ML040570665

From kanterella
Jump to navigation Jump to search
Informational Copy of Operating License & Appendices. Technical Specification Pages 1.1-1 Through 1.2-3 for Amendment 176
ML040570665
Person / Time
Site: Robinson 
Issue date: 02/18/2004
From:
Progress Energy Carolinas
To:
Office of Nuclear Reactor Regulation
References
Download: ML040570665 (9)


Text

Definitions 1.1 1.0 USE AND APPLICATION 1.1 Definitions NOTE------------------------------------.

The defined terms of this section appear in capitalized type and are applicable throughout these Technical Specifications and Bases.

-_--_--__-______I__-----------------------------------------------------------

Term Definition ACTIONS ACTIONS shall be that part of a Specification that prescribes Required Actions to be taken under designated Conditions within specified Completion Times.

ACTUATION LOGIC TEST An ACTUATION LOGIC TEST shall be the application of various simulated or actual input combinations in conjunction with each possible interlock logic state and the verification of the required logic output.

The ACTUATION LOGIC TEST, as a minimum, shall include a continuity check of output devices.

AXIAL FLUX DIFFERENCE MD)

AFD shall be the difference in normalized flux signals between the top and bottom halves of a two section excore neutron detector.

CHANNEL CALIBRATION A CHANNEL CALIBRATION shall be the adjustment, as necessary, of the channel so that it responds within the required range and accuracy to known input.

The CHANNEL CALIBRATION shall encompass the entire

channel, including the required
sensor, alarm, interlock,
display, and trip functions.

Calibration of instrument channels with resistance temperature detector (RTD) or thermocouple sensors may consist of an inplace qualitative assessment of sensor behavior and normal calibration of the remaining adjustable devices in the channel.

Whenever a sensing element is replaced, the next required CHANNEL CALIBRATION shall include an inplace cross calibration that compares the other sensing elements with the recently installed sensing element.

The CHANNEL CALIBRATION may be performed by means of any series of sequential, overlapping calibrations or total channel steps so that the entire channel is calibrated.

HBRSEP Unit No. 2 1.1-l (continued)

Amendment No. 176

Definitions 1.1 1.1 Definitions (continued)

CHANNEL CHECK A CHANNEL CHECK shall be the qualitative assessment, by observation, of channel behavior during operation.

This determination shall

include, where possible, comparison of the channel indication and status to other indications or status derived from independent instrument channels measuring the same parameter.

CHANNEL OPERATIONAL TEST (COT)

CORE ALTERATION CORE OPERATING LIMITS REPORT (COLR)

DOSE EQUIVALENT I-131 E-AVERAGE DISINTEGRATION ENERGY A COT shall be the injection of a simulated or actual signal into the channel as close to the sensor as practicable to verify the OPERABILITY of required

alarm, functions.

interlock,

display, and trip The COT shall include adjustments, as necessary, of the required
alarm, interlock, and trip setpoints so that the setpoints are within the required range and accuracy.

CORE ALTERATION shall be the movement of any fuel,

sources, or reactivity control components, within the reactor vessel with the vessel head removed and fuel in the vessel.

Suspension of CORE ALTERATIONS shall not preclude completion of movement of a component to a safe position.

The COLR is the unit specific document that provides cycle specific parameter limits for the current reload cycle.

These cycle specific parameter limits shall be determined for each reload cycle in accordance with Specification 5.6.5.

Plant operation within these limits is addressed in individual Specifications.

DOSE EQUIVALENT I-131 shall be that concentration of I-131 (microcuries/gram) that alone would produce the same thyroid dose as the quantity and isotopic mixture of I-131, I-132, I-133, I-134, and I-135 actually present.

The thyroid dose conversion factors used for this calculation shall be those listed in Regulatory Guide 1.109, Rev. 1, NRC, 1977.

E shall be the average (weighted in proportion to the concentration of each radionuclide in the reactor coolant at the time of sampling) of the sum of the average beta and gamma energies per disintegration (in MeV) for

isotopes, other than (continued)

HBRSEP Unit No. 2 1.1-2 Amendment No. 176

Definitions 1.1

.-c-r.

1.1 Definitions E-AVERAGE DISINTEGRATION ENERGY (continued)

LEAKAGE

iodines, with half lives

> 15 minutes, making up at least 95% of the total noniodine activity in the coolant.

LEAKAGE shall be:

a.

Identified LEAKAGE

1.

LEAKAGE, such as that from pump seals or valve packing (except reactor coolant pump (RCP) seal water injection or return),

that is captured and conducted to collection systems or a sump or collecting tank:

2.

LEAKAGE into the containment atmosphere from sources that are both specifically located and known either not to interfere with the operation of leakage detection systems or not to be pressure boundary LEAKAGE; or

3.

Reactor Coolant System (RCS) LEAKAGE through a steam generator (SG) to the Secondary System;

b.

Unidentified LEAKAGE All LEAKAGE (except RCP seal water injection or return) that is not identified LEAKAGE:

C.

Pressure Boundary LEAKAGE LEAKAGE (except SG LEAKAGE) through a

nonisolable fault in an RCS component body, pipe wall, or vessel wall.

MASTER RELAY TEST A MASTER RELAY TEST shall consist of energizing each master relay and verifying the OPERABILITY of each relay.

The MASTER RELAY TEST shall include a

MODE continuity check of each assoc A MODE shall correspond to any combination of core reactivity

level, average reactor coolant reactor vessel head closure bo ated slave relay.

one inclusive condition, power temperature, and t tensioning (continued)

HBRSEP Unit No. 2 1.1-3 Amendment No. 176

Definitions 1.1 1.1 Definitions MODE specified in Table 1.1-1 with fuel in the reactor (continued) vessel.

OPERABLE - OPERABILITY A system, subsystem,

train, component, or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified safety function(s) and when all necessary attendant instrumentation,
controls, normal or emergency electrical
power, cooling and seal water, lubrication, and other auxiliary equipment that are required for the system, subsystem,
train, component, or device to perform its specified safety function(s) are also capable of performing their related support function(s).

PHYSICS TESTS QUADRANT POWER TILT RATIO (QPTR)

RATED THERMAL POWER (R-W)

SHUTDOWN MARGIN (SDM)

PHYSICS TESTS shall be those tests performed to measure the fundamental nuclear characteristics of the reactor core and related instrumentation.

These tests are:

a.

Described in Chapter 14, Initial Test Program of the Updated Final Safety Analysis Report (UFSAR);

b.

Authorized under the provisions of 10 CFR 50.59; or

c.

Otherwise approved by the Nuclear Regulatory Commission.

QPTR shall be the ratio of the maximum upper excore detector calibrated output to the average of the upper excore detector calibrated

outputs, or the ratio of the maximum lower excore detector calibrated output to the average of the lower excore detector calibrated
outputs, whichever is greater.

RTP shall be a total reactor core heat transfer rate to the reactor coolant of 2339 MWt.

SDM shall be the instantaneous amount of reactivity by which the reactor is subcritical or would be subcritical from its present condition assuming:

(continued)

HBRSEP Unit No. 2 1.1-4 Amendment No. 196

Definitions 1.1

/--

1.1 Definitions SHUTDOWN MARGIN a

(continued) b SLAVE RELAY TEST STAGGERED TEST BASIS THERMAL POWER TRIP ACTUATING DEVICE OPERATIONAL TEST (TADOT)

All rod cluster control assemblies (RCCAs) are fully inserted except for the single RCCA of highest reactivity

worth, which is assumed to be fully withdrawn.

With any RCCA not capable of being fully

inserted, the reactivity worth of the RCCA must be accounted for in the determination of SDM: and In MODES 1 and 2, the fuel and moderator temperatures are changed to the 547F.

A SLAVE RELAY TEST shall consist of energizing each slave relay and verifying the OPERABILITY of each slave relay.

The SLAVE RELAY TEST shall

include, as a minimum, a continuity check of associated testable actuation devices.

A STAGGERED TEST BASIS shall consist of the testing of one of the systems, subsystems,

channels, or other designated components during the interval specified by the Surveillance Frequency, so that all
systems, subsystems,
channels, or other designated components are tested during n Surveillance Frequency intervals, where n is the total number of systems, subsystems,
channels, or other designated components in the associated function.

THERMAL POWER shall be the total reactor core heat transfer rate to the reactor coolant.

A TADOT shall consist of operating the trip actuating device and verifying the OPERABILITY of required

alarm, interlock,
display, and trip functions.

The TADOT shall include adjustment, as necessary, of the trip actuating device so that it actuates at the required setpoint within the required accuracy.

HBRSEP Unit No. 2 1.1-5 Amendment No. 176

Definitions 1.1 MODE Table 1.1-l (page 1 of 1)

MODES TITLE Power Operation Startup Hot Standby Hot Shutdown(b)

Cold Shutdown(b)

Refueling(c)

REACTIVITY CONDITION

( 44

> 0.99

> 0.99

< 0.99

< 0.99

< 0.99 NA

% RATED THERMAL POWER(a)

AVERAGE REACTOR COOLANT TEMPERATURE

("I3

>5 NA

<5 NA NA

> 350 NA 350 > Tavg > 200 NA

< 200 NA NA (a)

Excluding decay heat.

(b)

All reactor vessel head closure bolts fully tensioned.

(c)

One or more reactor vessel head closure bolts less than fully tensioned.

HBRSEP Unit No. 2 1.1-6 Amendment No. 176

Logical Connectors 1.2 1.0 USE AND APPLICATION 1.2 Logical Connectors PURPOSE The purpose of this section is to explain the meaning of logical connectors.

Logical connectors are used in Technical Specifications (TS) to discriminate

between, and yet connect, discrete Conditions, Required
Actions, Completion
Times, Surveillances, and Frequencies.

The only logical connectors that appear in TS are AND and QR.The physical arrangement of these connectors constitutes logical conventions with specific meanings.

BACKGROUND Several levels of logic may be used to state Required Actions.

These levels are identified by the placement (or nesting) of the logical connectors and by the number assigned to each Required Action.

The first level of logic is identified by the first digit of the number assigned to a Required Action and the placement of the logical connector in the first level of nesting (i.e.,

left justified with the number of the Required Action).

The successive levels of logic are identified by additional digits of the Required Action number and by successive indentations of the logical connectors.

When logical connectors are used to state a Condition.,

Completion Time, Surveillance, or Frequency, only the first level of logic is used, and the logical connector is left justified with the statement of the Condition, Completion Time, Surveillance, or Frequency.

HBRSEP Unit No. 2 (continued) 1.2-1 Amendment No. 176

Logical Connectors 1.2 1.2 Logical Connectors (continued)

EXAMPLES The following examples illustrate the use of logical connectors.

EXAMPLE 1.2-l ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

LCO not met.

A.1 Verify AND A.2 Restore In this example the logical connector AND is used to indicate that when in Condition A, both Required Actions A.1 and A.2 must be completed.

(continued)

HBRSEP Unit No. 2 1.2-2 Amendment No. 176

Logical Connectors 1.2 1.2 Logical Connectors EXAMPLES (continued)

EXAMPLE 1.2-2 ACTIONS CONDITION A.

LCO not met.

REQUIRED ACTION A.1 Trip OR A.2.1 Verify AND A.2.2.1 Reduce...

OR A.2.2.2 Perform OR A.3 Align COMPLETION TIME This example represents a more complicated use of logical connectors.

Required Actions A.l, A.2, and A.3 are alternative

choices, only one of which must be performed as indicated by the use of the logical connector QR and the left justified placement.

Any one of these three Actions may be chosen.

If A.2 is chosen, then both A.2.1 and A.2.2 must be performed as indicated by the logical connector AND.

Required Action A.2.2 is met by performing A.2.2.1 or A.2.2.2.

The indented position of the logical connector QR indicates that A.2.2.1 and A.2.2.2 are alternative

choices, only one of which must be performed.

HBRSEP Unit No. 2 1.2-3 Amendment No. 176