Attachment 1 to OCAN020405 Annual Radioactive Release Report for 2003

ARKANSAS NUCLEAR ONE UNIT 1 AND UNIT 2 OPERATING LICENSE NOS. DPR-51 AND NPF-6 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT JANUARY 1 THROUGH DECEMBER 31, 2003 1

TABLE OF CONTENTS

1. INTRODUCTION------------------------------------------------------------------------------------------

3

2. REGULATORY LIMITS ---------------------------------------------------------------------------------

3

3.

SUMMARY

OF LIQUID EFFLUENT DATA -------------------------------------------------------- 6

4.

SUMMARY

OF GASEOUS EFFLUENT DATA -------------------------------------------------- 15

5.

SUMMARY

OF RADIATION DOSES -------------------------------------------------------------- 24

6.

SUMMARY

OF DOSE TO MEMBERS OF THE PUBLIC -------------------------------------- 26

7. HISTORICAL EFFLUENT DATA-------------------------------------------------------------------- 27
8. SOLID WASTE

SUMMARY

39

9. UNPLANNED RELEASES ----------------------------------------------------------------------------

44

10. RADIATION INSTRUMENTATION --------------------------------------------------------------- 44
11. CHANGES TO THE PROCESS CONTROL PROGRAM --------------------------------------- 44
12. CHANGES TO THE OFFSITE DOSE CALCULATION MANUAL -------------------------- 45
13. LLD LEVELS--------------------------------------------------------------------------------------------45
14. RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM ------------------------ 45
15.

SUMMARY

OF HOURLY METEOROLOGICAL DATA -------------------------------------- 45

16. DESCRIPTION OF MAJOR CHANGES TO RADWASTE SYSTEMS ---------------------- 45
17. INDEPENDENT SPENT FUEL STORAGE INSTALLATION EFFLUENT RELEASES-----------------------------------------------------------------------------------------------

46 2

1.

INTRODUCTION Arkansas Nuclear One (ANO) is a two unit site consisting of a Babcock & Wilcox (Unit I) and a Combustion Engineering (Unit 2) nuclear steam supply system. Both liquid and gaseous effluents are released in accordance with the Offsite Dose Calculation Manual (ODCM). This report is a summary of the effluent data in accordance with Unit 1 TS 5.6.3 and Unit 2 TS 6.9.3. This report provides the following information:

A.

Routine radioactive effluent release reports covering the operation of the units and the independent spent fuel storage installation (ISFSI) during the reporting period.

B.

Description of unplanned releases to unrestricted areas.

C.

Description of changes to the Offsite Dose Calculation Manual (ODCM).

D.

Description of changes to the Process Control Program (PCP).

E.

Summary of radiation doses due to radiological effluents during the previous calendar year.

F.

Radiation dose to members of the public due to activities inside the site boundary.

G.

Description of licensee initiated major changes to the radioactive waste systems during the previous calendar year.

H.

Items to be reported in the annual Radioactive Effluent Release Report per other miscellaneous ODCM requirements.

This report covers the period from January 1 through December 31, 2003.

2.

REGULATORY LIMITS The ODCM contains the limits to which ANO must adhere. Because of the "as low as reasonably achievable" (ALARA) philosophy at ANO, an attempt is made to reduce the amount of radiation released to the environment. Liquid and gaseous release data show that the dose from both Unit 1 and Unit 2 is considerably below the ODCM limits. This data reveals that the radioactive effluents have an overall minimal dose contribution to the surrounding environment. The following are the limits required by the ODCM:

3

A.

Gaseous Effluents

1.

Dose rate due to radioactive materials released in gaseous effluent to unrestricted areas shall be limited to the following:

a.

Noble gases Less than or equal to 500 mrem/year to the total body Less than or equal to 3000 mrem/year to the skin

b.

Iodine-131, tritium, and for all radionuclides in particulate form with half lives greater than 8 days Less than or equal to 1500 mrem/yr to any organ

2.

Dose - Noble Gases Quarterly Less than or equal to 5 mrads gamma Less than or equal to 10 mrads beta Yearly Less than or equal to 10 mrads gamma Less than or equal to 20 mrads beta

3.

Dose - Iodine-131, Tritium, and Radionuclides in Particulate Form Quarterly Less than or equal to 7.5 mrems to any organ Yearly Less than or equal to 15 mrems to any organ 4

B.

Liquid Effluents

1.

Concentration The concentration of radioactive material released to the discharge canal shall be limited to the concentration specified in IOCFR2O, Appendix B, Table II, Column 2, for radionuclides other than dissolved or entrained noble gases. For dissolved or entrained noble gases, the total concentration released shall be limited to 2E-4 microcuries/ml.

2.

Dose Quarterly Less than or equal to 1.5 mrem total body Less than or equal to 5 mrem critical organ Yearly Less than or equal to 3 mrem total body Less than or equal to 10 mrem critical organ 5

3.

SUMMARY

OF LIQUID EFFLUENT DATA As required by Regulatory Guide 1.21, Rev. 1, Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Mater-Cooled Nuclear Powver Plants, a summary of data for liquid releases is provided in the annual Radioactive Effluent Release Report. This summary covers releases from January 1 through December 31, 2003. The summary of liquid effluents for both Unit 1 and Unit 2 is as follows:

Unit I Unit 2 Number of releases:

293 104 Total time for all releases (minutes):

566249 492508 Maximum time for a release (minutes):

10430 10420 Average time for a release (minutes):

1933 4736 Minimum time for a release (minutes):

20 55 The Unit 1 liquid releases consisted of:

293 Planned Releases 0

Unplanned Releases The Unit 2 liquid releases consisted of:

104 Planned Releases 0

Unplanned Releases 6

ANNUAL SUMMATION FOR ALL RELEASES BY QUARTER (ALL LIQUID EFFLUENTS)

January 1 through June 30, 2003 Unit 1 Type of Effluent A. Fission and Activation Products

1. Total Release (Not Including Tritium, Gases, Alpha)
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit B. Tritium
1. Total Release
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit C. Dissolved and Entrained Gases
1. Total Release
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit D. Gross Alpha Radioactivity
1. Total Release E. Waste Vol Released (Pre-Dilution)

F. Volume of Dilution Water Used Units Curies pCi/ml Quarter I Quarter 2 Est. Total Error %

1.428E-03 9.290E-03 25 4.925E-12 2.586E-1 I 1.642E-03 8.620E-03 Curies j1Ci/ml 2.100E+01 7.245E-08 4.364E+01 1.215E-07 25 2.415E-03 4.050E-03 Curies pCi/ml O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 25 O.OOOE+00 O.OOOE+00 Curies Liters Liters 2.709E-03 1.820E+07 2.898E+1 I O.OOOE+00 2.329E+07 3.592E+1 I 25 25 25 7

ANNUAL SUMMATION FOR ALL RELEASES BY QUARTER (ALL LIQUID EFFLUENTS)

July 1 through December 31, 2003 Unit 1 Type of Effluent Units Quarter 3 Quarter 4 Est. Total Error %

A. Fission and Activation Products

1. Total Release (Not Including Tritium, Gases, Alpha)
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit B. Tritium
1. Total Release
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit C. Dissolved and Entrained Gases
1. Total Release
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit D. Gross Alpha Radioactivity
1. Total Release E. Waste Vol Released (Pre-Dilution)

F. Volume of Dilution Water Used Curies jICi/ml 2.148E-03 5.516E-12 2.137E-02 7.144E-Il 25 1.839E-03 2.381E-02 Curies pCi/ml 1.621E+02 4.164E-07 1.388E-02 Curies jiCi/ml 2.094E-03 5.378E-12 2.365E+02 7.908E-07 2.636E-02 1.771E-02 5.921E-1 I 2.960E-05 0.000E+00 2.763E+07 2.990E+1 1 25 25 2.689E-06 Curies Liters Liters 0.000E+00 2.220E+07 3.893E+1 1 25 25 25 8

UNIT I REPORT CATEGORY TYPE OF ACTIVITY REPORTING PERIOD

ANNUAL LIQUID CONTINUOUS AND BATCH RELEASES
TOTALS FOR EACH NUCLIDE RELEASED
ALL RADIONUCLIDES
QUARTER # 1 AND QUARTER tt 2 YEAR 2003 NUCLIDE UNIT CONTINUOUS RELEASES QUARTER I QUARTER 2 BATCH RELEASES QUARTER 1 QUARTER 2 I-131 CURIES l 0.OOE+00 O.OOE+00 1.57E-06 O.OOE+00 NB-95 CURIES O.OOE+00 0.OOE+00 l 1.83E-06 0.OOE+00 NB-97 CURIES O.OOE+00 O.OOE+00 7.56E-06 O.OOE+00 1-133 CURIES 0.OOE+00 O.OOE+00 9.12E-06 0.OOE+00 G-ALPHA CURIES 1.63E-03 O.OOE+00 1.08E-03 O.OOE+00 CS-134 CURIES O.OOE+00 O.OOE+00 5.73E-07 2.60E-06 CO-60 CURIES O.OOE+00 O.OOE+00 4.70E-05 7.76E-05 CO-58 CURIES 0.00E+00 O.OOE+00 5.09E-04 2.63E-04 CS-137 CURIES 0.OOE+00 O.OOE+00 6.80E-05 4.80E-04 SB-125 CURIES 0.OOE+00 O.OOE+00 5.93E-04 5.61E-04 FE-55 CURIES 1.90E-04 5.05E-03 0.OOE+00 2.86E-03 H-3 CURIES 1.59E-01 2.46E-01 2.08E+01 4.34E+01 Total for CURIES 1.61E-01 2.5 lE-01 2.08E+01 4.34E+01 Period I

I I

I 9

UNIT 1 REPORT CATEGORY TYPE OF ACTIVITY REPORTING PERIOD

ANNUAL LIQUID CONTINUOUS AND BATCH RELEASES
TOTALS FOR EACH NUCLIDE RELEASED
ALL RADIONUCLIDES
QUARTER # 3 AND QUARTER # 4 YEAR 2003 CONTINUOUS RELEASES NUCLIDE UNIT BATCH RELEASES QUARTER 3 QUARTER 4 QUARTER 3 QUARTER 4 NB-97 CURIES O.OOE+00 O.OOE+00 3.85E-06 O.OOE+00 I-131 CURIES O.OOE+00 O.OOE+00 O.OOE+00 5.93E-05 CS-134 CURIES O.OOE+00 O.OOE+00 4.05E-07 6.73E-05 MN-54 CURIES O.OOE+00 O.OOE+00 6.47E-06 7.91E-05 I-133 CURIES O.OOE+00 O.OOE+00 O.OOE+00 8.59E-05 AG-11OM CURIES O.OOE+00 O.OOE+00 4.29E-05 1.88E-04 CS-137 CURIES O.OOE+00 O.OOE+00 1.34E-04 4.23E-04 CO-60 CURIES 0.00E+00 O.OOE+00 2.17E-04 7.82E-04 CR-51 CURIES O.OOE+00 O.OOE+00 O.OOE+00 9.29E-04 XE-135 CURIES 0.00E+00 O.OOE+00 3.13E-05 9.36E-04 ZR-95 CURIES 0.00E+00 O.OOE+00 2.12E-05 1.39E-03 NA-24 CURIES O.OOE+00 1.811E-03 O.OOE+00 0.00E+00 NB-95 CURIES O.OOE+00 O.OOE+00 8.45E-05 2.11 E-03 KR-85 CURIES O.OOE+00 O.OOE+00 O.OOE+00 3.43E-03 SB-125 CURIES O.OOE+00 O.OOE+00 4.97E-04 4.71E-03 CO-58 CURIES O.OOE+00 O.OOE+00 1.14E-03 8.72E-03 XE-133 CURIES O.OOE+00 O.OOE+00 2.06E-03 1.33E-03 H-3 CURIES 3.35E-01 1.71E-01 1.62E+02 2.37E+02 Total for CURIES 3.35E-01 1.73E-01 1.62E+02 2.37E+02 Period I

I II 10

ANNUAL SUMMATION FOR ALL RELEASES BY QUARTER (ALL LIQUID EFFLUENTS)

January 1 through June 30, 2003 Unit 2 Type of Effluent Units Quarter 1 Quarter 2 Est. Total Error %

A. Fission and Activation Products

1. Total Release (Not Including Tritium, Gases, Alpha)
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit B. Tritium
1. Total Release
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit C. Dissolved and Entrained Gases
1. Total Release
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit D. Gross Alpha Radioactivity
1. Total Release E. Waste Vol Released (Pre-Dilution)

F. Volume of Dilution Water Used Curies j1Ci/ml 7.11 OE-03 6.964E-04 25 2.453E-1 I 1.938E-12 8.177E-03 6.462E-04 Curies pCi/ml 2.528E+02 8.723E-07 2.908E-02 Curies pCi/ml 0.OOOE+00 O.OOOE+00 1.492E+02 4.154E-07 1.385E-02 1.495E-04 4.161E-13 2.0811E-07 0.000E+00 7.895E+06 3.592E+1 1 25 25 0.OOOE+00 Curies Liters Liters 0.OOOE+00 7.518E+06 2.898E+1 1 25 25 25 11

ANNUAL SUMMATION FOR ALL RELEASES BY QUARTER

  • (ALL LIQUID EFFLUENTS)

July 1 through December 31, 2003 Unit 2 Type of Effluent Units Quarter 3 Quarter 4 Est. Total Error %

A. Fission and Activation Products

1. Total Release (Not Including Tritium, Gases, Alpha)
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit B. Tritium
1. Total Release
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit C. Dissolved and Entrained Gases
1. Total Release
2. Average Diluted Concentration During Period
3. Percent of Applicable Limit D. Gross Alpha Radioactivity
1. Total Release E. Waste Vol Released (Pre-Dilution)

F. Volume of Dilution Water Used Curies pCi/ml 1.1211E-02 1.778E-02 2.879E-1 I 5.944E-l I 25 9.596E-03 Curies pCi/ml 2.746E+02 7.053E-07 1.981E-02 2.543E+01 8.504E-08 2.835E-03 25 2.3511E-02 Curies 11Ci/ml 9.632E-02 2.474E-10 2.206E-03 7.376E-12 25 1.237E-04 3.688E-06 Curies Liters Liters 0.000E+00 8.108E+06 3.893E+1 1 0.000E+00 1.434E+07 2.990E+1 I 25 25 25 12

UNIT 2 REPORT CATEGORY TYPE OF ACTIVITY REPORTING PERIOD

ANNUAL LIQUID CONTINUOUS AND BATCH RELEASES
TOTALS FOR EACH NUCLIDE RELEASED
ALL RADIONUCLIDES
QUARTER # 1 AND QUARTER # 2 YEAR 2003 CONTINUOUS RELEASES BATCH RELEASES NUCLIDE UNIT QUARTER 1 QUARTER 2 QUARTER 1 QUARTER 2 NB-95 CURIES O.OOE+00 0.00E+00 4.23E-05 O.OOE+00 ZR-95 CURIES O.OOE+00 O.OOE+00 4.82E-05 O.OOE+00 MN-54 CURIES O.OOE+00 O.OOE+00 9.98E-05 O.OOE+00 CR-51 CURIES O.OOE+00 O.OOE+00 2.13E-04 O.OOE+00 CO-58 CURIES O.OOE+00 O.OOE+00 8.65E-04 1.33E-05 NB-97 CURIES O.OOE+00 O.OOE+00 0.00E+00 1.47E-05 CS-137 CURIES O.OOE+00 O.OOE+00 9.63E-05 5.54E-05 SB-125 CURIES 0.00E+00 0.OOE+00 3.85E-04 6.19E-05 AG-1 10M CURIES 0.00E+00 0.OOE+00 4.72E-03 9.54E-05 CO-60 CURIES O.OOE+00 O.OOE+00 6.36E-04 1.44E-04 XE-133 CURIES O.OOE+00 O.OOE+00 O.OOE+00 1.49E-04 NA-24 CURIES O.OOE+00 3.12E-04 O.OOE+00 O.OOE+00 H-3 CURIES 1.04E-01 9.20E-02 2.53E+02 1.49E+02 Total for CURIES 1.04E-01 9.23E-02 2.53E+02 1.49E+02 Period 13

UNIT 2 REPORT CATEGORY TYPE OF ACTIVITY REPORTING PERIOD

ANNUAL LIQUID CONTINUOUS AND BATCH RELEASES
TOTALS FOR EACH NUCLIDE RELEASED
ALL RADIONUCLIDES
QUARTER # 3 AND QUARTER # 4 YEAR 2003 CONTINUOUS RELEASES UNIT BATCH RELEASES QUARTER 3 QUARTER 4 NUCLIDE QUARTER 3 QUARTER 4 NB-97 CURIES O.OOE+00 O.OOE+00 1.56E-05 O.OOE+00 AR-41 CURIES 0.00E+00 0.00E+00 1.66E-05 0.00E+00 CS-138 CURIES 0.00E+00 0.00E+00 3.44E-05 O.OOE+00 I-131 CURIES O.OOE+00 O.OOE+00 7.58E-05 O.OOE+00 XE-135 CURIES O.OOE+00 O.OOE+00 5.88E-04 0.00E+00 XE-133M CURIES O.OOE+00 O.OOE+00 8.34E-04 O.OOE+00 CS-134 CURIES 0.00E+00 O.OOE+00 0.001E+00 4.19E-06 CS-137 CURIES O.OOE+00 0.00E+00 4.611E-04 1.21E-04 NA-24 CURIES 3.1 OE-04 1.50E-04 0.00E+00 O.OOE+00 AG-1i0M CURIES O.OOE+00 O.OOE+00 2.84E-03 1.56E-04 SB-125 CURIES 0.00E+00 O.OOE+00 1.88E-03 1.60E-04 MN-54 CURIES O.OOE+00 O.OOE+00 2.19E-04 2.86E-04 CO-60 CURIES 0.00E+00 0.00E+00 1.55E-03 5.01 E-04 FE-59 CURIES 0.00E+00 O.OOE+00 3.47E-05 6.OOE-04 ZR-95 CURIES O.OOE+00 0.001E+00 1.74E-04 8.00E-04 NB-95 CURIES 0.OOE+00 0.OOE+00 1.44E-04 1.11 E-03 XE-133 CURIES O.OOE+00 0.00E+00 9.49E-02 2.21E-03 CR-51 CURIES 0.00E+00 O.OOE+00 1.25E-03 5.37E-03 CO-58, CURIES O.OOE+00 O.OOE+00 2.22E-03 8.52E-03 H-3 CURIES 1.97E-02
7. 1 E-02 2.75E+02 2.53E+01 Total for CURIES 2.OOE-02 7.13E-02 2.75E+02 2.54E+01 Period 14
4.

SUMMARY

OF GASEOUS EFFLUENT DATA As required by Regulatory Guide 1.21, Rev. 1, a summary of data for gaseous releases is provided in the annual Radioactive Effluent Release Report. This summary covers releases from January 1 to December 31, 2003. The summary of gaseous effluents for both Unit 1 and Unit 2 is as follows:

Unit I Unit 2 Number of releases:

133 121 Total time for all releases (minutes):

1022574 904022 Maximum time for a release (minutes):

10581 10499 Average time for a release (minutes):

7688 7471 Minimum time for a release (minutes):

0.1 7

The Unit 1 gaseous releases consisted of:

133 Planned vent & tank releases 0

Unplanned releases The Unit 2 gaseous releases consisted of:

121 Planned vent & tank releases 0

Unplanned releases 15

ANNUAL SUMMATION FOR ALL RELEASES BY QUARTER (ALL AIRBORNE EFFLUENTS)

January 1 through June 30, 2003 Unit I Type of Effluent Units Quarter 1 Quarter 2 Est. Total Error %

A. Fission and Activation Products

1. Total Release
2. Average Release Rate for Period
3. Percent of Applicable Limit B. Radioiodines
1. Total Iodine-131
2. Average Release Rate for Period
3. Percent of Applicable Limit C. Particulates
1. Particulates (Half-Lives > 8 Days)
2. Average Release Rate for Period
3. Percent of Applicable Limit
4. Gross Alpha Radioactivity D. Tritium
1. Total Release
2. Average Release Rate for Period
3. Percent of Applicable Limit Curies pCi/Sec Curies pCi/Sec Curies pCi/Sec Curies Curies pCi/Sec 4.049E-02 5.207E-03 7.290E-05 O.OOOE+00 O.OQOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 1.065E+01 1.369E+00 1.917E-03 1.523E-01 1.937E-02 2.71 IE-04 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 1.067E+01 1.357E+00 1.900E-03 25 25 25 25 16

ANNUAL SUMMATION FOR ALL RELEASES BY QUARTER (ALL AIRBORNE EFFLUENTS)

July 1 through December 31, 2003 Unit 1 Type of Effluent Units Quarter 3 Quarter 4 Est. Total Error %

A. Fission and Activation Products

1. Total Release
2. Average Release Rate for Period
3. Percent of Applicable Limit B. Radioiodines
1. Total Iodine-131
2. Average Release Rate for Period
3. Percent of Applicable Limit C. Particulates
1. Particulates (Half-Lives > 8 Days)
2.. Average Release Rate for Period
3. Percent of Applicable Limit
4. Gross Alpha Radioactivity D. Tritium
1. Total Release
2. Average Release Rate for Period
3. Percent of Applicable Limit Curies PCi/Sec Curies pCi/Sec Curies

.tCi/Sec Curies Curies gCi/Sec O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 9.536E+00 1.200E+00 1.679E-03 O.OOOE+00 O.OOOE+00 0.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 7.271E+00 9.147E-01 1.281E-03 25 25 25 25 17

UNIT I REPORT CATEGORY TYPE OF ACTIVITY REPORTING PERIOD

ANNUAL AIRBORNE GROUND LEVEL CONTINUOUS AND BATCH RELEASES
TOTALS FOR EACH NUCLIDE RELEASED
FISSION GASES, IODINES, AND PARTICULATES
QUARTER # 1 AND QUARTER # 2 YEAR 2003 CONTINUOUS RELEASES QUARTER I QUARTER 2 BATCH RELEASES QUARTER I QUARTER 2 NUCLIDE UNIT Fission Gases KR-85 CURIES O.OOE+00 0.00E+00 4.05E-02 1.52E-01 Total for CURIES O.OOE+00 O.OOE+00 4.05E-02 1.52E-01 Period lodines NONE CURIES l O.OOE+0 I O.00E+00 l O.OOE+00 0.0E+00

]

Total for CURIES O.OOE+00 0.00E+00 O.OOE+00 O.OOE+00 Period Particulates NONE CURIES O.OOE+00 O.OOE+00 O.OOE+00 0.00E+00

]

Total for CURIES 0.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Period l

Other H-3 CURIES O.OOE+00 0.00E+00 1.06E+01 I 1.07E+01l Total for CURIES O.OOE+00 O.OOE+00 1.06E+01 1.07E+0I Period III 18

UNIT 1 REPORT CATEGORY TYPE OF ACTIVITY REPORTING PERIOD

ANNUAL AIRBORNE GROUND LEVEL CONTINUOUS AND BATCH RELEASES
TOTALS FOR EACH NUCLIDE RELEASED
FISSION GASES, IODINES, AND PARTICULATES
QUARTER # 3 AND QUARTER # 4 YEAR 2003 CONTINUOUS RELEASES QUARTER 3 QUARTER 4 BATCH RELEASES QUARTER 3 QUARTER 4 NUCLIDE UNIT Fission Gases NONE CURIES 0.00E+00 0.00E+00 O.OOE+00 O.OOE+00 Total for CURIES O.OOE+00 O.OOE+00 0.00E+00 O.OOE+00 PeriodI__

lodines NONE CURIES 0.OOE+00 0.00E+00 l O.OOE+00 O.OOE+00 1

Total for CURIES 0.00E+00 0.001+00 0.00E+00 0.OOE+00 Period Particulates NONE CURIES 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Total for CURIES 0.OOE+00 0.OOE+00 0.00E+00 0.OOE+00 Other H-3 CURIES 0.OOE+00 0.OOE+00 9.54E+00 7.27E+00 Total for CURIES 0.OOE+00 0.OOE+00 9.54E+00 7.27E+00 Period I

19

ANNUAL SUMMATION FOR ALL RELEASES BY QUARTER (ALL AIRBORNE EFFLUENTS)

January 1 through June 30, 2003 Unit 2 Type of Effluent Units Quarter I Quarter 2 Est. Total Error %

A. Fission and Activation Products

1. Total Release
2. Average Release Rate for Period
3. Percent of Applicable Limit B. Radioiodines
1. Total Iodine-131
2. Average Release Rate for Period
3. Percent of Applicable Limit C. Particulates
1. Particulates (Half-Lives > 8 Days)
2. Average Release Rate for Period
3. Percent of Applicable Limit
4. Gross Alpha Radioactivity D. Tritium
1. Total Release
2. Average Release Rate for Period
3. Percent of Applicable Limit Curies pCi/Sec Curies pCi/Sec Curies pCi/Sec Curies Curies pCi/Sec O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+O0 O.OOOE+00 6.61 OE+00 8.501E-01 1.190E-03 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 O.OOOE+00 4.71 OE+00 5.991E-01 8.387E-04 25 25 25 25 20

ANNUAL SUMMATION FOR ALL RELEASES BY QUARTER (ALL AIRBORNE EFFLUENTS)

July 1 through December 31, 2003 Unit 2 Type of Effluent Units Quarter 3 Quarter 4 Est. Total Error %

A. Fission and Activation Products

1. Total Release
2. Average Release Rate for Period
3. Percent of Applicable Limit B. Radioiodines
1. Total Iodine-131
2. Average Release Rate for Period
3. Percent of Applicable Limit C. Particulates
1. Particulates (Half-Lives > 8 Days)
2. Average Release Rate for Period
3. Percent of Applicable Limit
4. Gross Alpha Radioactivity D. Tritium
1. Total Release
2. Average Release Rate for Period
3. Percent of Applicable Limit Curies pCi/Sec Curies pCi/Sec Curies pCi/Sec Curies Curies pCi/Sec 3.886E-O0 4.889E-02 6.845E-04 I.OOlE-06 1.259E-07 3.526E-07 O.OOOE+OO O.OOOE+OO O.OOOE+OO O.OOOE+OO 5.484E+OO 6.900E-O1 9.660E-04 O.OOOE+OO O.OOOE+OO O.OOOE+OO O.OOOE+OO O.OOOE+OO O.OOOE+OO O.OOOE+OO O.OOOE+OO O.OOOE+OO O.OOOE+OO 8.307E+OO 1.045E+OO 1.463E-03 25 25 25 25 21

UNIT 2 REPORT CATEGORY TYPE OF ACTIVITY REPORTING PERIOD

ANNUAL AIRBORNE GROUND LEVEL CONTINUOUS AND BATCH RELEASES
TOTALS FOR EACH NUCLIDE RELEASED
FISSION GASES, IODINES, AND PARTICULATES
QUARTER # 1 AND QUARTER # 2 YEAR 2003 CONTINUOUS RELEASES QUARTER 1 QUARTER 2 BATCH RELEASES QUARTER I QUARTER 2 NUCLIDE UNIT Fission Gases NONE CURIES O.OOE+00 O.OOE+00 l0.00E+00 0.00E+00 Total for CURIES 0.00E+00 0.00E+00 l0.00E+00 0.00E+00 P e rio d_

Iodines NONE CURIES 0.00E+00 O.OOE+00 O.OOE+00 0.00E+00 Total for CURIES 0.00E+00 O.OOE+00 0.00E+00 O.OOE+00 Period Particulates NONE CURIES 0.00E+00 O.OOE+00 O.OOE+00 0.OOE+00 Total for CURIES O.OOE+00 0.00E+00 0.00E+00 O.OOE+00 Period Other H-3 CURIES 0.00E+00 O.OOE+00 6.611E+00 4.71 E+00 Total for CURIES 0.00E+00 0.00E+00 6.611E+00 4.71E+00 Period 22

UNIT 2 REPORT CATEGORY TYPE OF ACTIVITY REPORTING PERIOD

ANNUAL AIRBORNE GROUND LEVEL CONTINUOUS AND BATCH RELEASES
TOTALS FOR EACH NUCLIDE RELEASED
FISSION GASES, IODINES, AND PARTICULATES
QUARTER # 3 AND QUARTER # 4 YEAR 2003 CONTINUOUS RELEASES BATCH RELEASES NUCLIDE UNIT QUARTER 3 QUARTER 4 QUARTER 3 QUARTER 4 Fission Gases XE-135 CURIES O.OOE+00 O.OOE+00 2.32E-02 O.OOE+00 XE-133 CURIES O.OOE+00 O.OQE+00 3.65E-01 J O.OOE+00 Total for CURIES O.OOE+00 O.OOE+00 3.89E-01 O.OOE+00 Period Iodines I-131 CURIES O1 0.OOE+00 O.OOE+00 1.OOE-06 O.OOE+00 Peortlodr CURIES O.OOE+00 O.OOE+00 I.OOE-06 O.OOE+00 Particulates NONE CURIES_-

O.OOE+00 I O.OOE+00 0OOOE+00 l O.OOE+00 Total for CURIES O.OOE+00 O.OOE+00 O.OOE+l O

Period I

I

+00I I

I____ ______

Other H-3 CURIES l O.OOE+00 l O.OOE+00 5.48E+00 8.31E+00 Total for CURIES 0.00E+00 O.OOE+00 5.48E+00 8.31E+00 Period 23

5.

SUMMARY

OF RADIATION DOSES The following is a summary of the annual radiation doses due to radiological effluents during 2003 calculated in accordance with the Offsite Dose Calculation Manual.

UNIT 1 Liquid Radwaste Effluents Dose Limits (mRem): Total Body = 1.5/Qtr 3/Yr, Other Organs = 5/Qtr 10/Yr Organ Qtr I Otr 2 Otr 3 Qtr 4 Year TBody 0.0001 0.00 0.0003 0.02 0.0003 0.02 0.0006 0.04 Bone 0.0000 0.00 0.0003 0.01 0.0001 0.00 0.0002 0.00 Liver 0.0001 0.00 0.0004 0.01 0.0003 0.01 0.0007 0.01 Thyroid 0.0000 0.00 0.0001 0.00 0.0001 0.00 0.0004 0.01 Kidney 0.0001 0.00 0.0002 0.00 0.0002 0.00 0.0005 0.01 Lung 0.0000 0.00 0.0001 0.00 0.0002 0.00 0.0004 0.01 GI-LLI 0.0000 0.00 0.0001 0.00 0.0002 0.00 0.0008 0.02 0.0012 0.04 0.0006 0.01 0.0015 0.02 0.0007 0.01 0.0009 0.01 0.0008 0.01 0.0011 0.01 Gaseous Radwaste Effluents Iodine, H-3, and Particulate (ITP) - Dose Limits (mRem) = 7.5/Qtr 15/Yr Organ Otr I Otr 2 Otr 3 Otr 4 Year TBody 0.0066 0.09 0.0066 0.09 0.0059 0.08 0.0045 0.06 Bone 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.0000 0.00 Liver 0.0066 0.09 0.0066 0.09 0.0059 0.08 0.0045 0.06 Thyroid 0.0066 0.09 0.0066 0.09 0.0059 0.08 0.0045 0.06 Kidney 0.0066 0.09 0.0066 0.09 0.0059 0.08 0.0045 0.06 Lung 0.0066 0.09 0.0066 0.09 0.0059 0.08 0.0045 0.06 GI-LLI 0.0066 0.09 0.0066 0.09 0.0059 0.08 0.0045 0.06 0.0235 0.0000 0.0235 0.0235 0.0235 0.0235 0.0235 0.16 0.00 0.16 0.16 0.16 0.16 0.16 Noble Gas Air Dose Limits (mRad) = Gamma 5/Qtr I 0/Yr, Beta 10/Qtr 20/Yr Type Otr I Qtr 2 Qtr 3 Otr 4 Year Gamma 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.0000 Beta 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.00 24

UNIT 2 Liquid Radwaste Effluents Dose Limits (mRem): Total Body = 1.5/Qtr 3/Yr, Other Organs = 5 /Qtr 10/Yr Organ Otr I Otr 2 Otr 3 Otr 4 Year TBody 0.0005 0.03 0.0002 0.02 0.0005 0.04 0.0001 0.01 Bone 0.0001 0.00 0.0000 0.00 0.0002 0.00 0.0001 0.00 Liver 0.0005 0.01 0.0002 0.00 0.0006 0.01 0.0002 0.00 Thyroid 0.0004 0.01 0.0002 0.00 0.0002 0.01 0.0000 0.00 Kidney 0.0004 0.01 0.0002 0.00 0.0004 0.01 0.0001 0.00 Lung 0.0004 0.01 0.0002 0.00 0.0004 0.01 0.0001 0.00 GI-LLI 0.0005 0.01 0.0002 0.00 0.0005 0.01 0.0003 0.01 0.0013 0.04 0.0004 0.00 0.0015 0.02 0.0010 0.01 0.0012 0.01 0.0011 0.01 0.0014 0.01 Gaseous Radwaste Effluents Iodine, H-3, and Particulate - Dose Limits (mRem) = 7.5/Qtr 15/Yr Organ Otr I Otr 2 Qtr 3 Otr 4 Year Tbody 0.0041 0.05 0.0029 0.04 0.0034 0.05 0.0051 0.07 Bone 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.0000 0.00 Liver 0.0041 0.05 0.0029 0.04 0.0034 0.05 0.0051 0.07 Thyroid 0.0041 0.05 0.0029 0.04 0.0036 0.05 0.0051 0.07 Kidney 0.0041 0.05 0.0029 0.04 0.0034 0.05 0.0051 0.07 Lung 0.0041 0.05 0.0029 0.04 0.0034 0.05 0.0051 0.07 GI-LLI 0.0041 0.05 0.0029 0.04 0.0034 0.05 0.0051 0.07 0.0155 0.10 0.0000 0.00 0.0155 0.10 0.0157 0.10 0.0155 0.10 0.0155 0.10 0.0155 0.10 Noble Gas Air Dose Limits (mRad) = Gamma 5/Qtr I 0/Yr, Beta I O/Qtr 20/Yr Type tr I Otr 2 Otr 3 Otr 4 Year Gamma 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.0000 0.00 Beta 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.0000 0.00 0.0001 0.00 25

6.

SUMMARY

OF DOSE TO MEMBERS OF THE PUBLIC The following is a summary of the annual radiation dose to members of the public (in mrem) due to activities inside the site boundary.

UNIT 1 BONE LIVER I TBODY I THYROID I KIDNEY I GI-LLI LUNG I SKIN Gaseous Effluent Iodine/Tritium Particulate Noble Gas Liquid Effluent Fish Sediment Unit I Total 0.OOE+00 I13.90E-031I3.90E-03 8.43E-08 1.24E-03 2.68E-05 5.17E-03 3.90E-03 7.17E-04 4.62E-03 3.90E-03 9.49E3-04 4.85E-03 3.90E-03 7.80E-04 4.68E-03 3.90E-03 7.122E-06 3.14E-05 3.85E-05 6.08E-04 l 1.52E-03 1.1I3E-03 5.03E-03 6.08E-04 l5.42E-03 UNIT 2 Y

P Gaseous Effluent Iodine/Tritium Particulate Noble Gas Liquid Effluent Fish Sediment Unit 2 Total 1.09E-07 l 2.57E-03 l 2.57E-03 l 2.60E-03 I 2.57E-03 l 2.57E-03 l 2.57E-03 4.06E-06 1.35E-03 6.5 lE-05 3.99E-03 9.39E-06 7.63E-05 8.57E-05 3.5 1E-04 11.52E-03 1.04E-03 1.171E-03 I 1.06E-0311l.45E-03 3.51E-04 14.09E-03 3.64E-03 3.74E-03 13.63E-0314.02E-03 I

I Site Total 9.59E-04 9.5 1E-03 9.16E-03 8.26E-03 8.59E-03 8.31lE-03 9.05E-03 1.24E-04 Limit 25 25 25 75 25 25 25 25 (40CFR 190)

% Limit 3.84E-03 3.80E-02 3.66E-02 1.10E-02 3.44E-02 3.32E-02 3.62E-02 4.97E-04 26

7.

HISTORICAL EFFLUENT DATA The following graphs show the historical release data for both units on a yearly basis. These graphs compare data from 1993 through 2003.

UNIT I LIQUID EFFLUENTS FISSION AND ACTIVATION PRODUCTS 1.COE+02 1.OE+01 on w

1.00E-01 1.00E-02 1993 1994 1995 1996 1997 1998 19 2000 2001 2002 20M YEAR UNIT I LIQUID EFFLUENTS TRImIUM 1.OOE+04 E 1.00E+03 1.00E+02 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR 27

UNIT I LIQUID EFFLUENTS DISSOLVED AND ENTRAINED GASES 1.OOE+03 1.OOE.02

,,1.00E+02 co 1.OOE+01 w

u 1.OOE+DO 1.00E-01 1.00E-02 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT I LIQUID EFFLUENTS TOTAL VOLUME RELEASED 1.00E+08 9 1.00E+07

-j 1.00E.06 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 1 LIQUID EFFLUENTS TOTAL BODY DOSE 1.00E+00 1.00E-01 1.00E-02 1.00E-03 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR 28

1.OOE+00 1.OOE-01 1.00E-02 1.OOE-03 UNIT I LIQUID EFFLUENTS CRITICAL ORGAN DOSE 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 1 LIQUID EFFLUENTS COLLECTIVE DOSES 2.000 1.800 1.600 1.400 1.200 M 1.000 0.800 0.600 0.400 0.200 0.000 I

d~in VA U.

.And..I,,

1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR IOABONE ELIVER CGI-LU OTHYROID CKIDNEY a LUNGI UNIT I GASEOUS EFFLUENTS FISSION AND ACTIVATION PRODUCTS 1.00E+04 1.OOE+03 1.OOE+02 1.OOE+01 cn w

E 1.00E+00 1.00E-01 1.00E-02 1.00E-03 1.00E-04 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR 29

1.00E-01 1.00E-02 1.0OE-03 U)l 1.0OE-04 u 1.0OE-05 1.OOE-06 1.OOE-07 1.OOE-08 1.0OE-01 1.0OE-02 1.0OE-03 E2 1.00E-04 1.COE-05 1.OOE-06 1.OOE-07 UNIT I GASEOUS EFFLUENTS RADIOIODINES 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT I GASEOUS EFFLUENTS PARTICULATES 1.OOE.02 ILl

& 1.OOE+01 1.OOE+00 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT I GASEOUS EFFLUENTS TRmuaU 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR 30

1.OOE-01 1.00 E-02 0

1.00E-03 1.00E-04 UNIT I GASEOUS EFFLUENTS GAMMA DOSE JILL _flD7 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT I GASEOUS EFFLUENTS BETA DOSE 1.OOE+00 1.OOE-01 f

1.00E-02 1.00E-03 1.00E-04 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT I GASEOUS EFFLUENTS TOTAL BODY DOSE 1.OOE+00 1.OOE-01 1.00E-02 1.00E-03 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR 31

UNIT I GASEOUS EFFLUENTS CRITICAL ORGAN DOSE 1.00E+00 1.00E-01 1.OOE-02 1.00E.03 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT I GASEOUS EFFLUENTS COLLECTIVE DOSES 0.400 0.350 0.300 0.250 P.-

0.200 0.150 0.100 0.050 0.000 I

1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR I M BONE M LIVER U THYROID E KIDNEY 0 LUNG MGI-LLI 32

UNIT 2 LIQUID EFFLUENTS FISSION AND ACTIVATION PRODUCTS 1.OOE+02 1.OE+01 en 1.00E+00 U

1.00E-01 1.OOE-02 1.OE+04 1.OOE+03 w

1.OOE+02 1.OOE+01 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 2 LIQUID EFFLUENTS TRIUM 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 2 LIQUID EFFLUENTS DISSOLVED AND ENTRAINED GASES 1.OOE+03 1.OOE+02 1.OOE+01

= 1.OOE+00 1.00E-01 1.00E-02 1.00E-03 1993 1994 1995 1998 1997 1998 1999 2000 2001 2002 2003 YEAR 33

UNIT 2 LIQUID EFFLUENTS TOTAL VOLUME RELEASED 1.00E+08 0

.1.OOE+.7 (9

1.OOE+06 i.OOE*00 1.00 E-01 E 1.00E-02 1.OOE-03 1.00E-04 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 2 LIQUID EFFLUENTS TOTAL BODY DOSE 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 2 LIQUID EFFLUENTS CRITICAL ORGAN DOSE 1.OOE+00 1.00E-01 1.OOE-02 1.00E-03 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR 34

4.000 3.500 3.000 2.500 I.-

i 2.000 1.500 1.000 0.500 0.000 UNIT 2 LIQUID EFFLUENTS COLLECTIVE DOSES Ls

. op.,

An -

A_.--M -

-q 1993 1994 1995 1996 1997 1998 YEAR 1999 2000 2001 2002 2003 I BONE 1LIVER 0GI-LU 0 THYROID M KIDNEY CLUNG I UNIT 2 GASEOUS EFFLUENTS FISSION AND ACTIVATION PRODUCTS 1.OOE+04 1.OOE+03 1.OOE+02 E 1.00E+01 U

1.OOE+DO 1.00E-01 1.00E-02 1.OOE-01 1.OOE-02 1.00E-03 E

) 1.00E-045 1.00E-06 1.00E-07 1.00E-08 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 2 GASEOUS EFFLUENTS RADIOIOCINES 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR 35

UNIT 2 GASEOUS EFFLUENTS PARTICULATES 1.OOE+00 1.00E-01 1.00E-02 en 1.00E-03 w

D 1.00E-04 1.00E-05 1.00E-06 1.00E-07 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 2 GASEOUS EFFLUENTS TRmuM 1.00E+02 w

UE 1.00E+01 1.0OE+00 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 2 GASEOUS EFFLUENTS GAMMA DOSE 1.00E+00 1.00E-01 1.00E-02 1.00E-03 1.00E-04 1.00E-05 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR 36

UNIT'2 GASEOUS EFFLUENTS BETA DOSE 1.OE+00 1.00E-01 9

1.OOE.02 1.00E-03 1.OOE.04 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 2 GASEOUS EFFLUENTS TOTAL BODY DOSE 1.OOE+00 1.00E-01 1.OOE-02 1.00E-03 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR UNIT 2 GASEOUS EFFLUENTS CRITICAL ORGAN DOSE 1.00E+00 1.00E-01 1.00E-02 1.00E-03 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR 37

UNIT 2 GASEOUS EFFLUENTS COLLECTIVE DOSES 1.600 1.400 1.200 1.000 I.-

0.800 0.6 0.600 0.400 0.200 0.000 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 YEAR eBONE LIVER E THYROID E KIDNEY 0 LUNG 0 GI-LLI 38
8.

SOLID WASTE

SUMMARY

As required by Regulatory Guide 1.21, Rev. 1, a summary of data for solid wastes shipped offsite is provided in the annual Radioactive Effluent Release Report.

This summary covers shipments from January 1 through December 31, 2003. The summary for solid waste shipments is as follows:

REGULATORY GUIDE 1.21 REPORT EFFLUENT AND WASTE DISPOSAL ANNUAL

SUMMARY

REPORT SOLID WASTE AND IRRADIATED FUEL SHIPMENTS JANUARY 1, 2003 THROUGH JUNE 30, 2003 A.

Solid Waste Shipped Offsite for Burial or Disposal (Not Irradiated Fuel)

1.

Type of Waste Unit 6-Month Est. Total Period Error, %

a. Spent resins, filter sludges, m3 2.50E+02 evaporator bottoms, etc.

Ci 2.72E+03

+/-2.5E+01

b. Dry compressible waste, m3 3.62E+01 contaminated equip, Ci 1.1 8E-02

+2.5E+0I etc.

c. Irradiated components, m3 6.74E-01 control rods, etc.

Ci 1.04E+00

+2.5E+0I

d. Other (describe):

m3 1.14E+0I Oil Ci 2.82E-01

+2.5E+01 39

2.

Estimate of Major Nuclide Composition (by Type of Waste)

a.

Spent resins, filter sludges, evaporator bottoms, etc.

Curies C-14 3.06 8.33E+01 FE-55 11.22 3.06E+02 CO-58 4.70 1.28E+02 CO-60 6.31 1.72E+02 NI-59 7.60 2.07E+02 NI-63 48.90 1.33E+03 CS-134 1.02 2.77E+01 CS-137 14.63 3.99E+02

b.

Dry compressible waste, contaminated equipment, etc.

Curies CR-51 18.82 2.23E-03 MN-54 1.94 2.29E-04 FE-55 18.54 2.19E-03 CO-58 26.90 3.18E-03 CO-60 3.07 3.64E-04 NI-59 17.90 2.12E-03 NI-63 3.98 4.71E-04 ZR-95 3.05 3.61E-04 NB-95 4.31 5.1 OE-04

c.

Irradiated components, control rods, etc.

Curies MN-54 3.06 3.18E-02 FE-55 50.15 5.21E-01 CO-60 41.42 4.30E-01 NI-63 1.39 1.44E-02 PM-147 2.35 2.44E-02

d.

Other (Oil)

Curies NI-59 97.01 2.74E-01 NI-63 1.61 4.54E-03

3.

Solid Waste Disposition Number of Shipments Mode of Transportation Destination 15 Cask Barnwell, SC 32 Cask Erwin, TN I

Flatbed/Sea Van Oak Ridge, TN 7

Flatbed/Sea Van Memphis, TN 40

B.

Irradiated Fuel Shipments (Disposition)

Number of Shipments Mode of Transportation None Destination 41

REGULATORY GUIDE 1.21 REPORT EFFLUENT AND WASTE DISPOSAL ANNUAL

SUMMARY

REPORT SOLID WASTE AND IRRADIATED FUEL SHIPMENTS JULY 1, 2003 THROUGH DECEMBER 31, 2003 A.

Solid Waste Shipped Offsite for Burial or Disposal (Not Irradiated Fuel)

1.

Type of Waste Unit 6-Month Est. Total Period Error, %

a. Spent resins, filter sludges, m3 5.08E+01 evaporator bottoms, etc.

Ci 3.02E+05 A2.5E+01

b. Dry compressible waste, m3 1.81E+02 contaminated equip, etc.

Ci 1.81E+00

+2.5E+01

c. Irradiated components, m3 0.OOE+00 control rods, etc.

Ci 0.OOE+00

-2.5E+01

d. Other (describe):

m3 0.00E+00 Ci 0.00E+00

+2.5E+01 42

2.

Estimate of Major Nuclide Composition (by Type of Waste)

a.

Spent resins, filter sludges, evaporator bottoms, etc.

Curies CO-60 55.62 1.6813-05 CD-1 09 9.57 2.89E-06 CS-134 1.24 3.7413-07 CS-137 33.58 1.0113-05

b.

Dry compressible waste, contaminated equipment, etc.

Curies CR-51 18.89 1.62E-01 MN-54 1.94 1.6613-02 FE-55 18.51 1.58E-01 CO-58 26.90 2.3013-01 CO-60 3.07 2.6313-02 NI-59 17.86 1.53E-01 NI-63 3.97 3.40E-02 ZR-95 3.05 2.61E-02 NB-95 4.32 3.7013-02

c.

Irradiated components, control rods, etc.

Curies None

d.

Other Curies None

3.

Solid Waste Disposition Number of Shipments Mode of Transportation Destination 4

Flatbed/Sea Van Memphis, TN 4

Flatbed/Sea Van Oak Ridge, TN B.

Irradiated Fuel Shipments (Disposition)

Number of Shipments Mode of Transportation Destination None 43

9.

UNPLANNED RELEASES.

An unplanned release is defined as any release of radioactive material to the environment that does not meet the following criteria:

A.

Sample analysis prior to release, and B.

Release calculations performed prior to release.

During 2003, there were no unplanned releases to an unrestricted area.

10.

RADIATION INSTRUMENTATION As required by ODCM Appendices I and 2, any radioactive effluent instrumentation inoperable for more than 30 days shall be reported in the annual Radioactive Effluent Release Report.

On June 26, 2003, while performing the monthly Noble Gas Source Check surveillance on the Unit 1 Containment Purge SPING (SPING #1), the high range noble gas detector (channel 9) failed high prior to the introduction of the check source. A 30 day time clock was entered per the ODCM and a Condition Report (CR-ANO-1-2003-00686) and a Work Request (#4699) were issued to document and repair the condition. It was determined that the interface box between the SPING computer and the channel 9 detector had failed and needed to be replaced. A new interface box had to be ordered from an offsite vendor. On July 26 at 16:29 hrs the 30 day time clock expired. Condition Report CR-ANO-1-2003-00801 was issued to document the exceeded time clock. The new interface box was received onsite on August 21 and the SPING successfully repaired and the time clock exited on August 26, 2003.

It is important to note that the Unit I Containment Vent was secured during the time SPING 1 was out of service and no gaseous releases occurred via the

-Containment Vent during this period.

11.

CHANGES TO THE PROCESS CONTROL PROGRAM As required by ODCM Appendices I and 2, a description of changes made to the Process Control Program (PCP) shall be included in the annual Radioactive Effluent Release Report for the period in which the change was made effective.

Revision 1 of the Process Control Program (RW-105) was implemented on January 2, 2003.

The changes implemented under this revision were as follows:

1.

The procedure classification was changed from "Non-Quality" to "Quality".

2.

Section 5.4, "Administrative Controls", was revised to include the requirement that vendors performing radwaste services under 1 OCFR61 and IOCFR71 (Step 5.4.5) must be on the Entergy Qualified Suppliers List.

3. Section 8.0, "Requirements and Commitment Cross Reference", was updated to list correct section numbers.

There were no other changes made to the Process Control Program during 2003.

44

12.

CHANGES TO THE OFFSITE DOSE CALCULATION MANUAL In accordance with Unit I and Unit 2 TS, changes to the ODCM shall be included in the annual Radioactive Effluent Release Report for the period in which the change(s) was made effective.

There were no changes to the ODCM in 2003.

13.

LLD LEVELS In accordance with ODCM Appendices I and 2, lower limits of detection (LLDs) higher than required shall be documented in the annual Radioactive Effluent Release Report.

During 2003, there were no LLDs higher than required.

14.

RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM In accordance with ODCM Appendices 1 and 2 Limitations L2.6.1.A and L2.6.2.A, unavailability of milk or fresh, leafy vegetable samples, or an increase in an environmental sample location's calculated dose commitment must be identified in the annual Radioactive Effluent Release Report.

A. Changes in Sample Locations During 2003, there were no changes to milk or fresh leafy vegetable sample locations or instances where milk or fresh leafy vegetable samples were unavailable.

B. Increase in Calculated Dose Commitment There were no environmental sampling locations identified during 2003 that would yield a calculated dose commitment greater than the values currently being calculated.

15.

SUMMARY

OF HOURLY METEOROLOGICAL DATA In accordance with ODCM Appendices I and 2 Limitations L3.2.1.D.1, in lieu of including a summary of the meteorological data in this report, the 2003 data is retained at ANO. This data is available for NRC review.

16.

DESCRIPTION OF MAJOR CHANGES TO RADIOACTIVE WASTE SYSTEMS There were no major changes made to the Unit 1 liquid and gaseous or Unit 2 liquid and gaseous radwaste systems during 2003.

45

17.

INDEPENDENT SPENT FUEL STORAGE INSTALLATION (ISFSI)

EFFLUENT RELEASES No effluent releases occurred from the ISFSI during 2003.

46