Submittal of Unit 1 Emergency Response Data System (ERDS) Data Point Library
ML070160070
Person / Time
Site: Browns Ferry Tennessee Valley Authority icon.png
Issue date: 01/11/2007
From: Crouch W
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Security and Incident Response
References
1-TI-411, Rev 1
Download: ML070160070 (48)


Text

Tennessee Valley Authority, Post Office Box 2000, Decatur, Adabama 35609-2000 January 11, 2007 10 CFR 50, Appendix E U.

S.

Nuclear Regulatory Commission ATTN:

Document Control Desk Washington, D.C.

20555 Gentlemen:

In the Matter of

)

Docket No.

50-259 Tennessee Valley Authority BROWNS FERRY NUCLEAR PLANT (BFN)

UNIT 1 -

SUBMITTAL OF UNIT 1 EMERGENCY RESPONSE DATA SYSTEM (ERDS)

DATA POINT LIBRARY In accordance with 10 CFR 50, Appendix E, Section VI, "Emergency Response Data System,"

TVA is providing the BFN Unit 1 ERDS Data Point Library.

This is submitted in accordance with the BFN implementation schedule provided to NRC in the letter dated December 13, 1991.

There are no commitments contained in this letter.

If you have any questions, please contact me at (256) 729-2636.

Sincerely, William D. Crouch Manager of Site Licensing and Industry Affairs cc:

See page 2

U.S. Nuclear Regulatory Commission Page 2 January 11, 2007 Enclosure cc (Enclosure):

Ms.

Eva A.

Brown, Project Manager U.S. Nuclear Regulatory Commission One White Flint, North (MS 08G9) 11555 Rockville Pike Rockville, Maryland 20852-2739 Ms. Margaret Chernoff, Project Manager U.S. Nuclear Regulatory Commission One White Flint, North (MS 08G9) 11555 Rockville Pike Rockville, Maryland 20852-2739 Mr. Malcolm T.

Widmann, Branch Chief U.S. Nuclear Regulatory Commission Region II Atlanta Federal Center 61 Forsyth Street S.W.,

Suite 23T85 Atlanta, Georgia 30303-8931 NRC Resident Inspector Browns Ferry Nuclear Plant 10833 Shaw Road Athens, Alabama 35611

ENCLOSURE TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT UNIT 1 REVISION TO THE EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY

Browns Ferry Nuclear Plant Unit I Technical Instruction 1 -TI-411 Emergency Response Data System (ERDS) Data Point Library Revision 0001 Quality Related Level of Use: Information Use Effective Date:

12-22-2006 Responsible Organization:

SIE, System Eng - &C Elect Prepared By:

John Balash Approved By:

Robert Moll

BFN Emergency Response Data System I1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 2 of 45 Current Revision Description Meteorological PID's have been revised along with several descriptions.

Drywell H2 and oxygen analyzer ranges and setpoints have been revised.

Drywell Temperature Startup setpoint has been corrected.

IC 002

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 3 of 45 Table of Contents 1.0 INTRO DUCTION......................................................................................................

4 1.1 PURPOSE............................................................................................................

4 1.2 SCOPE.........................................................................................................................

4 1.3 FREQ UENCY...............................................................................................................

4

2.0 REFERENCES

4 3.0 DEFINITIONS...............................................................................................................

4 4.0 PRECAUTIO NS AND LIM ITATIONS.......................................................................

5 5.0 PREREQ UISITES.........................................................................................................

5 6.0 EQ UIPM ENT................................................................................................................

5 7.0 PROCEDURE...............................................................................................................

5 8.0 ACCEPTANCE CRITERIA.......................................................................................

5 9.0 APPENDICES......................................................................................................

5 Appendix A:

Browns Ferry Unit 1 - ERDS Data Point Library...................................

6

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 4 of 45

1.0 INTRODUCTION

This Technical Instruction provides an appendix which contains the Emergency Response Data System (ERDS) Data Point Library for Unit 1. The ERDS Data Point Library is provided to the Nuclear Regulatory Commission (NRC) to document information relative to applicable data points that are transmitted from BFN Unit 1 Integrated Computer System (ICS) to the NRC whenever ERDS is activated. As such, changes to this Data Point Library must be coordinated with Licensing in order to ensure the NRC is informed of changes. Relative to ERDS changes, 1 OCFR50 Appendix E, Part VI, Paragraph 3a states:

"Any hardware or software changes that affect transmitted data points identified in the ERDS Data Point Library (site specific data base residing on the ERDS computer) must be submitted to the NRC within 30 days after the changes are completed."

ERDS consists of processes that run on ICS which collect applicable data and transmit this data across the network to TVA offices in Chattanooga. ERDS is NOT normally transmitting data to the NRC; the NRC only receives this data when they specifically request its transmission. When the NRC desires to receive BFN ERDS data, they will make a connection to a computer(s) in Chattanooga to obtain this data. ERDS is intended for use during radiological emergencies.

1.1 PURPOSE This instruction provides a controlled BFN instruction that documents the ERDS Data Point Library for Unit 1.

1.2 SCOPE This instruction is applicable to Unit 1 only.

1.3 FREQUENCY NOT applicable

2.0 REFERENCES

1 OCFR50 Appendix E Part VI 3.0 DEFINITIONS None

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 5 of 45 4.0 PRECAUTIONS AND LIMITATIONS None 5.0 PREREQUISITES None 6.0 EQUIPMENT None 7.0 PROCEDURE Appendix A contains the ERDS Data Point Library for BFN Unit 1 8.0 ACCEPTANCE CRITERIA NOT applicable.

9.0 APPENDICES Appendix A - Browns Ferry Unit 1 - ERDS Data Point Library

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 6 of 45 Appendix A (Page 1 of 40)

Browns Ferry Unit 1 - ERDS Data Point Library ERDS PNT No 1

2 3

4 5

6 7

8 9

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 DATE 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 NRC ERDS PARAMETER NI POWER RNG NI INTER RNG NI SOURC RNG REAC VES LEV MAIN FD FLOW RCIC FLOW RCS PRESSURE HPCI FLOW LPCI FLOW LPCI FLOW CR SPRAY FL CR SPRAY FL CND A/E RAD CND A/E RAD DW RAD DW RAD MN STEAM RAD MN STEAM RAD MN STEAM RAD MN STEAM RAD DW PRESS DW TEMP SPTEMP SP LEVEL H2 CONC 02 CONC POINT ID PLANT SPECIFIC POINT DESCRIPTION SPDS0001 CALC045 SPDS0041 SPDS0007 CALC040 71-36 SPDS0008 73-33 74-50 74-64 75-21 75-49 SPDS0047 90-157 90-272A 90-273A 90-136 90-137 90-138 90-139 SPDS0009 SPDS0010 SPDS0016 SPDS001 3 76-39 76-43 RX POWER APRM - COMPOSED AVERAGE OF 8 IRM'S RX POWER SRM - AVG RX WATER LEVEL - COMPOSED RFW FLOW TO REACTOR RCIC PUMP DISCHARGE FLOW RX PRESSURE - COMPOSED HPCI PUMP DISCHARGE FLOW RHR SYS I FLOW RHR SYS II FLOW CORE SPRAY SYS I FLOW CORE SPRAY SYS II FLOW OFFGAS POST TREATMENT AVG OFFGAS PRE TREATMENT AVG DW RAD-RX 582,45 DEG AZIMUTH DW RAD-RX 560, 270 DEG AZIMUTH MAIN STM LINE A RAD LEVEL MAIN STM LINE C RAD LEVEL MAIN STM LINE B RAD LEVEL MAIN STM LINE D RAD LEVEL DRYWELL PRESSURE - COMPOSED DRYWELL TEMPERATURE-COMPOSED SUPPR PL WTR TEMP - COMPOSED SUPPR PL WTR LVL (IN) - COMPOSED DRYWELL H2 CONCENTRATION DRYWELL OXYGEN CONCENTRATION

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 7 of 45 ERDS PNT No 27 28 29 30 31 32 33 34 35 36 37 38 DATE 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 12/20/2006 NRC ERDS PARAMETER CST LEVEL WIND SPEED WIND SPEED WIND SPEED WIND DIR WIND DIR WIND DIR STAB CLASS STAB CLASS STAB CLASS TYPEDATA EFF GAS RAD Appendix A (Page 2 of 40)

POINT ID 2-169 MET005 MET013 MET021 MET003 MET011 MET019 MET035 MET037 MET039 REAL /

SIMULATED SPDS0024 PLANT SPECIFIC POINT DESCRIPTION CONDENSATE STORAGE TANK #1 (UNIT 1) LEVEL 91M AVERAGE WIND SPEED (15 MIN AVG) 46M AVERAGE WIND SPEED (15 MIN AVG) 10M AVERAGE WIND SPEED (15 MIN AVG) 91 M VECTOR WIND DIR (15 MIN AVG) 46M VECTOR WIND DIR (15 MIN AVG) 1OM VECTOR WIND DIR (15 MIN AVG)

STACK LVL ATM STAB CLASS (15 MIN)

OVERALL ATM STAB CLASS (15 MIN)

GRND LVL ATM STAB CLASS (15 MIN)

INDICATES IF DATA IS FROM THE UNIT OR SIMULATOR.

STACK RELEASE RATE - COMPOSED

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 8 of 45 Appendix A (Page 3 of 40)

ERDS Point Number 1

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital:

Engr Units/Dig States:

Engr Units:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On:

Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

NI POWER RNG SPDS0001 12/20/2006 BF1 1

N I POWER RNG SPDS0001 RX POWER APRM - COMPOSED Reactor Power Reactor Power A

N/A 0

125 N/A N/A P

4 Weighted Average w/Fault Detect (PSVA)

N/A HIHI=5 (Inhibited if no SCRAM)

N/A N/A N/A N

N/A The HIGH alarm is inhibited when the plant is not in a SCRAM condition. This supports plant EOI's.

BFN Emergency Response Data System I1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 9 of 45 Appendix A (Page 4 of 40)

ERDS Point Number 2

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital:

Engr Units/Dig States:

Engr Units:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

NI INTER RNG CALC045 Reactor Power Intermediate Ring 12/20/2006 BF1 1

NI INTER RNG CALC045 AVERAGE OF 8 IRM'S Reactor Power - Intermediate Rng A

% SCALE N/A 0

125 N/A N/A P

8 Average (AVG)

N/A See Below N/A N/A N/A N

N/A Since the IRMs have a range switch this average is difficult to interpret.

Alarm:

Run:

Startup:

Shutdown:

Refuel:

HIHI=120 HIHI=108 HI=80 LO=20 LOLO=15 HIHI=50 HI-25 HIHI=50 HI=25

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 10 of 45 Appendix A (Page 5 of 40)

ERDS Point Number 3 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital:

Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On:

Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

NI SOURC RNG SPDS0041 Reactor Power - Source Range 12/20/2006 BF1 1

N1 SOURC RNG SPDS0041 RX POWER SRM - AVG Reactor Power - Source Range A

CPS N/A

.1 1000000 N/A N/A P

4 Average of healthy inputs (HAVE)

N/A See Below N/A N/A N/A N

N/A Alarm: Startup/Shutdown/Refuel: HIHI=500000, HI=100000, LO=5, LOLO=3

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 11 of 45 Appendix A (Page 6 of 40)

ERDS Point Number 4

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

REAC VES LEV SPDS0007 Reactor Vessel Water Level 12/20/2006 BF1 1

REAC VES LEV SPDS0007 RX WATER LEVEL - COMPOSED Reactor Vessel Water Level A

INCHES N/A

-268 400 MSSKRT 528" above vessel zero P

11 Weighted Average w/Fault Detect (PSVA)

N/A All modes: HIHI=51, HI=39, LO=27, LOLO=2 N/A N/A N/A Y

N/A Combines one 0 - +400 (floodup), four + 70 (Normal), four -155 -

+ 60 (Emerg) and two -268 - +32 (post accident) into one wide range indication; therefore, for off normal conditions this point could be difficult to interpret. Instruments are calibrated for normal operating conditions, except for the floodup instrument which is calibrated for atmospheric conditions, and the post accident instruments which are calibrated assuming 212 degrees Fahrenheit water in all lines. Top of fuel is at - 162".

Unique System Desc.:

Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0001 Page 12 of 45 Appendix A (Page 7 of 40)

ERDS Point Number 5

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital:

Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On:

Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

MAIN FD FLOW CALC040 Feedwater Flow into the Reactor 12/20/2006 BF1 1

MAIN FD FLOW CALCO40 RFW FLOW TO REACTOR Feedwater Flow into the Reactor A

MLB/HR N/A 0

20 N/A N/A P

2 Sum of RFW LINE A and RFW LINE B N/A Run: HIHI=14.8, HI=14.7 (EPU values HIHI=17.1, HI=17.0)

N/A N/A N/A N

N/A Sum of feedflow instruments (3-78A & 3-78B),

uncompensated

BFN Emergency Response Data System I1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 13 of 45 Appendix A (Page 8 of 40)

ERDS Point Number 6 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

RCIC FLOW 71-36 Core Isolation Cooling Flow 12/20/2006 BF1 1

RCIC FLOW 71-36 RCIC PUMP DISCHARGE FLOW Core Isolation Cooling Flow A

GPM N/A 0

700 N/A N/A S

1 Polynomial Downstream of Min Flow Line All modes: HIHI=625 N/A N/A LOW N

N/A

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 14 of 45 Appendix A (Page 9 of 40)

ERDS Point Number 7

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital:

Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On:

Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

RCS PRESSURE SPDS0008 Reactor Coolant System Pressure 12/20/2006 BF1 1

RCS PRESSURE SPDS0008 RX PRESSURE - COMPOSED Reactor Coolant System Pressure A

PSIG N/A 0

1500 N/A N/A P

6 Weighted Average w/Fault Detect (PSVA)

N/A See Below N/A N/A N/A Y

N/A Instruments are calibrated for rated operating conditions Alarm:

Run:

Startup:

Shutdown:

Refuel:

HIHI=1073, H1=1070, LO=918, LOLO=915 HIHI=1 073, H1=1070, LO=918, LOLO=915 HIHI=1073, HI-1070 HIHI=1073, H1=1070

BFN Emergency Response Data System I1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 15 of 45 Appendix A (Page 10 of 40)

ERDS Point Number 8 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

HPCI FLOW 73-33 High Pressure Coolant Inj. Flow 12/20/2006 BF1 1

HPCI FLOW 73-33 HPCI Pump Discharge Flow High Pressure Coolant Inj. Flow A

GPM N/A 0

6000 N/A N/A S

1 Polynomial Downstream of Min. Flow Line All modes: HIHI=5200 N/A N/A LOW N

N/A

BFN Emergency Response Data System I1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 16 of 45 Appendix A (Page 11 of 40)

ERDS Point Number 9

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

LPCI FLOW 74-50 LPCI - RHR System I Flow 12/20/2006 BF1 1

LPCI FLOW 74-50 RHR SYS I Flow LPCI - RHR System I Flow A

GPM N/A 0

25000 N/A N/A S

1 Polynomial Downstream of HX and Before Sprays All modes: HIHI=20000, HI=13000 N/A N/A LOW N

N/A

BFN Emergency Response Data System I1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 17 of 45 Appendix A (Page 12 of 40)

ERDS Point Number 10 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

LPCI FLOW 74-64 LPCI - RHR System II Flow 12/20/2006 BF1 1

LPCI FLOW 74-64 RHR SYS II Flow LPCI - RHR System II Flow A

GPM N/A 0

25000 N/A N/A S

1 Polynomial Downstream of HX and Before Sprays All modes: HIHI=20000, H1=13000 N/A N/A LOW N

N/A

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 18 of 45 Appendix A (Page 13 of 40)

ERDS Point Number 11 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

CR SPRAY FL 75-21 Core Spray - System I Flow 12/20/2006 BF1 1

CR SPRAY FL 75-21 CORE SPRAY SYS I FLOW Core Spray - System I Flow A

GPM N/A 0

10000 N/A N/A S

1 Polynomial Downstream of Min Flow Line All modes: HIHI=6300, H1=6275 N/A N/A LOW N

N/A

BFN Emergency Response Data System 11-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 19 of 45 Appendix A (Page 14 of 40)

ERDS Point Number 12 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

CR SPRAY FL 75-49 Core Spray - System II Flow 12/20/2006 BF1 1

CR SPRAY FL 75-49 CORE SPRAY SYS II FLOW Core Spray - System II Flow A

GPM N/A 0

10000 N/A N/A S

1 Polynomial Downstream of Min Flow Line All modes: HIHI=6300, HI=6275 N/A N/A LOW N

N/A

BFN Emergency Response Data System I1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 20 of 45 Appendix A (Page 15 of 40)

ERDS Point Number 13 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

CND A/E RAD SPDS0047 Condensor Air Ejector Rad Level 12/20/2006 BF1 1

CND A/E RAD SPDS0047 OFFGAS POST TREATMENT AVG Condensor Air Ejector Rad Level A

CPS N/A

.1 1000000 N/A N/A P

2 Healthy Average (HAVE)

N/A See Below N/A N/A N/A N

N/A Alarm:

Run/Startup:

Shutdown/Refuel:

HIHI=290000 HI=58000 LOLO=10 LOLO=10

BFN Emergency Response Data System I1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 21 of 45 Appendix A (Page 16 of 40)

ERDS Point Number 14 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

CND A/E RAD 90-157 Offgas Pre Treatment Avg 12/20/2006 BF1 1

CND A/E RAD 90-157 OFFGAS PRE TREATMENT RADIATION Offgas Pre Treatment Avg A

MRPHR N/A 1.0 1000000 N/A N/A S

1 SALG N/A Run/Startup: HIHI=1690, HI=845, LOLO=1 N/A N/A Downscale N

N/A

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 22 of 45 Appendix A (Page 17 of 40)

ERDS Point Number 15 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

DW RAD 90-272A Drywell Radiation - 45 Deg 12/20/2006 BF1 1

DW RAD 90-272A DW RAD-RX 582, 45 DEG AZIMUTH Drywell Radiation -45 Deg A

R/HR N/A 1.0 10000000 N/A N/A S

1 SALG At Level 582, 45 Degree Azimuth All modes:

HIHI=1440, HI=1000 N/A N/A LOW N

N/A

BFN Emergency Response Data System I1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 23 of 45 Appendix A (Page 18 of 40)

ERDS Point Number 16 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

DW RAD 90-273A Drywell Radiation - 270 Deg 12/20/2006 BF1 1

DW RAD 90-273A DW RAD-RX 560,270 DEG AZIMUTH Drywell Radiation - 270 Deg A

R/HR N/A 1.0 10000000 N/A N/A S

1 SALG At Level 560, 270 Degree Azimuth All modes:

HIHI=1440, HI=1000 N/A N/A LOW N

N/A

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 24 of 45 Appendix A (Page 19 of 40)

ERDS Point Number 17 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

MN STEAM RAD 90-136 Rad Level - Main Steam Line A 12/20/2006 BF1 1

MN STEAM RAD 90-136 MAIN STM LINE A RAD LEVEL Rad Level - Main Steam Line A A

MR/HR N/A 1.0 1000000 N/A N/A S

1 SALG Main Steam Tunnel All modes:

HIHI=1500, HI=750 N/A N/A LOW N

N/A

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 25 of 45 Appendix A (Page 20 of 40)

ERDS Point Number 18 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

MN STEAM RAD 90-137 Rad Level - Main Steam Line C 12/20/2006 BF1 1

MN STEAM RAD 90-137 MAIN STM LINE C RAD LEVEL Rad Level - Main Steam LineC A

MR/HR N/A 1.0.

1000000 N/A N/A S

1 SALG Main Steam Tunnel All modes:

HIHI=1500, H1=750 N/A N/A LOW N

N/A

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 26 of 45 Appendix A (Page 21 of 40)

ERDS Point Number 19 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

MN STEAM RAD 90-138 Rad Level - Main Steam Line B 12/20/2006 BF1 1

MN STEAM RAD 90-138 MAIN STM LINE B RAD LEVEL Rad Level -Main Steam Line B A

MR/HR N/A 1.0 1000000 N/A N/A S

1 SALG Main Steam Tunnel All modes: HIHI=1500, HI=750 N/A N/A LOW N

N/A

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 27 of 45 Appendix A (Page 22 of 40)

ERDS Point Number 20 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

MN STEAM RAD 90-139 Rad Level - Main Steam Line D 12/20/2006 BF1 1

MN STEAM RAD 90-139 MAIN STM LINE D RAD LEVEL Rad Level -Main Steam Line D A

MR/HR N/A 1.0 1000000 N/A N/A S

1 SALG Main Steam Tunnel All modes: HIHI=1500, H1=750 N/A N/A LOW N

N/A

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 28 of 45 Appendix A (Page 23 of 40)

ERDS Point Number 21 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

DW PRESS SPDS0009 Drywell Pressure 12/20/2006 BF1 1

DW PRESS SPDS0009 DRYWELL PRESSURE - COMPOSED Drywell Pressure A

PSIG N/A

-15 300 N/A N/A P

6 Weighted Average w/Fault Detect (PSVA)

N/A See Below N/A N/A N/A N

N/A Alarm:

Run:

Startup:

Shutdown:

Refuel:

HIHI=2.45, HI=1.96, LO=1.15, LOLO=1.1 HIHI=2.45, HI=1.96, LO=1.15, LOLO=1.1 HIHI=2.45, HI=1.96, LO=1.15, LOLO=1.1 HIHI=2.45, HI=1.96

BFN Emergency Response Data System 11-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 29 of 45 Appendix A (Page 24 of 40)

ERDS Point Number 22 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

DW TEMP SPDS0010 Drywell Temperature 12/20/2006 BF1 1

DW TEMP SPDS0010 DRYWELL TEMPERATURE - COMPOSED Drywell Temperature A

DEGF N/A 0

400 N/A N/A P

2 Weighted Average w/Fault Detect (PSVA)

See Below N/A N/A N/A N

N/A Alarm:

Run:

Startup:

Shutdown/Refuel:

HIHI=160, HI=145, LO=100, LOLO=70 HIHI=160, HI=145, LO=90, LOLO=t0 HIHI=160, HI=145, LO=65, LOLO=60

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 30 of 45 Appendix A (Page 25 of 40)

ERDS Point Number 23 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

SP TEMP SPDS0016 Suppression Pool Temperature 12/20/2006 BF1 1

SP TEMP SPDS0016 SUPPR PL WTR TEMP - COMPOSED Suppression Pool Temperature A

DEGF N/A 30 230 N/A N/A P

16 Average (PSVA)

Around Circumference of Torus All modes: HIHI=95, HI=93, LOLO=50 N/A N/A N/A N

N/A

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 31 of 45 Appendix A (Page 26 of 40)

ERDS Point Number 24 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

SP LEVEL SPDS0013 Suppression Pool Water Level 12/20/2006 BF1 1

SP LEVEL SPDS0013 SUPPR PL WTR LVL (IN) - COMPOSED Suppression Pool Water Level A

INCHES N/A

-181.45 58.55 Below 181.45 inches above Torus Bottom P

4 Weighted Average w/Fault Detect (PSVA)

N/A See Below N/A N/A N/A N

N/A All modes: HIHI = -1 HI = -2 LO = -5.5 LOLO = -6.25

Emergency Response Data System (ERDS) Data Point Library 1-TI-411I Rev. 0001 Page 32 of 45 I

Appendix A (Page 27 of 40)

ERDS Point Number 25 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

H2 CONC 76-39 Drywell or Torus Hydrogen Level 12/20/2006 BF1 1

H2 CONC 76-39 DRYWELL H2 CONCENTRATION Drywell or Torus Hydrogen Level A

N/A 0

10 N/A N/A P

1 Weighted Average w/Fault Detect (PSVA)

N/A All modes: HIHI=2.4 HI=2.0 LOLO=0.10 N/A N/A N/A N

N/A Sensor input can be switched between the Torus and Drywell, therefore this point may be difficult to interpret.

Unique System Desc.:

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 33 of 45 Appendix A (Page 28 of 40)

ERDS Point Number 26 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

02 CONC 76-43 Drywell or Torus Oxygen Level 12/20/2006 BF1 1

02 CONC 76-43 DRYWELL OXYGEN CONCENTRATION Drywell or Torus Oxygen Level A

N/A 0

25 N/A N/A S

1 Polynomial N/A All modes: HIHI=3.3 H1=2.8 LOLO=0.10 N/A N/A LOW N

N/A Sensor input can be switched between the Torus and Drywell, therefore this point may be difficult to interpret.

Unique System Desc.:

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 34 of 45 Appendix A (Page 29 of 40)

Condensate Storage Tank #1 2-169 (UNIT 1) Level ERDS Point Number 27 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

CST LEVEL 12/20/2006 BF1 1

CST LEVEL 2-169 CST#1 (UNIT 1) LEVEL Condensate Storage Tank Level A

FEET 28 feet = 375,000 GALLONS 0

32 Below 2 feet above bottom of tank S

1 Polynomial N/A All modes: HIHI=29 HI=27 LO=12 LOLO=10 N/A N/A LOW N

N/A Zero level reference point is 2 feet above bottom of tank.

Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0001 Page 35 of 45 J

Appendix A (Page 30 of 40)

ERDS Point Number 28 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

WIND SPEED MET005 91M AVG WIND SPEEO 12/20/2006 BF1 1

WIND SPEED MET005 91M AVERAGE WIND SPEED (15 MIN AVG)

Wind Speed - Upper Level A

m/sec N/A 0

44.6 N/A N/A S

1 N/A At the 91 Meter Level of the Met Tower No Alarms N/A N/A LOW N

N/A The CECC computer system supplies the data for this point.

BFN Emergency Response Data System I1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 36 of 45 Appendix A (Page 31 of 40)

ERDS Point Number 29 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

WIND SPEED MET013 46M AVERAGE WIND SPEE[4 12/20/2006 BF1 1

WIND SPEED MET01 3 46M AVERAGE WIND SPEED (15 MIN AVG)

Wind Speed - Intermediate Level A

m/sec N/A 0

44.6 N/A N/A S

1 N/A At the 46 Meter Level of the Met Tower No Alarms N/A N/A LOW N

N/A The CECC computer system supplies the data for this point.

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 37 of 45 Appendix A (Page 32 of 40)

ERDS Point Number 30 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

WIND SPEED MET021 10M AVG WIND SPEE[I) 12/20/2006 BF1 1

WIND SPEED MET021 1OM AVERAGE WIND SPEED (15 MIN AVG)

Wind Speed - Lower Level A

m/sec N/A 0

44.6 N/A N/A S

1 N/A At the 10 Meter Level of the Met Tower No Alarms N/A N/A LOW N

N/A The CECC computer system supplies the data for this point.

BFN Emergency Response Data System I1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 38 of 45 Appendix A (Page 33 of 40)

ERDS Point Number 31 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

WIND DIR MET003 91M VECTOR WIND DIII 12/20/2006 BF1 1

WIND DIR MET003 91M VECTOR WIND DIR (15 MIN AVG)

Wind Speed - Upper Level A

DEG N/A 0

360 N/A N/A S

1 N/A At the 91 Meter Level of the Met Tower No Alarms N/A N/A LOW N

N/A Wind direction indicates the direction from which the wind is blowing.

The CECC computer system supplies the data for this point.

Emergency Response Data System (ERDS) Data Point Library 1-TI-411I Rev. 0001 Page 39 of 45 Appendix A (Page 34 of 40)

ERDS Point Number 32 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

WIND DIR MET011 46M VECTOR WIND DIR I

12/20/2006 BF1 1

WIND DIR MET011 46M VECTOR WIND DIR (15 MIN AVG)

Wind Direction - Intermed Level A

DEG N/A 0

360 N/A N/A S

1 N/A At the 46 Meter Level of the Met Tower No Alarms N/A N/A LOW N

N/A Wind direction indicates the direction from which the wind is blowing.

The CECC computer system supplies the data for this point.

Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0001 Page 40 of 45 I

Appendix A (Page 35 of 40)

ERDS Point Number 33 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

WIND DIR MET019 10M VECTOR WIND DIRI 12/20/2006 BF1 0

WIND DIR MET019 1OM VECTOR WIND DIR (15 MIN AVG)

Wind Direction - Lower Level A

DEG N/A 0

360 N/A N/A S

1 N/A At the 10 Meter Level of the Met Tower No Alarms N/A N/A LOW N

N/A Wind direction indicates the direction from which the wind is blowing.

The CECC computer system supplies the data for this point.

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 41 of 45 Appendix A (Page 36 of 40)

ERDS Point Number 34 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

STAB CLASS MET035 STACK LVL ATM ST'ý'B 12/20/2006 BF1 1

STAB CLASS MET035 STACK LVL ATM STAB CLASS (15 MIN) edit Stability STABA

-100

+100 N/A N/A P

2 No Alarms N/A N/A N/A N

N/A Differential Temperature Upper-Lower (deg C) (from CECC)

Difference

-1.9

-1.7

-1.5

-0.5 1.5 4.0

-1.9

-1.7

-1.5

-0.5 1.5 4.0 Stability Class Point Value A

1 B

2 C

3 D

4 E

5 F

6 G

7

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 42 of 45 Appendix A (Page 37 of 40)

ERDS Point Number 35 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

STAB CLASS MET037 OVERALL ATM STAh 12/20/2006 BF1 1

STAB CLASS MET037 OVERALL ATM STAB CLASS (15 MIN)

Air Stability Intermediate STABA

-100

+100 N/A N/A P

2 No Alarms N/A N/A N/A N

N/A Differential Temperature Upper-Intermed. (deg C) (from CECC)

Difference

< =Stabilitv Class Point Value

-1.9

-1.7

-1.5

-0.5 1.5 4.0

-1.9

-1.7

-1.5

-0.5 1.5 4.0 A

1 B

2 C

3 D

4 E

5 F

6 G

7

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0001 Page 43 of 45 Appendix A (Page 38 of 40)

ERDS Point Number 36 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

Generic Cond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

STAB CLASS MET039 GRND LVL ATM ST4B 12/20/2006 BF1 1

STAB CLASS MET039 GRND LVL ATM STAB CLASS (15 MIN)

Air Stability Lower STABA

-100

+100 N/A N/A P

2 No Alarms N/A N/A LOW N

N/A Differential Temperature Intermed-Lower (deg C) (from CECC)

Difference

<=

Stabilitv Class Point Value

-1.9

-1.7

-1.5

-0.5 1.5 4.0

-1.9

-1.7

-1.5

-0.5 1.5 4.0 A

1 B

2 C

3 D

4 E

5 F

6 G

7

BFN Emergency Response Data System 1-TI-411 Unit I (ERDS) Data Point Library Rev. 0001 Page 44 of 45 Appendix A (Page 39 of 40)

ERDS Point Number 37 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

TYPEDATA REAL/SIMULATED 12/20/2006 BF1 1

TYPEDATA REAL/SIMULATED REAL/SI MULATED A

REAL/SIMU N/A N/A N/A N/A N/A P

0 0 IF REAL, 1 IF SIMULATED N/A N/A N/A N/A N/A N

N/A This point is used to indicate whether the data is coming from the unit or from the simulator.

Unique System Desc.:

Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0001 Page 45 of 45 Appendix A (Page 40 of 40)

ERDS Point Number 38 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc:

GenericCond Desc:

Analog/Digital Engr Units/Dig States:

Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations:

Alarm/Trip Set Points:

NID Power Cutoff Level:

NID Power Cut-On Instrument Failure Mode:

Temperature Compensation:

Level Reference Leg:

Unique System Desc.:

RADIOACTIVITY OF RELEASED GASES EFF GAS RAD SPDS0024 12/20/2006 BF1 1

EFF GAS RAD SPDS0024 STACK RELEASE RATE - COMPOSED Radioactivity of Released Gasses A

Ci/SEC N/A 0.0 200 N/A N/A P

7 See Below Plant Stack All modes: HIHI=140 HI=14 N/A N/A LOW Y

N/A How Processed: Stack flow (cfm) X Stack Release Activity (uCi/cc) (MULT). where Stack Activity = Monitor counts X Calibration constant X Temperature correction X Pressure correction X Dead Time correction.