C C

C I

Monthly Analysis Data for the Main Fuel Oil Storage Tank for 2000 and 2003 Date Sulfur Cu Corr.

Flash Point Cetane Index Water &sed Dist Temp 90%

Viscosity Cloud Point Ash Carbon res Particulates Cetane Index D-4294 D-130 D-93 D-976 D-1796 D-86 D-445 D-2500 D-482 D-524 D-2276 D-4737 January-03

<0.10 %

pass 1-A 140 deg F 45

<0.025%

600 deg F 2.2 cST

-4 deg F

<0.005%

0.25%

NA NA February-03

<0.10%

pass 1-A 147 deg F 45

<0.025%

600 deg F 2.1 cST

-4 deg F

<0.005%

0.17%

NA NA March-03

<0.10%

pass I-A 136 deg F 44.7

<0.025%

600 deg F 2.1 cST

-6 deg F

<0.005%

0.17%

0.3 mg/L NA April Top 0.03%

pass I-A 138 deg F 45

<0.025%

600 deg F 2.1 cST

-5 deg F

<0.005%

0.18%

3.1 mg/L NA April Middle 0.02%

pass 1-A 140 deg F 45.2

<0.025%

600 deg F 2.1 cST

-5 deg F

<0.005%

0.16%

NA NA April Bottom 0.02%

pass 1-A 138 deg F 45.2

<0.025%

600 deg F 2.1 cST

-5 deg F

<0.005%

0.18%

NA NA Fuel Oil Deliv.

0.05%

pass 1-A 124 deg F 45.8

<0.025%

607 deg F 1.98 CST

-5 degF

<0.005%

0.13%

1.0 mg/L 44.6 May-03 0.04%

pass 1-A 138 deg F 44.8

<0.025%

597 deg F 2.1 cST

-5 deg F

<0.005%

0.17%

NA 43.9 June-03 0.04%

pass 1-A 134 deg F 45.4

<0.025%

595 deg F 2.08 cST.

-4 deg F

<0.005%

0.16%

1.5 mg/L 44.4 July Top 0.04%

pass 1-A 136 deg F 44.9

<0.025%

597 deg F 2.06 cST

-3 deg F

<0.005%

0.19%

3.6 mg/L 44.1 July Middle 0.04%

pass 1-A 136 deg F 45.1

<0.025%

597 deg F 2.07 cST

-3 deg F

<0.005%

0.16%

2.8 mg/L 44.3 July Bottom 0.04%

pass I-A 138 deg F 45.5

<0.025%

598 degF 2.07 cST

-3 deg F

<0.005%

0.11%

1.9 mg/L 44.6 August-03 0.04%

pass 1-A 138 deg F 45.1

<0.025%

598 degF 2.11 cST

-4 deg F

<0.005%

0.14%

NA 44.2 September-03 0.04%

pass 1-A 140 deg F 45.4

<0.025%

600 deg F 2.05 cSt

-3 degF

<0.005%

0.16%

0.7 mg/L 44.4 October Top 0.04%

pass 1-A 138 deg F 45.4

<0.025%

600 deg F 2.09 cST

-3 deg F

<0.005%

0.18%

1.9 mg/L 44.5 October Middle 0.04%

pass 1-A 136 deg F 45.1

<0.025%

596 deg F 2.08 cST

-2 deg F

<0.005%

0.14%

1.7 mg/L 44.2 October Bottom 0.04%

pass 1-A 136 deg F 45.1

<0.025%

596 deg F 2.09 cST

-2 degF

<0.005%

0.15%

1.1 mg/L 44.2 November-03 0.04%

pass 1-A 142 deg F 45.4

<0.025%

598 degF 2.07 cST

-1 degF

<0.005%

0.10%

2.3 mg/L 44.7 December-03 0.04%

pass 1-A 142 deg F 45.4

<0.025%

600 deg F 2.10 cSt

-2 deg F

<0.005%

0.15%

1.7 mg/L 44.3 D-129 Pour Point January-00

<0.1%

pass 1-A 146 deg F 46 0.00%

588 deg F 2.1 cST NA 0.00%

0.14%

NA

<-25 deg F February-00

<0.10 pass 1-A 146.4 deg F 46

<0.025%

586 deg F 2.10 cSt NA 0.01%

0.14%

NA

<-30 deg F March-00

<0.10%

pass 1-A 146.4 deg F 46.3

<0.025%

592 deg F 2.10 cSt NA 0.00%

0.11%

1.4 mg/L

<!-35 deg F April-00

<0.10%

pass 1-A 146.4 deg F 46

<0.025%

594 deg F 2.08 cST NA 0.00%

0.11%

NA

<-30 deg F May-00

<0.10%

pass 1-A 151 deg F 47.2

<0.025%

590 deg F 2.09 cST NA 0.00%

0.13%

NA

<'-25 deg F June-00

<0.10%

pass 1-A 136 deg F 45

<0.025%

582 deg F 2.10 cSt NA

<0.005%

0.16%

3.6 mg/L

<-25 deg F July-00

<0.10%

pass 1-A 136 deg F 46.2

<0.025%

596 deg F 2.07 cST NA

<0.005%

0.14%

NA

<-25 deg F August-00

<0.10%

pass 1-A 138 deg F 46

<0.025%

594 deg F 2.07 cST NA

<0.005%

0.16%

NA

<-25 deg F September-00

<0.10%

pass 1-A 144 deg F 45.4

<0.025%

588 deg F 2.05 cSt 3 deg F

<0.005%

0.14%

NA

<-25 deg F October-00

<0.10%

pass 1-A 142 deg F 45.9

<0.025%

590 deg F 2.13 cSt 0 deg F

<0.005%

0.15%

NA

<-25 deg F November-00

<0.05%

pass 1-A 140 deg F 44.5

<0.025%

596 deg F 2.07 cST 1 deg F

<0.005%

0.09%

2.2 mg/L

<-35 deg F December-00

<0.10%

pass 1-A 142 deg F 45

<0.025%

594 deg F 2.17 cST 1 deg F

<0.005%

0.14%

4.5 mg/L

<-25 deg F Note: Analyses Starting April, 2003 performed using ASTM D-975-02; Analyses for 2000 were performed using ASTM D-975-68

C C

Quarterly Top, Middle and Bottom Sampling Results for the Main Fuel Oil Storage Tank 2003-2004 C

ASTM D978-02 &

07/14/03 10/17/03 01/21/04 4/21/04 7/22/04 D-2276 Analysis by Martel Labs Parameter Top Middle Bottom Top Middle Bottom Top Middle Bottom Top Middle Bottom Top Middle Bottom Sulfur in Petroleum % 0.0387 0.0406 0.0396 0.0392 0.0387 0.0382 0.0432 0.0418 0.0435 0.0378 0.0389 0.0371 0.04 0.04 0.04 Cu-Corrosion

<IA

<IA

<1A

<IA

<IA

<IA

<IA

<IA

<IA

<IA

<IA

<IA

<IA

<IA

<IA Flash Point, 'F 136 136 138 138 136 136 140 140 140 136 136 136 130 128 128 Cetane Index 44.9 45.1 45.5 45.4 45.1 45.1 45.5 45.7 45.7 44.6 44.5 44.8 44.4 44.7 44.4 Water & Sed. % by vol 0.025

<0.025

<0.025

<0.025

<0.025

<0.025

<0.025

<0.025 0.025

<0.025

<0.025

<0.025

<0.025

<0.025

<0.025 Distillation Temp. 90%

597 597 598 600 596 596 598 598 599 598 596 597 600 598 598 Viscosity, Kinematic 2.06 2.07 2.07 2.09 2.08 2.09 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 Cloud Point F

-3

-3

-3

-3

-2

-2

-4

-4

-4

-4

-4

-4

-2

-2

-2 Ash from Petroleum %

o.o00

<0.005

<0.005

<0.005

<0.005

<0.005

<0.005

<0.005

<0.005

<0.005

<0.005

<0.005

<0.005

<0.005

<0.005 Carbon Residue, %

0.19 0.16 0.11 0.18 0.14 0.15 0.14 0.16 0.13 0.07 0.08 0.15 0.09 0.09 0.09 Particulates mg/L 3.6 2.8 1.9 1.9 1.7 1.1 3.1 2.7 2.9 1.5

    • >:8 ii 1.7 1

0.9 1