Request for Additional Information (RAI) Regarding Request for Change to Technical Specifications Emergency Diesel Generator Surveillance Testing Requirements
ML041190204
Person / Time
Site: Hope Creek PSEG icon.png
Issue date: 05/07/2004
From: Dan Collins
NRC/NRR/DLPM/LPD1
To: Richard Anderson
Public Service Enterprise Group
Collins D S, NRR/DLPM, 415-1427
References
TAC MC1224
Download: ML041190204 (4)


Text

May 7, 2004 Mr. Roy A. Anderson President & Chief Nuclear Officer PSEG Nuclear, LLC - X04 Post Office Box 236 Hancocks Bridge, NJ 08038

SUBJECT:

HOPE CREEK GENERATING STATION, REQUEST FOR ADDITIONAL INFORMATION REGARDING REQUEST FOR CHANGE TO TECHNICAL SPECIFICATIONS EMERGENCY DIESEL GENERATOR SURVEILLANCE TESTING REQUIREMENTS (TAC NO. MC1224)

Dear Mr. Anderson:

By letter dated October 23, 2003, PSEG Nuclear LLC submitted a license amendment request, LCR H03-07, for the Hope Creek Generating Station (Hope Creek) seeking approval of proposed changes to the Hope Creek Technical Specifications. Specifically, the requested change would delete surveillance requirements associated with the emergency diesel generator lockout features.

The Nuclear Regulatory Commission staff has been reviewing your submittal and has determined that additional information is required to complete our review. The required information was discussed with Mr. Courtney Smyth of your staff on April 8, 2004. Please provide your response to the enclosed question within 30 days of receipt of this letter. If circumstances result in the need to revise the target date, please contact me at (301) 415-1427.

Sincerely,

/RA/

Daniel S. Collins, Project Manager, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-354

Enclosure:

As stated cc w/encl: See next page

ML041190204

  • see previous concurrence NRR-088 OFFICE PDI-2/PM PDI-2/LA EEIB/SC*

PDI-2/SC NAME DCollins CRaynor RJenkins JClifford DATE 5/7/04 5/7/07 5/03/2004 5/7/04

Hope Creek Generating Station cc:

Mr. A. Christopher Bakken, III Senior Vice President - Site Operations PSEG Nuclear - X15 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. John T. Carlin Vice President - Nuclear Assessment PSEG Nuclear - N10 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. David F. Garchow Vice President - Eng/Tech Support PSEG Nuclear - N28 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. James A. Hutton Plant Manager PSEG Nuclear - X15 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Steven Mannon Acting Manager - Nuclear Safety and Licensing PSEG Nuclear - N21 P.O. Box 236 Hancocks Bridge, NJ 08038 Jeffrie J. Keenan, Esquire PSEG Nuclear - N21 P.O. Box 236 Hancocks Bridge, NJ 08038 Ms. R. A. Kankus Joint Owner Affairs Exelon Generation Company, LLC Nuclear Group Headquarters KSA1-E 200 Exelon Way Kennett Square, PA 19348 Lower Alloways Creek Township c/o Mary O. Henderson, Clerk Municipal Building, P.O. Box 157 Hancocks Bridge, NJ 08038 Dr. Jill Lipoti, Asst. Director Radiation Protection Programs NJ Department of Environmental Protection and Energy CN 415 Trenton, NJ 08625-0415 Brian Beam Board of Public Utilities 2 Gateway Center, Tenth Floor Newark, NJ 07102 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Senior Resident Inspector Hope Creek Generating Station U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, NJ 08038

REQUEST FOR ADDITIONAL INFORMATION REGARDING AMENDMENT REQUEST TO DELETE EMERGENCY DIESEL GENERATOR SURVEILLANCE REQUIREMENTS HOPE CREEK GENERATING STATION DOCKET NO. 50-354 By letter dated October 23, 2003, PSEG Nuclear LLC submitted a license amendment request, LCR H03-07, for the Hope Creek Generating Station (Hope Creek) seeking approval of proposed changes to the Hope Creek Technical Specifications (TSs). Specifically, the requested change would delete surveillance requirements (SRs) associated with the emergency diesel generator lockout features. The Nuclear Regulatory Commission staff has been reviewing your submittal and has determined that the following additional information is required to complete our review:

1.

Title 10 of the Code of Federal Regulations (10 CFR), Section 50.36(b) requires that the TSs be derived from the analyses and evaluation included in the safety analysis report (SAR). Additional requirements for the contents of TSs are contained in 10 CFR 50.36(c)(2).

Hope Creeks Updated Final Safety Analysis Report (UFSAR) Section 8.3.1.1.3.3, "SDG

[Standby Diesel Generator] Tripping" indicates that when a Class 1E bus is energized only by the SDG (during loss of offsite power and/or loss-of-coolant-accident), each diesel engine and the circuit breaker that connects the diesel engine generator to the 4.16 KV Class 1E bus are tripped and locked out by protective devices under the following conditions:

1. Operation of SDG differential relay
2. Operation of the bus differential relay for the bus to which the SDG is connected
3. Engine overspeed
4. Low lube oil pressure
5. SDG overcurrent This section of the UFSAR indicates that these SDG lockout features were evaluated in the SAR to assure the availability of the SDG when needed pursuant with the requirements of general design criteria (GDC) 17. Pursuant with 10 CFR 50.36, the Hope Creek TS SR 4.8.1.1.2.h.14 requires verification that these trip and lockout features prevent diesel generator starting only when required. The proposed TS change deletes SR 4.8.1.1.2.h.14.

Provide a detailed explanation of how Hope Creek would continue to meet the requirements of GDC 17 and 10 CFR 50.36 following the proposed TS changes.