05000445/LER-2003-004, Regarding Condition Prohibited by Technical Specifications

From kanterella
(Redirected from ML033000104)
Jump to navigation Jump to search
Regarding Condition Prohibited by Technical Specifications
ML033000104
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 10/16/2003
From: Blevins M, Walker R
TXU Energy
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
10010, CPSES-200301986, TXX-03153 LER 03-004-00
Download: ML033000104 (11)


LER-2003-004, Regarding Condition Prohibited by Technical Specifications
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)
4452003004R00 - NRC Website

text

O TXU

- W14O.w TXU Energy Comanche Peak Steam Electric Station P.O. Box 1002 (EO1)

Glen Rose,TX 76043 Tel: 254 897 5209 Fax: 254 897 6652 mike.blevins@txu.com Mike Blevins Senior Vice President & Principal Nuclear Officer Ref: 10CFR50.73(a)(2)(i)(B)

CPSES-200301986 Log # TXX-03153 File#

10010 October 16, 2003 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 CONDITION PROHIBITED BY TECHNICAL SPECIFICATIONS LICENSEE EVENT REPORT 445/03-004-00 Gentlemen:

Enclosed is Licensee Event Report (LER) 03-004-00 for Comanche Peak Steam Electric Station Units 1 and 2, "Inadvertent Technical Specification 3.0.3 Entry due to Inoperable Control Room Air Conditioning System Trains."

This communication contains no new licensing basis commitments regarding CPSES Units 1 and 2.

I VTXU TXX-03 153 Page 2 of 2 Sincerely, TXU Generation Company LP By:

TXU Generation Management Company LLC, Its General Partner M. R. Blevins Senior Vice President and Principal Nuclear Officer By:

Regulatory Affairs Manager GLM/gm Enclosures c -

B. S. Mallett, Region IV W. D. Johnson, Region IV M. C. Thadani, NRR Resident Inspectors, CPSES

Enclosure to TXX-03153 NRC FORMI 366 US. NUCLEAR REGULATORY CONINIISSION APPROVED BY ONIB NO. 3150-104 (7-2001)~

EXPIRES 07/3112004 the NRC may not conduct or sponsor, and a person hoot requied to respond to. the Infornattn collection.

Facility Name (I)

Docket Number (2)

Page (3)

COMANCHE PEAK STEAM ELECTRIC STATION UNIT I 05000445 1 OF 9 Ttle (4)

CONDITION PROHIBITED BY TECHNICAL SPECIFICATIONS Event Date (5)

LER Nunmer (d Retn Date (7)

Other Facilties Involved ({)

Month Day Year Year equental Revision Month Day Year Faciliy Name Docket Numbers Numer i

Number 1 CPSES UNIT 2 05000446 08 20 03 03 004 00 10 16 03 05000 Operating Th report Ls submuted pursuant to the requ retments of 10 CFR: (teck alt that apply)

(I 11 Mode (9) 20.2201(b) 20.2203(a)(3)(i) l 50.73(a)(2Xi)(C) 50.73(a)(2)(vii)

PoLer 20.2201(d) 20.2203(a)(3)(ii)

=

S0.73(a)(2)(ii)(A) 50.73(a)(2)(viii)(A)

Leve 100) 20.2203(a)(1) 20.2203(a)(4) 50.73(a)(2)(ii)(B) 50.73(a)(2)(viii)(B) 20.2203(a)(2)(i) 50.36(c)(2Xi)(A) 50.73(a)(20iii) 50.73(a)(2)(ix)(A) 20.2203(a)(2)(ii) 50.36(c)(1)(iiXA) 50.73(a)(2XivXA) 50.72(a)(2)(x)

_ 20.2203(a)(2)(iii)

I 50.36(c)(2)

I 50.73(aM2WvXA) 73.71 (a)(4)

I 20.2203(a)(2)(iv) 50.46(aX3)(ii)

=

50.73(a')(2 vXB)

= 73.71 (a)(5) 20.2203(a)(2)(v) 50.73(a)(2)(iXA) 50.73(a){2)(v)(C)

OTHER 20.2203(a)(2)(vi)

X 50.73(a)(2)(iXB) 50.73(a){2XvXD)

Specify in Abstract below or in =

(If mare space is required use asditinal copies of SUMMARY OF THE EVENT, INCLUDING DATES AND APPROXIMATE TIMES The CPSES Control Room is common to both Units 1 and 2. There are two 50 percent capacity air conditioning units that make up a single Train of the Control Room Air Conditioning System [EIIS:(VI)]. All four Control Room Air Conditioning System (CRACS) units share common ductwork. CRACS units X-01 and X-02 comprise Train A and CRACS units X-03 and X-04 comprise Train B. Normal alignment for CRACS support systems is as follows:

Train A CRACS Unit and Supporting SSCs:

Unit 1 Train A CRACS unit X-01 Unit 1 Train A Diesel Generator Unit 1 Train A Component Cooling Water Unit 2 Train A CRACS unit X-02 Unit 2 Train A Diesel Generator Unit 2 Train A Component Cooling Water (If we spae is requd use addtonal copes of (If more space is required use akidgtnnailcopies of (If more space is requred. use idtinonal copies of (If nore space requred. use aditional copts of (If more space Is required, use addiLional copies of (If tnre space is requedw we additional copies of (if nore spaec is required use additional copies of NRC Form 366A) (17)

VI. PREVIOUS SIMILAR EVENTS

There have been no other previous similar reportable events during the last 3 years.

N~t It).> XO jl-ZWI)