SOUTHERN CALIFORNIA
-- EDISON An EDISON INTERNA77ONAL Company Dwight E. Nunn Vice President March 17, 2004 U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555
Subject:
Docket No. 50-361 Special Report: Inservice Inspection of Steam Generator Tubes, Cycle 13 San Onofre Nuclear Generating Station, Unit 2
Reference:
Steam Generator Program Guidelines, Nuclear Energy Institute, Document Number NEI 97-06, Revision 1 Gentlemen:
On March 3, 2004, Southern California Edison (SCE) completed the inservice inspection of steam generator tubes at San Onofre Nuclear Generating Station Unit 2. The attached report is submitted in accordance with Technical Specification (TS) 5.7.2.c reporting requirements:
Report the number of tubes plugged and tubes sleeved in each steam generator within 15 days of completing the inspection; Report the complete results of steam generator tube inspections within 12 months of inspection completion; Report the results of steam generator tube inspections which fall into Category C-3 prior to resumption of plant operation.
The attachment to this letter, "Special Report - Inservice Inspection of Steam Generator Tubes,"
which was prepared in accordance with the referenced industry guidance, satisfies these reporting requirements. The report contains no new commitments.
Independent from the TS 5.7.2.c reporting requirements, this report also incorporates results of a secondary side inspection of eggcrate tube supports using remote video equipment.
If you require any additional information, please advise.
Si Attachments:
cc:
B. S. Mallett, Regional Administrator, NRC Region IV B. M. Pham, NRC Project Manager, San Onofre Units 2 & 3 C. C. Osterholtz, NRC Senior Resident Inspector, San Onofre Units 2 & 3 Institute of Nuclear Power Operations (INPO)
P.O. Box 128 San Clemente. CA 92674-0128 949-368-1480 Fax 949-368-1490 U
Inservice Inspection of Steam Generator Tubes Special Report Attachment Page 1 of 23 SPECIAL REPORT - INSERVICE INSPECTION OF STEAM GENERATOR TUBES Regulatory Reporting Requirements Reporting Requirement 5.7.2.c of Appendix A, Technical Specifications to Facility Operating License NPF-1 0, requires the number of tubes plugged and tubes sleeved in each steam generator to be reported to the Nuclear Regulatory Commission within 15 days following completion of the inspection.
Reporting Requirement 5.7.2.c of Appendix A, Technical Specifications to Facility Operating License NPF-10, requires the results of steam generator tube inspections which fall into Category C-3 to be reported to the Nuclear Regulatory Commission prior to resumption of plant operation.
Reporting Requirement 5.7.2.c of Appendix A, Technical Specifications to Facility Operating License NPF-1 0, requires the complete results of steam generator tube inspections to be reported to the Nuclear Regulatory Commission within 12 months following completion of the inspection.
Planned Inspection Scope Table 1 summarizes the planned inspection program. Also, when indications by the bobbin probe were non-quantifiable or distorted, the inspection program included inspection with the Plus-Point Probe.
Table 2 provides the list of Nondestructive Examination (NDE) techniques utilized for each degradation mechanism.
Inspection Scope Expansion There were no significant inspection program scope expansions in response to inspection results.
Results of the Inservice Inspection of Tubes This report satisfies the listed regulatory reporting requirements.
The contents of this report were prepared using the guidance contained in NEI 97-06, Rev. 1, 'Steam Generator Program Guidelines." The NEI guidance is an initiative to unify the industry approach towards steam generator issues and strengthen, where necessary, the steam generator program.
Table 3 summarizes the number of tubes repaired and active degradation mechanisms found. Each tube is only counted once in this listing, although it may also have an eddy current indication of a type below the point in the listing where it appears. The Appendices provide the complete results of the steam generator tubing inservice inspection.
Ten inservice sleeves were found with a reduced inside diameter. In response, SCE took the following actions:
- These ten tubes have been removed from service by plugging both ends of the tubes.
SCE Nuclear Fuel Management has implemented a conservative assumption in the safety analyses that each inservice sleeve may pose the potential for reactor coolant flow blockage, similar to that of a tube that is removed from service by plugging.
Inservice Inspection of Steam Generator Tubes Special Report Attachment Page 2 of 23 Evaluation of the reduced diameter of these inservice sleeves has not identified a cause. Measures to prevent recurrence include installation process enhancements related to the parent tubing at the location where the lower roll joint of the sleeve is to be performed. These enhancements include:
Visual examination after the process surface cleaning of the parent tube at this location.
Eddy current examination with a rotating Plus-Point coil probe of the parent tube at this location.
Table 4 summarizes results of in-situ pressure and leak testing conducted in accordance with EPRI guidelines. These results demonstrate the structural and leakage (i.e., there was no leakage) integrity of the tested tubes. Eddy current testing results and in-situ pressure and leak testing results (Condition Monitoring) provide assurance that performance criteria in the NEI guidance (structural integrity and accident-induced leakage) were met during operation prior to this inspection.
Results of the Secondary Side Inspection (SSI) of Eggcrate Tube Supports Visual inspections of the steam generator lattice supports for both steam generators at SONGS Unit 2 were completed using remote video equipment. The Unit 2 Cycle 13 inspection encompassed fifteen camera drops on each of the two steam generators. These inspections were conducted from the fifth to the tenth or uppermost lattice support structure.
The results indicate no evidence of ongoing Flow Accelerated Corrosion (FAC). These results are similar to the last lattice inspection on Unit 2 conducted in the Cycle 10 refueling outage. Using the conservative plugging criteria developed from the initial FAC discovery, no tubes were plugged.
Repair of Tubes Table 5 provides an itemized listing of the tubes plugged in steam generator E-088 along with the corresponding Table 3 category specifying the indication orientation/location.
Table 6 provides an itemized listing of the tubes sleeved in steam generator E-088 along with the corresponding Table 3 category specifying the indication orientation/location.
Table 7 provides an itemized listing of tubes plugged in steam generator E-089 along with the corresponding Table 3 category specifying the indication orientation/location.
Table 8 provides an itemized listing of the tubes sleeved in steam generator E-089 along with the corresponding Table 3 category specifying the indication orientation/location.
Repair Methods, Number of Tubes Repaired and Effective Plugging Percentage All tube plugging was performed using the design, materials, and installation methods of AREVA (formerly FRAMATOME-ANP or FANP). A "roll" method was used for all tube plugs. Five tubes were
.stabilized" in the vicinity of the top of the tubesheet using the design, materials, and installation methods of AREVA.
All tube sleeving was performed using the welded sleeve design, materials, and installation methods of Westinghouse (formerly ABB Combustion Engineering). This repair method is approved for use in Technical Specification 5.5.2.11.f.1.j for Unit 2.
Inservice Inspection of Steam Generator Tubes Special Report Attachment Page 3 of 23 One hundred sixty-six (166) tubes were plugged and one hundred thirteen (113) tubes were sleeved in Steam Generator E-088 during the Unit 2 Cycle 13 refueling outage. To date, a total of nine hundred thirty-nine (939) tubes have been plugged and three hundred forty-five (345) sleeved tubes are in service. The design number of tubes is 9350 tubes and the sleeve to plug equivalency ratio is thirty-eight sleeves per plug. The effective plugging percentage for E-088 is 10.2%.
One hundred forty-three tubes (143) were plugged and fifty-one (51) tubes were sleeved in Steam Generator E-089 during the Unit 2 Cycle 13 refueling outage. To date, a total of nine hundred sixty (960) tubes have been plugged and one hundred eighty-nine (189) sleeved tubes are in service. The design number of tubes is 9350 tubes and the sleeve to plug equivalency ratio is thirty-eight sleeves per plug. The effective plugging percentage for E-089 is 10.4%.
Causes and Corrective Actions The degradation detected during this inspection remained within the Technical Specification Category C-3. There is no significant update from previous reports of causes and corrective actions for Category C-3 results. The following actions were taken to improve the secondary side chemistry environment for steam generator tubing in both Unit 2 steam generators:
- 1. Chemical cleaning of the entire tube bundle (full bundle) performed during the Cycle 9 refueling outage in December, 1996.
- 2. Use of titanium dioxide, an IGA/SCC inhibitor, began immediately following the completion of the Cycle 9 refueling outage in April 1997 for maximum crevice penetration potential. This treatment is ongoing.
- 3. Use of Ethanolamine (ETA) for pH control of the secondary fluids began in July 1997. This treatment is ongoing.
- 4. Use of Boric Acid addition in the secondary side began in February 1998 to help reduce denting of the tube supports and stress corrosion cracking of tubing. This treatment is ongoing.
In addition, SCE reduced the reactor coolant temperature at the steam generator inlet (T-hot) by about 11 "F. SCE expects this will reduce stress corrosion cracking of the tubing initiating from the inside diameter of the tubing. An initial temperature reduction of about 40F was completed in January 1998.
Subsequently, plant modifications were effected to yield an additional reduction of 70F.
Inservice Inspection of Steam Generator Tubes Attachment Description of Tables and Appendices Special Report Page 4 of 23 Table 1 -
Table 2 -
Table 3-Table 4 -
Table 5 -
Table 6 -
Table 7 -
Table 8 -
Appendix 1 -
Appendix 2 -
Appendix 3 -
Appendix 4 -
Summary of the Planned Inspection Program for the Unit 2 Cycle 13 (U2C13) Refueling Outage List of Nondestructive Examination (NDE) Techniques Utilized for Each Degradation Mechanism for the U2C1 3 Refueling Outage Number of Tubes Repaired and Active Degradation Mechanisms Found During the U2C13 Refueling Outage Summary of Results of In-Situ Pressure and Leak Testing for the U2C1 3 Refueling Outage U2C1 3 Refueling Outage Tubes Plugged, Steam Generator E-088 U2C1 3 Refueling Outage Tubes Sleeved, Steam Generator E-088 U2C1 3 Refueling Outage Tubes Plugged, Steam Generator E-089 U2C1 3 Refueling Outage Tubes Sleeved, Steam Generator E-089 Steam Generator Reference Information Legend for Appendices 3 and 4 Inspection Summary, Steam Generator E-088 Inspection Summary, Steam Generator E-089
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 5 of 23 TABLE I - Summary of the Planned Inspection Program for the Unit 2 Cycle 13 (U2C13) Refueling Outage Number of Tubes/Percentage of Tubes Steam Generator E-088 E-089 Full length of tube with the bobbin probe (excluding sleeved 8577 / 100%
8533 / 100%
regions and U-bends for Rows 1-3)
Hot leg expansion transition at the top-of-tubesheet with the 8577 1 100%
8533 / 100%
Plus-Point Probe (to 16 inches below the expansion transition)
Cold leg expansion transition at the top-of-tubesheet with 2670 /31%
2640 / 30%
the Plus-Point Probe U-bend regions of Rows 1, 2, and 3 with both mid and high 181 / 100%
174 I100%
frequency Plus-Point Probes U-bend regions of Rows 4 through 10 at the U-bend with 428 / 100%
432 / 100%
the mid frequency Plus-Point Probe Plus-Point Probe examinations of Hot leg scallop bar 81 / 20%
81 / 20%
supports with the above adjacent hot leg square bend and the below one support elevation of tubing freespan Plus-Point Probe examinations of tube support 2676 / 100%
1858 / 100%
intersections with dents greater than, or equal to, 2 volts Plus-Point Probe examination of dings greater than, or 349 / 100%
325 /100%
equal to, 4 volts Plus-Point Probe examination of all tube support 573 /100%
661 /100%
intersections with quantified wear indications by the bobbin probe Full length of sleeves with the Plus-Point Probe 252/ 100%
1461 100%
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 6 of 23 TABLE 2 - List of Nondestructive Examination (NDE) Techniques Utilized for Each Degradation Mechanism for the U2C13 Refueling Outage Probe Type for I
Characterization Indication OrientationlLocation Detectiot Axially oriented ID (initiated on the inside-diameter of Bobbin Plus-Point the tubing wall) indications at tube support locations Plus-Point Plus-Point (Note 1)
Axially oriented OD (initiated on the outside-diameter Bobbin Plus-Point of the tubing wall) indications at tube support locations Plus-Point Plus-Point (Note 1)
Axially oriented OD indications not associated with a Bobbin Plus-Point tube support (freespan)
Circumferentially oriented ID indications near or below Plus-Point Plus-Point the expansion transition at the top of the hot leg tubesheet Circumferentially oriented OD indications near the Plus-Point Plus-Point expansion transition at the top of the hot leg tubesheet Axially oriented indications in the sludge pile region Plus-Point Plus-Point near the top of the hot leg tubesheet Axially oriented ID indications near or below the Plus-Point Plus-Point expansion transition at the top of the hot leg tubesheet Indications of wear at tube support locations Bobbin Plus-Point Volumetric indications Bobbin or Plus-Point Plus-Point Miscellaneous preventive plugging Bobbin or Plus-Point Plus-Point Note 1: Plus-Point technique is used at dents with greater than or equal to two volts.
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 7 of 23 TABLE 3 - Number of Tubes Repaired and Active Degradation Mechanisms Found During the U2C13 Refueling Outage Steam Generator E-088 E-089 Indication Orientation/Location I
Tubes with axially oriented ID (initiated on the inside-diameter of the tubing wall) indications at tube support locations 5
0 (ID Axial @ Support) 2 Tubes with axially oriented OD (initiated on the outside-diameter of the tubing wall) indications at tube support locations 30 34 (OD Axial @ Support) 3 Tubes with axially oriented OD indications not associated with a 19 23 tube support (freespan) (OD Axial @ Freespan) 4 Tubes with circumferentially oriented ID indications near the expansion transition at the top of the hot leg tubesheet 29 11 (ID Circ @ TSH) 5 Tubes with circumferentially oriented OD indications near the expansion transition at the top of the hot leg tubesheet 15 (OD Circ @ TSH) 6 Tubes with axially oriented OD indications in the sludge pile region near the top of the hot leg tubesheet 15 16 (OD Axial @ Sludge Pile TSH) 7 Tubes with axially oriented OD indications near the expansion 1
1 transition at the top of the hot leg tubesheet (OD Axial @ TSH) 8 Tubes with axially oriented ID indications near the expansion 0
transition at the top of the hot leg tubesheet (ID Axial @ TSH) 9 Tubes with axially oriented ID indications below the inlet top-of-45 32 tubesheet (ID Axial below TSH) 45_32 10 Tubes with circumferentially oriented ID indications below the 56 27 inlet top-of-tubesheet (ID Circ below TSH) 11 Tubes with indications of wear at tube support locations 51 31 (Wear @ Support) 12 Sleeved Tubes with obstructions in the sleeved area 7
3 (OBS @ Sleeve) 13 Tubes with Data Quality/ALARA complications 4
1 (Data Quality @ Miscellaneous)
Total 279 194
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 8 of 23 TABLE 4 - Summary of Results of In-Situ Pressure and Leak Testing for the U2C13 Refueling Outage S/G 88 March 2004 TUBE AND EDDY CURRENT INFORMATION IN-SITU TEST RESULTS TUBE INFORMATION PLUS-POINT DATA GPM GPM NOPD PRESSURE REGION max.
D POST 3xNOIPD ROW COL LOCATION CA VOLTS Depth PDA ORIENTATION NOPD MSLB MSLB TUBESHEET 7
135 TSH -8.60 325 6.78 100 84 ID CIRC 0
0 0
0 TUBESHEET 18 134 TSH-9.78 172 l 2.3 l 100 l 44 IDCIRC 0
0 0
0 S/G 89 March 2004 TUBE AND EDDY CURRENT INFORMATION IN-SITU TEST RESULTS TUBE INFORMATION PLUS-POINT DATA GPM GPM GPM ~
REGION max.
NOPD PRESSURE ROW COL LOCATION CA VOLTS Depth (P)
ORIENTATION NOPD MSLB MPST 3xNLPD TUBESHEET 39 127 TSH-9.4 189 13.43 96 49 IDCIRC 0
0 0
0 NOTES:
GPM = Gallons per Minute NOPD = Normal Operation Pressure Differential MSLB = Main Steam Line Break Pressure Differential CA = Crack angle, the circumferential extent of a circumferential crack, degrees.
ID = Degradation initiated on the inside diameter of the tubing PDA = Percent degraded area
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 9 of 23 TABLE 5-SONGS U2C13 Refueling Outage Tubes Plugged STEAM GENERATOR E-088 Row Column Reason for Plugging Tube (per Table 3) 14 12 (OD Axial @ Support) 38 12 (OD Axial @ Freespan) 39 13 (OD Axial @ Support) 13 23 (ID Axial below TSH) 72 24 (OD Axial @ Support) 37 25 (ID Axial below TSH) 76 26 (OD Axial @ Support) 79 27 (OD Axial @ Support) 98 30 (OD Axial @ Support) 34 32 (ID Circ below TSH) 94 32 (OD Axial @ Support) 59 33 (ID Axial below TSH) 95 33 (OD Axial @ Support) 16 34 (OD Axial @ Freespan) 37 35 (ID Circ below TSH) 8 36 (OBS @ Sleeve) 19 39 (OBS @ Sleeve) 71 39 (OD Axial @ Support) 4 40 (OD Axial @ Support) 34 40 (ID Circ below TSH) 28 42 (ID Axial below TSH) 65 47 (ID Circ below TSH) 24 48 (OBS @ Sleeve) 117 49 (OD Axial @ Freespan) 70 50 (OD Axial @ Freespan) 21 51 (ID Circ below TSH) 25 51 (ID Circ below TSH) 6 52 (OD Axial @ Support) 126 52 (ID Circ below TSH) 49 53 (OD Axial @ Support) 65 53 (ID Circ below TSH) 67 53 (ID Circ below TSH) 4 54 (ID Circ below TSH)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 10 of 23 TABLE 5 (CONT.) - SONGS U2C13 Refueling Outage Tubes Plugged STEAM GENERATOR E-088 Row Column Reason for Plugging Tube (per Table 3) 12 54 (ID Circ below TSH) 5 55 (OD Axial @ Support) 75 55 (OD Axial @ Freespan) 93 55 (OD Axial @ Support) 14 56 (ID Axial @ Support) 98 56 (ID Circ below TSH) 25 57 (ID Circ below TSH) 87 59 (ID Circ below TSH) 18 60 (ID Axial below TSH) 44 60 (ID Circ below TSH) 76 62 (ID Axial @ Support) 126 62 (Wear @ Support) 1 63 (OD Axial @ Support) 140 66 (Wear @ Support) 30 68 (OBS @ Sleeve) 33 71 (Wear @ Support) 49 71 (Wear @ Support) 34 72 (Wear @ Support) 128 72 (OD Axial @ Support) 142 72 (Wear @ Support) 49 73 (ID Axial below TSH) 73 73 (Wear @ Support) 143 73 (Wear @ Support) 38 74 (Wear @ Support) 144 74 (Wear @ Support) 43 75 (ID Axial below TSH) 45 75 (Wear @ Support) 46 76 (Wear @ Support) 50 76 (Wear @ Support) 51 77 (Wear @ Support) 49 79 (Wear @ Support) 141 79 (Wear @ Support) 129 81 (OD Axial @ Support)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 11 of 23 TABLE 5 (CONT.) - SONGS U2C13 Refueling Outage Tubes Plugged STEAM GENERATOR E-088 Row Column Reason for Plugging Tube (per Table 3) 135 81 (OD Axial @ Support) 141 81 (OD Axial @ Freespan) 145 81 (Wear @ Support) 82 82 (ID Circ below TSH) 142 82 (Wear @ Support) 144 82 (Wear @ Support) 55 83 (Wear @ Support) 87 83 (ID Circ below TSH) 125 83 (Wear @ Support) 135 83 (OD Axial @ Support) 145 83 (Wear @ Support) 58 84 (Wear @ Support) 82 84 (ID Circ below TSH) 146 84 (Wear @ Support) 57 85 (Wear @ Support) 59 85 (Wear @ Support) 65 85 (Wear @ Support) 71 85 (Wear @ Support) 58 86 (Wear @ Support) 86 86 (OBS @ Sleeve) 57 87 (Wear @ Support) 59 87 (ID Axial below TSH) 63 87 (Wear @ Support) 72 88 (Wear @ Support) 144 88 (Wear @ Support) 55 89 (Wear @ Support) 57 89 (Wear @ Support) 52 90 (Wear @ Support) 129 93 (OD Axial @ Support) 147 93 (Wear @ Support) 52 94 (Wear @ Support) 54 94 (ID Axial @ Support) 129 95 (OD Axial @ Freespan)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 12 of 23 TABLE 5 (CONT.) - SONGS U2C13 Refueling Outage Tubes Plugged STEAM GENERATOR E-088 Row Column Reason for Plugging Tube (per Table 3) 52 96 (Wear @ Support) 133 97 (OD Axial @ Freespan) 46 98 (Wear @ Support) 48 98 (Wear @ Support) 51 99 (Wear @ Support) 146 100 (Wear @ Support) 36 102 (Wear @ Support) 38 102 (Wear @ Support) 42 102 (Data Quality @ Miscellaneous) 36 104 (Wear @ Support) 46 104 (ID Circ below TSH) 41 105 (Data Quality @ Miscellaneous) 51 105 (ID Circ below TSH) 144 106 (Wear @ Support) 51 107 (ID Axial below TSH) 28 108 (ID Axial below TSH) 48 108 (OD Axial @ Support) 114 108 (OBS @ Sleeve) 97 109 (OD Axial @ Freespan) 46 110 (ID Circ below TSH) 64 110 (ID Axial below TSH) 119 111 (Wear @ Support) 123 111 (Wear @ Support) 23 113 (Data Quality @ Miscellaneous) 29 113 (ID Axial @ Support) 65 113 (ID Circ below TSH) 71 113 (ID Circ below TSH) 22 114 (ID Axial @ Support) 28 114 (OBS @ Sleeve) 68 114 (ID Circ below TSH) 65 115 (ID Circ below TSH) 67 115 (OD Axial @ Freespan) 9 119 (OD Axial @ Support)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 13 of 23 TABLE 5 (CONT.) - SONGS U2C13 Refueling Outage Tubes Plugged STEAM GENERATOR E-088 Row Column Reason for Plugging Tube (per Table 3) 74 120 (ID Circ below TSH) 80 120 (OD Axial @ Freespan) 15 121 (OD Axial @ Support) 19 121 (OD Axial @ Support) 25 121 (ID Circ below TSH) 45 121 (ID Circ below TSH) 16 122 (OD Axial @ Freespan) 34 122 (ID Circ below TSH) 34 124 (ID Axial below TSH) 15 125 (OD Axial @ Support) 31 125 (ID Circ below TSH) 69 127 (ID Axial below TSH) 38 128 (OD Axial @ Freespan) 67 129 (OD Axial @ Support) 1 131 (Data Quality @ Miscellaneous) 37 133 (ID Circ below TSH) 18 134 (ID Circ below TSH) 60 134 (ID Circ below TSH) 7 135 (ID Circ below TSH) 18 136 (ID Circ below TSH) 17 137 (OD Axial @ Support) 75 139 (Wear @ Support) 26 140 (ID Circ below TSH) 15 143 (OD Axial ( Freespan) 6 144 (OD Axial @ Support) 74 146 (Wear @ Support) 69 149 (OD Axial @ Freespan) 45 151 (OD Axial @ Freespan) 16 152 (OD Axial ( Freespan) 71 155 (OD Axial @ Support) 72 160 (OD Axial @ Support) 4 164 (ID Axial @ TSH) 25 165 (OD Axial @ Freespan) 26 168 (OD Axial @ Freespan)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 14 of 23 TABLE 6-SONGS U2C13 Refueling Outage Tubes Sleeved STEAM GENERATOR E-088 Row Column Reason for Sleeving Tube (per Table 3) 11 35 (ID Axial below TSH) 23 35 (ID Circ @ TSH) 38 36 (ID Circ @ TSH) 25 39 (ID Axial below TSH) 25 41 (OD Circ @ TSH) 18 42 (ID Circ below TSH) 44 42 (ID Axial below TSH) 7 43 (ID Axial below TSH) 16 54 (ID Circ below TSH) 18 54 (ID Circ below TSH) 32 54 (ID Circ below TSH) 27 55 (ID Circ below TSH) 57 55 (ID Circ below TSH) 10 56 (ID Circ below TSH) 16 56 (ID Circ @ TSH) 30 56 (ID Circ below TSH) 46 56 (OD Circ @ TSH) 48 56 (OD Axial @ TSH) 64 56 (ID Axial below TSH) 13 57 (ID Circ below TSH) 23 57 (ID Circ @ TSH) 67 57 (ID Circ @ TSH) 83 59 (ID Circ @ TSH) 18 62 (ID Axial below TSH) 20 62 (OD Circ @ TSH) 11 63 (ID Axial below TSH) 43 63 (ID Axial below TSH) 83 63 (ID Circ @ TSH) 43 65 (ID Axial below TSH) 47 65 (ID Axial below TSH) 59 65 (OD Axial @ Sludge Pile TSH) 64 66 (ID Axial below TSH)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 15 of 23 TABLE 6 (CONT.) - SONGS U2C13 Refueling Outage Tubes Sleeved STEAM GENERATOR E-088 Row Column Reason for Sleeving Tube (per Table 3) 43 67 (ID Axial below TSH) 48 68 (OD Axial @ Sludge Pile TSH) 78 68 (ID Circ @ TSH) 47 69 (ID Axial below TSH) 48 70 (OD Axial @ Sludge Pile TSH) 53 71 (OD Axial @ Sludge Pile TSH) 56 72 (OD Circ @ TSH) 74 74 (OD Circ @ TSH) 99 75 (ID Circ @ TSH) 53 77 (ID Axial below TSH) 55 77 (OD Axial @ Sludge Pile TSH) 61 77 (OD Axial @ Sludge Pile TSH) 64 78 (OD Axial @ Sludge Pile TSH) 80 78 (OD Circ @ TSH) 53 79 (ID Axial below TSH) 78 80 (ID Circ @ TSH) 63 81 (ID Axial below TSH) 57 83 (OD Axial @ Sludge Pile TSH) 70 84 (OD Axial @ Sludge Pile TSH) 80 86 (ID Circ @ TSH) 59 91 (OD Axial @ Sludge Pile TSH) 63 91 (ID Axial below TSH) 67 91 (OD Circ @ TSH) 77 91 (OD Circ @ TSH) 60 92 (ID Axial below TSH) 68 92 (OD Axial @ Sludge Pile TSH) 68 94 (OD Axial @ Sludge Pile TSH) 53 95 (ID Axial below TSH) 85 95 (ID Circ below TSH) 73 97 (OD Axial @ Sludge Pile TSH) 75 97 (OD Axial @ Sludge Pile TSH) 91 97 (ID Circ @ TSH) 61 99 (OD Circ @ TSH) 89 99 (ID Circ @ TSH)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 16 of 23 TABLE 6 (CONT.) - SONGS U2C13 Refueling Outage Tubes Sleeved STEAM GENERATOR E-088 Row Column Reason for Sleeving Tube (per Table 3) 51 101 (ID Axial below TSH) 69 101 (ID Circ @ TSH) 49 103 (ID Axial below TSH) 57 103 (ID Axial below TSH) 67 103 (ID Circ @ TSH) 42 104 (ID Axial below TSH) 80 104 (ID Circ @ TSH) 82 104 (ID Circ @ TSH) 47 105 (ID Axial below TSH) 30 108 (ID Axial below TSH) 70 108 (ID Circ @ TSH) 55 111 (OD Axial @ Sludge Pile TSH) 42 112 (ID Axial @ TSH) 50 112 (ID Circ @ TSH) 17 113 (ID Circ below TSH) 43 113 (ID Circ @ TSH) 44 114 (ID Circ below TSH) 46 114 (ID Circ @ TSH) 52 114 (ID Axial below TSH) 82 114 (ID Circ @ TSH) 44 116 (ID Axial below TSH) 60 116 (ID Circ @ TSH) 28 118 (ID Axial below TSH) 30 118 (ID Circ @ TSH) 13 119 (ID Circ @ TSH) 57 119 (ID Circ @ TSH) 75 119 (ID Axial below TSH) 22 120 (ID Axial below TSH) 7 121 (ID Circ below TSH) 13 121 (ID Circ @ TSH) 83 121 (ID Circ below TSH) 42 122 (ID Axial below TSH) 48 122 (OD Circ @ TSH)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 17 of 23 TABLE 6 (CONT.) - SONGS U2C13 Refueling Outage Tubes Sleeved STEAM GENERATOR E-088 Row Column Reason for Sleeving Tube (per Table 3) 19 123 (ID Circ below TSH) 60 126 (ID Circ @ TSH) 25 127 (ID Circ below TSH) 27 127 (OD Circ @ TSH) 47 127 (ID Circ below TSH) 39 131 (ID Circ below TSH) 10 132 (ID Circ below TSH) 18 138 (ID Circ @ TSH) 7 139 (ID Circ below TSH) 12 144 (ID Axial below TSH) 37 147 (OD Circ @ TSH) 35 149 (OD Circ @ TSH) 65 149 (OD Circ @ TSH) 57 151 (OD Circ @ TSH)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 18 of 23 TABLE 7 - SONGS U2C13 Refueling Outage Tubes Plugged STEAM GENERATOR E-089 Row Column Reason for Plugging Tube (per Table 3) 19 9
(OD Axial @ Support) 4 10 (ID Axial below TSH) 12 10 (OD Axial @ Support) 20 10 (OD Axial @ Freespan) 18 14 (OD Axial @ Support) 48 14 (OD Axial @ Freespan) 13 15 (OD Axial @ Support) 47 15 (OD Axial @ Support) 75 17 (OD Axial @ Support) 67 19 (OD Axial @ Freespan) 68 20 (OD Axial @ Support) 68 22 (OD Axial @ Support) 93 31 (OD Axial @ Freespan) 114 34 (ID Axial below TSH) 9 35 (ID Circ below TSH) 100 36 (OD Axial @ Support) 15 37 (ID Circ below TSH) 112 38 (OD Axial @ Freespan) 103 39 (OD Axial @ Freespan) 36 40 (OD Axial @ Freespan) 38 40 (ID Circ below TSH) 47 41 (ID Axial below TSH) 47 45 (ID Axial below TSH) 65 47 (OD Axial @ Support) 111 47 (OD Axial @ Support) 9 49 (OD Axial @ Support) 110 50 (OD Axial @ Support) 120 50 (OD Axial @ Support) 47 51 (OD Circ @ TSH) 51 51 (ID Circ @ TSH) 62 52 (OD Axial @ Freespan) 1 55 (OD Axial @ Support) 114 56 (OD Axial @ Support) 23 57 (OD Axial @ Support) 22 58 (OD Axial @ Support) 39 59 (OD Axial @ Sludge Pile TSH) 49 59 (OD Axial @ Sludge Pile TSH)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 19 of 23 TABLE 7 (CONT.) - SONGS U2C13 Refueling Outage Tubes Plugged STEAM GENERATOR E-089 Row Column Reason for Plugging Tube (per Table 3) 24 60 (ID Circ @ TSH) 51 61 (OD Axial @ Support) 81 61 (OD Axial @ Freespan) 22 62 (ID Axial below TSH) 9 63 (ID Axial below TSH) 78 64 (ID Axial below TSH) 22 66 (ID Circ below TSH) 78 66 (OD Axial @ Freespan) 39 69 (ID Circ below TSH) 71 71 (ID Axial below TSH) 87 71 (OD Axial @ Support) 74 72 (OBS @ Sleeve) 118 72 (OD Axial @ Freespan) 39 73 (ID Axial below TSH) 45 73 (ID Axial below TSH) 144 74 (Wear @ Support) 37 75 (Wear @ Support) 145 75 (Wear @ Support) 62 76 (OD Axial @ Freespan) 82 76 (ID Circ @ TSH) 114 76 (OBS @ Sleeve) 138 76 (Wear @ Support) 47 77 (Wear @ Support) 49 77 (OD Axial @ Support) 95 77 (ID Axial below TSH) 74 78 (OD Axial @ Sludge Pile TSH) 43 79 (Wear @ Support) 63 79 (Wear @ Support) 75 79 (Wear @ Support) 131 79 (OD Axial @ Support) 50 82 (Wear @ Support) 56 82 (Wear @ Support) 53 83 (Wear @ Support) 57 83 (Wear @ Support) 63 83 (Wear @ Support) 58 86 (Wear @ Support)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 20 of 23 TABLE 7 (CONT.) - SONGS U2C13 Refueling Outage Tubes Plugged STEAM GENERATOR E-089 Row Column Reason for Plugging Tube (per Table 3) 138 86 (OD Axial @ Support) 142 86 (ID Circ below TSH) 146 86 (Wear @ Support) 89 87 (ID Axial below TSH) 136 88 (OD Axial @ Support) 65 89 (Wear @ Support) 58 90 (Wear @ Support) 63 91 (OBS @ Sleeve) 146 92 (Wear @ Support) 54 94 (Wear @ Support) 56 94 (Wear @ Support) 62 94 (Wear @ Support) 146 94 (Wear @ Support) 51 95 (Wear @ Support) 51 97 (Wear @ Support) 146 98 (OD Axial @ Freespan) 49 99 (Wear @ Support) 44 100 (Wear @ Support) 45 101 (Wear @ Support) 47 101 (Wear @ Support) 135 101 (OD Axial @ Support) 25 109 (ID Axial below TSH) 33 109 (Data Quality @ Miscellaneous) 42 110 (Wear @ Support) 108 110 (ID Axial below TSH) 138 110 (ID Axial below TSH) 27 111 (OD Circ @ TSH) 75 111 (Wear @ Support) 89 111 (ID Axial below TSH) 82 112 (ID Axial below TSH) 126 112 (OD Axial @ Support) 21 113 (OD Axial @ Support) 71 113 (OD Axial @ Freespan) 85 113 (ID Axial below TSH) 5 115 (ID Circ below TSH) 127 115 (OD Axial @ Freespan)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 21 of 23 TABLE 7 (CONT.) - SONGS U2C13 Refueling Outage Tubes Plugged STEAM GENERATOR E-089 Row Column Reason for Plugging Tube (per Table 3) 58 116 (OD Axial @ Support) 90 116 (OD Axial @ Freespan) 2 118 (ID Circ below TSH) 18 118 (ID Circ below TSH) 45 119 (OD Axial @ Freespan) 112 120 (ID Axial below TSH) 102 122 (OD Axial @ Support) 14 124 (ID Axial below TSH) 42 124 (ID Axial below TSH) 4 126 (ID Circ below TSH) 9 127 (ID Circ below TSH) 11 127 (OD Axial @ Support) 29 127 (ID Circ below TSH) 39 127 (ID Circ below TSH) 18 128 (ID Circ below TSH) 112 128 (OD Axial @ Support) 46 130 (ID Axial below TSH) 9 131 (ID Circ below TSH) 81 131 (ID Circ below TSH) 46 132 (OD Axial @ Freespan) 46 136 (OD Axial @ Sludge Pile TSH) 75 139 (ID Axial below TSH) 13 141 (OD Axial @ Freespan) 95 141 (ID Axial below TSH) 66 144 (Wear @ Support) 65 151 (ID Axial below TSH) 24 152 (ID Circ @ TSH) 11 159 (OD Axial @ Support) 26 162 (OD Axial @ Support) 11 163 (OD Axial @ Freespan) 22 164 (OD Axial @ Freespan) 11 165 (OD Axial @ Support) 14 166 (OD Axial @ Freespan) 19 167 (OD Axial @ Freespan)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 22 of 23 TABLE 8 - SONGS U2C13 Refueling Outage Tubes Sleeved STEAM GENERATOR E-089 Row Column Reason for Sleeving Tube (per Table 3) 56 38 (ID Circ @ TSH) 28 42 (ID Circ @ TSH) 46 44 (ID Axial below TSH) 45 47 (ID Axial below TSH) 16 58 (ID Circ below TSH) 37 59 (OD Circ @ TSH) 20 60 (OD Circ @ TSH) 38 60 (OD Axial @ Sludge Pile TSH) 35 61 (OD Circ @ TSH) 43 65 (OD Circ @ TSH) 64 66 (OD Axial @ Sludge Pile TSH) 39 67 (OD Axial @ TSH) 45 67 (ID Axial below TSH) 67 71 (OD Axial @ Sludge Pile TSH) 46 72 (ID Axial below TSH) 75 73 (OD Axial @ Sludge Pile TSH) 48 74 (OD Circ @ TSH) 78 74 (ID Circ @ TSH) 50 78 (OD Axial @ Sludge Pile TSH) 54 78 (OD Axial @ Sludge Pile TSH) 68 84 (OD Axial @ Sludge Pile TSH) 89 85 (OD Circ @ TSH) 64 88 (OD Circ @ TSH 95 93 (ID Circ below TSH) 83 95 (OD Circ @ TSH) 101 97 (OD Axial @ Sludge Pile TSH) 62 100 (OD Circ @ TSH) 57 103 (ID Circ @ TSH) 106 104 (OD Axial @ Sludge Pile TSH) 116 106 (IDAxial belowTSH) 51 107 (OD Circ @ TSH) 97 107 (ID Axial below TSH) 48 108 (OD Axial @ Sludge Pile TSH) 47 109 (OD Axial @ Sludge Pile TSH) 26 110 (OD Axial @ Sludge Pile TSH) 8 114 (ID Circ @ TSH)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 23 of 23 TABLE 8 (CONT.) - SONGS U2C13 Refueling Outage Tubes Sleeved STEAM GENERATOR E-089 Row Column Reason for Sleeving Tube (per Table 3) 18 114 (OD Circ @ TSH) 35 115 (OD Circ @ TSH) 77 115 (ID Circ below TSH) 38 116 (ID Axial below TSH) 12 120 (ID Circ below TSH) 53 125 (OD Circ @ TSH) 81 125 (ID Circ @ TSH) 36 126 (ID Circ below TSH) 33 127 (ID Circ below TSH) 36 132 (ID Circ below TSH) 36 134 (ID Circ below TSH) 12 138 (ID Circ below TSH) 10 140 (ID Circ below TSH) 9 147 (ID Circ below TSH) 27 147 (ID Circ @ TSH)
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 4 Appendix I Steam Generator Reference Information
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 2 of 4 10OH C
C C
C C
C C
C T
Steam Generator CE Model 3410 Tube Support Drawing H0 18H 8
17H
-D____
7(
16H
=-06(
14H
=--
04(
i3H
-03(
12H
=
02(
11H 1C
__H_
TS(
EH TEC HotLog Cold Leg INLET OLTLET 1OC -
50.75w
.7r 357 C
37r ASa II.25 Sr Us I;' 75
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 3 of 4 STEAM GENERATOR TUBE SUPPORT INTERSECTIONS ABOVE THE 7 TH (FULL) EGGCRATE SUPPORT SUPPORT INTERSECTIONS ROW STRUCTURES 122-147 08H 09H 1OH DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC IOC 09C 08C 120-121*
08H 09H IOH DBH VHI VH2 VH3 VSM VC3 VC2 VC1 DBC IOC 09C 08C 115-119 08H 09H DBH VHI VH2 VH3 VSM VC3 VC2 VC1 DBC 09C 08C 86-114 08H 09H DBH VH2 VH3 VSM VC3 VC2 DBC 09C 08C 84-85*
08H 09H DBH VH2 VH3 VSM VC3 VC2 DBC 09C 08C 83 08H DBH VH2 VH3 VSM VC3 VC2 DBC 08C 51-82 08H DBH VH3 VSM VC3 DBC 08C 49-50*
08H DBH VSM DBC 08C 19-48 DBH VSM DBC 1-18 DBH DBC
- Indicates those rows adjacent to scallop bars
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 4 of 4 SOUTHERN CALIFORNIA EDISON, SAN ONOFRE CE MODEL 3410 STEAM GENERATOR 1to a
so 90 b
I" 114 12° 10 IS InS 3
1*1 I I lit 0 o0 o O I
I 141 i
8 1
1 i
I-1<,
4 C09gi¢§ T
9 0
.~t QYQ!0@
101r04 11OA A*.A 0olt I
1In i
-fi 8
+*
p.09 W t
I iiC l 1t M800o~~o8ca0 o0°810 Sa~amagn q
~on a
0 9o6o`1 bit196",
oo;oo IJ If.
I Igl S~.J o£ I
o1a31aoggg o
- 30.
oo, 00, 0 Ig~
8g-g1g--1i ogoge.....
3--o-.......... g 0C t 1
o 1,~ffj~0b ao.s$
S~ ~g g Sgo ISO It Mt.
-A c,,o2020QoicWtovw^zsolo2evho59;^-c MI too PLC 0.--.-
_t
- PoXgO KO O
x01ox ox ON-60 oO8AMPNgI A
9X 9N 919 I 9 Ng '. 9A 45O8oOvooovvgoB2iovgt C50°0°8
,ogoVO^6g4Ac 0qoC V-gOO 70
'0 0 ~ og~opo gog~oo A A ~c o%~
~
og~oAgo~ggo ooog g~go ggo~o6 o~oo%40Q 0 ~crngag 000 o
a00 0
00 000 0~g~o00333.8 t
43 00ooog3 S38 1
0 g9~
3 ~~3 3
~~~
~~
3oo oocc 0033
~~~3 ~~~~ 88338S23?3 3 o
- 0' o30oo 0ooo%)0o;o I
4
- OO NIPS 0?O*~
~b~~ ~
0 ~ggggggoooooog 0 ggg ~~~
~ggg~~
0 gggggg aogo
~Q~~
2-42 4
4pe
'S I1 6,95;l706g5:6 5ggi5g 63.mneg5g ~
6 64~
ga~~
,,ogog 0o0o~o egoogc 00,0~% 00 I
'0205C5% 60Vg 6r5n6-5 1
, g z
t0 2*
Is 4
7 lo I"
II*
In Is 140 tS*
Its tIC
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 2 Appendix 2 Legend for Appendices 3 and 4
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 2 of 2 List of Abbreviations and Format Used to Describe Indications from Rotating Probe Testing "I-Code" Abbreviations Explanation of the Abbreviations SCI Single Circumferential Indication MCI Multiple Circumferential Indications SAI Single Axial Indication MAI Multiple Axial Indications MMI Mixed Mode Indications SVI Single Volumetric Indication (i.e. no special axial or circumferential aspect)
MVI Multiple Volumetric Indications (i.e. no special axial or circumferential aspect)
Format In Appendices 3 and 4, a single line of data is associated with each individual rotating probe indication. Below is a descriptive example of the format.
- 1. All 'I-Code' indications require a single line entry. The example above displays the form of a Resolution Report line. The VOLTS field contains the Plus-Point P-to-P voltage of the largest, most representative response. The DEG field contains the corresponding phase angle. The CHN field contains the reporting channel (i.e. the appropriate 300kHz Plus-Point channel). The IND field contains the appropriate 3-letter code (see list above). The %TW field indicates the percent wall loss for wear indications. The LOCATION field contains the abbreviation for the referenced landmark and the (FROM-TO) distance for the indication. The EXT fields contain the landmarks of the beginning and end of the test extent The UTIL 1 field contains the 300kHz pancake P-to-P voltage of the largest, most representative response. The UTIL 2 field was used to document the actual inspection distance below the hot leg top-of-tubesheet or Sleeve Bottom Hot for applicable inspections. Exceptions to this general guidance are provided in paragraphs 2 through 4 below.
- 2.
For axial indications of extended length, the location should be ranged (FROM-TO) in the LOCATION field. If the range of such an indication includes any part of a support structure, it should be references from that landmark.
- 3.
For 'I-Code' indications which have both axial and circumferential extent (i.e. SVI, MVI, and MMI), the location should be ranged in the LOCATION field (as above) and the UTIL 2 field should contain the circumferential length.
- 4.
Some data lines contain a note abbreviation in the Util 1 column. These are the definitions of these abbreviations.
LAR: Lead Analyst Reviewed LOCOK: Location Verification
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 29 Appendix 3 Inspection Summary Steam Generator E-088
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand_0-100%twd 3/7/2004 1:56:06 PM Component:
S/G 88 Page 2 of 29 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 1
63 0.34 119 2 SAI DBC
-0.02 DBC 07C 0.26 149 COLD 560P2 0.28 102 5 SAI DBC
+0.15 07H 07C 85 COLD 5002P 4
40 0.53 87 2
SAI 07C
-0.45 07C 07C 0.52 134 COLD 580PP 4
54 2.50 33 P 1 MCI TSH
-9.35 TSH TSH 2.33 17.77 255 HOT 580PP 4
164 0.77 20 2
SAI TSH
-0.16 TSH TSH 0.00 18.61 177 HOT 580PP 5
55 0.37 131 2 SAI 06H
+0.48 06H 06H 0.14 255 HOT 580PP 6
52 0.32 75 2
SAI 07H
-0.53 07H 07H 0.38 256 HOT 580PP 6
144 0.29 84 2
SAI 07H
-0.35 07H 07H 0.23 271 HOT 580PP 6
168 0.24 128 P 5 TWD 15 04H
-0.75 04H 04H 223 HOT 580PP 7
43 0.59 22 2
SAI TSH
-7.23 TSH TSH 0.0 18.39 149 HOT 580PP 7
121 0.37 23 P 1 MCI TSH
-3.47 TSH TSH 0.17 18.48 170 HOT 580PP 7
135 5.73 39 P 1 MCI TSH
-8.60 TSH TSH 11.28 18.75 174 HOT 580PP 7
139 0.35 17 P 1 SCI TSH
-5.48 TSH TSH 0.14 18.50 174 HOT 580PP 9
119 0.21 112 2 SAI 05H
+0.24 05H 05H 0.00 240 HOT 580PP 9
123 0.35 144 P 2 TWD 17 05H
-0.36 TEH TEC 20 COLD 60OUL 0.22 139 P 2 TWD 11 04H
-1.13 TEH TEC 20 COLD 600UL 0.40 144 P 2 TWD 19 04H
+0.90 TEH TEC 20 COLD 600UL 10 56 1.06 26 P 1 SCI TSH
-8.84 TSH TSH 1.88 18.21 256 HOT 580PP 10 126 0.27 53 P 2 TWD 15 05H
+0.86 TEH TEC 19 COLD 600UL 10 132 0.82 33 P 1 SCI TSH
-7.68 TSH TSH 1.51 21.00 329 HOT 580PP 11 35 0.45 21 2
SAI TSH
-4.34 TSH TSH 0.0 17.68 171 HOT 580PP 11 63 0.35 17 2
SAI TSH
-0.85 TSH TSH 0.00 19.35 238 HOT 580PP 12 54 4.53 51 P 1 SCI TSH
-10.18 TSH TSH 5.23 17.61 229 HOT 58OPP 12 144 0.51 16 2
SAI TSH
-2.03 TSH TSH 0.46 18.70 189 HOT 58OPP 13 9
0.43 63 P 2 TWD 17 05H
-0.12 TEC TEH 1
HOT 600UL 0.19 82 P 5 TWD 14 05H
-0.10 05H 05H 259 HOT 580PP 13 23 0.95 16 2
SAI TSH
-12.09 TSH TSH 1.90 17.41 168 HOT 580PP 13 57 0.44 21 P 1 SCI TSH
-7.23 TSH TSH 0.00 17.52 235 HOT 580PP 13___119__0.33___22__P__1___C___TSR__-0.13______TSR____TSR____0.11_____17.53______162____HOT____580______
13 119 0.33 22 P 1 SCI TSH
-0.13 TSH TSH 0.11 17.53 162 HOT 580PP 13 121 0.33 21 P 1 SCI TSH
-0.13 TSH TSH 0.29 18.41 166 HOT 580PP 14 12 0.23 72 2
SAI 05H
-0.40 05H 05H 0.55 259 HOT 580PP 14 40 0.22 53 P 2 TWD 12 02H
-1.18 TEC TEH 18 HOT 600UL 14 56 1.02 14 2
SAI 05H
+0.71 05H 05H 0.88 228 HOT 580PP 15 119 0.30 96 P 2 TWD 18 07C
-0.85 TEH TEC 4
COLD 600UL 0.16 114 P 5 TWD 12 07C
-0.90 07C 07C 139 COLD 580PP 15 121 0.26 102 2 SAI 05H
+0.66 05H 05H 0.52 244 HOT 580PP 15 125 0.14 82 2
SAI 04H
+0.93 04H 04H 0.00 245 HOT 580PP 15 143 0.21 113 2 SAI 01H
+16.82 01H 01H 0.10 220 HOT 580PP 4.95 38 P 1 SCI TSH
-10.48 TSH TSH 5.83 18.50 189 HOT 580PP 16 20 0.21 134 P 3 TWD 11 DBC
+2.21 TEC TEH 8
HOT 600UL 16___34___0.43____98___2_________0214____+3.84_________7___59__0214_____02____.60___263____HOT___58022___
16 34 0.43 98 2
MAI 02H
+3.84 TO+7.59 02H 02H
.60 263 HOT 580PP
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 3/7/2004 1:56:06 PM Component: S/G 88 Page 3 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 16 54 0.28 22 P 1 SCI TSH
-7.49 TSH TSH 0.23 17.44 229 HOT 580PP 16 56 0.25 24 P 1 SCI TSH
-0.07 TSH TSH 0.00 17.38 250 HOT 580PP 16 122 0.14 108 2 SAI 02H
-1.21 02H 02H 0.50 245 HOT 580PP 16 152 0.13 114 2 SAI 02H
+1.11 02H 02H 0.49 223 HOT 580PP 0.15 84 2
SAI 02H
+1.31 02H 02H 0.30 223 HOT 580PP 17 113 0.43 21 P 1 MCI TSH
-5.53 TSH TSH 0.53 19.96 157 HOT 580PP 17 137 0.26 120 2 SAI 06H
+0.08 06H 06H 0.00 220 HOT 580PP 17 161 0.38 150 P 2 TWD 16 06H
+0.76 TEC TEH 21 HOT 600UL 18 42 1.95 32 P 1 SCI TSH
-7.18 TSH TSH 2.34 18.74 175 HOT 580PP 18 44 0.29 103 P 3 TWD 12 DBH
-2.18 TEC TEH 17 HOT 600UL 18 54 0.34 25 P 1 SCI TSH
-2.06 TSH TSH 0.00 17.68 228 HOT 580PP 18 60 0.57 24 P 1 SCI TSH
-10.13 TSH TSH 0.14 20.04 331 HOT 580PP 0.56 14 2
SAI TSH
-1.47 TSH TSH 0.00 331 HOT 580PP 18 62 0.41 26 P 1 MCI TSH
-6.78 TSH TSH 0.00 17.79 235 HOT 580PP 0.49 7
2 SAI TSH
-1.80 TSH TSH 0.00 235 HOT 580PP 0.45 17 2
SAI TSH
-1.14 TSH TSH 0.00 235 HOT 580PP 0.27 15 2
SAI TSH
-0.99 TSH TSH 0.00 235 HOT 580PP 18 134 2.18 40 P 1 SCI TSH
-9.76 TSH TSH 2.99 18.41 181 HOT 580PP 18 136 3.38 37 P 1 SCI TSH
-12.11 TSH TSH 4.35 18.48 181 HOT 580PP 18 138 0.26 27 P 1 SCI TSH
-0.15 TSH TSH 0.00 18.23 189 HOT 580PP 19 25 0.32 26 P 2 TWD 17 01H
-0.36 TEC TEH 8
HOT 600UL 19 111 0.13 119 P 5 TWD 14 VSM
-0.90 VSM DBC 170 COLD 560P2 0.34 4
P 3 TWD 19 DBC
+2.25 TEH TEC LAR 6
COLD 600UL 19 121 0.39 131 2 SAI 05H
+0.00 05H 05H 0.52 244 HOT 580pp 19 123 0.37 18 P 1 SCI TSH
-3.68 TSH TSH 0.31 17.87 165 HOT 580PP 19 135 0.34 141 P 3 TWD 13 DBH
+2.10 TEC TEH 11 HOT 60OUL 19 159 0.23 61 P 2 TWD 11 04H
+0.84 TEC TEH 21 HOT 600UL 20 62 0.19 57 P 1 SCI TSH
-0.02 TSH TSH 0.0 18.18 234 HOT 58OPP 20 68 0.30 39 P 3 TWD 17 DBH
-1.61 TEH TEC 32 COLD 600UL 0.37 98 P 5 TWD 25 DBH
-1.94 DBH DBH AIC 147 COLD 560P2 20 108 0.18 44 P 3 TWD 8 DBH
-1.55 TER TEC 8
COLD 600UL 0.37 93 P 5 TWD 18 DBH
-1.77 07H DBH 377 HOT 560P2 0.34 88 P 5 TWD 25 DBH
-1.69 DBH DBH 170 COLD 560P2 21 51 0.67 32 P 1 SCI TSH
-13.13 TSH TSH 0.43 20.41 222 HOT 580PP 21 61 0.29 145 P 3 TWD 15 DBH
+1.97 TEH TEC 29 COLD 600UL 22 114 1.22 13 2
SAI 06H
+0.61 05H 06H 0.00 346 HOT 500P2 22 120 0.53 16 2
SAI TSH
-2.06 TSH TSH 0.70 17.50 162 HOT 580PP 23 35 0.58 24 P 1 SCI TSH
-0.11 TSH TSH 0.0 17.94 171 HOT 580PP 23 57 0.44 30 P 1 SCI TSH
-0.14 TSH TSH 0.86 18.30 232 HOT 580PP 23 109 0.27 106 P 2 TWD 14 VSM
+0.74 TEH TEC 7
COLD 600UL 0.22 140 P 5 TWD 20 VSM
+0.99 VSM VSM 170 COLD 560P2 23 125 0.30 76 P 2 TWD 16 07H
-0.21 TEH TEC 3
COLD 600UL 24 14 0.24 73 P 2 TWD 13 VSM
+0.99 TEC TEH 2
HOT 600UL 0.23 92 P 5 TWD 14 VSM
+0.93 VSM VSM 144 COLD 560P2
Framatome ANP Inc.
3/7/2004 1:56:06 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 4 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-========================-
-=======-=======-=====-========-===
24 68 0.38 45 P 2 TWD 19 06H
+0.88 TEH TEC 32 COLD 600UL 25 39 0.37 11 2
SAI TSH
-6.56 TSH TSH 0.46 18.37 176 HOT 580PP 25 41 0.19 121 P 1 MCI TSH
-0.03 TSH TSH 0.40 18.47 176 HOT 580PP 25 51 2.02 38 P 1 SCI TSH
-9.88 TSH TSH 2.83 20.53 222 HOT 580PP 25 57 0.24 15 P 1 SCI TSH
-9.83 TSH TSH 0.17 17.94 233 HOT 580PP 25 121 0.80 27 P 1 SCI TSH
-10.70 TSH TSH 0.81 18.55 165 HOT 58OPP 0.68 30 P 1 SCI TSH
-10.25 TSH TSH 0.64 165 HOT 580PP 25 127 0.60 21 P 1 SCI TSH
-6.20 TSH TSH 0.24 18.46 170 HOT 580PP 25 165 0.18 75 2
SAI 05H
+12.15 05H 05H 0.44 223 HOT 580PP 26 140 1.97 36 P 1 SCI TSH
-13.39 TSH TSH 1.87 18.21 189 HOT 580PP 0.80 30 P 1 SCI TSH
-7.93 TSH TSH 0.63 189 HOT 58OPP 0.51 29 P 1 SCI TSH
-5.12 TSH TSH 0.57 189 HOT 58OPP 26 146 0.22 126 P 3 TWD 15 DBH
+1.92 TEC TEH 16 HOT 600UL 26 168 0.12 82 2
SAI 06H
+13.09 06H 06H 0.35 223 HOT 58OPP 27 55 0.38 17 P 1 SCI TSH
-2.00 TSH TSH 0.40 18.43 228 HOT 580PP 27 127 0.54 66 P 1 SCI TSH
-0.07 TSH TSH 0.47 17.86 169 HOT 58OPP 27 145 0.24 160 P 3 TWD 17 DBH
+1.55 TEC TEH 16 HOT 600UL 28 36 0.26 76 P 2 TWD 12 01H
+0.84 TEC TEH 17 HOT 600UL 28 42 0.36 14 2
SAI TSH
-16.49 TSH TSH 0.00 18.48 176 HOT 580PP 28 108 0.64 21 2
SAI TSH
-12.55 TSH TSH 1.02 152 HOT 580PP 0.88 21 2
SAI TSH
-13.55 TSH TSH 1.09 19.73 152 HOT 580PP 2.66 29 2
SAI TSH
-11.22 TSH TSH 3.92 152 HOT 580PP 28 118 0.45 13 2
SAI TSH
-1.78 TSH TSH 0.00 17.39 162 HOT 58OPP 29 113 0.67 8
2 SAI 04H
+0.01 04H 04H 0.00 252 HOT 580PP 30 40 0.41 72 P 2 TWD 19 02H
-1.24 TEC TEH 18 ROT 600UL 30 56 0.46 17 P 1 SCI TSH
-3.61 TSH TSH 0.41 18.93 330 HOT 58OPP 30 108 0.54 14 2
SAI TSH
-1.17 TSH TSH 0.0 20.27 156 HOT 580PP 30 118 0.46 15 P 1 SCI TSH
-0.07 TSH TSH 0.26 17.34 161 HOT 580PP 31 11 0.33 82 P 3 TWD 13 DBH
+1.27 TEC TEH 1
HOT 600UL 0.16 84 P 5 TWD 10 DBH
+1.53 DBH DBH 144 COLD 560P2 31 125 1.47 35 P 1 SCI TSH
-14.41 TSH TSH 2.21 17.96 165 HOT 58OPP 0.98 29 P 1 SCI TSH
-11.92 TSH TSH 1.07 165 HOT 580PP 31 141 0.30 98 P 2 TWD 19 01H
+0.86 TEC TEH 16 HOT 60OUL 32 54 0.77 27 P 1 SCI TSH
-0.32 TSH TSH 0.88 18.20 228 HOT 580PP 33 71 0.84 95 P 5 TWD 37 DBC
-1.95 DBC DBC AIC 155 COLD 560P2 0.29 101 P 5 TWD 16 DBH
-1.89 DBH DBH 155 COLD 560P2 0.78 92 P 5 TWD 38 DBC
-1.74 DEC DBC 155 COLD 560P2 0.59 144 P 3 TWD 27 DBC
-1.95 TEH TEC 32 COLD 600UL 0.10 22 P 3 TWD 7 DBH
-1.74 TEH TEC LAR 32 COLD 60OUL 33 105 0.19 102 P 3 TWD 12 DBH
-1.88 TEH TEC 8
COLD 600UL 0.19 92 P 3 TWD 9 DBC
-1.97 TEH TEC 8
COLD 60OUL 0.32 95 P 5 TWD 21 DBH
-2.05 DBH DBH 169 COLD 560P2 0.17 84 P 5 TWD 13 DBC
+1.47 DBC DBC 169 COLD 560P2 0.33 99 P 5 TWD 22 DEC
-1.80 DBC DBC 169 COLD 560P2 33__159__0.26__83__P_2__TWO__12__0_R_-0.84__________TEC________TER_______21______ROT________________U____
33 159 0.26 83 P 2 TWD 12 07H
-0.84 TEC TEH 21 HOT 600UL
Framatome ANP Inc.
3/7/20 Customer Name: San Onofre -
Unit 2 Compon MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT E 34 32 0.75 22 P 1 SCI TSH
-9.76 TSH I 0.85 22 P 1 SCI TSH
-11.92 TSH 'I 1.82 31 P 1 SCI TSH
-14.60 TSH I 04 1:56:06 PM ent: S/G 88 Page 5 of 29 XT UTIL 1
'SH 0.54
'SH 1.13
'SH
- 3. 19 UTIL 2 CAL #
171 171 171 LEG HOT HOT HOT PROBE 5 80PP 580PP 58aPP 1.06 26 P 1 SCI TSH
-9.20 TSH TSH 1.09 17.93 171 HOT 580PP 34 40 0.59 20 P 1 SCI TSH
-11.64 TSH TSH 1.01 176 HOT 580PP 0.64 22 P 1 SCI TSH
-12.06 TSH TSH 1.09 176 HOT 580PP 0.43 18 P 1 SCI TSH
-14.24 TSH TSH 0.65 176 HOT 580PP 0.40 13 P 1 SCI TSH
-15.31 TSH TSH 0.68 18.83 176 HOT 580PP 34 72 1.26 85 P 5 TWD 44 DBC
+1.68 DBC DBC 155 COLD 560P2 0.87 92 P 3 TWD 33 DBC
+2.08 TEH TEC 32 COLD 600UL 34 116 0.21 44 P 2 TWD 14 VSM
-0.86 TEH TEC 6
COLD 600UL 34 122 0.26 20 P 1 SCI SBH
-0.72 SBH SBH 0.41 6.38 343 HOT 520ET 34 124 0.30 25 P 1 SCI TSH
-11.40 TSH TSH 1.04 17.96 165 HOT 580PP 1.05 22 2
SAI TSH
-10.42 TSH TSH 2.20 165 HOT 580PP 0.46 14 2
SAI TSH
-10.18 TSH TSH 0.65 165 HOT 580PP 0.38 14 2
SAI TSH
-9.83 TSH TSH 0.62 165 HOT 580PP 0.44 17 2
SAI TSH
-9.68 TSH TSH 0.66 165 HOT 580PP 0.52 19 2
SAI TSH
-9.47 TSH TSH 0.55 165 HOT 580PP 0.56 18 2
SAI TSH
-8.07 TSH TSH 0.49 165 HOT 580PP 0.48 11 2
SAI TSH
-6.65 TSH TSH 0.23 165 HOT 580PP 0.37 15 2
SAI TSH
-4.37 TSH TSH 0.52 165 HOT 580PP 34 162 0.36 102 P 2 TWD 16 04H
-0.80 TEC TEH 21 HOT 600UL 35 25 0.74 87 P 2 TWD 29 VSM
-0.93 TEC TEH 8
HOT 600UL 0.23 38 P 2 TWD 13 VSM
+0.88 TEC TEH 8
HOT 600UL 0.53 94 P 5 TWD 30 VSM
-0.90 VSM VSM 150 COLD 560P2 0.15 97 P 5 TWD 10 VSM
+0.88 VSM VSM 150 COLD 560P2 35 27 0.29 137 P 2 TWD 13 VSM
+0.98 TEC TEH 7
HOT 600UL 35 71 0.65 88 P 5 TWD 32 DBC
-1.58 DBC DBC 155 COLD 560P2 0.38 85 P 3 TWD 17 DBC
-1.40 TEH TEC 31 COLD 60OUL 35 149 0.29 122 P 1 SCI TSH
-0.03 TSH TSH 0.00 18.01 193 HOT 580PP 35 155 0.12 32 P 3 TWD 10 DBH
+1.43 TEC TEH 22 HOT 600UL 36 102 1.27 55 P 3 TWD 40 DBC
+1.77 TEH TEC 8
COLD 600UL 1.58 77 P 5 TWD 54 DBC
-1.90 TO+2.00 DBC DBC APN 174 COLD 560P2 36 104 0.78 127 P 5 TWD 43 DBH
-1.73 DBH DBH 166 COLD 560P2 0.84 83 P 3 TWD 34 DBH
-1.73 STH TEC 58 COLD 600UL 37 25 0.60 18 2
SAI TSH
-17.22 TSH TSH 1.19 17.85 168 HOT 580PP 0.27 16 2
SAI TSH
-17.40 TSH TSH 0.80 168 HOT 580PP 37 35 0.37 20 P 1 SCI TSH
-9.83 TSH TSH 0.19 18.02 172 HOT 580PP 37 47 0.37 128 P 2 TWD 19 VSM
+0.83 TEC TEH 131 HOT 600UL 0.33 94 P 5 TWD 21 VSM
+0.83 VSM VSM 150 COLD 560P2 37 61 0.29 98 P 5 TWD 20 VSM
+1.03 VSM VSM 149 COLD 560P2 0.26 140 P 2 TWD 14 VSM
+0.96 TEH TEC 29 COLD 600UL 37 133 5.55 38 P 1 SCI TSH
-11.87 TSH TSH 5.94 18.37 181 HOT 580PP 37 147 0.16 134 P 1 SCI TSH
+0.01 TSH TSH 0.00 17.91 194 HOT 580PP 38 12 0.65 26 P 2 TWD 23 06H
+0.53 TEC TEH 1
HOT 600UL 0.13 87 2
MAI 06H
+3.98 TO+4.86 06H 06H 0.0 259 HOT 580PP 38 24 0.37 92 P 2 TWD 16 VSM
-0.68 TEC TEH 7
HOT 600UL 38 36 0.39 21 P 1 SCI TSH
-0.13 TSH TSH 0.17 17.97 175 HOT 58OPP 38 74 1.26 89 P 5 TWD 47 DBH
-1.99 TO+2.13 DBH DBH 155 COLD 560P2 0.29 72 P 5 TWD 17 DBC
+1.64 DBC DBC 155 COLD 560P2 0.83 87 P 5 TWD 37 DBC
+2.00 DBC DBC 155 COLD 560P2 1.11 41 P 3 TWD 31 DBC
+1.72 TEH TEC 33 COLD 600UL 1.24 112 P 3 TWD 33 DBH
+0.00 TEH TEC LAR LOCOK 33 COLD 600UL
Framatome ANP Inc.
3/7/2004 1:56:06 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 6 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-=====2-===-===-===-===-========================-=======-=======-=======-=====-=====2==-====
38 102 1.09 116 P 3 TWD 33 DBC
+1.72 TEH TEC 7
COLD 600UL 0.46 123 P 3 TWD 20 DBC
+1.35 TEH TEC 7
COLD 600UL 1.12 88 P 5 TWD 45 DBC
-2.00 TO+2.00 DBC DBC 169 COLD 560P2 38 104 0.15 137 P 5 TWD 15 DBH
-1.82 DBH DBH 169 COLD 560P2 38 128 0.07 114 2 MAI 01H
+11.40 TO+21.98 01H 01H 0.0 244 HOT 58OPP 39 13 0.31 138 P 2 TWD 16 VSM
+0.10 TEC TEH 2
HOT 60OUL 0.14 104 2 SAI VSM
+0.08 VSM VSM 375 HOT 560P2 39 103 0.46 135 P 5 TWD 34 DBC
+1.80 DBC DBC 166 COLD 560P2 0.37 65 P 3 TWD 21 DBC
+1.80 STH TEC 58 COLD 600UL 39 127 0.33 55 P 2 TWD 19 VSM
-0.86 TEH TEC 4
COLD 600UL 39 131 0.25 20 P 1 SCI TSH
-0.21 TSH TSH 0.13 18.40 181 HOT 58OPP 39 155 0.11 11 P 3 TWD 10 DBH
-1.12 TEC TEH 22 HOT 60OUL 40 72 0.23 86 P 2 TWD 13 VSM
+0.90 TEH TEC 32 COLD 600UL 40 156 0.33 94 P 2 TWD 15 VSM
+0.80 TEC TEH 21 HOT 600UL 41 39 0.25 141 P 2 TWD 13 03H
-1.19 TEC TEH 18 HOT 600UL 41 73 0.26 93 P 5 TWD 15 VSM
+0.92 VSM VSM 155 COLD 560P2 0.31 130 P 2 TWD 17 VSM
+0.95 TEH TEC 34 COLD 600UL 41 101 0.56 91 P 5 TWD 31 DBC
+1.91 DBC DBC 169 COLD 560P2 0.23 93 P 3 TWD 17 DBC
+2.00 TEC TEH 6
HOT 600UL 0.14 153 P 2 TWD 11 VSM
-0.80 TEC TEH 6
HOT 600UL 41 157 0.31 23 P 3 TWD 22 DBH
+0.17 TEC TEH 22 HOT 600UL 42____74____0.55_____85___P___5___TWO____29____DEC____+1.88______DEC____DEC_____155____COLD_____560P2____
42 74 0.55 85 P 5 TWD 29 DBC
+1.88 DBC DBC 155 COLD 560P2 0.53 86 P 5 TWD 29 DBC
-1.77 DBC DBC 155 COLD 560P2 0.29 106 P 3 TWD 16 DBC
-2.00 TEH TEC 34 COLD 60OUL 0.33 37 P 3 TWD 18 DBC
+1.56 TEH TEC 34 COLD 60OUL 42 104 0.54 23 2
SAI TSH
-4.45 TSH TSH 1.05 19.76 152 HOT 580PP 42 106 0.51 122 P 2 TWD 22 VSM
-0.70 TEH TEC 7
COLD 600UL 0.43 98 P 5 TWD 26 VSM
-0.92 VSM VSM 169 COLD 560P2 0.20 90 P 5 TWD 14 VSM
-0.10 VSM VSM 169 COLD 560P2 42 112 0.57 13 2
SAI TSH
-0.09 TSH TSH 0.26 19.37 157 HOT 58OPP 42 122 0.51 13 2
SAI TSH
-2.60 TSH TSH 0.00 18.33 165 HOT 58OPP 42 152 0.27 142 P 3 TWD 19 DBC
+1.33 TEC TEH 20 HOT 600UL 42 158 0.11 84 P 3 TWD 10 DBH
+1.28 TEC TEH 22 HOT 600UL 0.14 99 P 5 TWD 14 DBH
+1.90 DBH DBH 175 COLD 560P2 42 160 0.31 150 P 3 TWD 22 DBC
+0.86 TEC TEH 22 HOT 600UL 42 170 0.33 155 P 3 TWD 22 DBC
+1.30 TEC TEH 26 HOT 600UL 43 19 0.60 89 P 2 TWD 25 02H
+0.86 TEC TEH 8
HOT 60OUL 0.25 120 P 5 TWD 14 02H
+0.82 02H 02H 259 HOT 58OPP 43 21 0.34 39 P 2 TWD 17 05H
+0.82 TEC TEH 8
HOT 60OUL 43 51 0.73 118 P 2 TWD 29 VSM
+0.85 TEC TEH 131 HOT 60OUL 0.47 95 P 5 TWD 28 VSM
+0.93 VSM VSM 150 COLD 560P2 43 57 0.29 96 P 3 TWD 18 DBC
+1.59 STH TEC 58 COLD 600UL 0.35 84 P 5 TWD 22 DBC
+1.80 DBC DBC 150 COLD 560P2 43 63 0.65 18 2
SAI TSH
-2.93 TSH TSH 0.49 17.36 239 HOT 580PP 43 65 0.60 14 2
SAI TSH
-3.99 TSH TSH 0.57 19.52 238 HOT 58OPP 0.66 16 2
SAI TSH
-3.85 TSH TSH 0.37 238 HOT 58OPP
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 3/7/2004 1:56:06 PM Component: S/G 88 Page 7 of 29 MAI, MCI, MMI, MVI, SAI,
- SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 43 67 0.46 15 2
SAI TSH
-1.32 TSH TSH 0.00 17.42 239 HOT 580PP 43 75 0.41 86 P 5 TWD 24 VSM
+0.95 VSM VSM 155 COLD 560P2 1.30 86 P 5 TWD 46 DBC
+1.81 DBC DBC 155 COLD 560P2 0.67 106 P 2 TWD 29 VSM
+0.84 TEH TEC 34 COLD 600UL 0.80 120 P 3 TWD 32 DBC
+2.00 TEH TEC 34 COLD 600UL 0.39 15 2
SAI TSH
-7.25 TSH TSH 0.57 17.29 219 HOT 580PP 43 101 0.21 98 P 5 TWD 15 DBC
+1.90 DBC DBC 169 COLD 560P2 0.31 99 P 5 TWD 21 DBC
-1.65 DBC DEC 169 COLD 560P2 0.29 83 P 3 TWD 13 DBC
-1.78 TEC TEH 5
HOT 600UL 43 113 0.81 16 2
SAI TSH
-2.97 TSH TSH 0.85 19.56 157 HOT 580PP 0.47 33 P 1 SCI TSH
-0.13 TSH TSH 0.60 19.56 157 HOT 58OPP 43 125 0.20 89 P 5 TWO 15 VSM
-0.83 VSM VSM 170 COLD 560P2 0.40 127 P 2 TWO 22 VSM
-0.83 TEH TEC 4
COLD 600UL 43 149 0.25 157 P 3 TWD 18 DEC
+2.25 TEC TEH 20 HOT 600UL 44 42 0.50 13 2
SAI TSH
-1.13 TSH TSH
.19 18.50 180 HOT 580PP 44 54 0.28 80 P 2 TWD 15 02H
-0.13 TEH TEC 28 COLD 60OUL 44 58 0.25 102 P 5 TWD 17 VSM
+0.83 VSM VSM 150 COLD 560P2 0.15 104 P 5 TWD 10 VSM
-1.11 VSM VSM 150 COLD 560P2 0.33 133 P 2 TWD 18 VSM
+0.83 TEH TEC 28 COLD 600UL 0.18 12 P 2 TWD 10 VSM
-1.01 TEH TEC 28 COLD 600UL 44 60 3.16 38 P 1 SCI TSH
-12.73 TSH TSH 3.46 17.64 235 HOT 580PP 44 76 0.71 124 P 5 TWD 42 DBH
+1.86 DBH DBH 166 COLD 560P2 0.16 136 P 5 TWD 18 DBH
-1.56 DBH DBH 166 COLD 560P2 0.43 166 P 3 TWD 22 DBH
+1.86 STH TEC 59 COLD 60OUL 44 98 0.66 168 P 3 TWO 23 DBC
+1.59 TEC TEH 9
HOT 600UL 0.58 11 P 3 TWD 21 DBH
+1.13 TEC TEH 9
HOT 600UL 0.24 148 P 3 TWD 11 DBH
-1.47 TEC TEH 9
HOT 600UL 0.34 66 P2 TWD 18 01H
-0.28 TEC TEH 9
HOT 600UL 0.15 137 P 5 TWD 15 DEC
-1.76 DEC DBC 168 COLD 560P2 0.56 129 P 5 TWD 36 DEC
+1.75 DEC DBC 168 COLD 560P2 0.23 123 P 5 TWD 20 DBH
-1.75 DBH DBH 168 COLD 560P2 0.81 121 P 5 TWD 42 DBH
+1.75 DBH DBH 168 COLD 560P2 44 114 2.34 32 P 1 MCI TSH
-7.82 TSH TSH 3.55 19.17 162 HOT 58OPP 0.46 21 P 1 SCI TSH
-7.05 TSH TSH 0.60 162 HOT 580PP 44 116 0.89 20 2
SAI TSH
-6.83 TSH TSH 0.81 18.49 161 HOT 580PP 44 124 0.20 140 P 5 TWD 19 VSM
-0.85 VSM VSM 170 COLD 560P2 0.29 72 P 2 TWD 18 VSM
-0.85 TEH TEC 4
COLD 600UL 45 73 0.48 94 P 5 TWD 26 DEC
-1.69 DBC DBC 155 COLD 560P2 0.32 135 P 3 TWD 19 DBC
-1.61 STH TEC 58 COLD 60OUL 45 75 1.06 82 P 5 TWD 45 DEC
-2.00 TO+2.00 DBC DBC 155 COLD 560P2 0.97 91 P 5 TWD 40 DBH
-1.87 DBH DBH 155 COLD 560P2 0.90 72 P 3 TWO 28 DBH
-1.61 TEH TEC 33 COLD 600UL 1.59 143 P 3 TWD 37 DBC
+1.84 TEH TEC LAR LOCOK 33 COLD 600UL 45 121 0.32 22 P 1 SCI TSH
-11.48 TSH TSH 0.46 18.64 165 HOT 580PP 45 151 0.12 102 2 SAI 02H
-1.69 02H 02H 0.15 223 HOT 580PP 45 167 0.51 116 P 2 TWD 21 VSM
-0.78 TEC TEH 25 HOT 600UL 46 6
0.26 143 P 3 TWD 14 DEC
+1.41 TEC TEH 2
HOT 600UL 0.35 84 P 5 TWD 21 DEC
+1.83 DEC DBC 144 COLD 560P2 46 56 0.15 106 P 1 SCI TSH
+0.04 TSH TSH 0.23 17.48 229 HOT 580PP 46 76 1.09 133 P 5 TWD 48 DBH
+1.87 DBH DBH APN 167 COLD 560P2 0.21 126 P 5 TWD 19 DBC
-2.00 TO+2.00 DBC DBC 167 COLD 560P2 0.96 28 P 3 TWD 38 DBH
+1.39 TEC TEH 6
HOT 600UL 0.12 44 P 3 TWD 10 DEC
-1.75 TEC TEH 6
HOT 600UL
Framatome ANP Inc.
3/7/2004 1:56:06 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodes and_0-100%twd.qry Page 8 of 29 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 46 98 0.95 63 P 3 TWD 38 DBH
-1.74 TEC TEE 10 HOT 60OUL 1.31 98 P 5 TWD 49 DBH
-1.78 DBH DBH APN 168 COLD 560P2 46 104 0.26 19 P 1 SCI TSH
-11.39 TSH TSH 0.00 20.79 329 HOT 58OPP 46 110 0.69 31 P 1 MCI TSH
-12.49 TSH TSH 0.49 18.95 157 HOT 58OPP 46 114 0.46 18 P 1 SCI TSH
-0.11 TSH TSH 0.63 18.81 161 HOT 580PP 46 116 0.54 62 P 2 TWD 26 VSM
-0.84 STH TEC 58 COLD 600UL 46 160 0.24 24 P 3 TWD 19 DBH
-2.10 TEC TER 22 HOT 60OUL 47 65 0.48 12 2
SAI TSH
-6.30 TSH TSH 0.81 19.56 238 HOT 580PP 0.55 10 2
SAI TSH
-4.27 TSH TSH 0.60 238 HOT 580PP 0.58 10 2
SAI TSH
-3.36 TSH TSH 0.55 238 HOT 580PP 47 69 0.33 17 2
SAI TSH
-1.62 TSH TSH
.47 17.62 213 HOT 580PP 47 105 0.55 14 2
SAI TSH
-1.29 TSH TSH 0.62 19.67 156 HOT 580PP 47____109____0.20_____98____P__5___TWD____16____V__M_____0.03_____VS_____VSM____166____COLD_____560P_____
47 109 0.20 98 P 5 TWD 16 VSM
+0.03 VSM VSM 166 COLD 560P2 0.20 102 P 5 TWD 16 VSM
+0.93 VSM VSM 166 COLD 560P2 0.31 118 P 2 TWD 15 VSM
+0.97 STH TEC 59 COLD 600UL 47 125 0.28 115 P 2 TWD 17 VSM
+0.80 TER TEC 4
COLD 60OUL 47 127 0.48 21 P 1 SCI TSH
-3.73 TSH TSH 1.68 18.18 169 HOT 580PP 47 143 0.16 117 P 2 TWD 11 VSM
-0.78 TEC TEE 16 HOT 600UL 48 56 0.24 104 2 SAI TSH
+0.00 TSH TSH 0.20 18.30 228 HOT 580PP 48 68 0.28 56 P 2 TWD 15 VSM
+0.83 TER TEC 31 COLD 600UL 0.11 87 2
SAI TSH
+0.96 TSH TSH 0.00 17.79 250 HOT 580PP 48 70 0.16 122 2 SAI TSH
+0.65 TSH TSH 0.0 17.81 213 HOT 58OPP 48 76 0.38 139 P 5 TWD 29 DBC
-1.75 DBC DEC 167 COLD 560P2 0.24 69 P 3 TWD 11 DBC
-1.61 TEC TER 5
HOT 600UL 48 98 1.37 79 P 5 TWD 50 DBH
+1.75 DBH DBH 174 COLD 560P2 1.02 88 P 3 TWD 30 DBH
+1.47 TEC TEE 9
HOT 600UL 0.35 35 P 3 TWD 14 DBC
+1.43 TEC TER 9
HOT 600UL 0.36 126 P 5 TWD 28 DEC
+1.43 DBC DBC 168 COLD 560P2 48 108 0.64 130 P 2 TWD 26 VSM
+0.00 TEE TEC 7
COLD 600UL 0.59 91 P 5 TWD 32 VSM
+0.12 VSM VSM 169 COLD 560P2 0.28 102 P 5 TWD 19 VSM
-0.77 VSM VSM 169 COLD 560P2 0.22 103 P 5 TWD 16 VSM
+0.75 VSM VSM 169 COLD 560P2 0.24 144 2 SAI 06H
+0.03 06H 06H 0.39 248 HOT 580PP 48 120 0.54 34 P 2 TWD 24 08H
+0.99 TEE TEC LOCOK 3
COLD 600UL 48 122 0.15 96 P 1 SCI TSH
+0.13 TSH TSH 0.00 18.34 166 HOT 580PP 48 148 0.49 30 P 3 TWD 15 DBC
+2.00 TEC TEE 19 HOT 600UL 49 33 0.44 132 P 2 TWD 16 08C
-1.23 TEC TER 13 HOT 600UL 49 53 0.47 77 P 2 TWD 22 08C
-1.23 TEC TER 131 HOT 600UL 0.28 91 2
SAI 08C
-1.23 08C 08C 0.18 142 COLD 580PP 49 71 0.53 93 P 5 TWD 34 VSM
-0.89 VSM VSM 155 COLD 560P2 0.85 117 P 2 TWD 34 VSM
-0.89 STH TEC 58 COLD 600UL 49 73 0.49 18 2
SAI TSH
-6.77 TSH TSH 0.64 18.56 218 HOT 58OPP 1.51 25 2
SAI TSH
-10.63 TSH TSH 1.83 218 HOT 580PP 0.35 18 2
SAI TSH
-10.42 TSH TSH 0.00 218 HOT 580PP 49 75 0.53 95 P 5 TWD 28 DBH
-1.79 08H DBH 155 COLD 560P2 0.36 87 P 3 TWD 15 DBH
-1.60 TER TEC 33 COLD 600UL 49 79 0.39 138 P 5 TWD 29 DBH
-1.66 08H DBH 167 COLD 560P2 0.78 137 P 5 TWD 42 0.38 141 P 3 TWD 16 DBC DBH
-2.00
-1.57 TO+2.00 DEC 08C TEC TER 167 COLD 560P2 5
HOT 60OUL
Framatome ANP Inc.
3/7/2004 1:56:06 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 9 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.73 76 P 3 TWD 25 DEC
-1.34 TEC TER 5
HOT 60OUL 49 103 0.45 17 2
SAI TSH
-1.21 TSH TSH 0.33 19.31 156 HOT 580PP 49 169 0.33 104 P 3 TWD 21 DBC
+1.43 TEC TER 26 HOT 600UL 50 8
0.32 137 P 2 TWD 16 VSM
+0.83 TEC TEE 2
HOT 60OUL 0.29 78 P 5 TWD 16 VSM
+0.93 VSM 07H 195 HOT 560P2 50 32 0.41 100 P 2 TWD 19 01H
+0.75 TEC TEE 14 HOT 600UL 50 66 0.31 24 P 2 TWD 18 08C
+1.20 STH TEC 58 COLD 60OUL 50 76 0.76 135 P 5 TWD 41 DBC
-2.00 TO+2.00 DBC DBC 167 COLD 560P2 0.70 110 P 3 TWD 34 DBC
-1.84 TEC TEE 6
HOT 60OUL 0.33 104 P 2 TWD 20 01H
+0.92 TEC TEE 6
HOT 600UL 50 98 0.31 109 P 2 TWD 20 VSM
-0.85 TEC TEE 10 HOT 600UL 0.25 142 P 5 TWD 22 VSM
-0.85 VSM VSM 168 COLD 560P2 50 100 0.89 146 P 5 TWD 35 DEC
-2.00 TO+0.18 DBC 08C 169 COLD 560P2 0.46 130 P 3 TWD 19 DEC
-1.43 TEC TER 5
HOT 600UL 50 110 0.43 84 P 2 TWD 20 08H
+1.48 TER TEC LOCOK 7
COLD 600UL 50 112 0.26 17 P 1 SCI TSH
-0.13 TSH TSH 0.00 19.59 157 HOT 580PP 50 118 0.31 121 P 2 TWD 17 08H
-1.20 TEE TEC 5
COLD 600UL 50 124 0.25 134 P 2 TWD 14 VSM
+0.85 TEH TEC 3
COLD 60OUL 51 45 0.19 160 P 3 TWD 11 DEH
-1.56 TEC TEE 18 HOT 600UL 51 77 0.73 134 P 5 TWD 40 DBC
-1.89 DBC DEC 167 COLD 560P2 0.42 117 P 3 TWD 25 DBC
-1.79 TEC TER 6
HOT 600UL 51 81 0.47 134 P 5 TWD 32 DBH
-1.81 DBH DBH 167 COLD 560P2 0.39 135 P 5 TWD 29 DEE
+1.79 DBH DBH 167 COLD 560P2 0.59 130 P 5 TWD 37 DEC
-2.00 TO+2.00 DBC DBC 167 COLD 560P2 0.36 172 P 3 TWD 15 DEE
+1.43 TEC TEE 5
HOT 600UL 0.41 ll P 3 TWD 17 DBC
-1.49 TEC TEE 5
HOT 600UL 0.34 127 P 3 TWD 15 DEC
+1.97 TEC TEE 5
HOT 60OUL 0.41 150 P 3 TWD 17 DEE
-1.53 TEC TER 5
HOT 600UL 51 99 0.60 79 P 3 TWD 32 DBH
-1.99 TEC TEE 10 HOT 600UL 0.27 72 P 3 TWD 19 DBC
-1.16 TEC TEE 10 HOT 60OUL 0.46 95 P 5 TWD 27 DBC
-2.00 DBC 08C 169 COLD 560P2 0.76 131 P 5 TWD 41 DOE
-1.99 DBH DBH 168 COLD 560P2 51 101 0.33 25 2
SAI TSH
-2.60 TSH TSH 0.41 18.60 144 HOT 580PP 0.57 17 2
SAI TSH
-2.25 TSH TSH 0.49 144 HOT 580PP 0.40 18 2
SAI TSH
-1.92 TSH TSH 0.42 144 HOT 580PP 0.52 22 2
SAI TSH
-1.36 TSH TSH 0.38 144 HOT 580PP 51 105 0.33 21 P 1 SCI SBH
-1.87 SBH SBH 0.00 6.19 340 HOT 520ET 51 107 1.21 28 P 1 SCI TSH
-16.50 TSH TSH 0.96 19.34 156 HOT 580PP 0.82 26 P 1 SCI TSH
-15.57 TSH TSH 0.88 156 HOT 580PP 0.79 18 P 1 SCI TSH
-15.08 TSH TSH 0.52 156 HOT 580PP 0.42 12 2
SAI TSH
-7.52 TSH TSH 0.73 156 HOT 580PP 0.83 17 2
SAI TSH
-7.21 TSH TSH 1.37 156 HOT 580PP 51 117 0.47 113 P 2 TWD 23 08H
+0.80 TER TEC 5
COLD 600UL 51 163 0.31 167 P 3 TWD 22 DBC
+1.55 TEC TEE 22 HOT 600UL 0.27 106 P 2 TWD 19 VH3
+0.85 TEC TEH 22 HOT 600UL 0.04 130 P 5 TWD 18 VH3
+1.04 VH3 VH3 172 COLD 560P2 52 68 0.27 68 P 2 TWD 15 VSM
-0.66 TEE TEC 32 COLD 600UL 52 76 0.30 144 P 5 TWD 24 DEC
-1.76 DBC DBC 167 COLD 560P2 0.20 40 P 3 TWD 9 DBC
-1.44 TEC TEE 5
HOT 60OUL 52 90 0.53 80 P 5 TWD 31 DBC
-1.86 DEC DBC 166 COLD 560P2 0.98 127 P 5 TWD 47 DBH
-2.25 TO+2.25 DBH DBH 166 COLD 560P2 0.35 140 P 3 TWD 19 DBC
-1.75 STH TEC 59 COLD 600UL
Framatome ANP Inc.
3/7/2004 1:56:06 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 10 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 1.27 57 P 3 TWD 40 DBH
-2.00 TO+2.00 STH TEC 59 COLD 60OUL 52 94 0.45 123 P 3 TWD 27 DEC
-1.39 TEC TEH 6
HOT 60OUL 0.57 21 P 3 TWD 30 DBH
+1.49 TEC TEH 6
HOT 600UL 0.72 93 P 5 TWD 36 DEC
-1.68 DEC DBC 168 COLD 560P2 1.26 87 P 5 TWD 46 DBH
-0.60 TO+2.00 DBH DBH 168 COLD 560P2 52 96 0.24 159 P 3 TWD 11 DEC
-2.17 TEC TEH 9
HOT 600UL 0.78 87 P 3 TWD 26 DBH
-1.59 TEC TEH 9
HOT 600UL 1.05 91 P 5 TWD 43 DBH
-2.00 TO+2.00 DBH DBH 168 COLD 560P2 0.28 146 P 5 TWD 23 DBC
-2.17 DBC DBC 168 COLD 560P2 52 114 0.52 15 2
SAI TSH
-1.92 TSH TSH 0.43 19.28 162 HOT 580PP 0.49 15 2
SAI TSH
-1.67 TSH TSH 0.07 162 HOT 58OPP 52 144 0.18 171 P 2 TWD 9 VH3
-1.00 TEC TEH 15 HOT 600UL 53 21 0.40 28 P 2 TWD 17 VSM
-0.84 TEC TEH 7
HOT 600UL 53__45__0.18___133__P_3__TWO__7_DEE__-2.20__________TEC________TEE_______17______HOT___________________L_
53 45 0.18 133 P 3 TWD 7 DBH
-2.20 TEC TEH 17 HOT 600UL 53 71 0.13 114 2 SAI TSH
+0.48 TSH TSH 0.0 18.30 215 HOT 580PP 53 77 0.28 11 2
SAI TSH
-0.57 TSH TSH 0.29 19.38 150 HOT 580PP 53 79 0.38 14 2
SAI TSH
-1.24 TSH TSH
.28 18.43 151 HOT 580PP 53 95 0.94 15 2
MAI TSH
-0.88 TSH TSH 1.09 18.41 145 HOT 580PP 0.25 121 P 3 TWD 18 DEC
-1.75 TEC TEH 6
HOT 60OUL 0.43 131 P 5 TWD 31 DBC
-1.75 DEC DEC 168 COLD 560P2 54 8
0.33 116 P 2 TWD 16 01H
+0.00 TEC TEH 2
HOT 600UL 0.18 129 P 2 TWD 10 01H
-1.01 TEC TEH 2
HOT 600UL 0.28 85 P 5 TWD 19 01H
+0.09 01H 01H 259 HOT 58OPP 0.18 70 P 5 TWD 13 01H
-1.00 01H 01H 259 HOT 580PP 54 58 0.20 25 P 3 TWD 11 DER
-2.06 TEH TEC 28 COLD 60OUL 54 76 0.25 146 P 5 TWD 22 DBC
-1.71 DBC DEC 167 COLD 560P2 0.27 106 P 3 TWD 19 DBC
-1.71 TEC TEH 6
HOT 600UL 54 84 0.64 142 P 5 TWD 38 DBH
-0.50 TO+2.00 DBH DBH 167 COLD 560P2 0.56 57 P 3 TWD 21 DBH
+1.63 TEC TEH 5
HOT 600UL 54 92 0.12 132 P 3 TWD 6 DBH
-1.47 TEC TEH 5
HOT 600UL 0.18 104 P 5 TWD 13 DBH
-2.00 DBH DBH 168 COLD 560P2 54 94 0.35 109 P 3 TWD 15 DBH
-1.56 TEC TEH 5
HOT 600UL 0.83 19 2
SAI 06H
+0.69 06H 06H 0.00 200 HOT 58OPP 0.70 14 2
SAI 06H
+0.50 06H 06H 0.00 200 HOT 58OPP 0.71 89 P 5 TWD 35 DBH
-2.00 TO+2.00 DBH DBH 168 COLD 560P2 54 96 0.51 140 P 5 TWD 36 DBH
-1.61 08H DBH 166 COLD 560P2 0.43 49 P 3 TWD 24 DBH
-1.61 STH TEC 58 COLD 600UL 55 17 0.29 115 P 2 TWD 15 VC3
-0.79 TEC TEH 8
HOT 60OUL 55 29 0.26 140 P 2 TWD 11 VC3
+0.77 TEC TEH 13 HOT 600UL 55 77 0.13 103 2 SAI TSH
+0.30 TSH TSH 0.0 18.40 151 HOT 580PP 55 81 0.33 142 P 5 TWD 26 DBH
-1.70 DBH DBH 167 COLD 560P2 0.14 129 P 3 TWD 11 DBH
-1.40 TEC TEH 6
HOT 60OUL 55 83 0.71 142 P 5 TWD 42 DBH
-1.84 TO+1.95 DBH DBH 166 COLD 560P2 0.39 167 P 3 TWD 21 DBH
+1.79 STH TEC 59 COLD 60OUL 0.61 104 P 3 TWD 28 DBH
-1.67 STH TEC 59 COLD 600UL 55 89 0.65 126 P 5 TWD 40 DEC
-1.54 DEC DBC 166 COLD 560P2 0.29 126 P 5 TWD 27 DEC
+1.47 DEC DEC 166 COLD 560P2 0.24 135 P 3 TWD 14 DEC
+1.47 STH TEC 59 COLD 600UL 0.68 90 P 3 TWD 30 DBC
-1.54 STH TEC 59 COLD 600UL 55 91 0.30 67 P 3 TWD 13 DBH
-1.75 TEC TEH 5
HOT 600UL 0.43 108 P 5 TWD 28 DEH
-1.75 DBH DBH 168 COLD 560P2
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 3/7/2004 1:56:06 PM Component: S/G 88 Page 11 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc icodes and_0-100%twd.qry ROW LINE VOLTS 55 95 0.60 0.45 DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2
175 P 3 TWD 22 DBC
+1.99 TEC TEH 132 P 5 TWD 31 DBC
5 168 LEG HOT COLD PROBE 600UL 560P2 55 97 0.39 168 P 3 TWD 24 DBH
+1.30 TEC TEH 10 HOT 600UL 0.47 94 P 5 TWD 29 DBH
+1.75 DBH DBH 168 COLD 560P2 55 111 0.11 104 2 SAI TSH
+2.10 TSH TSH 0.30 19.60 157 HOT 580PP 55 157 0.38 57 P 2 TWD 17 VH3
+0.64 TEC TEH 21 HOT 60OUL 0.37 59 P 2 TWD 16 VH3
-0.81 TEC TEH 21 HOT 600UL 56 72 0.13 114 P 1 SCI TSH
+0.00 TSH TSH 0.00 18.21 246 HOT 580PP 56 80 0.45 144 P 5 TWD 32 DBC
-1.78 DBC DEC 167 COLD 560P2 0.30 139 P 5 TWD 25 DBH
-1.80 DBH DBH 167 COLD 560P2 0.22 133 P 5 TWD 20 DBH
-1.20 TO+1.75 DBH DBH 167 COLD 560P2 0.43 134 P 3 TWD 18 DEC
-1.82 TEC TEH 5
HOT 600UL 0.36 68 P 3 TWD 15 DBH
-1.90 TEC TEH 5
HOT 600UL 56 108 0.37 55 P 2 TWD 18 03H
+0.78 TEH TEC 7
COLD 60OUL 57 19 0.29 131 P 2 TWD 13 VH3
-0.84 TEC TEH 7
HOT 600UL 57 23 0.41 57 P 2 TWD 20 VC3
+0.85 TEC TEH 8
HOT 60OUL 57 25 0.45 87 P 2 TWD 19 VH3
-0.92 TEC TEH 7
HOT 600UL 57 55 0.33 29 P 1 SCI TSH
-4.06 TSH TSH 0.73 20.09 203 HOT 580PP 57 81 0.52 137 P 5 TWD 34 DBH
-1.75 DBH DBH 167 COLD 560P2 0.54 109 P 3 TWD 20 DBH
-1.77 TEC TEH 5
HOT 600UL 57 83 0.65 139 P 5 TWD 38 DBH
-2.00 TO+1.90 DBH DBH 167 COLD 560P2 0.27 110 P 3 TWD 19 DBH
-1.54 TEC TEH 6
HOT 60OUL 0.15 123 2 SAI TSH
+1.24 TSH TSH
.23 18.37 151 HOT 580PP 57 85 0.53 132 P 5 TWD 35 DBH
-1.90 TO+1.90 DBH DBH 167 COLD 560P2 0.46 38 P 3 TWD 27 DBH
+1.91 TEC TEH 6
HOT 600UL 0.24 49 P 3 TWD 18 DBH
-1.56 TEC TEH 6
HOT 600UL 57 87 0.70 132 P 5 TWD 40 DBH
-2.00 TO+2.00 DBH DBH 167 COLD 560P2 0.73 25 P 3 TWD 34 DBH
+1.71 TEC TEH 6
HOT 600UL 57 89 0.68 44 P 3 TWD 24 DBC
+1.93 TEC TEH 5
HOT 60OUL 1.10 90 P 5 TWD 44 DBH
-1.70 TO+2.00 DBH DBH 168 COLD 560P2 0.52 106 P 5 TWD 32 DBC
+1.75 DEC DEC 168 COLD 560P2 0.62 74 P 3 TWD 23 DBH
-1.74 TEC TEH 5
HOT 600UL 0.66 121 P 3 TWD 24 DBH
+1.36 TEC TEH 5
HOT 60OUL 57 97 0.53 16 P 3 TWD 19 DBH
+1.61 TEC TEH 9
HOT 600UL 0.44 121 P 5 TWD 29 DBH
+1.78 DBH DBH 168 COLD 560P2 57 103 0.37 13 2
SAI TSH
-8.31 TSH TSH 0.0 19.22 156 HOT 580PP 57 119 0.43 23 P 1 MCI TSH
-0.09 TSH TSH 0.31 17.75 162 HOT 580PP 57___151____0.28____135___P__1____C____T__H__+0.04_____TEE___TEE___0.51____18.14_____196___HOT____580___2 57 151 0.28 135 P 1 SCI TSH
+0.04 TSH TSH 0.51 18.14 196 HOT 580PP 57 159 0.31 121 P 2 TWD 14 VH3
-0.86 TEC TEH 21 HOT 60OUL 57 167 0.48 137 P 2 TWD 22 02C
+0.87 TEC TEH 25 HOT 600UL 0.37 76 P 5 TWD 23 02C
+0.83 02C 02C 137 COLD 580PP 0.25 82 P 5 TWD 17 02C
+0.06 02C 02C 137 COLD 580PP 58 32 0.30 88 P 2 TWD 14 VH3
-0.93 TEC TEH 14 HOT 600UL 58 82 0.32 140 P 5 TWD 28 DBC
-1.98 TO+1.90 DBC DEC 166 COLD 560P2 0.20 176 P 3 TWD 12 DEC
+2.00 STH TEC 59 COLD 600UL 0.34 81 P 3 TWD 19 DBC
+1.25 STH TEC 59 COLD 600UL 58 84 1.28 126 P 5 TWD 50 DBH
-2.00 TO+2.00 DBH DBH 167 COLD 560P2 0.42 144 P 5 TWD 30 DBC
-1.60 TO+1.90 DEC DBC 167 COLD 560P2 0.78 14 P 3 TWD 27 DBH
-2.00 TO+2.00 TEC TEH 5
HOT 600UL 0.14 152 P 3 TWD 7 DEC
-1.75 TEC TEH 5
HOT 600UL 0.51 83 P 3 TWD 20 DBC
+1.95 TEC TEH 5
HOT 60OUL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 3/7/2004 1:56:06 PM Component: S/G 88 Page 12 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 58 86 0.33 131 P 5 TWD 26 DBC
+1.85 DBC DBC 167 COLD 560P2 1.60 78 P 5 TWD 54 DBH
+0.00 TO+2.00 DBH DBH 174 COLD 560P2 1.65 68 P 3 TWD 39 DBH
+1.01 TEC TEH 5
HOT 60OUL 0.53 172 P 3 TWD 21 DBC
+1.82 TEC TEH 5
HOT 600UL 58 88 0.30 144 P 5 TWD 27 DBC
-1.63 DBC DBC 166 COLD 560P2 0.41 123 P 3 TWD 22 DBC
-1.63 STH TEC 59 COLD 600UL 58 96 0.19 115 P 3 TWD 15 DBH
-1.70 TEC TEH 10 HOT 60OUL 0.43 121 P 5 TWD 29 DBH
-1.75 DBH DBH 168 COLD 560P2 58 116 0.21 101 P 2 TWD 14 VC3
+0.84 TEH TEC 6
COLD 600UL 59 23 0.48 123 P 2 TWD 19 VH3
-0.92 TEC TEH 7
HOT 600UL 59 25 0.36 131 P 2 TWD 18 VH3
-1.01 TEC TEH 8
HOT 600UL 0.36 162 P 2 TWD 18 VH3
+0.89 TEC TEH 8
HOT 60OUL 59 27 0.24 134 P 2 TWD 10 VH3
-1.14 TEC TEH 7
HOT 600UL 59 33 2.67 29 2
SAI TSH
-9.50 TSH TSH 3.27 17.46 171 HOT 580PP 59 57 0.34 57 P 2 TWD 17 02H
-1.13 TEH TEC 28 COLD 600UL 59 63 0.31 105 P 2 TWD 17 VSM
+0.89 TEH TEC 30 COLD 600UL 59 65 0.16 96 2
SAI TSH
+1.04 TSH TSH 0.21 20.70 208 HOT 580PP 59 85 0.84 135 P 5 TWD 43 DBC
-1.90 TO+1.90 DBC DBC 167 COLD 560P2 0.37 59 P 3 TWD 15 DBC
-1.78 TEC TEH 5
HOT 600UL 1.00 130 P 3 TWD 30 DBC
+1.72 TEC TEH 5
HOT 600UL 59 87 0.37 14 2
SAI TSH
-3.86 TSH TSH 0.23 19.56 150 HOT 58OPP 0.59 131 P 5 TWD 37 DBH
-1.80 DBH DBH 167 COLD 560P2 0.76 114 P 3 TWD 26 DBH
-1.80 TEC TEH 5
HOT 60OUL 59 91 0.15 114 2 MAI TSH
+0.98 TSH TSH 0.0 18.51 151 HOT 580PP 59 95 0.20 96 P 3 TWD 15 DBC
+1.93 TEC TEH 6
HOT 600UL 0.36 134 P 5 TWD 28 DBC
+1.93 DBC DBC 168 COLD 560P2 59 99 0.20 118 P 2 TWD 15 01H
-0.17 TEC TEH 10 HOT 600UL 59 157 0.32 94 P 2 TWD 15 VH3
-0.92 TEC TEH 21 HOT 600UL 59 161 0.37 88 P 2 TWD 16 VH3
-0.86 TEC TEH 21 HOT 600UL 60 92 0.41 20 2
SAI TSH
-0.38 TSH TSH 0.49 19.42 150 HOT 58OPP 60 116 0.47 29 P 1 MCI TSH
+0.00 TSH TSH 0.37 19.06 162 HOT 580PP 60 126 0.40 20 P 1 MCI TSH
-0.13 TSH TSH 0.65 18.04 165 HOT 58OPP 60 134 0.72 23 P 1 SCI TSH
-9.25 TSH TSH 0.75 18.41 182 HOT 58OPP 61 27 0.37 39 P 2 TWD 18 VH3
-1.07 TEC TEH 8
HOT 600UL 61 31 0.26 119 P 2 TWD 11 VH3
+1.00 TEC TEH 13 HOT 600UL 61 61 0.28 147 P 2 TWD 15 VH3
+0.80 TEH TEC 30 COLD 600UL 61 77 0.14 104 2 MAI TSH
+0.71 TO+1.46 TSH TSH 0.0 18.38 151 HOT 580PP 61 85 0.45 134 P 5 TWD 32 DBC
-1.90 TO+1.90 DBC DBC 167 COLD 560P2 0.57 169 P 3 TWD 21 DBC
+1.88 TEC TEH 5
HOT 600UL 61 99 0.14 107 P 1 SCI TSH
+0.03 TSH TSH 0.16 18.19 144 HOT 58OPP 61 125 0.26 119 P 2 TWD 14 VC3
-0.10 TEH TEC 3
COLD 600UL 0.43 31 P 2 TWD 21 02H
-1.14 TEH TEC 3
COLD 600UL 0.26 90 P 5 TWD 20 VC3
+0.18 VC3 VC3 169 COLD 560P2 62 24 0.29 125 P 2 TWD 14 VH3
+0.12 TEC TEH 7
HOT 600UL 62____1___8__0.20______168____P___3__TWO_____16_____BC____+1.48______TEC____TEE____22______OT____________
62 158 0.20 168 P 3 TWD 16 DBC
+1.48 TEC TEH 22 HOT 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodes and 0-100%twd.qry 3/7/2004 1:56:06 PM Component: S/G 88 Page 13 of 29 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG 63 81 0.30 18 2
SAI TSH
-1.86 TSH TSH 0.0 18.77 151 HOT PROBE 580_PP 63 87 0.69 134 P 5 TWD 41 DBH
-0.58 TO+1.97 DBH DBH 166 COLD 560P2 0.80 21 P 3 TWD 32 DBH
+1.97 STH TEC 59 COLD 600UL 63 91 0.43 16 2
SAI TSH
-1.22 TSH TSH
.44 18.16 151 HOT 58OPP 64 26 0.30 85 P 2 TWD 13 03H
-1.22 TEC TEH 7
HOT 600UL 64 56 0.34 14 2
SAI TSH
-1.22 TSH TSH 0.0 20.09 203 HOT 58OPP 64 66 0.69 13 2
SAI TSH
-3.84 TSH TSH 0.62 20.73 208 HOT 58OPP 64 78 0.17 95 2
MAI TSH
+0.67 TSH TSH 0.31 18.48 151 HOT 58OPP 64 80 0.34 131 P 5 TWD 27 DBH
-1.85 TO+1.85 DBH DBH 167 COLD 560P2 0.38 106 P 3 TWD 16 DBH
+1.28 TEC TEH 5
HOT 60OUL 64 110 0.44 18 2
SAI TSH
-10.93 TSH TSH 0.91 19.54 158 HOT 58OPP 0.50 16 2
SAI TSH
-10.76 TSH TSH 0.94 19.54 158 HOT 580PP 64__120__0.20__129__P_2_TW_________3_-0.53__________TEE________TEC_______3_____COLD_________6____0_____L_
64 120 0.20 129 P 2 TWD 11 VH3
-0.53 TEH TEC 3
COLD 600UL 64 158 0.44 54 P 2 TWD 19 VH3
-0.94 TEC TEH 21 HOT 600UL 0.65 139 P 2 TWD 24 VH3
+0.73 TEC TEH 21 HOT 600UL 65___47__0.69___25__P_____SCI___TSR__-22.79______TSR____TS_____0.47_____29.98______203____HOT____________
65 47 0.69 25 P I SCI TSH
-12.79 TSH TSH 0.47 19.98 203 HOT 580PP 65 53 2.59 38 P 1 SCI TSH
-12.74 TSH TSH 4.87 19.98 203 HOT 580PP 65 81 0.28 139 P 5 TWD 23 DBC
-2.00 TO+2.00 DBC DBC 167 COLD 560P2 0.14 101 P 3 TWD 7 DBC
-1.32 TEC TEH 5
HOT 600UL 65 85 0.63 135 P 5 TWD 38 DEC
-2.00 TO+2.00 DBC DBC 167 COLD 560P2 0.46 91 P 3 TWD 27 DBC
-1.75 TEC TEH 6
HOT 600UL 0.37 173 P 3 TWD 24 DBC
+1.75 TEC TEH 6
HOT 600UL 65 97 0.28 92 P 2 TWD 15 02H
-1.23 TEC TEH 9
HOT 600UL 65 113 0.95 31 P 1 MCI SBH
-0.54 SBH SBH 2.39 6.63 340 HOT 520ET 0.39 24 P 1 SCI SBH
-0.96 SBH SBH 0.00 340 HOT 520ET 65 115 0.27 15 P 1 SCI SBH
-3.22 SBH SBH 0.00 340 HOT 520ET 1.36 34 P 1 MCI SBH
-0.35 SBH SBH 3.05 6.62 340 HOT 520ET 65 149 0.19 155 P 1 SCI TSH
+0.02 TSH TSH 0.00 18.34 194 HOT 580PP 66 18 0.53 34 P 2 TWD 23 VH3
+0.67 TEC TEH 8
HOT 600UL 66 48 0.26 97 P 5 TWD 18 VSM
+0.92 VSM VSM 152 COLD 560P2 0.36 98 P 5 TWD 23 VSM
-0.77 VSM VSM 152 COLD 560P2 0.53 116 P 2 TWD 23 VSM
-0.78 TEC TEH 129 HOT 600UL 0.28 144 P 2 TWD 15 VSM
+0.84 TEC TEH 129 HOT 600UL 66 124 0.37 80 P 2 TWD 21 VH3
-0.73 TEH TEC 4
COLD 600UL 66 142 0.35 21 P 3 TWD 22 DBC
+0.79 TEC TEH 16 HOT 600UL 67 11 0.59 79 P 2 TWD 22 VH3
-0.83 TEC TEH 1
HOT 600UL 67 25 0.32 53 P 2 TWD 17 06H
+0.77 TEC TEH 8
HOT 60OUL 67___53__0.45___21__P__1____C___TSR__-12.20______TSR____TSR____0.00_____21.04______204____ROT____________
67 53 0.45 21 P 1 SCI TSH
-12.20 TSH TSH 0.00 21.04 204 HOT 580PP 67 57 0.51 21 P 1 MCI TSH
-0.15 TSH TSH 0.0 20.08 203 HOT 580PP 67 81 0.38 146 P 5 TWD 29 DBC
-2.00 TO+2.00 DBC DBC 167 COLD 560P2 0.35 113 P 3 TWD 23 DBC
-1.55 TEC TEH 6
HOT 600UL 67 85 0.66 137 P 5 TWD 39 DBC
-1.90 TO+0.00 DBC DBC 167 COLD 560P2 0.65 84 P 3 TWD 24 DBC
-1.74 TEC TEH 5
HOT 60OUL 67 87 0.31 0.30 0.27 0.19 133 P 5 TWD 25 DBH 138 P 5 TWD 25 DEH 56 P 3 TWD 12 DBH 69 P 3 TWD 9 DEH
-1.65
+1.75
+1.32
-1.76 DBH DBH DEH DBH TEC TEH TEC TEH 167 COLD 560P2 167 COLD 560P2 5
HOT 600UL 5
HOT 60OUL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 3/7/2004 1:56:06 PM Component: S/G 88 Page 14 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-========================-
-=======-=======-=====-========-===
67 91 0.26 57 P 1 SCI TSH
+0.14 TSH TSH 1.09 18.19 151 HOT 580PP 67 97 0.25 54 P 2 TWD 18 021
-1.25 TEC TEE 10 HOT 600UL 67 103 0.21 23 P 1 SCI TSH
-0.08 TSH TSH 0.00 19.14 156 HOT 5S8OPP 67 115 0.32 119 2 SAI 02H
-13.72 02H 02H 0.37 248 HOT 580PP 67 129 0.24 146 P 2 TWD 13 VH3
+0.04 TEH TEC 3
COLD 600UL 0.18 108 2 SAI VH3
+0.03 VH3 VH3 169 COLD 560P2 67 155 0.35 161 P 3 TWD 24 DBC
+0.68 TEC TEH 22 HOT 600UL 67 157 0.32 92 P 2 TWD 15 VH3
-0.80 TEC TEH 21 HOT 60OUL 67 165 0.71 114 P 2 TWD 28 VH3
-0.88 TEC TEH 25 HOT 600UL 0.43 79 P 5 TWD 27 VH3
-0.80 VH3 VH3 173 COLD 560P2 68 92 0.33 98 P 2 TWD 16 01H
+0.88 TEC TEH 5
HOT 600UL 0.25 134 2 SAI TSH
+0.46 TSH TSH 0.0 18.35 151 HOT 580PP 68 94 0.24 104 2 SAI TSH
+0.77 TSH TSH 0.25 19.69 150 HOT 580PP 0.14 91 2
SAI TSH
+1.18 TSH TSH 0.00 19.69 150 HOT 580PP 68 114 0.33 19 P 1 SCI TSH
-10.55 TSH TSH 0.37 19.98 158 HOT 580PP 68 146 0.43 78 P 2 TWD 20 VC3
-0.88 TEC TEH 15 HOT 600UL 0.34 87 P 5 TWD 22 VC3
-0.92 VC3 VC3 173 COLD 560P2 69 13 0.70 86 P 2 TWD 24 VH3
+0.85 TEC TEH 1
HOT 60OUL 0.59 115 P 2 TWD 22 VH3
-0.87 TEC TEH 1
HOT 600UL 69__17__0.53__131__P_2__TWO__20____3_-0.78__________TEC_________TEN________7____ROT______________________
69 17 0.53 131 P 2 TWD 20 VH3
-0.78 TEC TEH 7
HOT 600UL 69 19 0.50 133 P 2 TWD 20 VH3
+0.72 TEC TEH 7
HOT 600UL 69 85 0.27 149 P 5 TWD 23 DBC
-1.75 DBC DBC 167 COLD 560P2 0.17 147 P 3 TWD 13 DBC
-1.42 TEC TEH 6
HOT 600UL 69 101 0.37 22 P 1 SCI TSH
-0.02 TSH TSH 0.72 19.04 145 HOT 580PP 69 127 1.13 20 2
SAI TSH
-12.49 TSH TSH 1.75 18.15 170 HOT 580PP 69 149 0.12 114 2 SAI 03H
+2.26 03H 03H 0.15 271 HOT 580PP 69 163 0.31 58 P 2 TWD 14 VSM
+0.82 TEC TEH 21 HOT 600UL 0.36 109 P 2 TWD 16 VH3
+0.73 TEC TEH 21 HOT 600UL 70 22 0.43 109 P 2 TWD 20 06H
+0.83 TEC TEH 8
HOT 600UL 70 24 0.34 79 P 3 TWD 15 DBH
+1.78 TEC TEH 7
HOT 600UL 70 50 0.13 89 2
SAI 02H
+5.04 02H 02H 0.12 203 HOT 580PP 70 82 0.27 139 P 5 TWD 22 DBC
+1.70 DBC DBC 167 COLD 560P2 0.21 153 P 3 TWD 16 DBC
+1.75 TEC TEH 6
HOT 600UL 70 84 0.12 80 2
SAI TSH
+1.46 TSH TSH 0.0 18.45 151 HOT 580PP 70 86 0.27 140 P 5 TWD 23 DBH
-1.50 DBH DBH 167 COLD 560P2 0.21 137 P 5 TWD 19 DBH
+1.50 DBH DBH 167 COLD 560P2 0.22 93 P 3 TWD 16 DBH
-1.25 TEC TEH 6
HOT 600UL 70 108 0.64 27 P 1 SCI TSH
-0.04 TSH TSH 0.42 19.21 156 HOT 580PP 71__13__0.49__125__P_2__TWO__19__V_3_-0.80__________TEC________T____________1____NOT_____________________
71 13 0.49 125 P 2 TWD 19 VH3
-0.80 TEC TEH 7
HOT 600UL 71 19 0.40 147 P 2 TWD 16 VH3
-0.80 TEC TEH 7
HOT 600UL 71 39 0.21 115 2 SAI 02H
+0.77 02H 02H
.52 263 HOT 580PP 71 85 0.86 126 P 5 TWD 44 DBC
-2.00 TO+1.90 DBC DBC 167 COLD 560P2 0.91 70 P 3 TWD 29 DBC
-1.58 TEC TEH 5
HOT 600UL 0.33 58 P 2 TWD 16 03H
-1.20 TEC TEH 5
HOT 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-li QUERY: rpc_icodesand 0-100%twd.qry 3/7/2004 1:56:06 PM Component: S/G 88 Page 15 of 29 ROW LINE 71 97 VOLTS 0._20 DEG 34 CHN P 2 IND TWD
%TW 11 LOCATION EXT EXT 01H
+0.91 TEC TEH UTIL 1 UTIL 2
CAL 9
LEG HOT PROBE 60OUL 71 113 0.38 26 P 1 SCI TSH
-10.72 TSH TSH 0.65 19.38 157 HOT 58OPP 0.45 32 P 1 MCI TSH
-10.09 TSH TSH 0.46 157 HOT 580PP 71 155 0.20 112 2 SAI 07H
-0.43 07H 07H 0.26 223 HOT 58OPP 72 24 0.50 94 P 2 TWD 22 06H
+0.77 TEC TEH 8
HOT 600UL 0.18 119 2 SAI 06H
+0.76 06H 06H 0.0 263 HOT 58OPP 72 28 0.32 153 P 2 TWD 13 VH3
-1.25 TEC TEH 13 HOT 60OUL 72 70 0.34 59 P 2 TWD 17 VC3
-0.71 TEH TEC 31 COLD 60OUL 72 80 0.24 166 P 3 TWD 11 DBH
+1.88 TEC TEH 5
HOT 600UL 72 88 0.46 110 P 3 TWD 27 DBC
-1.82 TEC TEH 6
HOT 60OUL 0.55 135 P 5 TWD 35 DBC
-1.82 DBC DBC 168 COLD 560P2 72 90 0.33 143 P 2 TWD 20 VSM
+0.62 TEC TEH 6
HOT 60OUL 0.30 108 P 5 TWD 20 VSM
+0.97 VSM VSM 168 COLD 560P2 0.15 119 P 5 TWD 12 VSM
-0.97 VSM VSM 168 COLD 560P2 72 98 0.32 77 P 2 TWD 20 02H
-1.19 TEC TEH 10 HOT 600UL 72 160 0.28 120 2 SAI 03H
-0.41 03H 03H 0.36 223 HOT 580PP 0.43 80 P 2 TWD 18 03H
-1.13 TEC TEH 21 HOT 60OUL 73 17 0.42 128 P 2 TWD 18 VH3
-0.86 TEC TEH 7
HOT 600UL 73 73 0.37 47 P 2 TWD 19 VC3
+0.38 TEH TEC 34 COLD 60OUL 0.73 112 P 2 TWD 30 VSM
+0.90 TEH TEC 34 COLD 600UL 0.46 94 P 5 TWD 29 VSM
+0.97 VSM VSM 153 COLD 560P2 0.37 93 P 5 TWD 25 VC3
+0.22 VC3 VC3 153 COLD 560P2 73 97 0.29 98 2
SAI TSH
+0.51 TSH TSH 0.58 18.41 145 HOT 580PP 73 125 0.29 106 P 2 TWD 16 VSM
+0.76 TEH TEC 3
COLD 600UL 73 133 0.33 99 P 5 TWD 22 VH3
+0.93 VH3 VH3 172 COLD 560P2 0.30 103 P 2 TWD 20 VH3
+0.87 TEC TEH 12 HOT 60OUL 73 163 0.69 24 P 2 TWD 25 VH3
-0.84 TEC TEH 21 HOT 60OUL 74 74 0.17 124 P 1 SCI TSH
+0.03 TSH TSH 0.00 17.83 219 HOT 580PP 74 82 0.36 142 P 5 TWO 28 VSM
+0.84 VSM VSM 167 COLD 560P2 0.24 147 P 5 TWD 21 VSM
-0.98 VSM VSM 167 COLD 560P2 0.13 136 P 5 TWD 13 VSM
+0.00 VSM VSM 167 COLD 560P2 0.51 138 P 2 TWD 29 VSM
+0.84 TEC TEH 6
HOT 60OUL 0.24 116 P 2 TWD 18 VSM
-0.98 TEC TEH 6
HOT 60OUL 74 120 0.50 17 P 1 SCI TSH
-11.24 TSH TSH 0.72 18.93 165 HOT 580PP 74 146 0.69 124 P 2 TWD 32 VC3
+0.91 TEC TEH 16 HOT 60OUL 0.51 65 P 2 TWD 27 VC3
-0.99 TEC TEH 16 HOT 60OUL 0.46 136 P 2 TWD 26 VH3
-0.77 TEC TEH 16 HOT 60OUL 0.44 91 P 5 TWD 26 VH3
-0.89 VH3 VH3 173 COLD 560P2 0.48 101 P 5 TWD 32 VC3
+0.88 VC3 VC3 175 COLD 560P2 0.34 98 P 5 TWD 26 VC3
-0.85 VC3 VC3 175 COLD 560P2 74 148 0.16 103 P 5 TWD 10 VH3
-0.89 VH3 VH3 173 COLD 560P2 0.17 122 P 2 TWD 11 VH3
-0.95 TEC TEH 20 HOT 600UL 75 17 0.28 127 P 2 TWD 15 VH3
-0.81 TEC TEH 8
HOT 600UL 75 55 0.17 104 2 SAI 02H
+3.78 TO+14.34 02H 02H 0.24 204 HOT 58OPP 0.38 128 P 3 TWD 15 DBH
+1.94 TEH TEC 27 COLD 60OUL 75 97 0.52 85 2
MAI TSH
+0.31 TSH TSH 0.43 18.12 144 HOT 580PP 0.28 101 2 MAI TSH
+0.56 TSH TSH 0.30 18.12 144 HOT 580PP 75 119 0.59 12 2
SAI TSH
-7.24 TSH TSH 0.22 17.23 161 HOT 580PP 75 139 0.98 92 P 2 TWD 33 VSM
-0.02 TEC TEH 15 HOT 60OUL 0.31 128 P 2 TWD 15 VH3
+0.76 TEC TEH 15 HOT 60OUL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 3/7/2004 1:56:06 PM Component:
S/G 88 Page 16 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.19 19 P 2 TWD 9 VH3
-0.92 TEC TEH 15 HOT 600UL 0.78 82 P 5 TWD 39 VSM
+0.12 VSM VSM 173 COLD 560P2 0.26 142 P 5 TWD 21 VH3
+0.89 VH3 VH3 173 COLD 560P2 0.15 138 P 5 TWD 13 VH3
-0.85 VH3 VH3 173 COLD 560P2 75 141 0.20 131 P 5 TWD 16 VH3
-0.91 VH3 VH3 173 COLD 560P2 0.25 132 P 2 TWD 20 VH3
-0.89 TEC TEH 16 HOT 600UL 76 26 0.30 132 2 SAI 08H
-0.24 08H 08H
.54 263 HOT 580PP 76 34 0.28 91 P 2 TWD 10 01H
+1.19 TEC TEH 13 HOT 600UL 76 62 0.46 12 2
SAI 08H
-0.02 08H 08H 0.50 208 HOT 58OPP 76 84 0.14 115 P 5 TWD 14 VH3
+0.90 VH3 VH3 167 COLD 560P2 0.19 127 P 5 TWD 18 VH3
-0.90 VH3 VH3 167 COLD 560P2 0.30 73 P 2 TWD 15 VH3
-0.86 TEC TEH 5
HOT 600UL 0.22 83 P 2 TWD 12 VH3
+0.84 TEC TEH 5
HOT 60OUL 76 86 0.27 140 P 5 TWD 23 DBC
+1.75 DBC DBC 167 COLD 560P2 0.18 162 P 3 TWD 8 DBC
+2.00 TEC TEH 5
HOT 60OUL 76 88 0.39 68 P 2 TWD 19 03H
-1.25 TEC TEH 5
HOT 600UL 76 100 0.25 58 P 2 TWD 14 VC3
-0.88 TEC TEH 9
HOT 600UL 76__124__0.22__96__P_2__TWO__12__VC3_-0.74__________TEE________TEC_______3_____COLD_________60______UL___
76 124 0.22 96 P 2 TWD 12 VC3
-0.74 TEH TEC 3
COLD 600UL 76 134 0.37 126 P 2 TWD 17 VH3
+0. 69 TEC TEH 11 HOT 600UL 77 19 0.25 129 P 2 TWD 13 VH3
+0.81 TEC TEH 8
HOT 600UL 77____31____0.41_____147_____P__2___TWO_____16___V___M___+0.80______TEC____TEE_____13____HOT_____________
77 31 0.41 147 P 2 TWD 16 VSM
+0.80 TEC TEH 13 HOT 600UL 0.28 90 P 2 TWD 12 VSM
+0.29 TEC TEH 13 HOT 600UL 0.15 61 P 5 TWD 11 VSM
+0.38 VSM VSM 154 COLD 560P2 0.25 94 P 5 TWD 19 VSM
+0.89 VSM VSM 154 COLD 560P2 77 33 0.62 87 P 2 TWD 22 VSM
+0.80 TEC TEH 13 HOT 600UL 0.30 104 P 5 TWD 22 VSM
+0.79 VSM VSM 154 COLD 560P2 77 39 0.36 166 P 3 TWD 19 DBC
+1.62 TEC TEH 18 HOT 600UL 0.30 95 P 5 TWD 20 DBC
+1.59 DBC DBC 152 COLD 560P2 77 91 0.14 87 P 1 SCI TSH
+0.08 TSH TSH 0.30 19.60 150 HOT 58OPP 77 125 0.15 9
P 3 TWD 8 DBH
-2.24 TEH TEC 3
COLD 600UL 77 159 0.27 88 P 2 TWD 12 VH3
-0.82 TEC TEH 21 HOT 60OUL 78 22 0.39 49 P 3 TWD 18 DBC
-1.88 TEC TEH 8
HOT 600UL 0.60 86 P 2 TWD 25 VC3
-0.89 TEC TEH 8
HOT 600UL 0.51 97 P 5 TWD 29 DBC
-1.80 DBC DBC 151 COLD 560P2 0.44 104 P 5 TWD 27 VC3
-0.82 VC3 VC3 161 COLD 560P2 78 32 0.19 68 P 3 TWD 10 DBC
-1.38 TEC TEH 14 HOT 60OUL 0.11 90 P 5 TWD 8 DBC
-1.22 DBC DBC 154 COLD 560P2 78 68 0.42 18 P 1 SCI TSH
-0.14 TSH TSH 0.40 17.82 207 HOT 580PP 78 80 0.63 26 P 1 SCI TSH
-0.06 TSH TSH 0.53 18.40 151 HOT 58OPP 78 120 0.27 114 P 2 TWD 16 VC3
+0.84 TEH TEC 4
COLD 600UL 78 136 0.21 116 P 5 TWD 15 DBH
-2.15 DBH DBH 172 COLD 560P2 0.29 58 P 3 TWD 20 DBH
-2.15 TEC TEH 12 HOT 600UL 78 138 0.21 103 P 5 TWD 15 DBC
+1.70 DBC DBC 173 COLD 560P2 0.19 17 P 3 TWD 15 DBC
+1.74 TEC TEH 12 HOT 600UL 78 142 0.36 97 P 5 TWD 23 VH3
+0.92 VH3 VH3 173 COLD 560P2 0.24 129 P 2 TWD 16 VH3
+0.89 TEC TEH 16 HOT 600UL 78 144 0.39 56 P 3 TWD 24 DBC
+1.84 TEC TEH 16 HOT 600UL 0.41 86 P 5 TWD 25 DBC
+1.64 DBC DBC 173 COLD 560P2 78 148 0.28 73 P 5 TWD 22 08C
-0.83 08C 08C 136 COLD 58OPP
Framatome ANP Inc.
3/7/2004 1:56:06 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 17 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.33 145 P 2 TWD 20 08C
-0.84 TEC TEH 20 HOT 60OUL 78__154__0.18__139__P_5_TWO__16__VC3_-0.85___________C3________C3______175_______COLD___________6____P2__
78 154 0.18 139 P 5 TWD 16 VC3
-0.85 VC3 VC3 175 COLD 560P2 0.27 133 P 5 TWD 22 VC3
+0.86 VC3 VC3 175 COLD 560P2 0.31 150 P 2 TWD 19 VC3
+0.87 TEC TEH 20 HOT 60OUL 79 15 0.42 21 P 3 TWD 17 DBH
+1.46 TEC TEH 1
HOT 600UL 0.19 88 P 5 TWD 16 DBH
+1.49 DBH DBH 146 COLD 560P2 79 19 0.25 69 P 3 TWD 11 DBC
+1.75 TEC TEH 7
HOT 600UL 0.31 91 P 5 TWD 20 DBC
+1.76 DBC DBC 151 COLD 560P2 79 23 0.28 65 P 3 TWD 12 DBC
+1.75 TEC TEH 7
HOT 600UL 0.37 100 P 5 TWD 23 DBC
+1.80 DBC DBC 151 COLD 560P2 79 27 0.21 111 2 SAI 06H
-0.16 06H 06H 0.0 263 HOT 580PP 79 75 0.41 74 P 2 TWD 18 VH3
+0.80 TEH TEC 33 COLD 600UL 79 143 0.14 121 P 3 TWD 11 DBC
-1.41 TEC TEH 16 HOT 600UL 0.18 105 P 5 TWD 12 DBC
-1.57 DBC DBC 173 COLD 560P2 79 155 0.28 145 P 2 TWD 13 VSM
+0.74 TEC TEH 21 HOT 600UL 80 78 0.35 91 P 1 SCI TSH
+0.07 TSH TSH 0.23 19.30 150 HOT 580PP 80 80 0.29 98 P 2 TWD 15 VSM
-0.82 TEC TEH 5
HOT 60OUL 80 86 0.49 22 P 1 SCI TSH
-0.02 TSH TSH 0.61 19.18 150 HOT 580PP 0.17 121 P 5 TWD 16 DBC
+2.00 DBC DBC 167 COLD 560P2 0.15 147 P 3 TWD 7 DBC
+2.00 TEC TEH 5
HOT 600UL 80 88 0.16 97 P 3 TWD 12 DBC
-1.75 TEC TEH 6
HOT 600UL 0.14 147 P 5 TWD 14 DBC
-1.75 DBC DBC 168 COLD 560P2 80 104 0.28 82 P 2 TWD 14 VH3
+1.13 TEH TEC 7
COLD 60OUL 0.28 20 P 1 SCI TSH
-0.10 TSH TSH 0.16 19.80 152 HOT 580PP 80 112 0.22 105 P 5 TWD 16 VSM
-0.81 VSM VSM 169 COLD 560P2 0.33 120 P 2 TWD 19 VSM
-0.68 TEH TEC 5
COLD 60OUL 80 120 0.16 102 2 SAI 02H
-7.76 02H 02H 0.25 248 HOT 580PP 81 23 0.39 36 P 3 TWD 16 DBC
+1.84 TEC TEH 23 HOT 600UL 0.32 97 P 5 TWD 21 DBC
+1.55 DBC DBC 157 COLD 560P2 81 109 0.37 84 P 3 TWD 17 DBC
+1.82 TEH TEC 16 COLD 60OUL 81 151 0.29 105 P 5 TWD 16 VH3
+0.63 VH3 VH3 350 HOT 560P2 0.18 92 P 5 TWD 10 VH3
-0.23 VH3 VH3 350 HOT 560P2 0.25 119 P 2 TWD 17 VH3
+0.60 TEC TEH 37 HOT 600UL 82 54 0.55 133 P 2 TWD 24 VH3
-0.92 TEH TEC 35 COLD 600UL 0.14 103 P 2 TWD 8 VH3
+1.17 TEH TEC 35 COLD 600UL 0.42 91 P 5 TWD 27 VH3
-0.94 VH3 VH3 336 HOT 560P2 0.23 89 P 5 TWD 17 VH3
+1.12 VH3 VH3 336 HOT 560P2 82 82 0.33 14 P 1 SCI TSH
-13.89 TSH TSH 0.86 18.12 274 HOT 580PP 82 84 0.63 22 P 1 MCI TSH
-13.09 TSH TSH 0.68 18.35 278 HOT 580PP 82 104 0.33 36 P 1 SCI TSH
-0.09 TSH TSH 0.38 18.24 294 HOT 580PP 82 114 0.56 19 P 1 SCI TSH
-0.08 TSH TSH 0.32 19.83 286 HOT 580PP 82 160 0.34 121 P 3 TWD 13 DBH
+1.65 TEC TEH 36 HOT 60OUL 0.32 93 P 5 TWD 17 DBH
+2.23 DBH DBH 350 HOT 560P2 83 59 0.24 16 P 1 SCI TSH
-0.17 TSH TSH 0.07 18.76 308 HOT 580PP 83 63 0.49 22 P 1 SCI TSH
-0.12 TSH TSH 0.51 18.97 312 HOT 580PP 83 121 0.46 16 P 1 SCI TSH
-9.02 TSH TSH 0.45 19.91 280 HOT 580PP 84____48____0.37_____79____P__2___TWO_____19___09C_____+0.16______TE______TEC____34____COLD_____6___00L__
84 48 0.37 79 P 2 TWD 19 09C
+0.16 TEH TEC 34 COLD 600UL
Framatome ANP Inc.
3/7/2004 1:56:06 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 18 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 84 114 0.32 131 P 2 TWD 17 09C
+0.00 TEH TEC 15 COLD 600UL 85 91 0.36 73 P 2 TWD 19 09H
-1.22 TEH TEC 51 COLD 600UL 85 95 0.36 23 P 1 SCI TSH
-0.23 TSH TSH 0.0 18.57 288 HOT 58OPP 85 119 0.42 91 P 2 TWD 21 09H
+1.65 TEH TEC LOCOK 12 COLD 600UL 85 123 0.35 107 P 2 TWD 18 09C
+1.16 TEH TEC 12 COLD 60OUL 85 127 0.23 37 P 3 TWD 10 DBH
-1.77 TEH TEC 10 COLD 60OUL 85 141 0.32 131 P 2 TWD 21 09H
+1.19 TEC TEH 32 HOT 60OUL 86 32 0.24 165 P 3 TWD 9 DBC
+1.02 TEC TEH 27 HOT 60OUL 0.24 94 P 5 TWD 14 DBC
+1.45 DBC 09C 156 COLD 560P2 86 112 0.39 51 P 2 TWD 19 VH2
+0.73 TEH TEC 15 COLD 60OUL 86 130 0.21 125 P 2 TWD 15 VC2
+0.74 TEC TEH 30 HOT 600UL 87 29 0.36 162 P 3 TWD 17 DBC
+1.96 TEC TEH 24 HOT 60OUL 87 35 0.54 145 P 2 TWD 18 VH2
-0.96 TEC TEH 27 HOT 600UL 87 37 0.23 57 P 2 TWD 10 VH2
+0.79 TEC TEH 28 HOT 60OUL 0.37 119 P 2 TWD 16 VH2
-0.93 TEC TEH 28 HOT 60OUL 87 39 0.24 131 P 2 TWD 11 VH2
-1.24 TEC TEH 28 HOT 600UL 87 43 0.32 170 P 3 TWD 18 DBH
+1.29 TEC TEH 28 HOT 600UL 87 59 0.92 29 P 1 SCI TSH
-10.53 TSH TSH 1.19 18.77 308 HOT 580PP 87 83 0.40 18 P 1 SCI TSH
-16.77 TSH TSH 0.23 17.87 274 HOT 580PP 87 125 0.43 96 P 2 TWD 20 VH2
-0.89 TEH TEC 10 COLD EQOUL 87 129 0.41 148 P 2 TWD 19 VH2
-0.85 TEH TEC 10 COLD 600UL 88 34 0.36 142 P 2 TWD 13 VH2
-1.14 TEC TEH 27 HOT 600UL 88 48 0.45 89 P 2 TWD 22 VH2
-0.77 TEH TEC 34 COLD 60OUL 88 52 0.15 163 P 3 TWD 10 DBH
+1.85 TEH TEC 36 COLD 600UL 88 108 0.32 82 P 2 TWD 17 VH2
-0.87 TEH TEC 17 COLD 60OUL 88 150 0.26 15 P 2 TWD 17 06H
-0.41 TEC TEH LAR 37 HOT 60OUL 0.23 108 P 5 TWD 13 06H
-0.38 06H 06H 226 HOT 58OPP 89 33 0.36 118 P 2 TWD 15 VH2
-0.99 TEC TEH 28 HOT 600UL 89 35 0.50 117 P 2 TWD 17 VH2
-0.98 TEC TEH 27 HOT 60OUL 89 37 0.70 138 P 2 TWD 21 VH2
-1.24 TEC TEH 27 HOT 60OUL 89 45 0.35 51 P 2 TWD 15 VH2
-1.24 TEC TEH 28 HOT 60OUL 89 57 0.25 158 P 3 TWD 15 DBH
+1.55 TEH TEC 36 COLD 60OUL 89 73 0.35 126 P 2 TWD 17 VC2
-0.73 TEH TEC 40 COLD 60OUL 89 99 0.70 23 P 1 MCI TSH
-0.10 TSH TSH 0.36 18.62 293 HOT 580PP 89__123__0.39__113__P_2_TWO__20____2_-0.79_________TEE________TEC_______12______COLD___________________L_
89 123 0.39 113 P 2 TWD 20 VH2
-0.79 TEH TEC 12 COLD 600UL 89 125 0.34 59 P 2 TWD 19 VH2
-0.82 TEH TEC 11 COLD 600UL 89 127 0.40 135 P 2 TWD 19 VH2
-0.79 TEH TEC 10 COLD 600UL 89__137__0.22__84__P_2__TWO__16__V_2_-0.94__________TEC________TEE_______30______HOT_____________________
89 137 0.22 84 P 2 TWD 16 VH2
-0.94 TEC TEH 30 HOT 60OUL 89__143__0.30__76__P_2__TWO__14__V_2_-0.81__________TEC________TEE_______31______HOT_____________________
89 141 0.22 69 P 2 TWD 16 VH2
+0.73 TEC TEH 32 HOT 600UL 89 143 0.30 76 P 2 TWD 14 VH2
-0.81 TEC TEH 31 HOT 600UL
Framatome ANP Inc.
3/7/2004 1:56:06 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 19
- MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-========================-
-=======-=======-=====-========-===
89 157 0.38 162 P 3 TWD 14 DBH
+1.37 TEC TEH 36 HOT 60OUL 0.27 90 P 5 TWD 14 DBH
+1.82 DBH DBH 350 HOT 560P2 90 22 0.47 137 P 2 TWD 19 07C
-1.12 TEC TEH 23 HOT 600UL 90 78 0.47 103 P 2 TWD 22 03H
-1.15 TEH TEC 48 COLD 60OUL 90 94 0.54 66 P 2 TWD 22 03H
-1.25 TEH TEC 52 COLD 60OUL 91 23 0.41 112 P 2 TWD 17 VH2
-0.98 TEC TEH 23 HOT 60OUL 91 53 0.34 88 P 2 TWD 17 02H
+0.84 TEH TEC 35 COLD 600UL 91 97 0.69 23 P 1 SCI TSH
-0.08 TSH TSH 0.81 18.37 292 HOT 580PP 91 129 0.22 29 P 3 TWD 10 DBH
-1.81 TEH TEC 10 COLD 600UL 92 26 0.52 62 P 2 TWD 23 VH2
-0.75 TEC TEH 24 HOT 60OUL 92 32 0.45 143 P 2 TWD 15 VSM
-0.83 TEC TEH 27 HOT 60OUL 92 36 0.85 93 P 2 TWD 24 VH2
-1.22 TEC TEH 27 HOT 600UL 92 46 0.26 139 P 2 TWD 12 VSM
+0.76 TEC TEH 28 HOT 600UL 93 27 0.35 113 P 2 TWD 17 VH2
-0.91 TEC TEH 24 HOT 60OUL 93 31 0.53 141 P 2 TWD 17 VH2
-1.22 TEC TEH 27 HOT 600UL 93 33 0.38 98 P 2 TWD 16 VH2
-1.03 TEC TEH 28 HOT 60OUL 93 51 0.36 109 P 2 TWD 19 VH2
-0.78 TEH TEC 36 COLD 600UL 93 55 0.24 80 2
SAI 04H
-0.15 04H 04H 0.00 302 HOT 580PP 93 139 0.29 142 P 2 TWD 19 VH2
-0.89 TEC TEH 32 HOT 600UL 93 153 0.12 100 P 5 TWD 11 03C
+0.90 03C 03C 136 COLD 580PP 0.35 91 P 5 TWD 25 05C
-0.92 05C 05C 136 COLD 580PP 0.29 100 P 2 TWD 19 03C
+0.92 TEC TEH 37 HOT 600UL 0.31 40 P 2 TWD 20 05C
+0.00 TEC TEH 37 HOT 600UL 94 24 0.43 114 P 2 TWD 18 VH2
+0.20 TEC TEH 23 HOT 600UL 94 32 0.17 82 2
SAI 06H
+0.66 06H 06H 0.19 267 HOT 580PP 0.51 46 P 2 TWD 17 06H
+0.02 TEC TEH 27 HOT 600UL 0.68 129 P 2 TWD 21 VH2
-1.12 TEC TEH 27 HOT 600UL 0.42 119 P 2 TWD 14 06H
+0.61 TEC TEH 27 HOT 600UL 94 36 0.69 77 P 2 TWD 21 VH2
-1.25 TEC TEH 27 HOT 60OUL 94 84 0.21 102 P 2 TWD 12 VH3
+0.84 TEH TEC 48 COLD 600UL 95 25 0.63 119 P 2 TWD 24 VH2
-1.14 TEC TEH 23 HOT 600UL 0.26 116 P 5 TWD 18 03H
+0.76 03H 03H 267 HOT 580PP 95 33 0.39 109 2 SAI 06H
-0.03 06H 06H 0.00 267 HOT 580PP 95 39 0.39 120 P 2 TWD 14 VSM
+0.63 TEC TEH 27 HOT 600UL 96 142 0.23 110 P 2 TWD 16 VH2
-0.93 TEC TEH 32 HOT 60OUL 96 150 0.31 131 P 2 TWD 20 VH2
-0.82 TEC TEH 37 HOT 600UL 97 109 0.39 102 2 SAI 06C
-8.38 06C 06C 0.33 137 COLD 580PP 97 139 0.24 73 P 2 TWD 16 VSM
-0.21 TEC TEH 32 HOT 60OUL 98 30 0.29 103 2 SAI 06H
+0.79 06H 06H 0.63 267 HOT 580PP 98 56 3.20 33 P 1 SCI TSH
-14.48 TSH TSH 4.03 18.41 305 HOT 580PP 98 74 0.19 157 P 2 TWD 11 VC2
+0.77 TEH TEC 39 COLD 600UL 98__130__0.21__43__P_2__TWO__15__V_2_-0.95____________EC______TEN_______30______NOT______________________
98 130 0.21 43 P 2 TWO 15 VH2
-0,95 TEC TEH 30 HOT 600UL of 29
Framatome ANP Inc.
3/7/2004 1:56:07 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 20 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
=--====-======-===-===-===-===-========================-s
-=======-=======-=====-========-===
99 75 0.76 24 P 1 SCI TSH
-0.11 TSH TSH 0.00 18.42 317 HOT 580PP 99 121 0.23 87 P 2 TWD 14 VH2
-0.90 TEH TEC 13 COLD 600UL 99 123 0.19 119 P 2 TWD 11 VC2
+0.75 TEH TEC 13 COLD 600UL 99 131 0.34 119 P 2 TWD 22 VH3
-0.81 TEC TEH 30 HOT 60OUL 0.22 99 P 5 TWD 12 VH3
+0.88 VH3 VH3 350 HOT 560P2 0.35 96 P 5 TWD 18 VH3
-0.86 VH3 VH3 350 HOT 560P2 100 150 0.39 52 P 2 TWD 23 VH2
+0.90 TEC TEH 37 HOT 600UL 101 27 0.50 138 P 2 TWD 20 VH2
+0.59 TEC TEH 23 HOT 60OUL 101 147 0.37 92 P 5 TWD 21 VSM
-0.66 VSM VSM 350 HOT 560P2 0.46 61 P 2 TWD 20 VSM
-0.66 TEC TEH 31 HOT 60OUL 102 26 0.30 74 P 5 TWD 16 06H
+0.81 06H 06H 267 HOT 580PP 0.37 111 P 2 TWD 18 06H
+0.81 TEC TEH 24 HOT 60OUL 102 140 0.25 91 P 3 TWD 18 DBC
+1.91 TEC TEH 32 HOT 60OUL 0.35 61 P 2 TWD 22 VH2
-0.98 TEC TEH 32 HOT 60OUL 104 40 0.45 170 P 3 TWD 23 DBC
+2.06 TEC TEH 28 HOT 600UL 0.33 64 P 5 TWD 19 DBC
+2.13 DBC DBC 156 COLD 560P2 106 30 0.35 109 P 2 TWD 15 06H
+0.76 TEC TEH 23 HOT 60OUL 0.28 80 P 5 TWD 15 06H
+0.83 06H 06H 267 HOT 580PP 106 78 0.19 96 P 5 TWD 12 VC2
+1.05 VC2 VC2 157 COLD 560P2 0.23 82 P 5 TWD 14 VC2
-0.66 VC2 VC2 APN 157 COLD 560P2 0.26 148 P 2 TWD 14 VC2
+0.94 TEC TEH 129 HOT 60OUL 0.20 156 P 2 TWD 11 VC2
-0.76 TEC TEH 129 HOT 60OUL 106 140 0.35 122 P 3 TWD 23 DBC
+1.68 TEC TEH 32 HOT 60OUL 107 29 0.29 70 P 5 TWD 20 DBC
+1.67 DBC DBC APN 157 COLD 560P2 0.49 163 P 3 TWD 22 DBC
+1.72 TEC TEH 24 HOT 60OUL 107 97 0.18 99 P 5 TWD 13 VH3
-0.86 VH3 VH3 356 HOT 560P2 0.23 126 P 2 TWD 12 VH3
-0.86 TEH TEC 53 COLD 60OUL 107 125 0.15 66 P 3 TWD 7 DBH
-1.42 TEH TEC 10 COLD 600UL 0.15 84 P 5 TWD 9 DBH
-1.55 DBH DBH 355 HOT 560P2 108 36 0.32 93 P 5 TWD 19 DBC
-1.94 DBC DBC 157 COLD 560P2 0.33 106 P 3 TWD 19 DBC
-1.40 TEC TEH 28 HOT 600UL 110 138 0.26 124 P 2 TWD 18 VC3
-0.96 TEC TEH 30 HOT 60OUL 0.29 98 P 5 TWD 21 VC3
-0.90 VC3 VC3 163 COLD 560P2 110 144 0.35 158 P 3 TWD 23 DBC
+2.24 TEC TEH 32 HOT 60OUL 111 33 0.39 101 P 2 TWD 14 03H
-0.77 TEC TEH 27 HOT 60OUL 111 37 0.43 38 P 3 TWD 15 DBH
+1.51 TEC TEH 27 HOT 60OUL 0.35 95 P 5 TWD 24 DBH
+1.80 DBH DBH 325 HOT 560P2 111 39 0.36 173 P 3 TWD 20 DBH
+1.55 TEC TEH 28 HOT 60OUL 111 101 0.19 50 P 3 TWD 7 DBH
-0.69 TEH TEC 52 COLD 60OUL 0.18 100 P 5 TWD 13 DBH
-0.95 DBH DBH 356 HOT 560P2 112 116 0.20 118 P 2 TWD 12 VH3
-0.83 TEH TEC 15 COLD 60OUL 0.16 101 P 5 TWD 9 VH3
-0.77 VH3 VH3 AIC 355 HOT 560P2 112 144 0.48 98 P 5 TWD 24 DBH
+2.00 DBH DBH 350 HOT 560P2 0.55 165 P 3 TWD 19 DBH
+1.83 TEC TEH 31 HOT 60OUL 113 37 0.26 126 P 2 TWD 11 VH2
-0.99 TEC TEH 28 HOT 60OUL 0.18 96 P 5 TWD 14 VH2
-0.99 VH2 VH2 325 HOT 560P2 113 39 0.51 116 P 3 TWD 18 DBH
+1.19 TEC TEH 27 HOT 60OUL 0.46 96 P 5 TWD 29 DBH
+2.00 DBH DBH 325 HOT 560P2
Framatome ANP Inc.
3/7/2004 1:56:07 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 21 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 113 41 0.71 103 P 2 TWD 22 VH2
-0.60 TEC TEH 27 HOT 600UL 0.35 94 P 5 TWD 25 VH2
-0.74 VH2 VH2 AIC 327 HOT 560P2 114 38 0.34 150 P 2 TWD 12 06C
-0.83 TEC TEH 27 HOT 600UL 114 96 0.17 88 P 5 TWD 12 VH3
-0.82 VH3 VH3 356 HOT 560P2 0.28 123 P 2 TWD 14 VH3
-0.82 TEH TEC 53 COLD 60OUL 114 110 0.27 55 P 3 TWD 16 DBH
-1.42 TEN TEC 15 COLD 60OUL 0.33 91 P 5 TWD 18 DBH
-1.42 DBH DBH 352 HOT 560P2 115 41 0.39 163 P 3 TWD 21 DBC
+1.53 TEC TEH 28 HOT 60OUL 115 53 0.24 64 P 2 TWD 13 02H
+0.92 TEH TEC 35 COLD 600UL 115 69 0.32 37 P 2 TWD 16 01H
+0.83 TEN TEC 40 COLD 60OUL 115 109 0.30 79 P 2 TWD 15 01H
+0.88 TEN TEC 17 COLD 60OUL 115 129 0.29 107 P 2 TWD 15 VH2
-0.74 TEN TEC 10 COLD 600UL 116 68 0.29 42 P 2 TWD 15 08H
-1.10 TEN TEC 39 COLD 600UL 116 102 0.33 131 P 3 TWD 16 DBH
+0.57 TEN TEC 16 COLD 60OUL 0.25 99 P 5 TWD 14 DBH
+0.62 DBH 10H 367 HOT 560P2 117 49 0.11 118 2 SAI 06H
+2.77 06H 06H 0.11 300 HOT 58OPP 117 71 0.46 111 P 2 TWD 21 VH1
-0.83 TEN TEC 39 COLD 600UL 117 115 0.30 50 P 2 TWD 16 01H
+0.86 TEN TEC 15 COLD 60OUL 118 88 0.20 141 P 3 TWD 8 DBH
-1.71 TEN TEC 50 COLD 600UL 0.14 103 P 5 TWD 10 DBH
-1.75 DBH DBH 354 HOT 560P2 118 90 0.17 22 P 3 TWD 8 DBH
-1.70 TEN TEC 50 COLD 60OUL 119 37 0.19 115 P 5 TWD 11 DBC
+1.94 DBC DBC 157 COLD 560P2 0.30 95 P 5 TWD 18 DBC
-1.74 DBC DBC 157 COLD 560P2 0.51 18 P 3 TWD 18 DBC
+1.57 TEC TEN 27 HOT 600UL 0.22 19 P 3 TWD 9 DBC
-1.78 TEC TEN LAR 27 HOT 600UL 119 41 0.44 146 P 2 TWD 18 09H
-1.07 TEC TEN 28 HOT 600UL 0.41 144 P 2 TWD 17 VH1
-1.13 TEC TEH 28 HOT 600UL 119 45 0.41 152 P 2 TWD 17 VH1
-0.97 TEC TEE 28 HOT 600UL 119 55 0.34 80 P 5 TWD 23 DBH
+2.14 DBH DBH 336 HOT 560P2 0.29 68 P 3 TWD 13 DBH
+2.09 TEN TEC 35 COLD 600UL 119 57 0.43 39 P 2 TWD 20 01H
-0.29 TEN TEC 35 COLD 600UL 119 59 0.31 105 P 2 TWD 17 VH1
-1.03 TEN TEC 37 COLD 60OUL 119 61 0.38 144 P 2 TWD 19 VHI
-0.89 TEH TEC 38 COLD 60OUL 119__63__0.60__128__P_2_TWO__26__VN1_-0.96_________TEN________TEC_______38______COLD_________60________L_
119 63 0.60 128 P 2 TWD 26 VH1
-0.96 TEH TEC 38 COLD 60OUL 119 65 0.43 142 P 2 TWD 21 VH1
-0.96 TEN TEC 38 COLD 600UL 119__69__0.38_139__P_2__TWO_18_______-0.84_________TEN________TEC_______40______COLD_________6____0____L_
119 67 0.40 136 P 2 TWD 20 VH1
-0.77 TEN TEC 38 COLD 600UL 119 69 0.38 139 P 2 TWD 18 VH1
-0.84 TER TEC 40 COLD 600UL 119 71 0.42 148 P 2 TWD 19 VH1
-0.84 TEH TEC 40 COLD 600UL 119 79 0.45 98 P 5 TWD 30 DBH
+1.98 DBH DBH 354 HOT 560P2 0.35 92 P 3 TWD 17 DBH
+2.00 TEN TEC 48 COLD 60OUL 119 81 0.51 105 P 2 TWD 23 VH1
-0.95 TEN TEC 48 COLD 60OUL 119 95 0.42 115 P 3 TWD 15 DBH
-0.81 TEN TEC 52 COLD 60OUL 0.42 107 P 2 TWD 18 VH1
-0.99 TEN TEC 52 COLD 60OUL 0.44 97 P 5 TWD 25 DBH
-1.60 DBH DBH 356 HOT 560P2 119 97 0.42 69 P 2 TWD 18 VHI
-0.95 TEN TEC 52 COLD 600UL of 29
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 3/7/2004 1:56:07 PM Component: S/G 88 Page 22 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.33 128 P 3 TWD 12 DBH
-1.70 TEH TEC 52 COLD 60OUL 0.26 104 P 5 TWD 17 DBH
-1.70 DBH DBH 356 HOT 560P2 119 99 0.33 86 P 3 TWD 12 DBH
-1.42 TEH TEC 52 COLD 60OUL 0.44 127 P 2 TWD 19 VH1
-0.98 TEH TEC 52 COLD 60OUL 0.31 100 P 5 TWD 20 DBH
-1.90 DBH DBH 356 HOT 560P2 119 101 0.26 134 P 3 TWD 7 DBH
-1.75 TEH TEC 52 COLD 600UL 0.37 96 P 5 TWD 23 DBH
-1.75 DBH DBH 356 HOT 560P2 119 109 0.47 11 P 3 TWD 24 DBH
+1.87 TEH TEC LAR 17 COLD 600UL 0.34 97 P 5 TWD 18 DBH
+1.91 DBH DBH 352 HOT 560P2 119 111 0.52 138 P 3 TWD 26 DBH
+2.04 TEH TEC 15 COLD 60OUL 0.48 73 P 2 TWD 22 VH1
-0.64 TEH TEC 15 COLD 60OUL 0.40 105 P 5 TWD 21 DBH
+2.04 DBH DBH 352 HOT 560P2 120 38 0.31 93 P 5 TWD 19 DBC
+2.11 DBC 10C 157 COLD 560P2 0.24 89 P 5 TWD 15 DBC
-1.68 DBC 10C 157 COLD 560P2 0.29 134 P 3 TWD 11 DBC
+1.83 TEC TEH 27 HOT 600UL 0.25 97 P 3 TWD 10 DBC
-1.63 TEC TEH 27 HOT 60OUL 120 42 0.41 128 P 2 TWD 17 VHI
-1.17 TEC TEH 28 HOT 60OUL 120 50 0.31 153 P 2 TWD 16 VH1
-0.86 TEH TEC 34 COLD 60OUL 120 66 0.61 88 P 5 TWD 33 DBH
-2.07 DBH 10H 336 HOT 560P2 0.43 117 P 3 TWD 21 DBH
-1.34 TEH TEC 38 COLD 600UL 120 74 0.25 97 P 2 TWD 13 10H
-1.23 TEH TEC 40 COLD 60OUL 0.23 104 P 5 TWD 15 10H
-1.18 10H 10H 317 HOT 58OPP 120 80 0.49 80 P 5 TWD 24 DBH
-1.86 VH1 09H ARS 195 HOT 560P2 0.23 41 P 3 TWD 12 DBH
-1.90 TEH TEC 48 COLD 600UL 120 86 0.22 63 P 3 TWD 10 DBH
-0.99 TEH TEC 50 COLD 60OUL 0.28 133 P 2 TWD 13 10H
+1.25 TEH TEC 50 COLD 600UL 0.37 74 P 5 TWD 20 DBH
-1.75 VH1 09H 195 HOT 560P2 0.27 85 P 5 TWD 15 10H
+1.50 VH1 09H 195 HOT 560P2 120 88 0.29 52 P 2 TWD 16 03H
-0.12 TEH TEC AAS 51 COLD 60OUL 120 92 0.31 101 P 3 TWD 12 DBH
-2.14 TEH TEC 50 COLD 600UL 0.34 98 P 5 TWD 21 DBH
-1.92 DBH DBH 356 HOT 560P2 120 94 0.11 112 P 3 TWD 8 DBH
-1.79 TEH TEC 53 COLD 600UL 0.23 69 P 5 TWD 13 DBH
-1.77 VH1 09H 195 HOT 560P2 120 106 0.47 23 P 3 TWD 21 DBH
+1.64 TEH TEC 16 COLD 600UL 0.52 77 P 5 TWD 25 DBH
+1.94 DBH DBH 352 HOT 560P2 120 114 0.23 93 P 3 TWD 15 DBH
-1.85 TEH TEC 15 COLD 600UL 120 120 0.25 93 P 2 TWD 14 VHI
-0.82 TEH TEC 12 COLD 600UL 120 138 0.49 96 P 5 TWD 25 DBH
-2.03 10H DBH 350 HOT 560P2 0.45 108 P 3 TWD 18 DBH
-1.57 TEC TEH 29 HOT 600UL 121 39 0.24 122 P 5 TWD 18 03C
-0.99 03C 03C 135 COLD 580PP 0.56 94 P 2 TWD 18 03C
-0.94 TEC TEH 27 HOT 600UL 121 43 0.53 157 P 2 TWD 20 VH1
-0.95 TEC TEH 28 HOT 600UL 121 59 0.46 142 P 2 TWD 22 VHI
-0.96 TEH TEC 38 COLD 60OUL 121 67 0.18 107 P 5 TWD 15 DBH
-1.97 DBH 10H 336 HOT 560P2 0.13 43 P 3 TWD 7 DBH
-1.68 TEH TEC 37 COLD 600UL 121 75 0.41 133 P 2 TWD 20 VH1
-0.92 TEH TEC 40 COLD 600UL 121__83__0.44_113__P_2__TWO_22_____i_-0.92_________TEM________TEC_______49______COLD________________UL___
121 83 0.44 113 P 2 TWD 22 VH1
-0.92 TEH TEC 49 COLD 600UL 121_______103______0.41________120______P____2___TWO_______20_____VM1______17_____C____L______60_______L_
121 99 0.49 138 P 2 TWD 22 VH1
-0.94 TEH TEC 53 COLD 600UL 121 103 0.41 120 P 2 TWD 20 VH1 0.32 79 P 2 TWD 16 VH1
-0.83 TEH TEC
+0.85 TEH TEC 17 COLD 600UL 17 COLD 600UL
Framatome ANP Inc.
3/7/2004 1:56:07 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 23 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-===========_============-
-=======-=======-=====-========-===
121 107 0.44 79 P 2 TWD 22 VH1
-0.82 TEH TEC 16 COLD 600UL 121 115 0.46 115 P 2 TWD 22 VHI
-0.92 TEH TEC 15 COLD 60OUL 121 125 0.33 90 P 2 TWD 18 10H
+0.52 TEH TEC 11 COLD 600UL 0.29 91 P 5 TWD 20 10H
+0.62 10H 10H 277 HOT 580PP 121 137 0.22 89 P 5 TWD 12 DBH
-1.69 10H DBH 350 HOT 560P2 0.19 160 P 3 TWD 9 DBH
-1.57 TEC TEH 29 HOT 600UL 122 94 0.26 119 P 3 TWD 10 DBH
+1.72 TEH TEC 52 COLD 600UL 0.37 86 P 5 TWD 22 DBH
+1.72 DBH DBH 356 HOT 560P2 122 96 0.46 93 P 5 TWD 26 DBH
+1.91 DBH DBH 356 HOT 560P2 0.37 126 P 3 TWD 21 DBH
+1.91 TEH TEC 53 COLD 600UL 122 108 0.32 114 P 2 TWD 17 09H
-1.11 TEH TEC 17 COLD 600UL 122 112 0.19 33 P 2 TWD 11 10H
-1.16 TEH TEC 15 COLD 600UL 0.25 98 P 5 TWD 15 10H
-0.99 10H 10H 286 HOT 580PP 122 114 0.31 80 P 2 TWD 17 10H
+0.87 TEH TEC 14 COLD 60OUL 0.24 100 P 5 TWD 14 10H
+0.89 10H 10H 286 HOT 580PP 122 124 0.40 133 P 3 TWD 18 DBH
+1.70 TEH TEC 12 COLD 600UL 0.40 93 P 5 TWD 20 DBH
+1.76 10H DBH 352 HOT 560P2 123 57 0.26 40 P 2 TWD 14 04H
+0.92 TEH TEC 35 COLD 600UL 123 59 0.35 124 P 2 TWD 19 VH1
-0.88 TEH TEC 37 COLD 600UL 123 63 0.38 150 P 2 TWD 19 VH1
-0.96 TEH TEC 38 COLD 60OUL 123 65 0.31 95 P 5 TWD 22 DBH
-0.65 DBH DBH 336 HOT 560P2 0.30 135 P 3 TWD 16 DBH
-0.75 TEH TEC 38 COLD 60OUL 0.49 136 P 2 TWD 22 VH1
-0.92 TEH TEC 38 COLD 600UL 123 67 0.48 142 P 2 TWD 22 VH1
-0.92 TEH TEC 38 COLD 600UL 123 69 0.50 147 P 2 TWD 22 VH1
-0.80 TEH TEC 40 COLD 600UL 123 71 0.45 131 P 2 TWD 21 VH1
-0.84 TEH TEC 40 COLD 60OUL 123 73 0.32 44 P 2 TWD 16 01H
+1.13 TEH TEC 39 COLD 600UL 123 77 0.23 35 P 2 TWD 13 VH2
-0.70 TEH TEC 48 COLD 60OUL 123 95 0.56 156 P 2 TWD 22 VH1
-0.91 TEH TEC 52 COLD 600UL 123 97 0.51 131 P 2 TWD 21 VH1
-1.00 TEH TEC 52 COLD 600UL 123 99 0.59 116 P 2 TWD 23 VH1
-0.81 TEH TEC 52 COLD 60OUL 123 109 0.45 135 P 2 TWD 21 VH1
-0.90 TEH TEC 17 COLD 60OUL 123 111 0.49 34 P 3 TWD 25 DBH
+1.70 TEH TEC 15 COLD 600UL 123 123 123 123 113 117 121 129 0.46
- 0. 62 0.37 0.54 0.46 0.51 130 94 142 139 90 149 TWD TWD TWD TWD TWD TWD 22 28 19 24 23 23 VH1 DBH Vfll VH1 VHI VHI
-0. 98
+l. BB
-1.01
-0. 95
-0.96
-0.77 TEH TEC DBH DEH TEE TEC--
TEH TEC TEE TEC--
TEH TEC TEH TEC TEH TEC 15 352 15 15 13 10 COLD HOT COLD COLD--
COLD COLD COLD 60OUL 560P2 6000L
_ECOUL 600UL 60CUL 600UL W
124 64 0.38 89 P 5 TWD 24 1DH
-0.97 1DH iCH 311 HOT 58OPP 0.25 65 P 2 TWD 14 iCH
-0.86 TEH TEC 37 COLD 600UL 124 88 0.27 101 P 5 TWD 21 DBH
+2.01 DBH DEH 354 HOT 560P2 0.27 20 P 3 TWD 16 DBH
+2.01 TEH TEC 51 COLD 600UL 125 69 0.37 90 P 2 TWD 18 VH1
-0.92 TEH TEC 39 COLD 60OUL
Framatome ANP Inc.
3/7/2004 1:56:07 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 24 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 125 73 0.41 130 P 2 TWD 20 VHI
-0.04 TEH TEC 40 COLD 60OUL 125 75 0.42 117 P 2 TWD 20 VHl
+0.00 TEH TEC 40 COLD 600UL 125 83 0.55 122 P 3 TWD 27 DBH
+1.73 TEH TEC 49 COLD 600UL 0.40 106 P 2 TWD 21 VH1
-0.94 TEH TEC 49 COLD 60OUL 0.70 92 P 5 TWD 28 DBH
+1.73 VH1 10H 367 HOT 560P2 125 85 0.44 128 P 2 TWD 22 VHi
-0.88 TEH TEC 51 COLD 600UL 0.27 113 P 2 TWD 15 VH2
-0.80 TEH TEC 51 COLD 600UL 125 91 0.26 105 P 5 TWD 17 DBH
+1.96 DBH DBH 356 HOT 560P2 0.22 110 P 3 TWD 13 DBH
+1.96 TEH TEC 51 COLD 60OUL 125 97 0.50 123 P 2 TWD 23 VHl
-0.96 TEH TEC 53 COLD 60OUL 125 103 0.39 146 P 2 TWD 19 VHI
-0.85 TEH TEC 17 COLD 600UL 126 52 0.79 15 P 1 SCI TSH
-11.69 TSH TSH 1.34 18.33 300 HOT 580PP 126 62 0.54 96 P 5 TWD 30 10H
-1.07 10H 10H 308 HOT 580PP 126 86 0.50 95 P 5 TWD 31 DBH
+1.92 DBH DBH 354 HOT 560P2 0.27 108 P 3 TWD 16 DBH
+1.92 TEH TEC 51 COLD 600UL 126 90 0.33 110 P 3 TWD 14 DBH
+2.16 TEH TEC 50 COLD 600UL 0.44 96 P 5 TWD 26 DBH
+2.06 DBH DBH 356 HOT 560P2 126 112 0.42 29 P 3 TWD 23 DBH
+1.86 TEH TEC 15 COLD 60OUL 0.42 102 P 5 TWD 21 DBH
+1.84 DBH 10H 367 HOT 560P2 127 53 0.52 71 P 2 TWD 23 VH1
-0.98 TEH TEC 35 COLD 600UL 127 63 0.33 137 P 2 TWD 17 VH1
-0.92 TEH TEC 38 COLD 600UL 127 69 0.37 160 P 2 TWD 18 VH1
-0.84 TEH TEC 40 COLD 600UL 127 73 0.35 81 P 2 TWD 18 02H
+0.90 TEH TEC 39 COLD 600UL 127 75 0.56 144 P 2 TWD 24 VHI
-0.83 TEH TEC 39 COLD 600UL 0.22 140 P 2 TWD 12 VH1
+0.77 TEH TEC 39 COLD 600UL 127 95 0.52 141 P 2 TWD 20 VH1
-0.95 TEH TEC 52 COLD 600UL 127 97 0.41 152 P 2 TWD 18 VH1
-1.02 TEH TEC 52 COLD 600UL 127 99 0.46 66 P 2 TWD 20 VHI
-1.01 TEH TEC 52 COLD 600UL 127 101 0.20 50 P 2 TWD 10 VH3
+0.83 TEH TEC 52 COLD 600UL 127__105_0.46__121__P_2_TWO__21_V__i_-0.81_________TEE________TEC_______17______COLD___________00______L_
127 105 0.46 121 P 2 TWD 21 VH1
-0.81 TEH TEC 17 COLD 600UL 127--109 -0.40-140-
-p-2-TWO-19-V----
0.81----
-TEN---
-TEC 17---
COLD----
-600---
127 107 0.48 142 P 2 TWD 22 VH1
-0.88 TEH TEC 17 COLD 60OUL 127 109 0.40 140 P 2 TWD 19 VH1
-0.91 TEH TEC 17 COLD 600UL 127 111 0.42 145 P 2 TWD 21 VH1
-0.97 TEH TEC 15 COLD 600UL 127 117 0.28 120 P 2 TWD 15 VH1
+0.90 TEH TEC 15 COLD 600UL 0.44 135 P 2 TWD 21 VH1
-0.90 TEH TEC 13 COLD 60OUL 127 121 0.44 123 P 2 TWD 22 VH1
-1.05 TEH TEC 13 COLD 600UL 127 123 0.38 142 P 2 TWD 22 VH1
-0.92 TEC TEH 132 HOT 600UL 127 125 0.53 117 P 2 TWD 23 VH1
-0.87 TEH TEC 10 COLD 600UL 128 60 0.32 90 P 5 TWD 20 10H
+0.05 10H 10H 307 HOT 58OPP 0.30 87 P 5 TWD 19 10H
-1.08 10H 10H 307 HOT 58OPP 0.41 133 P 2 TWD 20 10H
-1.01 TEH TEC 38 COLD 600UL 0.24 32 P 2 TWD 13 10H
+0.00 TEH TEC 38 COLD 600UL 128 68 0.23 91 P 5 TWD 17 DBH
+1.84 DBH DBH 336 HOT 560P2 0.23 17 P 3 TWD 12 DBH
+1.86 TEH TEC 39 COLD 600UL 128 72 0.27 139 2 SAI 06H
+0.00 06H 06H 0.00 317 HOT 58OPP
Framatome ANP Inc.
3/7/2004 1:56:07 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 25 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-========================-
-=======-=======-=====-========-===
129 47 0.66 131 P 2 TWD 28 VH3
-0.84 TEH TEC 34 COLD 600UL 0.45 93 P 5 TWD 28 VH3
-1.17 VH3 VH3 336 HOT 560P2 129 63 0.20 94 P 5 TWD 14 10H
-0.17 10H 10H 312 HOT 580PP 129 67 0.33 98 P 5 TWD 22 DBH
-2.23 DBH DBH 336 HOT 560P2 0.35 47 P 3 TWD 17 DBH
-2.20 TEH TEC 37 COLD 600UL 129 71 0.45 111 P 2 TWD 21 VH1
-0.90 TEH TEC 39 COLD 60OUL 129 73 0.43 137 P 2 TWD 20 VH1
-0.83 TEH TEC 40 COLD 600UL 129 75 0.29 104 P 2 TWD 15 VHI
+0.86 TEH TEC 40 COLD 600UL 0.58 86 P 2 TWD 24 VH1
-0.77 TEH TEC 40 COLD 60OUL 129 81 0.17 122 2 SAI 08H
-0.24 08H 08H 0.38 274 HOT 580PP 129 87 0.37 138 P 2 TWD 20 VH1
-0.94 TEE TEC 51 COLD 600UL 129 93 0.18 83 2
SAI 08H
-0.44 08H 08H 288 HOT 580PP 0.18 108 2 SAI 08H
+0.54 08H 08H 288 HOT 580PP 0.12 108 2 SAI 08H
+0.53 08H 08H 0.00 292 HOT 580PP 0.17 85 2
SAI 08H
-0.51 08H 08H 0.00 292 HOT 580PP 129 95 0.45 117 P 2 TWD 21 VH1
-0.92 TEH TEC 53 COLD 600UL 0.30 80 P 3 TWD 18 DBH
+1.76 TEH TEC 53 COLD 600UL 0.40 91 P 5 TWD 24 DBH
+1.76 DBH DBH 356 HOT 560P2 0.16 86 2
MAI 06H
+3.10 TO+28.73 06H 06H 0.15 289 HOT 580PP 129 113 0.44 146 P 2 TWD 21 VH1
-0.99 TEH TEC 15 COLD 600UL 129 119 0.46 85 P 2 TWD 22 VH1
-0.98 TEH TEC 12 COLD 600UL 129 121 0.36 156 P 2 TWD 19 VH1
-0.88 TEH TEC 12 COLD 600UL 129 123 0.34 100 P 2 TWD 18 VH1
-0.89 TEH TEC 12 COLD 60OUL 130 74 0.40 90 P 5 TWD 27 10H
-1.06 10H 10H 318 HOT 580PP 130 94 0.37 94 P 5 TWD 24 10H
-0.99 10H 10H 326 HOT 580PP 130 106 0.35 118 P 2 TWD 17 VH1
-0.70 TEH TEC 17 COLD 600UL 130 128 0.36 85 P 2 TWD 20 VH2
+0.40 TEH TEC 11 COLD 600UL 0.26 86 P 5 TWD 14 VH2
-0.49 VH2 VH2 352 HOT 560P2 131 67 0.47 101 P 2 TWD 21 10H
-1.02 TEH TEC 41 COLD 600UL 0.34 85 P 2 TWD 17 10H
+0.06 TEH TEC 41 COLD 60OUL 131 77 0.51 95 P 5 TWD 23 DBH
+1.99 DBH DBH 357 HOT 560P2 0.47 21 P 3 TWD 21 DBH
+1.99 TEH TEC 44 COLD 600UL 131 83 0.49 97 P 5 TWD 22 DBH
-2.28 TO+1.89 DBE DBH 357 HOT 560P2 0.20 133 P 3 TWD 11 DBH
-1.85 TEH TEC 44 COLD 60OUL 131 89 0.52 99 P 2 TWD 26 10H
+0.97 TEH TEC 44 COLD 60OUL 0.45 98 P 5 TWD 23 10H
+0.82 10H 10H AIC 301 HOT 580PP 131 115 0.45 108 P 2 TWD 22 VHl
-1.02 TEH TEC 46 COLD 600UL 131 125 0.48 84 P 2 TWD 23 VH1
-0.92 TEH TEC 46 COLD 60OUL 131 127 0.33 86 P 5 TWD 25 03C
+0.91 03C 03C 136 COLD 580PP 0.47 106 P 2 TWD 24 03C
+0.95 TEH TEC 47 COLD 600UL 132 94 0.38 95 P 5 TWD 20 10H
+0.80 10H 10H 306 HOT 580PP 0.55 43 P 2 TWD 27 10H
+0.97 TEH TEC 44 COLD 600UL 133 61 0.33 99 P 2 TWD 17 VHl
-0.86 TEC TEH 129 HOT 600UL 133 65 0.37 144 P 2 TWD 18 VH1
-0.75 TEH TEC 43 COLD 600UL 133 67 0.35 148 P 2 TWD 17 VH1
-0.85 TEH TEC 43 COLD 600UL 133__71__0.46__145__p_2_TWO__21______-0.81_________TEE________TEC_______43______COLD________________U____
133 71 0.46 145 P 2 TWD 21 VH1
-0.81 TEH TEC 43 COLD 600UL
Framatome ANP Inc.
3/7/2004 1:56:07 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 26 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-=============s==========-
-=======-=======-=====-========-===
133 75 0.47 97 P 5 TWD 24 DBH
+2.00 DBH DBH 357 HOT 560P2 0.33 96 P 3 TWD 15 DBH
+1.85 TEE TEC 41 COLD 60OUL 133 79 0.43 129 P 2 TWD 23 VH1
-0.93 TEH TEC 44 COLD 600UL 133 81 0.30 128 P 2 TWD 18 VH1
-0.92 TER TEC 44 COLD 60OUL 133 83 0.41 90 P 5 TWD 23 10H
-1.01 10H 10H 332 HOT 580PP 133 87 0.38 88 P 2 TWD 19 VH1
-1.12 TER TEC 45 COLD 600UL 133 97 0.16 123 2 SAI 05H
+4.49 TO+7.27 05H 05H 0.00 310 HOT 58OPP 0.12 110 2 SAI 07H
-11.10 07H 07H 0.00 310 HOT 580PP 0.12 104 2 SAI 07H
-17.27 07H 07H 0.28 310 HOT 580PP 133 105 0.42 120 P 2 TWD 21 VH1
-0.91 TEE TEC 46 COLD 60OUL 133 115 0.21 99 P 5 TWD 12 10H
+0.77 10H 10H 316 HOT 58OPP 0.40 97 P 2 TWD 20 10H
+0.92 TEE TEC 46 COLD 60OUL 134 68 0.21 98 P 5 TWD 12 10H
-0.71 10H 10H 320 HOT 580PP 0.27 127 P 2 TWD 14 10H
-0.71 TEH TEC 41 COLD 600UL 134 84 0.25 125 P 2 TWD 13 10H
-1.11 TEH TEC 45 COLD 600UL 0.32 100 P 5 TWD 18 10H
-1.08 10H 10H 301 HOT 580PP 134 86 0.44 99 P 5 TWD 23 10H
-1.02 10H 10H AIC 301 HOT 580PP 134 100 0.30 94 P 5 TWD 16 10H
+0.86 10H 10H 310 HOT 580PP 0.30 82 P 2 TWD 16 10H
+0.99 TER TEC 45 COLD 600UL 135 77 0.32 145 P 2 TWD 19 VH1
-0.79 TEH TEC 44 COLD 600UL 135 81 0.29 99 P 5 TWD 14 VH1
-0.83 VH1 VH1 357 HOT 560P2 0.28 56 P 2 TWD 15 07H
+0.80 TEE TEC 45 COLD 60OUL 0.12 90 2
SAI 07H
+0.55 07H 07H 0.00 298 HOT 58OPP 0.10 95 2
SAI 07H
+0.75 07H 07H 0.00 298 HOT 580PP 135 83 0.17 101 2 MAI 08H
+0.21 08H 08H 0.0 301 HOT 580PP 0.11 88 2
SAI 08H
+0.81 08H 08H 0.45 301 HOT 58OPP 135 85 0.43 106 P 2 TWD 23 VH1
+0.00 TEH TEC 44 COLD 600UL 135 87 0.33 100 P 5 TWD 18 10H
-1.06 10H 10H AIC 301 HOT 580PP 135 91 0.37 107 P 2 TWD 18 VH1
-1.08 TEE TEC 45 COLD 600UL 135 93 0.21 90 P 5 TWD 13 10H
+0.80 10H 10H 332 HOT 580PP 0.36 62 P 2 TWD 18 10H
+0.91 TEE TEC 45 COLD 600UL 135 97 0.21 35 P 2 TWD 13 10H
+0.97 TEE TEC 44 COLD 60OUL 0.14 100 P 5 TWD 8 10H
-1.03 10H 10H 310 HOT 580PP 0.19 103 P 5 TWD 11 10H
+0.84 10H 10H 310 HOT 58OPP 135 119 0.40 134 P 2 TWD 20 VH1
-1.03 TEH TEC 46 COLD 600UL 136 74 0.35 122 P 2 TWD 18 10H
-1.01 TEH TEC 43 COLD 600UL 0.44 93 P 5 TWD 22 10H
-1.04 10H 10H 298 HOT 580PP 136 86 0.41 135 P 2 TWD 22 10H
-1.10 TEE TEC 44 COLD 600UL 0.42 83 P 5 TWD 22 10H
-1.06 10H 10H AIC 301 HOT 58OPP 136 110 0.17 93 P 2 TWD 12 VH1
+1.12 TEC TEH 132 HOT 600UL 137 67 0.33 139 P 2 TWD 17 VH1
-0.80 TEE TEC 43 COLD 600UL 137 79 0.43 96 P 2 TWD 23 VH1
-0.88 TEE TEC 44 COLD 600UL 137 83 0.37 146 P 2 TWD 18 VH1
-0.86 TEH TEC 45 COLD 60OUL 137 91 0.39 94 P 5 TWD 16 10H
-0.95 10H 10H 324 HOT 58OPP 137 119 0.23 90 P 5 TWD 19 01C
-0.94 01C 01C 136 COLD 580PP 0.33 75 P 2 TWD 19 01C
-0.98 TEH TEC 47 COLD 600UL
Framatome ANP Inc.
3/7/2004 1:56:07 PM Customer Name: San Onofre -
Unit 2 Component: S/G 88 Page 27 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 138 74 0.27 91 P 2 TWD 14 VH1
-0.77 TEH TEC 41 COLD 600UL 138 78 0.34 46 P 2 TWD 20 VH1
-0.81 TEH TEC 44 COLD 600UL 139 71 0.38 137 P 2 TWD 18 VH1
-0.94 TEH TEC 41 COLD 600UL 139 77 0.45 128 P 2 TWD 24 VH1
-0.81 TEH TEC 44 COLD 60OUL 139 83 0.41 67 P 2 TWD 22 VH1
-1.01 TEH TEC 44 COLD 600UL 139 85 0.34 74 P 2 TWD 20 VH1
-1.04 TEH TEC 44 COLD 60OUL 139 105 0.47 71 P 2 TWD 24 10H
+0.98 TEH TEC 47 COLD 60OUL 0.36 121 P 2 TWD 20 VH1
-0.98 TEH TEC 47 COLD 60OUL 0.35 94 P 5 TWD 19 10H
+0.84 10H 10H 313 HOT 58OPP 140 66 0.22 123 P 3 TWD 14 DBH
+2.09 TEH TEC 43 COLD 600UL 0.57 15 P 3 TWD 27 DBC
+1.67 TEH TEC LAR 43 COLD 60OUL 0.70 78 P 5 TWD 37 DBC
+1.77 DBC DBC 162 COLD 560P2 0.23 93 P 5 TWD 13 DBH
+1.95 DBH DBH 359 HOT 560P2 140 76 0.16 103 P 5 TWD 7 DBH
-1.75 DBH DBH 357 HOT 560P2 0.18 93 P 3 TWD 12 DBH
-1.75 TEH TEC 45 COLD 60OUL 140 88 0.29 97 P 5 TWD 14 DBH
+1.94 DBH DBH 357 HOT 560P2 0.21 121 P 3 TWD 12 DBH
+1.94 TEH TEC 44 COLD 600UL 141 63 0.40 81 P 5 TWD 24 DBC
+1.58 DBC DBC 162 COLD 560P2 0.41 32 P 3 TWD 17 DBC
+1.37 TEH TEC 41 COLD 60OUL 141 65 0.22 80 P 5 TWD 18 08C
+0.85 08C 08C ASR 136 COLD 580PP 0.31 113 P 2 TWD 15 08C
+0.74 TEH TEC 41 COLD 600UL 141 67 0.62 107 P 2 TWD 26 VC1
+0.86 TEH TEC 43 COLD 600UL 0.33 143 P 2 TWD 17 VHI
-0.84 TEH TEC 43 COLD 600UL 0.43 96 P 5 TWD 28 VCI
+0.86 VC1 VC1 162 COLD 560P2 141 77 0.40 82 P 5 TWD 26 DBC
+1.88 DBC DBC 162 COLD 560P2 0.20 139 P 2 TWD 11 VC1
+0.88 TEH TEC 45 COLD 600UL 0.29 108 P 3 TWD 17 DBC
+1.45 TEH TEC 45 COLD 600UL 141 79 0.86 86 P 5 TWD 41 DBC
+2.00 DBC DBC 162 COLD 560P2 0.26 94 P 5 TWD 20 VC1
+0.94 VC1 VC1 162 COLD 560P2 0.46 118 P 2 TWD 24 VH1
-0.92 TEH TEC 44 COLD 600UL 0.31 124 P 2 TWD 18 VC1
+0.94 TEH TEC 44 COLD 600UL 0.79 121 P 3 TWD 30 DBC
+2.20 TEH TEC 44 COLD 600UL 141 81 0.35 157 P 2 TWD 20 VH1
-0.86 TEH TEC 44 COLD 600UL 0.12 102 2 SAI 07H
-22.55 TO-7.71 07H 07H 0.00 298 HOT 580PP 142 66 0.36 76 P 5 TWD 25 DBC
+1.77 DBC DBC 162 COLD 560P2 0.25 103 P 3 TWD 12 DBC
+1.27 TEH TEC 41 COLD 60OUL 142 68 0.16 95 P 5 TWD 11 10H
-0.31 10H 10H 320 HOT 58OPP 0.23 132 P 2 TWD 12 10H
-0.21 TEH TEC 41 COLD 600UL 142 72 0.81 81 P 5 TWD 40 DBC
+1.93 DBC DBC 162 COLD 560P2 0.26 74 P 5 TWD 21 10C
-1.17 10C 10C 136 COLD 580PP 0.36 115 P 2 TWD 17 10C
-1.01 TEH TEC 41 COLD 60OUL 0.99 114 P 3 TWD 31 DBC
+2.08 TEH TEC 41 COLD 600UL 142 82 0.66 84 P 5 TWD 36 DBC
+1.75 DBC DBC 162 COLD 560P2 0.62 104 P 3 TWD 29 DBC
+1.67 TEH TEC 45 COLD 60OUL 142 84 0.40 85 P 5 TWD 26 DBC
+1.68 DBC DBC 162 COLD 560P2 0.30 119 P 3 TWD 18 DBC
+1.40 TEH TEC 45 COLD 600UL 142 86 0.32 94 P 5 TWD 18 DBH
+1.86 DBH DBH 357 HOT 560P2 0.23 92 P 3 TWD 12 DBH
+1.88 TEH TEC 44 COLD 600UL 142 90 0.37 92 P 5 TWD 18 DBH
+1.72 DBH DBH 357 HOT 560P2 0.17 153 P 3 TWD 12 DBH
+1.94 TEH TEC 45 COLD 600UL 142 104 0.21 16 P 3 TWD 12 DBH
+1.52 TEH TEC 47 COLD 60OUL 0.23 87 P 5 TWD 13 DBH
+1.93 DBH DBH 359 HOT 560P2
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 3/7/2004 1:56:07 PM Component: S/G 88 Page 28 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodes and 0-100%twd.qry ROW LINE VOLTS 142 110 0.45 0.48 DEG CHN IND %TW 50 P 3 TWD 23 93 P 5 TWD 24 LOCATION DBH
+1.80 DBH
+1.29 EXT EXT UTIL 1 UTIL 2
TEH TEC DBH DBH CAL # LEG 47 COLD 359 HOT PROBE 600UL 560P2 143 73 0.18 103 P 5 TWD 10 01H
-0.92 01H 01H 320 HOT 580PP 1.39 80 P 5 TWD 50 DEC
+1.75 DEC DBC 174 COLD 560P2 0.12 32 P 2 TWD 7 01H
-0.95 TEH TEC 41 COLD 600UL 2.07 25 P 3 TWD 42 DEC
+2.14 TEH TEC 41 COLD 600UL 143 77 0.31 114 P 2 TWD 18 VH1
-0.77 TEH TEC 44 COLD 600UL 143 83 0.42 77 P 2 TWD 22 VHI
-0.94 TEH TEC 44 COLD 60OUL 143 89 0.26 103 P 5 TWD 15 DBH
-1.42 DBH DBH 357 HOT 560P2 0.21 36 P 3 TWD 14 DBH
-1.75 TEH TEC 45 COLD 60OUL 143 109 0.25 138 P 2 TWD 15 VC2
+0.94 TEH TEC 47 COLD 600UL 0.17 142 P 3 TWD 11 DBH
-1.61 TEH TEC 47 COLD 600UL 0.29 87 P 5 TWD 15 DBH
-1.96 DBH DBH 359 HOT 560P2 144 74 0.42 85 P 5 TWD 27 VC1
+0.85 VC1 VC1 162 COLD 560P2 0.60 74 P 5 TWD 34 DEC
+1.64 DEC DEC 162 COLD 560P2 0.50 84 P 5 TWD 30 DBC
-0.25 DEC DBC 162 COLD 560P2 0.50 86 P 2 TWD 22 VC1
+0.93 TEH TEC 41 COLD 600UL 0.26 56 P 3 TWD 12 DEC
-0.23 TEH TEC 41 COLD 600UL 0.77 82 P 3 TWD 27 DBC
+1.58 TEH TEC 41 COLD 600UL 144 78 0.39 70 P 5 TWD 26 DEC
-2.00 DBC DEC 162 COLD 560P2 0.34 91 P 3 TWD 17 DEC
-2.24 TEH TEC 44 COLD 600UL 144 80 0.53 94 P 5 TWD 23 DBH
+2.00 DBH DBH 357 HOT 560P2 0.40 121 P 3 TWD 22 DEE
+1.90 TEH TEC 45 COLD 600UL 144 82 1.08 80 P 5 TWD 45 DEC
+1.67 DEC DEC 162 COLD 560P2 0.84 95 P 3 TWD 31 DEC
+1.29 TEH TEC 44 COLD 600UL 144 84 0.79 89 P 5 TWD 39 DEC
+1.40 DEC DEC 162 COLD 560P2 0.51 101 P 3 TWD 23 DBC
+1.40 TEH TEC 44 COLD 600UL 144 86 0.33 98 P 5 TWD 18 DBH
+1.83 DBH DBH 357 HOT 560P2 0.25 121 P 3 TWD 15 DBH
+1.65 TEH TEC 45 COLD 600UL 144 88 0.82 85 P 5 TWD 40 DBC
+1.80 DEC DEC 162 COLD 560P2 0.74 51 P 3 TWD 29 DEC
+1.47 TEH TEC 44 COLD 600UL 144 90 0.73 96 P 5 TWD 36 DEC
+1.93 DEC DBC 163 COLD 560P2 0.43 28 P 3 TWD 20 DEC
+1.27 TEH TEC 44 COLD 600UL 144 96 0.46 8
P 3 TWD 21 DEC
+1.74 TEH TEC 44 COLD 600UL 0.59 71 P 5 TWD 33 DEC
+1.66 DEC DBC 162 COLD 560P2 0.43 95 P 5 TWD 22 DBH
+1.98 DBH DBH 359 HOT 560P2 0.24 132 P 3 TWD 13 DBH
+2.01 TEH TEC 44 COLD 600UL 144 106 0.75 75 P 3 TWD 31 DBC
+1.88 TEH TEC 47 COLD 60OUL 0.78 92 P 5 TWD 37 DEC
+2.00 DBC DEC 164 COLD 560P2 145 75 0.60 95 P 5 TWD 26 DBH
+1.89 DBH DBH 357 HOT 560P2 0.28 104 P 5 TWD 13 VH1
-0.88 VH1 VN1 357 HOT 560P2 0.76 73 P 5 TWD 38 DEC
+1.59 DEC DEC 162 COLD 560P2 0.51 77 P 3 TWD 21 DBH
+1.89 TEH TEC 41 COLD 600UL 0.43 122 P 2 TWD 20 VHi1
-0.88 TEH TEC 41 COLD 600UL 0.56 43 P 3 TWD 22 DEC
+1.33 TEH TEC 41 COLD 600UL 145 79 0.43 95 P 5 TWD 28 DEC
+2.00 DEC DEC 162 COLD 560P2 0.25 83 P 3 TWD 13 DEC
+2.00 TEH TEC 44 COLD 600UL 145 81 0.38 95 P 5 TWD 18 VH1
-0.82 VH1 VH1 357 HOT 560P2 1.10 79 P 5 TWD 46 DEC
-1.62 DEC DEC 162 COLD 560P2 0.50 118 P 2 TWD 26 VH1
-0.82 TEH TEC 44 COLD 600UL 0.64 76 P 3 TWD 29 DEC
-1.70 TEH TEC 44 COLD 60OUL 145 83 0.44 100 P 5 TWD 20 DBH
-1.72 DBH DBH 357 HOT 560P2 0.68 0.34 0.44 0.24 0.62 76 87 57 108 34 P
P P
2 2
S 5
2 3
3 TWD TWD TWD TWD TWD 36 23 2 1 15 29 DEC VC1 VC1 DEE DEC
+1.57
+0. 84
+0. 92
-1.72
+1.67 DEC VC1 TEH TEH TEH DEC VC1 TEC TEC TEC 162 162 45 45 45 COLD COLD COLD COLD COLD 560P2 560P2 600UL 600UL 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 3/7/2004 1:56:07 PM Component: S/G 88 Page 29 of 29 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 145 87 0.47 88 P 5 TWD 30 DBC
+2.13 DBC DBC 162 COLD 560P2 0.32 71 P 5 TWD 22 DBC
-1.63 DBC DBC 162 COLD 560P2 0.27 108 P 3 TWD 14 DBC
+1.75 TEH TEC 44 COLD 600UL 0.23 49 P 3 TWD 13 DBC
-1.75 TEH TEC 44 COLD 60OUL 145 89 0.30 107 P 5 TWD 17 DBH
-1.89 DBH DBH 357 HOT 560P2 0.31 89 P 5 TWD 22 VC1
+0.91 VC1 VC1 162 COLD 560P2 0.17 50 P 3 TWD 9 DBH
-1.72 TEH TEC 44 COLD 60OUL 0.30 35 P 2 TWD 18 VC1
+0.91 TEH TEC 44 COLD 60OUL 145 95 0.29 151 P 2 TWD 15 VHl
-0.95 TEH TEC 45 COLD 600UL 146 80 0.49 102 P 5 TWD 31 DBC
+2.00 DBC DBC 162 COLD 560P2 0.47 86 P 3 TWD 21 DBC
+2.00 TEH TEC 44 COLD 600UL 146 84 0.53 88 P 5 TWD 31 DBC
+1.70 DBC DBC 162 COLD 560P2 0.50 11 P 3 TWD 25 DBC
+1.73 TEH TEC 45 COLD 600UL 146 100 0.73 92 P 5 TWD 32 DBH
-2.05 DBH DBH 359 HOT 560P2 0.60 118 P 3 TWD 28 DBH
-1.93 TEH TEC 45 COLD 600UL 147 91 0.35 100 P 5 TWD 23 VC1
-0.83 VC1 VC1 163 COLD 560P2 0.37 142 P 2 TWD 18 VC1
-0.83 TEH TEC 45 COLD 60OUL 147 93 0.22 0.64 0.44 0.53 0.21 0.28 0.18 0.87 87 93 92 81 37 75 137 101 P
P P
P P
P P
P TWD TWD TWD TWD TWD TWD TWD TWD 16 33 20 34 13 15 11 32 VC1 VC1 DBH DBC DBC VC1 DBH VC1
-0.49
+0. 91
-2.27 TO+1.70
-1.80 TO+0.75
-1.89
-0.45
-2.05
+0.92 VC1 VC1 DBH DBC TEH TEH TEH TEH VC1 VC1 DBH DBC TEC TEC TEC TEC 163 163 357 175 45 45 45 45 COLD COLD HOT COLD COLD COLD COLD COLD 560P2 560P2 560P2 560P2 600UL 600UL 600UL 600UL Total Tubes
- 779 Total Records: 1307
Inservice Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 31 Appendix 4 Inspection Summary Steam Generator E-089
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd 03/07/04 14:17:29 Component: S/G 89 Page 2 of 31 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 1
55 0.22 103 2 SAI 02H
-0.45 02H 02H 0.0 192 HOT 580PP 2
118 0.27 20 P 1 SCI TSH
-3.06 TSH TSH 0.11 238 HOT 580PP 0.50 16 P 1 SCI TSH
-6.46 TSH TSH 0.33 17.77 238 HOT 580PP 4
10 0.42 10 2
SAI TSH
-3.84 TSH TSH 0.0 17.87 196 HOT 580PP 4
126 1.62 36 P 1 MCI TSH
-9.35 TSH TSH 4.00 19.83 234 HOT 580PP 5
115 0.85 28 P 1 SCI TSH
-7.82 TSH TSH 0.63 18.69 238 HOT 58OPP 6
60 0.33 28 P 2 TWD 15 02H
-1.25 TEH TEC 67 COLD 60OUL 6
126 0.56 40 P 2 TWD 21 03H
+0.89 TEH TEC 9
COLD 600UL 0.22 102 P 2 TWD 10 05H
+0.93 TEH TEC 9
COLD 60OUL 7
33 0.21 161 P 2 TWD 10 07H
-0.65 TEH TEC LAR 70 COLD 60OUL 8
34 0.35 25 P 2 TWD 22 07H
-0.60 TEC TEH LAR 54 HOT 600UL 8
114 0.31 16 P 1 SCI TSH
-5.80 TSH TSH 0.28 18.43 238 HOT 58OPP 0.38 14 2
SAI TSH
-1.02 TSH TSH 0.00 238 HOT 580PP 0.31 17 P 1 SCI TSH
+0.00 TSH TSH 0.00 238 HOT 580PP 8
128 0.34 88 P 2 TWD 14 01H
+0.95 TEH TEC 9
COLD 600UL 9__35___3.22___34___P__1___C____TSR__-9.50______TSR____TSR____3.41_____17.75______195____ROT____580______
9 35 3.22 34 P 1 SCI TSH
-9.50 TSH TSH 3.41 17.75 195 HOT 580PP 9
39 0.36 39 P 2 TWD 15 03H
+0.88 TEC TEH 48 HOT 600UL 9
49 0.41 102 2 SAI 05H
+0.15 05H 05H
.47 191 HOT 580PP 9
63 2.56 33 2
SAI TSH
-19.01 TSH TSH 3.55 19.01 291 HOT 58OPP 9
119 0.36 78 P 2 TWD 15 01H
+0.89 TEH TEC 9
COLD 600UL 9
127 3.54 37 P 1 MCI TSH
-9.73 TSH TSH 5.60 18.01 233 HOT 58OPP 9
131 0.68 33 P 1 SCI TSH
-14.44 TSH TSH 1.25 21.60 152 HOT 58OPP 3.31 34 P 1 SCI TSH
-11.17 TSH TSH 4.82 152 HOT 58OPP 1.14 29 P 1 MCI TSH
-10.73 TSH TSH 1.11 152 HOT 580PP 1.18 22 P 1 SCI TSH
-10.31 TSH TSH 0.76 152 HOT 58OPP 2.36 37 P 1 MCI TSH
-8.53 TSH TSH 4.45 152 HOT 58OPP 9
147 1.41 26 P 1 MCI TSH
-8.28 TSH TSH 2.27 22.69 155 HOT 580PP 10 140 0.15 20 P 1 SCI TSH
-0.35 TSH TSH 0.86 21.42 155 HOT 58OPP 11 119 0.36 87 P 2 TWD 16 07H
+0.87 TEH TEC 3
COLD 60OUL 11 127 0.24 142 P 3 TWD 10 DBH
+1.33 TEH TEC 59 COLD 600UL 0.16 100 2 SAI DBH
+1.35 DBH 07H
.16 145 COLD 560P2 11 159 0.17 108 2 SAI 06H
-0.37 06H 06H 0.42 194 HOT 580PP 11 163 0.10 69 2
SAI 06H
+1.48 06H 06H 0.00 254 HOT 580PP 11 165 0.23 85 2
SAI 06H
+0.74 06H 06H 0.00 255 HOT 580PP 0.41 63 P 2 TWD 18 06H
+0.53 TEC TEH 37 HOT 600UL 12 10 0.52 150 2 SAI 04H
-0.72 04H 04H 0.00 210 HOT 580PP 12 120 0.80 30 P 1 SCI TSH
-8.27 TSH TSH 1.08 19.56 217 HOT 580PP 12 138 1.94 33 P I SCI TSH
-7.34 TSH TSH 1.43 19.33 167 HOT 580PP 13 15 0.27 127 2 SAI 05H
-0.78 05H 05H 0.00 209 HOT 580PP 0.25 126 2 SAI 05H
+0.55 05H 05H 0.00 209 HOT 58OPP 0.35 131 P 2 TWD 19 05H
-0.78 TEC TEH 17 HOT 600UL 13 37 0.29 107 P 3 TWD 15 DBC
-0.15 TEC TEH 30 HOT 600UL 13 39 0.42 65 P 2 TWD 19 03H
+0.84 TEC TEH 30 HOT 600UL 13 141 0.19 112 2 SAI 02H
-2.27 02H 02H
.31 171 HOT 580PP
Framatome ANP Inc.
03/07/04 14:17:29 Customer Name: San Onofre -
Unit 2 Component: S/G 89 Page 3 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 14 124 1.72 27 2
SAI TSH
-9.52 TSH TSH 1.75 18.14 208 HOT 580PP 14 166 0.11 120 2 SAI 05H
+8.87 05H 05H 0.00 254 HOT 580PP 15 21 0.43 88 P 2 TWD 18 03H
+0.53 TEC TEH 22 HOT 600UL 15 37 0.29 19 P 1 SCI TSH
-9.74 TSH TSH 0.44 18.50 228 HOT 580PP 16 58 0.88 29 P 1 SCI TSH
-8.56 TSH TSH 2.01 20.93 165 HOT 580PP 18 14 0.38 135 2 SAI 05H
+0.22 05H 05H 0.23 210 HOT 580PP 18 30 0.46 49 P 3 TWD 21 DBH
+1.89 TEC TEH 26 HOT 60OUL 18 114 0.12 103 P 1 MCI TSH
+0.12 TSH TSH 0.10 17.56 225 HOT 580PP 18 118 0.33 28 P 1 SCI TSH
-10.19 TSH TSH 0.28 17.85 221 HOT 580PP 18 128 3.75 34 P 1 SCI TSH
-11.61 TSH TSH 4.30 18.07 197 HOT 580PP 0.55 14 P 1 SCI TSH
-11.20 TSH TSH 0.67 197 HOT 580PP 18 144 0.26 98 P 3 TWD 13 DBH
+1.26 TEC TEH 24 HOT 600UL 18 162 0.37 61 P 2 TWD 17 05H
-0.24 TEC TEH 37 HOT 600UL 19 9
0.28 91 2
SAI 05H
+0.89 05H 05H 0.80 204 HOT 580PP 19 109 0.19 100 P 3 TWD 8 DBC
+2.25 TEH TEC 5
COLD 600UL 0.15 103 P 5 TWD 13 DBC
+1.95 07C DBC 145 COLD 560P2 19 167 0.07 59 2
SAI 06H
+18.11 06H 06H 0.00 255 HOT 580PP 0.12 93 2
SAI 06H
+20.09 06H 06H 0.10 255 HOT 580PP 0.12 72 2
SAI 06H
+20.51 06H 06H 0.00 255 HOT 580PP 0.10 72 2
SAI 06H
+21.25 06H 06H 0.00 255 HOT 580PP 0.11 119 2 SAI 06H
+24.12 06H 06H 0.00 255 HOT 580PP 19 173 0.19 96 P 2 TWD 10 VSM
+0.81 TEC TEH 41 HOT 600UL 0.15 75 P 5 TWD 13 VSM
+0.90 VSM VSM 150 COLD 560P2 20 10 0.10 121 2 SAI 06H
+2.56 TO+5.33 06H 06H 0.10 210 HOT 580PP 20 18 0.22 87 P 5 TWD 20 VSM
+0.00 07C VSM 159 COLD 560P2 0.38 133 P 2 TWD 16 VSM
+0.00 TEC TEH 18 HOT 60OUL 20 58 0.47 137 P 2 TWD 17 01H
+0.95 TEH TEC 42 COLD 60OUL 20 60 0.17 138 P 1 SCI TSH
+0.15 TSH TSH 0.0 18.37 169 HOT 580PP 20 108 0.12 94 P 5 TWD 11 DBC
+2.07 07C DBC 145 COLD 560P2 0.20 114 P 3 TWD 11 DBC
+1.09 TEH TEC 8
COLD 60OUL 21 67 0.37 58 P 3 TWD 16 DBH
+1.89 TEH TEC 38 COLD 60OUL 0.36 125 P 2 TWD 18 VSM
+0.97 TEH TEC 38 COLD 60OUL 0.22 112 P 5 TWD 17 VSM
+0.55 VSM DBH 154 COLD 560P2 21 113 0.49 95 2
SAI 07C
+0.85 07C 07C 136 COLD 580PP 0.47 96 P 2 TWD 21 07C
+0.90 STH TEC 11 COLD 60OUL 22 2
0.37 148 P 2 TWD 18 VSM
-0.89 TEC TEH 9
HOT 600UL 0.31 106 P 5 TWD 17 VSM
-0.89 DBC VSM 161 COLD 560P2 22 10 0.23 112 P 2 TWD 12 03H
-0.90 TEC TEH 13 HOT 600UL 22 58 0.45 125 2 SAI 04H
-0.24 04H 04H 0.00 272 HOT 580PP 22 62 0.42 17 2
SAI TSH
-8.82 TSH TSH 1.08 18.63 169 HOT 580PP 0.43 18 2
SAI TSH
-8.16 TSH TSH
.32 18.63 169 HOT 580PP 22 66 0.42 24 P 1 SCI TEH
+0.83 TEH SBH 0.00 11.41 329 HOT 520ET 22 118 0.42 132 P 2 TWD 16 07H
+0.93 TEH TEC 4
COLD 60OUL 22 120 0.33 133 P 2 TWD 14 07H
-0.91 TEH TEC 4
COLD 600UL 22___164___0.22___96___2___A____OEM__-3.79_______OEM______OEM______0.46______172______ROT______58022_____
22 164 0.22 96 2
MAI 06H
-3.79 06H 06H 0.46 172 HOT 580PP of 31
Framatome ANP Inc.
03/07/04 14:17:29 Customer Name: San Onofre -
Unit 2 Component: S/G 89 Page 4 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 23 23 0.36 108 P 2 TWD 15 01H
+0.91 TEC TEH 22 HOT 600UL 23 57 0.35 123 2 SAI 07H
-0.83 07H 07H 0.00 272 HOT 580PP 23____59____0.40_____91____P__2___TWO_____17___________+0.86______TEE_____TEC____41____COLD_____________L 23 59 0.40 91 P 2 TWD 17 01H
+0.86 TEH TEC 41 COLD 600UL of 31 23 115 0.34 116 P 2 TWD 15 VSM
+0.82 TEH TEC 5
COLD 600UL 0.15 85 P 5 TWD 13 VSM
+0.82 VSM VSM 145 COLD 560P2 23 169 0.27 47 P 2 TWD 11 02H
+0.88 TEC TEH 37 HOT 600UL 24 18 0.12 98 P 5 TWD 10 VSM
-0.69 VSM DBH 159 COLD 560P2 0.23 69 P 2 TWD 10 VSM
-0.88 TEC TEH 18 HOT 600UL 24 60 0.54 22 2
SAI TSH
-15.96 TSH TSH 0.0 18.06 169 HOT 580PP 0.29 20 P 1 SCI TSH
-0.06 TSH TSH 1.04 18.06 169 HOT 58OPP 24____138____0.55______164____P___3__TWO_____23___DBH_____+1___17____TEC____TER____19____HOT_____________
24 138 0.55 164 P 3 TWD 23 DBH
+1.17 TEC TEH 19 HOT 600UL 24 150 0.47 157 P 3 TWD 22 DBH
+1.29 TEC TEH 28 HOT 600UL 24 152 0.39 24 P 1 SCI TSH
-0.11 TSH TSH 0.00 18.05 184 HOT 580PP 24 154 0.26 123 P 2 TWD 14 VSM
+0.26 TEC TEH 28 HOT 600UL 0.16 81 P 5 TWD 14 VSM
+0.40 VSM VSM 150 COLD 560P2 25 109 0.98 28 2
SAI TSH
-18.05 TSH TSH 1.43 18.47 230 HOT 580PP 26 14 0.31 79 P 2 TWD 17 VSM
+0.89 TEC TEH 17 HOT 60OUL 26 110 1.17 22 2
SAI TSH
-7.21 TSH TSH 1.33 18.39 230 HOT 580PP 0.22 126 2 SAI TSH
+0.33 TSH TSH 0.18 230 HOT 580PP 0.15 118 2 SAI TSH
+0.62 TSH TSH 0.16 230 HOT 580PP 26 162 0.26 80 P 2 TWD 13 06H
-0.47 TEC TEH 37 HOT 600UL 0.21 103 2 SAI 06H
-0.43 06H 06H 0.61 247 HOT 580PP 27 21 0.36 61 P 2 TWD 15 03H
+0.99 TEC TEH 22 HOT 600UL 27 23 0.47 83 P 2 TWD 19 07H
+0.61 TEC TEH 22 HOT 600UL 27 111 0.17 88 P 1 MCI TSH
+0.12 TSH TSH 0.00 17.61 225 HOT 58OPP 27 147 0.25 30 P 1 SCI TSH
-0.11 TSH TSH 0.48 18.91 254 HOT 580PP 28 42 0.35 27 P 1 SCI TSH
-0.08 TSH TSH 0.00 18.28 231 HOT 58OPP 29 19 0.36 36 P 2 TWD 15 07H
+0.96 TEC TEH 22 HOT 600UL 29 127 1.17 32 P 1 MCI TSH
-10.82 TSH TSH 2.65 18.52 198 HOT 580PP 0.46 27 P 1 MCI TSH
-7.59 TSH TSH 1.40 18.52 198 HOT 580PP 30 18 0.30 155 P 3 TWD 14 DBH
-1.83 TEH TEC 69 COLD 600UL 30 36 0.33 160 P 3 TWD 16 DBC
+1.97 TEC TEH 30 HOT 600UL 30 70 0.49 86 P5 TWD 31 DEC
-2.21 TO+2.13 DBC DBC 153 COLD 560P2 0.30 147 P 3 TWD 15 DBC
-1.99 TEH TEC LAR 37 COLD 600UL 31____71____0.35_____90___P_______TWO____24____DEC____+1.94______DEC____DEC_____153____COLD_______60P2___
31 71 0.35 90 P 5 TWD 24 DBC
+1.94 DBC DBC 153 COLD 560P2 0.28 95 P 5 TWD 21 DBC
-1.94 DBC DBC 153 COLD 560P2 0.36 82 P 5 TWD 25 DBH
-1.87 DBH DBH 153 COLD 560P2 0.25 127 P 3 TWD 11 DBC
+1.67 TEH TEC 37 COLD 600UL 0.21 138 P 3 TWD 9 DBC
-1.71 TEH TEC 37 COLD 600UL 0.50 52 P 3 TWD 19 DBH
-1.74 TEH TEC 37 COLD 600UL 31 117 0.30 143 P 2 TWD 13 07C
+0.34 TEH TEC 6
COLD 60OUL 32 22 0.32 77 P 2 TWD 13 07H
+0.81 TEC TEH 22 HOT 60OUL 33 13 0.36 99 P 2 TWD 19 VSM
+0.54 TEC TEH 17 HOT 600UL 33 127 1.27 30 P 1 SCI TSH
-8.34 TSH TSH 2.05 18.48 198 HOT 580PP 35 13 0.36 87 P 2 TWD 15 04H
-0.87 TEC TEH 18 HOT 60OUL
Framatome ANP Inc.
03/07/04 14:17:29 Customer Name: San Onofre - Unit 2 Component: S/G 89 Page
- MAI, MCI,
- MMI, MVI, SAI, SCI,
- SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 35 21 0.45 35 P 2 TWD 18 02H
+0.91 TEC TEH 22 HOT 600UL 5 of 31 35 61 0.20 151 P 1 SCI TSH
+0.06 TSH TSH 0.0 18.04 169 HOT 58OPP 35 115 0.17 139 P 1 SCI TSH
+0.10 TSH TSH 0.00 19.11 226 HOT 58OPP 36 40 0.10 94 2
SAI 01H
+15.52 01H 01H 0.00 228 HOT 580PP 0.10 103 2 SAI 01H
+17.44 01H 01H 0.00 228 HOT 58OPP 36 104 0.29 90 P 5 TWD 22 DBC
-1.75 DBC DBC 145 COLD 560P2 0.26 86 P 3 TWD 14 DBC
-2.22 TEH TEC 8
COLD 600UL 36 114 0.36 96 P 2 TWD 16 02H
+0.88 TEH TEC 5
COLD 60OUL 36 126 0.32 26 P 1 SCI TSH
-4.32 TSH TSH 0.13 19.07 198 HOT 580PP 36 132 0.50 22 P 1 SCI TSH
-6.64 TSH TSH 0.53 18.51 161 HOT 580PP 36 134 0.35 18 P 1 SCI TSH
-8.22 TSH TSH 0.0 18.48 161 HOT 580PP 37 59 0.19 79 P 1 SCI TSH
+0.09 TSH TSH
.37 21.67 169 HOT 580PP 37 75 0.71 77 P 5 TWD 38 DBC
-2.16 TO+2.27 DBC DBC 153 COLD 560P2 0.88 76 P 5 TWD 43 DBH
-2.20 TO+1.97 DBH DBH 153 COLD 560P2 1.13 86 P 3 TWD 33 DBH
-1.39 TEH TEC 36 COLD 600UL 0.54 163 P 3 TWD 20 DBC
+1.60 TEH TEC 36 COLD 600UL 0.62 98 P 3 TWD 22 DBC
-2.25 TEH TEC 36 COLD 60OUL 37 101 0.26 81 P 3 TWD 13 DBC
+1.91 TEC TEH AAS 16 HOT 600UL 0.33 96 P 5 TWD 22 DBC
+1.92 DBC DBC 152 COLD 560P2 37 103 0.42 76 P 5 TWD 29 DBH
-1.85 DBH DBH 145 COLD 560P2 0.24 40 P 3 TWD 13 DBH
-1.48 TEH TEC 7
COLD 600UL 37 105 0.13 95 P 5 TWD 11 DBH
-2.12 VSM DBH 145 COLD 560P2 38 4
0.31 55 P 2 TWD 16 01C
+0.09 TEC TEH 13 HOT 60OUL 0.29 72 P 2 TWD 15 02C
-0.88 TEC TEH 13 HOT 600UL 0.23 104 P 5 TWD 16 01C
+0.11 01C 01C 139 COLD 58OPP 0.27 102 P 5 TWD 18 02C
-1.04 02C 02C 139 COLD 580PP 38____20____0.22_____129_____P__3___TWO_____12___DEE_____+0.79______TEC____TEH_____25____ROT_____________
38 20 0.22 129 P 3 TWD 12 DBH
+0.79 TEC TEH 25 HOT 600UL 0.22 129 P 3 TWD 12 DBH
-0.10 TEC TEH 25 HOT 600UL 0.15 98 P 5 TWD 11 DBH
+0.79 VSM DBH 158 COLD 560P2 38 40 0.84 28 P 1 SCI TSH
-10.21 TSH TSH 1.26 17.57 227 HOT 580PP 38 60 0.18 104 2 SAI TSH
+1.00 TSH TSH 0.00 18.73 170 HOT 580PP 38 116 0.66 20 2
SAI TSH
-6.02 TSH TSH 1.00 18.38 222 HOT 58OPP 38 128 0.38 52 P 3 TWD 16 DBH
+2.24 TEH TEC 58 COLD 600UL 38 156 0.32 61 P 2 TWD 15 03H
-0.72 TEC TEH 33 HOT 60OUL 39 21 0.39 87 P 2 TWD 16 VSM
+0.74 TEC TEH 22 HOT 600UL 39 59 0.23 71 2
SAI TSH
+0.18 TSH TSH 0.00 22.46 170 HOT 580PP 39 67 0.30 114 2 SAI TSH
-0.07 TSH TSH 0.40 17.97 173 HOT 580PP 39 69 0.62 17 P 1 SCI TSH
-12.09 TSH TSH 0.67 17.87 173 HOT 580PP 39 73 4.06 35 2
SAI TSH
-10.15 TSH TSH 4.25 17.80 178 HOT 580PP 0.64 21 2
SAI TSH
-9.19 TSH TSH 0.42 178 HOT 580PP 0.43 18 2
SAI TSH
-1.21 TSH TSH 0.41 178 HOT 58OPP 0.63 83 P 5 TWD 36 DBC
-1.89 DBC DBC 153 COLD 560P2 0.61 82 P 3 TWD 22 DBC
-1.56 TEH TEC 36 COLD 600UL 39 127 14.03 46 P 1 SCI TSH
-9.34 TSH TSH 14.03 18.86 198 HOT 580PP 1.57 27 P 1 SCI TSH
-7.81 TSH TSH 1.54 198 HOT 580PP 40 62 0.41 22 P 3 TWD 19 DBC
-0.51 TEH TEC 40 COLD 600UL 40 140 0.34 106 P 2 TWD 16 VSM
-0.89 TEC TEH 23 HOT 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:29 Component: S/G 89 Page 6 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 41 47 0.46 63 P 2 TWD 19 02H
-1.19 TEH TEC 45 COLD 600UL 41 63 0.33 51 P 2 TWD 17 02H
+0.96 TEH TEC 38 COLD 600UL 0.32 58 P 2 TWD 16 06H
+0.87 TEH TEC 38 COLD 600UL 41 73 0.16 105 P 5 TWD 13 DBC
-1.83 DBC DBC 153 COLD 560P2 0.24 50 P 3 TWD 12 DBC
-1.80 TEH TEC 37 COLD 600UL 41 75 0.32 102 P 5 TWD 23 DBC
+2.21 DBC DEC 153 COLD 560P2 0.16 87 P 5 TWD 13 DBC
-1.59 DBC DBC 153 COLD 560P2 0.41 123 P 3 TWD 16 DBC
+1.69 TEH TEC LAR 36 COLD 600UL 41 101 0.37 94 P 3 TWD 17 DBC
+1.75 TEC TEH 16 HOT 60OUL 0.43 72 P 5 TWD 27 DBC
+1.92 DBC DBC 152 COLD 560P2 41 103 0.25 72 P 2 TWD 13 VSM
+0.87 STH TEC 11 COLD 60OUL 0.20 86 P 5 TWD 16 VSM
+0.79 VSM VSM 145 COLD 560P2 41 143 0.44 150 P 2 TWD 20 VSM
+0.65 TEC TEH 23 HOT 60OUL 41____159____0.35______90___P___2__TWO_____14_______E___+1___15____TEE____TEC_____61___COLD______________
41 159 0.35 90 P 2 TWD 14 01H
+1.15 TEH TEC 61 COLD 600UL 42 110 0.53 68 P 2 TWD 20 VSM
-0.15 TEH TEC 6
COLD 600UL 1.20 112 P 2 TWD 34 VSM
+0.98 TEH TEC 6
COLD 60OUL 0.34 92 P 5 TWD 24 VSM
-0.15 VSM VSN 145 COLD 560P2 0.47 88 P 5 TWD 31 VSM
+0.98 VSM VSM 145 COLD 560P2 42 124 0.80 17 2
SAI TSH
-12.60 TSH TSH 0.80 18.35 208 HOT 58OPP 1.19 25 P 1 MCI TSH
-11.31 TSH TSH 0.93 208 HOT 580PP 0.82 30 P 1 MCI TSH
-8.55 TSH TSH 1.44 208 HOT 580PP 42 168 0.50 147 P 2 TWD 22 VSM
+1.06 TEC TEH 36 HOT 60OUL 0.35 89 P 5 TWD 26 VSM
+1.04 VSM VSM 150 COLD 560P2 42 170 0.62 105 P 2 TWD 24 VSM
-0.25 TEC TEH 37 HOT 600UL 0.36 91 P 5 TWD 26 VSM
-0.46 VSM VSM 150 COLD 560P2 43 65 0.14 97 P 1 SCI TSH
-0.05 TSH TSH 0.33 18.02 173 HOT 580PP 43 79 0.74 69 P 3 TWD 26 DBH
+2.08 TEC TEH 11 HOT 60OUL 0.69 76 P 5 TWD 39 DOH
+1.70 DBH DBH 151 COLD 560P2 43 101 0.61 106 P 3 TWD 24 DBC
+1.77 TEC TEH 15 HOT 600UL 0.70 83 P 5 TWD 38 DBC
+2.00 DBC DBC 152 COLD 560P2 44 18 0.14 94 P 5 TWO 12 VSM
-0.71 VSM DEE 159 COLD 560P2 0.14 84 P 5 TWD 12 VSM
+0.91 VSM DBH 159 COLD 560P2 0.16 39 P 2 TWD 7 VSM
+0.63 TEC TEH 22 HOT 600UL 0.32 144 P 2 TWD 14 VSM
-0.90 TEC TEH 22 HOT 600UL 44 74 0.60 80 P 5 TWD 35 DBC
-2.18 DBC DBC 153 COLD 560P2 0.27 78 P 5 TWD 20 DBC
+1.98 DBC DBC 153 COLD 560P2 0.46 71 P 3 TWO 18 DBC
-2.24 TEH TEC 36 COLD 600UL 0.33 173 P 3 TWD 14 DBC
+1.92 TEH TEC 36 COLD 60OUL 44 100 1.05 77 P 5 TWD 47 DBC
+1.76 DBC DBC 152 COLD 560P2 0.15 92 P 5 TWD 11 DBC
-1.78 DBC DBC 152 COLD 560P2 1.25 91 P 3 TWD 36 DBC
+2.16 TEC TEH AAS 16 HOT 60OUL 0.18 85 P 3 TWD 9 DBC
-1.82 TEC TEH 16 HOT 600UL 44 104 0.22 89 P 5 TWO 18 VSM
+0.81 VSM VSM 145 COLD 560P2 0.16 89 P 5 TWD 14 VSM
-0.91 VSM VSM 145 COLD 560P2 0.56 58 P 2 TWD 23 VSM
+0.87 TEH TEC LAR 8
COLD 600UL 44 112 0.54 131 P 2 TWD 21 VSM
-0.91 TEH TEC 5
COLD 600UL 0.27 84 P 5 TWD 21 VSM
-0.78 VSM VSM 145 COLD 560P2 44 150 0.24 143 P 2 TWD 13 01H
+0.99 TEC TEH 28 HOT 60OUL 45 19 0.33 69 P 2 TWD 14 03H
+0.82 TEC TEH 22 HOT 600UL 45 47 0.33 26 2 SAI TSH
-4.74 TEH TSH 0.31 23.00 159 HOT 580PP 45 63 0.33 117 P 2 TWD 17 VSM
-0.85 TEH TEC 38 COLD 600UL 45 67 0.49 18 2
SAI TSH
-3. 44 TSH TSH 0.34 18.01 173 HOT 580PP
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:29 Component: S/G 89 Page 7 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-========================-
-=======-=======-=====-========-===
45 73 0.34 81 P 5 TWD 24 DBC
-1.79 DBC DBC 153 COLD 560P2 0.40 88 P 3 TWD 18 DBC
-1.99 TEH TEC 37 COLD 600UL 0.47 16 2
SAI TSH
-0.72 TSH TSH 0.30 18.92 278 HOT 580PP 0.37 11 2
SAI TSH
-0.42 TSH TSH 0.11 278 HOT 58OPP 45 101 1.01 91 P 3 TWD 32 DBC
+2.18 TEC TEH AAS 16 HOT 600UL 0.85 76 P 5 TWD 42 DBC
+1.27 DBC DBC 152 COLD 560P2 45__103__0.18__91__P_5__TWO__15__VN_-0.18_________V____N____V____M____145_______COLD________56022_______
45 103 0.18 91 P 5 TWD 15 VSM
-0.18 VSM VSM 145 COLD 560P2 0.14 90 P 5 TWD 12 VSM
-1.02 VSM VSM 145 COLD 560P2 0.41 81 P 5 TWD 28 VSM
+0.89 VSM VSM AEC 145 COLD 560P2 0.51 106 P 2 TWD 24 VSM
+0.89 TEH TEC 7
COLD 60OUL 0.15 91 P 2 TWD 10 VSM
+0.02 TEH TEC 7
COLD 600UL 0.15 29 P 2 TWD 10 VSM
-0.82 TEH TEC 7
COLD 600UL 45 119 0.09 126 2 SAI 01H
+5.86 01H 01H 0.19 221 HOT 580PP 0.09 106 2 SAI 01H
+4.20 01H 01H 0.11 221 HOT 58OPP 45 145 0.32 118 P 2 TWD 16 VSM
-0.91 TEC TEH 23 HOT 600UL 0.17 101 P 5 TWD 15 VSM
-0.93 TEM VSM 149 COLD 560P2 45 147 0.41 149 P 2 TWD 19 VSM
-0.75 TEC TEH 23 HOT 60OUL 45 167 0.44 135 P 2 TWD 18 VSM
+0.77 TEC TEH 37 HOT 600UL 46 44 3.53 31 2
SAI TSH
-8.24 TSH TSH 3.78 17.49 232 HOT 580PP 46 72 0.37 17 2
SAI TSH
-2.67 TSH TSH 0.0 17.82 279 HOT 580PP 46 104 0.37 90 P 5 TWD 26 VSM
+0.00 TSM VSM 145 COLD 560P2 0.24 92 P 5 TWD 19 VSM
-0.87 VSM VSM 145 COLD 560P2 0.22 105 P 5 TWD 18 VSM
+0.64 VSM VSM 145 COLD 560P2 0.55 52 P 2 TWD 25 VSM
-0.78 TEH TEC 7
COLD 60DUL 0.14 48 P 2 TWD 8 VSM
+0.10 TEH TEC 7
COLD 60OUL 46 128 0.30 123 P 2 TWD 13 VSM
-0.89 TEH TEC 58 COLD 600UL 0.14 104 P 5 TWD 13 VSM
-1.02 VSM VSM 145 COLD 560P2 46 130 1.49 21 2
SAI TSH
-14.96 TSH TSH 1.49 18.94 162 HOT 580PP 46 132 0.11 100 2 SAI 01H
+2.60 01H 01H
.18 171 HOT 580PP 0.12 122 2 MAI 07H
+18.60 TO+19.62 07H DBH 0.00 165 COLD 560P2 46 136 0.94 24 2
SAI TSH
-14.55 TSH TSH 1.09 162 HOT 58OPP 1.14 24 2
SAI TSH
-14.76 TSH TSH 1.17 18.20 162 HOT 580PP 0.22 129 2 SAI TSH
+0.84 TSH TSH 0.0 162 HOT 580PP 46 154 0.49 67 P 2 TWD 21 03H
-0.88 TEC TEH 29 HOT 600UL 46 156 0.54 110 P 2 TWD 22 VSM
-1.22 TEC TEH 33 HOT 600UL 0.20 67 P 2 TWD 11 VSM
+0.78 TEC TEH 33 HOT 60OUL 0.30 81 P 5 TWD 23 VSM
-0.98 VSM VSM 150 COLD 560P2 0.12 89 P 5 TWD 10 VSM
+0.71 VSM VSM 150 COLD 560P2 46 162 0.27 81 P 2 TWD 11 VSM
+0.89 TEC TEH 37 HOT 600UL 0.17 88 P 5 TWD 14 VSM
+0.74 VSM VSM 150 COLD 560P2 46 170 0.25 45 P 3 TWD 13 DBC
+1.54 TEC TEH 37 HOT 60OUL 0.18 93 P 5 TWD 15 DBC
+1.62 DBC DBC 150 COLD 560P2 47 15 0.18 121 2 SAI DBH
+1.68 DBC DBH 0.00 159 COLD 560P2 0.27 130 P 3 TWD 12 DBH
+1.07 TEC TEH 18 HOT 600UL 47 33 0.46 55 P 3 TWD 21 DBH
+1.70 TEC TEH 26 HOT 60OUL 47 41 0.50 10 2
SAI TSH
-11.41 TSH TSH 0.60 17.81 227 HOT 580PP 0.55 10 2 SAI TSH
-3.48 TSH TSH 0.59 227 HOT 580PP 47 45 2.80 31 2
SAI TEH
+6.43 TEH SBH 4.07 11.34 329 HOT 520ET 47 51 0.11 132 P 1 SCI TSH
+0.14 TSH TSH 0.06 22.09 160 HOT 580PP 47 77 1.10 131 P 3 TWD 34 DBC
+1.87 TEC TEH 12 HOT 60OUL 0.82 82 P 5 TWD 43 DBC
+1.90 DBC DEC 151 COLD 560P2
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:29 Component:
S/G 89 Page 8 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand_0-100%twd.qry ROW LINE VOLTS 47 101 0.34 0.96 0.34 0.96 DEG 147 68 86 76 CHN P 3 P 3 P 5 P 5 IND TWO TWD TWD TWD
%TW 15 31 23 45 LOCATION DBH
-1.98 DBC
+1.75 DBH
-1.83 DBC
+1.44 EXT TEC TEC DBH DBC EXT TEH TEH DBH DBC UTIL 1 UTIL 2
CAL #
15 15 152 152 LEG HOT HOT COLD COLD PROBE 60OUL 60OUL 560P2 560P2 47 109 0.18 85 2
SAI TSH
+0.24 TSH TSH 0.00 18.35 230 HOT 580PP 47 121 0.26 140 P 2 TWD 10 VSM
-0.86 TEH TEC 4
COLD 600UL 0.19 84 P 5 TWD 16 VSM
-0.88 VSM VSM 145 COLD 560P2 48 6
0.38 78 P 2 TWD 18 08C
-1.72 TEC TEH LOCOK 13 HOT 60OUL 0.14 88 P 5 TWD 11 08C
-1.72 08C DBC 160 COLD 560P2 48 8
0.30 128 P 2 TWD 14 02C
+0.94 TEC TEH 14 HOT 600UL 0.21 104 P 5 TWD 15 02C
+0.85 02C 02C 139 COLD 580PP 48 14 0.25 75 2
SAI 06H
-1.30 TO-7.29 06H 06H 0.15 209 HOT 580PP 48 34 0.19 24 P 2 TWD 10 VSM
-0.66 TEC TEH 30 HOT 600UL 0.18 101 P 5 TWD 13 VSM
-0.66 VSM VSM 157 COLD 560P2 48 66 0.99 157 P 2 TWD 29 VSM
-0.82 TEH TEC 40 COLD 600UL 0.64 80 P 5 TWD 36 VSM
-0.93 VSM VSM 153 COLD 560P2 48 74 0.14 119 P 1 SCI TSH
+0.08 TSH TSH 1.28 17.23 177 HOT 580PP 0.30 86 P 5 TWD 22 DBC
-1.95 DBC DBC 153 COLD 560P2 0.17 92 P 5 TWD 14 DBC
+2.19 DBC DBC 153 COLD 560P2 0.36 131 P 3 TWD 17 DBC
-1.92 TEH TEC LAR 37 COLD 600UL 48 100 0.44 90 P 5 TWD 28 DBC
+2.10 08C DBC 152 COLD 560P2 0.53 62 P 3 TWD 22 DBC
+2.17 TEC TEH AAS 16 HOT 600UL 48 108 0.28 88 2
SAI TSH
+0.18 TSH TSH 0.20 19.00 229 HOT 580PP 48 118 0.46 67 P 2 TWD 19 04H
-1.15 TEH TEC 3
COLD 600UL 0.17 87 P 5 TWD 11 04H
-1.15 04H 04H 222 HOT 580PP 48 146 0.47 151 P 3 TWD 20 DBH
+1.22 TEC TEH 23 HOT 600UL 48 158 0.66 158 P 2 TWD 23 VSM
-0.62 TEH TEC 61 COLD 600UL 0.17 97 P 5 TWD 14 VSM
+0.90 VSM VSM 150 COLD 560P2 0.34 88 P 5 TWD 26 VSM
-0.87 VSM VSM 150 COLD 560P2 49___9_0.29___86__P__2__TWO__15__VSM__-0.76________TEC______TEE________AS_____13_____HOT_________________
49 9
0.29 86 P 2 TWD 15 VSM
-0.76 TEC TEH AAS 13 HOT 600UL 49 39 0.29 137 P 2 TWD 13 VSM
-0.77 TEC TEH 31 HOT 600UL 49 49 0.40 64 P 2 TWD 16 08H
+1.70 TEH TEC LOCOK 44 COLD 60OUL 49 53 0.53 98 P 2 TWD 17 08C
-1.44 TEH TEC LOCOK 43 COLD 60OUL 49___59__0.15____102___2________TS_____1__56___T___2__25___TS____TS____0.0___19.65____169___HOT__________
49 59 0.15 102 2 MAI TSH
+1.56 TO+2.25 TSH TSH 0.0 19.65 169 HOT 580PP 49 65 0.28 108 P 2 TWD 10 VSM
-0.81 TEH TEC 40 COLD 600UL 49 75 0.34 115 P 3 TWD 15 DBC
-1.75 TEH TEC 70 COLD 600UL 0.30 82 P 5 TWD 22 DBC
-2.01 08C DBC 153 COLD 560P2 49 77 0.43 90 P 3 TWD 18 DEC
-1.96 TEC TEH 11 HOT 600UL 0.16 112 P 3 TWD 8 DEC
+1.52 TEC TEH 11 HOT 600UL 0.29 87 P 2 TWD 14 08H
+0.89 TEC TEH 11 HOT 60OUL 0.30 94 P 5 TWD 22 DEC
-1.95 08C DBC 151 COLD 560P2 0.24 98 P 5 TWD 19 DBC
+1.71 08C DBC 151 COLD 560P2 0.18 116 2 SAI 08C
-1.32 08C DBC 0.11 151 COLD 560P2 49 79 0.34 87 P 2 TWD 15 08C
-1.50 TEC TEH LOCOK 11 HOT 60OUL 0.24 105 P 2 TWD 12 08C
+1.35 TEC TEH LOCOK 11 HOT 600UL 0.22 135 P 2 TWD 11 08H
+1.46 TEC TEH LOCOK 11 HOT 600UL 49 99 0.55 81 P 5 TWD 32 DEC
-1.85 08C DBC 152 COLD 560P2 0.58 83 P 5 TWD 34 DBH
-1.94 DEH 08H 152 COLD 560P2 0.67 88 P 3 TWD 25 DEC
-1.75 TEC TEH 15 HOT 600UL 0.57 94 P 3 TWD 23 DEH
-1.75 TEC TEH 15 HOT 600UL 49 103 0.16 114 P 5 TWD 13 VSM 0.24 118 P 2 TWD 14 VSM
-0.79 VSM VSM
-0.88 TEH TEC 146 COLD 560P2 7
COLD 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:29 Component: S/G 89 Page 9 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-========================-
-=======-=======-=-==-========-===
49 113 0.31 93 P 2 TWD 16 08H
-1.21 STH TEC 11 COLD 600UL 49 121 0.36 119 P 2 TWD 16 08H
-0.86 TEH TEC 3
COLD 600UL 49 145 0.49 55 P 2 TWD 22 08H
-1.01 TEC TEH LOCOK 23 HOT 600UL 49 159 0.50 90 P 2 TWD 19 VSM
+0.71 TEH TEC 61 COLD 60OUL 0.21 98 P 5 TWD 17 VSM
+0.86 VSM VSM 150 COLD 560P2 0.19 94 P 5 TWD 16 VSM
+0.25 VSM VSM 150 COLD 560P2 50 44 0.31 116 P 2 TWD 13 VSM
-0.81 TEC TEH 35 HOT 600UL 50 64 0.50 107 P 2 TWD 18 08H
-1.45 TEH TEC LOCOK 40 COLD 60OUL 0.57 140 P 2 TWD 20 08H
+1.43 TEH TEC LOCOK 40 COLD 600UL 50 74 0.27 85 P 5 TWD 20 DBC
-2.03 08C DBC 153 COLD 560P2 0.47 86 P 5 TWD 30 DBC
+2.09 08C DBC 153 COLD 560P2 0.68 163 P 3 TWD 24 DBC
+1.96 TEH TEC 36 COLD 600UL 0.23 92 P 3 TWD 10 DBC
-2.24 TEH TEC 36 COLD 600UL 50 76 0.41 108 P 3 TWD 19 DBC
-1.62 TEC TEH 60 HOT 600UL 0.34 83 P 5 TWD 25 DBC
-1.66 DBC DBC 151 COLD 560P2 50 78 0.49 104 P 3 TWD 21 DBC
+1.98 TEC TEH AAS 12 HOT 600UL 0.36 139 P 3 TWD 16 DBC
-1.74 TEC TEH 12 HOT 600UL 0.33 92 2
SAI TSH
+0.55 TSH TSH 0.00 17.26 181 HOT 58OPP 0.06 76 2
SAI TSH
+0.98 TSH TSH 0.00 181 HOT 580PP 0.15 63 2
SAI TSH
+1.11 TSH TSH 0.00 181 HOT 580PP 0.15 94 2
SAI TSH
+1.26 TSH TSH 0.00 181 HOT 580PP 0.24 97 2
SAI TSH
+1.60 TSH TSH 0.00 181 HOT 580PP 0.36 87 P 5 TWD 25 DBC
+2.05 08C DBC 151 COLD 560P2 0.34 82 P 5 TWD 24 DBC
-1.96 08C DBC 151 COLD 560P2 50 82 0.46 143 P 3 TWD 19 DBC
-1.59 TEC TEH 11 HOT 600UL 0.72 67 P 3 TWD 26 DBC
+1.61 TEC TEH 11 HOT 600UL 0.44 115 P 3 TWD 18 DBH
-1.61 TEC TEH 11 HOT 600UL 0.18 97 P 3 TWD 9 DBH
+1.75 TEC TEH 11 HOT 600UL 0.18 76 P 5 TWD 15 DBH
+1.80 DBH 08H 151 COLD 560P2 0.30 89 P 5 TWD 22 DBH
-1.78 DBH 08H 151 COLD 560P2 0.48 89 P 5 TWD 31 DBC
-1.83 08C DBC 151 COLD 560P2 0.65 83 P 5 TWD 38 DBC
+1.94 08C DBC 151 COLD 560P2 50 158 0.44 72 P 2 TWD 20 08H
-1.15 TEC TEH 33 HOT 60OUL 51 51 0.34 117 2 SAI TSH
+0.31 TSH TSH 0.45 21.19 160 HOT 58OPP 0.28 100 P 1 SCI TSH
+0.14 TSH TSH
.24 21.19 160 HOT 580PP 0.45 20 P 1 SCI TSH
-0.15 TSH TSH
.09 21.19 160 HOT 580PP 51 61 0.89 21 2
SAI TSH
-14.07 TSH TSH 0.53 18.67 170 HOT 580PP 0.42 55 P 2 TWD 15 08C
-0.91 TEH TEC 40 COLD 600UL 0.35 77 2
SAI 08C
-0.82 08C 08C 0.52 137 COLD 58OPP 51 75 0.47 87 P 5 TWD 30 DBC
-2.24 TO+0.50 08C DBC 153 COLD 560P2 0.53 86 P 3 TWD 20 DBC
-1.76 STH TEC 66 COLD 600UL 51 95 0.70 78 P 5 TWD 38 DBC
+1.63 08C DBC 161 COLD 560P2 0.43 85 P 5 TWD 27 DBH
+1.57 DBH 08H 152 COLD 560P2 0.38 114 P 3 TWD 17 DBH
+1.82 TEC TEH 16 HOT 600UL 0.99 74 P 3 TWD 32 DBC
+1.45 TEC TEH 16 HOT 600UL 51 97 0.63 79 P 5 TWD 35 DBH
-1.74 DBH DBH 152 COLD 560P2 0.83 82 P 5 TWD 42 DBC
-1.83 08C DBC 152 COLD 560P2 1.17 84 P 3 TWD 35 DBC
-1.72 TEC TEH 15 HOT 60OUL 0.55 83 P 3 TWD 22 DBH
-2.25 TEC TEH 15 HOT 60OUL 51 107 0.20 123 P 1 SCI TSH
+0.10 TSH TSH 0.00 18.99 229 HOT 58OPP 51 121 0.40 105 P 2 TWD 15 08H
+1.07 TEH TEC 4
COLD 60OUL 51 169 0.28 123 P 2 TWD 15 VH3
+0.75 TEC TEH 36 HOT 600UL 52 14 0.30 37 P 2 TWD 13 03H
+1.13 TEC TEH 18 HOT 60OUL 52__16__0.50___83_P__2_TWO___24_V__3_-1.04__________TEC________TEE_______17______HOT_____________________
52 16 0.50 83 P 2 TWD 24 VH3
-1.04 TEC TEH 17 HOT 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand_0-100%twd.qry 03/07/04 14:17:29 Component: S/G 89 Page 10 of 31 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT 52 18 0.69 154 P 2 TWD 24 VH3
-1.04 TEC TER UTIL 1 UTIL 2
=
CAL # LEG PROBE 22 HOT 6EOUL 52 28 0.30 32 P 3 TWD 12 DBC
+2.01 TEC TEH 27 HOT 600UL 52 76 0.42 84 P 3 TWD 17 DBC
-1.49 TEC TEE 11 HOT 600UL 0.38 82 P 5 TWD 26 DBC
-1.86 08C DBC 151 COLD 560P2 52 80 0.57 90 P 3 TWD 22 DBC
-1.85 TEC TEE 11 HOT 60OUL 0.42 81 P 5 TWD 29 DBC
-1.91 DBC DBC 151 COLD 560P2 52 84 0.63 110 P 3 TWD 24 DBH
+1.29 TEC TEH 11 HOT 60OUL 0.32 101 P 3 TWD 14 DBH
-1.19 TEC TEE 11 HOT 600UL 0.26 160 P 3 TWD 11 DBC
-1.78 TEC TEE 11 HOT 600UL 0.44 119 P 3 TWD 18 DBC
+2.12 TEC TEE 11 HOT 600UL 0.55 84 P 5 TWD 34 DBH
+1.69 DBH DBH 151 COLD 560P2 0.21 93 P 5 TWD 17 DBH
-1.68 DBH DBH 151 COLD 560P2 0.33 85 P 5 TWD 24 DBC
+1.82 08C DBC 151 COLD 560P2 0.24 88 P 5 TWD 18 DBC
-1.81 08C DBC 151 COLD 560P2 52 96 0.42 85 P 5 TWD 27 DBH
-1.88 DBH DBH 152 COLD 560P2 0.28 161 P 3 TWD 13 DBH
-1.73 TEC TEH AAS 16 HOT 600UL 52 160 0.56 27 P 2 TWD 23 VH3
-1.05 TEC TEE 33 HOT 600UL 53 77 0.38 89 P 3 TWD 16 DBC
-1.83 TEC TEE 11 HOT 600UL 0.37 85 P 5 TWD 26 DBC
-1.81 08C DBC 151 COLD 560P2 53 81 0.21 112 P 3 TWD 9 DBC
-1.96 TEC TEH 11 HOT 600UL 0.22 99 P 5 TWD 18 DBC
-1.90 DBC DBC 151 COLD 560P2 53 83 0.69 129 P 3 TWD 25 DBH
+1.33 TEC TEH 11 HOT 60OUL 1.07 91 P 3 TWD 33 DBC
-1.66 TEC TEH 11 HOT 60OUL 0.64 81 P 5 TWD 38 DBH
+1.81 DBH DBH 151 COLD 560P2 0.87 79 P 5 TWD 44 DBC
-1.80 08C DBC 151 COLD 560P2 53 95 0.28 85 P 5 TWD 20 DBH
+1.85 DBH DBH 152 COLD 560P2 0.27 76 P 3 TWD 13 DBH
+1.75 TEC TEH 15 HOT 600UL 53 125 0.20 72 P 1 SCI TSH
+0.05 TSH TSH 0.00 18.91 198 HOT 580PP 54 8
0.24 84 P 2 TWD 13 01C
+0.13 TEC TEH 13 HOT 600UL 0.26 102 P 5 TWD 18 01C
+0.14 01C 01C 139 COLD 580PP 54 12 0.39 67 P 2 TWD 16 VH3
+0.72 TEC TEE 18 HOT 600UL 54 14 0.32 73 P 2 TWD 17 VSM
-0.90 TEC TEE 17 HOT 600UL 54 22 0.18 89 P 3 TWD 10 DBH
-1.06 TEC TEE 25 HOT 600UL 54 32 0.34 110 P 2 TWD 16 VH3
-0.87 TEC TEH 26 HOT 600UL 54 66 0.31 69 P 2 TWD 16 VSM
-0.73 TEE TEC 38 COLD 600UL 54 78 0.18 95 2
SAI TSH
+0.97 TSH TSH 0.49 17.61 181 HOT 580PP 54 94 0.72 80 P 5 TWD 38 DBH
-1.79 DBH DBH 152 COLD 560P2 0.20 102 P 5 TWD 15 DBC
-1.84 DBC DBC 152 COLD 560P2 0.79 118 P 3 TWD 28 DBH
-2.14 TEC TEH 16 HOT 600UL 0.39 80 P 3 TWD 18 DBC
-1.99 TEC TEE AAS 16 HOT 60OUL 54 146 0.30 141 P 2 TWD 15 VH3
-0.81 TEC TEH 24 HOT 600UL 54 150 0.37 63 P 2 TWD 17 VH3
-1.01 TEC TEE 29 HOT 600UL 55 11 0.35 123 P 2 TWD 17 VH3
-0.81 TEC TEE 13 HOT 60OUL 55 15 0.32 117 P 2 TWD 14 VH3
-0.82 TEC TEH 18 HOT 60OUL 55 21 0.31 144 P 2 TWD 13 VH3
+0.85 TEC TEH 22 HOT 600UL 55 79 0.31 34 P 3 TWD 15 DBC
-1.80 TEC TEE 12 HOT 60OUL 0.25 88 P 5 TWD 19 DBC
-1.88 DBC DBC 151 COLD 560P2 55 85 0.34 96 P 3 TWD 15 DEE
+1.38 TEC TEE 11 HOT 60OUL 0.55 83 P 5 TWD 34 DBH
+1.74 DBH DBH 151 COLD 560P2
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:29 Component: S/G 89 Page 11 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand 0-100%twd.qry ROW LINE VOLTS 55 91 0.35 0.30 0.32 DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG 100 P 5 TWD 23 DBC
+1.95 DBC DBC 152 COLD 75 P 3 TWD 13 DBC
+1.93 TEC TEH 11 HOT 117 P 2 TWD 14 O1H
-0.18 TEC TEH 11 HOT PROBE 560P2 600UL 600UL 55 97 0.21 69 P 2 TWD 10 05H
+0.80 TEC TEH 15 HOT 60OUL 55 151 0.36 31 P 2 TWD 17 VH3
+0.74 TEC TEH 29 HOT 600UL 55 165 0.32 72 P 2 TWD 16 VH3
-0.80 TEC TEH 36 HOT 60OUL 56 8
0.34 70 P 2 TWD 17 VH3
+0.76 TEC TEH 13 HOT 60OUL 56 10 0.32 28 P 2 TWD 16 VH3
-0.96 TEC TEH 13 HOT 60OUL 56__12__0.38__137__P__2__TWO__20___H3_-0.81__________TEC_______TE_________17______HOT__________________L_
56 12 0.38 137 P 2 TWD 20 VH3
-0.81 TEC TEH 17 HOT 600UL 56 16 0.37 145 P 2 TWD 20 VH3
-0.96 TEC TEH 17 HOT 600UL 56 18 0.28 130 P 2 TWD 12 VH3
+0.73 TEC TEH 22 HOT 600UL 0.44 101 P 2 TWD 18 VH3
-0.84 TEC TEH 22 HOT 60OUL 56__30__0.37__114__P__2__TWO__14_V__3_-0.92__________TEC_______TEH________27______HOT__________________L_
56 22 0.40 90 P 2 TWD 19 VH3
-0.91 TEC TEH 25 HOT 600UL 56 28 0.48 101 P 2 TWD 18 VH3
-0.92 TEC TEH 27 HOT 600UL 56 30 0.37 114 P 2 TWD 14 VH3
-0.92 TEC TEH 27 HOT 60OUL 56 34 0.32 73 P 2 TWD 15 VH3
-0.86 TEC TEH 30 HOT 600UL 0.22 20 P 2 TWD 11 VH3
+0.76 TEC TEH 30 HOT 600UL 0.31 51 P 2 TWD 15 VC3
+0.82 TEC TEH 30 HOT 600UL 56 38 0.27 20 P 1 SCI TSH
-0.14 TSH TSH 0.00 17.80 227 HOT 580PP 56 64 0.32 102 P 2 TWD 16 VH3
-0.82 TEH TEC 38 COLD 600UL 56 82 1.08 88 P 2 TWD 34 VH3
-1.01 TEC TEH 12 HOT 600UL 0.62 98 P 2 TWD 25 VH3
+0.96 TEC TEC 12 HOT 600UL 0.36 83 P 5 TWD 25 VH3
+0.85 VH3 VH3 151 COLD 560P2 0.44 85 P 5 TWD 30 VH3
-0.92 VH3 VH3 151 COLD 560P2 56 84 0.58 118 P 3 TWD 22 DBH
+1.57 STH TEC 66 COLD 600UL 0.58 146 P 3 TWD 22 DBC
-1.80 STH TEC 66 COLD 600UL 0.52 85 P 5 TWD 33 DBH
+1.82 DBH DBH 151 COLD 560P2 0.83 77 P 5 TWD 43 DBC
-1.62 DBC DBC 151 COLD 560P2 56 92 0.34 144 P 3 TWD 16 DBC
+1.91 TEC TEH 12 HOT 600UL 0.21 77 P 3 TWD 10 DBC
-1.56 TEC TEH AAS 12 HOT 600UL 0.44 94 P 5 TWD 28 DBC
+1.54 DBC DBC 152 COLD 56OP2 0.28 98 P 5 TWD 20 DBC
-1.64 DBC DBC 152 COLD 56OP2 56 94 0.67 87 P 5 TWD 37 DBH
-1.85 DBH DBH 152 COLD 560P2 0.66 76 P 3 TWD 25 DBH
-1.75 TEC TEH 15 HOT 600UL 56 104 0.24 166 P 3 TWD 13 DBC
-0.96 TEH TEC 8
COLD 600UL 0.10 142 P 3 TWD 6 DBH
-0.15 TEH TEC 8
COLD 600UL 56 108 0.28 34 P 2 TWD 14 VSM
+0.81 TEH TEC 8
COLD 600UL 56 146 0.52 76 P 2 TWD 22 VH3
-0.90 TEC TEH 23 HOT 60OUL 56__148__0__35_123__P__2_TWO__17__V_3_-1.14__________TEC_______TE_________29______HOT_______________UL___
56 148 0.35 123 P 2 TWD 17 VH3
-1.14 TEC TEH 29 HOT 600UL 56 152 0.27 49 P 3 TWD 14 DBH
+0.58 TEC TEH 28 HOT 60OUL 56 154 0.28 66 P 2 TWD 15 03H
+0.82 TEC TEH 28 HOT 600UL 56 158 0.41 41 P 2 TWD 16 VH3
-0.71 TEH TEC 61 COLD 600UL 56 162 0.42 72 P 2 TWD 20 VH3
-0.96 TEC TEH 36 HOT 600UL 56 164 0.31 84 P 2 TWD 15 VH3
-0.79 TEC TEH 37 HOT 60OUL 57 15 0.35 103 P 2 TWD 19 VH3
-0.90 TEC TEH 17 HOT 600UL 57 79 0.58 86 P 3 TWD 22 DBC
-1.94 TEC TEH 11 HOT 600UL 0.64 78 P 5 TWD 37 DBC
-1.61 DBC DBC 151 COLD 560P2
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:29 Component: S/G 89 Page 12 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-=================__=====-
-=======-=======-=====-========-===
57 81 0.54 122 P 3 TWD 21 DBC
-1.87 STE TEC 66 COLD 600UL 0.51 83 P 5 TWD 33 DBC
-2.03 DBC DBC 151 COLD 560P2 57 83 1.10 78 P 3 TWD 33 DBC
-1.89 TEC TEN 11 HOT 60OUL 0.96 78 P 5 TWD 47 DBC
-1.61 DBC DBC 151 COLD 560P2 57 103 0.63 18 P 1 MCI TSH
-0.10 TSH TSH 0.30 18.20 233 HOT 580PP 57 159 0.45 77 P 2 TWD 18 VH3
+0.83 TEN TEC 61 COLD 600UL 58 16 0.45 56 P 2 TWD 18 VH3
-0.94 TEC TER 18 HOT 60OUL 58 24 0.51 93 P 2 TWD 20 VH3
-0.89 TEC TEE 22 HOT 600UL 58 80 0.22 99 P 2 TWD 11 VC3
+0.83 TEC TEE 11 HOT 600UL 0.15 152 P 2 TWD 8 VC3
-0.85 TEC TEE 11 HOT 600UL 0.20 60 P 2 TWD 10 VH3
+0.91 TEC TEE 11 HOT 60OUL 58 82 0.42 135 P 3 TWD 18 DBH
+1.47 TEC TEE 11 HOT 600UL 0.38 90 P 5 TWD 27 DBH
+1.71 DBH DBH 151 COLD 560P2 58 86 0.68 119 P 3 TWD 25 DBC
+1.29 TEC TEE 11 HOT 60OUL 0.60 83 P 5 TWD 36 DBC
+1.63 DBC DBC 151 COLD 560P2 58 90 0.53 114 P 3 TWD 22 DBC
+1.82 TEC TEN 12 HOT 600UL 1.08 94 P 3 TWD 33 DBH
-2.15 TEC TEE 12 HOT 600UL 0.79 83 P 5 TWD 40 DBH
-1.85 DBH DBH APN 152 COLD 560P2 0.39 88 P 5 TWD 26 DBC
+1.91 DBC DBC 152 COLD 560P2 58 92 0.25 94 P 5 TWD 18 DBH
+1.98 DBH DBH 152 COLD 560P2 0.28 73 P 3 TWD 13 DBH
+1.12 TEC TEE 11 HOT 60OUL 58 94 0.33 90 P 5 TWD 22 DBC
-1.70 DBC DBC 152 COLD 560P2 0.35 41 P 3 TWD 16 DBC
-1.67 TEC TEE AAS 16 HOT 600UL 58 96 0.28 88 P 5 TWD 20 DBH
-1.69 DBH DBH 152 COLD 560P2 0.26 50 P 3 TWD 12 DBH
-2.09 TEC TEE 15 HOT 600UL 58 116 0.27 95 P 2 TWD 12 08C
-0.19 TEN TEC 6
COLD 60OUL 0.18 120 2 SAI 08C
-0.15 08C 08C 136 COLD 580PP 58 146 0.51 46 P 2 TWD 21 08H
-0.95 TEC TEE 24 HOT 60OUL 0.45 70 P 2 TWD 20 VH3
-0.95 TEC TEE 24 HOT 600UL 58 154 0.36 131 P 2 TWD 17 VH3
-0.93 TEC TEN 29 HOT 60OUL 59__23__0.44___61_P__2_TWO___20_V__3_-1.11__________TEC________TEE_______25______HOT_____________________
59 23 0.44 61 P 2 TWD 20 VH3
-1.11 TEC TEE 25 HOT 600UL 59 25 0.43 90 P 2 TWD 20 VH3
-0.93 TEC TER 25 HOT 600UL 59 77 0.37 44 P 2 TWD 16 04H
+0.91 TEC TEE 11 HOT 600UL 59 95 0.45 84 P 5 TWD 28 DBH
-1.83 DBH DEH 152 COLD 560P2 0.19 67 P 3 TWD 9 DBC
+0.85 TEC TEE 15 HOT 600UL 0.34 128 P 3 TWD 15 DBH
-2.04 TEC TEE 15 HOT 600UL 59__143__0.30__143__P_2_TWD__15__V_3_-0.71__________TEC________TEE_______24______ROT_____________________
59 143 0.30 143 P 2 TWD 15 VH3
-0.71 TEC TEN 24 HOT 600UL 59 147 0.41 73 P 2 TWD 19 VH3
+0.89 TEC TEN 24 HOT 600UL 0.35 115 P 2 TWD 17 VH3
-0.91 TEC TEE 24 HOT 60OUL 59 153 0.38 122 P 2 TWD 18 VH3
+0.92 TEC TEE 29 HOT 600UL 59 157 0.24 132 P 2 TWD 12 VH3
+1.01 TEC TER 33 HOT 600UL 0.24 110 P 2 TWD 12 VH3
-0.93 TEC TEE 33 HOT 60OUL 59 159 0.39 33 P 2 TWD 18 VH3
-1.20 TEC TEN 33 HOT 600UL 0.32 51 P 2 TWD 15 VH3
+0.40 TEC TEE 33 HOT 60OUL 60 24 0.37 48 P 2 TWD 18 VH3
-0.91 TEC TEE 25 HOT 60OUL 60 30 0.48 65 P 2 TWD 18 VH3
-1.03 TEC TEE 27 HOT 600UL 60 88 0.55 85 P 5 TWD 32 DBH
+1.78 DBH DBH 152 COLD 560P2 0.55 143 P 3 TWD 21 DBH
+2.25 TEC TEE 11 HOT 60OUL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:29 Component:
S/G 89 Page 13 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-========================-
-=======-=======-=====-========-===
60 94 0.34 83 P 5 TWD 23 DBH
+1.77 DBH DBH 152 COLD 560P2 0.55 83 P 5 TWD 33 DBC
-1.79 DBC DBC 152 COLD 560P2 0.41 143 P 3 TWD 18 DBC
-1.75 TEC TEH 15 HOT 600UL 0.49 160 P 3 TWD 20 DBH
+1.75 TEC TEH 15 HOT 600UL 60 118 0.28 33 P 3 TWD 12 DBC
+1.50 TEH TEC 3
COLD 600UL 60 146 0.39 90 P 2 TWD 18 VH3
-1.06 TEC TEH 23 HOT 600UL 61 19 0.32 92 P 2 TWD 14 VH3
+0.87 TEC TEH 22 HOT 60OUL 61 35 0.24 136 P 2 TWO 12 VC3
+0.80 TEC TEH 30 HOT 600UL 61 89 0.36 77 P 5 TWD 24 DBC
-1.59 DBC DBC 152 COLD 560P2 0.34 42 P 3 TWD 15 DBC
-1.67 TEC TEH 11 HOT 60OUL 61 103 0.25 13 P 3 TWD 14 DBH
+1.94 TEH TEC 7
COLD 600UL 61 153 0.39 111 P 3 TWD 19 DBH
+1.35 TEC TEH 28 HOT 600UL 62 18 0.24 98 P 3 TWD 12 DBC
+1.85 TEH TEC 69 COLD 60OUL 62 40 0.36 36 P 3 TWD 15 DBC
+1.87 TEC TEH 31 HOT 600UL 62 52 0.14 89 2
MAI 01H
+15.15 TO+17.08 01H 01H 0.21 344 HOT 520ET 62 76 0.12 110 2 SAI TSH
+0.59 TSH TSH 0.92 18.08 182 HOT 580PP 0.10 115 2 SAI 02H
+6.19 02H 02H 0.16 182 HOT 580PP 62 84 0.58 79 P 3 TWD 24 DBH
-1.97 TEC TEH 12 HOT 60OUL 0.56 104 P 3 TWD 23 DBC
-1.82 TEC TEH 12 HOT 600UL 0.66 83 P 5 TWD 38 DBH
-1.68 DBH DBH 151 COLD 560P2 0.44 83 P 5 TWD 30 DBC
-1.67 DBC DBC 151 COLD 560P2 62 94 0.66 86 P 5 TWD 36 DBC
+1.86 DBC DBC 152 COLD 560P2 0.75 119 P 3 TWD 27 DBC
+1.56 TEC TEH AAS 16 HOT 600UL 62 100 0.12 77 P 1 SCI TSH
+0.07 TSH TSH 0.00 17.51 189 HOT 58OPP 63 21 0.33 123 P 2 TWD 14 VC3
-0.79 TEC TEH 22 HOT 600UL 63 79 0.68 47 P 3 TWD 25 DBC
-1.77 TEC TEH 11 HOT 600UL 0.59 81 P 5 TWD 36 DBC
-1.76 DBC DBC 151 COLD 560P2 63 83 0.74 120 P 3 TWD 26 DBC
-1.96 TEC TEH 11 HOT 600UL 0.82 78 P 5 TWD 43 DBC
-1.78 DBC DBC 151 COLD 560P2 63 87 0.64 83 P 5 TWD 36 DEH
-1.77 DBH DEH 152 COLD 560P2 0.68 133 P 3 TWD 24 DBH
-1.84 STH TEC 66 COLD 600UL 63 145 0.49 93 P 2 TWD 22 VH3
+0.75 TEC TEH 23 HOT 60OUL 63 159 0.35 90 P 2 TWD 17 VH3
-1.13 TEC TEH 33 HOT 600UL 0.29 136 P 2 TWD 14 VH3
+0.82 TEC TEH 33 HOT 600UL 64 10 0.44 103 P 2 TWD 20 03C
-0.97 TEC TEH 13 HOT 600UL 0.46 104 P 5 TWD 27 03C
-0.99 03C 03C 139 COLD 580PP 64 12 0.50 101 P 2 TWD 24 VH3
+0.74 TEC TEH 17 HOT 60OUL 64 16 0.23 156 P 2 TWD 13 VH3
-0.88 TEC TEH 17 HOT 600UL 64 18 0.49 81 P 2 TWD 19 VH3
+0.73 TEC TEH 22 HOT 600UL 0.35 133 P 2 TWD 15 VH3
-0.96 TEC TEH 22 HOT 600UL 64 20 0.59 143 P 2 TWD 22 VH3
+0.02 TEC TEH 22 HOT 600UL 64 66 0.12 75 2
SAI TSH
+1.53 TSH TSH 0.10 18.02 173 HOT 580PP 64 82 0.53 100 P 3 TWD 22 DBC
+1.89 TEC TEH 12 HOT 600UL 0.44 84 P 5 TWD 30 DBC
+1.46 DBC DBC 151 COLD 560P2 64 84 0.30 66 P 3 TWD 13 DBH
+1.54 TEC TEH 11 HOT 600UL 0.29 85 P 5 TWD 22 DBH
+1.89 DBH DBH 151 COLD 560P2
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodes and_0-100%twd.qry 03/07/04 14:17:29 Component: S/G 89 Page 14 of 31 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 64 86 0.31 139 P 3 TWD 13 DBH
-1.81 STH TEC 66 COLD 60OUL 0.37 84 P 5 TWD 26 DBH
-1.68 VH3 DBH 151 COLD 560P2 64 88 0.13 122 P 1 SCI TSH
+0.09 TSH TSH 0.00 18.43 182 HOT 580PP 64 92 0.21 82 P 5 TWD 15 DBH
-1.89 VH3 DBH 152 COLD 560P2 0.20 99 P 3 TWD 8 DBH
-1.98 STH TEC 66 COLD 60OUL 64 94 0.32 92 P 5 TWD 22 DBC
-1.85 DBC DBC 152 COLD 560P2 0.29 77 P 3 TWD 13 DBC
-1.39 TEC TER 15 HOT 60OUL 65 13 0.37 127 P 2 TWO 20 VH--
3
-0.88 TEC TEE 17 HOT 600UL 65 15 0.38 61 P 2 TWD 20 VSM
-0.74 TEC TER 17 HOT 60OUL 0.37 132 P 2 TWD 19 VH3
+0.80 TEC TEH 17 HOT 60OUL 0.37 133 P 2 TWD 19 VH3
-0.84 TEC TEH 17 HOT 60OUL 65 47 0.31 93 2
SAI 04H
+1.06 04H 04H 0.0 265 HOT 580PP 65 89 0.67 85 P 5 TWD 37 DBH
+1.68 DBH DBH 152 COLD 560P2 0.80 150 P 3 TWD 27 DBH
+1.78 TEC TEE 11 HOT 60OUL 65 151 0.53 14 2
SAI TSH
-18.48 TSH TSH 0.46 19.29 183 HOT 580PP 65 155 0.27 29 P 2 TWD 14 VH3
-0.74 TEC TER 28 HOT 60OUL 66 80 0.27 76 P 3 TWD 12 DBC
+2.02 TEC TEN 11 HOT 600UL 0.25 86 P 5 TWD 19 DBC
+2.07 DBC DBC 151 COLD 560P2 66 84 0.32 45 P 3 TWD 15 DBH
-2.02 TEC TEE 12 HOT 60OUL 0.33 73 P 5 TWD 24 DBH
-1.70 DBH DBH 151 COLD 560P2 66 88 0.38 90 P 5 TWD 25 DBC
+1.80 DBC DBC 152 COLD 560P2 0.45 93 P 3 TWD 19 DBC
+1.92 TEC TEH 11 HOT 60OUL 66 94 0.36 78 P 5 TWD 24 DBC
+1.16 DBC DBC 152 COLD 560P2 0.21 96 P 5 TWD 15 DBC
-1.85 DEC DBC 152 COLD 560P2 0.36 62 P 3 TWD 16 DBC
+2.03 TEC TEN 15 HOT 60OUL 0.15 81 P 3 TWD 8 DBC
-1.75 TEC TEN 15 HOT 60OUL 66 138 0.33 99 P 2 TWD 16 08C
-0.70 TEC TEN 20 HOT 60OUL 0.26 106 P 5 TWD 18 08C
-0.91 08C 08C 138 COLD 580PP 66 144 0.75 117 P 2 TWD 27 04C
-0.98 TEC TEN 24 HOT 600UL 0.91 73 P 2 TWD 31 06C
-0.98 TEC TEE 24 HOT 600UL 0.54 92 P 2 TWD 22 VSM
-0.95 TEC TEN 24 HOT 60OUL 0.41 71 P 2 TWD 17 VH3
-0.97 TEC TEE 24 HOT 60OUL 0.31 67 P 2 TWD 15 05C
+0.98 TEC TEN 24 HOT 600UL 0.23 91 P 5 TWD 19 VSM
-0.92 VSM VSM 149 COLD 560P2 0.20 83 P 5 TWD 18 VH3
-0.89 VH3 VH3 149 COLD 560P2 0.23 98 P 5 TWD 17 05C
+0.97 05C 05C 138 COLD 580PP 0.84 76 P 5 TWD 31 04C
-0.90 04C 04C 138 COLD 580PP 0.96 76 P 5 TWD 34 06C
-0.92 06C 06C 138 COLD 580PP 66 152 0.37 102 P 2 TWD 17 VH3
-1.24 TEC TEE 29 HOT 60OUL 66 156 0.47 120 P 2 TWD 21 VH3
-0.86 TEC TEE 29 HOT 60OUL 67 19 0.14 105 2 SAI 05H
+3.08 TO+5.04 05H 05H 0.24 211 HOT 580PP 0.12 98 2
SAI 05H
+1.23 05H 05H 0.18 211 HOT 580PP 67 71 0.13 104 2 SAI TSH
+2.28 TSH TSH 0.07 17.68 173 HOT 580PP 67 83 0.56 66 P 3 TWD 22 DBC
-1.98 TEC TEN 11 HOT 60OUL 0.30 59 P 3 TWD 13 DBH
-1.60 TEC TEN 11 HOT 600UL 0.54 79 P 5 TWD 34 DBC
-1.87 DBC DBC 151 COLD 560P2 0.26 82 P 5 TWD 20 DBH
-1.76 DBH DBH 151 COLD 560P2 68 12 0.33 127 P 2 TWD 18 VH3
-0.89 TEC TEE 17 HOT 60OUL 68 20 0.40 111 2 SAI 06H
+0.64 06H 06H 0.26 211 HOT 580PP 0.45 143 P 2 TWD 20 VH3
+0.89 TEC TEN 25 HOT 600UL 0.50 132 P 2 TWD 22 VH3
-0.87 TEC TEN 25 HOT 600UL 68 22 0.21 99 2
SAI 06H
+0.90 06H 06H 0.0 215 HOT 580PP 0.53 64 P 2 TWD 20 VH3
+0.80 TEC TEE 22 HOT 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:29 Component: S/G 89 Page 15 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand0-100%twd.qry ROW LINE VOLTS 0.65 0.50 DEG CHN 65 P 2 59 P 2 IND TWO TWD
%TW 23 19 LOCATION VH3
-0.78 06H
+0.90 EXT EXT TEC TEH TEC TEH UTIL 1 UTIL 2 CAL #
22 22 LEG HOT HOT PROBE 600UL 60OUL 68 78 0.18 80 P 2 TWD 9 VC3
+0.77 TEC TEH 11 HOT 600UL 68 84 0.13 99 2
SAI TSH
+2.10 TSH TSH 0.14 18.37 252 HOT 580PP 0.22 81 P 2 TWD 11 VSM
-0.87 TEC TEH 11 HOT 600UL 68 90 0.66 77 P 5 TWD 36 DBC
-1.74 DBC DBC 152 COLD 560P2 0.30 89 P 5 TWD 21 DBH
-1.58 DBH DBH 152 COLD 560P2 0.28 71 P 3 TWD 13 DBH
-0.59 TEC TEH 11 HOT 60OUL 0.55 98 P 3 TWD 22 DBC
-1.97 TEC TEH 11 HOT 600UL 68 128 0.31 45 P 2 TWD 13 VH3
-0.79 TEH TEC 2
COLD 600UL 68 146 0.31 136 P 2 TWD 15 VSM
+0.61 TEC TEH 23 HOT 600UL 69____13____0.36_____135_____P__2___TWO_____19_____H_____+0___80____T___C__T___R___17____HOT_____________
69 13 0.36 135 P 2 TWD 19 VH3
+0.80 TEC TEH 17 HOT 600UL 69 15 0.50 150 P 2 TWD 24 VH3
+0.86 TEC TEH 17 HOT 600UL 0.41 145 P 2 TWD 21 VH3
-0.80 TEC TEH 17 HOT 600UL 69 19 0.45 109 P 2 TWD 18 VH3
-0.73 TEC TEH 22 HOT 600UL 69 163 0.30 128 P 2 TWD 13 02C
+0.91 TEC TEH 37 HOT 600UL 0.29 92 P 5 TWD 20 02C
+0.92 02C 02C 138 COLD 580PP 70 14 0.47 149 P 2 TWD 23 VH3
-0.78 TEC TEH 17 HOT 60OUL 70 24 0.24 29 P 3 TWD 11 DBC
-1.11 TEC TEH 22 HOT 600UL 0.29 54 P 3 TWD 13 DBC
+1.46 TEC TEH 22 HOT 600UL 0.15 80 P 5 TWD 11 DBC
-1.31 DBC DBC 157 COLD 560P2 0.19 67 P 5 TWD 14 DBC
+1.51 DBC DBC 157 COLD 560P2 70 38 0.35 97 P 2 TWD 17 VC3
+0.69 TEC TEH 30 HOT 600UL 70 52 0.38 121 P 3 TWD 14 DBC
+1.75 TEH TEC 43 COLD 600UL 0.18 98 P 5 TWD 14 DBC
+1.67 DBC DBC 154 COLD 560P2 70 90 0.28 153 P 3 TWD 14 DBH
-2.00 TEC TEH 12 HOT 60OUL 0.23 99 P 5 TWD 17 DBH
-1.94 DBH DBH 152 COLD 560P2 70 94 0.26 94 P 5 TWD 18 DBC
-1.90 DBC DBC 152 COLD 560P2 0.31 81 P 3 TWD 13 DBC
-1.85 TEC TEH 15 HOT 60OUL 70 112 0.49 132 P 2 TWD 19 03C
-0.06 TEH TEC 6
COLD 600UL 70 144 0.42 87 P 2 TWD 18 VC3
-0.85 TEC TEH 24 HOT 600UL 0.32 24 P 2 TWD 13 VSM
-0.93 TEC TEH 24 HOT 60OUL 0.14 87 P 5 TWD 13 VSM
-0.85 VSM VSM 149 COLD 560P2 0.35 98 P 5 TWD 17 VC3
-0.77 VC3 VC3 165 COLD 560P2 70 152 0.28 112 P 2 TWD 14 VH3
-0.97 TEC TEH 29 HOT 600UL 71 71 2.77 34 2
SAI TSH
-11.36 TSH TSH 3.66 17.32 173 HOT 580PP 71 79 0.45 83 P 3 TWD 19 DBC
-1.76 TEC TEH 11 HOT 600UL 0.42 84 P 5 TWD 28 DBC
-1.84 DBC DBC 151 COLD 560P2 71 91 0.31 88 P 5 TWD 21 DBC
-1.40 DBC DBC 152 COLD 560P2 0.31 151 P 3 TWD 14 DBC
-1.59 TEC TEH 11 HOT 600UL 71 93 0.19 95 P 5 TWD 14 DBC
-1.97 DBC DBC 152 COLD 560P2 0.22 127 P 3 TWD 11 DBC
-1.91 TEC TEH 16 HOT 60OUL 71 103 0.32 73 P 3 TWD 16 DBH
-0.27 TEH TEC 7
COLD 600UL 71 113 0.21 88 2
SAI 02H
-16.98 02H 02H 0.18 225 HOT 580PP 71 143 0.34 115 P 2 TWD 14 VSM
+0.50 TEC TEH 24 HOT 600UL 0.40 119 P 2 TWD 17 VH3
-0.91 TEC TEH 24 HOT 60OUL 0.23 82 P 2 TWD 12 04C
-0.20 TEC TEH 24 HOT 600UL 0.27 153 P 2 TWD 11 VC3
-0.83 TEC TEH AAS 24 HOT 600UL 0.25 84 P 5 TWD 21 VSM
+0.46 VSM VSM 149 COLD 560P2 0.25 95 P 5 TWD 20 VH3
-0.92 VH3 VH3 149 COLD 560P2 0.16 91 P 5 TWD 15 VC3
-0.88 VC3 VC3 149 COLD 560P2
Framatome ANP Inc.
03/07/04 14:17:30 Customer Name: San Onofre -
Unit 2 Component: S/G 89 Page 16 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.18 117 P 5 TWD 14 04C
-0.11 04C 04C 138 COLD 580PP 71 147 0.44 97 P 2 TWD 20 VC3
-1.09 TEC TEE 29 HOT 600UL 0.69 103 P 2 TWD 27 VH3
-0.85 TEC TEE 29 HOT 600UL 0.28 91 P 5 TWD 23 VC3
-0.97 VC3 VC3 149 COLD 560P2 0.31 88 P 5 TWD 24 VH3
-0.93 VE3 VH3 149 COLD 560P2 71 155 0.47 58 P 2 TWD 21 VH3
+0.58 TEC TEE 29 HOT 60OUL 0.39 72 P 2 TWD 18 VH3
-0.78 TEC TEE 29 HOT 600UL 71 157 0.38 84 P 2 TWD 18 VH3
+0.84 TEC TEE 33 HOT 60OUL 71 161 0.32 138 P 2 TWD 14 VH3
-0.78 TEC TEN 37 HOT 60OUL 71 163 0.48 98 P 2 TWD 22 VH3
-0.85 TEC TEE 36 HOT 600UL 72 16 0.37 91 P 2 TWD 20 VH3
-0.79 TEC TEE 17 HOT 60OUL 72 26 0.52 113 P 2 TWD 19 VC3
+0.80 TEC TEE 27 HOT 600UL 0.31 86 P 5 TWD 21 VC3
+0.72 VC3 VC3 157 COLD 560P2 72 28 0.23 152 P 3 TWD 10 DBC
+0.47 TEC TEE 27 HOT 60OUL 72 36 0.48 40 P 3 TWD 19 DBC
+2.01 TEC TEE 31 HOT 600UL 0.21 91 P 5 TWD 15 DBC
+1.90 DBC DBC 157 COLD 560P2 72 38 0.34 20 P 3 TWD 14 DBC
+1.72 TEC TEE 31 HOT 600UL 0.25 97 P 5 TWD 17 DBC
+1.18 DBC DBC 157 COLD 560P2 72 78 0.22 140 P 2 TWD 11 VC3
+0.94 TEC TEE 11 HOT 600UL 0.28 104 P 2 TWD 13 VH3
+0.84 TEC TEE 11 HOT 600UL 0.54 85 P 2 TWD 22 VH3
-0.84 TEC TEE 11 HOT GO6UL 0.24 83 P 5 TWD 19 VH3
-0.88 VH3 VH3 151 COLD 560P2 0.18 85 P 5 TWD 15 VH3
+0.81 VH3 VH3 151 COLD 560P2 0.16 77 P 5 TWD 13 VC3
+0.82 VC3 VC3 151 COLD 560P2 72 80 0.39 147 P 2 TWD 17 VC3
+0.87 TEC TEE 11 HOT 60OUL 0.23 96 P 5 TWD 18 VC3
+0.79 VC3 VC3 151 COLD 560P2 72 84 0.27 91 P 2 TWD 12 VH3
-0.85 TEC TEE 11 HOT 60OUL 0.34 107 P 3 TWD 15 DBC
-1.82 TEC TEE 11 HOT 60OUL 0.20 70 P 5 TWD 16 VH3
-0.89 VH3 VH3 151 COLD 560P2 0.37 89 P 5 TWD 26 DBC
-2.16 DBC DBC 151 COLD 560P2 72 86 0.26 33 P 2 TWD 12 VSM
-0.91 TEC TEE 11 HOT 60OUL 0.39 97 P 3 TWD 16 DBH
+0.46 TEC TEE 11 HOT 600UL 72 90 0.28 82 P 5 TWD 20 DBC
-1.59 DBC DBC 152 COLD 560P2 0.34 101 P 3 TWD 15 DBC
-1.65 TEC TEE 11 HOT 600UL 72 114 0.27 75 P 2 TWD 12 VC3
+0.89 TEE TEC 5
COLD 60OUL 0.38 152 P 3 TWD 14 DBC
+1.92 TEE TEC S
COLD 600UL 0.16 92 P 5 TWD 13 VC3
+0.78 VC3 VC3 146 COLD 560P2 72 126 0.46 85 P 2 TWD 19 VSM
-0.80 TEE TEC 3
COLD 60OUL 0.38 116 P 2 TWD 17 VH3
-0.16 TEE TEC 3
COLD 600UL 0.23 87 P 5 TWD 16 VSM
-0.59 VSM VSM 146 COLD 560P2 0.33 82 P 5 TWD 23 VH3
-0.11 VH3 VH3 146 COLD 560P2 73 13 0.14 88 P 5 TWD 14 VH3
+0.84 VSM VH3 159 COLD 560P2 0.32 51 P 2 TWD 17 VH3
+0.84 TEC TEE 17 HOT 600UL 73 57 0.42 65 P 2 TWD 15 01H
+0.97 TEE TEC 42 COLD 600UL 73 103 0.36 96 P 2 TWD 17 02H
-1.24 TEE TEC 8
COLD 600UL 74 18 0.33 148 P 3 TWD 15 DBC
+1.78 TEE TEC 69 COLD 60OUL 0.22 91 P 5 TWD 15 DBC
+1.76 DBC DBC 156 COLD 560P2 74 26 0.28 83 P 2 TWD 14 VC3
-0.87 TEC TEE 26 HOT 600UL 74 44 0.51 110 P 2 TWD 19 VSM
-0.15 TEC TEE 35 HOT 600UL 0.62 144 P 2 TWD 23 VH3
-0.81 TEC TEE 35 HOT 600UL 0.19 98 P 5 TWD 14 VSM
+0.03 VSM VSM 177 COLD 560P2 0.32 89 P 5 TWD 22 VH3
-0.73 VH3 VH3 156 COLD 560P2
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:30 Component: S/G 89 Page 17 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1
74 54 0.10 134 P 3 TWD 4 DBH
-1.91 TEH TEC UTIL 2 CAL # LEG PROBE 44 COLD 600UL 74 56 0.40 139 P 3 TWD 16 DBH
+1.06 TEH TEC 42 COLD 600UL 0.26 82 P 5 TWD 19 DBH
+1.13 DBH DBH 153 COLD 560P2 74 78 0.16 112 2 SAI TSH
+3.67 TSH TSH 0.00 17.97 182 HOT 580PP 74 90 0.39 98 P 3 TWD 18 DEC
-1.75 TEC TEH 12 HOT 600UL 0.31 90 P 5 TWD 21 DEC
-1.47 DBC DBC 152 COLD 560P2 74 94 0.22 83 P 5 TWD 16 DBH
-1.66 DBH DBH 152 COLD 560P2 0.48 34 P 3 TWD 20 DBH
+1.60 TEC TEH 16 HOT 600UL 0.20 39 P 3 TWD 10 DBH
-1.90 TEC TEH 16 HOT 600UL 74 96 0.40 62 P 2 TWD 18 02H
-1.23 TEC TEH 16 HOT 60OUL 74 132 0.29 89 P 2 TWD 14 VC3
-1.06 TEC TEH 20 HOT 600UL 0.17 78 P 5 TWD 13 VC3
-0.99 VC3 VC3 147 COLD 560P2 74 140 0.32 15 P 3 TWD 16 DBH
+2.25 TEC TEH 24 HOT 600UL 74 146 0.32 84 P 2 TWD 15 VH3
+0.81 TEC TEH 24 HOT 600UL 74 148 0.18 22 P 2 TWD 10 VSM
-0.86 TEC TEH 28 HOT 600UL 0.41 145 P 2 TWD 21 VH3
-0.96 TEC TEH 28 HOT 600UL 0.31 78 P 5 TWD 24 VH3
-0.91 VH3 VH3 149 COLD 560P2 0.21 92 P 5 TWD 18 VSM
-0.82 VSM VSM 149 COLD 560P2 74 156 0.49 53 P 2 TWD 22 VC3
-0.84 TEC TEH 29 HOT 60OUL 0.47 86 P 2 TWD 21 VSM
-0.82 TEC TEH 29 HOT 600UL 0.55 97 P 2 TWD 23 VH3
-0.84 TEC TEH 29 HOT 60OUL 0.31 116 P 5 TWD 15 VH3
-0.84 VH3 VH3 165 COLD 560P2 0.25 87 P 5 TWD 20 VSM
-0.84 VSM VSM 150 COLD 560P2 0.20 82 P 5 TWD 16 VC3
-0.76 VC3 VC3 150 COLD 560P2 75 17 0.18 123 2 SAI 06H
+10.00 06H 06H 0.13 211 HOT 580PP 0.25 111 2 SAI 06H
-0.23 06H 06H 0.38 211 HOT 580PP 75 51 0.27 136 P 3 TWD 12 DBH
-1.93 TEH TEC 44 COLD 60OUL 0.13 93 P 5 TWD 11 DBH
-1.80 DBH DBH 153 COLD 560P2 75 73 0.20 108 2 SAI TSH
+0.26 TSH TSH 0.00 21.38 308 HOT 580PP 75 79 0.85 103 P 3 TWD 29 DBC
-1.68 TEC TEH 11 HOT 600UL 0.61 80 P 5 TWD 37 DBC
-1.83 DBC DEC 151 COLD 560P2 75 83 0.34 74 P 3 TWD 15 DEC
-1.97 TEC TEH 11 HOT 600UL 0.35 82 P 5 TWD 25 DEC
-1.65 DBC DBC 151 COLD 560P2 75 87 0.40 120 P 3 TWD 17 DBC
-2.02 TEC TEH 11 HOT 600UL 0.40 90 P 5 TWD 28 DBC
-1.94 DBC DEC 151 COLD 560P2 75 97 0.19 95 P 5 TWD 14 VC3
+0.90 VC3 VC3 152 COLD 560P2 0.17 110 P 5 TWD 13 VC3
-0.89 VC3 VC3 152 COLD 560P2 0.24 48 P 2 TWD 12 VC3
-0.90 TEC TEH 16 HOT 600UL 0.27 113 P 2 TWD 14 VC3
+0.83 TEC TEH AAS 16 HOT 600UL 75 103 0.15 85 P 5 TWD 12 VC3
+0.69 VC3 VC3 146 COLD 560P2 0.17 95 P 2 TWD 10 VC3
+0.95 TEH TEC 7
COLD 600UL 75 105 0.40 117 P 2 TWD 20 VH3
-0.72 STH TEC 11 COLD 600UL 0.39 126 P 2 TWD 19 VSM
-0.21 STH TEC 11 COLD 600UL 0.27 93 P 5 TWD 19 VH3
-0.89 VH3 VH3 AAS 146 COLD 560P2 0.32 102 P 5 TWD 22 VSM
-0.25 VSM VSM 146 COLD 560P2 75 111 1.03 110 P 2 TWD 32 VC3
+0.93 TEH TEC 5
COLD 600UL 0.50 129 P 2 TWD 20 VH3
+0.15 TEH TEC 5
COLD 600UL 0.33 20 P 2 TWD 15 VSM
+0.81 TEH TEC 5
COLD 600UL 0.28 92 P 5 TWD 20 VH3
-0.11 VH3 VH3 146 COLD 560P2 0.20 96 P 5 TWD 15 VSM
+0.77 VSM VSM 146 COLD 560P2 0.43 85 P 5 TWD 28 VC3
+0.75 VC3 VC3 146 COLD 560P2 75 119 0.56 127 P 3 TWD 20 DBC
+1.63 TEH TEC 3
COLD 600UL 75__125__0.25__85__P_2__TWO__12__07__-0.85__________TEE________TEC_______3_____COLD_________600UL________
75 125 0.25 85 P 2 TWD 12 07H
-0.85 TEH TEC 3
COLD 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc icodes and_0-100%twd.qry 03/07/04 14:17:30 Component: S/G 89 Page 18 of 31 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 75 139 2.48 22 2
MAI TSH
-13.75 TSH TSH 4.08 19.93 168 HOT 580PP 76 22 0.34 55 P 2 TWD 14 VSM
-0.78 TEC TEH 22 HOT 600UL 76 42 0.20 132 P 3 TWD 11 DBC
-1.74 TEC TEH 34 HOT 60OUL 76 66 0.39 57 P 2 TWD 14 01H
-1.21 TEH TEC 40 COLD 600UL 76 78 0.50 109 P 2 TWD 21 VC3
+0.90 TEC TEH 11 HOT 600UL 0.25 131 P 2 TWD 12 VC3
-0.88 TEC TEH 11 HOT 600UL 0.27 87 P 2 TWD 13 VH3
+0.84 TEC TEH 11 HOT 600UL 0.23 92 P 5 TWD 18 VC3
+0.82 VC3 VC3 151 COLD 560P2 0.17 92 P 5 TWD 14 VC3
-0.93 VC3 VC3 151 COLD 560P2 0.19 95 P 5 TWD 15 VH3
+0.85 VH3 VH3 151 COLD 560P2 76 90 0.36 74 P 5 TWD 24 DBC
-1.70 DBC DBC 152 COLD 560P2 0.32 126 P 3 TWD 14 DBC
-1.96 TEC TEH 11 HOT 60OUL 76 94 0.12 67 P 5 TWD 9 DBC
+1.77 DBC VC3 152 COLD 560P2 76 114 0.42 56 P 2 TWD 18 VH3
-0.75 TEH TEC 5
COLD 60OUL 0.15 88 P 5 TWD 12 VH3
-0.90 VH3 VH3 146 COLD 560P2 76 142 0.25 120 P 2 TWD 13 08C
-0.41 TEC TEH 23 HOT 60OUL 77 27 0.29 111 P 3 TWD 12 DBC
-1.60 TEC TEH 27 HOT 600UL 0.21 80 P 5 TWD 14 DEC
-1.58 DBC DEC 156 COLD 560P2 77 43 0.27 140 P 2 TWD 12 VH3
+0.84 TEC TEH 35 HOT 600UL 0.25 84 P 5 TWD 16 VH3
+0.70 VH3 VH3 156 COLD 560P2 77 113 0.23 83 P 2 TWD 10 VH3
-0.95 TEH TEC APN 6
COLD 600UL 0.16 89 P 5 TWD 13 VH3
-1.07 VH3 VH3 146 COLD 560P2 77 115 0.31 23 P 1 SCI TSH
-6.40 TSH TSH 0.50 18.03 225 HOT 580PP 77 137 0.53 83 P 2 TWD 25 VSM
-0.94 TEC TEH 19 HOT 600UL 0.37 82 P 5 TWD 25 VSM
-0.91 VSM VSM 147 COLD 560P2 77 139 0.68 128 P 2 TWD 27 VC3
+0.87 TEC TEH 23 HOT 60OUL 0.52 81 P 2 TWD 22 VSM
-0.96 TEC TEH 23 HOT 600UL 0.32 119 P 2 TWD 16 VH3
-0.93 TEC TEH 23 HOT 600UL 0.19 91 P 5 TWD 15 VSM
-0.90 VSM VSM 147 COLD 560P2 0.22 103 P 5 TWD 17 VH3
-0.95 VH3 VH3 147 COLD 560P2 0.38 93 P 5 TWD 25 VC3
+0.90 VC3 VC3 147 COLD 560P2 0.14 105 P 5 TWD 11 VC3
+0.16 VC3 VC3 147 COLD 560P2 0.13 102 P 5 TWD 10 VC3
-0.83 VC3 VC3 147 COLD 560P2 78 26 0.31 96 P 2 TWD 14 07C
-0.18 TEC TEH 26 HOT 600UL 78 28 0.25 86 P 5 TWD 16 DBC
-1.68 DBC DBC 156 COLD 560P2 0.16 133 P 3 TWD 8 DBC
-1.53 TEC TEH 26 HOT 60OUL 78 44 0.48 132 P 2 TWD 19 VSM
-0.82 TEC TEH 35 HOT 60OUL 0.23 87 P 5 TWD 15 VSM
-0.59 VSM VSM 156 COLD 560P2 78 64 0.26 14 2
SAI TSH
-10.99 TSH TSH 0.00 19.08 170 HOT 58OPP 1.36 24 2
SAI TSH
-10.68 TSH TSH 1.05 19.08 170 HOT 58OPP 0.96 26 2
SAI TSH
-10.51 TSH TSH 1.34 19.08 170 HOT 580PP 0.40 13 2
SAI TSH
-9.76 TSH TSH 0.18 19.08 170 HOT 58OPP 0.89 21 2
SAI TSH
-9.35 TSH TSH 0.59 19.08 170 HOT 580PP 1.85 27 2
SAI TSH
-9.18 TSH TSH 1.82 19.08 170 HOT 58OPP 78 66 0.12 120 2 SAI 02H
-1.87 02H 02H 0.13 278 HOT 580PP 78 74 0.62 25 P 1 SCI TSH
-0.09 TSH TSH 0.40 17.30 178 HOT 580PP 78 130 0.21 78 P 5 TWD 16 VSM
-1.19 VSM VSM 147 COLD 560P2 0.32 124 P 2 TWD 14 VSM
-0.95 TEH TEC 57 COLD 600UL 78 136 0.27 142 P 2 TWD 12 VC3
-0.76 STH TEC 63 COLD 600UL 0.19 91 P 5 TWD 15 VC3
-0.73 VC3 VC3 147 COLD 560P2 78 150 0.50 43 P 2 TWD 22 VH3
-0.74 TEC TEH 29 HOT 600UL 0.13 67 P 5 TWD 12 VH3
-0.78 VH3 VH3 149 COLD 560P2
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:30 Component: S/G 89 Page 19 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 78 160 0.28 137 P 3 TWD 14 DEC
-1.63 TEC TEH 33 HOT 600UL 0.13 99 P 5 TWD 11 DBC
-1.57 DBC DBC 150 COLD 560P2 79 43 0.27 89 P 2 TWD 13 VH3
-0.61 TEC TEH 34 HOT 600UL 0.24 90 P 5 TWD 16 VH3
-0.76 VH3 VH3 156 COLD 560P2 79 79 0.24 126 P 2 TWD 12 VH3
-0.91 TEC TEH 11 HOT 60OUL 0.17 66 P 5 TWD 14 VH3
-0.88 VH3 VH3 151 COLD 560P2 79____99____0.51_____169_____P__3___TWD_____21___DBH_____+1.03______TEC____TEN_____15____NOT_____________
79 99 0.51 169 P 3 TWD 21 DBH
+1.03 TEC TEH 15 HOT 600UL 80 98 0.52 149 P 3 TWD 21 DBH
+1.72 TEC TEH 15 HOT 600UL 80 106 0.10 89 P 5 TWD 8 VH3
+0.75 VH3 VH3 146 COLD 560P2 0.24 33 P 2 TWD 14 VH3
+0.89 TEH TEC 7
COLD 60OUL 80 114 0.36 57 P 2 TWD 16 VC3
+0.85 TEH TEC 5
COLD 600UL 80 152 0.52 49 P 2 TWD 24 VC3
+0.94 TEC TEH 28 HOT 600UL 0.44 29 P 2 TWD 22 VC3
-0.94 TEC TEH 28 HOT 60OUL 0.30 66 P 2 TWD 16 VSM
+1.00 TEC TEH 28 HOT 600UL 0.51 90 P 2 TWD 24 VSM
-0.94 TEC TEH 28 HOT 600UL 0.37 87 P 5 TWD 27 VC3
+0.89 VC3 VC3 150 COLD 560P2 0.22 88 P 5 TWD 18 VC3
-0.71 VC3 VC3 150 COLD 560P2 0.36 91 P 5 TWD 26 VSM
-0.86 VSM VSM 150 COLD 560P2 0.22 98 P 5 TWD 18 VSM
+0.81 VSM VSM 150 COLD 560P2 81 43 0.76 107 P 5 TWD 30 VSM
-0.84 VSM VSM 324 HOT 560P2 0.38 143 P 2 TWD 17 VC3
-0.46 TEC TEH 42 HOT 600UL 0.76 126 P 2 TWD 27 VSM
-0.91 TEC TEH 42 HOT 600UL 0.35 85 P 5 TWD 25 VC3
-0.81 VC3 VC3 171 COLD 560P2 0.18 92 P 5 TWD 14 VC3
+0.25 VC3 VC3 171 COLD 560P2 0.14 101 P 5 TWD 11 VC3
+0.96 VC3 VC3 171 COLD 560P2 81 55 0.28 47 P 2 TWD 12 VH3
-0.83 TEH TEC 48 COLD 600UL 81 61 0.13 107 2 MAI 01H
+3.20 01H 01H 0.00 292 HOT 580PP 81 75 0.27 33 P 2 TWD 15 VC3
+0.87 TEH TEC 53 COLD 600UL 0.14 112 P 5 TWD 12 VC3
+0.87 VC3 VC3 163 COLD 560P2 81 79 0.81 85 P 2 TWD 26 VH3
-0.89 TEH TEC 32 COLD 600UL 0.52 107 P 5 TWD 23 VH3
-0.79 VH3 VH3 322 HOT 560P2 81 105 0.60 77 P 2 TWD 22 VH3
+0.68 TEH TEC 21 COLD 600UL 0.27 137 P 2 TWD 12 VSM
+0.85 TEH TEC 21 COLD 600UL 0.29 115 P 5 TWD 15 VSM
+0.93 VSM VSM 166 COLD 560P2 0.27 83 P 5 TWD 19 VH3
+1.03 VH3 VH3 326 HOT 560P2 81 125 0.55 25 P 1 SCI TSH
-0.05 TSH TSH 0.71 17.25 294 HOT 580PP 81 131 1.24 15 P 1 SCI TSH
-16.67 TSH TSH
.48 18.10 262 HOT 580PP 81 135 0.40 120 P 2 TWD 18 VH3
+0.88 TEC TEH 41 HOT 60OUL 0.27 86 P 5 TWD 22 VH3
+0.88 VH3 VH3 323 HOT 560P2 0.18 96 P 5 TWD 16 VH3
-0.80 VH3 VH3 323 HOT 560P2 81 159 0.22 96 P 5 TWD 15 02H
-0.34 02H 02H 275 HOT 580PP 0.36 76 P 2 TWD 16 VH3
-0.82 TEC TEH 51 HOT 600UL 0.31 88 P 2 TWD 14 02H
-0.33 TEC TEH LAR 51 HOT 600UL 82 28 0.28 138 P 2 TWD 12 VH3
-0.71 TEC TEH 39 HOT 60OUL 0.29 101 P 5 TWD 14 VH3
-0.85 VH3 VH3 324 HOT 560P2 0.33 102 P 5 TWD 16 VH3
-0.15 VH3 VH3 324 HOT 560P2 82 50 0.13 127 P 5 TWD 10 08H
-0.43 08H 08H 240 HOT 580PP 82 68 0.46 104 P 5 TWD 21 VH3
+0.84 VH3 VH3 324 HOT 560P2 0.68 100 P 5 TWD 28 VH3
-0.84 VH3 VH3 324 HOT 560P2 0.76 98 P 2 TWD 27 VH3
-0.85 TEH TEC 51 COLD 60OUL 0.35 143 P 2 TWD 16 VH3
+0.83 TEH TEC 51 COLD 600UL 82 70 0.40 56 P 2 TWD 16 01H
+0.86 TEH TEC 52 COLD 600UL 82 76 0.20 26 P 1 SCI TSH
+0.00 TSH TSH 0.0 18.06 284 HOT 580PP
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc icodes and 0-100%twd.qry 03/07/04 14:17:30 Component:
S/G 89 Page 20 of 31 ROW LINE VOLTS DEG CHN IND %TW LOCATION 82 96 0.37 28 P 2 TWD 17 04H
-0.20 EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE TEH TEC 26 COLD 60OUL 82 104 0.35 85 P 2 TWD 15 02H
-1.09 TEH TEC 21 COLD 600UL 82 108 0.34 70 P 2 TWD 14 02H
-1.20 TEH TEC 19 COLD 60OUL 82 112 0.91 20 2
SAI TSH
-12.24 TSH TSH 1.33 300 HOT S8OPP 1.14 16 2
SAI TSH
-13.10 TSH TSH 1.19 300 HOT 58OPP 1.41 18 2
SAI TSH
-13.28 TSH TSH 1.63 300 HOT 580PP 1.98 19 2
SAI TSH
-13.65 TSH TSH 3.01 18.03 300 HOT 58OPP 82 148 0.73 126 P 2 TWD 27 VH3
-0.92 TEC TEH 50 HOT 60OUL 0.38 88 P 5 TWD 27 VH3
-0.93 VH3 VH3 323 HOT 560P2 83 95 0.20 150 P 1 SCI TSH
+0.07 TSH TSH 0.22 18.04 276 HOT 580PP 83 109 0.42 52 P 2 TWD 17 01H
+0.91 TEH TEC 19 COLD 600UL 0.37 44 P 2 TWD 15 02H
-1.20 TEH TEC 19 COLD 600UL 84 88 0.34 88 P 2 TWD 14 VH2
+0.78 TEH TEC 29 COLD 600UL 84 98 0.27 56 P 2 TWD 14 02H
-1.25 TEH TEC 26 COLD 60OUL 84 100 0.23 96 P 2 TWD 12 VH2
+0.81 TEH TEC 24 COLD 60OUL 84 110 0.58 55 P 2 TWD 23 VH2
-0.90 TEH TEC 18 COLD 600UL 84 124 0.47 56 P 2 TWD 21 VH2
+0.72 TEH TEC 14 COLD 60OUL 84 132 0.46 109 P 2 TWD 20 VC2
-0.64 TEC TEH 41 HOT 60OUL 85 71 0.44 40 P 2 TWD 17 02H
-1.19 TEH TEC 52 COLD 600UL 85 99 0.47 51 P 2 TWD 21 02H
-1.24 TEH TEC 26 COLD 600UL 85 113 1.61 17 2
SAI TSH
-11.79 TSH TSH 1.62 300 HOT 580PP 2.35 18 2
SAI TSH
-12.78 TSH TSH 3.23 17.92 300 HOT 580PP 85 145 0.26 150 P 2 TWD 15 VSM
+0.82 TEC TEH 47 HOT 60OUL 86 82 0.40 73 P 2 TWD 17 VH2
+0.80 STH TEC 63 COLD 600UL 86 130 0.35 88 P 2 TWD 17 VH2
-0.86 TEC TEH 41 HOT 600UL 87 43 0.38 63 P 2 TWD 17 VH2
+0.63 TEC TEH 42 HOT 60OUL 87 49 0.37 72 P 2 TWD 16 VH2
+0.82 TEH TEC 45 COLD 600UL 87 71 0.26 98 2
SAI 08H
-0.41 08H 08H
.30 249 HOT 580PP 88 38 0.43 120 P 2 TWD 19 VH2
-1.05 TEC TEH 42 HOT 600UL 88 40 0.31 50 P 2 TWD 15 VH2
-0.81 TEC TEH 42 HOT 600UL 88 44 0.48 139 P 2 TWD 21 VH2
-0.82 TEC TEH 43 HOT 600UL 88 68 0.37 92 P 2 TWD 15 VH2
-0.83 TEH TEC 52 COLD 600UL 0.37 63 P 2 TWD 15 01H
+0.94 TEH TEC 52 COLD 600UL 88 88 0.33 58 P 2 TWD 14 VH2
+0.91 TEH TEC 29 COLD 600UL 88 138 0.37 125 P 2 TWD 17 VH2
-0.83 TEC TEH 46 HOT 600UL 88 140 0.43 98 P 2 TWD 19 VH2
+1.02 TEC TEH 46 HOT 60OUL 88 152 0.44 137 P 2 TWD 19 VH2
-0.82 TEC TEH 51 HOT 600UL 89 85 0.36 55 P 2 TWD 15 VH2
-0.71 TEH TEC 31 COLD 600UL 0.28 135 P 1 SCI TSH
+0.08 TSH TSH 0.00 18.86 285 HOT 580PP 89 87 0.52 17 2
SAI TSH
-13.33 TSH TSH 0.98 18.89 285 HOT 580PP 89 111 3.22 29 2
SAI TSH
-12.99 TSH TSH 4.96 17.71 301 HOT 58OPP 89__133__0.30__82__P_2__TWO__15____2_-0.88__________TEC________T____R____41______HOT_____________________
89 133 0.30 82 P 2 TWD 15 VH2
-0.88 TEC TEH 41 HOT 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:30 Component: S/G 89 Page 21 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION 90 38 0.55 101 P 2 TWD 23 VH2
-0.93 EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE TEC TEE 43 HOT 600UL 90 40 0.50 95 P 2 TWD 22 VH2
-1.02 TEC TEE 43 HOT 600UL 90__52__0.51___89_P__2_TWO___20______-0.79_________TEE________TEC_______47______COLD_________6____0UL____
90 52 0.51 89 P 2 TWD 20 VH2
-0.79 TEE TEC 47 COLD 60OUL 90 58 0.37 119 P 2 TWD 16 VH2
-0.81 TEE TEC 47 COLD 600UL 90 106 0.25 96 P 2 TWD 11 VH2
+0.68 TER TEC 21 COLD 600UL 90 114 0.37 85 P 2 TWD 17 VH3
-0.59 TEE TEC 18 COLD 600UL 90 116 0.11 110 2 SAI 02H
+10.21 02H 02H 0.00 300 HOT 58OPP 0.38 129 P 2 TWD 16 VH2
-0.83 TEE TEC 17 COLD 60OUL 90 118 0.38 126 P 2 TWD 16 VH2
-0.81 TEH TEC 17 COLD 60OUL 90 140 0.29 73 P 2 TWD 16 VH2
-0.83 TEC TEE 47 HOT 60OUL 90 144 0.37 20 P 2 TWD 20 VSM
+0.88 TEC TEE 47 HOT 60OUL 90 156 0.35 69 P 2 TWD 15 VH2
-0.81 TEC TEE 50 HOT 60OUL 91 43 0.58 127 P 2 TWD 24 06C
-0.93 TEC TEH 42 HOT 60OUL 0.45 107 P 5 TWD 26 06C
-0.92 06C 06C 140 COLD 580PP 91 67 0.33 89 P 2 TWD 13 09H
-0.93 TEE TEC 52 COLD 600UL 91 119 0.35 106 P 2 TWD 15 VH2
-0.66 TER TEC 17 COLD 60OUL 91 145 0.26 78 P 2 TWD 13 VH2
-1.00 TEC TEE 46 HOT 600UL 91 151 0.30 34 P 2 TWD 14 VH2
-0.91 TEC TEE 50 HOT 600UL 92 60 0.46 142 P 2 TWD 19 09H
-1.23 TEE TEC 49 COLD 600UL 92 96 0.30 48 P 2 TWD 15 VC3
+0.75 TEE TEC 26 COLD 60OUL 93 31 0.09 107 2 SAI 06H
+4.15 06H 06H 0.00 286 HOT 580PP 0.10 99 2
SAI 06H
+5.78 06H 06H 0.00 286 HOT 580PP 93 33 0.55 130 P 2 TWD 23 VH2
+0.87 TEC TEE 38 HOT 600UL 94 26 0.45 85 P 2 TWD 18 VH2
+1.04 TEC TEE 39 HOT 600UL 94 50 0.18 94 P 5 TWD 12 05C
-0.15 05C 05C 136 COLD 580PP 0.24 114 P 2 TWD 11 05C
-0.14 TEE TEC 45 COLD 600UL 94 124 0.34 123 P 2 TWD 14 VH2
-0.93 TEH TEC 56 COLD 600UL 94 146 0.24 106 P 2 TWD 14 VH3
-0.88 TEC TEE 47 HOT 600UL 0.14 94 P 5 TWD 13 VH3
-0.81 VH3 VH3 323 HOT 560P2 94 154 0.28 30 P 2 TWD 13 VH2
-1.24 TEC TEE 50 HOT 600UL 95 29 0.52 152 P 2 TWD 22 VH2
+0.89 TEC TEE 38 HOT 600UL 95 35 0.57 79 P 2 TWD 23 VH2
+0.97 TEC TEH 42 HOT 600UL 95 77 2.11 25 2
SAI TSH
-9.20 TSH TSH 3.03 18.63 289 HOT 580PP 95 93 1.17 28 P 1 SCI TSH
-7.33 TSH TSH 1.81 18.41 280 HOT 58OPP 95 97 0.35 91 P 2 TWD 16 VH3
-0.81 TEH TEC 26 COLD 600UL 95 141 1.23 14 2
SAI TSH
-12.35 TSH TSH
.79 18.53 271 HOT 580PP 0.79 11 2
SAI TSH
-12.01 TSH TSH
.54 271 HOT 580PP 96 48 0.43 113 P 2 TWD 21 VH2
-0.86 TEE TEC 46 COLD 60OUL 96__52__0.39__114__p_2__TWO__17____2_-0.83_________TEE________TEC_______47______COLD_________600UL_______
96 52 0.39 114 P 2 TWD 17 VH2
-0.83 TEE TEC 47 COLD 600UL 96 74 0.39 129 P 2 TWD 19 VSM
-0.87 TEE TEC 53 COLD 600UL 96 98 0.28 105 P 2 TWD 14 07H
+1.25 TER TEC 26 COLD 600UL
Framatome ANP Inc.
03/07/04 14:17:30 Customer Name: San Onofre -
Unit 2 Component: S/G 89 Page 22 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 96 152 0.36 75 P 2 TWD 16 VH2
+0.86 TEC TEH 51 HOT 60OUL 97 37 0.41 103 P 2 TWD 18 VC3
+0.61 TEC TER 42 HOT 60OUL 0.30 81 P 5 TWD 21 VC3
+0.81 VC3 VC3 164 COLD 560P2 97 41 0.47 135 P 2 TWD 20 VH2
+0.91 TEC TEE 42 HOT 60OUL 97 107 1.01 18 2
SAI TSH
-8.96 TSH TSH 0.92 17.32 305 HOT 58OPP 97 123 0.31 113 P 2 TWD 13 VH2
-0.77 TEE TEC 17 COLD 60OUL 98 94 0.35 70 P 2 TWD 14 VH3
+0.81 TEH TEC 27 COLD 60OUL 98 136 0.27 65 P 2 TWD 13 VH2
-0.83 TEC TEE 46 HOT 60OUL 0.40 55 P 2 TWD 18 VH2
+0.76 TEC TEH 46 HOT 60OUL 98 148 0.42 135 P 2 TWD 18 VH2
+0.98 TEC TEE 50 HOT 60OUL 98 150 0.49 43 P 2 TWD 20 VH2
+0.81 TEC TEE 50 HOT 60OUL 100 36 0.42 150 P 2 TWD 19 06H
-0.53 TEC TEE 42 HOT 60OUL 0.25 99 2
SAI 06H
-0.45 06H 06H 0.37 286 HOT S80PP 0.13 100 2 SAI 06H
+1.55 06H 06H 0.20 286 HOT 580PP 0.08 87 2
SAI 06H
+2.18 06H 06H 0.00 286 HOT 58OPP 0.12 87 2
SAI 06H
+2.92 06H 06H 0.37 286 HOT 580PP 0.12 98 2
MAI 06H
+3.24 06H 06H 0.19 286 HOT 580PP 0.12 131 2 SAI 06H
+3.80 06H 06H 0.00 286 HOT 580PP 100 98 0.37 70 P 2 TWD 17 01H
+0.79 TEH TEC 26 COLD 600UL 100 140 0.58 113 P 2 TWD 24 VH2
+0.96 TEC TER 46 HOT 600UL 0.45 79 P 2 TWD 20 VH2
-0.92 TEC TER 46 HOT 600UL 101 37 0.54 84 P 2 TWD 22 03H
+0.84 TEC TEE 42 HOT 600UL 101 97 0.15 106 2 SAI TSH
+1.65 TSH TSH 0.0 17.87 276 HOT 580PP 101 143 0.33 121 P 3 TWD 17 DBH
+1.95 TEC TEE 47 HOT 600UL 0.41 100 P 2 TWD 21 VH2
-0.85 TEC TEE 47 HOT 600UL 0.19 92 P 5 TWD 17 DBH
+2.09 DBH DBH 323 HOT 560P2 101 147 0.39 96 P 2 TWD 17 VH2
+0.81 TEC TEE 50 HOT 600UL 0.35 106 P 2 TWD 16 VH2
-0.92 TEC TEH 50 HOT 600UL 101 151 0.45 115 P 2 TWD 20 VH2
+0.83 TEC TEN 50 HOT 600UL 102__56__0.32__104__p_2_TWO__14__V_2_-0.79_________TEE________TEC_______47______COLD________________UL___
102 56 0.32 104 P 2 TWD 14 VH2
-0.79 TEH TEC 47 COLD 600UL 102 58 0.31 123 P 2 TWD 14 VC3
-0.75 TER TEC 47 COLD 600UL 0.27 79 P 2 TWD 12 VC2
-0.79 TEE TEC 47 COLD 600UL 0.15 99 P 5 TWD 13 VC2
-0.81 VC2 VC2 163 COLD 560P2 0.18 76 P 5 TWD 14 VC3
-0.59 VC3 VC3 163 COLD 560P2 102 92 0.40 126 P 2 TWD 18 03H
+0.84 TEH TEC 26 COLD 600UL 102 120 0.31 121 P 2 TWD 13 VH2
-0.89 TEE TEC 17 COLD 600UL 102 122 0.45 94 P 2 TWD 19 VC2
-0.80 TER TEC 16 COLD 600UL 0.18 120 2 SAI VC2
-0.83 VC2 VC2 0.0 171 COLD 560P2 103 39 0.12 131 2 SAI 06H
+1.38 06H 06H 0.00 286 HOT 580PP 0.15 89 2
SAI 06H
+1.99 06H 06H 0.45 286 HOT 580PP 0.12 57 2
SAI 06H
+2.02 06H 06H 0.33 286 HOT 580PP 0.19 94 2
SAI 06H
+3.38 06H 06H 0.48 286 HOT 58OPP 0.11 140 2 SAI 06H
+4.40 06H 06H 0.00 286 HOT 580PP 0.12 73 2
SAI 06H
+17.83 06H 06H 0.00 286 HOT 58OPP 103 47 0.41 54 P 2 TWD 17 VH2
-0.86 TEH TEC 45 COLD 600UL 103 97 0.37 65 P 2 TWD 17 06H
+0.76 TEE TEC 26 COLD 600UL 103 137 0.37 75 P 2 TWD 17 VH3
-0.91 TEC TEH 46 HOT 60OUL 0.14 82 P 5 TWD 13 VH3
-0.91 VH3 VH3 323 HOT 560P2 104__94__0.38__117__P_2_TWO__18__V___-0.83_________TEE________TEC_______26______COLD_________E______UL___
104 94 0.38 117 P 2 TWD 18 VSM
-0.83 TER TEC 26 COLD 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:30 Component: S/G 89 Page 23 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodes and 0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION 104 122 0.32 118 P 2 TWD 14 VH2
-0.72 EXT EXT UTIL 1 UTIL 2 CAL # LEG TEE TEC 17 COLD PROBE 60OUL 105 87 0.38 40 P 2 TWD 16 VC2
+0.65 TEH TEC 31 COLD 600UL 105 91 0.45 93 P 2 TWD 20 01H
+0.95 TEE TEC 26 COLD 600UL 105 93 0.30 146 P 2 TWD 15 VSM
+0.78 TER TEC 26 COLD 60OUL 105 137 0.37 59 P 2 TWD 20 VH2
-0.84 TEC TEE 47 HOT 600UL 105 141 0.49 155 P 3 TWD 22 DBH
+1.75 TEC TEN 47 HOT 600UL 0.12 83 P 5 TWD 11 DBH
+2.02 DBH DBH 323 HOT 560P2 106 62 0.29 98 P 2 TWD 14 VC2
-0.65 TEE TEC 49 COLD 60OUL 106 86 0.20 22 P 3 TWD 9 DBH
-2.06 TEE TEC 31 COLD 600UL 106 88 0.51 45 P 2 TWD 19 01H
+0.86 TEE TEC 29 COLD 600UL 106 104 0.22 23 P 2 TWD 10 VC2
-0.75 TEE TEC 21 COLD 60OUL 0.12 84 2
SAI TSH
+1.91 TSH TSH 0.0 18.15 306 HOT 580PP 106 132 0.26 104 P 2 TWD 12 VH2
-0.95 TEC TEE 40 HOT 60OUL 106 136 0.31 128 P 2 TWD 15 VH2
-0.89 TEC TEE 46 HOT 600UL 106 146 0.25 174 P 3 TWD 13 DBH
+1.15 TEC TEE 47 HOT 60OUL 107 33 0.54 17 P 3 TWD 20 DBC
+2.06 TEC TEE 39 HOT 600UL 0.27 81 P 5 TWD 19 DBC
+2.06 DBC DBC 164 COLD 560P2 107 35 0.59 164 P 3 TWD 23 DBC
+1.61 TEC TEE 42 HOT 600UL 0.38 79 P 5 TWD 25 DBC
+1.61 DBC DBC 164 COLD 560P2 107 37 0.48 55 P 3 TWD 21 DBC
+1.70 TEC TEE 43 HOT 600UL 107 103 0.51 52 P 2 TWD 19 VH2
-0.92 TEE TEC 21 COLD 60OUL 0.26 88 P 5 TWD 19 VH2
-0.77 VH2 VH2 326 HOT 560P2 108 42 0.17 99 P 5 TWD 10 DBH
-2.20 DBH DBH 347 HOT 560P2 0.18 84 P 5 TWD 13 DBH
+1.85 DBH DBH 347 HOT 560P2 0.36 79 P 3 TWD 17 DBH
+1.81 TEC TEE 43 HOT 600UL 0.43 108 P 3 TWD 19 DBH
-2.10 TEC TEE 43 HOT 600UL 108 74 0.23 27 P 2 TWD 12 VH2
-0.77 TEE TEC 53 COLD 600UL 108 110 1.26 25 2
MAI TSH
-14.99 TSH TSH 1.85 18.03 300 HOT 58OPP 108 136 0.35 111 P 2 TWD 17 VH2
-0.85 TEC TEE 41 HOT 600UL 109 47 0.35 108 P 5 TWD 21 VSM
-1.00 VSM VSM 347 HOT 560P2 0.28 144 P 2 TWD 15 VSM
-0.95 TEE TEC 46 COLD 600UL 0.24 116 P 2 TWD 13 VC3
-0.85 TEE TEC 46 COLD 600UL 0.29 98 P 5 TWD 21 VC3
-0.81 VC3 VC3 163 COLD 560P2 109 55 0.30 81 P 2 TWD 13 VH2
-0.72 TEE TEC 48 COLD 600UL 110 34 0.20 103 P 5 TWD 12 VH2
+0.97 VH2 VH2 347 HOT 560P2 0.27 134 P 2 TWD 13 VH2
+0.87 TEC TEE 38 HOT 600UL 110 50 0.26 90 2
SAI 06H
+0.50 06H 06H 0.00 241 HOT 580PP 111 43 0.39 49 P 2 TWD 18 VH3
-1.02 TEC TEE 42 HOT 600UL 111 47 0.24 127 2 SAI 05H
+0.29 05H 05H 0.00 235 HOT 580PP 0.41 149 P 2 TWD 17 05H
+0.27 TEE TEC 45 COLD 600UL 111 87 0.38 75 P 2 TWD 17 VC2
+0.95 TEE TEC 30 COLD 600UL 0.15 99 P 5 TWD 13 VC2
+0.95 VC2 VC2 163 COLD 560P2 111 89 0.37 84 P 2 TWD 17 01H
+0.93 TEE TEC 26 COLD 600UL 111 99 0.17 102 P 5 TWD 12 09C
+0.60 09C 09C 136 COLD 580PP 0.44 81 P 2 TWD 20 09C
+0.55 TEE TEC 26 COLD 60OUL 111 137 0.42 87 P 2 TWD 19 VH2
-0.87 TEC TEE 46 HOT 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpcicodes and_0-100%twd.qry 03/07/04 14:17:30 Component: S/G 89 Page 24 of 31 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 0.35 67 P 2 TWD 16 VH2
+0.74 TEC TEH 46 HOT 60OUL 112 38 0.12 106 2 MAI 07H
-15.38 TO-21.03 07H 07H 0.00 287 HOT 580PP 112 72 0.35 24 P 2 TWD 15 VH3
+0.84 TEH TEC 51 COLD 600UL 112 120 2.52 25 2
SAI TSH
-15.78 TSH TSH 3.12 17.87 297 HOT 580PP 112 128 0.19 97 P 2 TWD 8 VH2
+0.15 TEH TEC 13 COLD 600UL 0.20 85 2
SAI VH2
+0.31 VH2 VH2 0.26 326 HOT 560P2 112 144 0.42 51 P 3 TWD 19 DBC
+2.19 TEC TEH 46 HOT 60OUL 0.30 62 P 5 TWD 15 DBC
+2.25 DEC DBC 166 COLD 560P2 113 53 0.23 74 P 2 TWD 11 VC2
-0.55 TEH TEC 47 COLD 60OUL 113 67 0.36 121 P 2 TWD 15 09H
-1.08 TEH TEC 52 COLD 60OUL 113 77 0.32 87 P 2 TWD 12 VC3
+0.92 TEH TEC 32 COLD 60OUL 0.16 80 P 5 TWD 13 VC3
+0.92 VC3 VC3 163 COLD 560P2 113 105 0.28 26 P 2 TWD 14 VH2
+0.88 TEH TEC 20 COLD 600UL 0.33 73 P 2 TWD 16 VH3
+0.92 TEH TEC 20 COLD 600UL 0.14 82 P 5 TWD 11 VH3
+1.11 VH3 VH3 326 HOT 560P2 0.22 89 P 5 TWD 16 VH2
+1.02 VH2 VH2 326 HOT 560P2 113 125 0.18 92 P 5 TWD 14 05H
-0.57 05H 05H 295 HOT 580PP 113 131 0.31 109 P 3 TWD 16 DBH
+1.81 TEC TEH 41 HOT 600UL 114 34 0.30 8
2 SAI TSH
-5.00 TSH TSH 0.77 19.48 286 HOT 58OPP 114 36 0.21 129 P 3 TWD 10 DBC
-1.77 TEC TEH 43 HOT 600UL 0.17 84 P 5 TWD 13 DEC
-1.77 DBC DBC 164 COLD 560P2 114 40 0.45 104 P 5 TWD 26 DBH
+1.81 DEH DBH 347 HOT 560P2 0.50 99 P 3 TWD 20 DBH
+1.63 TEC TEH 42 HOT 600UL 114 48 0.44 45 P 2 TWD 18 03H
+0.93 TEH TEC 45 COLD 600UL 114 56 0.19 82 2
SAI 06H
+0.38 06H 06H 0.00 241 HOT 58OPP 114 62 0.28 115 P 5 TWD 17 DEH
-1.81 DEH DBH 347 HOT 560P2 0.30 129 P 3 TWD 13 DBH
-1.88 TEH TEC 49 COLD 600UL 114 88 0.38 25 P 2 TWD 15 01H
+0.77 TEH TEC 29 COLD 600UL 114 136 0.30 89 P 5 TWD 19 VC3
+0.84 VC3 VC3 166 COLD 560P2 0.28 147 P 2 TWD 13 VC3
+0.85 TEC TEH 40 HOT 600UL 115 39 0.21 125 P 5 TWD 13 VH1 0.50 140 P 2 TWD 21 VH1
+0.58
+0.94 115 115 116 116 116
- 123 139 58 60 98 D
0.27 0.24 0.61 0.20 0.29 41 110 127 145 97 2
2 o -
2 2
2 TWD TWD TWO TWD TWD 13 12 22 10 14 VSM VHl VHl VH1 VC2 VH1 VSM D
u+0.80
+0.96
-0. 98
-1.01
-0.83 VH1 VH1 TEC TEH TEH TEC TEC TEH TEE TEC__
TEH TEC TEH TEC TEH TEC D-- --
347 HOT 42 14 46 48 49 26 HOT COLD HOT COLD COLD COLD 560P2 600UL 600UL 60OUL 600UL 600UL 60OUL 116 106 0.35 16 2
SAI TSH
-5.02 TSH TSH 0.00 18.10 304 HOT 58OPP 116 122 0.57 27 P 2 TWD 21 VH1
-0.98 TEH TEC 17 COLD 600UL 116 128 0.36 70 P 2 TWD 14 VH2
-1.19 TEH TEC 13 COLD 60OUL 0.34 33 P 2 TWD 15 02H
+0.86 TEH TEC 13 COLD 600UL 116 130 0.22 159 P 3 TWD 10 DBH
-1.40 TEC TEH 40 HOT 600UL 116 136 0.28 67 P 2 TWD 14 VHl
-1.09 TEC TEH 41 HOT 600UL 0.40 124 P 2 TWD 18 VH2
-1.11 TEC TEH 41 HOT 60OUL 117 73 0.36 61 P 2 TWD 14 04H
+0.90 TEH TEC 52 COLD 600UL
Framatome ANP Inc.
03/07/04 14:17:30 Customer Name: San Onofre -
Unit 2 Component: SIG 89 Page 25 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
2--====-======-===-===-===-===-========================-=======-=======-=======-=====-========-=====
117 75 0.55 63 P 2 TWD 24 VHI
-0.02 TEH TEC 53 COLD 600UL 117 129 0.22 77 P 5 TWD 17 05H
-0.20 05H 05H 295 HOT 580PP 0.39 133 P 2 TWD 17 05H
-0.14 TEH TEC 12 COLD 600UL of 31 118 56 0.39 55 P 2 TWD 17 VHl
+0.79 TEH TEC 47 COLD 600UL 118 58 0.43 140 P 2 TWD 18 VH1
-0.85 TEH TEC 47 COLD 600UL 118 70 0.52 50 P 2 TWD 21 VH1
-0.64 TEH TEC 51 COLD 600UL 118 72 0.25 107 2 SAI 04H
-7.40 TO-14.94 04H 04H
.51 248 HOT 580PP 118 74.
0.47 60 P 2 TWD 21 VHl
-0.77 TEH TEC 53 COLD 600UL 118 106 0.46 152 P 2 TWD 21 VH1
-0.75 TEH TEC 20 COLD 60OUL 118 126 0.37 130 P 2 TWD 17 VH1
+0.80 TEH TEC 14 COLD 600UL 0.39 138 P 2 TWD 18 VHI
-0.78 TEH TEC 14 COLD 600UL 118 128 0.17 95 P 5 TWD 11 05H
+0.55 05H 05H 294 HOT 580PP 0.31 82 P 2 TWD 14 05H
+0.65 TEH TEC 12 COLD 600UL 118 132 0.31 140 P 2 TWD 14 VH1
-1.01 TEC TEH 40 HOT 60OUL 118 138 0.11 176 P 3 TWD 6 DBH
+1.49 TEC TEH 47 HOT 600UL 119 69 0.57 118 P 2 TWD 21 09H
-1.02 TEH TEC 52 COLD 600UL 119 79 0.68 115 P 2 TWD 24 VH3
+0.85 TEH TEC 32 COLD 600UL 0.54 112 P 5 TWD 24 VH3
+0.95 VH3 VH3 322 HOT 560P2 119 119 0.45 41 P 2 TWD 18 10H
-1.14 TEH TEC LOCOK 17 COLD 600UL 0.25 83 P 5 TWD 18 10H
-1.17 10H DEH 326 HOT 560P2 119 121 0.49 120 P 2 TWD 19 10H
-1.09 TEH TEC LOCOK 17 COLD 60OUL 0.32 92 P 5 TWD 22 10H
-1.37 10H DBH 326 HOT 560P2 120 38 0.35 37 P 2 TWD 17 10H
+1.25 TEC TEH 42 HOT 60OUL 120 42 0.30 128 P 2 TWD 15 VHl
-0.81 TEC TEH 42 HOT 600UL 120 50 0.19 128 2 SAI 07H
-0.37 07H 07H 0.66 240 HOT 580PP 120 54 0.60 116 P 2 TWD 23 VH1
-0.83 TEH TEC 47 COLD 600UL 120 62 0.41 127 P 2 TWD 16 VH1
-0.90 TEH TEC 50 COLD 600UL 120 68 0.44 70 P 2 TWD 17 VH1
-0.96 TEH TEC 52 COLD 600UL 0.14 110 P 5 TWD 7 VHI
-0.80 VHI VHI 347 HOT 560P2 120 70 0.35 124 P 2 TWD 14 VHi
-0.89 TEH TEC 52 COLD 60OUL 120 72 0.41 101 P 5 TWD 21 10H
-1.03 10H 10H 249 HOT 580PP 0.45 146 P 2 TWD 19 VH1
-0.72 TEH TEC 51 COLD 60OUL 0.54 128 P 2 TWD 21 10H
-1.09 TEH TEC 51 COLD 600UL 120 74 0.49 111 P 2 TWD 22 VH1
-0.64 TEH TEC 53 COLD 600UL 0.65 105 P 2 TWD 26 10H
-1.54 TEH TEC LOCOK 53 COLD 600UL 120 88 0.35 77 P 2 TWD 17 VH1
-0.75 TEH TEC 28 COLD 600UL 120 98 0.42 30 P 2 TWD 19 VHl
-0.79 TEH TEC 26 COLD 600UL 121 39 0.28 41 P 2 TWD 14 10H
-1.83 TEC TEH LOCOK 42 HOT 60OUL 121 45 0.60 144 P 2 TWD 24 VC2
-0.57 TEC TEH 44 HOT 600UL 121 57 0.23 85 P 5 TWD 16 10C
-1.57 i0C 10C LOCOK 136 COLD 58OPP 0.45 106 P 2 TWD 17 10C
-1.32 TEH TEC LOCOK 48 COLD 60OUL 121 67 0.49 100 P 2 TWD 19 09H
-1.00 TEH TEC 52 COLD 600UL 121 83 0.57 116 P 2 TWD 21 VC3
-0.90 TEH TEC 31 COLD 600UL 0.25 83 P 5 TWD 19 VC3
-0.91 VC3 VC3 163 COLD 560P2
Framatome ANP Inc.
03/07/04 14:17:31 Customer Name: San Onofre -
Unit 2 Component: S/G 89 Page 26 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-========================-
-=======-=======-=====-========-===
121 109 0.62 79 P 2 TWD 25 10H
-1.51 TEH TEC LAR LOCOK 18 COLD 600UL 0.17 128 P 5 TWD 13 10H
+1.00 10H 10H 301 HOT 580PP 0.22 90 P 5 TWD 17 10H
-1.54 10H 10H 301 HOT 580PP 122 52 0.48 116 P 2 TWD 19 VHI
-0.85 TEH TEC 47 COLD 60OUL 122 88 0.28 64 P 2 TWD 12 VH1
+0.77 TEH TEC 29 COLD 60OUL 122 118 0.43 120 P 2 TWD 17 VHi
-0.94 TEH TEC 17 COLD 600UL 0.35 68 P 2 TWD 15 VH2
+0.77 TEH TEC 17 COLD 60OUL 122 126 0.45 107 P 2 TWD 20 VH3
+1.21 TEH TEC 14 COLD 60OUL 123 61 0.43 28 P 2 TWD 19 03H
-0.77 TEH TEC 49 COLD 60OUL 123 117 0.57 82 P 2 TWD 21 03H
+0.82 TEH TEC 17 COLD 60OUL 0.27 145 P 3 TWD 12 DBH
-1.63 TEH TEC 17 COLD 60OUL 0.22 86 P 5 TWD 16 DBH
-1.63 DBH DBH 326 HOT 560P2 123 121 0.30 85 P 2 TWD 13 VH1
-0.85 TEH TEC 17 COLD 60OUL 124 42 0.25 102 P 2 TWD 12 VHi
-1.04 TEC TEH 43 HOT 60OUL 124 54 0.55 102 P 2 TWD 21 VH1
-0.81 TEH TEC 47 COLD 600UL 124 56 0.66 116 P 2 TWD 23 VHI
-0.83 TEH TEC 48 COLD 600UL 124 68 0.40 130 P 2 TWD 16 VHl
-0.96 TEH TEC 52 COLD 600UL 124 98 0.51 13 P 3 TWD 20 DBH
+2.14 TEH TEC 26 COLD 60OUL 0.24 107 P 5 TWD 12 DBH
+1.59 DBH DBH 322 HOT 560P2 125 49 0.33 94 P 2 TWD 17 03H
-0.82 TEH TEC 46 COLD 60OUL 125 53 0.37 119 P 2 TWD 16 VHI
-0.85 TEH TEC 47 COLD 600UL 0.34 112 P 5 TWD 18 VHl
-0.85 VHI VHi 327 HOT 560P2 125 55 0.30 116 P 3 TWD 12 DBH
+1.85 TEH TEC 48 COLD 60OUL 0.65 93 P 5 TWD 28 DBH
+2.00 DBH DBH 327 HOT 560P2 125 77 0.27 52 P 2 TWD 12 VHi
-0.83 TEH TEC 33 COLD 60OUL 0.33 93 P 2 TWD 14 VHi
+0.79 TEH TEC 33 COLD 60OUL 0.38 111 P 5 TWD 18 VH1
+0.68 VHl VHI 322 HOT 560P2 125 97 0.25 80 P 2 TWD 13 VH3
+0.79 TEH TEC 26 COLD 60OUL 125 lll 0.29 141 P 3 TWD 13 DBH
+1.84 TEH TEC 19 COLD 600UL 0.29 92 P 5 TWD 20 DEH
+1.84 DBH DEH 326 HOT 560P2 125 119 0.30 74 P 3 TWD 12 DBH
+1.75 TEH TEC 16 COLD 600UL 0.31 95 P 5 TWD 21 DBH
+1.75 DBH DBH 326 HOT 560P2 125 121 0.41 142 P 2 TWD 18 VHi
-0.82 TEH TEC 16 COLD 600UL 126 48 0.66 115 P 2 TWD 24 VHI
-1.23 TEH TEC 45 COLD 60OUL 126 50 0.36 122 P 2 TWD 16 VH1
-0.98 TEH TEC 45 COLD 60OUL 126 52 0.33 123 P 2 TWD 15 VHl
-1.05 TEH TEC 47 COLD 600UL 126 56 0.57 114 P 2 TWD 22 VHI
-1.01 TEH TEC 47 COLD 600UL 126 102 0.31 126 P 3 TWD 14 DBH
-1.58 TEH TEC 20 COLD 600UL 0.29 83 P 5 TWD 20 DBH
-1.58 DBH DBH 326 HOT 560P2 126 108 0.20 151 P 3 TWD 10 DBH
-1.48 TEH TEC 21 COLD 60OUL 0.24 90 P 5 TWD 17 DBH
-1.48 DBH DBH 326 HOT 560P2 126 112 0.28 134 2 SAI 07H
+0.47 07H 07H 0.00 301 HOT 580PP 126 118 0.36 34 P 2 TWD 15 VH2
-0.19 TEH TEC 17 COLD 60OUL 0.34 30 P 2 TWD 14 06C
+1.20 TEH TEC 17 COLD 600UL 126__120_0.39__113__p_2_TWO__16_V____-1.07_________TEE________TEC_______16______COLD_________600UL_______
126 120 0.39 113 P 2 TWD 16 VHl
-1.07 TEH TEC 16 COLD 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:31 Component: S/G 89 Page 27 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 126 122 0.47 65 P 2 TWD 19 VHl
-1.12 TEN TEC 16 COLD 600UL 126__124__0.55__116_p_2__TWO_23___N1_-1.13_________TEN________T____C____14______COLD___________00UL______
126 124 0.55 116 P 2 TWD 23 VH1
-1.13 TEN TEC 14 COLD 60OUL 126 126 0.42 116 P 2 TWD 19 VH1
-1.20 TER TEC 14 COLD 600UL 127 89 0.39 45 P 2 TWD 18 VH1
-0.79 TEN TEC 26 COLD 600UL 127 115 0.19 115 2 MAI 07H
-30.70 TO-10.30 07H 07H 0.22 300 HOT 580PP 127 123 0.34 123 P 2 TWD 16 09C
-1.17 TER TEC 14 COLD 600UL 128 56 0.28 166 P 3 TWD 12 DBH
+2.03 TEN TEC 70 COLD 600UL 0.41 150 P 2 TWD 19 VH1
-0.84 TEN TEC 70 COLD 600UL 0.57 92 P 5 TWD 25 DBH
+1.59 DBH DBH 327 HOT 560P2 128 70 0.38 115 P 2 TWD 15 VHI
-0.88 TER TEC 52 COLD 60OUL 128 72 0.24 105 P 5 TWD 14 10H
-1.00 10H 10H 249 HOT 580PP 0.32 95 P 5 TWD 17 10H
+0.88 iOH 10H 249 HOT 580PP 0.43 146 P 2 TWD 18 10H
+0.95 TEN TEC 51 COLD 600UL 0.50 136 P 2 TWD 20 10H
-1.15 TEN TEC 51 COLD 600UL 128 116 0.34 117 P 2 TWD 16 VNI
-0.63 TEN TEC 18 COLD 600UL 0.42 149 P 2 TWD 19 VH1
+0.70 TEN TEC 18 COLD 600UL 129 47 0.26 98 P 5 TWD 17 10H
+0.76 10H 10H 292 HOT 58OPP 0.40 144 P 2 TWD 17 10H
+0.77 TEN TEC 45 COLD 600UL 129 49 0.45 76 P 2 TWD 21 VH1
-0.80 TEN TEC 46 COLD 60OUL 0.31 89 P 2 TWD 16 VH1
+0.84 TER TEC 46 COLD 600UL 0.29 101 P 2 TWD 15 VC1
+0.84 TEN TEC 46 COLD 600UL 0.35 92 P 5 TWD 17 VH1
+0.92 VH1 VHI 327 HOT 560P2 0.42 113 P 5 TWD 20 VH1
-0.95 VH1 VH1 327 HOT 560P2 129 73 0.20 31 P 3 TWD 9 DBH
+1.91 TEN TEC 53 COLD 600UL 0.32 85 P 5 TWD 17 DBH
+1.91 DBH DBH 327 HOT 560P2 129 89 0.34 99 P 2 TWD 14 VH2
+0.86 TEN TEC 27 COLD 600UL 0.35 121 P 5 TWD 17 VH2
+0.92 VH2 VH2 322 HOT 560P2 0.29 121 P 5 TWD 15 VH2
-0.79 VH2 VH2 322 HOT 560P2 129 109 0.43 153 P 2 TWD 19 10H
-1.02 TEN TEC 18 COLD 600UL 0.29 104 P 5 TWD 21 10H
-1.02 10H 10H 301 HOT 580PP 130 48 0.35 103 P 5 TWD 21 02C
-0.15 02C 02C 136 COLD 580PP 0.41 65 P 2 TWD 17 02C
-0.17 TEN TEC 45 COLD 600UL 130 52 0.50 131 P 2 TWD 20 VH1
-0.84 TEN TEC 47 COLD 600UL 130 54 0.64 78 P 2 TWD 24 VHI
-0.81 TEN TEC 47 COLD 600UL 130 56 0.39 150 P 2 TWD 17 VHI
-0.95 TEH TEC 47 COLD 600UL 130 60 0.42 93 P 2 TWD 18 VH1
-0.83 TEN TEC 49 COLD 600UL 130 64 0.48 117 P 2 TWD 20 VH1
-0.96 TEN TEC 49 COLD 600UL 130 74 0.37 60 P 2 TWD 18 10H
+0.93 TEN TEC 53 COLD 600UL 0.21 91 P 5 TWD 13 10H
+0.87 10H 10H 253 HOT 580PP 130 78 0.34 114 P 5 TWD 22 10H
-1.05 10H 10H 289 HOT 58OPP 130 94 0.37 136 P 2 TWD 17 VH1
-0.59 TEN TEC 26 COLD 600UL 0.42 117 P 2 TWD 19 VH1
+0.59 TEN TEC 26 COLD 60OUL 130 110 0.35 81 P 2 TWD 16 VH1
-0.80 TEN TEC 18 COLD 600UL 131 79 0.28 103 2 SAI 07H
-0.61 07H 07H
.41 296 HOT 580PP 132 56 0.50 69 P 2 TWD 19 VH1
-0.88 TEN TEC 57 COLD 600UL 132 106 0.64 112 P 2 TWD 23 10H
-1.16 TEN TEC 23 COLD 600UL 0.24 128 P 5 TWD 19 10H
-1.06 10H 10H 302 HOT 58OPP 132 116 0.44 149 P 2 TWD 17 VH1
-0.80 TEN TEC 23 COLD 600UL
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:31 Component: S/G 89 Page 28 of 31
- MAI, MCI,
- MMI, MVI,
- SAI, SCI,
- SVI, 0-100%
QUERY: rpc_icodesand_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 132 122 0.48 91 P 2 TWD 19 VH1
-0.69 TEH TEC 23 COLD 600UL 133 55 0.24 63 P 2 TWD 10 02H
+0.23 TEH TEC 57 COLD 60OUL 0.15 75 P 5 TWD 11 02H
+0.30 02H 02H 293 HOT 580PP 133 81 0.20 100 P 5 TWD 22 VH1
+0.93 VH1 VH1 313 HOT 560P2 0.45 119 P 2 TWD 17 VH1
+1.00 TEH TEC 25 COLD 60OUL 133 119 0.53 82 P 2 TWD 22 VH1
+0.84 TEH TEC 22 COLD 600UL 0.30 93 P 5 TWD 15 VH1
+0.84 VH1 VH1 322 HOT 560P2 133 125 0.31 61 P 2 TWD 15 01C
+0.82 TEN TEC 22 COLD 600UL 0.18 112 P 5 TWD 13 01C
+0.94 01C 01C 136 COLD 580PP 134__52__0.26_113__p_2__TWO__1_______-0.74_________TEN________TEC_______58______COLD_________6_________L_
134 52 0.26 113 P 2 TWD 11 VHI
-0.74 TEH TEC 58 COLD 600UL 134 58 0.40 84 P 2 TWD 16 VH1
-0.84 TEH TEC 53 COLD 600UL 134 64 0.32 94 P 2 TWD 13 VH3
-0.92 TEH TEC 58 COLD 600UL 0.35 134 P 2 TWD 14 VC3
-0.84 TEH TEC 58 COLD 600UL 0.13 84 P 5 TWD 15 VH3
-0.90 VH3 VH3 313 HOT 560P2 0.35 117 P 5 TWD 16 VC3
-0.84 VC3 VC3 165 COLD 560P2 134 66 0.48 95 P 2 TWD 18 VHI
-0.78 TEH TEC 58 COLD 60OUL 134 76 0.33 55 P 2 TWD 14 VH1
-0.77 TEH TEC 25 COLD 600UL 134 80 0.15 82 P 5 TWD 18 DBH
+1.90 DBH DBH 313 HOT 560P2 0.50 7
P 3 TWD 20 DBH
+1.95 TEH TEC LAR 25 COLD 600UL 134 88 0.38 59 P 2 TWD 15 VH1
+0.79 TEH TEC 25 COLD 600UL 134 92 0.22 126 P 2 TWD 9 VH1
-0.84 TEH TEC 25 COLD 600UL 134 116 0.49 155 P 2 TWD 21 VH1
-0.75 TEH TEC 22 COLD 600UL 134 124 0.19 130 P 2 TWD 9 VC3
+0.62 01C TEH 140 HOT 60OUL 0.31 113 P 5 TWD 15 VC3
+0.74 VC3 VC3 165 COLD 560P2 135 71 0.22 117 P 3 TWD 11 DBH
-1.84 TEH TEC 58 COLD 600UL 0.23 87 P 5 TWD 24 DBH
-1.97 DBH DBH 313 HOT 560P2 135 101 0.22 118 2 SAI 07H
-0.47 07H 07H 0.49 299 HOT 58OPP 0.41 137 P 2 TWD 19 07H
-0.38 TEH TEC 22 COLD 600UL 136 68 0.42 41 P 2 TWD 17 VH1
-0.91 TEH TEC 57 COLD 600UL 0.18 94 P 5 TWD 20 VH1
-0.84 VH1 VH1 313 HOT 560P2 136 76 0.39 12 P 3 TWD 16 DBH
+2.14 TEH TEC 24 COLD 600UL 0.30 83 P 5 TWD 16 DBH
+2.00 DBH DBH 313 HOT 560P2 136 78 0.19 89 P 5 TWD 21 DBH
+1.76 DBH DBH 313 HOT 560P2 0.28 116 P 3 TWD 13 DBH
+1.81 TEH TEC 25 COLD 600UL 0.31 39 P 2 TWD 14 VH1
+0.81 TEH TEC 25 COLD 60OUL 136 88 0.24 92 P 2 TWD 12 06H
+0.72 TEH TEC 24 COLD 600UL 0.15 122 2 SAI 06H
+0.48 06H 06H 299 HOT 580PP 136 90 0.28 69 P 2 TWD 12 VHI
+0.79 TEH TEC 25 COLD 60OUL 136 110 0.22 35 P 2 TWD 10 VH1
-1.01 TEH TEC 23 COLD 600UL 137 69 0.30 47 P 2 TWD 13 VH1
+0.62 TEH TEC 57 COLD 600UL 0.40 95 P 5 TWD 20 VH1
+0.72 VH1 VH1 313 HOT 560P2 137 71 0.34 88 P 3 TWD 14 DBH
-1.73 TEH TEC 57 COLD 600UL 0.25 102 P 5 TWD 26 DBH
-1.71 DBH DBH 313 HOT 560P2 137 117 0.53 107 P 3 TWD 20 DBH
+1.55 TEH TEC 22 COLD 600UL 0.42 114 P 2 TWD 19 VH1
-0.88 TEH TEC 22 COLD 600UL 0.62 108 P 5 TWD 26 DBE
+1.67 DBH DBH ATC 322 HOT 560P2 0.28 108 P 5 TWD 14 VH1
-0.88 VH1 VH1 322 HOT 560P2 138 58 0.41 34 P 3 TWD 17 DBH
+1.82 TEH TEC 58 COLD 60OUL 0.15 63 P 5 TWD 18 DBH
+2.15 DBH DBH 313 HOT 560P2
Framatome ANP Inc.
03/07/04 14:17:31 Customer Name: San Onofre -
Unit 2 Component: S/G 89 Page 29 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE 138 64 0.34 126 P 2 TWD 14 10H
+0.80 TEH TEC 58 COLD 600UL 0.15 102 P 5 TWD 11 10H
+0.68 10H 10H 293 HOT 580PP 138 68 0.26 63 P 2 TWD 11 VH2
-0.84 TEH TEC 58 COLD 60OUL 0.31 28 P 2 TWD 13 VH2
+0.86 TEH TEC 58 COLD 600UL 138 76 0.66 93 P 5 TWD 29 DBH
+2.00 DBH VHI 313 HOT 560P2 0.77 14 P 3 TWD 27 DBH
+2.00 TEH TEC LAR 25 COLD 600UL 138 80 0.22 60 P 2 TWD 11 VHI
-0.88 TEH TEC 24 COLD 60OUL 0.13 79 P 5 TWD 15 VHI
-0.66 VHI VH1 313 HOT 560P2 138 86 0.20 101 2 SAI 06H
-0.24 06H 06H 0.00 299 HOT 580PP 138 92 0.51 36 P 2 TWD 20 07C
+1.25 TEH TEC 25 COLD 600UL 138 102 0.42 115 P 2 TWO 19 VH1i
-0.63 TEE TEC 22 COLD 6000L 138 104 0.55 150 P 2 TWD 23 VH1
-0.65 TEH TEC 22 COLD 600UL 138 110 0.31 11 2
SAI TSH
-4.26 TSH TSH 0.0 18.03 302 HOT 580PP 139 61 0.22 112 P 5 TWD 15 09C
-0.99 09C 09C 136 COLD 58OPP 0.26 121 P 2 TWD 11 09C
-1.06 TEH TEC 58 COLD 600UL 139 103 0.56 106 P 2 TWD 21 VH2
+0.88 TEH TEC 23 COLD 600UL 0.50 105 P 5 TWD 23 VH2
+0.88 VH2 VH2 322 HOT 560P2 139 115 0.31 144 P 3 TWD 13 DBH
+1.32 TEH TEC 22 COLD 600UL 0.41 106 P 5 TWD 26 DBH
+0.29 TO+1.93 DBH DBH 322 HOT 560P2 140 76 0.38 78 P 2 TWD 18 VH1
-0.81 TEH TEC 24 COLD 600UL 140 90 0.34 53 P 2 TWD 14 VH1
-0.83 TEH TEC 25 COLD 60OUL 140 96 0.46 123 P 2 TWD 20 VH1
-0.98 TEH TEC 22 COLD 600UL 140 100 0.24 88 P 2 TWD 10 VC1
+0.91 TEH TEC 23 COLD 600UL 140 112 0.35 89 P 5 TWD 22 DBC
+1.80 DBC DBC 165 COLD 560P2 0.33 134 P 3 TWD 13 DBC
+1.69 TEH TEC 22 COLD 600UL 141 67 0.33 92 P 2 TWD 13 09C
-1.08 TEH TEC 58 COLD 600UL 0.24 105 P 5 TWD 16 09C
-1.01 09C 09C 136 COLD 580PP 141 77 0.27 129 P 2 TWD 12 VH1
+0.83 TEH TEC 25 COLD 600UL 141 89 0.37 90 P 2 TWD 15 VH1
-0.66 TEH TEC 25 COLD 600UL 0.26 95 P 5 TWD 13 VH1
-0.46 VH1 VH1 317 HOT 560P2 141 103 0.20 106 P 5 TWD 14 VH3
-1.03 VH3 VH3 322 HOT 560P2 0.33 98 P 2 TWD 16 VH3
-0.85 TEH TEC 22 COLD 600UL 141 109 0.49 76 P 2 TWD 19 VH3
-0.02 TEH TEC 23 COLD 600UL 0.18 101 P 5 TWD 13 VH3
-0.02 VH3 VH3 322 HOT 560P2 142 72 0.40 98 P 3 TWD 17 DBC
+1.20 TEH TEC 58 COLD 600UL 0.64 106 P 5 TWD 28 DBC
+1.74 DBC DBC 165 COLD 560P2 142 86 1.09 15 P 1 SCI TSH
-0.88 TSH TSH 1.76 18.60 299 HOT 580PP 0.31 99 P 2 TWD 13 VH1
-0.85 TEH TEC 25 COLD 600UL 142 88 0.30 62 P 2 TWD 12 VH1
-0.81 TEH TEC 25 COLD 600UL 142 92 0.47 121 P 2 TWD 18 VH1
-0.88 TEH TEC 25 COLD 600UL 0.35 114 P 5 TWD 17 VH1
-0.78 VH1 VH1 317 HOT 560P2 143 71 0.24 117 P 2 TWD 10 VH2
-0.92 TEH TEC 58 COLD 600UL 0.54 94 P 2 TWD 20 VH1
-0.84 TEH TEC 58 COLD 60OUL 0.50 93 P 2 TWD 19 VHI
+0.64 TEH TEC 58 COLD 600UL 0.61 167 P 3 TWD 23 DBE
+1.82 TEH TEC 58 COLD 60OUL 0.45 78 P 5 TWD 36 DBH
+1.28 DBH VH2 313 HOT 560P2 0.16 83 P 5 TWD 18 VH1
+0.71 DBH VH2 313 HOT 560P2 0.24 87 P 5 TWD 25 VH1
-0.71 DBH VH2 313 HOT 560P2
- 0. 21 91 P 5 TWD 12 VH2
-O. 90 DBH VH2 313 HOT 560P2
Framatome ANP Inc.
Customer Name: San Onofre -
Unit 2 03/07/04 14:17:31 Component: S/G 89 Page 30 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-========================-
-=======-=======-=====-========-===
143 73 0.42 103 P 5 TWD 20 VC2
-0.87 VC2 VC2 166 COLD 560P2 0.37 99 P 5 TWD 23 VC1
-0.89 VC1 VC1 166 COLD 560P2 0.86 99 P 5 TWD 35 DBC
-1.49 DBC DBC 166 COLD 560P2 0.34 103 P 5 TWD 17 DBC
+1.76 DBC DBC 166 COLD 560P2 0.39 109 P 2 TWD 15 VH1
+0.84 TEH TEC 58 COLD 600UL 0.46 87 P 2 TWD 18 VC2
-0.88 TEH TEC 58 COLD 600UL 0.61 121 P 2 TWD 22 VC1
-0.84 TEH TEC 58 COLD 60OUL 0.45 120 P 3 TWD 19 DBC
-1.42 TEH TEC 58 COLD 600UL 0.24 76 P 3 TWD 11 DBC
+1.88 TEH TEC 58 COLD 60OUL 0.11 95 P 5 TWD 14 VH1
+0.16 VH1 VH1 313 HOT 560P2 143 81 0.30 110 P 5 TWD 15 VC1
-0.93 VC1 VC1 166 COLD 560P2 0.26 33 P 2 TWD 13 VC1
-0.81 TEH TEC 24 COLD 600UL 143 87 0.31 91 P 2 TWD 15 10C
+0.86 TEH TEC 24 COLD 600UL 0.55 81 P 3 TWD 21 DBC
+1.77 TEH TEC 24 COLD 600UL 0.17 91 P 5 TWD 12 10C
+0.91 10C 10C 136 COLD 580PP 0.33 110 P 5 TWD 16 DBC
-1.77 DBC DBC 165 COLD 560P2 0.78 102 P 5 TWD 32 DBC
+1.91 DBC DBC 165 COLD 560P2 143 103 0.64 74 P 3 TWD 24 DBH
+1.60 TEH TEC 23 COLD 600UL 0.86 97 P 5 TWD 40 DBH
+1.70 DBH DBH 322 HOT 560P2 143 109 0.72 106 P 5 TWD 30 DBC
-1.79 DBC DBC 165 COLD 560P2 0.53 79 P 3 TWD 19 DBC
-1.91 TEH TEC 22 COLD 600UL 144 74 0.73 102 P 5 TWD 31 VC1
+1.01 VC1 VC1 166 COLD 560P2 0.61 107 P 5 TWD 27 DBC
-1.56 DBC DBC 166 COLD 560P2 1.07 102 P 2 TWD 31 VC1
+0.94 TEH TEC 58 COLD 600UL 0.62 58 P 3 TWD 23 DBH
+1.84 TEH TEC 58 COLD 600UL 0.34 98 P 3 TWD 15 DBC
-1.56 TEH TEC 58 COLD 600UL 0.84 98 P 5 TWD 34 DBH
+1.53 DBH DBH 313 HOT 560P2 144 78 0.24 103 P 5 TWD 12 VC1
+0.91 VC1 VC1 166 COLD 560P2 0.28 131 P 2 TWD 14 VC1
+0.83 TEH TEC 24 COLD 600UL 144 84 0.50 106 P 5 TWD 23 DBC
-1.90 DBC DBC 166 COLD 560P2 0.32 112 P 5 TWD 16 DBC
+1.83 DBC DBC 166 COLD 560P2 0.22 89 P 3 TWD 10 DBC
-1.63 TEH TEC 24 COLD 60OUL 144 90 0.24 115 P 2 TWD 10 VH1
-0.83 TEH TEC 25 COLD 60OUL 144 102 0.56 114 P 5 TWD 24 DBH
-1.90 DBH DBH ATC 322 HOT 560P2 0.33 135 P 3 TWD 14 DBH
-1.59 TEH TEC 22 COLD 600UL 145 75 0.74 151 P 3 TWD 26 DBH
+1.89 TEH TEC 58 COLD 600UL 0.40 86 P 5 TWD 34 DBH
+2.12 DBH DBH 313 HOT 560P2 145 81 0.26 87 P 5 TWD 26 DBH
+1.61 DBH DBH 313 HOT 560P2 0.36 90 P 5 TWD 32 VH1
+0.96 VH1 VH1 313 HOT 560P2 0.50 34 P 3 TWD 20 DBH
+1.86 TEH TEC 25 COLD 600UL 0.87 120 P 2 TWD 28 VHl
+0.88 TEH TEC 25 COLD 60OUL 145 89 0.47 55 P 2 TWD 18 VC2
+0.91 TEH TEC 25 COLD 600UL 0.40 103 P 5 TWD 19 VC2
+0.90 VC2 VC2 165 COLD 560P2 145 99 0.40 127 P 3 TWD 17 DBH
+1.91 TEH TEC 23 COLD 60OUL 0.89 105 P 5 TWD 34 DBH
+2.09 DBH DBH ARS 317 HOT 560P2 145 103 0.61 98 P 5 TWD 33 DBH
+1.49 DBH DBH 322 HOT 560P2 0.64 118 P 3 TWD 23 DBH
+1.49 TEH TEC 22 COLD 600UL 146 78 0.28 85 P 5 TWD 27 DBH
+1.80 DBH DBH 313 HOT 560P2 0.41 124 P 3 TWD 18 DBH
+1.92 TEH TEC 25 COLD 600UL 146 86 0.84 105 P 5 TWD 34 DBC
+1.84 DBC DBC 166 COLD 560P2 1.27 104 P 5 TWD 41 DBH
+1.76 DBH DBH 317 HOT 560P2 0.46 110 P 5 TWD 21 VC1
+1.08 VC1 VC1 165 COLD 560P2 0.27 138 P 2 TWD 11 VH1
-1.17 TEH TEC 25 COLD 600UL 0.25 101 P 2 TWD 11 VC1
+1.02 TEH TEC 25 COLD 60OUL 0.79 31 P 3 TWD 27 DBH
+1.66 TEH TEC 25 COLD 600UL 0.43 108 P 3 TWD 18 DBC
+1.63 TEH TEC 25 COLD 600UL 146 88 0.64 82 P 5 TWD 34 DBC
+1.86 DBC DBC 165 COLD 560P2
- 0. 59 62 P 3 TWD 23 DBC
+1. 64 TEH TEC 25 COLD 600UL
Framatome ANP Inc.
03/07/04 14:17:31 Customer Name: San Onofre -
Unit 2 Component: S/G 89 Page 31 of 31 MAI, MCI, MMI, MVI, SAI, SCI, SVI, 0-100%
QUERY: rpc_icodes_and_0-100%twd.qry ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1 UTIL 2 CAL # LEG PROBE
--====-======-===-===-===-===-========================-
-=======-=======-=====-========-===
146 92 0.26 83 P 3 TWD 12 DBH
+1.73 TEH TEC 25 COLD 600UL 0.30 120 P 2 TWD 13 VH1
-1.16 TEH TEC 25 COLD 600UL 0.83 103 P 3 TWD 28 DBC
+1.80 TEH TEC 25 COLD 600UL 0.28 99 P 5 TWD 14 DBH
-1.52 DBH DBH 317 HOT 560P2 0.49 82 P 5 TWD 23 DBH
+1.75 DBH DBH 317 HOT 560P2 1.06 79 P 5 TWD 46 DBC
-1.06 TO+2.07 DEC DEC APN 165 COLD 560P2 146 94 0.42 105 P 3 TWD 18 DBH
+1.97 TEH TEC 23 COLD 600UL 0.88 62 P 3 TWD 29 DBC
+1.76 TEH TEC 23 COLD 600UL 0.56 104 P 5 TWD 25 DBH
+2.03 DBH DBH 317 HOT 560P2 0.84 81 P 5 TWD 41 DBC
-0.41 TO+2.21 DEC DEC APN 165 COLD 560P2 146 98 0.39 39 P 2 TWD 16 03H
-1.19 TEH TEC 23 COLD 600UL 0.17 109 2 SAI 03H
-1.11 03H 03H 0.00 299 HOT 580PP Total Tubes
- 798 Total Records: 1422