 17698.00 145.00 105.98 1.00 MINUTES MINUTES MINUTES MINUTES 3.18E+03 CFS *

  • Average River Flow Rate, taken at Walter F.

George Lock and Dam, located 30,7 miles above Farley Nuclear Plant.

31

TABLE 1-6A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Abnormal Release Summary Unit: 1 Starting :

l-Jan-2006 Ending : 30-Jun-2006 LIQUID RELEASES NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 0

0.00 MINUTES 0.00 MINUTES 0.00 0.00

0. OOE+00 MINUTES MINUTES CURIES 32

TABLE 1-6A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents -

Abnormal Release Summary Unit: 1 Starting :

l-Jul-2006 Ending : 31-Dec-2006 LIQUID RELEASES NUMBER OF RELEASES 0

TOTAL TIME FOR ALL RELEASES 0.00 MINUTES MAXIMUM TIME FOR A RELEASE 0.00 MINUTES AVERAGE TIME FOR A RELEASE 0.00 MINUTES MINIMUM TIME FOR A RELEASE 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES 0.00E+00 CURIES 33

TABLE l-6B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents Abnormal Release Summary Unit: 2 Starting :

l-Jan-2006 Ending : 30-Jun-2006 LIQUID RELEASES NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 0

0.00 0.00 0.00 0.00

0. OOE+00 MINUTES MINUTES MINUTES MINUTES CURIES 34

TABLE l-6B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Liquid Effluents - Abnormal Release Summary Unit: 2 Starting :

l-Jul-2006 Ending : 31-Dec-2006 LIQUID RELEASES NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 0

0.00 MINUTES 0.00 MINUTES 0.00 MINUTES 0.00 MINUTES 0.00E+00 CURIES 35

2.0 GASEOUS EFFLUENTS This section contains applicable ODCM limits for gaseous effluents as well as the quantities of radioactive gaseous effluents released during 2006. These quantities are summarized on a quarterly basis and include any unplanned releases. Tabulations are provided of the offsite air doses calculated in accordance with ODCM 3.4.2 to show conformance with the limits of ODCM 3.1.3, and the offsite organ doses to a member of the public calculated in accordance with ODCM 3.4.3 to show conformance with ODCM 3.1.4.

2.1 Regulatory Requirements The requirements presented in this section are for Unit 1 and Unit 2.

2.1.1 Dose Rate Limits The dose rates due to radioactive materials released in gaseous effluents from the site to areas at and beyond the SITE BOUNDARY shall be limited to the following:

a. For noble gases: Less than or equal to 500 mrem/yr.

to the whole body and less than or equal to 3000 mrem/yr.

to the skin, and

b. For Iodine-131, Iodine-133,tritium and for all radionuclides in particulate form with half-lives greater than 8 days: Less than or equal to 1500 mrem/yr. to any organ.

2.1.2 Air Doses Due to Noble Gases in Gaseous Releases Technical Specifications 5.5.4.e and 5.5.4.h state that the air dose due to noble gases released in gaseous effluents, from each reactor unit, to areas at and beyond the SITE BOUNDARY (see ODCM Figure 10-1) shall be limited to the following:

a. During any calendar quarter: Less than or equal to 5 mrad for gamma radiation and less than or equal to 10 mrad for beta radiation, and
b. During any calendar year: Less than or equal to 10 mrad for gamma radiation and less than or equal to 20 mrad for beta radiation.

36

2.1.3 Doses to a Member of the Public Technical Specifications 5.5.4.e and 5.5.4.i state that the dose to a MEMBER OF THE PUBLIC from 1-131, 1-133, tritium, and all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents released, from each reactor unit, to areas at and beyond the SITE BOUNDARY (see ODCM Figure 10-1) shall be limited to the following:

a.

During any calendar quarter: Less than or equal to 7.5 mrem to any organ, and

b.

During any calendar year: Less than or equal to 15 mrem to any organ.

2.2 Measurements and Approximation of Total Radioactivity The following noble gases are considered in evaluating gaseous effluents:

KR-87 XE-133 KR-88 XE-135 XE-133M XE-138 The following radioiodines and radioactive materials in particulate form are specifically considered in evaluating gaseous effluents:

MN-54 MO-99 FE-59 1-131 CO-58 CS-134 CO-60 CS-137 ZN-65 CE-141 SR-89 CE-144 SR-90 H-3 2.2.1 Sample collection and Analysis Periodic grab samples from plant effluent streams are analyzed by a computerized pulse height analyzer system utilizing high resolution germanium detectors. Samples are obtained and analyzed in accordance with ODCM Table 3-3. Isotopic values thus obtained are used for release rate calculations as specified in ODCM 3.4.2 and ODCM 3.4.3. Only those nuclides which are detected are used in calculations. For radioiodines and particulates, in addition to the nuclides listed above other nuclides with half-lives greater than 8 days which are identified are also considered.

Continuous Releases: Continuous sampling is performed on the continuous release points (i.e.

the Plant Vent Stack, Containment Purge when in continuous mode, and the Turbine Building Vent).

Particulate material is collected by filtration. Periodically these filters are removed and analyzed on the pulse height analyzer to identify and quantify radioactive materials collected on the filters.

37

Particulate filters are then analyzed for gross alpha and strontium as required. All gross alpha, Sr-89 and SR-90 samples are sent offsite to the Georgia Power Environmental Laboratory for analysis.

Batch Releases: The processing of batch type releases (from Containment when in batch mode, or Waste Gas Decay Tanks) is analogous to continuous releases, except that the release is not commenced until samples have been obtained and analyzed. Containment Purge batch releases were commenced at FNP in 2006 in order to take advantage of additional decay time for short lived radionuclides.

Typically achieved minimum detectable concentrations for gaseous effluent sample analyses are reported in Table 2-6.

2.2.2 Total Quantities of Radioactivity, Dose Rates, and Cumulative Doses The methods for determining release quantities of radioactivity, dose rates, and cumulative doses follow:

2.2.2.1 Fission and Activation Gases The released radioactivity is determined using sample analyses results collected as described in section 2.2.1 and the average release flow rates over the period represented by the collected sample.

Dose rates due to noble gases, radioiodines, tritium, and particulates are calculated (with computer assistance).

The calculated dose rates are compared to the dose rate limits specified in ODCM 3.1.2 for noble gases, radioiodine, tritium, and particulates. Dose rate calculation methodology is presented in the ODCM.

Beta and gamma air doses due to noble gases are calculated for the location in the unrestricted area with the potential for the highest exposure due to gaseous releases. Air doses are calculated for each release period and cumulative totals are kept for each unit for the calendar quarter and year. Cumulative air doses are compared to the dose limits specified in ODCM 3.1.3.

The current percent of the ODCM limits are shown on the printout for each release period. Air dose calculation methodology is presented in the ODCM.

2.2.2.2 Radioiodine, Tritium, and Particulate Releases Released quantities of radioiodines are determined using the weekly samples and release flow rates for the applicable release points. Radioiodine concentrations are determined by gamma spectroscopy.

Release quantities of particulates are determined using the weekly (filter) samples and release flow rates for the applicable release points. Gamma spectroscopy is used to quantify the concentrations of principal gamma emitters.

38

After each quarter, the particulate filters from each applicable vent (plant vent stack and containment purge) are combined, fused, and a strontium separation is performed. Since sample flows and vent flows are almost constant over each quarterly period the filters from each vent can-be dissolved together.

Decay corrections are performed back to the middle of the quarterly collection period. If Sr-89 or Sr-90 is not detected, MDC's are calculated. Strontium concentrations are input into the composite file of the computer and used for release dose rate and individual dose calculations.

Tritium samples are obtained monthly from the Plant Vent Stack, the Containment Purge when in batch mode, and the Turbine Building Vent (and weekly for Containment Purge when in continuous mode) by passing the sample stream through a cold trap or by using the bubble method. The grams of water vapor/cubic meter is measured upstream of the cold trap in order to alleviate the difficulties in determining water vapor collection efficiencies. The tritium samples are analyzed onsite and the results furnished in uCi/ml of water.

The tritium concentration in water is converted to the tritium concentration in air and this value is input into the composite file of the computer and used in release, dose rate,and individual dose calculations.

Dose rates due to radioiodine, tritium and particulates are calculated for a hypothetical child exposed to the inhalation pathway at the location in the unrestricted area where the potential dose rate is expected to be the highest. Dose rates are calculated, for each release point for each release period, and the dose rates from each release point is compared to the dose rate limits specified in ODCM 3.1.2, allocated for each release point as described in ODCM 3.3.2.

Doses to a Member of the Public (individual doses) due to radioiodine, tritium and particulates are calculated for the controlling receptor, which is described in the ODCM. Individual doses are calculated for each release period, and cumulative totals are kept for each unit, for the current calendar quarter and year. Cumulative individual doses are compared to the dose limits specified in ODCM 3.1.4. The current percent of ODCM limits are shown on the printout for each release period.

2.2.2.3 Gross Alpha Release The gross alpha release is computed each month by counting the particulate filters, for each week for gross alpha activity in a proportional counter. The highest concentration calculated for any of these weeks is used for the monthly value. This value is input into the composite file of the computer and used for release calculations.

39

2.2.3 Total Error Estimation The maximum errors associated with monitor readings, sample flow, vent flow, sample collection, monitor calibration and laboratory procedure are collectively estimated to be:

Fission and Activation Gases Iodine Particulates Tritium 75%

60%

50%

45%

The average error associated with counting is estimated to be:

Fission and Activation Gases Iodine Particulates Tritium 19%

28%

20%

8%

2.3 Gaseous Effluent Release Data Regulatory Guide 1.21 Tables 1A, lB and 1C are found in this report as Tables 2-1A, 2-1B, 2-1C, 2-2A, 2-2B, 2-2C, 2-3A, 2-3B, and 2-3C. Data are presented on a quarterly basis as required by Regulatory Guide 1.21.

To complete Tables 2-1A and 2-1B, the total release for each of the four categories (fission and activation gases, radioiodines, particulates and tritium) was divided by the number of seconds in the quarter to obtain a release rate in uCi/second for each category. However, the percent of the ODCM limits are not applicable because FNP has no curie limit for gaseous releases.

Applicable limits are expressed in terms of dose. Noble gases are limited as specified in ODCM 3.1.2. The other three categories (tritium, radioiodines, and particulates) are limited as a group as specified in ODCM 3.1.2.

Dose rates due to noble gas releases and due to radioiodines, tritium and particulate releases were calculated as part of the pre-release and post-release permits. No limits were exceeded for this reporting period.

Gross alpha radioactivity is reported in Tables 2-1A, 2-1B and 2-7C as curies released in each quarter.

Limits for cumulative beta and gamma air doses due to noble gases are presented in Tables 2-4A and 2-4B along with the percent of ODCM limits.

Limits for cumulative doses to an individual due to radioiodines, tritium and particulates are specified in ODCM 3.1.4. Cumulative individual doses are presented in Tables 2-5A and 2-5B along with percent of ODCM limits.

40

2.4 Radiological Impact Due to Gaseous Releases The air doses due to noble gases and doses to a Member of the Public due to radioiodines, tritium and particulates in gaseous effluents for Units 1 and 2 are provided in the following tables in order to show conformance with the limits of ODCM 3.1.3 and ODCM 3.1.4:

Unit 1 2006 Air Doses Due to Noble Gases in Gaseous Releases: Table 2-4A Unit 2 2006 Air Doses Due to Noble Gases in Gaseous Releases: Table 2-4B Unit 1 2006 Doses to a Member of the Public Due to Radioiodines, Tritium, and Particulates in Gaseous Releases: Table 2-5A Unit 2 2006 Doses to Due to Radioiodines, in Gaseous Releases:

a Member of the Public Tritium, and Particulates Table 2-5B 2.5 Gaseous Effluents-Batch Releases Batch release information for Units 1 and 2 is following tables:

summarized in the Unit 1 2006 Gaseous Effluents -

Batch Release Summary: Table 2-7A Unit 2 2006 Gaseous Effluents -

Batch Release Summary: Table 2-7B 2.6 Gaseous Effluents - Abnormal Releases There were no abnormal releases on Unit 1 or Unit 2 during 2006.

Abnormal release information for the following tables:

Units 1 and 2 is summarized in Unit 1 2006 Unit 2 2006 Gaseous Effluents - Abnormal Release Summary: Table 2-8A Gaseous Effluents - Abnormal Release Summary: Table 2-8B 41

TABLE 2-1A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents -

Summation of All Releases Unit: 1 Starting :

l-Jan-2006 Ending : 30-Jun-2006 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE CURIES 9.04E+00 3.87E+00 7.74E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.16E+00 4.92E-01

3.

PERCENT OF APPLICABLE LIMIT B.

RADIOIODINES

1. TOTAL IODINE-131 CURIES 0.OOE+00 9.11E-05 6.62E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 0.OOE+00 1.16E-05

3.

PERCENT OF APPLICABLE LIMIT C.

PARTICULATES

1. PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 7.42E-08 4.90E-06 5.39E+01

2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 9.54E-09 6.23E-07

3.

PERCENT OF APPLICABLE LIMIT

4.

GROSS ALPHA RADIOACTIVITY CURIES 0.OOE+00 0.OOE+00 D.

TRITIUM

1. TOTAL RELEASE CURIES 2.91E+00 3.37E+00 4.57E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 3.75E-01 4.28E-01

3.

PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

42

TABLE 2-1A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents -

Summation of All Releases Unit: 1 Starting :

l-Jul-2006 Ending : 31-Dec-2006 TYPE OF EFFLUENT UNITS QUARTER 3

QUARTER 4 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE CURIES 5.28E+00 3.36E-01 7.74E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 6.64E-01 4.23E-02

3.

PERCENT OF APPLICABLE LIMIT B.

RADIOIODINES

1. TOTAL IODINE-131 CURIES 4.14E-05 7.14E-05 6.62E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 5.21E-06 8.98E-06

3.

PERCENT OF APPLICABLE LIMIT C.

PARTICULATES

1. PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 0.OOE+00 8.64E-07 5.39E+01

2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 0.OOE+00 1.09E-07

3.

PERCENT OF APPLICABLE LIMIT

4.

GROSS ALPHA RADIOACTIVITY CURIES 0.OOE+00 0.OOE+00 D.

TRITIUM

1. TOTAL RELEASE CURIES' 1.63E-01 7.73E-01 4.57E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 2.05E-02 9.72E-02

3.

PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

43

TABLE 2-1B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents -

Summation of All Releases Unit: 2 Starting :

l-Jan-2006 Ending : 30-Jun-2006 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE CURIES 5.32E+00 2.95E-01 7.74E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 6.84E-01 3.75E-02

3.

PERCENT OF APPLICABLE LIMIT B.

RADIOIODINES

1. TOTAL IODINE-131 CURIES 0.OOE+00 0.OOE+00 6.62E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 0.OOE+00 0.OOE+00

3.

PERCENT OF APPLICABLE LIMIT C. PARTICULATES

1. PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 3.64E-08 7.09E-09 5.39E+01

2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 4.68E-09 9.01E-10

3.

PERCENT OF APPLICABLE LIMIT

4.

GROSS ALPHA RADIOACTIVITY CURIES 0.OOE+00 0.OOE+00 D. TRITIUM

1. TOTAL RELEASE CURIES 1.50E+00 1.73E+00 4.57E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.93E-01 2.20E-01

3.

PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

44

TABLE 2-1B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents -

Summation of All Releases Unit: 2 Starting :

l-Jul-2006 Ending : 31-Dec-2006 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE CURIES 4.58E-01 8.91E-01 7.74E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 5.76E-02 1.12E-01

3.

PERCENT OF APPLICABLE LIMIT B.

RADIOIODINES

1. TOTAL IODINE-131 CURIES 0.OOE+00 0.OOE+00 6.62E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 0.OOE+00 0.OOE+00

3.

PERCENT OF APPLICABLE LIMIT C.

PARTICULATES

1. PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 4.24E-08 3.19E-09 5.39E+01

2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 5.33E-09 4.02E-10

3.

PERCENT OF APPLICABLE LIMIT

4.

GROSS ALPHA RADIOACTIVITY CURIES 1.81E-07 0.OOE+00 D.

TRITIUM

1. TOTAL RELEASE CURIES 6.86E-01 1.24E+00 4.57E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 8.62E-02 1.56E-01

3.

PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

45

TABLE 2-IC Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT 2006 Gaseous Effluents -

Summation of All Releases Unit: Site Starting :

l-Jan-2006 Ending : 30-Jun-2006 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE CURIES 1.44E+01 4.16E+00 7.74E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.85E+00 5.29E-01

3.

PERCENT OF APPLICABLE LIMIT B.

RADIOIODINES

1. TOTAL IODINE-131 CURIES 0.OOE+00 9.11E-05 6.62E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 0.OOE+00 1.16E-05

3.

PERCENT OF APPLICABLE LIMIT C.

PARTICULATES

1. PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 1.lIE-07 4.91E-06 5.39E+01

2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.42E-08 6.24E-07

3.

PERCENT OF APPLICABLE LIMIT

4.

GROSS ALPHA RADIOACTIVITY CURIES 0.OOE+00 0.OOE+00 D.

TRITIUM

1. TOTAL RELEASE CURIES 4.42E+00 5.09E+00 4.57E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 5.68E-01 6.48E-01

3.

PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

46

TABLE 2-IC Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents -

Summation of All Releases Unit: Site Starting :

l-Jul-2006 Ending : 31-Dec-2006 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST.

TOT ERROR %

A.

FISSION & ACTIVATION PRODUCTS

1. TOTAL RELEASE CURIES 5.74E+00 1.23E+00 7.74E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 7.22E-01 1.54E-01

3.

PERCENT OF APPLICABLE LIMIT B.

RADIOIODINES

1. TOTAL IODINE-131 CURIES 4.14E-05 7.14E-05 6.62E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 5.21E-06 8.98E-06

3.

PERCENT OF APPLICABLE LIMIT C.

PARTICULATES

1. PARTICULATES(HALF-LIVES>8 DAYS)

CURIES 4.24E-08 8.75E-07 5.39E+01

2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 5.33E-09 1.10E-07

3.

PERCENT OF APPLICABLE LIMIT

4.

GROSS ALPHA RADIOACTIVITY CURIES 1.81E-07 0.OOE+00 D.

TRITIUM

1. TOTAL RELEASE CURIES 8.48E-01 2.01E+00 4.57E+01
2.

AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.07E-01 2.53E-01

3.

PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.

See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.

47

TABLE 2-2A*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Mixed-Mode Level Releases Unit: 1 Starting :

l-Jan-2006 Ending : 30-Jun-2006 I

CONTINUOUS MODE I

BATCH MODE NUCLIDES RELEASED UNIT QUARTER 1 QUARTER 2 IQUARTER 1 IQUARTER 2 FISSION GASES AR-41 CURIES 9.04E+00 3.87E+00 1.79E-04 0.OOE+00 KR-85M CURIES 0.OOE+00 0.OOE+00 1.62E-05 0.OOE+00 XE-135 CURIES 0.OOE+00 0.OOE+00 5.32E-04 0.OOE+00 XE-133 CURIES 0.OOE+00 0.OOE+00 5.06E-03 2.17E-03 TOTAL FOR PERIOD CURIES 9.04E+00 I 3.87E+00 5.79E-03 2.17E-03 IODINES 1-133 CURIES 0.OOE+00 8.38E-05 0.OOE+00 0.OOE+00 1-131 CURIES 0.OOE+00 9.13E-05 0.OOE+00 0.OOE+00 TOTAL FOR PERIOD CURIES 0.OOE+00 Il75E-04 0.OOE+00 I 0.OOE+00 PARTICULATES SR-89 CURIES O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 CO-60 CURIES 6.56E-08 4.89E-06 0.OOE+00 0.OOE+00 TOTAL FOR PERIOD CURIES 6.56E-08 I 4.89E-06 I 0.OOE+00 I 0.OOE+00 H-3 CURIES 2.91E+00 3.37E+00 0.OOE+00 0.OOE+00 G-ALPHA CURIES 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

48

TABLE 2-2A*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Mixed-Mode Level Releases.

Unit: 1 Starting l-Jul-2006 Ending : 31-Dec-2006 CONTINUOUS MODE BATCH MODE NUCLIDES RELEASED UNIT FQUARTER 3 IQUARTER 4 QUARTER 3 IQUARTER 4 1

FISSION GASES AR-41 CURIES 2.11E+00 0.OOE+00 5.16E-01 3.26E-01 KR-85M CURIES 1.13E-02 0.OOE+00 0.OOE+00 0.OOE+00 XE-135 CURIES 0.OOE+00 0.OOE+00 4.22E-04 0.OOE+00 XE-133 CURIES 2.63E+00 0.OOE+00 1.37E-02 9.59E-03 TOTAL FOR PERIOD I CURIES I 4.75E+00 I 0.OOE+00 I 5.30E-01 I 3.36E-01 I

IODINES 1-133 CURIES 3.93E-04 8.61E-04 0.OOE+00 0.OOE+00 1-131 CURIES 4.14E-05 7.14E-05 0.OOE+00 0.OOE+00 TOTAL FOR PERIOD CURIES 4.35E-04 I 9.32E-04 I 0.OOE+00 I 0.OOE+00 PARTICULATES EU-155 I

CURIES I 0.OOE+00 I 8.64E-07 I 0.OOE+00 I 0.OOE+00 I TOTAL FOR PERIOD I

CURIES I 0.OOE+00 I 8.64E-07 I 0.OOE+00 I 0.OOE+00 I H-3 CURIES F 8.28E-02 6.44E-01 I 7.97E-02 I 1.29E-01 I G-ALPHA F CURIES F 0.OOE+00 0.OOE+00 I 0.OOE+00 I 0.00E+00-1 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

49

TABLE 2-2B*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Mixed-Mode Level Releases Unit: 2 Starting :

l-Jan-2006 Ending : 30-Jun-2006 I

CONTINUOUS MODE I

BATCH MODE NUCLIDES RELEASED I

UNIT IQUARTER 1 IQUARTER 2 IQUARTER 1 IQUARTER 2 FISSION GASES AR-41 I

CURIES 5.32E+00 0.OOE+00 0.OOE+00 2.95E-01 XE-133 I

CURIES 0.OOE+00 0.OOE+00 2.35E-04 I 0.OOE+00 TOTAL FOR PERIOD I

CURIES I 5.32E+00 I 0.OOE+00 I 2.35E-04 I 2.95E-01 IODINES TOTAL FOR PERIOD I

CURIES I 0.OOE+00 I 0.OOE+00 I 0.OOE+00 I 0.OOE+00 PARTICULATES SR-89 CURIES 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 SR-90 CURIES 3.64E-08 2.22E-16 0.OOE+00 I 0.00E+00 TOTAL FOR PERIOD CURIES 3.64E-08 I 2.22E-16 I 0.OOE+00 0.OOE+00 H-3 CURIES 1.50E+00 1 1.72E+00 0.OOE+00 3.40E-03 G-ALPHA CURIES 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

50

TABLE 2-2B*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Mixed-Mode Level Releases Unit: 2 Starting :

l-Jul-2006 Ending : 31-Dec-2006 I

CONTINUOUS MODE BATCH MODE NUCLIDES RELEASED UNIT IQUARTER 3 IQUARTER 4 QUARTER 3 IQUARTER 4 FISSION GASES AR-41 CURIES 1.49E-01 5.57E-01 3.09E-01 3.21E-01 KR-85M CURIES 0.OOE+00 0.OOE+00 0.OOE+00 1.97E-04 XE-133 CURIES 0.00E+00 0.00E+00 1.64E-05 3.29E-03 XE-131M CURIES 0.OOE+00 0.00E+00 0.OOE+00 9.86E-03 TOTAL FOR PERIOD CURIES 1.49E-01 5.57E-01 I 3.09E-01 3.34E-01 IODINES TOTAL FOR PERIOD I

CURIES I 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 PARTICULATES SR-89 CURIES 4.24E-08 3.19E-09 0.OOE+00 0.OOE+00 SR-90 CURIES 0.00E+00 0.OOE+00 0.00E+00 0.OOE+00 TOTAL FOR PERIOD CURIES 4.24E-08 I 3.19E-09 I 0.OOE+00 0.OOE+00 I H-3 CURIES 6.80E-01 1.24E+00 6.02E-03 4.51E-04 G-ALPHA CURIES 1.81E-07 0.OOE+00 0.OOE+00 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

51

TABLE 2-2C*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Mixed-Mode Level Releases Unit: Site Starting :

l-Jan-2006 Ending : 30-Jun-2006 I

CONTINUOUS MODE I

BATCH MODE I

NUCLIDES RELEASED I

UNIT IQUARTER 1 IQUARTER 2 IQUARTER I IQUARTER 2 1

FISSION GASES AR-41 CURIES 1.44E+01 3.87E+00 1.79E-04 2.95E-01 KR-85M CURIES 0.OOE+00 0.OOE+00 1.62E-05 0.OOE+00 XE-135 CURIES 0.00E+00 0.OOE+00 5.32E-04 0.OOE+00 XE-133 CURIES 0.OOE+00 0.OOE+00 5.29E-03 2.17E-03 TOTAL FOR PERIOD I CURIES I 1.44E+01 3.87E+00 1 6.02E-03 2.97E-01 IODINES 1-133 CURIES 0.OOE+00 8.38E-05 0.OOE+00 0.OOE+00 1-131 CURIES 0.OOE+00 9.11E-05 0.OOE+00 0.OOE+00 TOTAL FOR PERIOD CURIES 0.OOE+00 I 1.75E-04 I 0.OOE+00 I 0.OOE+00 PARTICULATES SR-89 CURIES 0.00E+00 0.OOE+00 0.OOE+00 0.OOE+00 CO-60 CURIES 6.56E-08 4.89E-06 0.OOE+00 0.OOE+00 SR-90 CURIES 3.64E-08 2.22E-16 0.00E+00 0.OOE+00 TOTAL FOR PERIOD CURIES 1.02E-07 I 4.89E-06 I 0.OOE+00 I 0.OOE+00 H-3 CURIES 4.42E+00 5.09E+00 0.OOE+00 3.40E-03 F G-ALPHA CURIES F 0.OOE+00 0.00E+00 0.OOE+00 0.OOE+00 F Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

52

TABLE 2-2C*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Mixed-Mode Level Releases Unit: Site Starting :

l-Jul-2006 Ending : 31-Dec-2006 I

CONTINUOUS MODE BATCH MODE NUCLIDES RELEASED I

UNIT IQUARTER 3 IQUARTER 4 IQUARTER 3 IQUARTER 4 1

FISSION GASES AR-41 CURIES 2.26E+00 I 5.57E-01 8.25E-01 6.47E-01 KR-85M CURIES 1.13E-02 0.OOE+00 0.OOE+00 1 1.97E-04 XE-135 CURIES 0.OOE+00 0.00E+00 I 4.22E-04 0.OOE+00 XE-133 I

CURIES I 2.63E+00 0.OOE+00 1 1.37E-02 1 1.29E-02 XE-131M I

CURIES 0.OOE+00 I 0.OOE+00 0.OOE+00 I 9.86E-03 TOTAL FOR PERIOD I

CURIES I 4.90E+00 I 5.57E-01 I 8.39E-01 I 6.70E-01 I IODINES 1-133 CURIES 3.93E-04 8.61E-04 0.OOE+00 0.OOE+00 1-131 I

CURIES 4.14E-05 7.14E-05 j 0.OOE+00 I 0.OOE+00 TOTAL FOR PERIOD I

CURIES I 4.35E-04 I 9.32E-04 I 0.OOE+00 I 0.OOE+00 I

PARTICULATES SR-89 I CURIES I 4.24E-08 3.19E-09 [ 0.OOE+00 I 0.OOE+00 EU-155 I CURIES 0.OOE+00 I 8.64E-07 0.OOE+00 0.OOE+00 SR-90 CURIES j 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 TOTAL FOR PERIOD I CURIES I 4.24E-08 I 8.67E-07 I 0.OOE+00 I 0.OOE+00 I

H-3 j

CURIES 7.62E-01 1.88E+00 I 8.58E-02 1.29E-01 G-ALPHA I

CURIES l.81E-07 0.OOE+00 I 0.OOE+00 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

53

TABLE 2-3A*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Ground Level Releases Unit: 1 Starting :

l-Jan-2006 Ending : 30-Jun-2006 I

CONTINUOUS MODE I

BATCH MODE NUCLIDES RELEASED UNIT QUARTER 1 QUARTER 2 QUARTER 1 IQUARTER 2 FISSION GASES TOTAL FOR PERIOD I

CURIES I 0.OOE+00 0.OOE+00 I 0.OOE+00 0.OOE+00 IODINES TOTAL FOR PERIOD I

CURIES I 0.OOE+00 0.OOE+00 0.OOE+00 I 0.00E+00 PARTICULATES CO-60 I

CURIES I 8.55E-09 I 6.41E-09 I 0.OOE+00 0.OOE+00 TOTAL FOR PERIOD CURIES I 8.55E-09 6.41E-09 I 0.OOE+00 0.OOE+00 H-3 I

CURIES I 2.68E-05 I 0.OOE+00 I 0.OOE+00 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

54

TABLE 2-3A*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Ground Level Releases Unit: 1 Starting :

l-Jul-2006 Ending : 31-Dec-2006 I

CONTINUOUS MODE BATCH MODE NUCLIDES RELEASED UNIT QUARTER 3 IQUARTER 4 QUARTER 3 IQUARTER 4 FISSION GASES TOTAL FOR PERIOD CURIES 0.OOE+00 I 0.OOE+00 0.OOE+00 0.OOE+00 IODINES TOTAL FOR PERIOD CURIES I 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 I

PARTICULATES TOTAL FOR PERIOD I

CURIES I 0.OOE+.00 0.OOE+00 0.OOE+00 I 0.OOE+00 H-3 CURIES I 0.OOE+00 I 0.OOE+00 0.OOE+00 I 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

55

TABLE 2-3B*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Ground Level Releases Unit: 2 Starting :

l-Jan-2006 Ending : 30-Jun-2006 CONTINUOUS MODE BATCH MODE NUCLIDES RELEASED I

UNIT QUARTER 1 IQUARTER 2 QUARTER 1 IQUARTER 2 FISSION GASES TOTAL FOR PERIOD I

CURIES I 0.OOE+00 0.OOE+00 I 0.OOE+00 0.OOE+00 IODINES TOTAL FOR PERIOD

.1 CURIES I 0.OOE+00 I 0.OOE+00 0.OOE+00 I 0.OOE+00 PARTICULATES TOTAL FOR PERIOD I

CURIES 0.OOE+00 1 0.00+00 1 0.00E+00 I 0.OOE+001 H-3 I

CURIES 0.OOE+00 0.00E+00 I 0.OOE+00 I 0.00E+001 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

56

TABLE 2-3B*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Ground Level Releases Unit: 2 Starting l-Jul-2006 Ending : 31-Dec-2006 I

CONTINUOUS MODE BATCH MODE NUCLIDES RELEASED UNIT IQUARTER 3 IQUARTER 4 QUARTER 3 IQUARTER 4 1

FISSION GASES TOTAL FOR PERIOD I CURIES I 0.OOE+00 0.00E+00 0.OOE+00 I 0.OOE+00 IODINES TOTAL FOR PERIOD I CURIES I 0.OOE+00 F 0.OOE+00 I 0.OOE+00 I 0.00E+00 PARTICULATES TOTAL FOR PERIOD I CURIES I 0.OOE+00 I 0.OOE+00 I 0.00E+00 I 0.OOE+00 I H-3 I CURIES I 0.OOE+00 I 0.00E+00 I 0.00E+00 I 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

57

TABLE 2-3C*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Ground Level Releases Unit: Site Starting :

l-Jan-2006 Ending : 30-Jun-2006 I

CONTINUOUS MODE I

BATCH MODE NUCLIDES RELEASED I

UNIT QUARTER 1 QUARTER 2 QUARTER 1 IQUARTER 2 FISSION GASES TOTAL FOR PERIOD CURIES 0.OOE+00 I 0.OOE+00 I 0.OOE+00 0.OOE+00 IODINES TOTAL FOR PERIOD I

CURIES I 0.OOE+00 0.OOE+00 I 0.OOE+00 0.OOE+00 PARTICULATES CO-60 CURIES 8.55E-09 I 6.41E-09 0.OOE+00 I 0.OOE+00 TOTAL FOR PERIOD I

CURIES I 8.55E-09 I 6.41E-09 I 0.OOE+00 0.OOE+00 H-3 CURIES 2.68E-05 I 0.OOE+00 I 0.OOE+00 0.OOE+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

58

TABLE 2-3C*

Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents-Ground Level Releases Unit: Site Starting :

l-Jul-2006 Ending : 31-Dec-2006 CONTINUOUS MODE BATCH MODE NUCLIDES RELEASED I

UNIT IQUARTER 3 IQUARTER 4 QUARTER 3

IQUARTER 4 FISSION GASES TOTAL FOR PERIOD I

CURIES I 0.OOE+00 I 0.OOE+00 0.OOE+00 I 0.OOE+00 IODINES TOTAL FOR PERIOD I

CURIES I 0.OOE+00 I 0.OOE+00 I 0.OOE+00 I 0.OOE+00 PARTICULATES TOTAL FOR PERIOD I

CURIES I 0.OOE+00 I 0.OOE+00 I 0.OOE+00 I 0.OOE+00 H-3 I

CURIES I 0.00E+00 I'0.00E+00 I 0.OOE+00 I 0.OOE+00 I Zeroes in this table indicate that no radioactivity was present at detectable levels.

See Table 2-6 for typically achieved minimum detectable concentrations.

59

TABLE 2-4A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 AIR DOSES DUE TO NOBLE GASES IN GASEOUS RELEASES Unit: 1 Starting: 01-Jan-2006 Ending: 30-Jun-2006 Cumulative Doses per Quarter Type ODCM Units Quarter

% of Quarter

% of of Limit 1

ODCM 2

ODCM Radi-Limit Limit ation Gamma 5.0 mrad 2.88E-03 5.75E-02 1.23E-03 2.46E-02 Beta 10.0 mrad 1.02E-03 1.02E-02 4.34E-04 4.34E-03 Cumulative Doses per Year Type ODCM Units Year to

% of of Limit Ending ODCM Radi-Date Limit ation Gamma 10.0 mrad 4.11E-03 4.11E-02 Beta 20.0 mrad 1.45E-03 7.25E-03 60

TABLE 2-4A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 AIR DOSES DUE TO NOBLE GASES IN GASEOUS RELEASES Unit: 1 Starting: 01-Jul-2006 Ending: 31-Dec-2006 Cumulative Doses per Quarter Type ODCM Units Quarter

% of Quarter

% of of Limit 3

ODCM 4

ODCM Radi-Limit Limit ation Gamma 5.0 mrad 8.69E-04 1.74E-02 1.04E-04 2.08E-03 Beta 10.0 mrad 3.91E-04 3.91E-03 3.70E-05 3.70E-04 Cumulative Doses per Year Type ODCM Units Year to

% of of Limit Ending ODCM Radi-Date Limit ation Gamma 10.0 mrad 5.08E-03 5.08E-02 Beta 20.0 mrad 1.88E-03 9.39E-03 61

TABLE 2-4B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 AIR DOSES DUE TO NOBLE GASES IN GASEOUS RELEASES Unit: 2 Starting: 01-Jan-2006 Ending: 30-Jun-2006 Cumulative Doses per Quarter Type ODCM Units Quarter

% of Quarter

% of of Limit 1

ODCM 2

ODCM Radi-Limit Limit ation Gamma 5.0 mrad 1.69E-03 3.39E-02 9.40E-05 1.88E-03 Beta 10.0 mrad 5.98E-04 5.98E-03 3.31E-05 3.31E-04 Cumulative Doses per Year Type ODCM Units Year to

% of of Limit Ending ODCM Radi-Date Limit ation Gamma 10.0 mrad 1.79E-03 1.79E-02 Beta 20.0 mrad 6.31E-04 3.15E-03 62

TABLE 2-4B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 AIR DOSES DUE TO NOBLE GASES IN GASEOUS RELEASES Unit: 2 Starting: 01-Jul-2006 Ending: 31-Dec-2006 Cumulative Doses per Quarter Type ODCM Units Quarter

% of Quarter

% of of Limit 3

ODCM 4

ODCM Radi-Limit Limit ation Gamma 5.0 mrad 1.46E-04 2.92E-03 2.80E-04 5.59E-03 Beta 10.0 mrad 5.14E-05 5.14E-04 9.91E-05 9.91E-04 Cumulative Doses per Year Type ODCM Units Year to

% of of Limit Ending ODCM Radi-Date Limit ation Gamma 10.0 mrad 2.21E-03 2.21E-02 Beta 20.0 mrad 7.81E-04 3.91E-03 63

TABLE 2-5A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES,

TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 1 Starting: 01-Jan-2006 Ending: 30-Jun-2006 Cumulative Doses per Quarter Organ ODCM Unit Quarter

% of Quarter

% of Limit 1

ODCM 2

ODCM Limit Limit Bone 7.5 mrem 6.23E-07 8.31E-06 4.08E-05 5.44E-04 Liver 7.5 mrem 3.98E-04 5.31E-03 5.01E-04 6.69E-03 TBody 7.5 mrem 3.98E-04 5.31E-03 5.01E-04 6.67E-03 Thyroid 7.5 mrem 3.98E-04 5.31E-03 2.17E-03 2.90E-02 Kidney 7.5 mrem 3.98E-04 5.31E-03 5.04E-04 6.72E-03 Lung 7.5 mrem 3.98E-04 5.31E-03 4.96E-04

.6.62E-03 GILLI 7.5 mrem 3.98E-04 5.31E-03 5.OOE-04 6.67E-03 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 15.0 mrem 4.14E-05 2.76E-04 Liver 15.0 mrem 9.OOE-04 6.00E-03 TBody 15.0 mrem 8.99E-04 5.99E-03 Thyroid 15.0 mrem 2.57E-03 1.71E-02 Kidney 15.0 mrem 9.02E-04 6.02E-03 Lung 15.0 mrem 8.95E-04 5.97E-03 GILLI 15.0 mrem 8.99E-04 5.99E-03 64

TABLE 2-5A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES,

TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 1 Starting: 01-Jul-2006 Ending: 31-Dec-2006 Cumulative Doses per Quarter Organ ODCM Unit Quarter

% of Quarter

% of Limit 3

ODCM 4

ODCM Limit Limit Bone 7.5 mrem 3.44E-06 4.58E-05 6.36E-06 8.48E-05 Liver 7.5 mrem 2.58E-05 3.44E-04 1.12E-04 1.50E-03 TBody 7.5 mrem 2.43E-05 3.24E-04 1.09E-04 1.46E-03 Thyroid 7.5 mrem 9.16E-04 1.22E-02 1.71E-03 2.28E-02 Kidney 7.5 mrem 2.78E-05 3.70E-04 1.16E-04 1.54E-03 Lung 7.5 mrem 2.28E-05 3.03E-04 1.07E-04 1.42E-03 GILLI 7.5 mrem 2.32E-05 3.10E-04 1.08E-04 1.43E-03 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 15.0 mrem 5.12E-05 3.42E-04 Liver 15.0 mrem 1.04E-03 6.92E-03 TBody 15.0 mrem 1.03E-03 6.89E-03 Thyroid 15.0 mrem 5.20E-03 3.46E-02 Kidney 15.0 mrem 1.05E-03 6.97E-03 Lung 15.0 mrem 1.02E-03 6.83E-03 GILLI 15.0 mrem 1.03E-03 6.86E-03 65

TABLE 2-5B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES,

TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 2 Starting: 01-Jan-2006 Ending: 30-Jun-2006 Cumulative Doses per Quarter Organ ODCM Unit Quarter

% of Quarter

% of Limit 1

ODCM 2

ODCM Limit Limit Bone 7.5 mrem 1.53E-05 2.03E-04 1.90E-12 2.53E-11 Liver 7.5 mrem 2.05E-04 2.74E-03 2.36E-04 3.14E-03 TBody 7.5 mrem 2.09E-04 2.79E-03 2.36E-04 3.14E-03 Thyroid 7.5 mrem 2.05E-04 2.74E-03 2.36E-04 3.14E-03 Kidney 7.5 mrem 2.05E-04 2.74E-03 2.36E-04 3.14E-03 Lung 7.5 mrem 2.05E-04 2.74E-03 2.36E-04 3.14E-03 GILLI 7.5 mrem 2.06E-04 2.74E-03 2.36E-04 3.14E-03 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 15.0 mrem 1.53E-05 1.02E-04 Liver 15.0 mrem 4.41E-04 2.94E-03 TBody 15.0 mrem 4.45E-04 2.97E-03 Thyroid 15.0 mrem 4.41E-04 2.94E-03 Kidney 15.0 mrem 4.41E-04 2.94E-03 Lung 15.0 mrem 4.41E-04 2.94E-03 GILLI 15.0 mrem 4.41E-04 2.94E-03 66

TABLE 2-5B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES,

TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 2 Starting: 01-Jul-2006 Ending: 31-Dec-2006 Cumulative Doses per Quarter Organ ODCM Unit Quarter

% of Quarter

% of Limit 3

ODCM 4

ODCM Limit Limit Bone 7.5 mrem 8.23E-07 1.10E-05 3.88E-08 5.18E-07 Liver 7.5 mrem 9.36E-05 1.25E-03 1.69E-04 2.25E-03 TBody 7.5 mrem 9.36E-05 1.25E-03 1.69E-04 2.25E-03 Thyroid 7.5 mrem 9.36E-05 1.25E-03 1.69E-04 2.25E-03 Kidney 7.5 mrem 9.36E-05 1.25E-03 1.69E-04 2.25E-03 Lung 7.5 mrem 9.36E-05 1.25E-03 1.69E-04 2.25E-03 GILLI 7.5 mrem 9.36E-05 1.25E-03 1.69E-04 2.25E-03 Cumulative Doses per Year Organ ODCM Units Year to

% of Limit Ending ODCM Date Limit Bone 15.0 mrem 1.61E-05 1.07E-04 Liver 15.0 mrem 7.04E-04 4.69E-03 TBody 15.0 mrem 7.08E-04 4.72E-03 Thyroid 15.0 mrem 7.04E-04 4.69E-03 Kidney 15.0 mrem 7.04E-04 4.69E-03 Lung 15.0 mrem 7.04E-04 4.69E-03 GILLI 15.0 mrem 7.04E-04 4.69E-03 67

TABLE 2-6 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 MINIMUM DETECTABLE CONCENTRATIONS GASEOUS EFFLUENT ANALYSES The values in this table represent a priori Minimum Detectable Concentrations (MDC) that are typically achieved in laboratory analyses of gaseous radwaste samples.

Nuclide MDC(uCi/ML)

MN-54 3.21E-15 CO-58 1.53E-14 FE-59 7.96E-15 CO-60 1.95E-14 ZN-65 2.34E-14 MO-99 1.81E-13 CS-134 1.41E-14 CS-137 7.83E-15 CE-141 6.96E-15 CE-144 3.47E-14 KR-87 8.18E-07 KR-88 3.94E-08 XE-133 4.30E-08 XE-133M 4.82E-08 XE-135 1.78E-08 XE-138 1.99E-07 1-131 9.67E-15 1-133 1.80E-13 68

TABLE 2-7A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents -

Batch Release Summary Unit: 1 Starting :

l-Jan-2006 Ending : 30-Jun-2006 GASEOUS RELEASES NUMBER OF BATCH RELEASES TOTAL TIME PERIOD FOR BATCH RELEASES MAXIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE TIME PERIOD FOR BATCH RELEASES MINIMUM TIME FOR A BATCH RELEASE 20 7692.00 791.00 384.60 257.00 MINUTES MINUTES MINUTES

.MINUTES 69

TABLE 2-7A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents -

Batch Release Summary Unit: 1 Starting :

l-Jul-2006 Ending : 31-Dec-2006 GASEOUS RELEASES NUMBER OF BATCH RELEASES 72 TOTAL TIME PERIOD FOR BATCH RELEASES 11943.00 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE 645.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 165.88 MINUTES MINIMUM TIME FOR A BATCH RELEASE 26.00 MINUTES 70

TABLE 2-7B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents - Batch Release Summary Unit: 2 Starting :

l-Jan-2006 Ending : 30-Jun-2006 GASEOUS RELEASES NUMBER OF BATCH RELEASES TOTAL TIME PERIOD FOR BATCH RELEASES MAXIMUM TIME PERIOD FOR A BATCH RELEASE AVERAGE TIME PERIOD FOR BATCH RELEASES MINIMUM TIME FOR A BATCH RELEASE 36 5162.00 MINUTES 477.00 MINUTES 143.39 MINUTES 72.00 MINUTES 71

TABLE 2-7B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents - Batch Release Summary Unit: 2 Starting :

l-Jul-2006 Ending : 31-Dec-2006 GASEOUS RELEASES NUMBER OF BATCH RELEASES 65 TOTAL TIME PERIOD FOR BATCH RELEASES 8503.00 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE 493.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 130.82 MINUTES MINIMUM TIME FOR A BATCH RELEASE 19.00 MINUTES 72

TABLE 2-8A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents - Abnormal Release Summary Unit: 1 Starting :

l-Jan-2006 Ending : 30-Jun-2006 GASEOUS RELEASES NUMBER OF RELEASES TOTAL TIME FOR ALL MAXIMUM TIME FOR A AVERAGE TIME FOR A MINIMUM TIME FOR A TOTAL ACTIVITY FOR RELEASES RELEASE RELEASE RELEASE ALL RELEASES 0

0.00 MINUTES 0.00 MINUTES 0.00 MINUTES 0.00 MINUTES 0..OOE+00 CURIES 73

TABLE 2-8A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents - Abnormal Release Summary Unit: 1 Starting :

l-Jul-2006 Ending : 31-Dec-2006 GASEOUS RELEASES NUMBER OF RELEASES 0

TOTAL TIME FOR ALL RELEASES 0.00 MINUTES MAXIMUM TIME FOR A RELEASE 0.00 MINUTES AVERAGE TIME FOR A RELEASE 0..00 MINUTES MINIMUM TIME FOR A RELEASE 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES :

0.OOE+00 CURIES 74

TABLE 2-8B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents -

Abnormal Release Summary Unit: 2 Starting :

l-Jan-2006 Ending : 30-Jun-2006 GASEOUS RELEASES NUMBER OF RELEASES TOTAL TIME FOR ALL RELEASES MAXIMUM TIME FOR A RELEASE AVERAGE TIME FOR A RELEASE MINIMUM TIME FOR A RELEASE TOTAL ACTIVITY FOR ALL RELEASES 0

0.00 MINUTES 0.00 MINUTES 0.00 MINUTES 0.00 MINUTES 0.OOE+00 CURIES 75

TABLE 2-8B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 Gaseous Effluents -

Abnormal Release Summary Unit: 2 Starting :

l-Jul-2006 Ending : 31-Dec-2006 GASEOUS RELEASES NUMBER OF RELEASES 0

TOTAL TIME FOR ALL RELEASES 0.00 MINUTES MAXIMUM TIME FOR A RELEASE 0.00 MINUTES AVERAGE TIME FOR A RELEASE 0.00 MINUTES MINIMUM TIME FOR A RELEASE 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES 0.00E+00 CURIES 76

3.0 SOLID WASTE 3.1 Regulatory Requirements 3.1.1 Solid Radioactive Waste System PCP B.3.1 states in part that the radwaste solidification system shall be operable and used for the solidification and packaging of radioactive wastes to ensure meeting the requirements of 10CFR Part 20 and 10CFR Part 71 prior to shipment of radioactive wastes from the site.

3.1.2 Reporting Requirements PCP B.5.1.1 states in part that the Annual Radioactive Effluent Release Report, submitted in accordance with Technical Specification 5.6.3, shall include a summary of the quantities of solid radwaste released from the units as outlined in Regulatory Guide 1.21, with data summarized on a six-month basis following the format of Appendix B thereof.

3.2 Solid Waste Data Regulatory Guide 1.21 Table 3 is found in this report as Table 3-1.

The error involved in determining the contents of solid radwaste shipments is estimated to be less than + or -

15%.

77

TABLE 3-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Starting: 01-Jan-2006 Ending: 30-Jun-2006 A.

SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (not irradiated fuel)

1. Type of Waste.
a.

Spent resins, Filter

sludges, evaporator bottoms, etc.
b.

Dry compressible waste, contaminated equipment, etc.

c. Irradiated components, control rods, etc.

UNITS 6-Months 3

m 1.720E+00 Ci*

1.11OE+02 3

m 3.340E+02 Ci*

2.062E+01 3

m None Ci*

None 3

m None Ci*

None

d.

Other (describe)

2.

Estimate of major nuclide composition (by type of waste).

a.

NI-63 59.0%

CO-60 15.0%

FE-55 10.0%

NI-59 7.1%

C-14 2.0%

CO-58 1.4%

b.

CO-60 33.2%

FE-55 24.2%

ZN-65 19.2%

CO-58 6.0%

CR-51 4.3%

ZR-95 3.0%

NB-95 2.8%

SB-125 1.4%

MN-54 1.1%

  • Measured and/or with I0CFR61.55.

estimated by correlations in accordance 78

TABLE 3-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Starting: 01-Jan-2006 Ending: 30-Jun-2006 (continued)

3.

Solid Waste Disposition Number of Shipments Mode of Transl 15 HighwE 6

2 Highwa Waterway/H

)ortation Destination

  • y Envirocare of Utah
  • y
Barnwell, SC Iighway Envirocare of Utah Envirocare of Utah for burial/processing)

Number Container 3 of Volume (m

Containers 1

3.850E+00 50 Rail

4.

Type of Containers (Shipped offsite Container Type of Description Container

a.

RADLOC 500 High Integrity Container CNS 8-120 High Integrity Container

b.

20' Sealand General Design Package Retired Rx General Design Heads Package

5.

Solidification Agent

a.

None

b.

None 1

3.410E+00 18 2.945E+01 2

1. 448E+02 B.

IRRADIATED FUEL SHIPMENTS (Disposition)

Number of Shipments Mode of Transportation Destination None N/A N/A 79

TABLE 3-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Starting: 01-Jul-2006 Ending: 31-Dec-2006 A.

SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (not irradiated fuel)

1. Type of Waste.
a.

Spent resins, Filter

sludges, evaporator bottoms, etc.
b.

Dry compressible waste, contaminated equipment, etc.

c. Irradiated components, control rods, etc.

UNITS 6-Months 3

m 1.033E+00 Ci*

7.020E+00 3

m 5.581E+01 Ci*

1.435E+00 3

m 3.251E+00 Ci*

8.590E+02

d.

Other (describe) 3 m

None Ci*

None

2.

Estimate of major nuclide composition (by type of waste).

a.

CO-60 59.0%

FE-55 15.0%

C-14 10.0%

NI-63 7.1%

CO-58 2.0%

CS-137 1.4%

SB-125 1.4%

MN-54 1.1%

ZR-95 1.1%

b.

CO-58 23.8%

H-3 20.0%

ZN-65 14.0%

NB-95 8.6%

ZR-95 7.2%

CO-60 7.2%

CR-51 7.1%

FE-55 5.3%

C-14 1.1%

NI-63 1.7%

  • Measured and/or with IOCFR61.55.

estimated by correlations in accordance 80

TABLE 3-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Starting: 01-Jul-2006 Ending: 31-Dec-2006 (continued)

c.

CO-60 FE-55 ZN-65 CO-58 CR-51 ZR-95 NI-63 NB-95 SB-125 MN-54 34.4%

25.0%

20. 0%

5.1%

4.0%

2.8%

2.7%

2.4%

1.5%

1.2%

3.

Solid Waste Disposition Number of Shipments Mode of Transportation 5

4 Highway Highway Destination Envirocare of Utah

Barnwell, SC Envirocare of Utah 23 Rail
4.

Type of Containers (Shipped offsite for burial/processing)

Container Description Type of Container Number of Containers Container 3 Volume (m

a.

55 Gallon Drum CNS 8-120

b.

20' Sealand General Design Package High Integrity Container General Design Package General Design Package USA/5805/B()

6 1

2.120E-01 3.410E+00 14 2.945E+01 55 Gallon Drum 3-55 Liner 8

2 2.120E-01

1. 625E+00 81

TABLE 3-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Starting: 01-Jul-2006 Ending: 31-Dec-2006 (continued)

5.

Solidification Agent

a.

None

b.

None B.

IRRADIATED FUEL SHIPMENTS (Disposition)

Number of Shipments Mode of Transportation Destination None N/A N/A 82

4.0 DOSES TO MEMBERS OF THE PUBLIC INSIDE THE SITE BOUNDARY 4.1 Regulatory Requirements Current FNP effluent controls as established by ODCM 6.1 do not require assessment of the radiation doses from radioactive liquid and gaseous effluents to MEMBERS OF THE PUBLIC due to their activities inside the SITE BOUNDARY (ODCM Figure 10-1).

4.2 Demonstration of Compliance

However, this assessment has been performed for 2006 using the methods described in ODCM 6.2 and is included in this section as Table 4-1.

83

TABLE 4-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jan-2006 Ending: 30-Jun-2006 Page:

Location Name VISITOR LOCATION 1 (VIS.CENTER)

Distance (kilometers) 3.06E-01 Sector WSW Occupancy Factor 1.37E-03 (1.20E+01 hr/yr)

Age Group CHILD Ground Level Releases:

Noble Gas X/Q (sec/m3) 1.04E-04 Particulate X/Q (sec/m3) 1.04E-04 Particulate D/Q (m-2) 4.80E-07 mixed mode Releases:

Noble Gas X/Q (sec/m3) 8.80E-06 Particulate X/Q (sec/m3) 8.80E-06 Particulate D/Q (m-2) 6.20E-08 Elevated Releases:

Noble Gas X/Q (sec/m3)

N/A Particulate X/Q (sec/m3)

N/A Particulate D/Q (m-2)

N/A Units Quarter 1 Quarter 2 Quarters Year to 1 and 2 Ending Date Bone mrem 4.97E-05 1.37E-05 6.35E-05 6.35E-05 Liver mrem 5.17E-05 1.59E-05 6.76E-05 6.76E-05 TBody mrem 5.17E-05 1.59E-05 6.76E-05 6.76E-05 Thyroid mrem 5.17E-05 1.66E-05 6.83E-05 6.83E-05 Kidney mrem 5.17E-05 1.59E-05 6.76E-05 6.76E-05 Lung mrem 5.17E-05 1.60E-05 6.76E-05 6.76E-05 GI-LLI mrem 5.17E-05 1.59E-05 6.76E-05 6.76E-05 84

TABLE 4-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jan-2006 Ending: 30-Jun-2006 Page:

2 Location Name VISITOR LOCATION 2 (SW.POND)

Distance (kilometers) 9.66E-01 Sector SSW Occupancy Factor 7.53E-03 (6.60E+01 hr/yr)

Age Group CHILD Ground Level Releases:

Noble Gas X/Q (sec/m3) 4.74E-05 Particulate X/Q (sec/m3) 4.74E-05 Particulate D/Q (m-2) 1.31E-07 Mixed Mode Releases:

Noble Gas X/Q (sec/m3) 9.75E-07 Particulate X/Q (sec/m3) 9.75E-07 Particulate D/Q (m-2) 2.78E-08 Elevated Releases:

Noble Gas X/Q (sec/m3)

N/A Particulate X/Q (sec/m3)

N/A Particulate D/Q (m-2)

N/A Units Quarter 1 Quarter 2 Quarters Year to 1 and 2 Ending Date Bone mrem 3.03E-05 8.90E-06 3.92E-05 3.92E-05 Liver mrem 3.15E-05 1.02E-05 4.17E-05 4.17E-05 TBody mrem 3.15E-05 1.02E-05 4.17E-05 4.17E-05 Thyroid mrem 3.15E-05 1.07E-05 4.21E-05 4.21E-05 Kidney mrem 3.15E-05 1.02E-05 4.17E-05 4.17E-05 Lung mrem 3.15E-05 1.02E-05 4.17E-05 4.17E-05 GI-LLI mrem 3.15E-05 1.02E-05 4.17E-05 4.17E-05 85

TABLE 4-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jan-2006 Ending: 30-Jun-2006 Page:

3 Location Name VISITOR LOCATION 3 (RW DISCH.)

Distance (kilometers) 1.64E+00 Sector SE Occupancy Factor 1.14E-02 (9.99E+01 hr/yr)

Age Group CHILD Ground Level Releases:

Noble Gas X/Q (sec/m3) 1.63E-05 Particulate X/Q (sec/m3) 1.63E-05 Particulate D/Q (m-2) 4.55E-08 Mixed Mode Releases:

Noble Gas X/Q (sec/m3) 7.05E-07 Particulate X/Q (sec/m3) 7.05E-07 Particulate D/Q (m-2) 1.39E-08 Elevated Releases:

Noble Gas X/Q (sec/m3)

N/A Particulate X/Q (sec/m3)

N/A Particulate D/Q (m-2)

N/A Units Quarter 1 Quarter 2 Quarters Year to 1 and 2 Ending Date Bone mrem 3.32E-05 9.50E-06 4.27E-05 4.27E-05 Liver mrem 3.44E-05 1.10E-05 4.54E-05 4.54E-05 TBody mrem 3.44E-05 1.10E-05 4.54E-05 4.54E-05 Thyroid mrem 3.44E-05 1.14E-05 4.59E-05 4.59E-05 Kidney mrem 3.44E-05 1.10E-05 4.54E-05 4.54E-05 Lung mrem 3.44E-05 1.10E-05 4.54E-05 4.54E-05 GI-LLI mrem 3.44E-05 1.10E-05 4.54E-05 4.54E-05 86

TABLE 4-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jul-2006 Location Name V

Distance (kilometers) 3 Sector W

Occupancy Factor 1

Age Group C]

Ground Level Releases:

Noble Gas X/Q (sec/m3)

Particulate X/Q (sec/m3)

Particulate D/Q (m-2)

Mixed Mode Releases:

Noble Gas X/Q (sec/m3)

Particulate X/Q (sec/m3)

Particulate D/Q (m-2)

Elevated Releases:

Noble Gas X/Q (sec/m3)

Particulate X/Q (sec/m3)

Particulate D/Q (m-2)

Ending: 31-Dec-2006 ISITOR LOCATION 1 (VIS.CENTER)

.06E-01 SW

.37E-03 (1.20E+01 hr/yr)

HILD 1.04E-04 1.04E-04 4.80E-07 8.80E-06 8.80E-06 6.20E-08 N/A N/A N/A Units Quarter 3 Quarter 4 Quarters Year to 3 and 4 Ending Date Bone mrem 1.08E-05 3.42E-06 1.42E-05 7.77E-05 Liver mrem 1.12E-05 4.25E-06 1.54E-05 8.30E-05 TBody mrem 1.12E-05 4.24E-06 1.54E-05 8.30E-05 Thyroid mrem 1.20E-05 5.91E-06 1.79E-05 8.62E-05 Kidney mrem 1.12E-05 4.25E-06 1.54E-05 8.30E-05 Lung mrem 1.12E-05 4.24E-06 1.54E-05 8.30E-05 GI-LLI mrem 1.12E-05 4.24E-06 1.54E-05 8.30E-05 87

TABLE 4-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jul-2006 Ending: 31-Dec-2006 Location Name VISITOR LOCATION 2 (SW POND)

Distance (kilometers) 9.66E-01 Sector SSW Occupancy Factor 7.53E-03 (6.60E+01 hr/yr)

Age Group CHILD Ground Level Releases:

Noble Gas X/Q (sec/m3) 4.74E-05 Particulate X/Q (sec/m3) 4.74E-05 Particulate D/Q (m-2) 1.31E-07 Mixed Mode Releases:

Noble Gas X/Q (sec/m3) 9.75E-07 Particulate X/Q (sec/m3) 9.75E-07 Particulate D/Q (m-2) 2.78E-08 Elevated Releases:

Noble Gas X/Q (sec/m3)

N/A Particulate X/Q (sec/m3)

N/A Particulate D/Q (m-2)

N/A Units Quarter 3 Quarter 4 Quarters Year to 3 and 4 Ending Date Bone mrem 6.60E-06 2.10E-06 8.70E-06 4.79E-05 Liver mrem 6.81E-06 2.60E-06 9.41E-06 5.lIE-05 TBody mrem 6.81E-06 2.60E-06 9.41E-06 5.lIE-05 Thyroid mrem 7.34E-06 3.62E-06 1.10E-05 5.31E-05 Kidney mrem 6.81E-06 2.60E-06 9.42E-06 5.lIE-05 Lung mrem 6.81E-06 2.60E-06 9.40E-06 5.lIE-05 GI-LLI mrem 6.81E-06 2.60E-06 9.41E-06 5.lIE-05 88

TABLE 4-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -

2006 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jul-2006 Ending: 31-Dec-2006 Location Name VISITOR LOCATION 3 (RW DISCH.)

Distance (kilometers) 1.64E+00 Sector SE Occupancy Factor 1.14E-02 (9.99E+01 hr/yr)

Age Group CHILD Ground Level Releases:

Noble Gas X/Q (sec/m3) 1.63E-05 Particulate X/Q (sec/m3) 1.63E-05 Particulate D/Q (m-2) 4.55E-08 Mixed Mode Releases:

Noble Gas X/Q (sec/m3) 7.05E-07 Particulate X/Q (sec/m3) 7.05E-07 Particulate D/Q (m-2) 1.39E-08 Elevated Releases:

Noble Gas X/Q (sec/m3)

N/A Particulate X/Q (sec/m3)

N/A Particulate D/Q (m-2)

N/A Units Quarter 3 Quarter 4 Quarters Year to 3 and 4 Ending Date Bone mrem 7.22E-06 2.29E-06 9.51E-06 5.22E-05 Liver mrem 7.45E-06 2.84E-06 1.03E-05 5.57E-05 TBody mrem 7.45E-06 2.84E-06 1.03E-05 5.57E-05 Thyroid mrem 8.03E-06 3.95E-06 1.20E-05 5.79E-05 Kidney mrem 7.45E-06 2.84E-06 1.03E-05 5.57E-05 Lung mrem 7.45E-06 2.84E-06 1.03E-05 5.57E-05 GI-LLI mrem 7.45E-06 2.84E-06 1.03E-05 5.57E-05 89

5.0 TOTAL DOSE FROM URANIUM FUEL CYCLE (40CFR190) 5.1 Regulatory Requirements Technical Specification 5.5.4.j states that the dose or dose commitment to any MEMBER OF THE PUBLIC over a calendar year, due to releases of radioactivity and to radiation from uranium fuel cycle sources, shall be limited to less than or equal to 25 mrem to the total body or to any organ, except the thyroid, which shall be limited to less than or equal to 75 mrem (as stated in ODCM 5.1).

With the calculated doses from the release of radioactive materials in liquid or gaseous effluents exceeding twice the limits of ODCM 2.1.3, 3.1.3, or 3.1.4, calculations shall be made according to ODCM 5.2 methods to determine whether the above (ODCM 5.1) limits have been exceeded (as stated in ODCM 5.1.2).

5.2 Demonstration of Compliance Since none of the ODCM 2.1.3, 3.1.3, or 3.1;4 limits were exceeded during 2006, no calculations were required.

6.0 METEOROLOGICAL DATA Meteorological data are retained onsite; these data are available to the NRC upon request.

The meteorological data include annual as well as quarterly summaries of hourly measurements of wind speed, wind direction and atmospheric stability in the form of joint frequency distribution tables.

7.0 PROGRAM DEVIATIONS 7.1 Inoperable Liquid or Gaseous Effluent Monitoring Instrumentation 7.1.1 Regulatory Requirements ODCM 7.2.2.6 states in part that the Annual Radioactive Effluent Release Report (the report) shall include deviations from the liquid and gaseous effluent monitoring instrumentation operability requirements included in Sections 2.1.1 and 3.1.1 of the ODCM.

The report must also include an explanation as to why the inoperability was not corrected in a timely manner.

7.1.2 Description of Deviations There were two deviations from liquid effluent monitoring instrumentation operability requirements during 2006.

The Unit 1 service water dilution flow recorder was out of service from April 6, 2006 until July 6, 2006. Dilution flow was estimated based on pump flows while the recorder was out of service in accordance with plant procedures.

The recorder was unable to be repaired and had to be replaced. Details of this deviation are documented in condition report 2006104715.

The Unit 2 service 90

water dilution flow recorder was out of service from June 23, 2006 until October 25, 2006. Dilution flow was estimated based on pump flows while the recorder was out of service in accordance with plant procedures. The recorder was unable to be repaired and had to be replaced. Details of this deviation are documented in condition report 2006106092.

7.2 Effluent Sample Analysis Exceeding Minimum Detectable Concentration (MDC) 7.2.1 Regulatory Requirements ODCM 7.2.2.6 states in part that the report shall include deviations from the MDC requirements included in ODCM Tables 2-3 and 3-3.

7.2.2 Description of Deviations There were no deviations during 2006.

7.3 Incorrect Compositing of Liquid or Gaseous Effluent Samples 7.3.1 Regulatory Requirements ODCM 7.2.2.6 states in part that the report shall include deviations from composite sampling requirements included in ODCM Tables 2-3 and 3-3.

7.3.2 Description of Deviations There were two deviations from liquid effluent sampling requirements during 2006. Unit 2 had a deviation on September 18, 2006, when the auto-sampler for Turbine Building Sump 2A failed to collect a sample for the day. Details of this event are documented in condition report 2006108616. Unit 2 also had a deviation on September 22, 2006, when the auto-sampler for Turbine Building Sump 2B failed to collect a sample for the day.

Details of this event are documented in condition report 2006108753.

8.0 CHANGES TO THE PLANT FARLEY ODCM 8.1 Regulatory Requirements Pursuant to Technical Specification 5.5.1.c and ODCM 7.2.2.5, licensee initiated changes to the ODCM shall be submitted to the Nuclear Regulatory Commission as a part of or concurrent with the Annual Radioactive Effluent Release Report for the period in which any changes were made. Included are changes to the radiological environmental monitoring program sampling locations or dose calculation locations or pathways, including any changes made pursuant to ODCM 4.1.2.2.2 (land use census).

91

8.2 Description of Changes There was one revision to the ODCM during 2006. Guidance concerning Containment Purge batch sampling was added, and dose factors for Antimony-126 were added. This revision accompanies this report.

9.0 MAJOR CHANGES TO LIQUID,

GASEOUS, OR SOLID RADWASTE TREATMENT SYSTEMS 9.1 Regulatory Requirements ODCM 7.2.2.7 states in part that, as required by ODCM 2.1.5 and 3.1.6, licensee initiated MAJOR CHANGES TO RADIOACTIVE WASTE TREATMENT SYSTEMS (liquid and gaseous) shall be reported to the Nuclear Regulatory Commission in the Annual Radioactive Effluents Release Report covering the period in which the change was reviewed and accepted for implementation.

Process Control Program (PCP) B.5.1.2 states that licensee initiated major changes to the solid radioactive waste treatment system shall be reported to the Nuclear Regulatory Commission in the Annual Radioactive Effluent Release Report for the period in which the change was implemented. The discussion of each change shall include the information specified in PCP B.4.1.

9.2 Description of Major Changes Although there were no major system changes to the gaseous rad waste system during 2006 there was a change to the methodology for releasing containment atmosphere within the methods allowed by the ODCM.

Unit-i changed from "continuous release" to a "batch release" in July 2006.

Unit-2 changed from a "continuous release" to a "batch release" in April 2006(CR2006102871).

These changes were made in an effort to reduce off site Curies released from noble gases.

In a further effort to improve the process for containment atmosphere releases, the FNP Operations, chemistry, and Engineering groups implemented a "modified continuous release" for Unit-l in November 2006(CR2007100626).

In February 2007, a question concerning possible non-representative sample was brought up by the engineering group based upon the release alignment pathway for containment atmosphere (CR2007102133).

Unit-i was immediately placed on "batch release" until the question could be resolved. A change to operating procedures for the release alignment pathway eliminated the representative sample concern and Unit-i returned to a "modified continuous release" in April 2007. Further evaluations indicate Unit 1 was actually getting a representative sample during releases using the original release alignment pathway for the "modified continuous release" method. Therefore the releases performed during this alignment will be reported in this report as was recorded in the gaseous effluent database at the actual time of the release. The methodology will be considered for Unit 2 application to allow Unit 2 to go from a "batch release" to a "modified continuous release".

92