August 5, 2004 Mr. A. Christopher Bakken, III President & Chief Nuclear Officer PSEG Nuclear - X15 P.O. Box 236 Hancocks Bridge, NJ 08038

SUBJECT:

HOPE CREEK GENERATING STATION, CORRECTION TO REQUEST FOR ADDITIONAL INFORMATION (TAC NO. MC1224)

Dear Mr. Bakken:

By letter dated October 23, 2003, PSEG Nuclear, LLC submitted license amendment request LCR H03-07 for the Hope Creek Generating Station (Hope Creek) seeking approval of proposed changes to the Hope Creek Technical Specifications. Specifically, the requested change would delete surveillance requirements associated with the emergency diesel generator lockout features.

By letter dated June 24, 2004, you responded to the Nuclear Regulatory Commission staffs May 7, 2004, request for additional information (RAI). By letter dated August 2, 2004, the staff communicated further information needs in a second RAI. Subsequent to this letter, an error was identified in question number one. The second to last sentence of question one of the August 2, 2004, letter should read as follows:

The PSEG submittal does not indicate where the surveillance requirements currently in TS 8.8.1.1.2.h.14 will be relocated to.

If you have any questions, please contact me at (301) 415-2481.

Sincerely,

/RA/

Daniel S. Collins, Sr. Project Manager, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-354 cc: See next page

Mr. A. Christopher Bakken, III August 5, 2004 President & Chief Nuclear Officer PSEG Nuclear - X15 P.O. Box 236 Hancocks Bridge, NJ 08038

SUBJECT:

HOPE CREEK GENERATING STATION, CORRECTION TO REQUEST FOR ADDITIONAL INFORMATION (TAC NO. MC1224)

Dear Mr. Bakken:

By letter dated October 23, 2003, PSEG Nuclear, LLC submitted license amendment request LCR H03-07 for the Hope Creek Generating Station (Hope Creek) seeking approval of proposed changes to the Hope Creek Technical Specifications. Specifically, the requested change would delete surveillance requirements associated with the emergency diesel generator lockout features.

By letter dated June 24, 2004, you responded to the Nuclear Regulatory Commission staffs May 7, 2004, request for additional information (RAI). By letter dated August 2, 2004, the staff communicated further information needs in a second RAI. Subsequent to this letter, an error was identified in question number one. The second to last sentence of question one of the August 2, 2004, letter should read as follows:

The PSEG submittal does not indicate where the surveillance requirements currently in TS 8.8.1.1.2.h.14 will be relocated to.

If you have any questions, please contact me at (301) 415-2481.

Sincerely,

/RA/

Daniel S. Collins, Sr. Project Manager, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-354

Enclosure:

As stated cc w/encl: See next page DISTRIBUTION PUBLIC JClifford ECoby, RGN-I ACRS DCollins GMiller OGC PDI-2 Reading CBixler, RGN-I ADAMS Accession Number: ML042180290 OFFICE PDI-2/PE PDI-2/PM PDI-2/SC NAME GMiller DCollins JClifford DATE 8/3/04 8/4/04 8/5/04 OFFICIAL RECORD COPY

Hope Creek Generating Station cc:

Mr. John T. Carlin Vice President - Nuclear Assessment PSEG Nuclear - N10 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. David F. Garchow Vice President - Engineering/Technical Support PSEG Nuclear - N28 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Michael Brothers Vice President - Site Operations PSEG Nuclear - N10 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. James A. Hutton Plant Manager PSEG Nuclear - X15 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Steven Mannon Acting Manager - Nuclear Safety and Licensing PSEG Nuclear - N21 P.O. Box 236 Hancocks Bridge, NJ 08038 Jeffrie J. Keenan, Esquire PSEG Nuclear - N21 P.O. Box 236 Hancocks Bridge, NJ 08038 Ms. R. A. Kankus Joint Owner Affairs Exelon Generation Company, LLC Nuclear Group Headquarters KSA1-E 200 Exelon Way Kennett Square, PA 19348 Lower Alloways Creek Township c/o Mary O. Henderson, Clerk Municipal Building, P.O. Box 157 Hancocks Bridge, NJ 08038 Dr. Jill Lipoti, Asst. Director Radiation Protection Programs NJ Department of Environmental Protection and Energy CN 415 Trenton, NJ 08625-0415 Brian Beam Board of Public Utilities 2 Gateway Center, Tenth Floor Newark, NJ 07102 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Senior Resident Inspector Hope Creek Generating Station U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, NJ 08038