ML050390182

From kanterella
Jump to navigation Jump to search
Detroit Edison - Fermi 2 Automated Record Management Distribution Control List 01/31/05 Licensing Document Transmittal Fermi 2 Technical Requirements Manual - Vol I Revision 73 Dated 1/31/05
ML050390182
Person / Time
Site: Fermi DTE Energy icon.png
Issue date: 01/31/2005
From:
Detroit Edison
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
00935, cb1461
Download: ML050390182 (12)


Text

.

N T

I I

DETROIT EDISON -

FERMI 2 AUTOMATED RECORD MANAGEMENT DISTRIBUTION CONTROL LIST 01/31/05 To: 00935 US NRC DOCUMENT CNTRL DESK PAGE 1

WASHINGTON, DC 20555 Media: 8 1/2 X 11 Number Cnt Issue DTC Doc. Serial Number Page Rev Copies Lvi Date Sec Status TMTRM TRM VOL I 73 11 IR 01/31/05 AFC Please destroy or mark all revised, superseded, or cancelled documents as such.

CONTROLLED stamps must be voided by lining through and initialing.

Detroit Edison EF2, C/O Info Mgmt 140 NOC, 6400 North Dixie Highway, Newport MI 48166. (734) 586-4338 OR (734) 586-4061 for questions or concerns.

Ref: cbl461

LICENSING DOCUMENT TRANSMITTAL FERMI 2 TECHNICAL REQUIREMENTS MANUAL - VOL I Revision 73 dated 1/31/05 Immediately, upon receipt of the item(s) below, please insert and/or remove the pages indicated.

Destroy the removed pages. Be sure that Revision 72 has been inserted prior to inserting these pages.

Location Remove Title Page Rev 72 12/08/04 Insert In Front of TRM Manual Title Page Rev 73 1/31/05 List of Effective Pages LEP-I through LEP-4 Rev 73 1/31/05 Immediately following Title Page Table of Contents 3.7 Plant Systems 3.8 Electrical Power Systems BASES B3.7 Plant Systems List of Effective Pages LEP-M through LEP-4 Rev 72 12/08/04 Page TRM-ii Rev 70 Page TRM 3.7-a Rev 31 Page TRM 3.7-4 Rev 31 Page TRM 3.8-3 Rev 60 Page TRM B3.7.3-1 Rev 31 Page TRM-ii Rev 73 Page TRM 3.7-a Rev 73 Page TRM 3.7-4 Rev 73 Page TRM 3.8-3 Rev 73 Page TRM B3.7.3-1 Rev 73 END

fermi 2 Technical Requirements

  • Manual Volume I Detroit Edison ARMS - INFORMATION DTC: TMTRM l File: 1754 I DSN: TRM VOL I l Rev: 73 Date 1/31/05 Recipient

FERMI 2 -

TECHNICAL REQUIREMENTS MANUAL VOL I LIST OF EFFECTIVE PAGES Page Page Revision Revision TRM i TRM ii TRM iii TRM iv TRM v TRM vi TRM 1.0-a TRM 1.0-1 TRM 2.0-1 TRM 3.0-a TRM 3.0-1 TRM 3.0-2 TRM 3.0-3 TRM 3.0-4 TRM 3.1-a TRM 3.1-1 TRM 3.2-1 TRM 3.3-a TRM 3.3-b TRM 3.3-c TRM 3.3-d TRM 3.3-1 TRM 3.3-2 TRM 3.3-3 TRM 3.3-4 TRM 3.3-5 TRM 3.3-6 TRM 3.3-7 TRM 3.3-8 TRM 3.3-9 TRM 3.3-10 TRM 3.3-11 TRM 3.3-12.

TRM 3.3-13 TRM 3.3-13a TRM 3.3-14 TRM 3.3-15 TRM 3.3-16 TRM 3.3-17 TRM 3.3-18 TRM 3.3-19 TRM 3.3-20 TRM 3.3-21 TRM 3.3-22 TRM 3.3-23 TRM 3.3-24 TRM 3.3-25 TRM 3.3-26 TRM 3.3-27 TRM 3.3-28 TRM 3.3-29 TRM 3.3-30 Revision 31 Revision 73 Revision 31 Revision 34 Revision 70 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 63 Revision 72 Revision 54 Revision 72 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 34 Revision 59 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 67 Revision 67 Revision 67 Revision 67 Revision 31 Revision 31 Revision 31

.Revision 52 Revision 31 Revision 31 Revision 59 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 TRM 3.3-31 TRM 3.3-32 TRM 3.3-33 TRM 3.3-34 TRM 3.3-35 TRM 3.3-36 TRM 3.3-37 TRM 3.3-38 TRM 3.3-39 TRM 3.3-40 TRM 3.3-41 TRM 3.3-42 TRM 3.3-43 TRM 3.3-44 TRM 3.3-45 TRM 3.3-46 TRM 3.3-47 TRM 3.3-48 TRM 3.3-49 TRM 3.4-a TRM 3.4-1 TRM 3.4-la TRM 3.4-lb TRM 3.4-2 TRM 3.4-3 TRM 3.4-4 TRM 3.4-5 TRM 3.4-6 TRM 3.4-7 TRM 3.4-8 TRM 3.4-9 TRM 3.4-10 TRM 3.5-1 TRM 3.6-a TRM 3.6-1 TRM 3.6-2 TRM 3.6-3 TRM 3.6-4 TRM 3.6-5 TRM 3.6-6 TRM 3.6-.7 TRM 3.6-8 TRM 3.6-9 TRM 3.6-10 TRM 3.6-11 TRM 3.6-12 TRM 3.6-13 TRM 3.6-14 TRM 3.6-15 TRM 3.6-16 TRM 3.6-17 TRM 3.6-18 Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision Revision 31 31 31 31 60 41 72 31 31 56 56 45 62 72 31 31 31 31 31 31 36 71 71 31 31 31 31 31 31 31 31 31 31 70 60 67 31 55 31 33 31 31 66 31 31 31 71 31 31 31 31 31 TRM Vol. I LEP-1 REV 73 1/31/05

FERMI 2 -

TECHNICAL REQUIREMENTS MANUAL VOL I LIST OF EFFECTIVE PAGES Page Page Revision Revision TRM 3.6-19 TRM 3.6-20 TRM 3.6-21 TRM 3.6-22 TRM 3.6-23 TRM 3.6-24 TRM 3.6-25 TRM 3.6-26 TRM 3.6-27 TRM 3.6-28 TRM 3.6-29 TRM 3.6-30 TRM 3.6-31 TRM 3.6-32 TRM 3.6-33 TRM 3.6-34 TRM 3.6-35 TRM 3.7-a TRM 3.7-b TRM 3.7-1 TRM 3.7-2 TRM 3.7-3 TRM 3.7-4 TRM 3.7-5 TRM 3.7-6 TRM 3.7-7 TRM 3.7-8 TRM 3.7-9 TRM 3.7-10 TRM 3.7-11 TRM 3.7-12 TRM 3.7-13 TRM 3.7-14 TRM 3.7-15 TRM 3.7-16 TRM 3.7-17 TRM 3.7-18 TRM 3.7-19 TRM 3.7-20 TRM 3.8-a TRM 3.8-1 TRM 3.8-2 TRM 3.8-3 TRM.3.8-4 TRM 3.8-5 TRM 3.8-6 TRM 3.8-7 TRM 3.8-8 TRM 3.8-9 TRM 3.8-10 TRM 3.8-11 TRM 3.8-12 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 58 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 70 Revision 31 Revision 31 Revision 31 Revision 73 Revision 31 Revision 60 Revision 70 Revision 70 Revision 73 Revision 31 Revision 31 Revisibn 31 Revision 31 Revision 31 Revision 44 Revision 31 Revision 72 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 73 Revision 31 Revision 31 Revision 50 Revision 50 Revision 50 Revision 50 Revision 50 Revision 50 Revision 31 TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM TRM 3.8-13 3.8-14 3.8-15 3.8-16 3.8-17 3.8-18 3.9-a 3.9-1 3.9-2 3.9-3 3.9-4 3.9-5 3.10-1 3.11-a 3.11-1 3.12-a 3.12-1 3.12-2 3.12-3 3.12-4 3.12-5 3.12-6 3.12-7 3.12-8 3.12-9 3.12-10 3.12-11 3.12-12 3.12-13 3.12-14 3.12-15 3.12-16 3.12-17 3.12-18 3.12-19 3.12-20 3.12-21 3.12-22 3.12-23 3.12-24 3.12-25 3.12-26 3.12-27 3.12-28 3.12-29 3.12-30 4.0-1 5.0-a 5.0-1 5.0-2 5.0-3 5.0-4 Revision 61 Revision 46 Revision 31 Revision 31 Revision 43 Revision 33 Revision 31 Revision 31 Revision 65 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 53 Revision 53 Revision 53 Revision 31 Revision 57 Revision 40 Revision 31 Revision 49 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 TRM Vol. I LEP-2 REV 73 1/31/05

FERMI 2 - TECHNICAL REQUIREMENTS MANUAL VOL I LIST OF EFFECTIVE PAGES Page Page Revision Revision TRM 5.0-5 TRM 5.0-6 TRM 5.0-7 TRM 5.0-8 TRM 5.0-9 TRM B1.0-1 TRM B2.0-1 TRM B3.0-1 TRM B3.0-2 TRM B3.0-2a TRM B3.0-2b TRM B3.0-2c TRM B3.0-3 TRM B3.0-4 TRM B3.0-5 TRM B3.0-6 TRM B3.0-7 TRM B3.1-1 TRM B3.2-1 TRM B3.3.1-1 TRM B3.3.1-2 TRM B3.3.2-1 TRM B3.3.2-2 TRM B3.3.3-1 TRM B3.3.4-1 TRM B3.3.4-2 TRM B3.3.5-1 TRM B3.3.5-2 TRM B3.3.6-1 TRM B3.3.6-2 TRM B3.3.6-3 TRM B3.3.6-4 TRM B3.3.6-5 TRM B3.3.7-1 TRM B3.3.7-2 TRM B3.3.8-1 TRM B3.3.9-1 TRM B3.3.10-1 TRM B3.3.11-1 TRM B3.3.12-1 TRM B3.3.13-1 TRM B3.3.14-1 TRM B3.4.1-1 TRM B3.4.1-2 TRM B3.4.1-3 TRM B3.4.1-4 TRM B3.4.1-5 TRM B3.4.2-1 TRM B3.4.3-1 TRM B3.4.4-1 TRM B3.4.5-1 TRM B3.4.6-1 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 63 Revision 63 Revision 72 Revision 72 Revision 72 Revision 31 Revision 31 Revision 54 Revision 72 Revision 72 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 67 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 56 Revision 45 Revision 62 Revision 31 Revision 31 Revision 31 Revision 71 Revision 71 Revision 71 Revision 71 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 TRM B3.4.7-1 TRM B3.5-1 TRM B3.6.1-1 TRM B3.6.2-1 TRM B3.6.3-1 TRM B3.6.4-1 TRM B3.6.5-1 TRM B3.6.6-1 TRM. B3.6.7-1 TRMEB3.6.8-1 TRM B3.7.1-1 TRM B3.7.2-1 TRM B3.7.3-1 TRE B3.7.4-1 TRM B3.7.4-2 TRM B3.7.5-1 TRM B3.7.6-1 TRM B3.7.7-1 TRM B3.7.8-1 TRM B3.7.9-1 TRM B3.7.9-2 TRM B3.8.1-1 TRM B3.8.2-1 TRM B3.8.3-1 TRM B3.8.4-1 TRM B3.8.5-1 TRM B3.8.6-1 TRM B3.9.1-1 TRM B3.9.2-1 TRM B3.9.3-1 TRM B3.9.4-1 TRM B3.10-1 TRM B3.11.1-1 TRM B3.12.1-1 TRM B3.12.2-1 TRM B3.12.3-1 TRM B3.12.4-1 TRM B3.12.5-1 TRM B3.12.6-1 TRM B3.12.7-1 TRM B3.12.8-1 Revision 31 Revision 31 Revision 31 Revision 67 Revision 68 Revision 31 Revision 31 Revision 70 Revision 31 Revision 31 Revision 31 Revision 31 Revision 73 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 43 Revision 31 Revision 65 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 44 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 Revision 31 TRM Vol. I LEP-3 REV 73 1/31/05

FERMI 2 -

TECHNICAL REQUIREMENTS MANUAL VOL I LIST OF EFFECTIVE PAGES CORE OPERATING LIMITS REPORT COLR 11, Revision 0 Page Revision Notation Page 1

2 3

4 5

6 7

8 9

10 11 12 13 14 15 16 17

-18 19

  • 20 21 22 0

0 0

0 0

0

-0 0

0 0

.0 0

0 0

0 0

0 0

0 0

0 TRM Vol. I LEP-4 REV 73 1/31/05

FERMI 2 -

TECHNICAL REQUIREMENTS MANUAL VOL I Table of Contents (Cont'd)

Section and Title Page TR 3.4.2 TR 3.4.3 TR 3.4.4 TR 3.4.5 TR 3.4.6 TR 3.4.7 TR 3.5 TR 3.6 TR 3.6.1 TR 3.6.2 TR 3.6.3 TR 3.6.4 TR 3.6.5 TR 3.6.6 TR 3.6.7 TR 3.6.8 Safety Relief Valve (SRV) Position Indication....

Reactor Coolant System (RCS) Leakage Detection System...........................................

Reactor Pressure Vessel-Water Level -

Cold Shutdown.........................................

Chemistry........................................

Structural Integrity..............................

Recirculation Pump MG Set Scoop Tube.............

EMERGENCY CORE COOLING SYSTEMS (ECCS) AND REACTOR CORE ISOLATION COOLANT (RCIC) SYSTEM (Blank).............

CONTAINMENT SYSTEMS Suppression Chamber..............................

Primary Containment Hydrogen Recombiners (Blank).

Primary Containment Isolation Valves (PCIVs).....

Reactor Building-to-Suppression Chamber Vacuum Breaker Position Indication......................

Suppression Chamber-to-Drywell Vacuum Breaker Position Indication..............................

Main Steam Isolation Valve (MSIV) Leakage Control System (LCS)

(Blank)...............

Secondary Containment Isolation Valves (SCIVs)...

Drywell Spray..................................

PLANT SYSTEMS Ultimate Heat Sink (UHS) Minimum Temperature.....

Control Room Emergency Filtration (CREF) System..

(Blank)

Shore Barrier Protection..........................

Sealed Source Contamination......................

Main Turbine Bypass System.......................

Appendix R Alternative Shutdown Auxiliary Systems (Blank)........................................

Snubbers.........................................

ELECTRICAL POWER SYSTEMS AC Circuits Inside Primary Containment...........

(Blank)..........................................

AC Sources......................................

Electrical Equipment Protective Devices Motor-Operated Valves Thermal Overload Protection Primary Containment Penetration Conductor Overcurrent Protection Devices...................

Standby Liquid Control (SLC) System Associated Isolation Devices................................

TRM 3.4-2 TRM 3.4-3 TRM 3.4-4 TRM 3.4-5 TRM 3.4-9 TRM 3.4-10 TRM 3.5-1 TRM 3.6-1 TRM 3.6-2 TRM 3.6-3 TRM 3.6-27 TRM 3.6-29 TRM 3.6-32 TRM 3.6-33 TRM 3.6-34 TRM 3.7-1 TRM 3.7-2 TRM 3.7-4 TRM 3.7-5 TRM 3.7-9 TRM 3.7-11 TRM 3.7-12 TRM 3.7-19 TRM 3.7-20 TRM 3.8-1 TRM 3.8-2 TRM 3.8-3 TR 3.7 TR 3.7.1 TR 3.7.2 TR 3.7.3 TR 3.7.4 TR 3.7.5 TR -3.7.6 TR 3.7.7 TR 3.7.8 TR 3.7.9 TR 3.8 TR 3.8.1 TR 3.8.2 TR 3.8.3 TR 3.8.4 TR 3.8.5 TR 3.8.6 TRM 3.8-5 TRM 3.8-12 TRM 3.8-16 (continued)

TRM VOL I TRM-ii REV 73 01/05

SECTION 3.7 DETAILED INDEX OF SECTION Page TR 3.7.1 Ultimate Heat Sink (UHS) Minimum Temperature......

TRM 3.7-1 (TRLCO, ACTION, TRSR)

TR 3.7.2 Control Room Emergency Filtration (CREF) System...

(Tables TR3.7.2-1 and TR 3.7.2-2)

TRM 3.7-2 Table TR3.7.2-1 Table TR3.7.2-2 CREF System Duct Work.............................

(Technical Specification 3.7.3, specifically SR 3.7.3.3, duct work)

CREF System Duct Work Leak Testing Requirements...

(Technical Specification 3.7.3, specifically SR 3.7.3.6, duct work and associated leak testing requirements)

TRM 3.7-2 TRM 3.7-3 TR 3.7.3 TR 3.7.4 Control Center Air Temperature....................

(TRLOC, ACTION) (Intentionally Left Blank)

Shore Barrier Protection..........................

(TRLCO, ACTION, TRSR)

TRM 3.7-4 TRM 3.7-5 Table TR3.7.4-1 TR 3.7.5 TR 3.7.6 Table TR3.7.6-1 Shore Barrier Survey Points

.................... TRM 3.7-7 (TR 3.7.4 applicability)

Sealed Source Contamination...

.................... TRM 3.7-9 (TRLCO, ACTION, TRSR)

Main Turbine Bypass System...

...................... TRM 3.7-11 (Table TR3.7.6-1 only)

Main Turbine Bypass System........................ TRM 3.3-11 (Technical Specification 3.7.6 response time)

TR 3.7.7 Appendix R Alternative Shutdown Auxiliary Systems.

.......................................... TRM 3.7-12 (TRLCO, ACTION, TRSR)

Appendix R Alternative Shutdown Control Circuits.. TRM 3.7-15 (TR 3.7.7 applicability)

Table TR3.7.7-1 (continued)

TRM Vol. I ITRM 3.7-a REV 73 01/05

TR 3.7 Control Center Air Temperature TR 3.7.3 PLANT SYSTEMS THIS PAGE INTENTIONALLY LEFT BLANK TRM Vol.

I TRM 3.7-4 Rev 73 01/05

AC Sources TR 3.8.3 TR 3.8 ELECTRICAL POWER SYSTEMS TR 3.8.3 AC Sources TRLCO 3.8.3 APPLICABILITY:

Emergency Diesel Generator (EDG) surveillance requirements TRSR 3.8.3.1, 3.8.3.2, 3.8.3.3, and 3.8.3.4 shall be met.

MODES 1, 2, 3, 4, and 5, During movement of recently irradiated fuel assemblies in the secondary containment.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

TRSR 3.8.3.1 not met.

A.1 Perform OPERABILITY Immediately assessment on the OR affected EDG(s).

TRSR 3.8.3.2 not met.

OR TRSR 3.8.3.3 not met.

OR TRSR 3.8.3.4 not met.

TRM Vol. I TRM 3.8-3 REV 73 01/05