LCO Applicability 3.0 3.0 LIMITING CONDITION FOR OPERATION (LCO) APPLICABILITY LCO 3.0.1 LCOs shall be met during the MODES or other specified conditions in the Applicability. except as provided in LCO 3.0.2 and3.0.7.
LCO 3.0.2 Upon discovery of a failure to meet an LCO. the Required Actions of the associated Conditions shall be met, except as provided in LCO 3.0.5 and LCO 3.0.6.
If the LCO is met or is no longer applicable prior to expiration of the specified CompletionTime(s), completion of the Required Action(s) is not required unless otherwise stated.
LCO 3.0.3 When an LCO is not met and the associated ACTIONS are not met, an associated ACTION is not provided, or if directed by the associated ACTIONS, the unit shall be placed in a MODE or other specified condition in which the LCO is not applicable. Action shall beinitiatedwithinI hour to place the unit, as applicable, in:
- a. MODE 3 within 7 hours8.101852e-5 days <br />0.00194 hours <br />1.157407e-5 weeks <br />2.6635e-6 months <br />;
- b. MODE 4 within 13 hour1.50463e-4 days <br />0.00361 hours <br />2.149471e-5 weeks <br />4.9465e-6 months <br />s: and
- c. MODE 5 within 37 hours4.282407e-4 days <br />0.0103 hours <br />6.117725e-5 weeks <br />1.40785e-5 months <br />.
Exceptions to this Specification are stated in the individual Specifications.
Where corrective measures are completed that permit operation in accordance with the LCO or ACTIONS, completion of the actions required by LCO 3.0.3 is not required.
LCO 3.0.3 is only applicable in MODES 1, 2. 3, and 4.
LCO 3.0.4 When an LCO is not met, entry into a MODE or other specified condition in the Applicability shall only be made:
(continued)
HBRSEP Unit No. 2 3.0-1 Amendment No. 44, 203
- LCO Applicability 3.0 3.0 LCO APPLICABILITY LCO 3.0.4 (continued)
- a.
When the associated ACTIONS to be entered permit continued operation in the MODE or other specified condition in the Applicability for an unlimited period of time, or
- b. After performance of a risk assessment addressing inoperable systems and components, consideration of the results, determination of the acceptability of entering the MODE or other specified condition in the Applicability, and establishment of risk management actions, if appropriate:
exceptionstothisSpecificationare stated inthe individual Specifications, or
- c. When an allowance is stated in the individual value, parameter, or other Specification.
This Specification shall not prevent changes in MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.
LCO 3.0.5 Equipment removed from service or declared inoperable to comply with ACTIONS may be returned to service under administrative control solely to perform testing required to demonstrate its OPERABILITY or the OPERABILITY of other equipment. This is an exception to LCO 3.0.2 for the system returned to service under administrative control to perform the testing required to demonstrate OPERABILITY.
LCO 3.0.6 When a supported system LCO is not met solely due to a support system LCO not being met. the Conditions and Required Actions associated with this supported system are not required to be entered. Only the support system LCO ACTIONS are required to be entered. This is an exception to LCO 3.0.2 for the supported system. In this event, additional evaluations and limitations may be required in accordance with Specification 5.5.15, "Safety Function Determination Program (SFDP)." If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which (continued)
HBRSEP Unit No. 2 3.0-2 Amendment No. -76, 203
LCO Applicability 3.0 3.0 LCO APPLICABILITY LCO 3.0.6 the loss of safety function exists are required to be entered.
(continued)
When a support system's Required Action directs a supported system to be declared inoperable or directs entry into Conditions and Required Actions for a supported system, the applicable Conditions and Required Actions shall be entered in accordance with LCO 3.0.2.
LCO 3.0.7 Test Exception LCO 3.1.8 allows specified Technical Specification (TS) requirements to be changed to permit performance of special tests and operations. Unless otherwise specified, all other TS requirements remain unchanged.
Compliance with Test Exception LCOs is optional. When a Test Exception LCO is desired to be met but is not met, the ACTIONS of the Test Exception LCO shall be met. When a Test Exception LCO is not desired to be met, entry into a MODE or other specified condition in the Applicability shall be made in accordance with the other applicable Specifications.
HBRSEP Unit No. 2 3.0-3 Amendment No. F46, 203
SR Applicability 3.0 3.0 SURVEILLANCE REQUIREMENT (SR) APPLICABILITY SR 3.0.1 SRs shall be met during the MODES or other specified conditions in the Applicability for individual LCOs, unless otherwise stated in the SR. Failure to meet a Surveillance, whether such failure is experienced during the performance of the Surveillance or between performances of the Surveillance, shall be failure to meet the LCO. Failure to perform a Surveillance within the specified Frequency shall be failure to meet the LCO except as provided in SR 3.0.3. Surveillances do not have to be performed on inoperable equipment or variables outside specified limits.
SR 3.0.2 The specified Frequency for each SR is met if the Surveillance is performed within 1.25 times the interval specified in the Frequency, as measured from the previous performance or as measured from the time a specified condition of the Frequency is met.
For Frequencies specified as "once," the above interval extension does not apply.
If a Completion Time requires periodic performance on a "once per..." basis, the above Frequency extension applies to each performance after the initial performance.
Exceptions to this Specification are stated in the individual Specifications.
SR 3.0.3 If it is discovered that a Surveillance was not performed within its specified Frequency, then compliance with the requirement to declare the LCO not met may be delayed, from the time of discovery, up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or up to the limit of the specified Frequency, whichever is less. This delay period is permitted to allow performance of the Surveillance.
(continued)
HBRSEP Unit No. 2 3.0-4 Amendment No. 1-76, 203
SR Applicability 3.0 3.0 SR APPLICABILITY SR 3.0.3 If the Surveillance is not performed within the delay period, (continued) the LCO must immediately be declared not met, and the applicable Condition(s) must be entered.
When the Surveillance is performed within the delay period and theSurveillance is not met, the LCOmust immediately be declared not met, and the applicable Condition(s) must be entered.
SR 3.0.4 Entry into a MODE or other specified condition in the Applicability of an LCO shall only be made when the LCO's Surveillances have been met within their specified Frequency, except as provided by SR 3.0.3. When an LCO is not met due to Surveillances not having been met, entry into a MODE or other specified condition in the Applicability shall only be made in accordance with LCO 3.0.4.
This provision shall not prevent entry into MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.
HBRSEP Unit No. 2 3.0-5 Amendment No. 446, 203
PAM Instrumentation 3.3.3 3.3 INSTRUMENTATION 3.3.3 Post Accident Monitoring (PAM) Instrumentation LCO 3.3.3 APPLICABILITY:
The PAM instrumentation for each Function in Table 3.3.3-1 shall be OPERABLE.
MODES 1. 2. and 3.
ACTIONS NOTE-------------
Separate Condition entry is allowed for each Function.
........................................ I CONDITION REQUIRED ACTION COMPLETION TIME A. --------
NOTE--------- A.1 Restore required 30 days Not applicable to channel to OPERABLE Functions 3. 4. 19, status.
22, 23. and 24.
One or more Functions with one required channel inoperable.
B.
Required Action and B.1 Initiate action in Immediately associated Completion accordance with Time of Condition A Specification 5.6.6 not met.
(continued)
HBRSEP Unit No. 2 3.3-29 Amendment No.
46, 203
Remote Shutdown System 3.3.4 3.3 INSTRUMENTATION 3.3.4 Remote Shutdown System LCO 3.3.4 The Remote Shutdown System Functions shall be OPERABLE.
APPLICABILITY:
MODES 1. 2. and 3.
ACTIONS
NOTE-Separate Condition entry is allowed for each Function.
CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required A.1 Restore required 30 days Functions inoperable.
Function to OPERABLE status.
B. Required Action and B.1 Be in MODE 3.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time not met.
AND B.2 Be in MODE 4.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> HBRSEP Unit No. 2 3.3-33 Amendment No. P6, 203
Pressurizer PORVs 3.4.11 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.11 Pressurizer Power Operated Relief Valves (PORVs)
LCO 3.4.11 APPLICABILITY:
Each PORV and associated block valve shall be OPERABLE.
MODES 1, 2. and 3.
ACTIONS Separate Condition entry is allowed for each PORV.
I CONDITION REQUIRED ACTION COMPLETION TIME A. One or more PORVs A.1 Close and maintain 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> inoperable and capable power to associated of being manually block valve.
cycled.
B. One PORV inoperable B.1 Close associated 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and not capable of block valve.
being manually cycled. AND B.2 Remove power from 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> associated block valve.
AND B.3 Restore PORV to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> OPERABLE status.
(continued)
HBRSEP Unit No. 2 3.4-25 Amendment No. 476, 203
LTOP System 3.4.12 ACTIONS LCO 3.0.4.b is not applicable when entering MODE 4.
CONDITION REQUIRED ACTION COMPLETION TIME A. Two or more SI pumps A.1 Initiate action to Immediately capable of injecting verify a maximum of into the RCS with all one SI pump is RCS cold leg capable of injecting temperatures 2 1750F.
into the RCS.
AND Requirements of LCO 3.4.12.b not met.
B. One or more SI pumps B.1 Initiate action to Immediately capable of injecting verify no SI pumps into the RCS with any capable of injecting RCS cold leg into the RCS.
temperature < 175SF.
AND Requirements of LCO 3.4.12.b not met.
C. An accumulator C.1 Close and deenergize isolation valve not affected accumulator 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> closed and deenergized isolation valve.
when the accumulator pressure is greater than or equal to the maximum RCS pressure for existing cold leg temperature allowed in Figures 3.4.3-1 and 3.4.3-2.
(continued)
HBRSEP Unit No. 2 3.4-30 Amendment No. 4.76,203
RCS Leakage Detection Instrumentation 3.4.15 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.15 RCS Leakage Detection Instrumentation LCO 3.4.15 The following RCS leakage detection instrumentation shall be OPERABLE:
- a. One containment sump level monitor;
- b. One containment atmosphere radioactivity monitor (gaseous or particulate); and
- c. One containment fan cooler condensate flow rate monitor.
APPLICABILITY:
ACTIONS MODES 1. 2. 3. and 4.
CONDITION REQUIRED ACTION COMPLETION TIME A. Required containment A.1 Perform SR 3.4.13.1.
Once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> sump monitor inoperable.
AND A.2 Restore required 30 days containment sump monitor to OPERABLE status.
(continued)
I HBRSEP Unit No. 2 3.4-41 Amendment No. 46, 203
RCS Leakage Detection Instrumentation 3.4.15 ACTIONS (continued)
CONDITION REQUIRED ACTION COMPLETION TIME B. Required containment B.1.1 Analyze grab samples Once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> atmosphere of the containment radioactivity monitor atmosphere.
OR B.1.2 Perform SR 3.4.13.1.
Once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> AND B.2.1 Restore required 30 days containment atmosphere radioactivity monitor to OPERABLE status.
OR B.2.2 Verify required 30 days containment fan cooler condensate flow rate monitor is OPERABLE.
C. Required containment C.1 Perform SR 3.4.15.1.
Once per fan cooler condensate 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> flow rate monitor OR inoperable.
C.2 Perform SR 3.4.13.1.
Once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> (continued)
I HBRSEP Unit No. 2 3.4-42 Amendment No. a46, 203
RCS Specific Activity 3.4.16 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.16 RCS Specific Activity LCO 3.4.16 The specific activity of the reactor coolant shall be within limits.
APPLICABILITY:
MODES 1 and MODE 3 with 2,
RCS average temperature CTavg) 2 5000F.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. DOSE EQUIVALENT I-131
.........---Note-----------
> 0.25 yCi/gm.
LCO 3.0.4.c is applicable.
A.1 Verify DOSE Once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> EQUIVALENT I-131
< 60 /2Ci/gm.
AND A.2 Restore DOSE EQUIVALENT I-131 to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> within limit.
B. Gross specific activity B.1 Be in MODE 3 with 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> of the reactor coolant Tavn < 5000F.
not within limit.
(continued)
HBRSEP Unit No. 2 3.4-45 Amendment No. 244,203
ECCS-Shutdown 3.5.3 3.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) 3.5.3 ECCS-Shutdown LCO 3.5.3 APPLICABILITY:
One ECCS train shall be OPERABLE.
MODE 4.
ACTIONS
--.------------------------------- NOTE----------------...-
LCO 3.0.4.b is not applicable to the ECCS high head subsystem.
CONDITION REQUIRED ACTION COMPLETION TIME A. Required ECCS residual A.1 Initiate action to Immediately heat removal (RHR) restore required ECCS subsystem inoperable.
RHR subsystem to OPERABLE status.
B. Required ECCS high head B.1 Restore required ECCS 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> injection subsystem high head injection inoperable.
subsystem to OPERABLE status.
C. Required Action and C.1 Be in MODE 5.
24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> associated Completion Time of Condition B not met.
HBRSEP Unit No. 2 3.5-8 Amendment No. 476, 203
AFW System 3.7.4 3.7 PLANT SYSTEMS 3.7.4 Auxiliary Feedwater (AFW) System LCO 3.7.4 Four AFW flow paths and three AFW pumps shall be OPERABLE.
NOTE -- -----------
Only one AFW flow path with one motor driven pump is required to be OPERABLE in MODE 4.
APPLICABILITY:
MODES 1. 2, and 3.
MODE 4 when steam generator is being used for heat removal.
ACTIONS
NOTE------------------------------------
LCO 3.0.4.b is not applicable.
CONDITION REQUIRED ACTION COMPLETION TIME A. One AFW pump A.1 Restore AFW pump or 7 days inoperable in MODE 1.
flow path(s) to 2, or 3.
OPERABLE status.
AND OR 8 days from discovery of One or two AFW flow failure to paths inoperable in meet the LCO MODE 1, 2. or 3.
B. Two motor driven AFW B.1 Restore one motor 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> pumps inoperable in driven AFW pump or MODE 1. 2. or 3.
one flow path to AND OPERABLE status.
OR 8 days from discovery of Three motor driven AFW failure to flow paths inoperable meet the LCO in MODE 1. 2, or 3.
(continued)
HBRSEP Unit No. 2 3.7-10 Amendment No. 476, 203
AC Sources-Operating 3.8.1 3.8 ELECTRICAL POWER SYSTEMS 3.8.1 AC Sources-Operating LCO 3.8.1 The following AC electrical sources shall be OPERABLE:
- a. The qualified circuit between the offsite transmission network and the onsite emergency AC Electrical Power Distribution System; and
- b. Two diesel generators (DGs) capable of supplying the onsite emergency power distribution subsystem(s)
APPLICABILITY:
MODES 1. 2, 3. and 4.
ACTIONS NOTE------------------------------------
LCO 3.0.4.b is not applicable to DGs.
CONDITION REQUIRED ACTION COMPLETION TIME A. The qualified offsite A.1 Declare required 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> from circuit inoperable.
feature(s) with no discovery of no offsite power offsite power to available inoperable one train when its redundant concurrent with required feature(s) is inoperability of inoperable.
redundant required AND feature(s).
A.2 Restore offsite 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> circuit to OPERABLE status.
AND 8 days from discovery of failure to meet LCO (continued)
HBRSEP Unit No. 2 3.8-1 Amendment No. 476. 203