ML062720179

From kanterella
Jump to navigation Jump to search

Tech Spec Pages for Amendment 167 Regarding Extended Containment Isolation Valve Completion Times
ML062720179
Person / Time
Site: Wolf Creek 
(NPF-042)
Issue date: 09/28/2006
From:
NRC/NRR/ADRO/DORL/LPLIV
To:
Donohew J N, NRR/DORL/LP4, 415-1307
Shared Package
ML062710545 List:
References
TAC MC3944
Download: ML062720179 (18)


Text

Amendment Number 167 Implementation Additional Condition Date WCNOC will revise the WCGS containment isolation fault tree model prior to utilization of the requested cointainment-isolation valve Completion Time extensions by either: 1) modeling containment isolation valves for at least one of each WCAP-1 5791 penetration type applicable to WCGS, including penetrations to the containment atmosphere greater than 2 inches in diameter or 2) modeling all containment isolation valves associated with this license amendment request, including penetrations to the containment atmosphere greater than 2 inches in diameter. A peer revi 'ew of the changes to the containment isolation fault tree model, including addressing Category A and Category B findings, will be completed following revision to the containment isolation fault tree model.

Prior to implementation of the amendment WCNOC Will implement in its procedures the requirement to confirm that the remaining containment isolation valve(s) in the affected penetration(s) are in their correct position(s) prior to performing maintenance on a containment isolation valve.'

Prior to the start of Refueling Outage 16 Prior to the start of Refueling Outage 16 167 Amendment No. 167 Amendment.

Number Implementation Additional Condition Date 123 163 163 For SRs that existed prior to this amendment whose intervals of performance are being extended, the first extended surveillance interval begins upon completion of the last surveillance performed prior to implementation of this amendment..

The licensee will perform a one-time load acceptance test of the Sharpe Station prior to the first use of the 7-day Completion Time of Required.

Action B.4.2.2 of TS 3.8.1. The test shall utilize a nearby large -motor for the purposes of simulating a large plant load. This test will be performed in conjunction with a dynamic voltage flow analysis.

The licensee will coordinate with KEPCo to ensure the load capability testing/verification is performed within 8 months prior to utilization of the 7-day Completion Time of Required Action B.4.2.2 in TS 3.8.1. The load capability testing/verification will consist of either crediting a running of the gensets for load for commercial reasons for greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or tested by loading of the gensets for greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to a load equal to or greater than required to supply safety related loads in the event of a station blackout.

The licensee will ensure the RCP. seal model from WCAP-1 5603, Rev. 1 -A, "WOG 2000 Reactor Coolant Pump Seal Leakage Model for Westinghouse PWRs" is utilized in the -2002 WOGS PSA Model. The licensee will verify that the utilization of the Sharpe Station for supporting an extended DG Completion Time in the 2002 WCGS PSA Model meets the risk acceptance guidelines of Regulatory Guide 1.174 and Regulatory Guide 1.177. Additionally, the licensee will include the risk impact of the Sharpe Station in the Safety Monitor, i 'ncluding adding an activity to the Activity Table that will account for the impact of the plant configuration associated with crediting the Sharpe Station during the use of an extended Completion Time for pre-planned maintenance activities.

This amendment shall be implemented by December 31,i 1999.

Prior to the first use of the 7-day Completion Time of Required Action B.4.2.2 of TS 3.8.1.

Prior to the use of the 7-day Completion Time of Required Action B.4.2.2 of TS 3.8.1.

Prior to the first use of the 7-day Completion Time of Required Action B.4.2.2 of TS 3.8.1.

163 Amendment No. 42-3,163

TABLE OF CONTENTS 3.3 INSTRUMENTATION (continued) 3.3.6 Containment Purge Iso -lation Instrumentation........................... 3.3-46

'3.3.7 Control Room Emergency Ventilation System (CREVS)

Actuation Instrumentation............................................3.3-50 3.3.8 Emergency Exhaust System (EES) Actuation Instrumentation.......................................................

3.3-55

.3.4 REACTOR COOLANT SYSTEM (RCS)......................................

3.4-1 3.4.1 RCS Pressure, Temperature, and Flow Departure from Nucleate Boiling (DNB) Limits........................... 3.4:-1 3.4.2 RCS Minimum Temperature for Criticality...............................

3.4-5 3.4.3 RCS Pressure and Temperature (PIT) Limits......... *................

3.4-6 3.4.4 RCS Loops - MODES 1 and 2...........................................

3.4-8 3.4.5 RCS Loops - MODE 3....................................................

3.4-9 3.4.6 RCS Loops - MODE 4....................................................

3.4-12 3.4.7 RCS Loops - MODE 5, Loops Filled.................

3.4-14 3.4.8 RCS Loops - MODE 5, Loops Not Filled...............................

3.4-17 3.4.9 Pressurizer............................................. 3.4-19 3.4.10 Pressurizer Safety Valves................................................

3:4-21 3.4.11 Pressurizer Power Operated Relief Valves (PORVs).................. 3.4-23 3.4.12

.Low Temperature Overpressure Protection (LTOP) System......... 3.4-26 3.4.13 RCS Operational LEAKAGE..........

................. o3.4-31 3.4.14 RCS Pressure Isolation Valve (PIV) Leakage...........3.-3 3.4.15 RCS Leakage Detection Instrumentation..............................

3.4-37 3.4.16 RCS Specific Activity.......................................................

3.4-41 3.4.17 Steam Generator.(SG) Tube Integrity...................................

3.4-45 3.5

.EMERGENCY CORE COOLING SYSTEMS (ECCS).......................

3.5-1 3.5.1 Accumulators.............................................................

3.5-1 3.5.2 ECCS - Operating........................................................

3.5-3 3.5.3 ECCS - Shutdown.........................................................

3.5-6 3.5.4.

Refueling Water Storage Tank (RWST)................................ 3.5-8 3.5.5 Seal Injection Flow........................................................

3.5-10 3.6.

CONTAINMENT SYSTEMS...................................................

3.6-1 3.6.1 Containment........................................

3.6-1 3.6.2 Containment Air Locks....................................................

3.6-2 3.6.3

.Containment Isolation Valves...........................................

3.6-7 3.6.4 Containment Pressure...................................................

3.6-14 3.6.5 Containment Air Temperature...........................................

3.6-15 3.6.6 Containment Spray and Cooling Systems.............................

3.6-16 3.6.7 Spray Additive System...................................................

3.6-19 Wolf Creek - Unit 1 ii WolfCrek - nitI i

Amendment No. 1 23, 131, 157, 1 61, 167

.TABLE OF CONTENTS 1.0 USE AND APPLICATION............................................................

1.1-1 1.1 Definitions..............................................

......................... 1-1.2 Logical Connectors....................................................

1.2-1 1.3 Completion Times..............................................................

1.3-1 1.4 Frequency.......................................................................

1.4-1 2.0.

SAFETY LIMITS (SLs)...............................................................

2.0-1 2.1 SLs 2.0-1 2.2 SL Violations....................................................................

2.0-1 3.0 LIMITING CONDITION FOR OPERATION (LCO) APPLICABILITY............ 3.0-1 3.0 SURVEILLANCE REQUIREMENT (SR) APPLICABILITY.......................

3.0-3 3.1 REACTIVITY CONTROL SYSTEMS.........................................

3.1-1 3.1.1 SHUTDOWN MARGIN (SDM)...........................................

3.1-1 3.1.2 Core Reactivity............................................................

3.1-2

.3. 1.3 Moderator Temperature Coefficient (MTC).............................

3.1-4 3.1.4 Rod Group Alignment Limits.............................................

3.1-7 3.1.5 Shutdown Bank Insertion Limits........................................

3.1-11 3.1.6 Control Bank Insertion Limits............

............ 3.1-13 3.1.7 Rod Position Indication...................................................

3.1-16 3.1.8 PHYSICS TESTS Exceptions - MODE 2..............................

3.1-19 3.2 POWER DISTRIBUTION LIMITS.............................................

3.2-1 3.2.1 Heat Flux Hot Chaninel Factor (FQ(Z))

(EQ Methodology)'......

3.2-1 3.2.2 Nuclear Enthalpy Rise* Hiot'6Channe Facto~r*(Fý.)........................ 3.2-6 3.2.3 AXIAL FLUX DIFFERENCE (AFD) (Relaxed Axial Offset Control (RAOC) Methodology)........... ;...........................

3.2-9 3.2.4 QUADRANT POWER TILT RATIO (QPTR)............................

3.2-10 3.3 INSTRUMENTATION... **.....................................................

3.3-1 3.3.1 Reactor Trip System (RTS) Instrumentation...........................

3.3-1 3.3.2 Engineeired Safety Feature Actuation System (ESFAS)

Instrumentation...............................................

........ 3.3-21 3.3.3 Post Accident Monitoring (PAM) Instrumentation......................

3.3-37 3.3.4 Remote Shutdown System...............................................

3.3-41 3.3.5 Loss of Power (LOP) Diesel Generator (DG) Start.

Instrumentation........................................................

3.3-44 Wolf Creek -,Unit 1 i

WolfCree - Uit IAmendment No. 123

Containment Isolation Valves 3.6.3 3.6 CONTAINMENT SYSTEMS 3.6.3 Containment Isolation Valves LCO 3.6.3 APPLICABILITY:

Each containment isolation valve shall be OPERABLE.

MODES 1, 2, 3,and 4.

ACTIONS.

1.

Penetration flow path(s) except for containment -shutdown purge valve flow paths may be unisolated intermittently under administrative controls.

2.

Separate Condition entry is allowed for each penetration flow path.

3.

Enter applicable Conditions and Required Actions for systems made inoperable by containment isolation valves.

4.

Enter applicable C 'oniditions and Required Actions of LCO 3.6.1, "Containment," when isolation valve leakage results in exceeding the overall containment leakage rate acceptance criteria..

CONDITION REQUIRED ACTION COMPLETION TIME A.

One or more penetration A.1 Isolate the affected 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for flow paths with one.penetration flow path by Category I CIVs containment isolation valve use of at least one closed (CIV) inoperable except for and de-activate~d AND purge valve leakage not automatic valve, closed within limit.

manual valve, blind 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for flange, or check valve with Category 2 CIVs flow through the valve secured.

AND AND 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> for Category 3 CIVs AND

___(continued)

Wolf Creek - Unit 1 3.6-7 WolfCrek -UnitI 36-7Amendment No. 4 23, 4 3 4, 167

Containment Isolation Valves 3.6.3 ACTIONS (continued)

CONDITION J

REQUIRED ACTION JCOMPLE TIME A.

(continued)

A.2 1.Isolation devices in high radiation areas may be verified by use of administrative means.

2.

Isolation devices that are locked, sealed, or otherwise secured may be verified by administrative means.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> for Category 4 CIVs AND 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> for Category 5 CIVs AND 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> for Category 6 CIVs AND 7 days for Category 7 CIVs Once per 31 days for isolation devices outside containment AND Verify the affected penetration flow path is.

isolated.

(continued)

I Wolf Creek - Unit 1 3.6-8 WolfCrek -UnitI 36-8Amendment No. 42-3,167

Containment Isolation Valves 3.6.3 ACTIONS (continued)_________________________

CONDITION REQUIRED ACTION COMPLETION TIME A.

(continued)

Prior to entering MODE 4 from MODE 5 if not performed within the previous 92 days for isolation devices inside containment B. -------

NOTE--------

B.1 Isolate the affected 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Only applicable to penetration flow path by penetration flow paths with use of at least one closed two containment isolation and de-activated valves.

automatic valve, closed manual valve, or blind flange.

One or more penetration flow paths with two containment isolation valves inoperable except*

for containment purge valve leakage not within

  • limit.

C. Two or more penetration 0.1 Isolate all but one 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> flow paths with one penetration flow path by containment isolation valve use of at least one closed inoperable for reasons and de-activated other than Condition D.

automatic valve, closed manual valve, or blind flange.

(continued)

Wolf Creek - Unit 1 3.6-9 Wolf reek-Unt I.6-9Amendment No.-423, 167

Containment Isolation Valves 3.6.3 ACTIONS (continued)

CONDITION REQUIRED ACTION jCOMPLETION TIME D.1 D. One or more penetration flow

  • paths with one or more containment purge valves not within leakage limits.

Isolate the affected penetration flow path by use of at least one closed and de-activated automatic valve, closed manual valve, or blind flange.

AND D.2 1 Isolation devices in high radiation areas may be verified by use of administrative means.

2.

Isolation devices that are locked, sealed, or otherwise secured may be verified by administrative

-means.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Once per 31 days for isolation devices outside containment AND Prior to entering MODE 4 from Verify the affected penetration flow path is isolated.

MODE 5 if not performed within the previous 92 days for isolation devices inside containment (continued)

AND Wolf Creek - Unit 1 3.6-10 WolfCrek - nit1 3.-10Amendment No. 123, 167.

Containment Isolation.Valves 3.6.3 ACTIONS (continued).

CONDITION REQUIRED ACTION COMPLETION TIME D. (continued)

D.3 Perform SR 3.6.3.'6 or Once per 92 days SR 3.6.3.7 for the resilient seal purge valves closed to comply with Required Action D.1.

E.

Required Action and EA1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

AND E.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> SURVEILLANCEREQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.3.1 Verify each containment shutdown purge valve is Once per 31 days sealed closed or closed and blind flange insta*lled for isolation except for one purge valve in a. penetration flow path devices outside while in Condition D of this LCO.

Containment

'AND Prior to entering MODE 4 from MODES5 if not performed within the previous 92 days for isolation devices inside containment (continued)

Wolf Creek - Unit 1 3.6-11 Wolf reek-Uni I 36-11Amendment No. 423.4,13I,67 1

Containment isolation Valves 3.6.3 SURVEILLANCE REQUIREMENTS (continued)

S URVEI LLAN CE FREQUENCY S R 3.6.3.2 Verify each containment, 'mini-purge valve is closed, 31 days except when the containment mini-purge valves are open for pressure control, ALARA or air quality considerations for-personnel entry, or for Surveillances that require the valves to be open.

SR 3.6.3.3 NT---

Valves and blind flanges in high radiation areas may be verified by use of administrative controls.

Verify each containment isolation manual valve and 31 days blind flange that is located outside containment and not locked, sealed, or otherwise secured and required to be closed during accident conditions is closed, except for containment isolation valves that are open under administrative controls.

SR 3.6.3.4 Valves and blind flanges in high radiati.on areas may be verified by use of administrative means.

Verify each containment isolation manual valve and Prior to entering blind flange that is located inside containment and not MODE 4 from locked, sealed, or otherwise secured and required to MODE 5 if not be closed during accident conditions is closed, except performed within for containment isolation valves that are open under the previous administrative controls.

92 days SR 3.6.3.5 Verify the isolation time of each automatic power In accordance with operated containment isolation valve is within limits, the Inservice Testing Program (continued)

Wolf Creek - Unit 1 3.6-12 WolfCrek - nitI 3.-12Amendment No. 42-3, 167 1

Containment Isolation Valves 3.6.3 SURVEILLANCE RE QUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.6.3.6


NOTE--------

Only required to be performed when containment shutdown purge valve blind flanges are installed.

Perform leakage rate testing for containment 24 months shutdown purge valves with resilient seals and associated blind flanges.

.AND Following each

-reinstallation of the blind flange S R 3.6.3.7-------NOE Only required to be performed for the containment shutdown purge valves when associated blind flanges are removed.

Perform leakage rate testing for containment 184 days mini-purge and shutdown purge valves with resilient seals.

AND Within 92 days after opening the valve S R 3.6.3.8 Verify each automatic contain ment isolation valve 18 months that is not locked, sealed or otherwise secured in position, actuates to the isolation position on an actual or simulated actuation signal..

Wolf Creek - Unit I 3.6-13 Wolf reek-Uni I 36-13Amendment No. 4-43, 167 1

Containment Pressure 3.6.4 3.6 CONTAINMENT SYSTEMS 3.6.4 Containment Pressure LCO 3.6.4 APPLICABILITY:

Containment pressure shall be Ž-0.3 psig and * + 1.5 psig.

MODES 1, 2,3, and 4.

ACTIONS_________________

CONDITION REQUIRED ACTION COMPLETION TIME A.

Containment pressure not A.1 Restore containment 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> within limits, pressure to within limits.

B.

Required Action and B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

AND

83.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLAN CE FREQUENCY SR 3.6.4.1 Verify containment pressure is within limits.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Wolf Creek - Unit 1 3.6-14 WolfCrek - nitI 3.-14Amendment No. 42-3, 167 1

Containment Air Temperature 3.6.5 3.6 CONTAINMENT SYSTEMS 3.6.5 Containment Air Temperature LCO 3.6.5 APPLICABILITY:

Containment average air temperature shall be

  • 1200F.

MODES 1, 2, 3, and 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

Containment average air A.1 Restore containment 8 hoUrs temperature not within average air temperature limit.

to within limit.

1.

Required Action and B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

AND B.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6.5.1 Verify containment average air temperature is within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> limit.

Wolf Creek - Unit 1 3.6-15 WolfCrek - nitI 3.-15Amendment No. 4-2-3,167 1

Containment Spray and Cooling Systems 3.6.6 3.6 CONTAINMENT SYSTEMS 3.6.6 Containment Spray and Cooling Systems LCO 3.6.6 APPLICABILITY:

OPERABLE.

MODES 1, 2, 3, and 4.

  • ACTIONS___

CONDITION REQUIRED ACTION COMPLETION TIME A.

One containment spray A.1

.Restore containment 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> train inoperable.

spray train to OPERABLE status.

AND 10 days from discovery of failure.

to meet the LCO B.

Required Action and B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition A not AND met.

B.2 Be in MODE 5.

84 hours9.722222e-4 days <br />0.0233 hours <br />1.388889e-4 weeks <br />3.1962e-5 months <br /> C. One containment cooling CA1 Restore containment 7 days train inoperable.

cooling train to OPERABLE status.

AND 10 days from

  • discovery of failure to meet the LCO
  • (continued)

Wolf Creek - Unit 1 3.6-16 WolfCrek - nitI 3.-16Amendment No. 42-3, 167 1

Containment Spray and Cooling Systems 3.6.6 ACTIONS (continued)__________________________

CONDITION REQUIRED ACTION COMPLETION TIME D. Two containment cooling D.1 Restore one containment 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> trains inoperable.

Cooling train to OPERABLE status.

E.

Required Action and E.1 Be in MODE 3.'

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated. Completion Time of Condition C or D AND not met.

E.2 Be in MODE 5.

36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> F.

Two containment spray F.1 Enter LCO 3.0.3.

Immediately trains inoperable.

OR Any combination of three or more trains inoperable.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY S R 3.6.6.1 Verify each containment spray manual, power 31 day operated, and automatic valve in the flow path that is not locked, sealed, or otherwise secured in position is in the correct position.

S R 3.6.6.2 Operate each containment cooling train fan unit for 31 days

>15 minutes.

(continued)

Wolf Creek - Unit I 3.6-17 WolfCrek - nitI 3.-17Amendment No. 42-3, 167 1

Containment Spray and Cooling Systems 3.6.6 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY S R 3.6.6.3 Not Used.

S R 3.6.6.4 Verify each containment spray pump's developed In accordance with head at the flow test point is greater than or equal to the Inservice the required developed head.

Testing Program SR 3.6..6.5 Verify each automatic*contain ment spray valve in the 18 months flow path that is not locked, sealed, or otherwise secured -in position, actuates to the correct position on an actual or simulated actuation signal.

SR.3.6.6.6 Verify each containment spray pump starts 18 months automatically on an actual or simulated actuation signal.

S R 3.6.6.7 Verify each containment cooling train starts 18 months automatically and minimum cooling water flow rate is established on an actual or simulated actuation signal.

S R 3.6.6.8 Verify each spray nozzle is unobstructed.

10 years Wolf Creek - Unit I 3.6-18 WolfCrek - nit1 3.-18Amendment No. 42-3, 167 1

Spray Additive System 3.6.7 3.6 CONTAINMENT SYSTEMS 3.6.7 Spray Additive System LCO 3.6.7 APPLICABILITY:

The Spray Additive System shall be OPERABLE.

MODES 1, 2, 3, and 4.

ACTIONS CONDITION

-REQUIRED ACTION COMPLETION TIME A.

Spray Additive System A.1 Restore Spray Additive 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> inoperable.

System, to OPERABLE status.

  • .B. Required Action and B.1 Be in MODE 3.

6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.

AND B.2 Be in MODE 5.

84 hours9.722222e-4 days <br />0.0233 hours <br />1.388889e-4 weeks <br />3.1962e-5 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.6..1 Verify each spray additive manual, power operated, 31 days and automatic valve in the flow path that is not locked, sealed, or otherwise secured in position is in the correct position.

(continued)

Wolf Creek - Unit 1 3.6-19 WolfCrek - nit1 3.-19Amendment No. 423, 167 1

Spray Additive System 3.6.7 SURVEILLANCE REQUIREMENTS (continued)________

SURVEILLANCE FREQUENCY S R 3.6.7.2 Verify spray additive tank solution volume is Ž4340 184 days gal and *ý 4540 gal.

S R 3.6.7.3 Verify spray additive tank solution concentration is 184 days

Ž28% and5 *31 % by weight.

SR 3.6.7.4 Verify each spray additive automatic valve in the flow 18 months path that is not locked, sealed, or otherwise secured in position, actuates to the -correct position on an actual or simulated actuation signal.

S R 3.6.7.5 Verify spray additive flow rate from each solution's 5 years flow path.

Wolf Creek - Unit 1 3.6-20 Wolf reek-Uni I 36-20Amendment No. 42-3,1I67