ML032230455

From kanterella
Jump to navigation Jump to search
Draft Information Input, Attachment 20, E-Mailed on July 23, 2003 (50-368)
ML032230455
Person / Time
Site: Arkansas Nuclear 
(NPF-006)
Issue date: 07/23/2003
From: Alexion T
NRC/NRR/DLPM/LPD4
To: Miller D
Entergy Operations
Shared Package
ML032260096 List:
References
Download: ML032230455 (3)


Text

Iihomas~lexion__Spent Fuel Pool Loading Pattern RAI -Plant Systems Branch 1

Page 1 From:

To:

Date:

Subject:

Thomas Alexion MILLAR, DANA 7123103 3:02PM Spent Fuel Pool Loading Pattern RAI -Plant Systems Branch

Dana, See the attached RAI.

Tom

_LaeWINDOWS\\rEMoperties

-imp Mail Envelope Properties (3F1EDBB9.8B: :0: 20628)

LFej)

Subject:

Creation Date:

From:

Created By:

Spent Fuel Pool Loading Pattern RAI -Plant Systems Branch 7/23/03 3:02PM Thomas Alexion TWA@nrc.Rov Recipients entergy.com DMILLAR (MILLAR, DANA)

Action Date & Time Post Office Delivered Pending Route entergy.com Files Stubbs.wpd MESSAGE Options Auto Delete:

Expiration Date:

Notify Recipients:

Priority:

Reply Requested:

Return Notification:

Concealed

Subject:

Security:

To Be Delivered:

Status Tracking:

Size 8107 718 Date & Time 07/23/03 02:58PM 07/23/03 03:02PM No None Yes Standard No None No Standard Immediate Delivered & Opened

REQUEST FOR ADDITIONAL INFORMATION REGARDING PLANT SYSTEMS BRANCH AMENDMENT REQUEST TO REVISE THE SPENT FUEL POOL LOADING PATTERN ARKANSAS NUCLEAR ONE. UNIT 2 (ANO-2)

In the staff's safety evaluation for WCAP-15516-P, 'Westinghouse Spent Fuel Rack Criticality Analysis Methodology," the staff stated that all licensees proposing to credit soluble boron should identity potential events which could dilute the spent fuel pool soluble boron to the concentration required to maintain the 0.95 k-eff limit and should quantify the time span of these dilution events to show that sufficient time is available to enable adequate detection and suppression of any dilution event. The staff also stated that the effects of incomplete boron mixing, such as boron stratification, should be considered, and that the boron dilution analysis should also be used to justify the surveillance interval used for verification of technical specification minimum pool boron concentration. In order to complete our review, the NRC staff requests that the licensee provides the following information regarding Section 7.0, Soluble Boron Dilution Evaluation," of Attachment 5, of their application dated June 30, 2003:

1.

The fuel pool heat exchanger provides a boundary between unborated service water on the shell side and borated pool water on the tube side. The operation of the heat exchanger is such that the shell side is at a higher pressure than the tube side. In the event of a tube rupture In the spent fuel pool heat exchanger, unborated water can be introduced into the pool through the ruptured tube. Please describe how this event, and the potential dilution resulting from it, would be detected and mitigated. The response should include expected alarms and specific steps from alarm response or off-normal procedures that would lead to corrective actions.

2.

Section 9.1.2 of the ANO-2 Safety Analysis Report states that damage to the spent fuel pool floor resulting from light load drops would not cause a loss of coolant inventory in excess of the capacity of the normal makeup systems. Describe how this event and the potential dilution resulting from use of unborated makeup water sources would be detected and mitigated. The response should include expected alarms and specific steps from alarm response or off-normal procedures that would lead to corrective actions.

3.

Section 9.1.3 of the ANO-2 Safety Analysis Report states that service water makeup is piped to the pool, and the valves are located such that minimal operator action Is required to initiate makeup from either or both service water headers. Describe how the boron dilution resulting from both a slow, steady makeup of 8 gpm or makeup at the maximum rate from the source would be detected and mitigated. Again, this response should include expected alarms and specific steps from alarm response or off-normal procedures that would lead to corrective actions.