ML031820718
| ML031820718 | |
| Person / Time | |
|---|---|
| Site: | Farley (NPF-002, NPF-008) |
| Issue date: | 07/03/2003 |
| From: | Ernstes M Operator Licensing and Human Performance Branch |
| To: | Beasley J Southern Nuclear Operating Co |
| References | |
| 50-348/03-301, 50-364/03-301 50-348/03-301, 50-364/03-301 | |
| Download: ML031820718 (68) | |
See also: IR 05000348/2003301
Text
0. E. Grisselte
Southern Nuclear
General Manager
Operating Company, Inc.
Farley Nuclear Plant
Post Office Drawer 470
Ashford. Alabama 36312-0470
Tel 334.814.4511
Fax 334.814.4728
\\
SOUTHERN&
COMPANY
FNP-2003-0057-TRN
June 6,2003
Mr. Lee Miller
United States Nuclear Regulatory Commission
Region 11, Atlanta Federal Center
61 Forsyth St., Suite 23T85
Atlanta, GA 30303
Dear Mr. Miller:
Please find enclosed the question comments for the written examination administered at
Farley Nuclear Plant on May 30,2003, as required per NUREG 1021.
The completed examination security agreement, with the exception of the two people that
Gary Ohmstede discussed with you, is enclosed. These will be forwarded as soon as they are
received.
If you have any questions, please contact Joel Deavers at (334) 814-4853 or John Horn at
(334) 814-4652.
Sincerely,
Nu6ear Plant General Manager
Enclosure
JLD:mgr
cc:
B. D. McKinney
File
M I X DISK 5535
56. 075K1.01 001/2/2//MEM 2.5/2.5/NIFA03301/DR
Unit 1 is in the process of starting up and is currently at 25% power.
Unit 1 Circulating water pit level has dropped to 150 feet.
Which ONE of the following describes the process by which water is made up to the
Circulating Water Canal?
A. Service Water is automatically made up to the system via Circulating Water Makeup
Valve (560).
B. Service Water must be manually made up to the system via Circulating Water
Makeup Valve (560).
C. River Water is automatically made up to the system via Circulating Water Makeup
Valve (560).
D. River Water must be manually made up to the system via Circulating Water Makeup
Valve (560).
A - Incorrect; At this low power level the Circulating Water Makeup Valve (560) will be
controlled in "Remote Manual" not automatic.
B - Correct; Per OPS-52104D
C & D - Incorrect; Service water is the makeup supply to the Circ water canal, river
water is the makeup to the service water system.
Change to accept both the A and B answers as correct.
The stem of the question states that Unit 1 is starting up but does not state if the startup
is being conducted per UOP-1.2 or UOP-1.3.
UOP-1.2 States:
2.23 Circ water canal make up is being controlled manually with NlP16V748, C W
CANAL SW SUPP MANUAL ISO, or with QIP16V560 in Remote Manual per
appendix 1 of FNP-1-SOP-26.0.
UOP-1.3 has no initial conditions regarding the control of the canal makeup. It does
have a requirement to complete UOP-2.1, which states:
2.11 The Circulating Water Make-up Control Valve, QlP16V560, is in the OPEN
position, and canal level is being maintained by use of manual valve, QIP16V748,
Make-up Control Valve, QlP16V560, is in the AUTO position, and canal level is
being maintained by Remote operations per FNP-1-SOP-26.0, Appendix 1.
SOP-26.0 Appendix 1 allows the canal makeup valve to be in remote manual or in
automatic operation.
Answer A. Service Water is automatically made up to the system via Circulating Water
Makeup Valve (560),
is correct if the startup is done per UOP-1.3, because service
water may be automatically made up to the circulating water canal.
Answer B.
Service Water must be manually made up to the system via Circulating
Water Makeup Valve (560). is correct if the startup is conducted per UOP-1.2 because
service water is manually made up to the circulating water canal.
Answers C and D are both incorrect because the river water system does not connect to
the circulating water canal, but it does supply water to the service water pond.
01/28/03 10:43:56
FNP- 1 -UOP- 1.2
-
2.14
1
CHEM
-
2.15
1
-
2.16
-
2.17
1
-
2.18
-I-
-
2.19
-/-
-
2.20
1
-
2.21
1
2.22
-
-/-
-/-
-- 2.23
/
-
IF the Condensate and Feedwater System was placed in wet layup,
Chemistry has verified that the system's water chemistry is within specifications.
The settings on MCB Manual/Auto station potentiometers have been verified per
the Curve Book.
The control rod drive system is aligned for normal operation per
SYSTEM.
FNP-1-SOP-41.0, CONTROL ROD DRIVE AND POSITION INDICATION
Verify the wet layup recirc filtration system has been taken out of service.
Steam generator blowdown is established at maximum flow rate allowed by
TAVG consideration.
-
IF this procedure is being performed for an initial cycle startup following a
refueling, THEN the Technical Group has verified that the prerequisites and
initial conditions of FNP-1-STP-101, ZERO POWER REACTOR PHYSICS
TESTING, have been met. (SOER88-02)
A briefing has been performed by the Senior Line Manager of all involved
personnel. This briefing requires completion of the AP-92, BRIEFING
CHECKLIST FOR THE CONDUCT OF INFREQUENTLY PERFORMED
TESTS OR EVOLUTIONS. The completed briefing form should be attached to
this procedure for document tracking purposes.
The Power Range NIS High Flux Reactor Trip setpoint is reduced to less than
or equal to 85% Reactor Power. (Ref. OR 1-97-007, NEL 96-0451 and
CMT 10485)
Prior to rod withdrawal, verify the following items on the plant computer:
2.22.1
Page 2RS2: All rods at zero steps.
2.22.2
Page 2RS3: Correct ARO limit.
0, or with QlP16V560 in Remote Manual per
-3-
Version 62.0
~
03/12/03 11:26:36
FNP-1 -UOP-I .3
FAmEY NUCLEAR PLANT
UNIT 1
UNIT OPERATING PROCEDURE UOP-1.3
STARTUP OF UNIT FOLLOWING AN
AT POWER REACTOR TRIP
1.0
Purpose
This procedure provides the Initial Conditions, Precautions, Technical Specifications and
Instructions for startup of Unit within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> following a reactor trip. This procedure
has been identified as involving an infrequently performed test or evolution (IPTE)
requiring Senior Line Manager oversight. Periodic monitoring by the Senior Line
Manager is required at specified steps within the body of this procedure. The Operations
Manager, or his designee may perform all functions of the Senior Line Manager for
performance of this test. Per AP-92, the designee may be an Operations Superintendent
or an individual at the manager level, or higher.
1.1
The Shift Supervisor or Plant Operator shall initial for the completion of each step
and record the date and time in the space provided by the associated step.
Initials
Datemime
1.2
plant conditions preclude the performance of any step(s) in the Instructions
Section,
Supervisor.
Instruction steps noted by an asterisk (*) are operations that do not have to be
performed in the specified sequence.
those step(s) shall be marked NIA and initialed by the Shift
1.3
2.0
Initial Conditions
__ 2.1
The version of this procedure has been verified to be the current version and
correct unit for the task. (OR 1-98-498)
--
2.2
M LOAD TO HOT
I
__ 2.3
L
__ 2.4
RCS temperature is being controlled by steam dumps or SG Atmospheric Reliefs
and the auxiliary feedwater system is being used to maintain SG level.
Reactor startup is anticipated to be within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of reactor trip.
I
Page 1 of 29
Version 44.0
03/12/03 11:26:36
FNP-I-UOP-1.3
__ 2.5
RCS Zinc concentration is < 80 ppb.
CHEM
)NOTE:
IF Comtmter Services is unable to copy the data in step 2.6 AND Operations
I
I
Management approves, THEN the foilbwing step maybe marked N/A.
I
__ 2.6
1
-
2.7
1
__ 2.8
I
2.9
-
1
Computer Services has been notified to make a copy and store the unit trip
history to tape. This takes approximately 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> to accomplish and must be
completed before performance of step 5.10.11.
A briefing has been performed by the Senior Line Manager of all involved
personnel. This briefing requires completion of the AP-92, BRIEFING
CHECKLIST FOR THE CONDUCT OF INFREQUENTLY PERFORMED
TESTS OR EVOLUTIONS. The completed briefing form should be attached to
the Official Test Copy of this procedure for document tracking purposes.
The Power Range NIS High Flux Reactor Trip setpoint is reduced to less than or
equal to 85% Reactor Power. (Ref. OR 1-97-007, NEL 96-0451 and
CMT 10485)
Prior to rod withdrawal, verify the following on the plant computer:
2.9.1
Page 2RS2: All rods at zero steps.
2.9.2
Page 2RS3: Correct ARO limit.
-I-
3.0
Precautions and Limitations
3.1
3.2
3.3
3.4
3.5
Main Steam Line Drain Pots shall be unisolated prior to rolling the main turbine.
During reactor startup, at least two licensed reactor operators shall be present in
the control room.
Criticality shall be anticipated any time the shutdown or control rod banks are
being withdrawn or when dilution operations are in progress. {CMT 0007639)
All approaches to criticality shall be guided by an inverse count rate plot per
Appendix 2. {CMT 0007640)
All shutdown rods shall be fully withdrawn before the reactor is brought to
critical condition. {CMT 0008552)
Page 2 of 29
Version 44.0
01/03/03 11:56:12
FNP-1-SOP-26.0
APPENDIX 1
APPENDIX I
SW TO CW CANAL LCV, QlP16V560, OPERATION
1.0
MCB Switch Operation
1.1
Placing the QlP16V560 MCB switch from AUTO to OPEN.
NOTE:
Placing the QlP16V560 MCB switch to OPEN fails QlP16V560 to its open
I
position.
I
Drawing A-170059, Sheet 146, may be used as a reference.
I
1.1.1 When maintenance or plant conditions require, place the QlP16V560
MCB switch to OPEN.
1.1.2 Maintain CW canal level withNlP16V748, CW CANAL SW SUPP
MANUAL ISO.
1.2
Placing the QlP16V560 MCB switch from OPEN to AUTO.
NOTE:
With the QlP16V560 MCB switch in AUTO, QlP16V560 can be controlled
automatically or manually (pneumatically) on local control panel NlP16F501.
This is accomplished by having the local control panel NlP16VF501 mode
selector switch in AUTOMATIC or MANUAL. (respectively).
Ensure Chemistry personnel are available to operate the clarifier system.
1.2.1 VerifyNlPI9V943T, AIR SUPP TO CW MKUP LVL CONT
NlP16F501, is open.
1.2.2 Verify the local control panel NlP16F501 mode selector switch is in
MANUAL.
1.2.3 Using NlP16V748, CW CANAL SW SUPP MANUAL ISO, adjust the
CW canal level to be a few inches below the upper limit.
1.2.4 Using the black knob, adjust local control panel NlP16F501 MANUAL
LOADING PRESSURE gage reading to 3 pig.
1.2.5 Place the QlP16V560 MCB switch to AUTO.
1.2.6 Using the black knob on local control panel NlP16F501, adjust
MANUAL LOADING PRESSURE gage reading to 15 psig to obtain
minimum expected position of QlP16V560 during automatic operation.
Page 1 of 6
Version 3 1 .O
01/03/03 11:56:12
FNP-
1-SOP-26.0
APPENDIX 1
NOTE: In the following steps, NlP16V748 should be closed enough to keep the clarifier
supply transfer sump (wet pit) spilling a small amount of water into the CW canal,
but open enough to allow QlP16V560 to modulate within its expected band of
3-15 psig.
1.2.7 Have Chemistry perform the following.
1.2.7.1 If possible, have both clarifier pumps in operation.
1.2.7.2 Fully open NlP16V744, SW SOV TO CLAR SUPPLY PMP
VT' handle valve), to maximize SW to the supply transfer sump
(clarifier wet pit).
1.2.8 Adjust NlP16V748 so the clarifier wet pet is spilling a small amount of
water into the CW canal.
I
-
control of QlP16V560 may cause the SWEuiergency Recirc Valves to open. 11
1.2.9
1.2.10
1.2.1 I
1.2.12
1.2.13
Using the black h o b on local control panel NlP16F501, adjust
MANUAL LOADING PRESSURE gage reading to match the
INSTRUMENT LOADING PRESSURE gage reading.
Place the local control panel NlP16F501 mode selector switch to
AUTOMATIC.
Using the black knob on local control panel NlP16F501, adjust
MANUAL LOADING PRESSURE gage reading to zero.
Verify that the CW can
canal level and res
within its expected band.
Notify Chemistry to operate the clarifier system per procedure (maintain
NlP16V744 and clarifier pumps as required).
1.2.14 Initial Cooling Tower Blow Down Operation after QlP16V560 MCB switch is
taken from OPEN to AUTO.
1.2.14.1 When CTBD is initially put on service (e.g., following an outage
or first time after a ramp downhp & QlP16V560 MCB switch is
placed from OPEN to AUTO), observe the operation of
NlP16F501.
Page 2 of 6
Version 3 1 .O
01/03/03 11:56:12
FNP-1-SOP-26.0
APPENDIX 1
1.2.14.2 Adjust NlP16V588, CTBD FCV, as necessary to allow
NlP16F501 to maintain the CW canal level with a local control
panel NlP16F501 INSTRUMENT LOADING PRESSURE gage
reading of greater than 3 psig for the duration of the blow-down.
1.2.14.3 Inform Chemistry if an adjustment ofNlP16V588 is necessary.
I
2.0
Local Control Panel NlP16F501 Automatic or Remote Manual Operation.
2.1
Shifting from Automatic Control to Remote Manual Control of QlP16V560.
2.1.1 VerifyNIP19V943T, AIR SUPP TO CW MKUP LVL CON7
NlP16F501, is open.
Verify QlP16V560 MCB switch is in AUTO.
Verify local control panel NlP16F501 mode selector switch is in
AUTOMATIC.
2.1.2
2.1.3
NOTE:
A MANUAL LOADING PRESSURE reading of 3 psig should position
QlP16V560 at approximately 75% open, which provides valve maximum flow.
A MANUAL LOADING PRESSURE reading of 15 psig equates to QlP16V560
being 25% open, which allows approximately 2000 gpm flow to pass to ensure
proper clarifier system operation.
II
readin
II
I
controlof QIP16V560 may cause the SW Emergency Recirc Valves to open. 11
2.1.4 Using the black knob on local control panel NIP16FjOl. adjust
MANUAL LOADING PRESSURE gage reading to match the
INSTRUMENT LOADING PRESSURE gage reading.
Page 3 of 6
Version 31.0
01/03/03 11:56:12
FNP-1-SOP-26.0
APPENDIX 1
2.1.5
Place local control panel NlP16F501
de selector switch to MANUAL.
2.1.6
S
2.1.7
ired position with the local
NlP16F501 black knob.
2.2
Shifting from Remote Manual Control to Automatic Control of QlP16V560.
2.2.1 VerifyNlP19V943T AIR S W P TO CW
LVL CONTNlP16
open.
2.2.2 Verify QlP16V560 MC
2.2.3 Verify local control panel NlP16V501 mode selector switch is in MANUAL.
2.2.4
Verify controller NlP16F501 indicates a supply air pressure of- 20 psig.
2.2.5 Using the black knob on local control panel NlP16F501, adjust
MANUAL LOADING PRESSURE gage reading to match the
INSTRUMENT LOADING PRESSURE! gage reading.
2.2.6 Place local control panel NlP16F501 mode selector switch to
AUTOMATIC.
2.2.7 Using the black knob on local control panel NlP16F501, adjust
MANUAL LOADING PRESSURE gage reading to zero.
ic by observing
2.2.8
3.0
Manual Jacking Operation with the Actuator Handwheel
Page 4 of 6
Version 31.0
01/03/03 11:56:12
CAUTION:
WHEN manually jacking QlP16V560 closed,
approximately 25% open due to mechanical blocks that are internal to the
actuator.
it cau only be positioned
CAUTION:
W H E N manually jacking Q1P16V560 open, THEN for design considerations
only position the valve to a maximum Of 75% open as indicated on the
circular dial on the actuatorm thc indication marked on the stem. Use
caution because the valve can be positioned to greater that 75% open by
backing out the actuator handwheel too far.
-
FNP-1-SOP-26.0
APPENDIX 1
TOTE: 0
Prior to jacking QlP16V560 with the handwheel on the actuator, loosen the
locking nut on the actuator stem.
After jacking QlP16V560 to the desired position, tighten the locking nut on
the actuator stem.
The wrench size needed for the actuator locking nut is 1% inches.
The actuator stem for the handwheel and locking nut has left handed threads;
therefore, when looking down on the actuator and handwheel, turning the
handwheel counter clockwise closes QlP16V560 and turning the locking nut
counter clockwise will tighten the locking nut.
0
0
3.1
Placing QlP16V560 On the Actuator Handwheel Jack
3.1.1 Place the QlP16V560 MCB switch to OPEN.
3.1.2
In the valve box, verify that QlP16V560 has failed to its fully open
position (approximately 75%
indication marked on the stem).
3.1.3
Close NlP19V152C, IA to QlP16V560.
3.1.4 Manually jack QlP16V560 to its desired position.
3.2
Taking QlP16V560 Offthe Actuator Handwheel Jack
3.2.1
Check the QlP16V560 MCB switch in OPEN.
3.2.2
At local control panel NlP16F501, verify the mode selector switch is in
MANUAL.
3.2.3 Using the black knob, adjust local control panel NlP16F501 MANUAL
LOADING PRESSURE gage reading to 3 psig.
Page 5 of 6
Version 31.0
01/03/03 11:56:12
FNP-1-SOP-26.0
APPFNnlX 1
l ( c A ~ T ~ N ~ S t e p s
3.2.4 through 3.2.8 should be performed expeditiously to ensure CW
cnnal level is maintained at tbe Droner level.
3.2.4 Manually jack QlP16V560 to the fully open position (approximately 75%
-
OR indication marked on the stem).
OpenNlP19V152C, IA to QlP16V560, and observe -80 psig k 5 psig on
N1P 16PI560C.
3.2.6
Place QlP16V560 MCB switch in AUTO.
3.2.5
NOTE:
3 PSI = 75% open and 15 PSI = 25% open.
I
3.2.7 Place QlP16V560 to desired position to control CW canal level with local
control panel NlP16F501 black knob.
3.2.8
desired to place QlP16V560 in automatic control, THEN proceed to
section 2.2 of this appendix.
Page 6 of 6
Version 3 1 .O
63. G2.1.22 00 1/3/iMODE/C/A 2.8/3.3iNiFA03301WSDR
Which ONE of the following Mode changes requires at least two (2) mode determination
parameters to change?
(Mode determination parameters are Reactivity Condition (Keff), Rated Thermal Power,
Average Coolant Temperature).
A. Going from Mode 1 to Mode 2.
B. Going from Mode 5 to Mode 4
C. Going from Mode 3 to Mode 2.
D. Going from Mode 5 to Mode 6.
Reference Technical Specification Definitions Table 1.1-1.
Distractor Analysis:
A: Incorrect, Difference between Mode 1 and Mode 2 requires only % Rated Thermal
Power to change.
B: Incorrect, Difference between Mode 5 and Mode 4 requires only Average Coolant
Temperature to change.
C: Incorrect, Difference between Mode 3 and Mode 2 requires only Reactivity Condition
(Keff), to change.
D: Correct, Difference between Mode 5 and Mode 6 requires both Reactivity Condition
(Keff), and Average Coolant Temperature to change.
This question should be deleted due to no correct answer.
A. This answer is incorrect for reasons stated above.
B. This answer is incorrect for reasons stated above.
C. This answer is incorrect for reasons stated above.
D. Incorrect, the Mode change parameters are Keff, Temp and power. Power is not
required to be changed. Temperature is not required to change to enter mode 6
either by tech specs or plant procedure. Temperature is required to be at 140°F for
fuel movement but not to detension the reactor head. Mode 6 is defined by the table
as the reactor vessel head less than fully tensioned. RCS boron is required to be at
2000 ppm prior to entering Mode 6 but is not listed in the stem as a mode change
parameter. This specification does not require a specific change to Keff for Mode 6
entry, only minimum RCS boron concentration that could also be met in Mode 5.
See table below from Tech Specs.
Table 1.1-1 (page 1 of 1)
MODES
MODE I
TITLE
1
Power Operation
2
Startup
3
Hot Standby
Hot Shutdown(b)
5
Cold Shutdown@)
6
Refueling(c)
REACTIVITY
CONDITION
(keff)
2 0.99
2 0.99
< 0.99
< 0.99
< 0.99
NA
Yo RATED
THERMAL
POWER(a)
> 5
5 5
NA
NA
NA
NA
AVERAGE
TEMPERATURE
(" F)
NA
NA
t 350
350 > Taus > 200
5 200
NA
(a)
Excluding decay heat.
(b)
(c)
All reactor vessel head closure bolts fully tensioned.
One or more reactor vessel head closure bolts less than fully tensioned
03/12/03 11:26:57
FNP-1-UOP-4.1
FARLEY NUCLEAR PLANT
UNIT 1
UNIT OPERATING PROCEDURE UOP-4.1
CONTROLLING PROCEDURE FOR REFUELING
1.0
Purpose
This procedure provides the Initial Conditions, Precautions, Limitations and Instructions
for refueling the reactor in a safe manner.
NOTE:
At the completion of each step, a person from the designated group, the SRO in
charge of fuel handling , a Plant Operator, the Shift Support Supervisor or the
Shift Supervisor shall initial
by the associated step as follows:
record the date and time in the space provided
Initials
DatefI'ime
Only the Shift Supervisor, the SRO in charge of fuel handling, or a person from
the designated group (with Shift Supervisor concurrence) may mark a step N/A
if it is not to be performed. Steps marked N/A shall be justified and approved by
the Shift Supervisor in accordance with the requirements of FNP-0-AP-6,
PROCEDURE ADHERENCE.
2.0
Initial Conditions
NOTE:
Initial Condition 2.29 must be completed prior to lowering RCS water level to
the vessel flange (step 4.1.9).
Initial Condition 2.7 must be completed prior to Mode 6 (Step 4.1.12).
I
Initial Conditions 2.22 and 2.23 must be completed prior to Reactor Vessel Head
lift (Step 4.1.20 or 4.1.26).
Initial Conditions 2.12,2.17,2.18,2.25, and 2.28 must be completed prior to
flood up (Step 4.1.29).
Initial Conditions 2.9,2.13.3,2.13.4,2.19,2.22,2.27, and 2.28 must be completed
prior to rod unlatching (Step 4.1.30) and upper internals lift (Step 4.1.32).
All Initial Conditions must be completed prior to fuel assembly movement
(Step 4.1.35).
Date/Time
__ 2.1
L
correct unit. (OR 1-98-498)
The version of this procedure has been verified to be the current version and
-1-
Version 24.0
03/12/03 11:26:57
FNP-1-UOP-4.1
DateITime
-
2.2
L
-
2.3
1
A Fuel Assembly Transfer Form or an approved Westinghouse Refueling
procedure with a fuel transfer form has been issued.
A full core offload is specified by the Fuel Assembly Transfer Form or approved
Westinghouse refueling procedure with a fuel transfer form.
is NOT to be performed, THEN initial condition 2.3.1 must be met.
-
2.3.1
a fuel shuffle is being performed,
specific guidance on
1
intermediate fuel locations has been incorporated into the refueling
sequence.
NOTE:
The guidance for intermediate fuel locations is stated in section 3.17 of
FUEL ASSEMBLIES. This guidance only applies to full core offloads. For a
fuel shuffle, additional guidance would have to be developed and incorporated in
the refueling sequence.
FNP-0-FW-7.0, LIMITATIONS AND PRECAUTIONS FOR HANDLING
__ 2.4
1
RF
coordinator
-
1
Component Movement section.)
WEST
__ 2.5
-/-
RF
coordinator
The refueling procedure contains guidance for intermediate fuel locations,
temporary storage of fuel assemblies and all appropriate refueling personnel
including Westinghouse personnel have been trained on this guidance and the
potential consequences of violating this guidance.
(Refer to Westinghouse refueling procedure, Fuel Assembly and Core Compound
The refueling procedure contains the following guidance to prevent
misalignments and subsequent abnormal gaps. Document performance of steps
2.5. I thru 2.5.5 by initialing step 2.5.
-
1
WEST
-/-
-
I
2.5.1
Load no more than one-half of a row in the same direction, to the
extent practicable. Exceptions may be granted by PRl3 approval of the
Refieling Procedure.
When completing rows (Le., loading the last assembly in a row,
adjacent to the baffle), complete the third row out from the baMe first,
the second row out from the baffle next, and the baffle row last.
2.5.2
-2-
Version 24.0
03/12/03 11:26:57
FNP-I-UOP-4.1
2.5.3
Inspect for non-uniformity or substantial misalignment after each fuel
assembly is seated, and for assemblies locked out of alignment by the
mechanical interaction of crossing rows of assemblies.
Inspect all assembly-to-assembly gaps, assembly-to-baffle gaps, and
all top nozzle comer-to-comer junctions during core verification.
If misalignments exist, determine the source of the misalignment.
Using normal fuel handling procedures, remove designated assemblies
and reseat them in the core as appropriate. Reinspect all gaps and
misalignments that may have been changed by reseating assemblies.
2.5.4
2.5.5
Perform F"-1-STP-13.0, REACTOR DECAY TIME, to verify reactor has been
subcritical for at least 140 hours0.00162 days <br />0.0389 hours <br />2.314815e-4 weeks <br />5.327e-5 months <br />.
in the last 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> per SR 3.9.1.1 prior to the start of head stud detensioning.
Deleted
The containment building penetrations are in the following status within 100
hours prior to the start of core alterations.
2.9.1
The equipment door closed and held in place by a minimum four bolts.
2.9.2
A minimum of one door in each air lock is closed.
2.9.3
Each penetration providing direct access from the containment
atmosphere (except pens 71,72,90, and 92 which are addressed in
step 2.9.4) shall be either closed by an isolation valve, blind flange or
manual valve per FNP-1-STP-18.4, CONTAINMENT MID-LOOP
AND/OR REFUELING INTEGRITY VERIFICATION AND
CONTAINMENT CLOSURE,
operable automatic containment purge and exhaust isolation valve as
tested per FNP-1-STP-18.1, CONTAINMENT PURGE AND
EXHAUST ISOLATION TEST MODES 5 & 6.
capable of being closed by an
-3-
Version 24.0
03/12/03 11:26:57
FNP-1-UOP-4.1
NOTE:
Water or air lines which penetrate through the adapter nozzles must be
pressurized or isolated with their individual isolation valves.
I
-
1
2.9.4
Blind flanges are installed at CTMT penetrations 71, 72, 90, and 92,
-
OR the special adapter nozzles for these penetrations are installed.
-
2.9.5
FNP-1-STP-18.4, CONTAINMENT MIDLOOP AND/OR
-I-
REFUELING INTEGRITY VERIFICATION AND CONTAINMENT
CLOSURE, has been reviewed and verified to satisfy refueling
integrity.
A caution sign concerning the establishment of containment integrity
has been posted in the following locations:
2.9.6
I NOTE:
The signs can be obtained from the Shift Support Supervisor and are normally I
I
_ _
storedin the Unit 2 CCW Storage Room.
-
I
2.9.6.1
Personnel Access Hatch
2.9.6.2
Auxiliaty Access Hatch
2.9.6.3
139' Electrical Penetration Room
2.9.6.4
121' Piping Penetration Room
2.9.6.5
100' Piping Penetration Room
2.9.6.6
Main Steam Valve Room (both entrances)
-4-
Version 24.0
03/12/03 11:26:57
FNP-1-UOP-4.1
2.10
Deleted
NOTE:
a One SFP cooling loop is required to be in service and the purification loop
should be maintained in service as much as possible. The skimmer loop may
be used as desired for surface cleanup.
The Tri Nuclear Filter System may be considered as a purification loop for
the purposes of the following initial condition.
The spent fuel pool cooling and purification system is aligned and in operation
with at least one cooling and purification loop in service per FNP-1-SOP-54.0,
SPENT FUEL PIT COOLING AND PURIFICATION SYSTEM or
FILTER SYSTEM. The skimmer loop may be used as desired.
The RCS has been purified to meet the requirements of FNP-0-CCP-202,
WATER CHEMISTRY SPECIFICATIONS, and FNP-1-CCP-203, CHEMISTRY
AND ENVIRONMENTAL GROUP CONSIDERATIONS DURING
OPERATIONAL TRANSIENTS before mixing with the RWST; and other
chemistry is within limits or as specified by the Chemistry Supervisor.
The following radiation monitors are in operation per FNP-1-SOP-45.0,
RADIATION MONITORING SYSTEM, or required action is being taken per
Tech. Specs 3.3.6,3.3.7, and 3.3.8, and TR 13.3.4.
2.13.1
__ 2.1 1
-
/
FNP-0-SOP-54.3, SPENT FUEL POOL CLEANUP USING TRI NUCLEAR
-
2.12
-
I
CHEM
2.13
-
-
/
R-5 Spent fuel pool or portable monitoring instrumentation used
to monitor SFP area at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
R-25A or B Spent fuel pool - Gaseous
2.13.2
-
-
I
in operation.
__
2.13.4
R-35A or B - Control Room HVAC.
2.13.3
R-24A or B - Containment purge system with main or mini purge
I -
-
2.14
-
/
The fuel handling area W A C is in operation per FNP-1-SOP-58.0,
AUXILIARY BUILDING HVAC SYSTEM.
-5-
Version 24.0
03/12/03 11:26:57
FNP-1-UOP-4.1
The direct communications system between the below listed stations is
verified available for use within one hour prior to fuel movement.
2.15.1
Control Room
2.15.2
Manipulator Crane
2.15.3
2.15.4
Spent fuel pool side fuel transfer system control panel.
Reactor side fuel transfer system control panel.
Fuel assembly status board is available in the control room.
The manipulator crane gripper has been load tested within 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br /> prior to
movement of fuel assemblies per FNP-1-STP-36.0, MANIPULATOR CRANE
CUTOFF AND LOAD TEST. (Required prior to Cavity flood up, OLL 1848)
The manipulator crane auxiliary hoist has been load tested within 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br /> of
movement of control rods per FNP-1-STP-36.0, MANIPULATOR CRANE
CUTOFF AND LOAD TEST. (Required prior to Cavity flood up, OLL 1848)
The Reactor Cavity water level is 2 1422 ( 2 23 feet over the top of the
irradiated fuel assemblies seated in the core) within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> prior to movement of
control rods within the reactor pressure vessel.
The Spent Fuel Pool water level is 2 15 16 ( 2 23 feet over the top of irradiated
fuel assemblies seated in the storage racks).
Two independent penetration room filtration systems are verified aligned to the
spent fuel pool room prior to fuel handling or crane operations in the spent fuel
storage room per FNP-I -STP-20.1, PENETRATION ROOM FILTRATION
ALIGNMENT VERIFICATION. Otherwise, comply with actions of Tech Spec 3.7.12.
The direct communications system between the control room and the
reactor cavity is verified available for use within one hour prior to latching or
unlatching control rods OR installing or removing upper internals.
-6-
Version 24.0
03/12/03 11:26:57
FNP-1 -UOP-4.1
__ 2.23
The Controlled Refueling Area Boundary (CRAB) has been established as
appropriate per FNP-0-ACP-7.0, FOREIGN MATERIAL EXCLUSION
PROGRAM.
2.24
Deleted
__ 2.25
Verify life ring is available at cavity area prior to flooding cavity.
I
__ 2.26
-
/
Ensure vital shared equipment is aligned to Unit 2 as follows:
-
IF the outage will involve reducing the availability of offsite power to the IF or
1 G 4 160V buses,
place or verify the following loads on Unit 2 per FNP-1-
SOP-36.3,600,480 and 208/120 VOLT AC ELECT DISTRIBUTION SYSTEM:
2.27
Verify at least two of the required source range neutron flux monitors are
operable with continuous visual indication in the Control Room and a channel
check performed within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> prior to any core alterations. Trip functions and
associated TSLBs are not required for Mode 6 or core alterations.
2.27.1 Source Range Nuclear Instrument, Channel N-31
2.27.2 Source Range Nuclear Instrument, Channel N-32
2.27.3 Gamma-Metrics Neutron Flux Monitor, Channel N-48
NOTE:
The Scaler-Timer may be verified to be operating properly by performing an
operational check per SOP-39.0. If performed, then ensure it is restored to a
normal alignment.
-1-
Version 24.0
03/12/03 11:26:57
FNP-1-UOP-4.1
-
2.28
At least one source range nuclear instrument charnel N-3 1 or N-32, has an
audible count rate in the control room or in containment using a stationed licensed
operator who will communicate with control room if required to alert them of a
possible dilution accident.
NOTE:
Step 2.9 may be performed at the same time as step 2.29.
I
2.29
Prior to lowering the reactor coolant water level to the vessel head flange
following reactor shutdown, perform the following:
-
2.29.1
Perform a containment integrity assessment for Mid-Loop integrity
and
maintain the assessment current per one of the following methods.
2.29.1.1
Perform Mid-Loop Integrity assessment for Mid-Loop
integrity per FNP-1-STP-18.4, CONTAINMENT IWD-
LOOP AND/OR REFUELING INTEGRITY
VERIFICATION AND CONTAINMENT CLOSURE.
2.29.1.2
For the initial draindown to the vessel head flange
following reactor shutdown an assessment may be
performed based on maintenance released which could
potentially impact midloop integrity. To maintain a valid
assessment administrative controls (LCO tracking sheet)
will be maintained to ensure the assessment is revised to
reflect any changes to the penetrations subsequent to the
performance of the assessment.
-
2.29.2
A Maintenance Closure Response Team (MCRT) is staffed and
briefed
with sufficient personnel, having the necessary tools and procedures
staged, to facilitate rapid closure of the CTMT Equipment Hatch. This
crew is normally staffed by the maintenance crew assigned to reactor
disassembly. The MCRT Leader is identified to the MCR staff to
ensure rapid notification if a loss of RHR event were to occur.
2
MM
NOTE:
Appendix 3 is meant to be a guide and can be changed by the Outage Manager I
~
-
-
I
depending on special plant conditions.
I
-
2
the Outage Manager.
2.29.3
Appendix 3 has been approved and appropriately distributed by
-8.
Version 24.0
03/12/03 11:26:57
.i^
FNP-1-UOP-4. I
-
L
2.29.4
A briefing has been performed by the Senior Line Manager of all
involved personnel. This briefing requires completion of the AP-92,
BRIEFING CHECKLIST FOR THE CONDUCT OF
INFREQUENTLY PERFORMED TESTS OR EVOLUTIONS. The
completed briefing form should be attached to this procedure for
document tracking purposes. Draining to the vessel flange (1297) or
mid plane (1233 to 1235) will be designated an IPTE and require
Senior Line Manager Oversight. (IN-97-83)
__ 2.30
RCS temperature < 140°F.
-/-
__ 2.31
-I-
RF
coordinator
3.0
Precautions and Limitations
Training has been completed on recent refueling equipment design changes
for the appropriate personnel. (Commitment 94- 13-01)
3.1
At least two source range neutron flux monitors shall be operating, each with
continuous visual indication in the control room
one channel of audible
count rate in the control room or in containment using a stationed licensed
operator that will communicate with control room if required to alert them of a
possible dilution accident.
The Gamma-Metrics source range channel may only be used as a back-up to N-31
or N-32 during certain core configurations. The Refueling Coordinator or
Westinghouse should be consulted if N-3 1 or N-32 becomes inoperable when the
core is not fully loaded.
The High Flux at Shutdown alarm serves as an additional monitor of neutron flux
during stable flux conditions. During core reload, continually changing neutron
flux is being closely monitored by performance of a 1/M plot. The High Flux at
Shutdown alarm may be placed in the BLOCK position to prevent spurious
alarms in containment.
3.2
3.3
3.4
the High Flux at Shutdown alarm is actuated,
all personnel will
evacuate the containment in an orderly manner. @the alarm is actuated during
movement of fuel, =return
the he1 to the position it occupied prior to the
alarm before evacuating the containment.
-9-
Version 24.0
Definitions
1.1
Table 1.1-1 (page 1 of 1)
MODES
TITLE I
1
Power Operation
2
Startup
3
Hotstandby
Hot Shutdown(b)
Cold Shutdowdb)
6
Refuelin&
REACTIVITY
CONDITION
(Ihd
2 0.99
2 0.99
< 0.99
< 0.99
< 0.99
NA
% FMTED
THERMAL
POWER(^)
> 5
s 5
NA
NA
NA
NA
AVERAGE
TEMPERATURE
(" F)
NA
NA
2 350
350 >Taw > 200
5 200
NA
(a)
Excluding decay heat
(b)
c)
All reactor vessel head closure bolts fully tensioned.
One or more reactor vessel head closure b l t s less than fully tensioned.
Farley Units 1 and 2
1.1-7
Amendment No. 146 (Unit 1)
Amendment No. 137 (Unit 2)
Boron Concentration
3.9.1
SURVEILLANCE
Verify boron concentration is wlthln the limit specified
In COLR.
3.9 REFUELING OPERATIONS
3.9.1 Boron Concentration
FREQUENCY
72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />
-co 3.9 1
Boron concentrattons of the Reactor Coolant Svstem. the relbelina canal
and the refuellnq caVltv shall be malntalned within the Ilm t specified in the
COLR.
APPLICABILITY:
MODE 6,
ACTIONS
Suspend CORE
within limit.
ALTERATIONS.
Suspend positive
reactivity additions.
Initiate action to restore
boron concentration to
within limit.
COMPLETION TIME
Immediately
Immediately
immediately
Fariey Units 1 and 2
3.9.1-135
Amendment No. 146 (Unit 1)
Amendment No. 137 (Unit 2)
\\
L.
2.7
CORE OPERATING LIMlTS REPORT, FNP UNIT 1 CYCLE 18, REV. ZDECEMBER 2001
I
Nuclenr Enthalov Rise Hot Channel Factor - FL, (Specification 3.2.2)
2.7.1
F:,
<Fr%(l+PFM*(l-P))
THERMAL POWER
RATED THERMAL POWER
where:
P =
2.7.2
F
r
= 1.70
2.7.3
PF,, = 0.3
Axial Flux Difference (Specification 3.2.3)
2.8.1
2.8
The Axial Flux Difference (AFD) acceptable operation limits are provided in Figure 3
2.9
Boron Concentration (Specification 3.9.1)
2.9. I
QLLcior Core Safetv Limits for THERMAL POWER (Specification 2.1.1)
1. IO. I
The boron concentration shall he gve.?rer &?E cr eqnz! tz 2%
pi.%.'
2.10
In MODES 1 and 2, the combination of THERMAL POWER, Reactor Coolant System
t KCS I hi~hest loop average temperature, and pressurizer pressure shall not exceed the safety
limit% spccified in Figure 8.
2.1 I
Kc:~ior Trip Sy\\tvni l~tgtrumentation Overtemperature AT (OTATI and Ovemower AT(0PAT)
'ieiixuni 1';s:tnkwr V:ilues for Table 3.3.1-1 (Specification 3.3.1)
2. I I. I Thc Kcacior Trip System Instrumentation Oveltemperature AT (OTATJ and Overpower AT
IIWJI~
,Scipoin~ Pmamerer Values for TS Table 3.3.1-1 are listed in COLR Tables 2 and 3.
2.12
KCS I)NH I':ir;imc!cr\\ lor.Prrssurizer Pressure, RCS Average Temoerature, and RCS Total Flow
K;w 1Spl.cili<:ttwn 3.4.1 )
2. 12, I KC'S I)NU Pwnniems for Pressurizer Pressure, RCS Average Temperature, and RCS Total
Fhw K : w ~liiill
he within the limits specified below:
- ,.
h.
c.
I'rcwurizer pressure 2 2209 psig;
KCS :ivcmgc temperature 5 S80.3"F; and
The minimum RCS total flow rate shall be 2 263,400 GPM when using the precision
bent halancu method and 2 264.200 GPM when using the elbow tap method.
'
This concentration hounds die condition of 14~5
0.95 (:ill rods in less the most reactive rod) and
subcriticality
rods out) over the entire cycle, This concentration includes additional boron to
address uncertainties and B"' deoletion.
Page 4 of 15
71. WlE03EK3.4 001 I1 12llMEM 3.513.9lBIFA03301lRDR
A failed open spray valve that could not be shut resulted in a safety injection. The
reactor coolant pump in the affected loop was tripped and, with pressurizer pressure
now under control, safety injection termination was permitted. With only one charging
pump running, pressurizer pressure remained stable.
At the procedural step when normal charging was established, PFZR level started
trending down from 15% level and could not be controlled.
Which ONE of the following describes the actions the operator should take at this point?
A. Manually SI and recommend transitioning to EEP-0, Reactor Trip or Safety Injection.
B. Realign HHSl flow; start additional charging pumps, and recommend transitioning to
EEP-0, Reactor Trip or Safety Injection.
C. Realign HHSl flow, start additional charging pumps, and recommend transitioning to
EEP-1, Loss of Reactor or Secondary Coolant.
D. Realign HHSl flow; start additional charging pumps, and recommend transitioning to
ESP-I .2, Post LOCA Cooldown and Depressurization.
Source: Farley Exam Bank Question #ESP-I .I-52531 E06 005
References: ESP-I .I
A - Incorrect; If PZR level can not be maintained, the flow path must be reestablished
and a transition to ESP-I .2 is warranted. There is no need to manually SI and transition
to EEP-0.
B - Incorrect; the transition to EEP-0 is incorrect.
C - Incorrect: the transition to EEP-1 is incorrect,
D - Correct; From ESP-I. 1, SI Termination, if PZR level can not be maintained, the flow
path must be reestablished and a transition to ESP-1.2 is warranted.
There are two correct answers to this question:
D.
Realign HHSl flow; start additional charging pumps, and recommend
transitioning to ESP-I .2, Post LOCA Cool-down and Depressurization.
This was the examination key answer based on the fact that the SS may wait on
the OATC to regain flow to the PZR to restore PZR level. If the candidate assumes that
they establish normal charging at that moment and waits on the step to be completed,
then they would see the PZR level dropping and would attempt to recover by raising
charging flow. In this case they would utilize the RNO column of ESP-1.1, step 10.2.3
to deal with the problem and go to ESP-1.2, or the team could use ESP-0.0,
REDIAGNOSIS to get to EEP-1. Either way would be acceptable.
the procedure, are: This procedure is entered based on Operator judgment.
The purpose as designated in ESP 0.0: This procedure provides a mechanism to allow
the operator to determine or confirm the most appropriate post accident recovery
procedure with SI in progress or required.
The Symptoms or Entry Conditions of ESP-0.0, REDIAGNOSIS, as stated in
The key word in the stem is Should, (Le., the actions the operator should take)
at this point. There are several flow paths that could be taken and should is subjective,
not a mandatory. This leaves the operator to take what he thinks is the best course of
action, which in this case, not knowing what the event is, may be to go to a procedure
(ESP-0.0, REDIAGNOSIS) that will lead you to either EEP-2, EEP-3, EEP-1 and then
to ESP-1.2 or some other contingency procedure as needed.
Answer C is also a correct answer that describes actions the operator could take.
C. Realign HHSl flow, start additional charging pumps, and recommend transitioning to
EEP-1, Loss of Reactor or Secondary Coolant.
With a failed open spray valve the RCP is required to be secured. Indications
following the reactor trip and safety injection are normal through the diagnostics of EEP-
0 and the subsequent steps of ESP-I .I,
SI termination. The stem of the question
indicates the team is at step 10.2.3 which says, Establish charging flow to maintain
pressurizer level 15-50%. The team would be in the process of accomplishing this task
as the SS continues on. In SOP-0.8 the definition of Establish is, To make
arrangements for a stated condition. Example: Establish normal charging. Establish is
also not listed as a Continuing Action word.
The team is still continuing through ESP-I .I
and after step 11 which secures
RHR, the team enters step 12 which has the operator check pressurizer level
GREATER THAN 7%. The stem says the operator cannot control PZR level at this
point.
There are no radiation alarms, containment moisture alarms or containment
sump problems. The team has no indications of anything going on other than PZR level
dropping. The operator would have two options at this point:
1 . Assume the PZR level cannot be restored and is trending to 7%, use the
RNO column to re-establish HHSI flow and then transition to EEP-1 per step
12.2 RNO
2. Due to the unexplained loss of level and needing an SI and a procedural flow
path, enter REDIAGNOSIS, ESP-0.0, based on Operator judgment, which
would lead you to EEP-1.
A simulator examination scenario was utilized for this class that recognized
REDIAGNOSIS as a viable option under similar conditions. This examination placed
the team in a situation at step 6 with pressure dropping and the crew entered
REDIAGNOSIS to get to EEP-1, a highly probable and also correct way to go. This is
the designed purpose of ESP 0.0 and answer C describes the actions the operators
would take from this guidance.
01/09/03 11:35:58
Defeat
Depress
Determine
Direct
Dispatch
Dump
Energize
Equalize
Establish
Evacuate
FNP-0-SOP-0.8
ATTACHMENT 1
GLOSSARY OF TERMS AND ACTIONS VERBS
To disable an automatic system or an input to a control circuit.
Example: Defeat automatic closure of the main feedwater bypass
valves.
To actuate a pushbutton device.
Example: Depress HOME key.
To calculate or evaluate using equations or graphs.
Example: Determine maximum venting time.
To order that an action be taken.
Example:
To send personnel to perfom a task outside the control room.
Example: Dispatch personnel to locally restore AC power.
Direct Chemistry to sample SGs for activity.
To release steam in a controlled manner.
Example: Dump steam to condenser.
To supply electric power to.
Example: Energize pressurizer heaters.
To make the value of a parameter the same as the value of a second
parameter.
Example:
To make arrangements for a stated condition.
Example: Establish normal charging.
To cause personnel to leave a specified area.
Example:
Equalize charging flow and letdown flow.
Evacuate affected portions of the AUX BLDG.
Page 3 of 8
Version 7.0
01/09/03 11:35:58
FNP-0-SOP-0.8
3.3
3.4
Notes or caution statements are placed just prior to the step to which they apply.
If a note or caution step applies to a sequence of steps, it is placed just prior to the
first step in the sequence. Any note or caution statement which applies to an
entire procedure is placed prior to the first operator action step.
Since notes and caution statements provide information needed to support proper
performance of the operator action steps, each note or caution statement must be
read and understood prior to performing the applicable steps. When the user is
directed to a specific ERP step, he must always read and understand any notes or
caution statements applicable to that step.
Terms and Action Verbs
To ensure correct performance, directed action verbs used in the ERPs are
restricted to a specific defined set. These verbs and other special terms are
presented in Attachment 1.
Step Performance
The operator action steps are arranged in a two column format. The left column
is the ActionExpected Response (AER) column. The right column is the
Response NOT Obtained (RNO) column. The expected operator actions are
presented in the A E R column in the order of performance. If the step cannot be
performed or the specified condition is not met, the user shall go to the RNO
column for that step and take the action(s) described. AAer the action steps in the
RNO column have been performed or if they cannot be performed, the user
should return to the A/ER column for the next action step. The user should keep
in mind any actions which could not be performed and complete them later as
appropriate.
The operator action steps in both the AER and RNO columns are normally
required to be performed sequentially in the numerical order specified. High
level action steps will always be numbered. If the order of performance of a
group of high level action steps is not important, this would be specifically stated
in a note prior to the first step in the group. Substeps will be numbered if the
order of performance is important. If the substeps may be performed in any order,
the substep will have a bullet ( 0 ) instead of a number.
Once the user has initiated action to accomplish an action steu, he should
the actions he has
mpleted, a note or caution statement is placed prior to the
If two steps should be performed simultaneously instead of
sequentially, a note or caution statement is placed prior to the first step to alert the
user.
-3-
Version 7.0
01/09/03 11:35:58
FNP-0-SOP-0.8
3.8
3 .o
3.10
Following verification of immediate actions, the Shift Supervisor will proceed
expeditiously to implement subsequent actions. If the UO is not in the Control
Room when an event occurs, performance of the immediate actions by the OATC
alone is sufficient. Concurrent with starting subsequent actions, the shift
supervisor should ensure the UO or another licensed operator responds to assist in
the implementation of the ERP.
Continuous Actions (CMT0008169)
Certain operator actions provided in a procedure
performance throu
generally remains applicable throughout its associated procedure unless otherwise
stated, and may apply after a transition is made to another procedure if it does not
contain any actions that are inappropriate for the subsequent procedure. For
example, a transition contained within a continuous action will not apply after a
transition is made to a RED or ORANGE path Functional Restoration Procedure
or the ECP-0 series. Furthermore, actions requiring equipment to be started
should not be performed in the ECP-0 series unless directed in that series.
Additionally, Optimal Recovery Procedure actions are not to be performed while
a Critical Safety Function is being restored from a RED or ORANGE condition.
FOLDOUT pages also identify continuous actions that apply only in their
associated procedure.
Status Determination
Two types of status determination steps are used in the Ems. The first type of
step uses the verb "check". The intent of this step is to determine if a condition
exists and then take the appropriate directed action based on this determination.
The second type uses the verb "verify". The intent of this step is to determine if a
condition exists and then take the required actions to achieve the condition if it
does not exist.
Branching
Three types of branching are possible when using the ERPs. The first type is a
branch to another step within the same ERP. If the step being branched to
precedes the step in effect, the verb "return" is used. If the step being branched to
follows the step in effect, the verb "proceed is used. The second type of branch
is a branch to a different ERP. The verb "go" is used to direct branching to a
different ERP. If the branch does not specify a step number with the ERP
number, the user is expected to begin with the first step. The third type of
branching is a branch to the Severe Accident Management Guidelines (SAMGs).
Branching to the SAMGs is covered in detail in ATTACHMENT 2.
-5-
Version 7.0
NP-1-ESP-1.1
SI TERMINATION
CAUTION: To ensure adequate supply voltage to all class 1E loads and to meet
short circuit analysis constraints, only one air compressor, 1C
(preferred) or lA, should be powered from the diesel generator. One
air compressor will consume 0.16 MW of diesel generator load.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision 17
7
Verify 1C air compressor i n
7
Align 1A air compressor for
service.
service as follows.
7 . 1
Verify 1C air compressor
handswitch in RUN/START.
7.2 Verify 1 C air compressor
started.
a) Verify 1C air compressor
handswitch in OFF.
b) Verify SI - RESET.
[I MLB-1 1-1 not lit
[] MLB-1 1 1 - 1 not lit
CAUTION:
offsite power is l o s t after sequencer is reset.
THEN manual actions may be required to restart safeguards equipment.
- , * f f f * * * * * * * * * * * * * L * * l * l t l t l * * * * * * t * * * * * * * * * * * * * * ~ * * * * * ~ . ~ * * * * * * * * * * * * * * * * * * * * * * *
c) Reset B1F sequencer by
depressing the ESS STOP
RESET pushbutton on the
sequencer panel.
(139 ft, AUX BLDG A train
SWGR room)
d )
Place BKR DF13 SYNCH SWITCH
in MAN.
e) Close BKR DF13 (1F 4160 V
bus tie to 1 H 4160 V bus).
Step 7 continued on next page
__ Page Completed
Page 4 of 50
FNP-1-ESP-1.1
NOTE :
Plant conditions may dictate establishment of contingency electrical
lineups. FNP-1-AOP-5.1. CONTINGENCY ELECTRICAL ALIGNMENTS provides
guidance for establishing those lineups.
SI TERMINATION
Revision 17
8.1 Check offsite power -
AVAILABLE.
8.1 Direct switchboard operator to
begin efforts to restore
offsite power.
8.2 Check BKR DFOl (1A startup
8.2 Verify 1 F 4160 V bus energized
transformer to 1F 4160 V bus)
- CLOSED.
generator.
by 1-2A or 1C diesel
8.3 Verify BKR OF02 (1F 4160 V bus
8.3
diesel generator cooling
tie to 1K 4160 V bus) -
NOT supplied from Unit 2,
CLOSED.
THEN secure 1-2A and/or 1C
diesel generator using
ATTACHMENT 1. SECURING A
DIESEL GENERATOR WITH A SAFETY
INJECTION SIGNAL PRESENT.
Step 8 continued on next page.
-Page
Completed
Page 5 of 50
FNP-1-ESP-1.1
8.7 Check 1E 4160 V bus
ENERGIZED.
SI TERMINATION
Revision 17
8.7 Establish power to 1C 600 V LC
emergency section loads.
8.7.1 Verify pressurizer heater
group 1B - OFF.
8.7.2 Open BKR EC08-1.
8.7.3 Close BKRs EE07-1 and
I
EC10-1.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAUTION: To prevent diesel generator overloading, at least 0.3 MW of diesel
generator capacity must be available prior to energizing a group of
pressurizer heaters.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.7.4 Energize pressurizer heater
group 1B as required.
8.8 Proceed to step 8.10.
8.9 a 1D 4160 V bus energized.
-
THEN proceed to step 9.
Step 8 continued on next page.
-Page
Completed
Page 6 of 50
SI TERMINATION
'NP-
1 -ESP-
1.1
Step
Action/Expected Response
Response NOT Obtained -
Revision 17
8.10 Establish power to
loads.
8.10.1 Verify pressurizer heater
group 1A - OFF.
8.10.2 Verify open BKR EA08-1.
8.10.3 Verify closed BKRs ED08-1
and EA09-1.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAUTION: To prevent diesel generator overloading, at least 0.3 MW of diesel
generator capacity must he available prior to energizing a group of
pressurizer heaters.
NOTE :
The BYPASS position allows manual energization of pressurizer heater
group 1A from the MCB handswitch, and automatic energization based on
either pressurizer pressure 5 2210 psig or pressurizer level 5% above
program.
8.10.4 WHEN pressurizer heater
group 1A operation is
desired,
THEN place HTR GRP 1A
BLOCKING BYPASS SW to
BYPASS.
8.10.5 a
required,
THEN manually energize
pressurizer heater group
1A.
Step 8 continued on next page.
-Page Completed
Page 7 of 50
'NP-1-ESP-1.1
CAUTION: To ensure adequate supply voltage to all class 1E loads and to meet
short circuit analysis constraints, only one air compressor, 1C
(preferred) or 1A. should be powered from the diesel generator. One
air compressor will consume 0.16 MW of diesel generator load.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
SI TERMINATION
Revision 17
8 . 1 1
Verify 1C air compressor in
8.11 Align 1A air compressor for
service.
service as follows.
8 . 1 1 . 1
Verify 1C air compressor
handswitch in RUN/START.
8 . 1 1 . 2
Verify 1C air compressor
started.
a) Verify 1C air compressor
handswitch in OFF.
b ) Verify SI - RESET.
[I MLB-1 1-1 not lit
[1 MLB-1 11-1 not lit
CAUTION: a
offsite power is lost after sequencer is.reset.
THEN manual actions may be required to restart safeguards equipment.
c) Reset B1F sequencer by
depressing the ESS STOP
RESET pushbutton on the
sequencer panel.
(139 ft, AUX BLDG A train
SWGR room)
d) Place BKR DF13 SYNCH
SWITCH in MAN.
e) Close BKR DF13 (1F 4160 V
bus tie to 1H 4160 V
bus) .
f)
1H 4160 V bus
energized.
from normal supply.
[I BKR DHOl closed
[I BKR EG02-1 closed
Step 8 continued on next page
Paee Comoleted
_____
Page 8 of 50
FNP-1-ESP-1.1
8.12.1 Restore air pressure.
Verify proper air
compressor operation
using FNP-1-SOP-31.0.
COMPRESSED AIR SYSTEM.
I
-
.IJ
2C air compressor
available,
THEN align 2C air
comuressor to Unit 1
SI TERMINATION
Revision 17
usiAg FNP- 1 -SOP-31.0.
COMPRESSED AIR SYSTEM.
8.12.2 a
instrument air NOT
restored,
-
THEN align nitrogen supply
to PORVs using
FNP-1-SOP-62.1. BACK-UP
THE PRESSURIZER POWER
OPERATED RELIEF VALVES.
8.12.3 a
instrument air NOT
restored,
THEN align emergency air
supply to atmospheric
relief valves and/or
TDAFWP using
FNP-1-SOP-62.0, EMERGENCY
AIR SYSTEM.
Step 8 continued on next page.
I-PaRe
Completed
Page 9 of 50
FNP-1-ESP-1.1
I
I
Step
ActiodExpected Response
Response NOT Obtained
I
I
SI TERMINATION
Revision 17
8.12.4
instrument air NOT
restored because 1G 600 V
LC is deenergized.
FNP-1-SOP-36.3,
600,
480 AND 208/120 VOLT AC
ELECTRICAL DISTRIBUTION
SYSTEM.
8.12.5 WHEN instrument air
pressure restored.
THEN perform step 8.13.
8.12.6 Proceed to step 9.
-Page
Comuleted
8.13 Align instrument air to
containment. (BOP)
[ I NlP19HV3825 open
[I NlP19HV3885 open
[I QlP19HV3611 open
Page 10 of 50
Step
ActiodExpected Response
Response NOT Obtained
CHG PUMPS TO
REGENERATIVE HX
[1 QlE21MOV8107 open
[I QlE21MOV8108 open
Step 9 continued on next page.
-Page
Completed
I
9
Isolate HHSI flow.
9.1 Check CHG PUMP - SUCTION
9.1 E CHG pump suction aligned to
ALIGNED TO RWST
recirculation mode,
TO CHG PMP
discharge of RHR Pumps [via
QlEllMOV8706A(B)I in the
THEN perform the following.
[I Q1E21LCV115B open
[1 QIE21LCV115D open
I
9.1.1 Manually close charging
flow control valve.
CHG FLOW
[1 FK 122
9.1.2
train A charging pump
running,
THEN perform the following.
IF NOT,
THEN proceed to RNO
Step 9.1.3.
-
-
Step n
Actionhxpected Response
Response NOT Obtained
- -
9.1.2.3
Verify only one charging
l i n e valve - OPEN.
RCS NORMAL
CHG LINE
[I QlE21HV8146
CHG LINE
[I QlE21HV8147
9.1.2.4
Open charging flow
control valve FK-122 as
necessary t o obtain
54-58 gpm.
CHG FLOW
[J FK 122 manually adjusted
9.1.2.5
Close HHSI i s o l a t i o n
valves.
HHSl TO
RCS CL IS0
[1 QlEZlMOV8803A
[I QlE21MOV8803B
9.1.2.6
Verify charging flow
greater than 60 gpm.
9.1.2.7
Proceed t o Step 11.
S t e p 9 continued on next page.
-Page
Completed
Page 1 2 of SO
NP-1-ESP-1.1
SI TERMINATION
Step
n
Revision 17
Action/Expected Response
Response NOT Obtained
-
I
I
9.1.3 x t r a i n B charging pump
running,
-
THEN perform the following
9.1.3.1 Close HHSI isolation
valves.
HHSI TO
RCS CL IS0
[I QlE21MOV8803A
[I QlE21MOV8803B
9.1.3.2 Verify charging pump
discharge flow path -
ALIGNED.
CHG PUMP
DISCH HDR IS0
[I QlE21MOV8132A open
11 QlE21MOV8132B open
[I QlE21MOV8133A open
[I QlE21MOV8133B open
CHG PUMPS TO
REGENERATIVE HX
[] QlE21MOV8107 open
[I QlE21MOV8108 open
9.1.3.3 Verify only one charging
line valve - OPEN.
RCS NORMAL
CHG LINE
[I QlE21HV8146
CHG LINE
[I QlE21HV8147
9.1.3.4 Open charging flow
control valve FK-122 as
necessary to obtain
54-58 gpm.
CHG FLOW
[I FK 122 manually adjusted
Step 9 continued on next page.
-
Page Completed
Page 13 of 50
Revision 17
I
NP-1-ESP-1.1
SI TERMINATION
Step
n
9 .
Action/Expected Response
Response NOT Obtained
Verify charging pump mini
valves - OPEN.
lA(lB.1C) CHG PUMP
MINIFLOW IS0
[I QlE21MOV8109A
[I QlE21MOV8109B
[ I QlE21MOV8109C
CHG PUMP
MINIFLOW IS0
[ I QlE21MOV8106
I
I
9.1.3.5 Close charging pump
recirculation to RCS
cold legs valve.
CHG PUMP RECIRC
TO RCS COLD LEGS
[I QlE21MOV8885
9.1.3.6 Verify charging flow
greater than 60 gpm.
9.1.3.7 Proceed to Step 11.
ow
9.3 Close HHSI isolation valves
HHSI TO
RCS CL IS0
[ I QlE21MOV8803A
[I QlE21MOV8803B
-Page
Completed
Page 14 of 50
S I TERMINATION
IP-1-ESP-1.1
Step
Actionhxpected Response
r
-
i
y
10
Establish normal charging.
10.1 Manually close charging flow
control valve.
CHG FLOW
[ ] EK 122
1 0 . 2
Verify charging flow path
aligned.
Revision 17
Response NOT Obtained
1
10.2.1
I
I
I
I
Verify charging pump
discharge flow path
ALIGNED.
(;IC PUMP
I!ISCII HDR IS0
(; I I:% 1 MOV8132A open
(:II:%lMOV8132B open
cril:%1MOV8133A open
(;II:7.1MOV8133B open
!:iic:
I'UMI'S TO
I:!:i:I:NI.RATIVE
I I (:II:%IMOV8107 open
1 I (!l1;71MOV8108 open
1 0 . 2 . 7
V i , r i f y o n l y one charging
I iiir v a l v e - OPEN.
llCS NOKMAL
CIK; LINE
j I 011:2111V8146
IKS ALT
CllG LINE
[ I 01121HV8147
Step 10 continued on next page.
-
Page Completed
Page 15 of 50
NP-1-ESP-1.1
S I TERMINATION
Step
ActionlExpected Response
Response NOT Obtained
3
Revision 1 7
NOTE:
The RCS may be approaching s o l i d p l a n t c o n d i t i o n s .
RCS must be operated w a t e r s o l i d . c h a r g i n g flow should be adjusted t o
maintain subcooling i n s t e a d of p r e s s u r i z e r l e v e l .
I n t h e event t h e
11
-
1 0 . 2 . 3 Esta
main
15%-50%(48%-52%1.
10.2.3.1
Control charging flow.
CHG FLOW
I] FK 122 a d j u s t e d
Secure RHR system.
1 0 . 2 . 3
Perform t h e following.
nnot be maintained
greater than 15%148%1.
perform the
owing.
1) E s t a b l i s h HHSI flow
u s i n g ATTACHMENT 2.
FLOW
RE-ESTABLISHING HHSI
> ) GO t o FNP-1-ESP-1.2,
POST LOCA COOLDOWN
AND DEPRESSURIZATION.
-
I F s o l i d plant operation
r e q u i r e d .
THEN c o n t r o l charging
flow t o maintain
subcooling greater than
16"F[45"F].
CHG FLOW
-
[I FK 122 adlusted
11.1 Stop both RHR PUMPS.
11.2 Isolate CCW t o the on s e r v i c e
t r a i n RHR heat exchanger.
ccw TO
[I QlP17MOV3185A closed
[I QlPlizV3185B closed
-
Page Completed
Page 16 o f 50
FNP-1-ESP-1.1
SI TERMINATION
12.2 Check pressurizer level -
GREATER THAN 7%(50%1.
Revision 17
12.2 Perform the following.
12.2.1 Establish HHSI flow using
ATTACHMENT 2,
RE-ESTABLISHING HHSI FAOW
12.2.2 GO to FNP-1 EEP-1, LOSS OF
REACTOR OR SECONDARY
COOLANT.
-
13
Check containment spray system.
13.1 Check any CS PUMP - STARTED.
13.1 Proceed to step 14
13.2 Reset containment spray
signals.
CS RESET
[I A TRN
[I B TRN
13.3 WHEN containment spray
recirculation flow has been
aligned for at least 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
-
AND containment pressure is
less than 16 psig,
-
THEN stop both CS PUMPS.
-
Page Completed
Page 17 of 50
81. 026A2.07 001/2/I//CIA 3.6/3.9/NIFA03301ISISDR
Unit 1 was at 100% power when a Large Break LOCA occurred inside containment. The
crew has responded per the ERGS and has transitioned to ESP-I .3, Transfer to Cold
Leg Recirculation, from EEP-1, Loss of Reactor or Secondary Coolant, Step 16. While
aligning 1 B RHR pump for cold leg recirculation, Containment pressure reached 27
psig. Both trains of containment spray have actuated.
The crew is currently performing Step 8 of ESP-1.3 checking containment spray in
operation. RWST level is 4.4 ft and slowly decreasing.
Which ONE of the following discribes the correct actions and procedure transition, if
any, required to mitigate this condition?
A. Secure the CS pumps, then transition to FRP-Z.1, Response to High Containment
Pressure.
B. Align the CS pumps for cold leg recirculation, then transition to FRP-Z.l, Response
to High Containment Pressure.
C. Transition to ECP-1.1, Loss of Emergency Recirculation.
D. Continue in ESP-I .3 and subsequently return to the procedure and step in effect (Le.
EEP-1, step 16)
NEED Licensee to verify that answer 'A' is the expected response. The information
provided to the NRC for exam development did not address this situation.
LICENSEE VALIDATION IS REQUIRED.
A - Correct; An ORANGE path exist for containment pressure.
B - Incorrect; NEED Licensee to veriv that this is not an expected response for this
condition otherwise a new distracter needs to be developed.
C - Incorrect; this is a logical procedure to transition to although not supported in step 9
of ESP-I .3. ESP-I .3 has no RNO actions for this situation. Lesson plan OPS-52531G
page 10, states that if at least one path from the sump to the RCS cannot be
established a transition to ECP-1.1 is made. The lesson plan does not address if a path
from the sump to the containment spray can not be established.
D - Incorrect; to continue in ESP-I .3 would result in securing all supply to the running
containment spray pumps without instructions to secure the pumps.
Change question to accept A and B
The stem of the question ask which ONE of the following (A, B, C, D) describes the
correct actions and procedure transition, if any, required to mitigate this condition.
A.
Secure the CS pumps, then transition to FRP-Z.1, Response to High
Containment Pressure.
This is designated as the correct answer, and is a proper response and
procedure transition. An ORANGE path exists for containment pressure and due to the
Continuing action step of ESP-I .3 and being 4.5 in the RWST, IF it is determined that
swap over is NOT imminent the CS pumps are secured, and a transition made to FRP-
z.1.
However, B actions could be acceptable in the described situation making B a possible
correct answer.
B
Align the CS pumps for cold leg recirculation, then transition to FRP-Z.l,
Response to High Containment Pressure.
This is the most conservative answer and correct depending on how the word
then is interpreted. A Shift Supervisor with knowledge of the requirements of FRP-Z-1
would likely direct an Operator to place the CS pumps on cold leg recirculation while
transitioning to FRP-Z.1. The SS realizes that FRP-Z-1 will place the pumps on
recirculation in step 3.4. In this case the actions of FRP-Z-1 and ESP-1.3 for aligning
containment spray for recirculation coincide, would be taking place regardless and the
entry to FRP-Z.l would not be delayed. At our plant we often start one step with the
UOlOATC and then the team will continue on while that step is being completed. The
word then is often utilized to give continuing action once a step has been
implemented, i.e. to start aligning the CS pumps recirculation off of the containment
sump while transitioning to FRP-Z-1 .
This is actuallv the most conservative thing to do since containment pressure is
rising and both ESP-I .3 and FRP-Z.l have you place CS on recirculation. If the CS
pumps just started as the stem maintains, then the CS pumps would be stopped in
answer A
response and then restarted within a few minutes. Hot starts on the pumps
and repeated cycling of breakers pose additional threats to accident recovery and
should not be performed unnecessarily. The conservative thing to do utilizing Operator
knowledge of upcoming procedural actions would be to leave the pumps running, use
an operator to complete the swap-over to help maintain the integrity of containment
while the team continues on to FRP-Z.1. The procedure for aligning containment spray
for recirculation does not require that the pumps be stopped. The containment sump
suctions are opened before the RWST suctions are closed. Therefore answer B actions
would be acceptable in the described situation.
Also when step 8 of the procedure is reached, FRP-Z.l is entered only after an
evaluation that there are no red paths or higher priority orange paths. During the
performance of this evaluation (typically done by the STA) the crew would be
proceeding. Per the stem (both trains of containment spray have actuated), Step 8
would be completed by observing the pump hand switches before the evaluation was
completed and the crew would be at step 9.
8
9
Check containment spray - IN OPERATION.
WHEN RWST level less than 4.5 ft,
THEN align containment spray for
cold leg recirculation.
Also in this case the rules of usage state (SOP-0.8):
3.8
Continuous Actions
Certain operator actions provided in a procedure direct or imply continuous
performance throughout the remainder of the procedure. A continuous action is an
action that is applicable from the point at which it is first encountered until superseded
by alternate guidance or stated to be inapplicable. A continuous action generally
remains applicable throughout its associated procedure unless otherwise stated, and
may apply after a transition is made to another procedure if it does not contain any
actions that are inappropriate for the subsequent procedure.
Tripping the containment spray pumps with 27 psig in containment could be
evaluated as inappropriate.
Since step 9 is a continuing action step the above rules of usage states the crew
should evaluate if it is appropriate to continue alignment for recirculation while in FRP-
Z. 1. This evaluation could determine that tripping the pumps is inappropriate because
recirculation is imminent.
Answer C is incorrect based on the information provided for this distracter.
Answer D is incorrect because a transition to FRP-Z.l is required for the existing
conditions.
01/09/03 11:35:58
FNP-0-SOP-0.8
Notes or caution statements are placed just prior to the step to which they apply.
If a note or caution step applies to a sequence of steps, it is placed just prior to the
first step in the sequence. Any note or caution statement which applies to an
entire procedure is placed prior to the first operator action step.
Since notes and caution statements provide information needed to support proper
performance of the operator action steps, each note or caution statement must be
read and understood prior to performing the applicable steps. When the user is
directed to a specific ERF' step, he must always read and understand any notes or
caution statements applicable to that step.
3.3
Terms and Action Verbs
To ensure correct performance, directed action verbs used in the ERPs are
restricted to a specific defined set. These verbs and other special terms are
presented in Attachment 1.
3.4
Step Performance
The operator action steps are arranged in a two column format. The left column
is the Action/Expected Response (AER) column. The right column is the
Response NOT Obtained (RNO) column. The expected operator actions are
presented in the A/ER column in the order of performance. If the step cannot be
pcrfornied or the specified condition is not met, the user shall go to the RNO
colunin for that step and take the action(s) described. After the action steps in the
RNO column have been performed or if they cannot be performed, the user
should return to the AER column for the next action step. The user should keep
in mind any actions which could not be performed and complete them later as
appropriate.
The operator action steps in both the A E R and RNO columns are normally
required to be performed sequentially in the numerical order specified. High
level action steps will always be numbered. If the order of performance of a
group of high level action steps is not important, this would be specifically stated
in a note prior to the first step in the group. Substeps will be numbered if the
order of performance is important. If the substeps may be performed in any order,
the substep will have a bullet ( 0 ) instead of a number.
If two steps should be performed simultaneously instead of
sequentially, a note or caution statement is placed prior to the first step to alert the
user.
-3-
Version 7.0
01/09/03 11:35:58
FNP-0-SOP-0.8
Following verification of immediate actions, the Shift Supervisor will proceed
expeditiously to implement subsequent actions. If the UO is not in the Control
Room when an event occurs, performance of the immediate actions by the OATC
alone is sufficient. Concurrent with starting subsequent actions, the shift
supervisor should ensure the UO or another licensed operator responds to assist in
the implementation of the ERP.
3.8
Continuous Actions (CMT0008169)
Certain operator actions provided in a procedure direct or imply continuous
performance throughout the remainder of the procedure. A continuous action is an
action that is applicable from the point at which it is first encountered until
superseded by alternate guidance or stated to be inapplicable. A continuous action
contain any actions that are inappropriate for the subsequent procedure. For
example, a transition contained within a continuous action will not apply after a
transition is made to a RED or ORANGE path Functional Restoration Procedure
or the ECP-0 series. Furthermore, actions requiring equipment to be started
should not be performed in the ECP-0 series unless directed in that series.
Additionally, Optimal Recovery Procedure actions are not to be performed while
a Critical Safety Function is being restored from a RED or ORANGE condition.
FOLDOUT pages also identify continuous actions that apply only in their
associated procedure.
3.9
Status Determination
Two types of status determination steps are used in the Ems. The first type of
step uses the verb "check". The intent of this step is to determine if a condition
exists and then take the appropriate directed action based on this determination.
The second type uses the verb "verify". The intent of this step is to determine if a
condition exists and then take the required actions to achieve the condition if it
does not exist.
3.10
Branching
Three types of branching are possible when using the EWs. The first type is a
branch to another step within the same ERP. If the step being branched to
precedes the step in effect, the verb "return" is used. If the step being branched to
follows the step in effect, the verb "proceed" is used. The second type of branch
is a branch to a different ERP. The verb "go" is used to direct branching to a
different ERP. If the branch does not specify a step number with the ERP
number, the user is expected to begin with the first step. The third type of
branching is a branch to the Severe Accident Management Guidelines (SAMGs).
Branching to the SAMGs is covered in detail in ATTACHMENT 2.
-5-
Version 7.0
FNP-1-ESP-1.3
TRANSFER TO COLD LEG RECIRCULATION
Revision 15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAUTION: To ensure that SI recirculation flow is maintained at all times, the
following steps should be performed without delay.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.......................................................................................
tion Procedure should be implemented until step 7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAUTION: Switchover to recirculation may cause high radiation levels in the
auxiliary building.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-
1
-
I F RWST l e v e l less than 4.5 f t
-_
lrND alignment for recirculation
NOT imminent,
___
THEN stop any pump taking
suction from the RWST.
-
Page Completed
Page 2 of 10
'NP-1-ESP-1.3
Step
Actionhxpected Response
Response NOT Obtained
I
I
TRANSFER TO COLD LEG RECIRCULATION
Revision 15
NOTE :
The intent of Step 2 is to differentiate between a steam line break
event (with SI terminated and RWST drain down only from containment
spray operation) and a l o s s of reactor coolant event (RWST drain down
from one or more ECCS pumps).
-
2
Check SI i n service.
2
Perform the following
Check HHSI flow - GREATER
2.1 Reset containment sump to RHR
THAN 0 gpm.
valve switches.
A TRN
HHSI FLOW
[I FI 943
PUMP RESET
[I A TRN
[I B TRN
-
2.2 Proceed to Step 8
- Check any RHR PUMP - STARTED
IN SI MODE.
Started RHR PUMP I
1A
I RWST TO
lA(1B) RHR PUMP
[I 8809A
TO lA(1B) RHR PUMP
Q2E1 lMOV
[I 8701A
closed
[I 8701B
closed
[I 8809B
[I 8702A
closed
[ I 8702B
closed
-
3
Verify SI - RESET
[I MLB-I 1-1 not lit (A TRN)
[I MLB-1 11-1 not lit (B TRN)
3
-
IF any train will NOT reset
using the MCB SI RESET
pushbuttons,
-
THEN place the affected train
S821 RESET switch to RESET.
(SSPS TEST CAB. )
-
4
Verify at least one train of
PRF i n operation using
ROOM FILTRATION SYSTEM i n
conjunction with the remaining
steps of t h i s procedure.
FNP-1-SOP-60.0. PENETRATION
-Page
Completed
Page 3 of 10
FNP-1-ESP-1.3
[J QIP17MOV3185A open
[I QlP17MOV3185B open
TRANSFER TO COLD LEG RECIRCULATION
Revision 15
-
6
Establish only one CHG PUMP in
each train - RUNNING.
11 A Train (1A or 1B) amps > 0
[ I B Train (1C or 1B) amps > 0
- * * * * I 1 * * * r * * * * * l * , l * * * * f * t l f ) t l * * * * t , * * * * * * * * * ~ * * *
- * * * . * * * * . * * f I * * * * . * * * * *.** * * *
CAUTION: Pump damage will occur if a charging pump o r RHR pump is started in a
train in which a flow path from the containment sump to the RCS
cannot be established or maintained.
- * * * * I * * * * * * * * * * * * * * * * * * * * * * * * * * ~ * * * * * * * . * * , * * * , * * ~ * , * * * * * * * * ~ * * * . * * * * * * * ~ * * * ~ * *
7
Align ECCS for cold leg
recirculation.
7.1 Check containment sump level
GREATER THAN 2 . 4 ft(3.0 ftl.
LVL
[I LI 3594A
POST ACCIDENT
CTMT WTR LVL
[I LR 3594B
7.2 Verify recirculation valve
disconnects - CLOSED USING
ATTACHMENT 1.
7.3 Stop both RHR PUMPS.
QlEllMOV8809A.
7.1
both containment sump level
indications less than
2.4 ft13.0 ft1,
THEN EO to FNP-1-ECP-1.1. LOSS
OF EMERGENCY COOLANT
RECIRCULATION.
7.4 Perform the following.
7.4.1 Stop the running A train
CHG PUMP.
7.4.2 Proceed to step 7.9.
Step 7 continued on next page.
-
Page Completed
Page 4 of 10
n
FNP-1-ESP-1.3
TRANSFER TO COLD LEG RECIRCULATION
I
Revision 15
Step
ActiodExpected Response
Response NOT Obtained
I
I
PUMP.
TO 1A RHR PUMP
[I QlEllMOV8811A open
[I QlEllMOV8812A open
7.6 Close RHR to RCS HOT LEGS XCON
QlEllMOV8887A.
7.7 Start 1A RHR PUMP.
RHR PUMP
[I 1A amps > 0
7.8 Verify A Train LHSI flow -
STABLE.
1A
FLOW
[I FI 605A
QlEllMOV8809B.
7.10 Align CTMT sump to 1B RHR
PUMP.
TO 1 B RHR PUMP
[J QlEllMOV8811B open
[ ] QlEllMOV8812B open
7.11 Close RHR to RCS HOT LEGS
XCON QlEllMOV8887B.
7.5 Perform the following.
7.5.1 Stop the running A train
CHG PUMP.
7.5.2 Proceed to step 7.9.
7.7 Perform the following.
7.7.1 Stop the running A train
CHG PUMP.
7.7.2 Proceed to step 7.9.
7.9 Perform the following.
7.9.1 Stop the running B train
CHG PUMP.
7.9.2 Proceed to step 7.14.
7.10 Perform the following.
7.10.1 Stop the running B train
CHG PUMP.
7.10.2 Proceed to step 7.14.
Step 7 continued on next page.
-Page
Completed
Page 5 of 10
NP-1-ESP-1.3
7.12 Start 1B RHR PUMP.
TRANSFER TO COLD LEG RECIRCULATION
Revision 15
RHR PUMP
[I 1B amps > 0
7.12 Perform the following.
7.12.1 Stop the running B train
CHG PUMP.
7.12.2 Proceed to step 7.14.
7.13 Verify B Train LHSI flow
STABLE.
1B
FLOW
I I FI bO5B
7 . 1 4
I A RHR PUMP started,
-
'I'IIKN a l i g n charging pump
s u r 1 i o n header isolation
v;~lvr;:
based on 1B charging
punip s t a t u s .
1B Ctrarp,inf
Pump
Status
JHG P U M P
SUCTION
HDR IS0
31E2 1 MOV
4lip,ncd As
4 Train
,ump
[ I 8130A
[ I 8130B
[ I 8131A
[ I 8131B
open
open
closed
closed
Aligned A:
B Train
Pump
[I 8130A
11 8130B
[I 8131A
[ I 8131B
closed
closed
open
open
Not
Available
[I 8130A
[I 8130B
[I 8131A
[I 8131B
closed
closed
closed
closed
7.14
1A RHR PUMP
started,
-
THEN perform the following.
7.14.1 Verify the A train CHG
PUMP stopped.
7.14.2 Proceed to step 7.18.
7.15 Perform the following.
7.15.1 Stop the running A train
CHG PUMP.
7.15.2 Proceed to step 7.18
7.15 Open RHR supply to A train
charging pump suction.
TO CHG PUMP SUCT
[I QlEllMOV8706A
7.16 Verify VCT level - GREATER
THAN 5%.
Step 7 continued on next page.
__ Page Completed
Page 6 of 10
NP-1-ESP-1.3 I
TRANSFER TO COLD LEG RECIRCULATION
I
Revision 15
1B Charging
Pump
Status
Step
Action/Expected Response
Response NOT Obtained -
Aligned As
A Train
Pump
7.17 Close A train RWST to
charging pump header valve.
TO CHG PUMP
[I QlE21LCV115B
7.18 E 1B RHR PUMP started,
THEN align charging pump
suction header isolation
valves based on 1B charging
pump status.
CHG PUMP
SUCTION
HDR IS0
Q 1 E 2 1 MOV
[I 8130A
[ I 8130B
open
I
closed
Aligned A:
B Train
Pump
[I 8130A
[I 8130B
[I 8131A
11 8131B
closed
closed
open
open
Not
Available
[I 8130A
[I 8130B
[I 8131A
[I 8131B
closed
closed
closed
closed
7.17 Perform the following.
7.17.1 Stop the running A train
CHG PUMP.
7.17.2 Close RHR supply to A
train charging pump
suction.
TO CHG PUMP SUCT
[I QlEllMOV8706A
7.18
1B RHR PUMP NOT started.
THEN perform the following.
7.18.1 Verify the B train CHG
PUMP stopped.
7.18.2 Proceed to step 7.22.
7.19 Perform the following.
7.19.1 Stop the running B train
CHG PUMP.
7.19.2 Proceed to step 7.22
7.19 Open RHR supply to B train
charging pump suction.
TO CHG PUMP SUCT
[I QlEllMOV8706B
7.20 Verify VCT level - GREATER
THAN 5%.
Step 7 continued on next page
-
Page Completed
Page 7 of 10
06/05/2003 11:41
Step
Action/Expected Response
Response NOT Obtained
n-
I
I
7.21 Close B train RWST to
7.21 Perform the following.
charging pump header valve.
CHG PUMP.
TO CHG PUMP
7.21.1 Stop the running B train
[I QlE21LCV115D
7.21.2 Close RHR supply to B
train charging pump
suction.
TO CHG PUMP SUCT
11 QlEllMOV8706B
7.21.3 Proceed to step 7.22
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAUTION: Injecting through 'A' train and 'B' train flowpaths simultaneously
with only one charging pump running could result in pump runout
conditions. Therefore, in Step 7.22 RNO the HHSI valves should be
closed without delay after MOV8885 is opened.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.22 Check one CHG PUMP in each
7.22 E an A train CHG PUMP
train - STARTED.
started.
THEN proceed to step 7.24
[ ] A train (1A o r 1B) amps > 0
establish B train
[ ] B train (1C or 1B) amps > 0
injection per the following.
7.22.1 Open charging pump
recirculation to RCS cold
legs valve.
CHG PUMP RECIRC
TO RCS COLD LEGS
11 QlE21MOV8885
7.22.2 Close HHSI isolation
valves.
HHSI TO
RCS CL IS0
11 QlE21MOV8803A
[I QlE21MOV8803B
7.22.3 Proceed to step 7.24
Step 7 continued on next page
-Page
Completed
Page 8 of 10
Step
Action/Expected Response
Response NOT Obtained
I
I
7.23 Open charging pump
recirculation to RCS cold
legs valve.
CHG PUMP RECIRC
TO RCS COLD LEGS
[I QlE21MOV8885
7.24 Align charging pump discharge
header isolation valves based
on 1B charging pump status.
Status
CHG PUMP
DISCH HDR IS0
QlE21MOV
7.25
I
Aligned As
4 Train pumi
[I 8132A
[I 8132B
[I 8133A
[I 8133B
open
open
closed
closed
[I 8132A
[I 8132B
[I 8133A
[I 8133B
closed
closed
open
open
Verify SI flow ~
STABLE.
A TRN
HHSI FLOW
FI 943
B TRN RECIRC
FLOW
[I FI 940
IA(~B)
FLOW
[I FI 605A
[I FI 605B
- 8
Check containment spray - IN
OPERATION.
[I 8132A
[I 8132B
[I 8133A
[I 8133B L
closed
closed
closed
closed
7.25 E at least one train of flow
from the containment sump to
the RCS can _NOT be
established or maintained,
THEN PO to FNP-1-ECP-1.1.
LOSS OF EMERGENCY COOLANT
RECIRCULATION.
8
Go to procedure and step in
effect.
Page 9 of 10
IP-1-ESP-1.3
Step
Actionhxpected Response
Response NOT Obtained
n
7
1
TRANSFER TO COLD LEG RECIRCULATION
Revision 15
- 9
RWST level less than
aliEn containme
4.5 ft.
for cold leg
[I MLB-3 1-1 not llt
[I MLB-3 6 1 n
9.2 Open containment spr
containment sump suction
isolation valves.
1'0 lA(1B) CS PUMP
[I QlE13MOV8826A
I I QlE13MOV8827A
[ I QlE13MOV8826B
[I QlE13MOV8827B
9.3 Close containment spray pump
RWST suction isolation valves.
RWST TO
lA(1B) CS PUMP
[I QlE13MOV8817A
[ ] QlE13MOV8817B
9.4 WHEN containment spray
recirculation f l o w has been
established for at least 8
hours,
containment
pressure is less than 16 psig,
THEN s t o p both CS PUMPS.
9.5 Consult TSC staff to evaluate
RWST makeup requlrements.
Go to procedure and step in
effect.
-
10
-END
-
Page 10 of 10
83. 03362.4.11 002I2/2/lMEM 3.4l3.6/NlFA03301lSlSDR
Spent Fuel Pool (SFP) cooling has been lost due to the total loss of CCW. SFP
temperature is 170-F and slowly increasing. AOP-36.0, Loss of Spent Fuel Pool
Cooling, has been implemented.
Which ONE of the following will provide the cooling method for the spent fuel pool on a
sustained loss of CCW to both trains of SFP cooling in accordance with AOP-36.0 for
the above conditions?
A. Feed and bleed using Refueling Water Storage Tank (RWST).
B. Evaporative loss while maintaining SFP level using the RWST.
C. Feed and Bleed using Recycle Holdup Tanks (RHT).
D. Evaporative loss while maintaining SFP level using the Demineralized water system.
A - Incorrect; This method is used initially during the performance of AOP-36.0, Loss of
Spent Fuel Pool Cooling, however, there is no procedure provisions to continue this
method once SPF temperature is above 150 O F .
B - Incorrect; Do not use RWST to maintain level.
C - Incorrect; Not recognized by AOP-36.0 as an approved cooling method
D - Correct; If level in the SFP cannot be maintained then the perferred source will be
demin water per step 14.
This question meets the requirements of 10CFR55.43(b)(5) for SRO only question
Delete from Exam due to low operational validity
Analysis (REA 98-18762) has shown that on a loss of cooling to the SFP, at
maximum design heat load and temperature (180°F) it will take 2.2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> before the
SFP reaches bulk boiling state. The normal operating temperature of the SFP is less
than 130°F (maximum allowed alarm setpoint). If it takes 2.2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> to increase 32"F,
then SFP temperature with the worst case heat load will be rising at a maximum rate of
0.242"FIhour. This means that in the worst case it will take -one hour and 30 minutes
to reach the decision point concerning use of demineralized water or RWST water.
NUREG 1021 Rev 9 Draft, ES 404 Page 7 of 34 states:
c. Ensure that the questions will differentiate between competent and less-than
competent applicants, that they are appropriate for the job level being examined, and
that they are operationally oriented when possible. Refer to Appendix A (Section C.2)
and Appendix B (Section C.l .a and Section B of Attachment 2) for additional discussion
of and examples to illustrate the concept of operational validity.
NUREG 1021 Appendix B Paragraph e on 5 and 6 states:
e. Avoid questions that are unnecessarily difficult or irrelevant. As discussed
conceptually in Appendix A, both the level of knowledge and item difficulty are at the
heart of examination discrimination. Examination authors Appendix 6 should develop
examinations that are estimated to center around the 80 percent cut score level, with
individual item difficulty estimated to fall in the 70 to 90 percent difficulty range. These
parameters should not be viewed as precise benchmarks, but rather as approximate
end points. Examination authors should consider the results of past examinations when
preparing a new one. Past performance on individual test questions may provide a
basis for generating new questions and for estimating the level of difficulty of the
examination. For example, questions that everyone got wrong may be an indicator that
the topic was not given sufficient emphasis in training or that the item was poorly
worded. Conversely, questions that everyone got correct may indicate that the item was
written at too low a level or that the distractors were not very plausible.
When attempting to determine the appropriate level of difficulty, it may be helpful to
think of two groups of individuals, one composed of experienced operators and the
other of typical applicants, and evaluate the likelihood that each group of individuals will
be able to answer the question. If at least 80 percent of the job incumbents or license
applicants should be able to answer the question as written based on the expected
knowledge levels for the position (operator or senior operator), then the item is likely
written at an appropriate discriminatory level. Examination authors and reviewers may
also ask themselves the following questions in an effort to identify questions that are
unnecessarily difficult or irrelevant:
Could someone do the job safely and effectively without being able to answer the
question? If so, is it because the content is inappropriate, because the wording is
unclear, or because the level of understanding is too great?
What aspects of the item or option might cause the most difficulty? Has the item
been made artificially difficult? Can a person understand the principle being
tested and still miss the item?
Estimates of difficulty made by the examination author and reviewers may vary
somewhat but should not vary widely. Unless there is some reason to doubt the
estimates of some reviewers, the average estimate may be taken as a basis for judging
the suitability of item difficulty for the examination. Items should be revised if estimates
fall well below or above the 70 to 90 percent target range.
Appendix Example question 2 under operational validity reads:
The plant is recovering from a scram due to a spurious Group I isolation. The cause of
the isolation has been repaired and preparations are being made to reopen the MSIVs.
Reactor pressure is currently 825 psig and the main steam lines are being pressurized.
WHICH ONE (1) of the following is the LOWEST main steam line pressure that will
allow the MSlVs to be opened per the procedure?
a.
625 psig
b.
675 psig
C.
725 psig
d.
775 psig"
This question does not discriminate and has low operational validity because in real life
the applicant may not be expected to have memorized the procedure.
From the previous calculation it will be an extended amount of time from the loss
of CCW until the criteria of 150°F is met. It is expected that a candidate will be able to
identify mechanisms for removing heat from the SFP but not the exact point of transition
from one method to another. AOP-36.0 is designated as a continuous use procedure.
The requirements for a continuous use procedure are that the procedure or applicable
section(s) must be physically present with worker at the work location and each step
MUST be read before performance UNLESS steps are designated in the procedure as
"Immediate Action" steps (table from FNP-0-AP-6 below). In the amount of time given
before the conditions required in the stem the operator is required to have the
procedure which was not provided with the examination. Therefore per the above
requirements from NUREG 1021 this question is not operationally valid and should be
deleted.
r
QUICK REFERENCE GUIDE FOR PROCEDURE LEVEL-OF-USE
INFORMATION USE
I
I
LEVELOFUSE
REFERENCE USE
LEVEL OF USE
CONTINUOUS USE
REFERENCE USE
INFORMATION USE
LOCATION
DURING USE
Procedure or
applicable section(s)
must be physically
present with worker
at the work
location.*
Procedure or
applicable section(s)
available at the
work location for
ready reference by
person performing
steps.
Available on plant
site for reference as
needed.
PERFORMANCE
OF STEPS
Each step
be
read before
performance
UNLESS steps are
designated in the
procedure as
"Immediate Action"
steps.
Refer to the procedure
before use and as
necessary to ensure
the work proceeds as
directed.
Need not proceed
step-by-step. Only
applicable steps need
to be done.
~~~
SIGNOFFS
MUST be completed
by the performer
upon completion of
each step, if
required.
~
~
be completed
by the performer
upon completion of
each step, if
required, but may be
delayed as the work
environment allows.
Not normally
required.
lY1'IUlll\\'C+T 10s
Ill:.,\\ QS.lliO! tequcrtrthc e\\aliiation of dcctgn options to rcducr the @*entia1 of rrathing il
hiilm$ ~oiidiliim
in 111c \\pent I:url I'cxd tSW\\. of lo $top pml ktling once i1 Wrl$ f t l i t re) icu
c\\;Iiiiiiirs iit$l ivil! opcfsliwal c h ~ n f o .
hut s)nicm ConfiprJtiolr chanpcc 1 s wcll It bhrwld he
iiotcd tliat a s)\\icm CY a n r m to stop J hiilinp rpcnt fuel p
~
l
IS tuyond the & r i p harir for
I.SP riid i h iwl\\idt Ihr haws a$ derrihed in the Technical Spcctfirrtionr.
Tlic iiraiit $11 hisc of Sff'rtwlinp it nondr!ennin~rtir lor the pufptHc of this rralurtim. Many
~\\qn.dcrl~bhm
friliirc nrthanionr could retult in the Imr or SIT coding. *u
include
niiiltiplc friluro of purnpr in thc SWccxilinp sptrrn or the tystcm's supwing coolins syrtcmr.
irruliiplt fJilittcs of cuppiitinp p w t r and/or ctmtrol s)strm% and pipinghihe failure. ln each
~ ~ t u a i i ~ ~ n .
the rouli of the loss of ccotinp capability is hcrt.up d r k S W from s p n t fuel decay
heat 1)cpciidinp vn ~ l i c cpiantit! of spcnt fucl prrcmhlies in the pwl and the residual hcrt
tii\\\\ip,wtl hy tlic arscmhlies. hcat.up may rrsult in crrr?prrrturcs exceding ck design hasis
iciriprratiirr of !tic Sfl', i e IW'F (we Syricm t)ctrriptioWDcsrgn Hasis below. Ref, 23). and
ilia) tv wlliciciit wfcruli in \\wiling of the pwl.
Lo\\s 01 SFP cwlinp n q wcur dunng any h l d c of plant npcrrltcwr. During and i m d i r t c l y
follti\\rinp rcfudinp cipcrrtions. the plential for SFP hoiling incrrrus I 8 the decry heat lord
from n w l y oflluidcd spent fuel rddr to the demand on the SFP cooling system and. therelore,
the n t c SI uhicli pw1 h c s t q would wcur if the SFP cooling iyrtem or one of its suppa
s)steins is lost.
A s itic rtccvcry lnm a kriling pol condition i s not a design hasir requirement of FhP and 1
boiling pwl in itrcll is ntq a condition detrimcnlal to plant safety. thcrc is no lim limit on *.hen
a h i l i n g pwI t))iist bc rcturned to J d c r i p basis condition.
dctermincd thdl Ihcrc I\\ no dctrinrnial impart of the hoiling condition to the SFP and Ik SfT'
cwlinc system. As such. repairs required to restore the cooling system($) to an operable
c,pndition can he pcrfimncd without regard to rim. and the suppning cooling system are
assumed to he a\\nilablc for hoiling pwl recor-eryactions.
SI'SlEhl DESCRIFTION~L~ICN
BASIS
Thc S W is dcrigned to pro\\idc underwater storage Cor spent fucl assemblies and control rods
aftcr ihcir removal fmm ccntainmcnt. The p o l i s filled with borated water and functions to
provide shielding during fuel handling operations. reduce the radioactive iodine released in the
ewnt of 8 fucl handling accident. and to n m v e spent fuel decay k a t .
may heat is removed from the pool through'rhc SFP cooling S&cm .Two LOO percent capacity
SFP cooling system trains circulate water through heat exchanges which Eject k a t to the
Component Cooling Water (COV) System.' A commo<discharge ksdct,ktums cooled water to
the pool. Opntirm of a single train provides enough Cooling capacity IO n ~ v e . t k
pool decay
heat durinfi normal. refueling. and accident conditions. such that the pool liner Id CmCfCte
' '
tcmpcrarure will remain hclow the design basis analysis limit of 1800F (Ref. 28);. This SFP
tous studies tHrfcrrnce 27) have
I
.
.
,
. . ::.
.
.
.
,
. ...
..:,