Inservice Inspection Program Plan, Revision 2, ASME Sec. XI Code Category, Page 141 - ASME Sec. XI Code Category F-A, Page 255
ML030430563
Person / Time
Site: Diablo Canyon  Pacific Gas & Electric icon.png
Issue date: 01/31/2003
From: Becker J
Pacific Gas & Electric Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
DCL-03-009, TAC MB1203, TAC MB1204
Download: ML030430563 (142)


Text

ASME Sec. Xl Clobe;ategory D-A ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

NOTE. Class 3 integral attachments are included with the support structure (Category F-A) when examination is required.

See Category F-A; Due to difference in format, pressure test tables follow Class 3 supports Page 141

ASME Sec. X 1 6.*Category D-B ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

See Category F-A; Due to difference in format, pressure test tables follow Class 3 supports Page 142

ASME Sec. XI C16-&.aegory D-C ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

See Category F-A; Due to difference in format, pressure test tables follow Class 3 supports Page 143

y ASME Sec. XI CoILJ'ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

All of the following Items are examined as applicable for each support (including snubbers) as follows F1.10 Mechanical connections to pressure retaining components and building structure F1 20 Weld connections to building structure F1.30 Weld and mechanical connetions at intermediate joints in multiconnected integral and nonintegral supports F1 40 Clearances of guides and stops, alignment of supports, assembly of support items F1.50 Spring supports and constant load supports F1 60 Sliding surfaces F1.70 Hot or cold position of spring supports and constant load supports 5300A Snubbers are also examined to the 1988 Addenda of OM-1987, Part 4 NOTE For multiple components in a Class 1 system, Loop 2 is chosen, for multiple Class 2 or 3 components, the lowest numbered or "A" line is selected, except when the lowest numbered or "A" line has no supports and the higher numbered line (or "B" or "C" line) does have supports Snubbers are shown for all non-exempt lines in the ISI boundary.

NOTE. Common Unit items are assigned to Unit 1; for multiple components, the lowest numbered is selected Page 144

ASME Sec. XI Co,*,...ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IS! DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Reactor Vessel Unit 1 Support Integrally forged nozzle pads rest directly on the building structure - no exam required Pressurizer Unit 1 Support Steam Generator 1-1 (Primary Side) Support Steam Generator 1-2 (Primary Side) Support Steam Generator 1-3 (Primary Side) Support Steam Generator 1-4 (Primary Side) Support Reactor Coolant Pump 1-1 Support Reactor Coolant Pump 1-2 Support Reactor Coolant Pump 1-3 Support Reactor Coolant Pump 1-4 Support Reactor Coolant Pump Suction Loop 1 Support Reactor Coolant Pump Suction Loop 2 Support Reactor Coolant Pump Suction Loop 2 Support Pressurizer 1-1 Steam Generator 1-1 Steam Generator 1-2 Steam Generator 1-3 Steam Generator 1-4 Reactor Coolant Pp 1-1 Reactor Coolant Pp 1-2 Reactor Coolant Pp 1-3 Reactor Coolant Pp 1-4

"*5-31SPL "6-31SPL "6-31SPL Support Skirt Not Selected Support Structure Not Selected Not Selected Not Selected Support Structure Not Selected Not Selected Not Selected Support A Support B Ul: 1 1-1 NOTES VT-3 3

VT-3 2

Vr-3 2

Ul. 1.2-1 Ul. 1.3-1 Ul' 1 3-1 Ul 1 3-1 Ul 1 3-1 Ul: 1 5-1 Ul: 1 5-1 Ut 1.5-1 U1 1 5-1 Ul 14-1 U1 14-2 Ul 1 4-2 Vr-3 VT-3 1

2 Page 145

ASME Sec. Xl C-..'Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IS! DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Reactor Coolant Pump Suction Loop 3 Support Reactor Coolant Pump Suction Loop 4 Support Reactor Coolant Out Loops

1. 2, 3 and 4 (support)

Reactor Coolant Pump Discharge Loop 1,2, 3 and 4 Pressurizer Surge Line Support Pressurizer Surge Line Support Pressurizer Surge Line Support Pressurizer Surge Line Support Pressurizer Surge Line Support Hot Leg Recirc Before V-8702 Support Hot Leg Recirc Before V-8702 Support Hot Leg Recirc Before V-8702 Support Hot Leg Recirc Before V-8702 Support Hot Leg Recirc Before V-8702 Support "7-31SPL "8-31SPL "1, *2, *3 and

  • 4-29SPL

"*9,

  • 10. *11 and

"*12-27 5SPL

"*16-14SPL

  • 16-14SPL "16-14SPL "16-14SPL
  • 16-14SPL S6-109-14SPL S6-109-14SPL S6-109-14SPL S6-109-14SPL S6-109-14SPL Ul. 1 4-3 Ul 1 4-4 NOTES Not Selected Not Selected No supports No supports51-24V 10-13SL 10-86SL 51-23V 51-25SL 56N-6V 56N-8V 12-3SL 56N-7V 12-144SL Ul 1 4-5 Ul 14-5 UI. 1 4-5 Ul: 1 4-5 UI: 1 4-5 Ul: 1 4-6 Ul 1 4-6 U1: 1.4-6 Ul: 1.4-6 Ul 14-6 VT-3 VT-3 Vr-3 vr-3 Vr-3 Vr-3 Vr-3 VT-3 VT-3 V--3 Page 146

ASME Sec. Xl Co'~ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Hot Leg Recirc Before V-8702 Support Loop 4 Hot Leg Before V-8701 Support Loop 4 Hot Leg Before V-8701 Support Loop 4 Hot Leg Before V-8701 Support Loop 4 Hot Leg Before V-8701 Support Loop 4 Hot Leg Before V-8701 Support Accumulator Injection Loop 1 Support Accumulator Injection Loop 1 Support Accumulator Injection Loop 1 Support Accumulator Injection Loop 2 Support Accumulator Injection Loop 2 Support Accumulator Injection Loop 2 Support Accumulator Injection Loop 3 Support Accumulator Injection Loop 3 Support S6-109-14SPL S6-1665-14SPL

$6-1665-14SPL S6-1665-14SPL S6-1665-14SPL S6-1665-14SPL S6-253-10SPL+

S6-253-10SPL+

S6-253-10SPL+

S6-254-10SPL+

S6-254-10OSPL+

S6-254-10SPL+

S6-255-1OSPL+

S6-255-1OSPL+

NOTES12-226SL 56N-4R 56N-5V 56N-3V 12-2SL 12-146SL 10-5SL 10-6SL Not Selected 10-4SL 52-24V 10-89SL 12-139SL Not Selected Ul: 1.4-6 Ul. 1 4-7 U" 1 4-7 Ul: 1.4-7 Ul 14-7 U1 1.4-7 Ul 1.4-8 Ul 14-8 Ul 1 4-8 Ul: 1 4-9 Ul. 1 4-9 Ul. 1.4-9 U1: 1.4-10 Ul: 1.4-10 V'-3 VT-3 VT-3 V'-3 Vr-3 VT-3 VT-3 VT-3 VT-3 V'-3 Vr-3 VT-3 Page 147

ASME Sec. XI CýieCategory F-A

'I7ýI SI*PROGRAMPLN.:

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Accumulator Injection Loop 4 Support SIS to RCS Loop 1 Hot Leg Support SIS to RCS Loop 1 Hot Leg Support SIS to RCS Loop 2 Hot Leg Support SIS to RCS Loop 2 Hot Leg Support SIS to RCS Loop 2 Hot Leg Support Safety Inj Loop 1 Hot Leg Support Safety Inj Loop 1 Hot Leg Support Safety Inj Loop 1 Hot Leg Support Safety Inj Loop 2 Hot Leg Support Safety Inj Loop 2 Hot Leg Support Safety Inj Loop 2 Hot Leg Support Safety Inj Loop 2 Hot Leg Support Safety Inj Loop 2 Hot Leg Support S6-256-10SPL+

S6-2575-8 S6-2575-8 S6-2576-8 S6-2576-8 S6-2576-8

$6-235-6SPL+

S6-235-6SPL+

S6-235-6SPL+

$6-236-6SPL+

S6-236-6SPL+

S6-236-6SPL+

S6-236-6SPL+

S6-236-6SPL+

NOTES Not Selected 10-34SL Not Selected 10-31 R 10-26SL 40-29R 10-24SL 10-25SL Not Selected 10-22R 10-21SL 10-30R 10-87R 10-133R UI" 1.4-11 Ul: 1.4-12 Ul. 1 4-12 UI: 1 4-12 Ul: 1 4-12 Ul: 1 4-12 Ul: 1 4-13 Ul: 1 4-13 Ul: 1 4-13 Ul: 1 4-14 Ut: 1.4-14 Ul 1.4-14 Ul 14-14 UI: 1.4-14 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 vr-3 Vr-3 VT-3 Page 148

ASME Sec. X1 CG-Zategory F-A D.iab

.no 2dIntra Rv ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Safety Inj Loop 3 Hot Leg Support Safety Inj Loop 3 Hot Leg Support Safety Inj Loop 4 Hot Leg Support RHR Pp 1-1 Inj Cold Leg 1 Support RHR Pp 1-1 Inj Cold Leg 2 Support RHR Pp 1-1 Inj Cold Leg 2 Support RHR Pp 1-1 Inj Cold Leg 2 Support RHR Pp 1-1 Inj Cold Leg 2 Support RHR Pp 1-1 Inj Cold Leg 2 Support RHR Pp 1-1 Inj Cold Leg 2 Support RHR Pp 1-1 Inj Cold Leg 2 Support RHR Pp 1-1 Inj Cold Leg 2 Support RHR Pp 1-1 Inj Cold Leg 2 Support RHR Pp 1-1 Inj Cold Leg 2 Support

$6-237-6SPL+

$6-237-6SPL+

$6-238-6SPL+

$6-3844-6SPL+

$6-3845-6SPL+

$6-3845-6SPL+

S6-3845-6SPL+

S6-3845-6SPL+

$6-3845-6SPL+

S6-3845-6SPL+

S6-3845-6SPL+

S6-3845-6SPL+

$6-3845-6SPL+

$6-3845-6SPL+

NOTES12-137SL Not Selected Not Selected Not Selected 11-82SL 11-16SL 11-79SL 11-15SL 11-81SL 42-43V 42-44V 11-80SL 42-42V 42-54V UI: 1.4-15 Ul: 1.4-15 UI. 1.4-16 Ul 1 4-17 Ul 1 4-18 Ul: 1.4-18 Ul 14-18 UI 1.4-18 Ul 1 4-18 Ul: 1 4-18 Ul: 1 4-18 Ul. 1.4-18 Ul: 1 4-18 Ul: 1.4-18 VT-3 VT-3 Vr-3 VT-3 Vr-3 Vr-3 VTr-3 VT-3 Vr-3 VT-3 VT-3 Page 149

ASME Sec. Xl Cv.*ategory F-A ITEM PARTS EXAMINED COM P/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

RHR Pp 1-2 Inj Cold Leg 3 Support RHR Pp 1-2 Inj Cold Leg 3 Support RHR Pp 1-2 Inj Cold Leg 3 Support RHR Pp 1-2 Inj Cold Leg 4 Support Pressunzer RV-8010A Inlet Support Pressurizer RV-8010A Inlet Support Pressurizer RV-8010B Inlet Support Pressurizer RV-8010B Inlet Support Pressurizer RV-8010C Inlet Support Pressurizer RV-8010C Inlet Support Pressurizer Power RV Inlet Support Pressurizer Power RV Inlet Support Pressurizer Power RV Inlet Support Pressurizer RV PCV-455C Inlet Support S6-3846-6SPL+

S6-3846-6SPL+

S6-3846-6SPL+

S6-3847-6SPL+

S6-729-6SPL S6-729-6SPL S6-728-6SPL S6-728-6SPL S6-727-6SPL S6-727-6SPL S6-730-6SPL S6-730-6SPL S6-730-6SPL S6-4081-4SPL NOTES 13-7SL 13-9SL Not Selected Not Selected 48-1R 11-44SL 11-43SL Not Selected 11-42SL Not Selected 48-26CS11-130SL 11-21SL 11-22SL Ul: 1.4-19 U1. 1.4-19 Ul 1.4-19 Ul. 1.4-20 UI' 1 4-21 Ul 1 4-21 U1 1 4-22 Ul. 1.4-22 Ul 1 4-23 U1" 1 4-23 Ul: 1 4-24 Ut: 1.4-24 Ut: 1.4-24 Ul. 1 4-24 V'-3 VT-3 VT-3 vr-3 Vr-3 VT-3 VT-3 VT-3 VT-3 Vr-3 Page 150

ASME Sec. XI ComeCategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Loop 1 Spray Line Support S6-13-4SPL 11-105SL U1. 1.4-25 VT-3 3

Loop 1 Spray Line Support S6-13-4SPL 11-110SL Ul: 1.4-27 VT-3 3

Loop 1 Spray Line Support S6-13-4SPL Not Selected U1. 1 4-26 Loop 2 Spray Line Support S6-14-4SPL 52-19V U1.1 4-28 VT-3 1

Loop 2 Spray Line Support S6-14-4SPL 42-63R Ul: 1 4-25 VT-3 1

Loop 2 Spray Line Support S6-14-4SPL 10-128SL UI: 1 4-28 VT-3 1

Loop 2 Spray Line Support S6-14-4SPL 10-129SL Ul: 1 4-28 VT-3 1

Loop 2 Spray Line Support S6-14-4SPL 10-131SL Ul: 1.4-28 VT-3 1

Loop 2 Spray Line Support

$6-14-4SPL 11-136SL U1-14-28 V'-3 1

Loop 2 Spray Line Support S6-14-4SPL 11-135SL U1. 1.4-28 VT-3 1

Loop 2 Spray Line Support

$6-14-4SPL 52-18R U1 1 4-28 VT-3 2

Loop 2 Spray Line Support S6-14-4SPL 11-19R U1. 1 4-25 VT-3 2

Loop 2 Spray Line Support

$6-14-4SPL 42-62R UI. 1 4-25 VT-3 2

Loop 2 Spray Line Support

$6-14-4SPL 10-41R U1. 1.4-28 VT-3 2

Page 151

ASME Sec. Xl Clo'Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Loop 2 Spray Line Support

$6-14-4SPL 11-17SL Ul. 14-25 VT-3 I

Loop 2 Spray Line Support S6-14-4SPL 11-18SL Ul 1.4-25 VT-3 1

Loop 2 Spray Line Support

$6-14-4SPL 11-139SL UI: 1.4-25 VT-3 1

Loop 2 Spray Line Support S6-14-4SPL 52-16R Ul 1.4-28 VT-3 3

Loop 2 Spray Line Support S6-14-4SPL 52-17R Ul: 1 4-28 VT-3 3

Loop 2 Spray Line Support

$6-14-4SPL 11-137R Ul: 1 4-28 VT-3 3

Loop 2 Spray Line Support

$6-14-4SPL 52-36V U1: 1.4-28 VT-3 3

Loop 2 Spray Line Support

$6-14-4SPL 11-138SL Ul: 1.4-28 VT-3 1

Pressurizer Spray Line S6-15-4SPL 42-5R UI: 1.4-29 VT-3 1

Support Pressurizer Spray Line

$6-15-4SPL 11-142SL U1: 1 4-29 V'-3 2

Support Pressurizer Spray Line S6-15-4SPL 11-143R Ul: 14-29 VT-3 1

Support Pressurizer Spray Line

$6-15-4SPL 11-24SL UI: 1.4-29 VT-3 1

Support Pressurizer Spray Line S6-15-4SPL 42-3R Ul 1 4-29 VT-3 2

Support Pressurizer Spray Line

$6-15-4SPL 42-75R UI: 1.4-29 VT-3 2

Support Page 152

ASME Sec. XI Cbui. Category F-A IS POGAMPAN Diabo1Cnvon2ndInevlR

.2 ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Loop 1 Stub [3" former RTD connection](support)

Loop 2 Stub [3" former RTD connection](support)

Loop 3 Stub [3" former RTD connection](support)

Loop 4 Stub [3" former RTD connection](support)

Charging Line Loop 4 Support Charging Line Loop 3 Support NOTES S6-15-4SPL S6-15-4SPL S6-155-4SPL S6-15-4SPL S6-15-4SPL S6-15-4SPL S6-15-4SPL S6-15-4SPL S6-1141-3SPL

$6-1147-3SPL S6-1153-3SPL

$6-1158-3SPL S6-246-3SPL S6-50-3SPL 43-1R 42-4V 11-10OR 42-64V 11-144R 43-1OCS48-22CS 11-150R No supports No supports No supports No supports Not Selected 56N-1 32V Ul. 1 4-29 Ul 1 4-29 Ul 1 4-29 Ul: 1.4-29 Ul 1.4-29 Ul 1.4-29 U1 1.4-29 U" 1.4-29 Ul 1 4-30 UI 1 4-31 Ul. 1.4-32 Ul. 1.4-33 Ul: 1 4-34 Ul. 1.4-35 Vr-3 V"-3 VT-3 V1r-3 Vr-3 vr-3 VT-3 Vr-3 VT-3 Page 153 J

ASME Sec. Xl CbU-/Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr (support)

Letdown Line Loop 2 Support Letdown Line Loop 2 Support Letdown Line Loop 2 Support Letdown Line Loop 2 Support Letdown Line Loop 2 Support Letdown Line Loop 2 Support S6-1995-3 S6-1995-3 S6-1995-3 S6-1995-3 S6-1995-3 S6-1995-3 S6-1995-3 S6-1016-3

$6-24-3SPL S6-24-3SPL

$6-24-3SPL S6-24-3SPL S6-24-3SPL S6-24-3SPL 57N-34R 57N-33R 12-94SL 57N-35R 57N-76R 12-102R 57N-102V No supports39-25R 52-3V 52-4R 52-31 R 52-9V 52-41R Ul: 1.4-36 VT-3 1

U l. 1 4-36 Ul. 1 4-36 Ul: 1.4-36 Ul: 1 4-36 Ul 1 4-36 Ul 1.4-36 UI 1.4-36 Ul 1 4-37 Ul. 1.4-37 Ul: 1 4-37 Ul: 1 4-37 Ul. 1.4-38 VT-3 Vr-3 VT-3 Vr-3 VT-3 Vr-3 VT-3 V'r-3 VT-3 Vr-3 Vr-3 U1.14-38 VT-3 3

Page 154 NOTES J

KU ASME Sec. XI Coc*-tCategory F-A I

I POGAMPLN.

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Pressurizer Power RV PCV-474 Support Pressurizer Power RV PCV-474 Support Pressurizer Power RV PCV-474 Support Pressurizer Power RV PCV-474 Support Pressurizer Power RV PCV-474 Support Pressurizer Power RV PCV-474 Support Pressurizer Power RV PCV-474 Support Pressurizer Power RV PCV-455C Support Pressurizer Power RV PCV-455C Support Pressurizer Power RV PCV-455C Support Pressurizer Power RV PCV-455C Support Pressurizer Power RV PCV-455C Support Pressurizer Power RV PCV-456 Support Pressurizer Power RV PCV-456 Support S6-1171-3SPL+

S6-1171-3SPL+

S6-1171-3SPL+

S6-1171-3SPL+

S6-1171-3SPL+

S6-1171-3SPL+

$6-1171-3SPL+

S6-1172-3SPL+

S6-1172-3SPL+

S6-1172-3SPL+

$6-1172-3SPL+

$6-1172-3SPL+

S6-1195-3SPL+

S6-1195-3SPL+

11-14SL 11-96SL 11-97SL UI: 1 4-24 VT-3 2

Ul: 1.4-24 Ul: 1.4-24 11-153SL 11-154SL 11-155SL Not Selected 48-27V 48-29A 11-148R 11-149R 11-131SL 11-94SL 11-95SL vr-3 vr*3 2

2 Ul: 1 4-24 Vr-3 2

Ul' 1 4-24 Ul 1 4-24 Ul: 1 4-24 Ul: 1 4-24 Ul: 1 4-24 Ul 1 4-24 Ul. 1.4-24 Ul" 1.4-24 Ul. 1.4-39 Ul 1.4-39 vr-3 v-r-3 VT-3 VT-3 VT-3 V'-3 VT-3 V'r-3 Page 155 NOTES

K1 ASME Sec. XI Cb6-ategory F-A Diabl Ca*

n2ndInt, a

e.

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Pressurizer Power RV PCV-456 Support Pressurizer Power RV PCV-456 Support Pressurizer Power RV PCV-456 Support Pressurizer Power RV PCV-456 Support Pressurizer Power RV PCV-456 Support Pressurizer Power RV PCV-456 Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support S6-1195-3SPL+

S6-1195-3SPL+

S6-1195-3SPL+

S6-1195-3SPL+

S6-1195-3SPL+

S6-1195-3SPL+

$6-51-2SPL+

$6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

NOTES11-124SL 11-125SL 11-126SL 11-127SL 11-132SL Not Selected 181-29 181-35 2152-13 2152-72 2180-15 43-3R 2152-14 181-30 U" 1.4-39 Ul: 1 4-39 U.

1 4-39 Ul. 1.4-39 Ul: 1 4-39 Ul: 1.4-39 Ul: 1 4-40B UI" 1.4-40B Ul 1 4-40A Ul: 1 4-40A UI: 1 4-41 Ul 14-41 Ul. 1 4-40A Ul: 1.4-40B VT-3 Vr-3 VT-3 Vr-3 vr-3 VT-3 V-r-3 VT-3 vr-3 Vr-3 vr-3 VT-3 VT-3 Page 156

<-I ASME Sec. Xi Cb,.eCategory F-A PROGAMPAN Diabl 'anv 2ndIntralRv ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support NOTES S6-51-2SPL+

S6-51-2SPL+

$6-51-2SPL+

$6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

$6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

$6-51-2SPL+

$6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

2152-19 2180-42V 22-398R 23-2A 22-70R 181-31 2185-19 22-399R 22-62R 23-IA 2180-16 181-28 2152-15 43-2R UI: 1 4-40A Ul: 1 4-41 Ul: 1 4-41 Ul: 1 4-40A Ul. 1 4-40B Ul. 1 4-40B Ul 1 4-41 U1 1.4-41 Ul: 1 4-40A UI: 1.4-40B U1 1 4-41 Ul 1.4-40B Ul: 1.4-40A UI: 1 4-41 VT-3 VT-3 VT-3 VT-3 VT-3 Vr-3 V'-3 Vr-3 VT-3 VT-3 VT-3 Vr-3 V"-3 VT-3 Page 157

Diablo v

ndIntrvl ev* 2 ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IS! DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray (support)

S6-51-2SPL+

$6-51-2SPL+

$6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

S6-51-2SPL+

S6-4532-2SPL+

Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-2 Seal Wtr In Support Reac Cool Pp 1-2 Seal Wtr In Support Reac Cool Pp 1-2 Seal Wtr In Support Reac Cool Pp 1-3 Seal Wtr In Support S6-54-2 S6-54-2 S6-55-2 S6-55-2 S6-55-2 S6-56-2 22-211ISL Not Selected 47-11 22-154SL 22-155SL 22-289SL U1: 14-42 VI-3 Ul. 1 4-42 UI" 14-43 VT-3 Ul 1 4-43 VT-3 Ul. 1.4-43 VT-3 Ul 1.4-44 VT-3 Page 158 NOTES 2152-9 2152-17 2180-18 2152-12 2152-18 2152-63 Not Selected VT-3 Vr-3 VT-3 VT-3 VT-3 VT-3 Ul: 1.4-40A Ul 1 4-40A Ul. 1 4-41 Ul 14-40A Ul 14-40A Ul' 1 4-40A Ul: 1 4-40B 3

3 3

3 3

3 2

2 1

I 3

ASME Sec. Al G*._JCategory F-A

K-I ASME Sec. Xl Coee Category F-A AI PRORAM LAN' ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Reac Cool Pp 1-3 Seal Wtr In Support Reac Cool Pp 1-4 Seal Wtr In Support Loop 1 Cold Leg Drain RCDT (support)

Loop 2 Cold Leg Drain RCDT Support Loop 3 Cold Leg Drain RCDT (support)

Loop 4 Cold Leg Drain RCDT Support SI Pp 1-1 Inj Hot Leg Loop 1 (support)

SI Pp 1-1 Inj Hot Leg Loop 2 (support)

Safety Inj Hot Leg Loop 3 Support Safety Inj Hot Leg Loop 3 Support Safety Inj Hot Leg Loop 4 (support)

SI Pps Cold Leg Loop 1 Recirc (support)

SI Pps Cold Leg Loop 2 Recirc (support)

SI Pps Cold Leg Loop 3 Recirc Support S6-56-2 S6-57-2 S6-958-2SPL+

S6-959-2SPL+

$6-960-2SPL+

S6-961-2SPL+

S6-3863-2 S6-3864-2 S6-1976-2 S6-1976-2 S6-1990-2

$6-3855-2SPL+

$6-3856-2SPL+

$6-3857-2SPL+

NOTES Not Selected Not Selected No supports 2169-42 No supports Not Selected No supports No supports 12-69SL 12-70SL No supports No supports No supports 2156-35 Ul. 1 4-44 Ul. 1 4-45 UI 1 4-46 UI" 1 4-47 U1 1 4-48 Ul 1.4-49 Ul. 1 4-50 Ul: 1.4-51 Ul: 1.4-52 Ul: 1 4-52 Ul: 1 4-53 Ul: 1 4-17 Ul: 1 4-18 UI: 1.4-54 VT-3 VT-3 V'-3 VT-3 Page 159

"ASME Sec. XI Co Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IST DWG.

NDE PER. LINE-TOTL RELIEF REQ.

SI Pps Cold Leg Loop 3 Recirc Support SI Pps Cold Leg Loop 3 Recirc Support SI Pps Cold Leg Loop 3 Recirc Support SI Pps Cold Leg Loop 4 Recirc Support Loop 1 Cold Leg RCS Vent and Fill Support Loop 2 Cold Leg Stub

[former RTD connection]

Loop 3 Cold Leg Stub

[former RTD connection]

Loop 4 Cold Leg Stub

[former RTD connection]

Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support S6-3857-2SPL+

S6-3857-2SPL+

$6-3857-2SPL+

S6-3858-2SPL+

S6-1140-2SPL S6-1146-2SPL S6-1152-2SPL S6-1159-2SPL S6-1991-1 5 S6-1991-1 5 S6-1992-1 5 S6-1992-1 5 S6-1992-1.5 S6-1992-1 5 NOTES 2156-36 2156-37 2157-8 Not Selected 23-283R No supports No supports No supports22-410SL Not Selected 2156-66 2156-82 2156-84 2182-44 Ul: 1 4-54 Ul 1.4-54 Ul 1 4-54 Ul 1 4-55 Ul. 14-60 Ul 1 4-61 Ul 1 4-62 Ul" 1.4-63 Ul: 1.4-66 Ul: 1.4-66 U 1:1.4-67 Ul 1 4-67 U1.1 4-67 U1.1.4-68 Vr-3 VT-3 VT-3 Vr-3 vr-3 V'-3 V'-3 VT-3 V'-3 Page 160

K>

ASME Sec. Xl Cc>.e-Category F-A IS POGAM AN I.V.

2.

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charging Inj Out Loop 2 Cold Leg Support ChargingInj Out Loop 2 Cold Leg Support Charging lnj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging lnj Out Loop 2 Cold Leg Support Charginglinj Out Loop 2 Cold Leg Support Charging lnj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging lnj Out Loop 2 Cold Leg Support CharginglIn Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support ChargingInj Out Loop 2 Cold Leg Support ChargingInj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support S6-1992-1.5 S6-1992-1 5 S6-1992-1.5 S6-1992-1 5 S6-1992-1 5 S6-1992-1 5 S6-1992-1 5 S6-1992-1 5 S6-1992-1 5 S6-1992-1 5 S6-1992-1 5 S6-1992-1.5 S6-1992-1.5 S6-1992-1.5 2155-68 2156-68 2156-87 2169-24 2182-41 2156-86 2169-25 2182-40 23-12A 2156-65 2156-83 2156-88 2169-21 2169-33 U1:1 4-68 VT-3 UV1" 4-67 VT-3 U1.1.4-67 VT-3 U1:14-69 Vr-3 U1 1 4-69 VT-3 Ul 1 4-67 VT-3 Ul 1 4-69 Vr-3 Ul 1.4-68 VT-3 U1I1.4-69 VT-3 U1:1.4-67 VT-3 Ul 1.4-67 VT-3 U1:1 4-67 V-r-3 U1:1 4-69 VT-3 U1.1.4-69 VT-3 Page 161 NOTES

ASME Sec. XI L,__.Category F-A isi ROGAM PAW:,

3ibl. g

-on2ndIntrvl e*2 ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support Charging Inj Out Loop 3 Cold Leg Support Charging Inj Out Loop 3 Cold Leg Support Charging Inj Out Loop 4 Cold Leg Support S6-1992-1.5 S6-1992-1.5 S6-1992-1.5 S6-1992-1 5 S6-1992-1 5 S6-1992-1 5 S6-1992-1 5 S6-1992-1 5 S6-1992-1.5 S6-1992-1 5 S6-1992-1 5 S6-1993-1 5 S6-1993-1 5 S6-1994-1.5 2182-43 2156-81 2169-22 2169-34 2182-42 2156-67 2156-85 2169-19 2169-23 2182-45 2169-32 22-545SL Not Selected 22-411SL U1:1.4-68 V'-3 3

U1:1 4-67 U1.1.4-69 U1:1.4-69 Ul 1 4-68 U1.1 4-67 Ul 1 4-67 Ul 1 4-69 Ul 1 4-69 U1 1.4-68 Ul 1 4-69 Ul: 1.4-71 Ul: 1 4-71 UI. I 4-65B VT-3 V'T-3 VT-3 VT-3 V'-3 Vr-3 VT-3 VT-3 VT-3 V'I-3 VT-3 Page 162 K>

NOTES

ASME Sec. X, C'o Category F-A JSIPRGRA PAN Diabl. Cnvo:,

n Ineral ev 2 ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF REQ.

Charging Inj Out Loop 4 Cold Leg Support Steam Generator 1-1 (Secondary Side) Support Steam Generator 1-1 (Secondary Side) Support Steam Generator 1-1 (Secondary Side) Support Steam Generator 1-1 (Secondary Side) Support Steam Generator 1-2 (Secondary Side) Support Steam Generator 1-2 (Secondary Side) Support Steam Generator 1-2 (Secondary Side) Support Steam Generator 1-2 (Secondary Side) Support Steam Generator 1-3 (Secondary Side) Support Steam Generator 1-3 (Secondary Side) Support Steam Generator 1-3 (Secondary Side) Support Steam Generator 1-3 (Secondary Side) Support Steam Generator 1-4 (Secondary Side) Support S6-1994-1.5 Steam Generator 1-1 Steam Generator 1-1 Steam Generator 1-1 Steam Generator 1-1 Steam Generator 1-2 Steam Generator 1-2 Steam Generator 1-2 Steam Generator 1-2 Steam Generator 1-3 Steam Generator 1-3 Steam Generator 1-3 Steam Generator 1-3 Steam Generator 1-4 NOTES Not Selected SG-01-01-NE (snubber)

SG-01-01-NW (snubber)

SG-01-01-SE (snubber)

SG-01-01-SW (snubber)

SG-01-02-NE (snubber)

SG-01-02-NW (snubber)

SG-01-02-SE (snubber)

SG-01-02-SW (snubber)

SG-01-03-NE (snubber)

SG-01-03-NW (snubber)

SG-01-03-SE (snubber)

SG-01-03-SW (snubber)

SG-01-04-NE (snubber)

Ul 1.4-65B UI: 2.1-1 UI: 2.1-1 Ul: 2 1-1 Ul: 2 1-1 Ul' 2 1-1 Ul: 2 1-1 Ul: 2 1-1 Ul 2 1-1 U1. 2.1-1 Ul 21-1 UI" 2.1-1 Ul. 2.1-1 Ul 2 1-1 vr-3 VT-3 VT-3 VT-3 vr-3 VT-3 Vr-3 VT-3 V1-3 VT-3 VT-3 VT-3 VT-3 Page 163 I,-,)

ASME Sec. X1 C6xetategory F-A 611ý 7.ý..ý.

.ý,ýIS

.P O

G AM P

A Dialo31

.n26 Ineral ev 2

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Steam Generator 1-4 (Secondary Side) Support Steam Generator 1-4 (Secondary Side) Support Steam Generator 1-4 (Secondary Side) Support Seal Injection Filter 1-1 Support Seal Injection Filter 1-2 Support Residual Ht Removal HX 1-1 (Class 2 Side) Support Residual Ht Removal HX 1-2 (Class 2 Side) Support Residual Heat Removal Pump 1-1 Support - Pump rests on plate embedded in building structure - no exam required Residual Heat Removal Pump 1-1 Support Steam Generator 1-4 Steam Generator 1-4 Steam Generator 1-4 Seal Injection Filter 1-1 Seal Injection Filter 1-2 RHR HX 1-1 RHR HX 1-2 RHR Pump 1-1 (motor)

SG-01-04-NW (snubber)

SG-01-04-SE (snubber)

SG-01-04-SW (snubber)

Not selected 3 Support Legs Two Support Legs Not selected 4-22SL (snubber)

Ul 2 1-1 VT-3 2

U1.2.1-1 VT-3 2

Ul 2 1-1 VT-3 2

Ul 2 1-3 Ul 2 1-3 V'-3 1

U1: 2 1-6 V'-3 2

Ul: 2 1-6 Ul: 2 3-1 U 12.3-1 VT-3 I

Page 164 NOTES

ASME Sec. XI C~oe--ategory F-A ITEM PARTS EXAMINED CONIP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Residual Heat Removal Pump 1-1 Support Residual Heat Removal Pump 1-2 Support Residual Heat Removal Pump 1-2 Support Residual Heat Removal Pump 1-2 Support Safety Injection Pump 1-1 Support Safety Injection Pump 1-2 Support Centrifugal Charging Pump 1-1 Support Centrifugal Charging Pump 1-2 Support RHR Pump 1-1 (motor)

RHR Pump 1-2 (motor)

RHR Pump 1-2 (motor)

RHR Pump 1-2 support SI Pump 1-1 SI Pump 1-2 CCP 1-1 CCP 1-2 4-23SL (snubber) 4-20SL (snubber) 4-21SL (snubber)

Not selected (N/A)

Pump Pedestals and Base Not Selecetd Four Support Legs and Base Not Selected Loop 4 Hot Leg to RHR Pps Support Loop 4 Hot Leg to RHR Pps Support Loop 4 Hot Leg to RHR Pps Support Loop 4 Hot Leg to RHR Pps Support Loop 4 Hot Leg to RHR Pps Support NOTES Vr-3 Vr-3 VT-3 1

1 1

Ul: 2 3-1 Ul: 2 3-1 Ul 23-1 Ul 23-1 Ul" 23-2 Ul 23-2 Ul" 23-3 Ul: 23-3 V'-3 vr-3 S1-927-14111 SI-927-141I1 S1-927-14111 S1-927-14111 S1-927-14111 57S-20V 56N-2R 12-7SL 12-133R 12-136R UI. 22-2 UI 22-1 Ut 22-I UI.2 2-I UI.2 2-I VT-3 VT-3 VT-3 Vr-3 Vr-3 1

1 2

2 2

Page 165 1

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF NOTES REQ.

Loop 4 Hot Leg to RHR Pps S1-927-14111 12-145SL U["22-1 VT7-3 2

Support Residual Heat Exchr I Outlet SI-3551-14111 288-11IR UI 22-3 VT-3 3

Support RHR Pump I-I Suction Support SI-110-14111 54S-26R UI 2 2-11 V'-3 1

RHR Pump I-I1Suction Support SI-I10-14111 15-5SL UI 22-2 V"-3 1

RHR Pump 1-1 Suction Support SI-110-14111 72-41R UI 22-11 VT-3 2

R1R Pump 1-I Suction Support SI-I110-14111 55S-90A UI. 2 2-2 VT-3 3

RIMRPump I-I Suction Support SI-110-14111 57S-21 V UI 22-2 V'-3 3

RHR Pump I-I Suction Support SI-ll0-14111 72-13V U1 22-11 VT-3 3

RHR Pump 1-2 Suction Support SI-11-141111 5-4SL UI 22-2 VT-3 1

RHR Pump 1-2 Suction Support SI-111-14111 15-96SL U1 22-2 VT-3 1

RHR Pump 1-2 Suction Support Si-I 1-14111 Not Selected Ul: 2 2-2 ContSmpto RHRPp 1-1 Suct SI-512-14111P 54S-IV U1 22-11 VT-3 1

Support Cont Smp to RHR Pp I-I Suct SI-512-14111P 54S-5R UI.L2.2-11 VT-3 1

Support ContSmptoRHRPp I-I Suct SI-512-1411IP 72-12R UI 22-11 VT-3 2

Support Page 166 ASME Sec. XI1 &P.Aategory F-A

ASME Sec. XI Co-atCategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. L1NE-TOTL RELIEF NOTES REQ.

ContSmptoRHRPp 1-1 Suet SI-512-14111P 54S-3A Ut 22-11 VT-3 2

Support ContSmptoRHRPp 1-1 Suct SI-512-141llP 54S-28R Ut 22-11 VT-3 3

Support ContSmptoRHRRPp 1-2Suct SI-513-14111P Not Selected Ut 22-12 Support RHR Injection to Hot Leg l& 2 S6-120-12 No Supports UI: 2 2-4 (support)

RHR Injection to Hot Leg l&2 SI-985-12111P 40-46A UI. 2 2-5 VT-3 1

Support RHR Injection to Hot Leg l&2 S1-985-12111P 15-112R UI: 2 2-7 VT-3 1

Support RHR Injection to Hot Leg 1&2 SI-985-12111P 15-69SL UI 22-7 VT-3 1

Support RHR Injection to Hot Leg 1&2 SI-985-12111P 12-228SL UI 2 2-6 VT-3 2

Support RHR Injection to Hot Leg 1&2 SI-985-121I1P 57N-153R UI. 2 2-6 VT-3 1

Support RHR Injection to Hot Leg 1&2 SI-985-12111P 40-45R UI 22-4 VT-3 1

Support RHR Injection to Hot Leg 1&2 SI-985-12111P 40-50R UI 2 2-5 VT-3 2

Support RHR Injection to Hot Leg 1&2 SI-985-12IIIP 10-18SL UI 2 2-5 VT-3 3

Support RHR Injection to Hot Leg 1&2 SI-985-12111P 10-19SL UI 22-5 VT-3 3

Support RHR Injection to Hot Leg 1&2 SI-985-12111P 57N-152R Ul. 22-6 VT-3 1

Support Page 167

ASME Sec. XI C'obe3ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

RHR Injection to Hot Leg l&2 SI-985-12111P 40-44R UI 22-4 VT-3 2

Support RHRInjectionto Hot Leg 1&2 SI-985-12111P 57N-15IR Ut 22-6 VT-3 2

Support RHR Injection to Hot Leg 1&2 SI-985-12111P 57S-24V U[I"2 2-7 VT-3 2

Support RHR Injection to Hot Leg 1&2 SI-985-12111P 57S-68R UI 22-7 VT-3 2

Support RHR Injection to Hot Leg l&2 SI-985-12111P 40-47R UI 2 2-5 VT-3 3

Support RHR Injection to Hot Leg 1 &2 SI-985-12111P 40-59R UI 22-5 VT-3 3

Support RHR Injection to Hot Leg 1&2 S1-985-12111P 56N-28R Ul[ 2 2-5 VT-3 3

Support RHR Injection to Hot Leg 1&2 SI-985-12111P 56N-78R UI: 2 2-5 VT-3 3

Support RHR Injection to Hot Leg l&2 SI-985-12111P 56N-79R Ut 22-5 VT-3 3

Support RHRInjection to Hot Leg 1&2 SI-985-12IIIP 12-34SL UI. 2 2-5 VT-3 2

Support RIIR Injection to Hot Leg l&2 SI-985-12111P 10-39SL UI 2 2-4 VT-3 3

Support RHR Injection to Hot Leg 1&2 SI-985-12111P 10-35SL UI'-2 2-4 V'-3 3

Support RWST to RHR Pps Suction SI-223-12111P No supports UI 2 2-2 (support)

RHR Pp 1-1Inj Cold Leg 1&2 S6-508-8I11 42-48R Ut 2 2-32 VT-3 1

Support Page 168

ASME Sec. Xl Cdu-category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOT, RELIEF NOTES REQ.

RHR Pp 1-1 Inj Cold Leg l&2 S6-508-8111 42-50R UI 2 2-32 VT-3 1

Support RHR Pp 1-1 Inj Cold Leg l&2 S6-508-8111 42-52R U1: 2 2-31 VT-3 1

Support RHR Pp h-1 InjCold Leg 1 &2 S6-508-8111 56N-119R UI 22-30 VT-3 1

Support RHRPp 1-1 Inj Cold Leg l&2 S6-508-8111 58N-SOR UI 22-31 V'-3 1

Support RHRPp 1-1 Inj Cold Leg l&2 S6-508-8111 58N-51R Ui 22-31 V'-3 1

Support RHR Pp 1-1 inj Cold Leg 1&2 S6-508-8IIi 42-76R UI 2 2-32 VT-3 1

Support RHR Pp 1-1 Inj Cold Leg l&2 S6-508-8111 1 1-37SL UI 2.2-30 VT-3 3

Support RHR Pp 1-1 In.j Cold Leg l&2 S6-508-8111 42-81R U 1. 22-32 VT-3 2

Support RHR Pp 1-1 lnj Cold Leg l&2 S6-508-8111 11-36SL UI. 2 2-32 VT-3 3

Support RHR Pp 1-1I lnj Cold Leg l&2 S6-509-8111 42-46R U1. 2 2-32 Vr-3 2

Support RHR Pp h-1 Inj Cold Leg l&2 S6-508-8111 42-68R Ul 22-32 VT-3 2

Support RHR Pp 1-1 Inj Cold Leg l&2 S6-508-8II!

56N-121R UI 2 2-31 VT-3 2

Support RHR Pp 1-1 lnj Cold Leg 1&2 S6-508-8111 42-47R UI 2 2-32 VT-3 2

Support RHR Pp 1-1 Inj Cold Leg l&2 S6-508-81II 42-49R U1 2 2-32 VT-3 2

Support Page 169

ASME Sec. Xl C1..

C ategory F-A A

A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF NOTES REQ.

RHR Pp 1-1 Inj Cold Leg l&2 S6-508-8111 42-77R U1 2 2-32 V'-3 2

Support RHR Pp 1-1 Inj Cold Leg l&2 S6-508-8111 56N-122R U1. 22-31 VT-3 2

Support RHR Pp 1-1 Inj Cold Leg l&2 S6-508-8111 58N-49R Ul. 22-31 VT-3 3

Support RHR Pp I-I Inj Cold Leg l&2 S6-508-8111 58N-52A U1: 2 2-31 VT-3 3

Support RHR Pp 1-I Inj Cold Leg 1&2 S6-508-811I 11-35SL U1: 2 2-32 V'-3 3

Support RHR Pp 1-I Inj Cold Leg 1&2 S6-508-8111 42-51R U1 2 2-31 Vr-3 3

Support RHR Pp 1-1 Inj Cold Leg 1&2 S6-508-8111 56N-140R Ul.L2 2-30 VT-3 3

Support RHR Pp 1-1 Inj Cold Leg l&2 S6-508-8111 58N-53R UI 22-31 VT-3 3

Support RHR Pp 1-1 Inj Cold Leg 1&2 S6-508-8111 42-45R UI" 2 2-32 VT-3 3

Support RHR Pp 1-1 Inj Cold Leg 1&2 S6-508-8111 56N-120R UPI2 2-30 V'-3 3

Support RHR Pp 1-! Inj Cold Leg 1&2 S6-508-81Il 15-65SL Uh: 2 2-30 VT-3 1

Support RHR Pp 1-1 Inj Cold Leg l&2 S6-508-8111 15-66SL U1:2 2-30 VT-3 I

Support RHR Pp 1-2 Inj Cold Leg l&2 S6-509-8111 15-79SL U1. 2 2-33 V'-3 1

Support RHR Pp 1-2 Inj Cold Leg l&2 S6-509-8111 15-80SL UI. 2 2-33 V'-3 1

Support Page 170

ASME Sec. XI Code Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

RHR Pp 1-2 lnj Cold Leg l&2 S6-509-8111 Not Selected UI 2 2-33 Support SIS to RCS Hot Leg Loop I S6-2575-8 40-26V Ut: 2 2-4 VT-3 1

Support SIS to RCS Hot Leg Loop 2 S6-2576-8 10-33SL Ul: 2 2-4 VT7-3 3

Support SIS to RCS Hot Leg Loop 2 S6-2576-8 I0-132SL UI. 2 2-4 VT-3 3

Support Centr Chg Pps Disch Hdr Support S6-1454-6 73-36R Ul: 2 2-10 VT-3 1

Centr Chg Pps Disch Hdr Support S6-1454-6 54S-19R Ul: 2 2-10 Vr-3 2

Centr Chg Pps Disch Ildr Support S6-1454-6 73-41R Ut 2 2-10 VT-3 2

Centr Chg Pps Disch Hdr Support S6-1454-6 54S-I8R U1 22-10 Vr-3 3

Centr Chg Pps Disch Hdr Support S6-1454-6 54S-16R U1 22-10 VT-3 3

Charging Pps Disch Emerg S6-1973-6 54S-21R Ul: 2 2-10 V17-3 2

Support Charging Injection Inlet Support S6-2032-6 54S-1 IV UI: 2 2-19 VT-3 2

RHR Pp 1-1 Inj Cold Leg Lp 1 S6-3844-6111 11-20R UI 2 2-34 V'-3 1

Support RHR Pp 1-I Inj Cold Leg Lp I S6-3844-6111 42-36R Ul 22-34 VT-3 1

Support RHR Pp I-I Inj Cold Leg Lp I S6-3844-6111 42-38R Ul[22-34 VT-3 1

Support Page 171

ASME Sec. XA Code Category F-A A

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISIDWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

RHR Pp 1-1 Inj Cold Leg Lp I S6-3844-6111 42-37A UP" 22-34 Vr-3 2

Support RHR Pp I-I lnj Cold Leg Lp I S6-3844-6111 42-39R UI 22-34 VT-3 2

Support RHR Pp 1-1 Inj Cold Leg Lp I S6-3844-6t11 42-66R UI 2 2-34 VT-3 2

Support RHR Pp 1-1 Inj Cold Leg Lp I S6-3844-6111 42-53R U1' 2 2-34 VT-3 1

Support RHR Pp 1-1 Inj Cold Leg Lp 2 S6-3845-6111 Not Selected U1 2 2-35 Support RHR Pp 1-2 Inj Cold Leg Lp 3 S6-3846-6111 No supports U1: 2 2-33 (support)

RHR Pp 1-2 Inj Cold Leg Lp 4 S6-3847-6111 Not Selected U1: 2 2-36 Support Cent Charg Pump 1-1 Disch S6-45-4 73-35R UI 446545 VT-3 1

Support Cent Charg Pump 1-1 Disch S6-45-4 73-65R Ut 446545 VT-3 2

Support Cent Charg Pump 1-1 Disch S6-45-4 73-85A Ut 446545 VT-3 3

Support Charg Pp 1-1 BP Sup to Seal S6-1474-3 73-21R Ut 446545 VT-3 1

Support Charg Pp 1-1 BP Sup to Seal S6-1474-3 73-22R Ut 446545 VT-3 2

Support Charg Pp 1-1 BP Sup to Seal S6-1474-3 73-40R Ut 446545 VT-3 3

Support Cent Charg Pps Disch Hdr S6-3678-3 54S-17R UI 446545 VT-3 1

Support Page 172

"ASME Sec. XI C6u,.*-ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Cent Charg Pps Disch Hdr Support Cent Charg Pps Disch Hdr Support Cent Charg Pump 1-2 Disch Support Charg Pp 1-2 BP Sup to Seal Support Regen HX In Chg Ln to V-8 108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8 108 Support S6-48-3 S6-48-3 S6-48-3 S6-48-3 S6-48-3 S6-48-3 55S-1 15R Location 1 55S-1 15R Location 2 55S-1 16R 55S-I 17R Location I 55S-1 17R Location 2 55S-I118A S6-3678-3 S6-3678-3 S6-46-4 S6-1475-3 73-46R 73-47A Not Selected Not Selected NOTES VT-3 Vr-3 2

3 Ul"446545 UI.446545 Ut 446545 U! 446545 Ul 446547 U1. 446547 Ut 446547 Uh 446547 U1. 446547 Ul 446547 Vr-3 V"-3 VT-3 VT-3 V'-3 2

3 3

Page 173

ASME Sec. X1 C6,..--Category F-A a

AA ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF REQ.

Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8 108 Support Regen HX In Chg Ln to V-8 108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support Regen HX In Chg Ln to V-8108 Support

$6-48-3 S6-48-3 S6-48-3 S6.48-3 S6-48-3 S6-48-3 S6-48-3 S6-48-3 S6-48-3 S6-48-3 S6-48-3 S6-48-3 S6.48-3 S6-48-3 55S-I19R 55S-120R Location 1 55S-120R Location 2 55S-121V 55S-122R 55S-123A 55S-124R 55S-125R 55S-136R 74-27A 74-47R 99-1R 99-12R 99-101R UI 446547 VT-3 2

Ut 446547 UI 446547 UI 446547 UI 446547 Uh:446547 UI 446547 Ut 446547 Ut 446547 Ut 446547 Ul 446547 Ut 446547 Ut 446547 Ut 446547 VT-3 VT-3 V'-3 V'-3 VT-3 Vr-3 Vr-3 VT-3 VT-3 Vr-3 VT-3 VI-3 Vr-3 Page 174 NOTES

ASME Sec. Xl Coletýategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Regen HX In Chg Ln to S6-48-3 99-168R U1 446547 VT-3 3

V-8108 Support Regen HX In Chg Ln to S6-48-3 99-172R UI. 446547 VT-3 1

V-8108 Support Regen HX In Chg Ln to S6-48-3 99-187V Ul 446547 VT-3 2

V-8108 Support Regen HX In Chg Ln to S6-48-3 99-219R U1 446547 VT-3 3

V-8108 Support Regen HX In Chg Ln to S6-48-3 99-33A UI: 446547 VT-3 1

V-8108 Support Regen HX In Chg Ln to S6-48-3 99-6R Ul 446547 VT-3 2

V-8108 Support Regen HX In Chg Ln to S6-48-3 99-7R UI. 446547 VT-3 3

V-8108 Support Regen HX In Chg Ln to S6-48-3 99-81R U1. 446547 VT-3 1

V-8108 Support Regen HX In Chg Ln to S6-48-3 99-84R UI: 446547 VT-3 2

V-8108 Support Regen HX In Chg Ln to S6-48-3 99-87R UI 446547 VT-3 3

V-8108 Support Regen HX In Chg Ln to S6-48-3 99-94R UI 446547 VT-3 1

V-8108 Support Charg Pps Disch Hdr VIv Byp S6-1312-3 No Supports UI 446547 (support)

Charging Pps Disch Emerg I S6-1974-4 54S-12R UI 447114 VT-3 2

Support Charging Pps Disch Emerg 1 S6-1974-4 54S-14R U! 447114 VT-3 3

Support Page 175

ASME Sec. XI C'.-ategory F-A is RORM LN.S D

iaboCni in 2nd IntraRe.2,:

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF REQ.

Charging Pps Disch Emerg 2 Support Charging Injection Out Support Charging Injection Out Support Charging Injection Out Support Charging Injection Out Support Charging Injection Out Support Charging Injection Out Support Charging Inj Out Cold Legs Support Charging Inj Out Cold Legs Support Charging Inj Out Cold Legs Support Charging Inj Out Cold Legs Support Charging lnj Out Cold Legs Support Charging Inj Out Header Support Charging Pps Disch Header Support S6-1975-4 S6-2033-4 S6-2033-4 S6-2033-4 S6-2033-4 S6-2033-4 S6-2033-4 S6-1978-4 S6-1979-4 S6-1979-4 S6-282-3 S6-283-3 S6-1016-3 S6-52-3 Not Selected 15-103SL 15-108R 288.4A 54S-20R 56S-50R 56S-51R No Supports 15-104R 56S-53R Not Selected 56S-105R 57S-123V 99-I01R Ut 447114 Ut 447114 Ut 447114 Ut 447114 UI 447114 Ut 447114 Ut I447114 Ut 447114 Ut 447114 Ut 447114 Ut 447114 Ut 447114 UI 447114 UI 446548 VT-3 Vr-3 VT-3 VT-3 VT-3 VT-3 1

2 3

1 2

3 1979 has supports VT-3 VT-3 Vr-3 VT-3 Vr-3 1

2 Same loop as 1978 3

1 2

Page 176 K>

NOTES

<-I ASME Sec. Xl C aoe-ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Charging Pps Disch Header S6-52-3 99-IR UI 446548 VT-3 3

Support Charging Pps Disch Header

$6-52-3 99-218R U! 446548 VT-3 1

Support Charging Pps Disch Header S6-52-3 99-24R Ul 446548 VT-3 2

Support Charging Pps Disch [leader S6-52-3 99-26R U! 446548 VT-3 3

Support Charging Pps Disch Header S6-52-3 99-27R Ul 446548 VT-3 1

Support Charging Pps Disch Header S6-52-3 99-6R Ut 446548 VT-3 2

Support Charging Pps Disch Header S6-52-3 99-74A Ut 446548 VT-3 3

Support Charging Pps Disch Header S6-52-3 99-7R UI 446548 VT-3 3

Support Charging Pps Disch Header S6-52-3 99-96V Ut 446548 V'-3 1

Support Charging Pps Disch Header S6-52-3 99-9R UI: 446548 VT-3 2

Support Charging Pumps Seal Supply S6-53-3 73-42R UI: 446548 V'-3 3

Support Charging Pumps Seal Supply S6-53-3 73-43R UI: 446548 VT-3 1

Support Charging Pumps Seal Supply S6-53-3 73-45A UI.446548 VT-3 2

Support Charging Pumps Seal Supply S6-53-3 73-63R Ul 446548 V'-3 3

Support Page 177

ASME Sec. XI Cbue1Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Charging Pumps Seal Supply S6-53-3 73-76R UI. 446548 VT-3 1

Support Charging Pumps Seal Supply S6-53-3 74-30A UI 446548 VT-3 2

Support Charging Pumps Seal Supply S6-53-3 74-48R Ul 446548 VT-3 3

Support Charging Pumps Seal Supply S6-53-3 74-49R UI 446548 V'-3 I

Support CVCS Seal Inj Filter 1-2 In S6-2047-3 Not Selected UI 446548 (support)

Seal Injection Filter Bypass S6-1455-3 No Supports U1 446548 (support)

CVCS Seal Inj Filter 1-2 Out S6-2048-3 Not Selected Ut. 446548 (support)

CVCS Seal Inj Filter I-I In S6-2044-3 512-39V UI 446548 VT-3 2

Support CVCS Seal Inj Filter 1-I In S6-2044-3 512-6R UI 446548 VT-3 3

Support CVCS Seal Inj Filter 1-I Out S6-2046-3 512-6R U1 446548 VT-3 3

Support React Cool Pps Seal Wtr In S6-746-3 15-40SL UI 446548 VT-3 1

Support React Cool Pps Seal Wtr In S6-746-3 56S-1 17R UI 446548 VT-3 2

Support React Cool Pps Seal Wtr In S6-746-3 57S-1 IOR U! 446548 VT-3 3

Support React Cool Pps Seal Wtr In S6-746-3 57S-IIIR UI 446548 VT-3 1

Support Page 178

ASME Sec. XI Co'-,-*ategory F-A AA ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

React Cool Pps Seal Wtr In S6-746-3 57S-1 12A UI 446548 VT-3 2

Support React Cool Pps Seal Wtr In S6-746-3 57S-I 13R U["446548 V'-3 3

Support React Cool Pps Seal Wtr In S6-746-3 57S-1 14R UI 446548 VT-3 1

Support React Cool Pps Seal Wtr In S6-746-3 57S-122R UI. 446548 VT-3 2

Support React Cool Pps Seal Wtr In S6-746-3 57S-124R UI 446548 VT-3 3

Support React Cool Pps Seal Wtr In S6-746-3 57S-191R UI 446548 VT-3 1

Support React Cool Pps Seal Wtr In S6-746-3 57S-192R UI 446548 VT-3 2

Support React Cool Pps Seal Wtr In S6-746-3 99-197R UI 446548 VT-3 3

Support React Cool Pps Seal Wtr In S6-746-3 99-25R UI 446548 V-3 1

Support React Cool Pps Seal Wtr In S6-746-3 99-26R UI 446548 VT-3 3

Support React Cool Pps Seal Wtr In S6-746-3 99-28R UI 446548 V-3 1

Support React Cool Pps Seal Wtr In S6-746-3 99-9R UI 446548 VT-3 2

Support React Cool Pps Seal Wtr In S6-1683-3 No Supports U1 446548 (support)

Charg Pp 1-1 Bypass Miniflow S6-1466-2 73-143 UI 446545 VT-3 2

Support Page 179

ISI PROGAM PLAN ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charg Pp 1-1 Bypass Miniflow Support Charg Pp 1-1 Bypass Miniflow Support Charg Pp 1-1 Bypass Miniflow Support S6-1466-2 S6-1466-2 S6-1466-2 73-144 73-25 73-29 UI 446545 Vr-3 3

Ul 446545 V'-3 1

UI 446545 VT-3 2

Charg Pp 1-1 Bypass Miniflow Support Charg Pp 1-1 Bypass Miniflow Support Charg Pp 1-1 Bypass Miniflow Support Charg Pp 1-2 Bypass Miniflow Support Cent Chg Pps BP Miniflow Hdr Support Cent Chg Pps BP Miniflow Hdr Support Cent Chg Pps BP Miniflow Hdr Support Cent Chg Pps BP Miniflow Hdr Support Cent Chg Pps BP Miniflow Hdr Support CVCS SeallIn Filter 1-1 In Support S6-1466-2 S6-1466-2 S6-1466-2 S6-1468-2 S6-1464-2 S6-1464-2 S6-1464-2 S6-1464-2 S6-1464-2 S6-3673-2 & S6-2 73-72 UI 446545 VT-3 1

73-73 73-74 Not Selected 73-20 Location B 73-24 73-31 73-34 73-98 1512-25 NOTES U! 446545 UI 446545 UI 446545 UI 224422 Ut 224422 Ut 224422 U1.224422 Ut 224422 Ul"446548 VT-3 VT-3 Vr-3 Vr-3 VT-3 VT-3 Vr-3 Vr-3 Page 180 ASME Sec. X1 Co ategory F-A

ASME Sec. XI Ct-- 6 ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

CVCS Seal Inj Filter 1-2 In Support CVCS Seal Inj Filter 1-1 Out Support CVCS Seal Inj Filter 1-2 Out Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support S6-3674-2 & S6-2 S6-1477-2 & S6-2 S6-1478-2 & S6-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 NOTES Not Selected 1512-24 Not Selected 180-10 180-15 180-9 2151-107 2151-109 2151-110 2151-113 2151-119 2151-131 2151-133 2151-137 Ui 446548 UI 446548 Ul"446548 Ul-446548 UI:446548 UI 446548 Ul'446548 UI.446548 UI.446548 UI:446548 UI 446548 UI 446548 UI 446548 Ut 446548 VT-3 V"-3 VT-3 VT-3 Vr-3 V1-3 Vr-3 VT-3 VT-3 Vr-3 Vr-3 Vr-3 Page 181

ASME Sec. XI

./jCategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-147 Ut 446548 VT-3 1

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-215 UI: 446548 VT-3 2

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-53 UI 446548 VT-3 3

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-54 UI 446548 VT-3 1

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-55 UI.446548 VT-3 2

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-58 U1 446548 VT-3 3

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-63 U[-446548 VT-3 1

Support Reac Cool Pp 1-1 Seal Wir In S6-54-2 2151-66 U1 446548 VT-3 2

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-67 Ut 446548 VT-3 3

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-86 Ut 446548 VT-3 1

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-89 U1. 446548 VT-3 2

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-96 U! 446548 VT-3 3

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2151-97 UI.446548 VT-3 1

Support Reac Cool Pp 1-1 Seal Wtr In S6-54-2 2155-185 UI 446548 Vr-3 2

Support Page 182

ASME Sec. Xl Code Category F-A DiaboCnvo 2ndIntra Rv ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal VVtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Mtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-1 Seal Wtr In Support Reac Cool Pp 1-2 Seal Wtr In Support Reac Cool Pp 1-3 Seal Wtr In Support S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-54-2 S6-55-2 S6-56-2 2155-272 2155-53 2155-54 2155-74 2155-78 2161-16 2161-47 22-212SL 39-8R 39-9R 46-20 55N-9R Not selected 22-291SL UI:446548 VT-3 UI: 446548 Vr-3 Ut 446548 Vr-3 Ut 446548 Vr-3 Ut 446548 VT-3 Ut 446548 VT-3 Ui 446548 VT-3 UI. 446548 Vr-3 UI 446548 Vr-3 Ut 446548 Vr-3 UI 446548 VT-3 Ut 446548 VT-3 UI: 446548 UI 446548 Vr-3 Page 183 I

NOTES

"ASME Sec. Xl C1oc--ategory F-A ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Reac Cool Pp 1-3 Seal Wtr In Support Reac Cool Pp 1-4 Seal Wtr In Support Reac Cool Pp 1-4 Seal Wtr In Support Reac Cool Pp 1-4 Seal Wtr In Support Steam Gen !-I Steam Outlet Support Steam Gen I-1 Steam Outlet Support Steam Gen 1-1 Steam Outlet Support Steam Gen 1-I Steam Outlet Support Steam Gen 1-1 Steam Outlet Support Steam Gen 1-I Steam Outlet Support Steam Gen I-I Steam Outlet Support Steam Gen 1-1 Steam Outlet Support Steam Gen 1-2 Steam Outlet Support Steam Gen 1-2 Steam Outlet Support S6-56-2 S6-57-2 S6-57-2 S6-57-2 K15-228-28V K15-228-28V K 15-229-28V K15-228-28V KI5-228-28V K 15-228-28V K15-228-28V K15-228-28V KI5-227-28V K1 5-227-28V Not selected 22-452SL 22-488SL Not selected 1020-IV 1032-31R 1032-24SL 1020-31R 1032-16R 1032-26SL 1020-2V 1021-11R 1032-2SL 1025-16SL UI 446548 UI 446548 UI 446548 UI: 446548 UI 2 2-21 Ut 22-21 UI 2.2-21 Uh: 2 2-21 U1 2 2-21 U1 2 2-21 Ut 22-21 UP 2 2-21 U1 22-22 VT-3 VT-3 VT-3 V-r-3 VT-3 Vr-3 Vr-3 VT-3 V'I-3 VT-3 VT-3 UI 2 2-22

'V'-3 Page 184 NOTES

ASME Sec. Xl Co*.-,ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Steam Gen 1-2 Steam Outlet Support Steam Gen 1-2 Steam Outlet Support Steam Gen 1-3 Steam Outlet Support Steam Gen 1-3 Steam Outlet Support Steam Gen 1-3 Steam Outlet Support Steam Gen 1-3 Steam Outlet Support Steam Gen 1-3 Steam Outlet Support Steam Gen 1-4 Steam Outlet Support Steam Gen 1-4 Steam Outlet Support Steam Gen 1-4 Steam Outlet Support Steam Gen 1-4 Steam Outlet Support Steam Gen 1-4 Steam Outlet Support Main Stm Relief VIv Hdr 1-3 Support Main Stm Relief VIv Hdr 1-3 Support K15-227-28V K15-227-28V K15-226-28V K 15-226-28V KIS-226-28V KI 5-226-28V K 15-226-28V K15-225-28V K15-225-28V K15-225-28V K] 5-225-28V K15-225-28V KI5-1065-24V K15-1065-24V 1032-20SL Not Selected 1030-16SL 1033-ISL 1033-3SL 1033-5SL Not Selected 1031-2SL 1033-4SL 1033-6SL 1033-2SL Not Selected 1030-14R 1033-15SL U 1. 2 2-22 U! 2 2-22 U t. 2 2-23 UI 2 2-23 UI. 2 2-23 Ut 2 2-23 Ul 2 2-23 UI: 2 2-24 U1: 2 2-24 Ut. 2 2-24 Ut 22-24 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 Vr-3 VT-3 Ut 22-24 UI 2 2-23 VT-3 UI 2 2-23 VT-3 3

Page 185 NOTES

ASME Sec. X1 ýJCategory F-A D.i boCa*n2n ntra Rv ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Main Stm Relief Vlv Hdr 1-3 Support Main Stm Relief Vlv Hdr 1-3 Support Main Stm ReliefVlv Hdr 1-3 Support Main Stm Relief Vlv Hdr 1-4 Support Main Stm Relief VIv Hdr 1-4 Support Main Stm ReliefVIv Hdr 1-4 Support Steam Gen 1-1 Feed Wtr Sup Support Steam Gen 1-1 Feed Wtr Sup Support Steam Gen 1-I Feed Wtr Sup Support Steam Gen !-I Feed Wtr Sup Support Steam Gen 1-1 Feed Wtr Sup Support Steam Gen 1-1 Feed Wtr Sup Support Steam Gen I-I Feed Wtr Sup Support Steam Gen 1-I Feed Wtr Sup Support KI5-1065-24V KIS-1065-24V K15-1065-24V K15-1066-24V K15-1066-24V K15-1066-24V K16-554-16V K16-554-16V K16-554-16V K16-554-16V K16-554-16V K16-554-16V K16-554-16V K16-554-16V 1033-23R 1027-8V 1033-27R 1033-16SL 1033-28SL Not Selected 1037-7V 1037-8V 1048-ISR I048-22R 1048-14R 1048-27SL 1037-9R 1048-IR U l. 2.2-23 VT-3 UI 2 2-23 VT-3 UI 2 2-23 VT-3 1

2 2

UI 2 2-24 Vr-3 3

U1 2 2-24 VT-3 3

Ut 2 2-24 Ut 2 2-25 UI -2 2-25 UI 2 2-25 Ut: 2 2-25 Ut: 2 2-25 Ut: 2 2-25 U 1: 2 2-25 U1: 2 2-25 Vr-3 VT-3 VT-3 VT-3 Vr-3 Vr-3 VT-3 V'-3 Page 186 NOTES

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Steam Gen 1-2 Feed Wtr Sup K16-555-16V 1048-28SL UI: 2 2-26 VT-3 1

Support Steam Gen 1-2 Feed Wtr Sup K16-555-16V Not selected U1: 2 2-26 Support Steam Gen 1-3 Feed Wtr Sup K16-557-16V 1049-ISL U!: 2 2-27 VT-3 3

Support Steam Gen 1-3 Feed Wtr Sup K16-557-16V 1049-17SL Ult 2 2-27 VT-3 1

Support Steam Gen 1-3 Feed Wtr Sup K16-557-16V 1049-2SL Ut 2 2-27 VT-3 2

Support Steam Gen 1-3 Feed Wtr Sup K16-557-16V Not selected UI 22-27 Support Steam Gen 1-4Feed Wtr Sup K16-556-16V 1049-4SL UI: 2 2-28 VT-3 3

Support Steam Gen 1-4 Feed Wtr Sup K16-556-16V 1049-5SL Ul: 2 2-28 VT-3 3

Support Steam Gen 1-4 Feed Wtr Sup K16-556-16V 1049-14SL Ut 22-28 VT-3 2

Support Steam Gen 1-4 Feed Wtr Sup K16-556-16V 1049-16SL Ut. 2 2-28 VT-3 2

Support Steam Gen 1-4 Feed Wtr Sup K16-556-16V Not selected UI. 2 2-28 Support Steam Gen I-I MSRV Risers K15-228-8V No supports Ut 2 2-21 (support)

Steam Gen 1-2 MSRV Risers K15-227-8V No supports Ut 22-22 (support)

Steam Gen 1-3 MSRV Risers K15-226-8V No supports U!. 2 2-23 (support)

Page 187 ASME Sec. XI CbýýCategory F-A

K>

ASME Sec. Xl Co v-i-ategory F-A IS POGAMPAN,`

D.,iaboano 2dIneva ev ITEM PARTS EXAMINED COMP/ILINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF REQ.

Steam Gen 1-4 MSRV Risers (support)

RC Pps Barrier CCW Ret Hdr Support RC Pps Barrier CCW Ret Hdr Support RC Pps Barrier CCW Ret Hdr Support RC Pps Barrier CCW Ret Hdr Support Auxiliary Feedwater Pump 1-1 Support Auxiliary Feedwater Pump 1-2 Support Auxiliary Feedwater Pump 1-3 Support RHR HX 1-1 (Class 3 side)

Intermediate Support RHR HX I-I (Class 3 side) Upper Support RHR HX 1-2 (Class 3 side)

Supports Letdown Heat Exchanger I-I Supports Seal Water Heat Exchanger 1-I Supports Spent Fuel Pool Heat Exchanger 1 1 Supports K15-225-8V K17-1357-6 K17-1357-6 K17-1357-6 K17-1357-6 AFW Pump 1-1 AFW Pump 1-2 AFW Pump 1-3 RHR HX I-1 RIIR HX I-I RHR HX 1-2 Letdo%%n HX 1-I Seal Wtr ItX 1-1 SFP HX 1-I No supports 57S-181R 57S-23V 5-35R 12-47R 4 Integral Legs, 2 Pedestals and Base 4 Integral Legs, 2 Pedestals and Base Not Selected 4 Braces at mid level of HX 4 Braces at top level of fiX Not Selected 2 Supports to Base 2 Supports to Base 2 Supports to Base NOTES UI 22-24 UI 2.2-37 Ut 2 2-37 UI. 2 2-37 Ut: 2 2-37 DC-663056 DC-663056 DC-663056 UlI2 1-6 UI.2 1-6 UI:2 1-6 DC-663210 DC-663210 DC-663211 V"-3 VT-3 VT-3 Vr-3 VT-3 Vr-3 VT-3 VT-3 VT-3 VT-3 VT-3 Page 188

ASME Sec. Xl Co'Iebtategory F-A 0

AA ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Component Cooling Water Surge Tank 1-1 Support Component Cooling Water Pump I-1 Support Component Cooling Water Pump 1-2 Support Component Cooling Water Pump 1-3 Support CCW Heat Exchanger I-I Support CCW Heat Exchanger 1-2 Support RC Pump I-1 Upper Bearing Oil Cooler Supports RC Pump 1-2 Upper Bearing Oil Cooler Supports RC Pump 1-3 Upper Bearing Oil Cooler Supports RC Pump 1-4 Upper Bearing Oil Cooler Supports Condensate Storage Tank 1-I Support Firewater Transfer Tank 0-1 Support Makeup Water Transfer Pump 0-1 Support Makeup Water Transfer Pump 0-2 Support CCW Surge Tank 1-P CCW Pump 1-1 CCW Pump 1-2 CCW Pump 1-3 CCW HX I-1 CCW HX 1-2 RCP 1-1 UBOC RCP 1-2 UBOC RCP 1-3 UBOC RCP 1-4 UBOC CST 1-1 Firewater Transfer Tk 0-1 MU WtrrTmsfr Pp 0-1 MU Wtr Tmsfr Pp 0-2 2 Supports and Braces 4 Integral Legs and Base Not Selected Not Selected 2 Supports and Braces Not Selected Brackets mount to pump motor Not selected Not selected Not selected Tank Base Bolts to concrete Tank Base Bolts to concrete Pump Support and Base Not selected DC-663225 VT-3 DC-663213 VT-3 DC-663213 DC-663213 DC-663212 Vr-3 DC-663212 DC-663207 VT-3 DC-663207 DC-663207 DC-663207 DC-663208 VT-3 438038 VT-3 DC-663062 Vr-3 DC-663062 Page 189 NOTES

ASME Sec. XI C,..ategory F-A LP GAM PAN Diabo Cnvon2ndIntera Rvg2'-

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Auxiliary Saltwater Pump I-I Base Support Auxiliary Saltxwater Pump 1-1 Suction Support Auxiliary Saltwater Pump 1-1 Motor Support Auxiliary Saltwater Pump 1-2 Supports Spent Fuel Pool Cooling Pump 1-1 Supports Spent Fuel Pool Cooling Pump 1-2 Supports Auxiliary Feedwater Pump 1-1 Suction Support Auxiliary Feedwater Pump 1-1 Suction Support Aux Feed Pump 1-1 Raw Water Suction Support Aux Feed Pump 1-2 & 1-3 Condens Suct Hdr Support Aux Feed Pump 1-2 & 1-3 Condens Suct Hdr Support Aux Feed Pump 1-2 & 1-3 Condens Suct Hdr Support Aux Feed Pump 1-2 & 1-3 Condens Suct Hdr Support Auxiliary Feedwater Pump 1-2 Suction Support ASW Pump 1-1 ASW Pump 1-1 ASW Pump I-I ASW Pump 1-2 SFP Pump I-I SFP Pump 1-2 K-558-8 K-558-8 K-561-8 K-562-8 K-562-8 K-562-8 K-562-8 K-559-6 Pump Base Bolts to concrete 44-64R 44-63R Not Selected 2 Supports and Base 2 Supports and Base 92-IOR 92-11R 92-9R 92-2R 92-13R 92-61R 92-150R Not selected DC-663030 049283 049283 049283 DC-663211 DC-663211 VT-3 Vr-3 VT-3 V'-3 Vr-3 V'-3 VT-3 VT-3 VT-3 Vr-3 Vr-3 VT-3 2

Located in intake bay Page 190

<-I.

Kl-i NOTES

K-,

<-I ASME Sec. X, Can, ategory F-A A

A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Auxiliary Feedwater K-560-6 Not selected Pump 1-3 Suction Support Auxiliary Feedwater K16-568-6 92-5R VT-3 3

Pump 1-1 Disch Hdr Support Auxiliary Feedwater K16-568-6 92-6R VT-3 1

Pump 1-1 Disch Hdr Support Auxiliary Feedwater K16-568-6 92-12R VT-3 2

Pump 1-1 Disch Hdr Support Auxiliary Feedwater K16-568-6 92-42R Vr-3 3

Pump 1-1 Disch Hdr Support Auxiliary Feedwater K 16-568-6 92-45R Vr-3 1

Pump 1-1 Disch Hdr Support Auxiliary Feedwater K 16-568-6 92-118R VT-3 2

Pump 1-1 Disch Hdr Support Auxiliary Feedwater K16-568-6 92-146R VT-3 3

Pump 1-1 Disch Hdr Support Aux Feed Pump 1-2 Raw K.488-6 No supports Water Suction (support)

Aux Feed Pump 1-3 Raw K-489-6 Not Selected Water Suction Support Aux Feed Pumps Raw Water K-638-8 92-8R 1IVT-3 2

Suction Hdr Support Aux Feed Pumps Raw Water K-638-8 92-5R VT-3 3

Suction Hdr Support Aux Feed Pumps Raw Water K-638-8 92-6R vr-3 1

Suction Hdr Support Aux Fdw Pps Disch to Stm K 16-476-4 1-23V.

VT7-3 2

Gen 1-1 & 1-2 Support Page 191

ASME Sec. XI C..

'ategory F-A ITEM PARTS EXAMINED COMP/LINE WVELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Aux Fdw Pps Disch to Stm K16.4764 1-24R Vr 3

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-476-4 1-25R VT-3 1

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-476-4 1-26R Vr-3 2

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-476-4 1-27R VT-3 3

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-476-4 1-28R VT-3 1

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-476-4 1-29R VT-3 2

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16476-4 1-30R VT-3 3

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-476-4 i-31R.

V-3S 1

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-476-4 1-32R VT-3 2

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-476-4 1-33R VT-3 3

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-4764 1-36R Vr-3 1

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16476-4 58S-I00R VT-3 2

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-4764 58S-95A VT-3 3

Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm K16-476-4 58S-96R VT-3 1

Gen 1-1 & 1-2 Support Page 192

ASME Sec. XI CG.,Z2ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Aux Fdw Pps Disch to Stm Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm Gen 1-1 & 1-2 Support Aux Fdw Pps Disch to Stm Gen 1-3 & 1-4 Support Aux Fdw Pp 1-2 Disch Header Support Aux Fdw Pp 1-3 Disch Header Support Aux Fdw Pps 1-2 & 1-3 Disch X-tie (support)

Stm Gen 1-1 Aux Fdw Supply Support Stm Gen 1-2 Aux Fdw Supply Support Stm Gen 1-3 Aux Fdw Supply Support Stm Gen 1-4 Aux Fdw Supply Support Aux Fdw Pp 1-2 Stm Gen 1-1 Disch Support Aux Fdw Pp 1-2 Stm Gen 1-2 Disch Support Aux Fdw Pp 1-3 Stm Gen 1-4 Disch Support NOTES 2

3 Vr-3 VT-3 VT-3 K16-476-4 K16-476-4 K16-476-4 K16-563-4 K16-573-4 K16-574-4 K16-4292-4 Kl6-569-31V+

K 16-570-31V+

KI6-571-31V+

K16-572-31V+

K16-575-31V+

K16-576-31V+

K16-577-31V+

58S-97R 58S-98R 58S-99R Not Selected Not Selected Not Selected No Supports 1-21R Not Selected Not Selected Not Selected 1-21R Not Selected Not Selected VT-3 2

VI-3 2

Page 193

\\ /

K>

ASME Sec. XI C -,,rategory F-A 1PRGAM PAN Diabo.

anon2n ntrvl ev ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Aux Fdw Pp 1-3 Stm Gen 1-3 Disch Support Aux FW Pp 1-1 Suction Line Drain (support)

Aux FW Pp 1-2 Suction Line Drain (support)

Aux FW Pp 1-3 Suction Line Drain (support)

Aux Fdw Pp 1-1 Recirc Support Aux Fdw Pp 1-2 Recirc Support Aux Fdw Pp 1-3 Recirc Support Aux Feed Pump 1-1 Turbine Exhaust Support Aux Feed Pump 1-1 Turbine Exhaust Support Aux Feed Pump 1-1 Turbine Exhaust Support Aux Feed Pump 1-1 Turbine Exhaust Support Aux Feed Pump 1-1 Turbine Exhaust Support Aux Feed Pump 1-1 Turbine Exhaust Support CCW Heat Exchanger 1-1 CCW Inlet Support K16-578-31V+

K-2 off K-558-8 K-2 off K-559-6 K-2 off K-560-6 K16-564-1 5 K16-565-1 5 K16-566-1 5 K-1045-10 K-1045-10 K-1045-10 K-1045-10 K-1045-10 K-1045-10 K-95-30 Not Selected No Supports No Supports No Supports 85-34 Not Selected Not Selected (No supports)86-28R 86-29R 86-30R 86-54R 92-69R 92-88R 5-37R NOTES VT-3 VT-3 vr-3 VT-3 vr-3 vr-3 Vr-3 Vr-3 2

3 2

3 2

Page 194

ASME Sec. XI Cod ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

CCW Heat Exchanger 1-1 K-95-30 5-73R v'r-3 3

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 5-76R VT-3 1

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 5-80R VT-3 2

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 14-23R VT-3 3

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 14-24SL VT-3 2

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 14-25R VT-3 2

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 14-34R VT-3 3

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 14-44SL.

V'-3 3

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 14-61 SL VT-3 2

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 14-67SL VT-3 1

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 14-84SL VT-3 3

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 14-90R VT-3 2

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 18-8R VT-3 3

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 18-9R VT-3 1

CCW Inlet Support Page 195

ASME Sec. XI Co ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

CCW Heat Exchanger 1-1 K-95-30 73-8V V'-3 2

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 73-75R VT-3 3

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 73-103R VT-3 1

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 73-109R VT-3 2

CCW Inlet Support CCW Heat Exchanger 1-1 K-95-30 301-238V VT-3 3

CCW Inlet Support CCW Heat Exchanger 1-2 K-96-30 4-24SL Vr-3 3

CCW Inlet Support CCW Heat Exchanger 1-2 K-96-30 4-62SL Vr-3 3

CCW Inlet Support CCW Heat Exchanger 1-2 K-96-30 4-63SL VT7-3 3

CCW Inlet Support CCW Heat Exchanger 1-2 K-96-30 4-90SL VT-3 3

CCW Inlet Support CCW Heat Exchanger 1-2 K-96-30 Not selected CCW Inlet Support CCW Heat Exchanger 1-1 K-101-30 18-ISL VT-3 1

CCW Outlet Support CCW Heat Exchanger 1-1 K-101-30 18-19R Vr-3 I

CCW Outlet Support CCW Heat Exchanger 1-2 K-1 02-30 4-98SL VT-3 1

CCW Outlet Support CCW Heat Exchanger 1-2 K-102-30 Not Selected CCW Outlet Support Page 196

ASME Sec. AI Cou..rCategory F-A ISI PROG AM LN D

giaboCavn2 nervlRe.2.:

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IS DWG.

NDE PER. LINE-TOTL RELIEF REQ.

CCW Heat Exchanger Outlet Crosstie (support)

CCW Return Header A Support CCW Return Header A Support CCW Return Header A Support CCW Return Header A Support CCW Return Header A Support CCW Return Header A Support CCW Return Header A Support CCW Return Header A Support CCW Return Header A Support CCW Return Header A Support CCW Return Header B Support CCW Return Header B Support CCW Return Header B Support NOTES K-98-24 K-81-20 K-81-20 K-81-20 K-81-20 K-81-20 K-81-20 K-81-20 K-81-20 K-81-20 K-81-20 K-82-20 K-82-20 K-82-20 No Supports 4-84SL 4-85SL 14-14R 14-37SL 73-5R 73-12R 73-98V 55S-5R 55S-IOR 55S-IIR 4-86SL 14-48SL Not Selected Vr-3 VT-3 vr-3 VT-3 VT-3 VT-3 V'-3 Vr-3 VT-3 VT-3 VT-3 Page 197

ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

IS] DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Comp Cooling Wtr Pump !-1 K-89-20 73-1OR Vr-3 1

Disch Support Comp Cooling Wtr Pump 1-2 K-90-20 Not Selected Disch Support Comp Cooling Wtr Pump 1-3 K-91-20 Not Selected Disch Support CCW Pumps 1-2 & 1-3 Suct K-97-20 No Supports Crosste (support)

CCW Supply Header A Support K-103-20 4-99SL Vr-3 1

CCW Supply Header A Support K-103-20 14-76R VT-3 3

CCW Supply Header A Support K-103-20 14-77SL VT-3 3

CCW Supply Header A Support K-103-20 18-2R VT-3 2

CCW Supply Header A Support K-103-20 18-3R VT-3 3

CCW Supply Header A Support K-103-20 18-13SL VT-3 1

CCW Supply Header A Support K-103-20 18-15R VT-3 2

CCW Supply Header A Support K-103-20 18-18R VT-3 3

CCW Supply Header A Support K-103-20 55S-2R VT-3 1

CCW Supply Header A Support K-103-20 55S-3R Vr-3 2

Page 198 ASME Sec. Xl C,_,i'ategory F-A

KJ ASME Sec. Xl C

.,ategory F-A A

A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

CCW Supply Header A Support K-103-20 55S-4R VT-3 3

CCW Supply Header A Support K-103-20 55S-5R VT-3 2

CCW Supply Header B Support K-104-20 14-74SL VT-3 3

CCW Supply Header B Support K-104-20 14-78SL VT-3 1

CCW Supply Header B Support K-104-20 Not Selected CCW Supply Header C Support K-2277-20 14-79SL VT-3 I

CCW Supply Header C Support K-2277-20 Not Selected CCW Return Header C Support K-2282-20 4-91SL VT-3 2

CCW Return Header C Support K-2282-20 14-31SL Vr-3 3

CCW Return Header C Support K-2282-20 Not Selected CCW Pps I-1 & 1-2 Suction K-2285-20 No Supports Crosstie (support)

CCW Pump 1-1 Disch Hdrs A &

K-2994-20 4-12SL VT-3 3

B Support CCW Pump 1-1 Dasch Hdrs A &

K-2994-20 4-13SL VT-3 3

B Support CCW Pump i-I Disch Hldrs A &

K-2994-20 4-14SL VT-3 3

B Support Page 199

ASME Sec. XI Co...Category F-A I

-9 A

I k

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

CCW Pump 1-1 Disch Ildrs A &

K-2994-20 73-1R VT-3 1

B Support CCW Pump 1-1 Disch Hdrs A &

K-2994-20 73-6V Vr-3 2

B Support CCW Pump I-I Dzsch Hdrs A &

K-2994-20 73-67R VT-3 3

B Support CCW Pump I-I Disch Hdrs A &

K-2994-20 73-68R VT-3 I

B Support CCW Pump I-I Disch Hdrs A &

K-2994-20 73-96R VT-3 2

B Support CCW Pump 1-2 Disch Hdrs A &

K-3036-20 Not Selected B (support)

CCW Pump 1-3 Disch Hdrs A &

K-3039-20 4-67SL.

V'-3 3

B Support CCW Pump 1-3 Disch Hdrs A &

K-3039-20 Not Selected B Support Cont Fan Cooler CCW Sup Hdr B K-105-18 14-3SL.

VT-3 2

Support Cont Fan Cooler CCW Sup Hdr B K-105-18 14-4SL.

VT-3 2

Support Cont Fan Cooler CCW Sup Hdr B K-105-18 14-71SL VT-3 2

Support Cont Fan Cooler CCW Sup Hdr B K-105-18 14-72SL.

V'-3 1

Support Cont Fan Cooler CCW Sup Ildr B K-105-18 14-73SL VT-3 1

Support Cont Fan Cooler CCW Sup Hdr B K-105-18 14-89SL VT-3 1

Support Page 200

ASME Sec. Xl C'

'Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Cont Fan Cooler CCW Sup Hdr B K-105-18 Not Selected Support Cont Fan Cooler CCW Ret Hdr B K-106-18 14-6SL VT-3 1

Support Cont Fan Cooler CCW Ret Hdr B K-106-18 14-7SL VT-3 2

Support Cont Fan Cooler CCW Ret Hdr B K-106-18 14-9SL VT-3 1

Support Cont Fan Cooler CCW Ret Hdr B K-106-18 14-18SL V'-3 2

Support Cont Fan Cooler CCW Ret Hdr B K-106-18 Not Selected Support CCW Supply Header C Support K-2278-18 Not Selected CCW Return Header C Support K-2281-18 14-22SL VT-3 2

CCW Return Header C Support K-2281-18 14-30SL VT-3 1

CCW Return Header C Support K-2281-18 Not Selected CCW Return Header B Bypass K-2369-18 5-61R V--3 2

Support CCW Return Header B Bypass K-2369-18 14-8SL VT-3 1

Support Cont Fan Cooler Supply Hdr A K-146-16 14-IOSL VT-3 1

Support Cont Fan Cooler Supply Hdr A K-146-16 14-12SL VT-3 I

Support Page 201

K->

ASME Sec. Xl Ct,..ategory F-A A

Ak ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Cont Fan Cooler Supply Hdr A K-146-16 14-13SL V'-3 1

Support Cont Fan Cooler Supply ltdr A K-146-16 14-45SL VT-3 1

Support Cont Fan Cooler Supply Hdr A K-146-16 14-88SL VT-3 1

Support Cont Fan Cooler Supply Htdr A K-146-16 55S-6R VT-3 3

Support Cont Fan Cooler Supply Hdr A K-146-16 55S-7R VT-3 1

Support Cont Fan Cooler Supply Hdr A K-146-16 55S-8R.

VT-3 2

Support Cont Fan Cooler Supply Hdr A K-146-16 55S-9R V'-3 3

Support Cont Fan Cooler Supply Hdr A K-146-16 55S-177R VT-3 1

Support Cont Fan Cooler Supply Hdr A K-146-16 55S-184R.

V'-3 2

Support Cont Fan Cooler Return Hdr A K-147-16 5-IR VT-3 3

Support Cont Fan Cooler Return Hdr A K-147-16 14-11SL VT-3 1

Support Cont Fan Cooler Return Hdr A K-147-16 55S-6R VT-3 3

Support Cont Fan Cooler Return Hdr A K-147-16 55S-8R VT-3 2

Support Cont Fan Cooler Return Hdr A K-147-16 55S-9R VT-3 3

Support Page 202

<-/

ASME Sec. XI CodrC~ategory F-A A

A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Cont Fan Cooler Return Hdr A K-147-16 55S-12R VT-3 1

Support Cont Fan Cooler Return Hdr A K-147-16 55S-!75R V'-3 2

Support Cont Fan Cooler Return Hdr A K-147-16 55S-180R V17-3 3

Support CCW Return Header A Bypass K-2399-16 14-65R VT-3 1

Support CCW Return Header A Bypass K-2399-16 55S-13R VT-3 2

Support RHR Heat Exchanger 1-2 CCW K-94-12 Not Selected Supply Support RIIR Heat Exchanger 1-2 CCW K-99-12 14-47SL V'-3 2

Return Support RHR Heat Exchanger 1-2 CCW K-99-12 Not Selected Return Support RHR Heat Exchanger I-1 CCW K-124-12 74-13R V17-3 3

Supply Support RHR Heat Exchanger I-I CCW K-124-12 74-33R VT7-3 1

Supply Support RHR Heat Exchanger 1-I CCW K-124-12 55S-66R VT-3 2

Supply Support RHR Heat Exchanger 1-1 CCW K-127-12 4-70SL Vr-3 3

Return Support RHR Heat Exchanger 1-1 CCW K-127-12 74-IOR VT-3 1

Return Support RHR Heat Exchanger Il-CCW K-127-12 55S-67R V'-3 2

Return Support Page 203

ASME Sec. Xl Core-%ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

CCW Supply Header C Support K-2279-12 55S-51R VT-3 3

CCW Supply Header C Support K-2279-12 55S-52R VT-3 1

CCW Return Header C Support K-2280-12 5-63R VT-3 2

Cont Fan Cooler 1-5 CCW K-3279-12 16-75SL VT-3 1

Supply Support Cont Fan Cooler 1-5 CCW K-3279-12 Not Selected Supply Support Cont Fan Cooler 1-4 CCW K-3280-12 Not Selected Supply Support Cont Fan Cooler 1-3 CCW K-3281-12 14-91SL 1VT-3 2

Supply Support Cont Fan Cooler 1-3 CCW K-3281-12 Not Selected Supply Support Cont Fan Cooler 1-2 CCW K-3282-12 Not Selected Supply Support Cont Fan Cooler 1-1 CCW K-3283-12 58S-141R VT7-3 1

Supply Support Cont Fan Cooler 1-5 CCW K-3284-12 14-83SL VT-3 2

Return Support Cont Fan Cooler 1-5 CCW K-3284-12 Not Selected Return Support Cont Fan Cooler 1-4 CCW K-3285-12 Not Selected Return Support Cont Fan Cooler 1-3 CCW K-3286-12 Not Selected Return Support Page 204

ASME Sec. Xl C ategory F-A 1 1 0

A I

kA ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Cont Fan Cooler 1-2 CCW K-3287-12 Not Selected Return Support Cont Fan Cooler 1-1 CCW K-3288-12 16-IR VT-3 1

Return Support Cont Fan Cooler 1-1 CCW K-3288-12 16-9R 1VT-3 2

Return Support CCW Pump 1-1 Recirc K-116-6 73-17R VT-3 3

Support CCW Pump 1-2 Recirc K-117-6 Not Selected Support CCW Surge Tank Conn K-121-6 14-53SL VT-3 3

Header B Support CCW Surge Tank Conn K-121-6 Not Selected Header B Support CCW Surge Tank Conn K-123-6 5-SR

.IVT-3 1

Header A Support CCW Surge Tank Conn K-123-6 5-18R VT-3 2

Header A Support CCW Surge Tank Conn K-123-6 5-21R VT-3 1

Header A Support CCW Surge Tank Conn K-123-6 5-22R VT-3 2

Header A Support CCW Surge Tank Conn K-123-6 5-23R VT-3 3

Header A Support CCW Surge Tank Conn K-123-6 5-25R VT-3 3

Header A Support CCW Surge Tank Conn K-123-6 75-IV VT-3 I

Header A Support Page 205 11--l/

ASME Sec. XI Ct,.-C..,ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IS DWG.

NDE PER.

LINE-TOTL RELIEF NOTES REQ.

CCW Surge Tank Conn K-123-6 75-4V VT-3 2

Header A Support CCW Surge Tank Conn K-123-6 75-5R VT-3 3

Header A Support CCW Surge Tank Conn K-123-6 58S-46V VT-3 1

Header A Support CCW Pump 1-3 Recirc Support K-I 57-6 Not Selected RC Pumps Therm Barrier CCW K-1357-6 12-46SL VT-3 2

Return Hdr Support RC Pumps Therm Barrier CCW K-1357-6 57N-28V VT-3 I

Return Hdr Support RC Pumps Therm Barrer CCW K17-2340-6 12-54SL VT-3 2

Return Hdr Support RC Pumps Therm Barrier CCW K17-2340-6 12-157SL VT-3 2

Return Hdr Support RC Pumps Therm Barrier CCW K17-2340-6 12-198SL VT-3 2

Return Hdr Support RC Pumps Therm Barrier CCW K17-2340-6 57N-27R VT-3 2

Return Hdr Support RC Pumps Therm Barrier CCW K1 7-2340-6 57N-32R VT-3 3

Return Hdr Support RC Pumps Therm Barrier CCW K17-2340-6 57N-33R VT-3 1

Return Hdr Support RC Pumps Therm Barrier CCW K 17-2340-6 57N-34R V1-3 2

Return Hdr Support RC Pumps Therm Barrier CCW K 17-2340-6 57N-68R VT-3 3

Return Hdr Support Page 206

ASME Sec. X1 CO ý ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

RC Pumps Therm Barrer CCW K17-2340-6 57N-70R VT-3 1

Return Hdr Support RC Pumps Therm Barrier CCW K17-2340-6 57N-71 R V'-3 2

Return Hdr Support RC Pumps Therm Bamer CCW K17-2340-6 57N-76R V'-3 3

Return Hdr Support RC Pumps Therm Barrier CCW K17-2340-6 57N-95R Vr-3 1

Return Hdr Support RC Pumps Therm Bamer CCW K17-2340-6 57N-161R VT-3 2

Return Hdr Support Aux Feedwater Pps Condensate K-380-10 86-78R V'-3 3

Suction Support Aux Feedwater Pps Condensate K-380-10 92-3R VT-3 1

Suction Support Aux Feedwater Pps Condensate K-380-10 85N-25R V'-3 2

Suction Support Aux Feedwater Pps Condensate K-380-10 85N-30R VT-3 3

Suction Support Aux Feedwater Pps Condensate K-380-10 85N-31R V'-3 1

Suction Support Aux Feedwater Pps Condensate K-380-10 85N-42R VT-3 2

Suction Support Aux Feedwater Pps Condensate K-380-10 85N-83R VT-3 3

Suction Support Aux Feedwater Pps Condensate K-380-10 85N-84R V'-3 1

Suction Support Aux Feedwater Pps Condensate K-380-10 85N-85R VT-3 2

Suction Support Page 207

ASME Sec. Xl Co'be-tategory F-A A

k ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IS! DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Aux Feedwater Pps Condensate K-380-10 85S-132R VT-3 3

Suction Support Aux Feedwater Pps Condensate K-380-10 85S-164R VT-3 1

Suction Support Aux Feedwater Pps Condensate K-380-10 85S-165R VT-3 2

Suction Support Aux Feedwater Pps Condensate K-380-10 85S-188R VT-3 3

Suction Support Aux Feedwater Pps Condensate K-380-10 85S-I89R VT-3 1

Suction Support Ram, Water Storage Resv Disch K-1862-8 92-12R VT-3 2

Hdr Support RaN% Water Storage Resv Disch K-1862-8 99-48R VT-3 3

fldr Support Raw Water Storage Resv Disch K-1862-8 99-198A VT-3 1

Hdr Support Raw Water Storage Resv Disch K-1862-8 99-212R V'-3 2

Hdr Support Raw Water Storage Resv Disch K-I 862-8 99-214R V'-3 3

Hdr Support Raw Water Storage Resv Disch K-1862-8 99-222R VT-3 1

Hdr Support Raw Water Storage Resv Disch K-1862-8 99-231R VT-3 2

Ildr Support Raw Water Storage Resv Disch K-1862-8 85S-80R V'-3 3

Hdr Support Raw Water Storage Resv Disch K-1862-8 85S-87R VT-3 1

Hdr Support Page 208

ASME Sec. Xl Coe-"ategory F-A ITEM PARTS EXAMINED COMP/LINE WELDICOMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Raw Water Storage Resv Disch Hdr Support Ram Water Storage Resv Disch Hdr Support Raw Water Storage Resv Disch Hdr Support Raw Water Storage Resv Disch Hdr Support Raw Water Storage Resv Disch Hdr Support Raw Water Storage Resv Disch Hdr Support Raw Water Storage Resv Disch Hdr Support Raw Water Storage Resv Disch Hdr Support Raw Water Storage Resv Disch IHdr Support Raw Water Storage Resv Disch Hdr Support Raw Water Storage Resv Diseh Hdr Support Raw Water Storage Resv Disch Hdr Support Raw Water Storage Resv Disch Hdr Support Aux FW Pps Raw Water Suct Hdr (support)

K-1862-8 K-1862-8 K-1862-8 K-1862-8 K-1862-8 K-1862-8 K-1862-8 K-1862-8 K-1862-8 K-1862-8 K-1862-8 K-1862-8 K-1862-8 K-6012-8 85S-98A 85S-99R 85S-118R 85S-158R 85S-159R 85S-167R 414-167R 414-168R 414-169R 414-170R 414-171R 414-172R 35N-IIIR 288-83R VT-3 VT-3 V'-3 VT-3 Vr-3 Vr-3 V'-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 2

3 2

3 Common Unit line thru LHUT room Page 209 NOTES

K.)

ASME Sec. XI C&ý..,.,Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Aux Saltwater Pps Units I & 2 GI-933-24 44-77R.

V'-3 3

Crosstie Support Component Cooling Water HX I-G1-713-24 No Supports I Outlet (support)

Component Cooling Water HX I-GI-714-24 No Supports 2 Outlet (support)

Auxiliary Saltwater Pump 1-1 GI-687-24 44-59R VT-3 1

Discharge Support Auxiliary Saltwater Pump I-1 G1-687-24 44-76R VT-3 2

Discharge Support Auxiliary Saltwater Pump I-I 01-687-24 44-81R Vr-3 3

Discharge Support Auxiliary Saltwater Pps Discharge GI-676-24 44-78R VT-3 1

Crosstie Support Auxiliary Saltwater Pps Discharge G1-676-24 44-79R VT-3 2

Crosstie Support Auxiliary Saltwater Pps Discharge G 1-676-24 44-80R Vr-3 3

Crosstie Support Auxiliary Saltwater Pps Discharge GI-676-24 44-83R VT-3 1

Crosstie Support Auxiliary Saltwater Pump 1-2 G1-680-24 Not Selected Discharge Auxiliary Saltwater Pump 1-1 G2-6159-24 288-94R VT-3 2

Discharge Support Auxiliary Saltwater Pump 1-1 G2-6159-24 288-103R VT-3 3

Discharge Support Auxiliary Saltwater Pump 1-1 G2-6159-24 288-105R Vr-3 1

Discharge Support Page 210

ASME Sec. Xl C*,Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Auxiliary Saltwater Pump I-I Discharge Support Auxiliary Saltwater Pump 1-I Discharge Support Auxiliary Saltwater Pump I-1 Discharge Support Auxiliary Saltwater Pump I-I Discharge Support Auxiliary Saltwater Pump I-I Discharge Support Auxiliary Saltwater Pump I-I Discharge Support Auxiliary Saltwater Pump 1-2 Discharge G2-6159-24 G2-6159-24 G2-6159-24 G2-6159-24 G2-6159-24 G2-6159-24 G2-6158-24 288-106R 288-104R 288-102R 288-lOIR 288-IOOR 288-90R Not selected V1"-3 VT-3 Vr-3 VT-3 Vr-3 VT-3 2

3 2

3 1

2 Also supports U-2 line 2G2-6158-24 All NOTE* For multiple components in a Class 1 system, Loop 2 is chosen; for multiple Class 2 or 3 components, the lowest numbered or "A" line is selected, except when the lowest numbered or "A" line has no supports and the higher numbered line (or "B" or "C" line) does have supports Snubbers are shown for all non-exempt lines in the ISI boundary NOTE. Common Unit items are assigned to Unit 1; for multiple components, the lowest numbered is selected Reactor Vessel Unit 2 Support U2 1.1-1 Integrally forged nozzle pads rest directly on the building structure - no exam required Page 211 NOTES

ASME Sec. Xl Co6e'ategory F-A I

POGAM PAN D

iabl

  • nvos2d ItevalRe.

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF REQ.

Pressurizer Unit 2 Support Steam Generator 2-1 (Primary Side) Support Steam Generator 2-2 (Primary Side) Support Steam Generator 2-3 (Primary Side) Support Steam Generator 2-4 (Primary Side) Support Reactor Coolant Pump 2-1 Support Reactor Coolant Pump 2-2 Support Reactor Coolant Pump 2-3 Support Reactor Coolant Pump 2-4 Support Reactor Coolant Pump Suction Loop 1 Support Reactor Coolant Pump Suction Loop 1 Support Reactor Coolant Pump Suction Loop 2 Support Reactor Coolant Pump Suction Loop 3 Support Reactor Coolant Pump Suction Loop 4 Support Pressurizer 2-1 Steam Generator 2-1 Steam Generator 2-2 Steam Generator 2-3 Steam Generator 2-4 Reactor Coolant Pp 2-1 Reactor Coolant Pp 2-2 Reactor Coolant Pp 2-3 Reactor Coolant Pp 2-4 2*5-31SPL 2"5-31SPL 2"6-31SPL 2*7-31SPL 2"8-31SPL Support Skirt Not Selected Support Structure Not Selected Not Selected Support Structure Not Selected Not Selected Not Selected Support A Support B Not Selected Not Selected Not Selected K_..

Kl-i NOTES V-3 3

Vr-3 2

VT-3 1

U2 1 2-1 U2 1 3-1 U2 1 3-1 U2 1.3-1 U2 1.3-1 U2 1 5-1 U2 1.5-1 U2. 1.5-1 U2 1 5-1 U2 4-1 U2 1 4-1 U2 1 4-2 U2. 1 4-3 U2. 1.4-4 VT-3 VT-3 Page 212

ASME Sec. Xl Cc 4ategory F-A I

POGAM PAN D

.iablo an n2dItr alRv2 ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IS DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Reactor Coolant Out Loops 1, 2, 3 and 4 (support)

Reactor Coolant Pump Discharge Loop 1, 2. 3 and 4 Pressurizer Surge Line Support Pressurizer Surge Line Support Pressurizer Surge Line Support Pressurizer Surge Line Support Pressurizer Surge Line Support Hot Leg Recirc Before 2V-8702 Support Hot Leg Recirc Before 2V-8702 Support Hot Leg Recirc Before 2V-8702 Support Hot Leg Recirc Before 2V-8702 Support Hot Leg Recirc Before 2V-8702 Support Loop 4 Hot Leg Before 2V-8701 Support Loop 4 Hot Leg Before 2V-8701 Support 2"1, 2"2, 2*3 and 2*4-29SPL 2*9, 2*10, 2*11, 2*12-27 5SPL 2"16-14SPL 2"16-14SPL 2"16-14SPL 2"16-14SPL 2"16-14SPL 2S6-109-14SPL 2S6-109-14SPL 2S6-109-14SPL 2S6-109-14SPL 2S6-109-14SPL 2S6-1665-14SPL 2S6-1665-14SPL "K..;

NOTES No supports No supports 1-23V 1-24V 1-25SL 70-27SL 70-59SL 6-7V 72-19SL 6-6V 72-20SL 6-8V 6-5V 6-3V U2.1.4-5 U2.1 4-5 U2 1 4-5 U2 1 4-5 U2:1.4-5 U2 1.4-10 U2 1.4-10 U2 1.4-10 U2 1.4-10 U2. 1.4-10 U2 1 4-10 U2. 1 4-10 VT-3 VT-3 vr-3 Vr-3 VT-3 VT-3 Vr-3 VT-3 VT-3 V1"-3 VT-3 V'I-3 Page 213

ASME ec.ROGR.~AMeoPLFAN.

.0Cavo I.,i g,

g*V.

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Loop 4 Hot Leg Before 2V-8701 Support Loop 4 Hot Leg Before 2V-8701 Support Loop 4 Hot Leg Before 2V-8701 Support Loop 4 Hot Leg Before 2V-8701 Support Accumulator Injection Loop 1 Support Accumulator Injection Loop 1 Support Accumulator Injection Loop 1 Support Accumulator Injection Loop 1 Support Accumulator Injection Loop 1 Support Accumulator Injection Loop 1 Support Accumulator Injection Loop 2 Support Accumulator Injection Loop 2 Support Accumulator Injection Loop 2 Support Accumulator Injection Loop 3 Support 2S6-1665-14SPL 2S6-1665-14SPL 2S6-1665-14SPL 2S6-1665-14SPL 2S6-253-10SPL+

2S6-253-1OSPL+

2S6-253-10SPL+

2S6-253-1OSPL+

2S6-253-10SPL+

2S6-253-1OSPL+

2S6-254-10SPL+

2S6-254-10SPL+

2S6-254-1OSPL+

2S6-255-1OSPL+

NOTES 72-22SL 72-23SL 6-4R 72-95SL 1-27R 70-1SL 70-2SL 70-58SL 2-23V 2-22V 412-22SL 70-5SL Not Selected 72-84SL U2 14-10 U2 14-10 U2 1.4-10 U2 14-10 U2. 1 4-6 U2 1 4-6 U2.1 4-6 U2 1 4-6 U2: 1.4-6 U2 1.4-6 U2. 1.4-7 U2 1 4-7 U2. 1.4-7 U2 1.4-8 VT-3 VT-3 VT-3 VT-3 VT-3 V'-3 VT-3 VT-3 VT-3 VT-3 VT-3 Vr-3 Vr-3 3

Page 214 ASME Sec. Xl Cb,=-,Category F-A

ASME Sec. X1 COý 5 ategory F-A Is a *nadas ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Accumulator Injection Loop 3 Support Accumulator Injection Loop 4 Support SIS to RCS Loop 1 Hot Leg Support SIS to RCS Loop 1 Hot Leg Support SIS to RCS Loop 1 Hot Leg Support SIS to RCS Loop 2 Hot Leg Support Safety Inj Loop 1 Hot Leg Support Safety Inj Loop 1 Hot Leg Support Safety Inj Loop 1 Hot Leg Support Safety Inj Loop 1 Hot Leg Support Safety Inj Loop 1 Hot Leg Support Safety Inj Loop 2 Hot Leg Support Safety Inj Loop 3 Hot Leg Support Safety Inj Loop 3 Hot Leg Support 2S6-255-10SPL+

2S6-256-10SPL+

2S6-2575-8 2S6-2575-8 2S6-2575-8 2S6-2576-8 2S6-235-6SPL+

2S6-235-6SPL+

2S6-235-6SPL+

2S6-235-6SPL+

2S6-235-6SPL+

2S6-236-6SPL+

2S6-237-6SPL+

2S6-237-6SPL+

Not Selected Not Selected 412-157R 412-160R 70-38SL Not Selected 412-129R 2-28V 70-33SL 70-62R 412-130R Not Selected 72-26SL 72-81SL U2. 1 4-8 U2:1 4-9 U2. 1.4-11 U2 14-11 U2 14-11 U2 1 4-12 U2 14-11 U2. 1 4-11 U2. 1 4-11 U2:1 4-11 U2 1 4-11 U2 1.4-12 U2.1.4-13 VT-3 Vr-3 VT-3 vrT-3 VT-3 VI-3 Vr-3 V'-3 VT-3 U2 14-13 V'-3 1

Page 215 NOTES

ASME Sec. Xl Co\\ue'ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Safety Inj Loop 3 Hot Leg Support Safety Inj Loop 3 Hot Leg Support Safety Inj Loop 3 Hot Leg Support Safety Inj Loop 4 Hot Leg Support RHR Pp 2-1 Inj Cold Leg 1 Support RHR Pp 2-1 Inj Cold Leg 1 Support RHR Pp 2-1 Inj Cold Leg 1 Support RHR Pp 2-1 Inj Cold Leg 1 Support RHR Pp 2-1 Inj Cold Leg 2 Support RHR Pp 2-1 Inj Cold Leg 2 Support RHR Pp 2-1 Inj Cold Leg 2 Support RHR Pp 2-1 Inj Cold Leg 2 Support RHR Pp 2-1 Inj Cold Leg 2 Support RHR Pp 2-1 Inj Cold Leg 2 Support 2S6-237-6SPL+

2S6-237-6SPL+

2S6-237-6SPL+

2S6-238-6SPL+

2S6-3844-6SPL+

2S6-3844-6SPL+

2S6-3844-6SPL+

2S6-3844-6SPL+

2S6-3845-6SPL+

2S6-3845-6SPL+

2S6-3845-6SPL+

2S6-3845-6SPL+

2S6-3845-6SPL+

2S6-3845-6SPL+

72-83SL 72-93SL Not Selected Not Selected 92-40R 92-41V 92-59R 71-72R 70-22SL 71-4SL 71-5SL 71-3SL 71-8SL 71-6SL U2' 1.4-13 VT-3 2

U2 1.4-13 V'-3 2

U2 1.4-13 U2 1.4-14 U2:1 4-15 U2-1 4-15 U2 14-15 U2 1.4-15 U2 14-16 U2 1 4-16 U2 1.4-16 U2. 1 4-16 U2:1.4-16 U2. 1.4-16 VT-3 VT-3 VT-3 VT-3 Vr-3 VT-3 V'-3 Vr-3 VT-3 VT-3 Page 216 NOTES

ASME Sec. X1 C\\__.,ategory F-A IS POGAMPAN Di sabl anv 2nanera Rv ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

RHR Pp 2-1 Inj Cold Leg 2 Support RHR Pp 2-2 Inj Cold Leg 3 Support RHR Pp 2-2 Inj Cold Leg 3 Support RHR Pp 2-2 Inj Cold Leg 3 Support RHR Pp 2-2 Inj Cold Leg 3 Support RHR Pp 2-2 Inj Cold Leg 4 Support Pressurizer 2RV-8010OA Inlet Support Pressurizer 2RV-8010OA Inlet Support Pressurizer 2RV-8010CA Inlet Support Pressurizer 2RV-801OB Inlet Support Pressurizer 2RV-8010B Inlet Support Pressurizer 2RV-8010OB Inlet Support Pressurizer 2RV-8010OC Inlet Support Pressurizer 2RV-8010CC Inlet Support 2S6-3845-6SPL+

2S6-3846-6SPL+

2S6-3846-6SPL+

2S6-3846-6SPL+

2S6-3846-6SPL+

2S6-3847-6SPL+

2S6-729-6SPL 2S6-729-6SPL 2S6-729-6SPL 2S6-728-6SPL 2S6-728-6SPL 2S6-728-6SPL 2S6-727-6SPL 2S6-727-6SPL Not Selected 73-1SL 73-2SL 73-5SL Not Selected Not Selected 414-591R 71-12SL 989-1R 989-12R 414-592R 71-58SL 71-57SL 989-17R U2' 1 4-16 U2.1.4-17 U2.1.4-17 U2 1.4-17 U2. 1.4-17 U2. 1.4-18 U2.1 4-19 U2 14-19 U2.1.4-19 U2 1 4-20 U2.1 4-20 U2 1 4-20 U2:1 4-21 V'I-3 VT-3 Vr-3 VT-3 VT-3 VT-3 Vr-3 VT-3 Vr-3 vr-3 U2' 1 4-21 V'-3 1

Page 217 NOTES

ASME Sec. X1I C_,,Category F-A I

POG AMPAN..

Diabo av.

ndIneva ev ITEM PARTS EXAMINED COMP/LINE WELD/COMlP NO.

IST DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Pressurizer 2RV-8010C Inlet Support Pressurizer Power RV Inlet Support Pressurizer Power RV Inlet Support Pressurizer Power RV Inlet Support Pressurizer RV 2PCV-455C Inlet Support Loop I Spray Line Support Loop I Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support 2S6-727-6SPL 2S6-730-6SPL 2S6-730-6SPL 2S6-730-6SPL 2S6-4081-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL NOTES Not Selected 989-23V 71-20SL 989-26V 71-21SL 70-26SL 2-34V 412-109R 92-6V 92-8R 92-23A 92-72V 2-12V 2-13R U2 1 4-21 U2 1 4-22 U2 1 4-22 U2. 1.4-22 U2. 1.4-22 U2 1 4-23 U2 1.4-23 U2 1.4-24 U2 1.4-24 U2 1.4-24 U2.1 4-24 U2 1.4-24 U2 1.4-23 U2 1 4-23 VT-3 VT-3 VT-3 VT-3 VI-3 VT-3 VT-3 VT-3 V'-3 Vr-3 Vr-3 VT-3 V'-3 Page 218

ASME Sec. X1 Coleý/ategory F-A IS RGRMPAN Dalo Canvn2dItevlRva ITEM PARTS EXAMINED Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop I Spray Line Support Loop I Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 1 Spray Line Support Loop 2 Spray Line Support COMP/LINE 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-13-4SPL 2S6-14.4SPL WELD/COMP NO.

2-44R 92-61R 2-33R 92-71R 2-14V 92-73R 2-32R 412-11OR 412-45R 92-IOR 92-9R 2-15V 92-70R 70-24SL ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

U2. 1 4-23 U2. 1 4-24 U2. 1.4-23 U2:1 4-24 U2:1 4-23 U2 1 4-24 U2 1 4-23 U2. 1.4-23 U2: 1.4-23 U2 1 4-24 U2.1 4-24 U2 1 4-23 U2.1 4-23 U2.1 4-25 VT-3 VT-3 Vr-3 Vr-3 Vr-3 VT-3 Vr-3 VT-3 Vr-3 Vi-3 VT-3 vr-3 Vr-3 VT-3 Page 219 NOTES

K>ASME Sec. XI Co&ategory F-A ITEM PARTS EXAMINED CONIP/LINE WELD/COMP NO.

IS[ DWG.

NDE PER.

LINE-TOTL RELIEF REQ.

Loop 2 Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Pressurizer Spray Line Support Loop 1 Stub [3" former RTD connection](support)

Loop 2 Stub [3" former RTD connection](support) 2S6-14-4SPL 2S6-15-4SPL 2S6-15-4SPL 2S6-15-4SPL 2S6-15-4SPL 2S6-15-4SPL 2S6-15-4SPL 2S6-15-4SPL 2S6-15-4SPL 2S6-15-4SPL 2S6-15-4SPL 2S6-15-4SPL 2S6-1141-3SPL 2S6-1147-3SPL NOTES Not Selected 412-84SL 92-4V 92-64V 92-3R 412-83R 989-22V 92-5R 93-1 R 71-19R 92-75R 71-24SL No supports No supports U2 1 4-24 U2 1 4-26 U2 1.4-26 U2 1 4-26 U2. 1 4-26 U2. 1 4-26 U2.1.4-26 U2 1.4-26 U2 1 4-26 U2:1 4-26 U2. 1 4-26 U2. 1.4-26 U2.1.4-27 U2 1 4-28 VT-3 Vr-3 VT-3 VT-3 VT-3 Vr-3 VT-3 Vr-3 VI-3 VT-3 Vr-3 Page 220

ASME Sec. Xi Co e Category F-A ISIPRORAMPLA DiaboC* nv*

g2d ne rvl ev 2.-,

ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Loop 3 Stub [3" former RTD connection](support)

Loop 4 Stub [3" former RTD connection](support)

Charging Line Loop 4 Support Charging Line Loop 3 Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron Inj Cold Leg Hdr Support Boron lnj Cold Leg Hdr Support Boron In] Cold Leg Hdr Support Letdown Line Loop 2 Support Letdown Line Loop 2 Support 2S6-1153-3SPL 2S6-1158-3SPL 2S6-246-3SPL 2S6-50-3SPL 2S6-1995-3 2S6-1995-3 2S6-1995-3 2S6-1995-3 2S6-1995-3 2S6-1995-3 2S6-1995-3 2S6-1016-3 2S6-24-3SPL 2S6-24-3SPL NOTES No supports No supports 7-8R Not Selected 7-33R 7-76R 7-35R 72-28R 72-30R 7-34R 72-27SL 7-88V 412-115R 412-113SL U2 1.4-29 U2 1 4-30 U2 1.4-31 U2 1 4-31 U2 1.4-32 U2 1.4-32 U2 1.4-32 U2 1.4-32 U2 1.4-32 U2. 1.4-32 U2 1.4-32 U2 1.4-32 U2 1.4-33 U2 1.4-33 vr-3 vr-3 VT-3 VT-3 Vr-3 Vr-3 VT-3 vr-3 VT-3 VT-3 Vr-3 VT-3 Page 221

"ASME Sec. Xl Ct-.ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Letdown Line Loop 2 Support Letdown Line Loop 2 Support Letdown Line Loop 2 Support Letdown Line Loop 2 Support Letdown Line Loop 2 Support Letdown Line Loop 2 Support Pressurizer Power RV 2PCV-474 Support Pressurizer Power RV 2PCV-474 Support Pressurizer Power RV 2PCV-474 Support Pressurizer Power RV 2PCV-474 Support Pressurizer Power RV 2PCV-474 Support Pressurizer Power RV 2PCV-474 Support Pressurizer Power RV 2PCV-474 Support Pressurizer Power RV 2PCV-455C Support 2S6-24-3SPL 2S6-24-3SPL 2S6-24-3SPL 2S6-24-3SPL 2S6-24-3SPL 2S6-24-3SPL 2S6-1171-3SPL+

2S6-1171-3SPL+

2S6-1171-3SPL+

2S6-1171-3SPL+

2S6-1 171-3SPL+

2S6-1171-3SPL+

2S6-1171-3SPL+

2S6-1172-3SPL+

2-4R U2 1.4-33 VT-3 2

U2 1.4-33 VT-3 2

70-67R 70-8R 2-9V 412-111 R 412-116R 71-69SL 412-142SL 412-143SL 412-151SL 412-152SL 412-171SL Not Selected 989-27V U2 1.4-33 U2 1.4-33 U2 1.4-33 U2 1.4-33 U2 1 4-34 U2 1.4-34 U2 1 4-34 U2. 1 4-34 U2:1 4-34 U2 1 4-34 U2. 1 4-34 VT-3 VT-3 VT-3 VT-3 V'-3 V'-3 V'-3 V'-3 VT-3 V'r-3 U2 1 4-35 Vr-3 1

Page 222 NOTES

ASME Sec. XI C6,-.,Category F-A ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Pressurizer Power RV 2PCV-455C Support Pressurizer Power RV 2PCV-455C Support Pressurizer Power RV 2PCV-455C Support Pressurizer Power RV 2PCV-455C Support Pressurizer Power RV 2PCV-455C Support Pressurizer Power RV 2PCV-455C Support Pressurizer Power RV 2PCV-455C Support Pressurizer Power RV 2PCV-456 Support Pressurizer Power RV 2PCV-456 Support Pressurizer Power RV 2PCV-456 Support Pressurizer Power RV 2PCV-456 Support Pressurizer Power RV 2PCV-456 Support Charging Line Aux Spray Support Charging Line Aux Spray Support 2S6-1172-3SPL+

2S6-1172-3SPL+

2S6-1172-3SPL+

2S6-1172-3SPL+

2S6-1172-3SPL+

2S6-1172-3SPL+

2S6-1172-3SPL+

2S6-1195-3SPL+

2S6-1195-3SPL+

2S6-1195-3SPL+

2S6-1195-3SPL+

2S6-1195-3SPL+

2S6-51-2SPL+

2S6-51-2SPL+

NOTES 412-148SL 412-149SL 989-29R 412-166SL 989-28R 412-167SL 412-168SL 412-1118SL 412-134SL 412-153SL 412-154SL Not Selected 2212-86 2215-9 U2.1 4-35 U2 1.4-35 U2:1.4-35 U2 1 4-35 U2 1.4-35 U2 1 4-35 U2 1 4-35 U2.1 4-36 U2 1 4-36 U2 1.4-36 U2 1 4-36 U2 1 4-36 U2:1 4-38 U2:1 4-39 VT-3 V'-3 VT-3 Vr-3 vr-3 V['-3 VTr-3 vrr-3 VT-3 VT-3 VT-3 VT-3 VT-3 Page 223

K-i ASME Sec. Xl C,"/Category F-A 3.,.PRORAM PLA ITEM PARTS EXAMINED COMP/LINE WVELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support 2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

NOTES 409-1A 409-2A 409-3A 898-1V 2212-20 2212-27 2215-5 78-363R 898-3 898-5 898-2 2216-16 2212-89 2215-49 U2. 1.4-38 U2 1.4-38 U2 1 4-38 U2 1.4-37 U2 1.4-38 U2.1 4-38 U2 1.4-39 U2:1.4-38 U2. 1.4-37 U2. 1 4-38 U2. 1 4-37 U2 1 4-39 U2 1 4-38 U2 1 4-39 VT-3 VT-3 VT-3 VT-3 V1-3 VT-3 Vr-3 VT.3 VT-3 V'-3 V'-3 Vr-3 V--3 Vr-3 Page 224

ASME Sec. Xl,-.-.Category F-A ITEM PARTS EXAMINED COMP/LINE WVELD/COMP NO.

IS! DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support Charging Line Aux Spray Support 2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

2S6-51-2SPL+

NOTES U2 U2 U2 U2 U2 U2 U2 U2 1 4-39 1 4-39 1.4-38 1 4-38 1.4-38 1 4-38 1.4-38 1 4-38 2215-6 2215-7 898-6 898-9 2212-21 2212-22 2212-25 2212-29 2212-88 2212-24 2212-28V 2212-91V 898-4 2212-87 VT-3 Vr-3 VT-3 VT-3 VT-3 Vr-3 Vr-3 VT-3 Vr-3 VT-3 Vr-3 VT-3 vr-3 VT-3 U2. 1 4-38 U2. 1 4-38 U2: 1.4-38 U2 1 4-38 U2. 1 4-38 U2 1 4-38 Page 225

K)

ASME Sec. XI Cd..Zategory F-A IS POGAM tA*,

Diabl C,

vn ndIntra e2 ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charging Line Aux Spray Support Charging Line Aux Spray Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-2 Seal Wtr In Support Reac Cool Pp 2-3 Seal Wtr In Support Reac Cool Pp 2-3 Seal Wtr In Support Reac Cool Pp 2-4 Seal Wtr In Support Reac Cool Pp 2-4 Seal Wtr In Support Loop 1 Cold Leg Drain RCDT Support Loop 2 Cold Leg Drain RCDT (support)

Loop 3 Cold Leg Drain RCDT Support Loop 4 Cold Leg Drain RCDT Support SI Pp 2-1 In] Hot Leg Loop 1 (support) 2S6-51-2SPL+

2S6-4532-2SPL+

2S6-54-2 2S6-54-2 2S6-55-2 &

2S6-5398-1 5 2S6-56-2 2S6-56-2 2S6-57-2 2S6-57-2 2S6-958-2SPL+

2S6-959-2SPL+

2S6-960-2SPL+

2S6-961-2SPL+

2S6-3863-2 NOTES VT-3 VT-3 vr-3 V'-3 VT-3 vr-3 2212-90 Not Selected 2730-72V 78-219SL Not Selected 78-520SL Not Selected 78-419SL Not Selected 889-5V No supports Not Selected Not Selected No supports U2 1 4-38 U2-1 4-39 U2. 1.4-40 U2:1 4-40 U2:1 4-41 U2. 1 4-42 U2. 1 4-42 U2. 1 4-43 U2 1.4-43 U2 1 4-44 U2.1.4-45 U2 1 4-46 U2. 1.4-47 U2 1.4-11 Page 226

ASME Sec. XI Co eategory F-A ISI PROGAM PLA ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

SI Pp 2-1 Inj Hot Leg Loop 2 (support)

Safety Inj Hot Leg Loop 3 (support)

Safety Inj Hot Leg Loop 4 Support SI Pps Cold Leg Loop 1 Recirc (support)

SI Pps Cold Leg Loop 2 Recirc Support SI Pps Cold Leg Loop 3 Recirc Support SI Pps Cold Leg Loop 4 Recirc Support SI Pps Cold Leg Loop 4 Recirc Support Loop 1 Cold Leg RCS Vent and Fill Support Loop 2 Cold Leg Stub

[former RTD connection]

Loop 3 Cold Leg Stub

[former RTD connection]

Loop 4 Cold Leg Stub

[former RTD connection]

Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support 2S6-3864-2 2S6-1976-2 2S6-1990-2 2S6-3855-2SPL+

2S6-3856-2SPL+

$6-3857-2SPL+

2S6-3858-2SPL+

2S6-3858-2SPL+

2S6-1140-2SPL 2S6-1146-2SPL 2S6-1152-2SPL 2S6-1159-2SPL 2S6-1991-1.5 2S6-1991-1.5 NOTES No supports No supports 2216-144 No supports 2213-16 Not Selected 78-77SL Not Selected 326-270R No supports No supports No supports 2734-36 2734-43 U2 1 4-12 U2 1 4-48 U2 1 4-49 U2. 1.4-15 U2: 1.4-16 U2. 1 4-17 U2 1.4-50 U2 1.4-50 U2* 1.4-55 U2. 1.4-56 U"2. 1.4-57 U2 1.4-58 U2. 1.4-60 U2. 1.4-60 VT-3 V-r-3 VT-3 Vr-3 Vr-3 VT-3 Page 227

KY ASME Sec. XI Co-ategory F-A IS POGAMPAN D.iabo gvo 2dIntt

e.

2 ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 1 Cold Leg Support Charging Inj Out Loop 2 Cold Leg Support 2S6-1991-1.5 2S6-1991-1.5 2S6-1991-1.5 2S6-1991-1.5 2S6-1991-1 5 2S6-1991-1 5 2S6-1991-1 5 2S6-1991-1 5 2S6-1991-1.5 2S6-1991-1.5 2S6-1991-1.5 2S6-1991-1 5 2S6-1991-1.5 2S6-1992-1 5 2217-33 2734-38 2734-40 2217-50 2734-21 2734-35 2734-23 2734-39 2217-32 2734-37 2734-41 2734-22 2734-42 Not Selected U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 1 4-59 1 4-60 1 4-60 1 4-59 1.4-60 1 4-60 1.4-60 1.4-60 1.4-59 1.4-60 1.4-60 1.4-60 Vr-3 VT-3 Vr-3 vrr-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 V'-3 VT-3 U2. 1.4-60 VT-3 3

U2. 1.4-61 Page 22B KY NOTES

ASME Sec. Xl C1,_,,ategory F-A SI PROGRM PLA ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charging Inj Out Loop 3 Cold Leg Support Charging Inj Out Loop 4 Cold Leg Support Steam Generator 2-1 (Secondary Side) Support Steam Generator 2-1 (Secondary Side) Support Steam Generator 2-1 (Secondary Side) Support Steam Generator 2-1 (Secondary Side) Support Steam Generator 2-2 (Secondary Side) Support Steam Generator 2-2 (Secondary Side) Support Steam Generator 2-2 (Secondary Side) Support Steam Generator 2-2 (Secondary Side) Support Steam Generator 2-3 (Secondary Side) Support Steam Generator 2-3 (Secondary Side) Support Steam Generator 2-3 (Secondary Side) Support Steam Generator 2-3 (Secondary Side) Support 2S6-1993-1 5 2S6-1994-1.5 Steam Generator 2-1 Steam Generator 2-1 Steam Generator 2-1 Steam Generator 2-1 Steam Generator 2-2 Steam Generator 2-2 Steam Generator 2-2 Steam Generator 2-2 Steam Generator 2-3 Steam Generator 2-3 Steam Generator 2-3 Steam Generator 2-3 Not Selected Not Selected SG-02-01-NE (snubber)

SG-02-01-NW (snubber)

SG-02-01-SE (snubber)

SG-02-O1-SW (snubber)

SG-02-02-NE (snubber)

SG-02-02-NW (snubber)

SG-02-02-SE (snubber)

SG-02-02-SW (snubber)

SG-02-03-NE (snubber)

SG-02-03-NW (snubber)

SG-02-03-SE (snubber)

SG-02-03-SW (snubber)

U2. 1.4-63 U2. 1.4-66 U2. 2.1-1 VT-3 U2 2 1-1 VT-3 U2. 2.1-1 Vr-3 U2. 2 1-1 VT-3 U2. 2 1-1 VT-3 U2:2 1-1 V'-3 U2. 2 1-1 vrr-3 U2:2 1-1 VT-3 U2: 21-1 Vr-3 U2.2 1-1 Vr-3 U2 2 1-1 VT-3 U2 2 1-1 V'-3 Page 229 KJ NOTES

ASME Sec. XI L ategory F-A 0

  • POGAMPAN Dialo anon ndIncvlR

'2 ITEM PARTS EXAMINED COM P/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Steam Generator 2-4 (Secondary Side) Support Steam Generator 2-4 (Secondary Side) Support Steam Generator 2-4 (Secondary Side) Support Steam Generator 2-4 (Secondary Side) Support Seal Injection Filter 2-1 Support Seal Injection Filter 2-2 Support Residual Ht Removal HX 2-1 (Class 2 Side) Support Residual Ht Removal HX 2-2 (Class 2 Side) Support Residual Heat Removal Pump 2-1 Support - Pump rests on plate embedded in building structure - no exam required Steam Generator 2-4 Steam Generator 2-4 Steam Generator 2-4 Steam Generator 2-4 Seal Injection Filter 2-1 Seal Injection Filter 2-2 RHR HX 2-1 RHR HX 2-2 SG-02-04-NE (snubber)

SG-02-04-NW (snubber)

SG-02-04-SE (snubber)

SG-02-04-SW (snubber)

Not Selected 3 Support Legs Two Support Legs Not Selected U2 2.1-1 VT-3 3

U2 2.1-1 VT-3 3

U2. 2.1-1 VT-3 3

U2 2.1-1 VT-3 3

U2 2 1-3 U2:2 1-3 Vr-3 U2 2.1-6 VT-3 2

U2 2.1-6 U2. 2 3-1 Page 230

,'Il K>

NOTES

"ASME Sec. Xl C\\:,ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF REQ.

Residual Heat Removal Pump 2-1 Support Residual Heat Removal Pump 2-1 Support Residual Heat Removal Pump 2-2 Support -

Pump rests on plate embedded in building structure - no exam required Residual Heat Removal Pump 2-2 Support Residual Heat Removal Pump 2-2 Support Safety Injection Pump 2-1 Support Safety Injection Pump 2-2 Support Centrifugal Charging Pump 2-1 Support Centrifugal Charging Pump 2-2 Support RHR Pump 2-1 (motor)

RHR Pump 2-1 (motor)

RHR Pump 2-2 (motor)

RHR Pump 2-2 (motor)

SI Pump 2-1 SI Pump 2-2 CCP 2-1 CCP 2-2 77-20SL (snubber) 77-21SL (snubber) 77-18SL (snubber) 77-19SL (snubber)

Pump Pedestals and Base Not selected Four Support Legs and Base Not selected Loop 4 Hot Leg to RHR Pps Support Loop 4 Hot Leg to RHR Pps Support Loop 4 Hot Leg to RHR Pps Support NOTES Vr-3 2

VT-3 2

U2 2 3-1 U2 2 3-1 U2 2 3-1 U2 2 3-1 U2. 2 3-1 U2 2 3-2 U2 2 3-2 U2: 2.3-3 U2 2 3-3 VT-3 VT-3 Vr-3 3

VT-3 1

2S1-927-14111 2SI-927-14111 2S1-927-14111 6-2R 48-41V 72-90R U2 22-1 U2 22-1 U2 22-1 Vr-3 vr-3 VT-3 1

1 2

Page 231

ASME Sec. XI Co'ftb ategory F-A Dib.1C'1 n

n nv I

tra Rv ITEM PARTS EXAMINED COM P/LINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF REQ.

Loop 4 Hot Leg to RHR Pps Support Loop 4 Hot Leg to RHR Pps Support Loop 4 Hot Leg to RHR Pps Support Residual Heat Exchr 2 Outlet Support RlIR Pump 2-1 Suction Support RHR Pump 2-1 Suction Support RHR Pump 2-1 Suction Support RHR Pump 2-1 Suction Support RHR Pump 2-1 Suction Support RHR Pump 2-1 Suction Support RHR Pump 2-1 Suction Support RHR Pump 2-1 Suction Support RHR Pump 2-1 Suction Support RHR Pump 2-1 Suction Support NOTES 2S1-927-14111 2SI-927-14111 2SI-927-14111 2SI-3551-14111 2S I-110-14111 2S1-110-14111 2S1-110-14111 2S I-110-14111 2S1-110-14111 2S1-110-14111 2Sl-110-14111 2SI-110-14111 2S1-110-14111 251-110-14111 72-77SL 412-78R 6-1 V 414-563R 22-39R 46-26R 413-101SL 47-7V 47-140R 22-11R 413-281SL 22-13V 413-IOOR 47-141A U2 2 2-1 U2 22-1 U2 22-1 U2 2 2-2 U2 2 2-25 U2 2.2-25 U2 2.2-25 U2 2.2-25 U2' 2 2-25 U2' 2 2-25 U2 2 2-25 U2 2 2-25 U2 2 2-25 U2 2 2-25 VF-3 Vr-3 Vr-3 Vr-3 Vr-3 VT-3 vr-3 VT-3 Vr-3 Vr-3 VT-3 VT-3 Vr-3 VT-3 Page 232

ASME Sec. XI C'o&m-ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IS! DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

RHR Pump 2-2 Suction Support Cont Smp to RHR Pp 2-1 Suct Support Cont Smp to RHR Pp 2-1 Suct Support Cont Smp to RHR Pp 2-1 Suct Support Cont Smp to RHR Pp 2-1 Suct Support Cont Smp to RHR Pp 2-2 Suct Support RHR Injection to Hot Leg 1& 2 (support)

RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg l&2 Support RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg 1&2 Support 2S1-111-14111 2S1-512-14111P 2SI-512-14111P 2S1-512-1411IP 2S1-512-141IIP 2S1-513-14111P 2S6-120-12 2SI-985-12111P 2S1-985-12111P 2S1-985-121IIP 2SI-985-12111P 2S1-985-12111P 2SI-985-12111P 2SI-985-12111P Not Selected 46-3A 46-IV 413-4R 22-12R Not Selected No Supports90-48R 413-376R 6-28R 7-152R 413-257V 6-78R 90-45R U2-2 2-6 U2 2 2-25 U2 2 2-25 U2 2 2-25 U2 2 2-25 U2 2 2-6 U2 22-5 U2.2 2-5 U2 2 2-3 U2. 2 2-5 U2.22-4 U2.2 2-3 U2. 2 2-5 U2 2 2-5 V'-3 VT-3 Vr-3 VT-3 V'-3 VT-3 VT*-3 VT-3 VT-3 Vr-3 VT-3 Page 233

<-I ASME Sec. XI C d-4/Category F-A I

POGAM PAN I.Dia Cnyn'2ngIneralRe.

ITEM PARTS EXAMINED CONMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg 1&2 Support RHR Injection to Ilot Leg 1&2 Support RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg l&2 Support RHR Injection to Hot Leg l&2 Support REIR Injection to Hot Leg M&2 Support RHR Injection to [lot Leg 1&2 Support RHR Injection to Hlot Leg 1&2 Support RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg 1&2 Support RHR Injection to Hot Leg l&2 Support 2SI-985-12111P 2SI-985-12111P 2SI-985-12111P 2S1-985-12111P 2SI-985-12111P 2SI-985-12111P 2SI-985-12111P 2S 1-985-121IIP 2SI-985-12111P 2SI-985-12111P 2SI-985-12111P 2SI-985-1211IP 2SI-985-12111P 2SI-985-12111P 7-153R 90-44R 90-47R 6-79R 7-151 R 412-127SL 412-92SL 49-12V 412-98R 90-46A 90-50R 70-36SL 72-25SL 72-44SL U2 22-4 V'-3 2

U2 2 2-5 VT-3 2

U2 22-5 VT-3 2

U2 22-5 VT-3 2

U2 22-4 Vr-3 2

U2 22-5 V'-3 3

U2 22-4 VT-3 3

U2 22-3 VT-3 3

U2.22-4 VT-3 3

U2:2 2-5 VT-3 3

U2 2 2-5 VT-3 3

U2-2 2-5 VT-3 1

U2 2 2-5 VT-3 2

U2 2 2-5 VT-3 2

Page 234 NOTES W

ASME Sec. Xl C'O-ategory F-A 18 POGAM AN Diabo anvn2n ntralRv2 ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

RHR Injection to Hot Leg l&2 Support RWST to RHR Pps Suction (support)

RHR Pp 2-1 lnj Cold Leg 1&2 Support RHR Pp 2-1 Inj Cold Leg 1&2 Support RIIR Pp 2-1 Inj Cold Leg 1&2 Support RHR Pp 2-1 Inj Cold Leg l&2 Support RHR Pp 2-1 Inj Cold Leg 1&2 Support RHR Pp 2-1 InJ Cold Leg 1&2 Support RHR Pp 2-1 Inj Cold Leg 1&2 Support RI-IR Pp 2-1 Inj Cold Leg l&2 Support RHR Pp 2-1 Inj Cold Leg 1&2 Support RHR Pp 2-1 Inj Cold Leg 1&2 Support RHR Pp 2-1 Inj Cold Leg l&2 Support RHR Pp 2-1 Inj Cold Leg 1&2 Support I

K-i NOTES 2S1-985-12111P 2S1-223-12111P 2S6-508-8111 2S6-508-8111 2S6-508-8111 2S6-508-8111 2S6-508-8111 2S6-508-8111 2S6-508-8111 2S6-508-8111 2S6-508-8111 2S6-508-8111 2S6-508-8111 2S6-508-8111 72-75SL 75-15SL 6-121 R 92-47R 412-17R 6-140R 92-46R 92-48R 92-50R 6-119R 71-46SL 72-31SL 412-163R 92-52R U2 2 2-5 U2 22-6 U2 22-30 U2 2 2-32 U2 2.2-32 U2 22-30 U2 2 2-32 U2 2 2-32 U2: 2 2-32 U2: 22-30 U2: 22-32 U2 2 2-30 U2 2 2-30 U2 22-31 VT-3 Vr-3 VT-3 VT-3 Vr-3 VT-3 VI-3 VT-3 Vr-3 VT-3 V'-3 Vr-3 V'-3 V'-3 Page 235

K-,

ASME Sec. Xl C*.-ategory F-A IS.I PROGRMPA ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

RHR Pp 2-1 Inj Cold Leg 1&2 2S6-508-8111 92-76R U2: 2 2-32 Vr-3 2

Support RHR Pp 2-1 Inj Cold Leg l&2 2S6-508-8111 92-45R U2 2 2-32 VT-3 2

Support RHR Pp 2-1 Inj Cold Leg 1&2 2S6-508-8111 92-67R U2 22-32 VT-3 2

Support RHR Pp 2-1 Inj Cold Leg l&2 2S6-508-8111 92-68R U2 2 2-32 VT-3 2

Support RHR Pp 2-1 lnj Cold Leg 1&2 2S6-508-8111 71-16SL U2 2 2-32 V'-3 1

Support RHR Pp 2-1 Inj Cold Leg 1&2 2S6-508-8111 71-34SL U2 2 2-32 VT-3 1

Support RHR Pp 2-1 Inj Cold Leg 1&2 2S6-508-81I1 8-49R U2 2 2-31 VT-3 3

Support RHR Pp 2-1 lnj Cold Leg 1&2 2S6-508-8111 8-52A U2 2 2-31 V17-3 3

Support RHR Pp 2-1 lnj Cold Leg 1&2 2S6-508-8111 8-53R U2 2 2-31 VT-3 3

Support RHRPp 2-1 Inj Cold Leg 1&2 2S6-508-8111 6-120R U2 22-30 VT-3 3

Support RHR Pp 2-1 InjCold Leg 1&2 2S6-508-8111 8-51R U2 2 2-31 VT-3 3

Support RHR Pp 2-1 Inj Cold Leg l&2 2S6-508-8111 92-51R U2 2 2-31 V'-3 3

Support RHR Pp 2-1 Inj Cold Leg l&2 2S6-508-8111 6-122R U2 2 2-30 VT-3 3

Support RHR Pp 2-1 Inj Cold Leg l&2 2S6-508-8111 92-49R U2. 2 2-32 VT-3 3

Support Page 236

ASME Sec. XI Cbv*tategory F-A A

ITEM PARTS EXAMINED COMP/LINE WVELD/COMP NO.

IS1 DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

RHR Pp 2-1 lnj Cold Leg l&2 2S6-508-8111 413-213SL U2 2 2-30 V'-3 3

Support RHR Pp 2-2 Inj Cold Leg 1&2 2S6-509-8111 413-204SL U2 2 2-33 VT-3 3

Support RHR Pp 2-2 Inj Cold Leg 1&2 2S6-509-8111 Not Selected U2 2 2-33 Support SIS to RCS Hot Leg Loop I 2S6-2575-8 70-55SL U2.2 2-5 VT-3 2

Support SIS to RCS Hot Leg Loop I 2S6-2575-8 90-26V U2 2 2-5 VT-3 2

Support SIS to RCS Hot Leg Loop 2 2S6-2576-8 Not Selected U2 2 2-5 Support Centr Chg Pps Disch Hdr Support 2S6-1454-6 23-36R U2 2 2-15 VT-3 1

Centr Chg Pps Disch Hdr Support 2S6-1454-6 46-19R U2 2 2-15 V'-3 1

Centr Chg Pps Disch Hdr Support 2S6-1454-6 46-16R U2 22-15 Vr-3 2

Centr Chg Pps Disch Hdr Support 2S6-1454-6 23-41R U2 22-15 VT-3 3

Centr Chg Pps Disch Hdr Support 2S6-1454-6 46-18R U2 2 2-15 VT-3 3

Charging Pps Disch Emerg 2S6-1973-6 46-21R U2 22-15 VT-3 3

Support Charging Injection Inlet Support 2S6-2032-6 413-68R U2 2 2-15 VT-3 2

Charging Injection Inlet Support 2S6-2032-6 46-1 IV U2 22-15 VT-3 3

Page 237

K>

ASME Sec. Xl

  • Category F-A I

A Ak ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. L1NE-TOTL RELIEF NOTES REQ.

RHR Pp 2-1 Inj Cold Leg Lp I 2S6-3844-6111 92-53R U2 2 2-34 Vr-3 1

Support RHR Pp 2-1 InjCold LegLp I 2S6-3844-6111 71-IR U2 2 2-34 V'-3 2

Support RfIR Pp 2-1I lnj Cold Leg Lp I 2S6-3844-6111 92-37A U2:2 2-34 VT-3 1

Support RHR Pp 2-1 Inj Cold Leg Lp I 2S6-3844-6111 92-66R U2.2 2-34 Vr-3 3

Support RHR Pp 2-1 Inj Cold Leg Lp 1 2S6-3844-6111 92-38R U2 2 2-34 VT7-3 3

Support RHR Pp 2-1 Inj Cold Leg Lp I 2S6-3844-6111 92-39R U2. 2 2-34 VT-3 3

Support RHR Pp 2-1 Inj Cold Leg Lp I 2S6-3844-6111 92-36R U2. 2 2-34 Vr-3 3

Support RHR Pp 2-1 Inj Cold Leg Lp 2 2S6-3845-6111 Not selected U2.2 2-34 Support RHR Pp 2-2 Inj Cold Leg Lp 3 2S6-3846-6111 No supports U2 2 2-33 (support)

RHR Pp 2-2 Inj Cold Leg Lp 4 2S6-3847-6111 Not Selected U2 2 2-33 Support Cent Charg Pump 2-1 Disch 2S6-45-4 23-35R U2 449292 VT-3 1

Support Cent Charg Pump 2-1 Disch 2S6-45-4 23-65R U2 449292 VT-3 2

Support Charg Pp 2-1 BP Sup to Seal 2S6-1474-3 23-21R U2. 449292 VT-3 3

Support Charg Pp 2-1 BP Sup to Seal 2S6-1474-3 23-34R U2. 449292 VT-3 1

Support Page 238

ASME Sec. XI Co-oe Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Charg Pp 2-1 BP Sup to Seal Support Charg Pp 2-1 BP Sup to Seal Support Charg Pp 2-1 BP Sup to Seal Support Cent Charg Pps Disch Hdr Support Cent Charg Pps Disch Hdr Support Cent Charg Pps Disch I-dr Support Cent Charg Pump 2-2 Disch Support Charg Pp 2-2 BP Sup to Seal Support Regen HX In Chg Ln to 2V-8108 Support Regen HX In Chg Ln to 2V-8108 Support Regen HX In Chg Ln to 2V-8108 Support 2S6-48-3 2S6-48-3 2S6-48-3 24-27A 24-47R 413-137R U2 449293 VT-3 I

U2 449293 VT-3 2

U2 449293 VT-3 3

Page 239 NOTES 2S6-1474-3 2S6-1474-3 2S6-1474-3 2S6-3678-3 2S6-3678-3 2S6-3678-3 2S6-46-4 2S6-1475-3 23-40R 413-566R 414-398R 23-46R 23-47A 46-17R Not Selected Not Selected 2

v'r-3 VT-3 Vr-3 V'-3 Vr-3 VT-3 U2 449292 U2 449292 U2 449292 U2 449292 U2 449292 U2 449292 U2 449292 U2.449292

ASME Sec. X1 Co--;ategory F-A ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Regen HX In Chg Ln to 2S6-48-3 413-58IR U2 449293 VT-3 1

2V-8 108 Support Regen HX In Chg Ln to 2S6-48-3 413-73R U2 449293 VT-3 2

2V-8108 Support Regen FIX In Chg Ln to 2S6-48-3 413-74R U2. 449293 VT-3 3

2V-8108 Support Regen HX In Chg Ln to 2S6-48-3 414-23R U2 449293 VT-3 1

2V-8108 Support RegenFHX In Chg Ln to 2S6-48-3 47-121V U2 449293 Vr-3 2

2V-8 108 Support Regen FIX In Chg Ln to 2S6-48-3 47-136R U2 449293 V17-3 3

2V-8108 Support Regen HX In Chg Ln to 2S6-48-3 47-88R U2 449293 VT-3 1

2V-8108 Support Regen HX In Chg Ln to 2S6-48-3 47-89R U2 449293 V'-3 2

2V-8108 Support Regen FIX In Chg Ln to 2S648-3 47-90R U2 449293 VT-3 3

2V-8108 Support Regen HX In Chg Ln to 2S6-48-3 47-91A U2 449293 VT-3 1

2V-8108 Support Regen HX In Chg Ln to 2S6-48-3 47-92R U2 449293 VT-3 2

2V-8108 Support Regen FIX In Chg Ln to 2S6-48-3 47-93R U2 449293 VI-3 3

2V-. 108 Support Regen HX In Chg Ln to 2S6-48-3 47-95R U2 449293 VT-3 1

2V-8108 Support Regen FIX In Chg Ln to 2S6-48-3 47-96A U2 449293 VT-3 2

2V-8 108 Support Page 240

ASME Sec. XI Ctb..ategory F-A ISIPRGRM LA Diablo. anv 2ndIntr alRv2 ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Regen HX In Chg Ln to 2V-8 108 Support Regen HX In Chg Ln to 2V-8108 Support Regen HX In Chg Ln to 2V-8108 Support Regen HX In Chg Ln to 2V-8108 Support Regen HX In Chg Ln to 2V-8 108 Support Regen IIX In Chg Ln to 2V-8108 Support Regen HX In Chg Ln to 2V-8 108 Support Regen HX In Chg Ln to 2V-8108 Support Rcgen HX In Chg Ln to 2V-8 108 Support Regen HX In Chg Ln to 2V-8108 Support Regen HX In Chg Ln to 2V-8108 Support Regen HX In Chg Ln to 2V-8108 Support Rcgen HX In Chg Ln to 2V-8108 Support Charg Pps Disch Hdr VIv Byp Support 2S6-48-3 2S6-48-3 2S6-48-3 2S6-48-3 2S6-48-3 2S6-48-3 2S6-48-3 2S6-48-3 2S6-48-3 2S6-48-3 2S6-48-3 2S6-48-3 2S6-48-3 2S6-1312-3 47-97R 47-98R 948-78R 949-190V 949-191IV 949-194A 949-196R 949-197R 949-IR 949-6R 949-7R 949-94R 949-9R No Supports U2 449293 V'-3 3

U2 449293 U2 449293 U2 449293 U2 449293 U2 449293 U2 449293 U2.449293 U2 449293 U2.449293 U2.449293 U2 449293 VT-3 vr-3 VT-3 VT-3 Vr-3 VI-3 VT-3 VT-3 V'-3 VT-3 VT-3 U2 449293 VT-3 3

U2 449293 Page 241

<-I NOTES

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Charging Pps Disch Emerg I 2S6-1974-4 46-12R U2 449305 VT-3 I

Support Charging Pps Disch Emerg I 2S6-1974-4 46-14R U2:449305 VT-3 2

Support Charging Pps Disch Emerg 2 2S6-19754 Not Selected U2:449305 Support Charging Injection Out Support 2S6-2033-4 413-16R U2:449305 VT-3 1

Charging Injection Out Support 2S6-2033-4 413-17R U2 449305 VT-3 2

Charging Injection Out Support 2S6-2033-4 414-558A U2 449305 VT-3 3

Charging Injection Out Support 2S6-2033-4 46-20R U2 449305 VT-3 1

Charging Injection Out Support 2S6-2033-4 47-59R U2 449305 VT-3 2

Charging Injection Out Support 2S6-2033-4 48-50R U2 449305 VT-3 3

Charging Inj Out Cold Legs 2S6-1978-4 413-12R U2 449305 VT-3 1

Support Charging Inj Out Cold Legs 2S6-1979-4 Not Selected U2 449305 Support Charging Inj Out Cold Legs 2S6-283-3 413-14SL U2:449305 VT-3 1

Support Charging Inj Out Cold Legs 2S6-283-3 Not Selected U2 449305 Support Charging Inj Out Cold Legs 2S6-282-3 413-1 ISL U2 449305 VT-3 3

Support Page 242 ASME Sec. Xl C,.,ýategory F-A

.11-1/ 1

ASME Sec. XI Co ategory F-A 1 1 A

IA ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Charging Inj Out Cold Legs 2S6-282-3 48-52R U2. 449305 V'-3 2

Support Charging Inj Out Header Support 2S6-1016-3 413-84V U2 449305 VT-3 3

Charging Inj Out Header Support 2S6-1016-3 413-85R U2 449305 VT-3 1

Charging Pps Disch Header 2S6-52-3 414-241R U2:449294 VT-3 2

Support Charging Pps Disch Header 2S6-52-3 414-249R U2 449294 VT-3 3

Support Charging Pps Disch Header 2S6-52-3 414-25IR U2 449294 VT-3 1

Support Charging Pps Disch Header 2S6-52-3 414-257R U2 449294 VT-3 2

Support Charging Pps Disch Header 2S6-52-3 414-261R U2 449294 VT-3 3

Support Charging Pps Disch Header 2S6-52-3 414-264R U2 449294 VT-3 1

Support Charging Pps Disch Header 2S6-52-3 949-106R U2 449294 VT-3 2

Support Charging Pps Disch Header 2S6-52-3 949-192V U2 449294 VT-3 3

Support Charging Pps Disch Header 2S6-52-3 949-193A U2. 449294 VT-3 I

Support Charging Pps Disch Header 2S6-52-3 949-1R U2 449294 VT-3 2

Support Charging Pps Disch Header 2S6-52-3 949-197R U2 449294 VT-3 3

Support Page 243

K>

ASME Sec. Xl Co -*ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Charging Pps Seal Supply 2S6-53-3 23-42R U2 449292 V'-3 1

Support Charging Pps Seal Supply 2S6-53-3 23-43R U2 449292 VT-3 2

Support Charging Pps Seal Supply 2S6-53-3 23-44R U2 449292 VT-3 3

Support Charging Pps Seal Supply 2S6-53-3 23-45A U2 449292 V"-3 1

Support Charging Pps Seal Supply 2S6-53-3 24-30A U2 449294 VT-3 2

Support Charging Pps Seal Supply 2S6-53-3 24-48R U2. 449294 VT-3 3

Support Charging Pps Seal Supply 2S6-53-3 24-49R U2 449294 V'-3 1

Support Charging Pps Seal Supply 2S6-53-3 414-621R U2 449294 VT-3 2

Support CVCS Seal Inj Filter 2-2 In 2S6-2047-3 Not Selected U2 449294 Support Seal Injection Filter Bypass 2S6-1455-3 No Supports U2 449294 Support CVCS Seal lnj Filter 2-2 Out 2S6-2048-3 Not Selected U2 449294 Support CVCS Seal lnj Filter 2-1 In 2S6-2044-3 413-95A U2 449294 VT-3 3

Support CVCS Seal Inj Filter 2-1 In 2S6-2044-3 512-41V U2 449294 VT-3 1

Support CVCS Seal Inj Filter 2-1 Out 2S6-2046-3 413-97A U2 449294 VT-3 2

Support Page 244

ASME Sec. XI Cbcategory F-A A

A ITEM PARTS EXAMINED COMP/LINE AWELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

React Cool Pps Seal WtrIn 2S6-746-3 413-533SL U2 449294 V17-3 3

Support React Cool Pps Seal Wtr In 2S6-746-3 414-294R U2 449294 Vr-3 1

Support React Cool Pps Seal Wtr In 2S6-746-3 414-314R U2 449294 V'-3 2

Support React Cool Pps Seal Wtr In 2S6-746-3 414-332R U2 449294 VT-3 3

Support React Cool Pps Seal Wtr In 2S6-746-3 48-117R U2 449294 VT-3 1

Support React Cool Pps Seal Wtr In 2S6-746-3 49-11OR U2 449294 VT-3 2

Support React Cool Pps Seal Wtr In 2S6-746-3 49-111IR U2 449294 V'-3 3

Support React Cool Pps Seal Wtr In 2S6-746-3 49-I 12A U2 449294 VT-3 1

Support React Cool Pps Seal Wtr In 2S6-746-3 49-1 13R U2 449294 VT-3 2

Support React Cool Pps Seal Wtr In 2S6-746-3 49-114R U2 449294 VT-3 3

Support React Cool Pps Seal Wtr In 2S6-746-3 49-122R U2 449294 Vr-3 1

Support React Cool Pps Seal WtrIn 2S6-746-3 49-191R U2 449294 Vr-3 2

Support React Cool Pps Seal Wtr In 2S6-746-3 49-192R U2 449294 Vr-3 3

Support React Cool Pps Seal Wtr In 2S6-746-3 75-IOR U2 449294 VT-3 1

Support Page 245

ASME Sec. Xl C Category F-A POGAM PAN-ý

"'Dabo anon2d ntrvl ev*

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

React Cool Pps Seal Wtr In Support React Cool Pps Sea! Wtr In Support Charg Pp 2-1 Bypass Miniflow Support Charg Pp 2-1 Bypass Miniflow Support Charg Pp 2-1 Bypass Miniflow Support Charg Pp 2-1 Bypass Miniflow Support Charg Pp 2-1 Bypass Miniflow Support Charg Pp 2-1 Bypass Miniflow Support Charg Pp 2-1 Bypass Miniflow Support Charg Pp 2-2 Bypass Miniflow Support Cent Chg Pps BP Miniflow Hdr Support Cent Chg Pps BP Miniflow Hdr Support Cent Chg Pps BP Miniflow Hdr Support Cent Chg Pps BP Miniflow Hdr Support 2S6-746-3 2S6-1683-3 2S6-1466-2 2S6-1466-2 2S6-1466-2 2S6-1466-2 2S6-1466-2 2S6-1466-2 2S6-1466-2 2S6-1468-2 2S6-1464-2 2S6-1464-2 2S6-1464-2 2S6-1464-2 949-28R No Supports 923-119 923-44 923-48 923-50 923-53 923-61 923-89 Not Selected 923-43 923-55 923-56 923-57 U2 449294 U2 449294 U2 449292 U2 449292 U2 449292 U2.449292 U2 449292 U2:449292 U2 449292 U2 449292 U2 449292 U2 449292 VT-3 VT-3 VT-3 V'-3 VT-3 VT-3 V'-3 Vr-3 VT-3 VT-3 U2"449292 VT-3 3

U2 449292 VT-3 I

Page 246

<-I NOTES

K>

ASME Sec. XI C~o*-dategory F-A I.,I PROGAM PAN ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Cent Chg Pps BP Miniflow Hdr Support CVCS Seal Inj Filter 2-1 In Support CVCS Seal Inj Filter 2-1 In Support CVCS Seal Inj Filter 2-2 In Support CVCS Seal Inj Filter 2-1 Out Support CVCS Seal Inj Filter 2-1 Out Support CVCS Seal Inj Filter 2-2 Out Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support 2S6-1464-2 2S6-3673-2 & 2S6-2 2S6-3673-2 & 2S6-2 2S6-3674-2 & 2S6-2 2S6-1477-2 & 2S6-2 2S6-1477-2 & 2S6-2 2S6-1478-2 & 2S6-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 923-91 949-192 949-193 U2 449292 VT-3 2

U2 449294 VT-3 3

U2 449294 VT-3 1

Not Selected 949-194 949-195 Not Selected 1548-106 1548-45 2215-3 2216-1 2216-19 2216-2 2216-4 U2 449294 U2 449294 U2 449294 U2.449294 U2 449294 U2 449294 U2 449294 U2 449294 U2 449294 U2.449294 U2 449294 VT-3 VT-3 VT-3 VT-3 Vr-3 V'-3 VT-3 VT-3 VT-3 Page 247 NOTES

ASME Sec. XI Cu-Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 2216-5 U2 449294 VT-3 2

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 2730-73 U2 449294 VT-3 3

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 2730-75 U2 449294 VT-3 1

Support Reac Cool Pp 2-1 Seal %Mr In 2S6-54-2 564-109 U2 449294 VT-3 2

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-12 U2 449294 VT-3 3

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-13 U2 449294 VT-3 1

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-15 U2 449294 VT-3 3

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-152 U2 449294 VT-3 1

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-155 U2. 470474 VT-3 2

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-16 U2 449294 Vr-3 3

Support Reac Cool Pp 2-1 Seal W'r In 2S6-54-2 564-17 U2 449294 VT-3 1

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-18 U2 449294 VT-3 2

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-19 U2 449294 VT-3 3

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-198 U2 449294 Vr-3 1

Support Page 248

ASME Sec. X1 C6%-4ategory F-A IS PRGAM LN Diab.Cavo 2nd Intra Re.

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal WMr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support Reac Cool Pp 2-1 Seal Wtr In Support 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 2S6-54-2 564-199 564-20 564-203 564-205 564-21 564-23 564-25 564-26 564-31 564-33 564-35 Location A 564-35 Location B 564-37 564-58 NOTES U2:449294 U2.449294 U2-449294 U2 449294 U2 449294 U2 449294 U2 449294 U2 449294 U2'470474 U2.470474 U2:470474 U2:470474 U2 470474 U2 449294 VT-3 Vr-3 VT-3 VT-3 VT-3 Vr-3 VT-3 vr-3 vr-3 VT-3 vr-3 VT-3 VT-3 V'-3 Page 249

ASME Sec. Xl CL..*ategory F-A A

A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-63 U2 449294 VT-3 1

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-65 U2. 449294 VT-3 2

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 564-66 U2 449294 V'-3 3

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 78-IOISL U2. 470474 VT-3 1

Support Reac Cool Pp 2-1 Seal Wtr In 2S6-54-2 78-505SL U2 449294 VT-3 1

Support Reac Cool Pp 2-2 Seal Wtr In 2S6-55-2 78-395SL U2 449294 V17-3 3

Support Reac Cool Pp 2-2 Seal Wtr In 2S6-55-2 Not Selected U2 449294 Support Reac Cool Pp 2-3 Seal Wtr In 2S6-56-2 Not Selected U2. 449294 Support Reac Cool Pp 2-4 Seal Wtr In 2S6-57-2 78-102SL U2 449294 Vr-3 1

Support Reac Cool Pp 2-4 Seal Wtr In 2S6-57-2 Not Selected U2. 449294 Support Steam Gen 2-1 Steam Outlet 2KI5-228-28V 2020-IV U2 2 2-17 VT-3 1

Support Steam Gen 2-1 Steam Outlet 2KI5-228-28V 2024-15R U2 2 2-17 VT-3 1

Support Steam Gen 2-1 Steam Outlet 2KI5-228-28V 2021-1IR U2 2 2-17 VT-3 1

Support Steam Gen 2-1 Steam Outlet 2KI5-228-28V 413-338R U2 2 2-17 VT-3 3

Support Page 250

ASME Sec. XI Cor'dCategory F-A ISI ROG AMPA Di abl gnv ndIntevalRe.-

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Steam Gen 2-1 Steam Outlet Support Steam Gen 2-1 Steam Outlet Support Steam Gen 2-2 Steam Outlet Support Steam Gen 2-2 Steam Outlet Support Steam Gen 2-2 Steam Outlet Support Steam Gen 2-3 Steam Outlet Support Steam Gen 2-3 Steam Outlet Support Steam Gen 2-4 Steam Outlet Support Steam Gen 2-4 Steam Outlet Support Steam Gen 2-4 Steam Outlet Support Main Stm Relief Vlv Hdr 2-3 Support Main Stm Relief Vlv Hdr 2-3 Support Main Stm Relief Vlv Hdr 2-3 Support Main Stm Relief Vlv Hdr 2-4 Support 2KI5-228-28V 2K15-228-28V 2KI5-227-28V 2K I5-227-28V 2K 15-227-28V 2K1 5-226-28V 2K I5-226-28V 2K 15-225-28V 2K15-225-28V 2K I5-225-28V 2KI5-1065-24V 2K15-1065-24V 2KI5-1065-24V 2KI5-1066-24V K>

NOTES 413-548R 2032-1SL 2032-2SL 413-344SL Not Selected 2033-ISL Not Selected 203 1-9SL 2033-2SL Not Selected 413-305R 2033-23SL 414-44IR 2033-16SL U2 2 2-17 U2 2.2-17 U2 2.2-18 U2 22-18 U2 22-18 U2 2 2-19 U2 2 2-19 U2.2 2-20 U2 2 2-20 U2. 2 2-20 U2 22-19 U2.2 2-19 U2 2 2-19 U2' 2 2-20 VT-3 Vr-3 VT-3 VT-3 vr-3 VT-3 V'-3 VT-3 VT-3 VT-3 Vr-3 Page 251

ASME Sec. Xl Co-rCategory F-A Diablo.Canvon 2nd Intra e.2 ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF REQ.

Main Stm Relief VIv Hdr 2-4 Support Main Stm Relief Vlv Hdr 2-4 Support Main Stm ReliefVlv tIdr 2-4 Support Steam Gen 2-1 Feed Wtr Sup Support Steam Gen 2-1 Feed Wtr Sup Support Steam Gen 2-1 Feed Wtr Sup Support Steam Gen 2-1 Feed Wtr Sup Support Steam Gen 2-1 Feed Wtr Sup Support Steam Gen 2-1 Feed Wtr Sup Support Steam Gen 2-2 Feed Wtr Sup Support Steam Gen 2-2 Feed Wtr Sup Support Steam Gen 2-3 Feed Wtr Sup Support Steam Gen 2-3 Feed Wtr Sup Support Steam Gen 2-3 Feed Wtr Sup Support 2K 15-1066-24V 2KI5-1066-24V 2K15-1066-24V 2K16-554-16V 2KI6-554-16V 2KI6-554-16V 2KI6-554-16V 2K16-554-16V 2K16-554-16V 2KI6-555-16V 2KI6-555-16V 2KI6-557-16V 2KI6-557-16V 2KI6-557-16V NOTES 2033-25SL 413-537SL Not Selected 2037-8V 413-278R 2048-15R 2048-22SL 2037-7V 413-267R 2048-23SL Not Selected 2049-13SL 2049-2SL 2049-ISL U2 2 2-20 U2 2 2-20 U2 2 2-20 U2 22-21 U2 22-21 U2 2 2-21 U2 2 2-21 U2 2 2-21 U2 2 2-21 U2 2.2-22 U2 2 2-22 U2 2 2-23 U2 2 2-23 U2 2 2-23 VT-3 Vr-3 vr-3 Vr-3 VT-3 vr-3 VT-3 Vr-3 VT-3 VT-3 VT-3 VT-3 Page 252

ASME Sec. XI C.,ýcategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Steam Gen 2-3 Feed Wtr Sup Support Steam Gen 2-3 Feed Wtr Sup Support Steam Gen 2-4 Feed Wtr Sup Support Steam Gen 2-4 Feed Wtr Sup Support Steam Gen 2-4 Feed Wtr Sup Support Steam Gen 2-4 Feed Wtr Sup Support Steam Gen 2-4 Feed Wtr Sup Support Steam Gen 2-1 MSRV Risers (support)

Steam Gen 2-2 MSRV Risers (support)

Steam Gen 2-3 MSRV Risers (support)

Steam Gen 2-4 MSRV Risers (support)

RC Pps Barrier CCW Ret ltdr Support RC Pps Barrer CCW Ret Hdr Support RC Pps Barrier CCW Ret Hdr Support NOTES 2KI6-557-16V 2KI6-557-16V 2K16-556-16V 2K16-556-16V 2KI6-556-16V 2KI6-556-16V 2KI6-556-16V 2K] 5-228-8V 2K I5-227-8V 2KI5-226-8V 2KI5-225-8V 2KI7-1357-6 2K17-1357-6 2K17-1357-6 413-388SL Not Selected 2049-14SL 2049-4SL 2049-5SL 413-399SL Not Selected No supports No supports No supports No supports 7-29V 49-23V 72-60SL U2 2 2-23 U2 2 2-23 U2. 22-24 U2 2 2-24 U2 2 2-24 U2. 2 2-24 U2 2 2-24 U2. 22-17 U2 22-18 U2 2 2-19 U2 2 2-20 U2 22-36 U2 22-36 U2 2 2-36 VT-3 vr-3 VT-3 VT-3 V'-3 VT-3 VT-3 Vr-3 VT-3 Page 253

ASME Sec. XI L,,,_jZategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

RC Pps Barrier CCW Ret Hdr Support RC Pps Barrier CCW Ret Hdr Support Auxiliary Feedwater Pump 2-1 Support Auxiliary Feedwater Pump 2-2 Support Auxiliary Feedwater Pump 2-3 Support RHR FIX 2-1 (Class 3 side)

Intermediate Support RHR HX 2-1 (Class 3 side) Upper Support RHR FI-X 2-2 (Class 3 side)

Supports Letdown Heat Exchanger 2-1 Supports Seal Water Heat Exchanger 2-1 Supports Spent Fuel Pool Heat Exchanger 2 1 Supports Component Cooling Water Surge Tank 2-1 Support Component Cooling Water Pump 2-1 Support Component Cooling Water Pump 2-2 Support 2K17-1357-6 2K17-1357-6 AFW Pump 2-1 AFW Pump 2-2 AFW Pump 2-3 RIIR HX 2-1 RHR fIX 2-1 RHR HX 2-2 Letdown HX 2-1 Seal Wtr ItX 2-I SFP ttX 2-1 CCW Surge Tank 2-1 CCW Pump 2-1 CCW Pump 2-2 404-35R 413-534R 4 Integral Legs, 2 Pedestals and Base 4 Integral Legs, 2 Pedestals and Base Not Selected 4 Braces at mid level of lix 4 Braces at top level of

'iX Not Selected 2 Supports to Base 2 Supports to Base 2 Supports to Base 2 Supports and Braces 4 Integral Legs and Base Not Selected NOTES U2 2 2-36 U2 2 2-36 DC-663056 DC-663056 DC-663056 U2 2 1-6 U2 2 1-6 U2 2 1-6 DC-6632 10 DC-663210 DC-663211 DC-663225 DC-663213 DC-663213 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3

\\rr-3 Page 254

ASME Sec. X1 Cýr..ý-ategory F-A IS POGAMPAN Diabo ano 2dentralRe*,e ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IS! DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Component Cooling Water Pump 2-3 Support CCW Heat Exchanger 2-1 Support CCW Heat Exchanger 2-2 Support RC Pump 2-1 Upper Bearing Oil Cooler Supports RC Pump 2-2 Upper Bearing Oil Cooler Supports RC Pump 2-3 Upper Bearing Oil Cooler Supports RC Pump 2-4 Upper Bearing Oil Cooler Supports Condensate Storage Tank 2-1 Support Auxiliary Saltwater Pump 2-1 Base Support Auxiliary Saltwater Pump 2-1 Suction Support Auxiliary Saltwater Pump 2-1 Motor Support Auxiliary Saltwater Pump 2-2 Supports Spent Fuel Pool Cooling Pump 2-1 Spent Fuel Pool Cooling Pump 2-2 CCW Pump 2-3 CCW HX 2-1 CCW HX 2-2 RCP 2-I UBOC RCP 2-2 UBOC RCP 2-3 UBOC RCP 2-4UBOC CST 2-1 ASW Pump 2-1 ASW Pump 2-1 ASW Pump 2-1 ASW Pump 2-2 SFPP 2-1 SFPP 2-2 Not Selected 2 Supports and Braces Not Selected Brackets mount to pump motor Not Selected Not Selected Not Selected Tank Base Bolts to concrete Pump Base Bolts to concrete 28-45R 28-44R Not Selected 2 Supports and Base 2 Supports and Base DC-663213 DC-663212 DC-663212 DC-663207 DC-663207 DC-663207 DC-663207 DC-663208 DC-663030 051373 051373 051373 DC-663211 DC-663211 V'-3 VT-3 VT-3 VT-3 Vr-3 Vr-3 VT-3 Vr-3 3

1 2

2 3

Located in intake bay 2

3 Page 255 NOTES

"ASME Sec. X1 COueJCategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Auxiliary Feedwater 2K-558-8 42-IOR VT-3 I

Pump 2-1 Suction Support Auxiliary Feedwater 2K-558-8 42-11 R VT-3 2

Pump 2-1 Suction Support Aux Feed Pump 2-1 Raw 2K-561-8 414-456R VT-3 3

Water Suction Support Aux Feed Pps 2-2 & 2-3 2K-562-8 42-2R Vr-3 I

Condens Suct Hdr Support Aux Feed Pps 2-2 & 2-3 2K-562-8 414-72R VT-3 2

Condens Suct Hdr Support Aux Feed Pps 2-2 & 2-3 2K-562-8 42-61A Vr-3 3

Condens Suct Hdr Support Auxiliary Feedwater 2K-559-6 Not Selected Pump 2-2 Suction Support Auxiliary Feedwater 2K-560-6 414-343SL VT-3 2

Pump 2-3 Suction Support Auxiliary Feedwater 2K-560-6 Not Selected Pump 2-3 Suction Support Auxiliary Feedwater 2K16-568-6 414-162SL Vr-3 I

Pump 2-1 Disch Hdr Support Auxiliary Feedwater 2KI6-568-6 414-365R Vr-3 2

Pump 2-1 Disch Hdr Support Auxiliary Feedwater 2KI6-568-6 414-386R VT-3 3

Pump 2-1 Disch Hdr Support Auxiliary Feedwater 2K16-568-6 414-480R v'r-3 I

Pump 2-1 Disch Hdr Support Auxiliary Feedwater 2KI6-568-6 414-504SL Vr-3 2

Pump 2-1 Disch Hdr Support Page 256

K>

ASME Sec. Xl ACo ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IS! DWG.

NDE PER.

LINE-TOTL RELIEF NOTES REQ.

Auxiliary Feedwater 2K16-568-6 414-505R VT-3 3

Pump 2-1 Disch Hdr Support Auxiliary Feedwater 2K 16-568-6 414-506V VT-3 I

Pump 2-1 Disch Hdr Support Auxiliary Feedwater 2KI6-568-6 42-12R VT-3 2

Pump 2-1 Disch Hdr Support Auxiliary Feedwater 2K16-568-6 42-42R VT-3 3

Pump 2-1 Disch Hdr Support Auxiliary Feedwater 2K]6-568-6 42-6R V--3 I

Pump 2-1 Disch Hdr Support Aux Feed Pump 2-2 Raw 2K-488-6 No Supports Water Suction (support)

Aux Feed Pump 2-3 Raw 2K-489-6 Not Selected Water Suction Support Aux Feed Pumps Raw Water 2K-638-8 414-173A.

V'-3 3

Suction Hdr Support Aux Feed Pumps Raw Water 2K-638-8 42-12R VT-3 2

Suction Hdr Support Aux Feed Pumps Raw Water 2K-638-8 42-5R VT-3 1

Suction Hdr Support Aux Feed Pumps Raw Water 2K-638-8 42-8R Vr-3 2

Suction Hdr Support Aux Fdw Pps Disch to Stm 2K16-476-4 111-46R VT-3 3

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2K16-476-4 111-48R V--3 I

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2K16-476-4 333-30R VT-3 2

Gen 2-1 & 2-2 Support Page 257

K)

ASME Sec. XI C&tCategory F-A AA ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

IS! DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Aux Fdw Pps Disch to Stm 2K16476-4 333-31R VT-3 3

Gen 2-1 & 2-2 Support Aux Fdw PpsDisch to Stm 2KI6-476-4 413-321R VT-3 I

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2K16-476-4 413-322R Vr-3 2

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2K16476-4 413-323R V'-3 3

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2K16-476-4 413-324R VT-3 I

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2K16-476-4 413-325R VT-3 2

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2K16-476-4 413-326R VT-3 3

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2KI6-476-4 413-421R VT-3 I

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2KI6-476-4 414-145A VT-3 2

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2KI6-476-4 414-300R VT-3 3

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2Ki6-476-4 414-483A VT-3 I

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2K16-476-4 50-IOOR VT-3 2

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2K16-476-4 50-IOIR VT-3 3

Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm 2K16-476-4 50-93R VT-3 I

Gen 2-1 & 2-2 Support Page 258

ASME Sec. X, Co kategory F-A 0

RGRMPAN Dibl ano 2dI ntra Rvm ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISl DWG.

NDE PER. LINE-TOTL RELIEF REQ.

Aux Fdw Pps Disch to Stm Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm Gen 2-1 & 2-2 Support Aux Fdw Pps Disch to Stm Gen 2-3 & 2-4 Support Aux Fdw Pp 2-2 Disch Header Support Aux Fdw Pp 2-3 Disch Header Support Aux Fdw Pps 2-2 & 2-3 Disch X-tie Support Stm Gen 2-1 Aux Fdw Supply Support Stm Gen 2-2 Aux Fdw Supply Support Stm Gen 2-3 Aux Fdw Supply Support Stm Gen 2-4 Aux Fdw Supply Support Aux Fdw Pp 2-2 Stm Gen 2-1 Disch Support Aux Fdw Pp 2-2 Stm Gen 2-1 Disch Support K-,;

NOTES V'-3 Vr-3 vr-3 vr-3 2

3 2

2K16-476-4 2KI6-476-4 2KI6-476-4 2K16-476-4 2KI6-563-4 2K16-573-4 2K16-574-4 2K 16-4292-4 2K16-569-31V+

2KI 6-570-31V+

2KI6-571-31V+

2K 16-572-31V+

2K16-575-31V+

2KI6-575-31V+

50-96R 50-97R 50-98R 50-99R Not Selected Not Selected Not Selected 414-545R 413-576A Not Selected Not Selected Not Selected 413-312R 413-418R VT-3 3

VT-3 I

Vr-3 Vr-3 2

2 Page 259

ASME Sec. X1 Cct.-/ategory F-A IS POGAMPAN Disabl ano 2dIneva ev ITEM PARTS EXAMINED COM P/LINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF REQ.

Aux Fdw Pp 2-2 Stm Gen 2-2 Disch Support Aux Fdw Pp 2-3 Stm Gen 2-4 Disch Support Aux Fdw Pp 2-3 Stm Gen 2-3 Disch Support Aux FW Pp 2-1 Suction Line Drain (support)

Aux FW Pp 2-2 Suction Line Drain (support)

Aux FW Pp 2-3 Suction Line Drain (support)

Aux Fdw Pp 2-1 Recirc Support Aux Fdw Pp 2-2 Recirc Support Aux Fdw Pp 2-3 Recirc Support Aux Feed Pump 2-1 Turbine Exhaust Support Aux Feed Pump 2-1 Turbine Exhaust Support Aux Feed Pump 2-1 Turbine Exhaust Support Aux Feed Pump 2-1 Turbine Exhaust Support Aux Feed Pump 2-1 Turbine Exhaust Support 2KI6-576-31V+

2KI6-577-31V+

2K 16-578-31V+

2K-2 off 2K-558-8 2K-2 off2K-559-6 2K-2 off 2K-560-6 2K16-564-1 5 2K16-565-1 5 2K16-566-1 5 2K-1045-10 2K-1045-10 2K-1045-10 2K-1045-10 2K-1045-10 NOTES Not Selected Not Selected Not Selected No Supports No Supports No Supports 942-14 Not Selected Not Selected 35N-24V 35N-25V 35N-4R 35N-5R 35N-74R VT-3 3

Vr-3 Vr-3 Vr-3 VT-3 V'-3 2

3 1

2 Page 260

ASME Sec. XI C

..-ategory F-A ITEM PARTS EXAMINED COMPILINE WELD/COMP NO.

ISI DWG.

NDE PER.

LINE-TOTL RELIEF NOTES REQ.

Aux Feed Pump 2-1 Turbine 2K-1045-I0 35S-38R VT-3 3

Exhaust Support Aux Feed Pump 2-1 Turbine 2K-1045-10 35S-40A VT-3 I

Exhaust Support Aux Feed Pump 2-1 Turbine 2K-1045-10 42-69R VT-3 2

Exhaust Support Aux Feed Pump 2-1 Turbine 2K-1045-10 36-56R VT-3 3

Exhaust Support Aux Feed Pump 2-1 Turbine 2K-1045-10 36-49R V'r-3 I

Exhaust Support Aux Feed Pump 2-1 Turbine 2K-1045-10 414-283R VT-3 2

Exhaust Support Aux Feed Pump 2-1 Turbine 2K-1045-I0 36-50R VT-3 3

Exhaust Support Aux Feed Pump 2-1 Turbine 2K-1045-10 414-21V VT-3 1

Exhaust Support Aux Feed Pump 2-1 Turbine 2K-1045-10 414-115R V17-3 2

Exhaust Support CCW Heat Exchanger 2-1 2K-95-30 23-75R VT-3 3

CCW Inlet Support CCW Heat Exchanger 2-1 2K-95-30 23-7V VT-3 I

CCW Inlet Support CCW Heat Exchanger 2-1 2K-95-30 404-13R VT-3 2

CcW Inlet Support CCW Heat Exchanger 2-1 2K-95-30 407-8R VT-3 3

CCW Inlet Support CCW Heat Exchanger 2-1 2K-95-30 413-105V VT-3 I

CCW Inlet Support Page 261

K.>

ASME Sec. X1 6ý..'Category F-A ROGAA is P*

M PLA CONI P/LINE ITEM PARTS EXAMINED CCW Heat Exchanger 2-1 CCW Inlet Support CCW Heat Exchanger 2-1 CCW Inlet Support CCW Heat Exchanger 2-1 CCW Inlet Support CCW Heat Exchanger 2-1 CCW Inlet Support CCW Heat Exchanger 2-1 CCW Inlet Support CCW Heat Exchanger 2-1 CCW Inlet Support CCW Heat Exchanger 2-1 CCW Inlet Support CCW Heat Exchanger 2-1 CCW Inlet Support CCW Heat Exchanger 2-1 CCW Inlet Support CCW Heat Exchanger 2-1 CCW Inlet Support CCW Heat Exchanger 2-2 CCW Inlet Support CCW Heat Exchanger 2-2 CCW Inlet Support CCW Heat Exchanger 2-1 CCW Outlet Support CCW Heat Exchanger 2-2 CCW Outlet Support WVELD/COMP NO.

2K-95-30 2K-95-30 2K-95-30 2K-95-30 2K-95-30 2K-95-30 2K-95-30 2K-95-30 2K-95-30 2K-95-30 2K-96-30 2K-96-30 2K-101-30 2K-102-30 ISI DWG.

NDE PER. LINE-TOTL RELIEF REO.

413-106V 413-108R 413-523R 413-585R 414-472A 47-5V 74-IR 74-4R 74-8R 77-1R 413-146SL Not Selected 413-119R Not Selected Vr-3 I

Page 262 NOTES VT-3 Vr-3 Vr-3 vr-3 VT-3 Vr-3 VT-3 VTr-3 VT-3 VT-3 Vr-3

,,.J ASME Sec. XI Co-de Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

IST DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

CCW Heat Exchanger Outlet 2K-98-24 No Supports Crosstie (support)

CCW Return Header A Support 2K-81-20 413-153R.

V'-3 3

CCW Return Header A Support 2K-81-20 413-158R Vl-3 I

CCW Return Header A Support 2K-81-20 413-589V VT-3 2

CCW Return Header A Support 2K-81-20 414-469A VT-3 3

CCW Return Header A Support 2K-81-20 47-20R VT-3 I

CCW Return Header A Support 2K-81-20 47-21R VT-3 2

CCW Return Header B Support 2K-82-20 Not Selected Comp Cooling Wtr Pump 2-1 2K-89-20 413-582V VT-3 3

Disch Support Comp Cooling Wtr Pump 2-2 2K-90-20 Not Selected Disch Support Comp Cooling Wtr Pump 2-3 2K-91-20 Not Selected Disch Support CCW Pumps 2-2 & 2-3 Suct 2K-97-20 No Supports Crosstte (support)

CCW Supply Header A Support 2K-103-20 407-2R VT-3 3

CCW Supply Header A Support 2K-103-20 407-3R VT-3 I

Page 263

K-I ASME Sec. XI Coe-Category F-A ITEM PARTS EXAMINED COMP/LINE WELDICOMP NO.

IS DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

CCW Supply [leader A Support 2K-103-20 413-122R VT-3 2

CCW Supply Header A Support 2K-103-20 413-124R.

VT-3 3

CCW Supply Header A Support 2K-103-20 413-126A VT-3 I

CCW Supply Header A Support 2K-103-20 47-1IR VT7-3 2

CCW Supply Header A Support 2K-103-20 47-12R VT-3 3

CCW Supply Header A Support 2K-103-20 47-13R VT-3 I

CCW Supply Hleader B Support 2K-104-20 Not Selected CCW Supply Header C Support 2K-2277-20 Not Selected CCW Return Header C Support K-2282-20 Not Selected CCW Pps 2-1 & 2-2 Suction 2K-2285-20 No Supports Crosstlie (support)

CCW Pump 2-1 Disch Hdrs A &

2K-2994-20 23-IR VT-3 1

B Support CCW Pump 2-1 Disch Hdrs A &

2K-2994-20 23-67R.

VT-3 2

B Support CCW Pump 2-1 Disch Hdrs A &

2K-2994-20 23-68R.

VT-3 3

B Support CCW Pump 2-1 Disch Hdrs A &

2K-2994-20 23-6V VT-3 I

B Support Page 264

ASME Sec. Xl C*-Kiategory F-A ISgI PRGA PLA ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

CCW Pump 2-1 Disch Hdrs A &

2K-2994-20 77-14SL VT-3 2

B Support CCW Pump 2-2 Disch Hdrs A &

2K-3036-20 Not Selected B (support)

CCW Pump 2-3 Disch Hdrs A &

2K-3039-20 Not Selected B (support)

Cont Fan Cooler CCW Sup Hdr B 2K-105-18 Not Selected Support Cont Fan Cooler CCW Ret Hdr B 2K-106-18 74-29SL VW-3 3

Support Cont Fan Cooler CCW Ret Hdr B 2K-106-18 Not Selected Support CCW Supply Header C Support 2K-2278-18 Not Selected CCW Return Header C Support 2K-2281-18 Not Selected CCW Return Header B Bypass 2K-2369-! 8 47-52V VT-3 2

Support Cont Fan Cooler Supply Hdr A 2K-146-16 413-82R VT-3 3

Support Cont Fan Cooler Supply Hdr A 2K-146-16 47-14R V'-3 1

Support Cont Fan Cooler Supply Hdr A 2K-146-16 47-15R VT-3 2

Support Cont Fan Cooler Supply Hdr A 2K-146-16 47-16R VT-3 3

Support Cont Fan Cooler Supply Hdr A 2K-146-16 74-32SL vr-3 3

Support Page 265

ASME Sec. Xl L,,

ategory F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Coant Fan Cooler Return Hdr A 2K-147-16 404-1R VT-3 2

Support Cont Fan Cooler Return Hdr A 2K-147-16 413-148R VT-3 3

Support Cont Fan Cooler Return Hdr A 2K-147-16 413-570R V'-3 I

Support Cont Fan Cooler Return Hdr A 2K-147-16 47-14R VT-3 I

Support Cont Fan Cooler Return Hdr A 2K-147-16 47-16R VT-3 3

Support Coant Fan Cooler Return Hdr A 2K-147-16 47-22R VT-3 2

Support Cont Fan Cooler Return Hdr A 2K-147-16 74-20SL VT7-3 3

Support Cont Fan Cooler Return Hdr A 2K-147-16 74-24SL VT-3 3

Support CCW Return Header A Bypass 2K-2399-16 47-23R vW-3 I

Support RHR Heat Exchanger 2-2 CCW 2K-94-12 Not Selected Supply Support RHR Heat Exchanger 2-2 CCW 2K-99-12 Not Selected Return Support RHR Heat Exchanger 2-1 CCW 2K-124-12 24-13R Vr-3 2

Supply Support RHR Heat Exchanger 2-1 CCW 2K-124-12 24-33R VT-3 3

Supply Support RHR Heat Exchanger 2-1 CCW 2K-124-12 47-86R VT-3 I

Supply Support Page 266

ASME Sec. XI Cýbuý Category F-A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

RHR Heat Exchanger 2-1 CCW 2K-127-12 24-1OR 1VT-3 2

Return Support RHR Heat Exchanger 2-1 CCW 2K-127-12 413-15SR Vr-3 3

Return Support RHR Heat Exchanger 2-1 CCW 2K-127-12 414-5R Vr-3 1

Return Support RHR Heat Exchanger 2-1 CCW 2K-127-12 47-85R VT-3 2

Return Support CCW Supply Header C Support 2K-2279-12 47-67R VT-3 3

CCW Supply Header C Support 2K-2279-12 47-68R VT-3 1

CCW Return Header C Support 2K-2280-12 413-152R V'-3 2

CCW Return Header C Support 2K-2280-12 74-11 R VT-3 3

Cont Fan Cooler 2-5 CCW 2K-3279-12 Not Selected Supply Support Cont Fan Cooler 2-4 CCW 2K-3280-12 Not Selected Supply Support Cont Fan Cooler 2-3 CCW 2K-3281-12 76-16SL 1VT-3 1

Supply Support Cont Fan Cooler 2-3 CCW 2K-3281-12 Not Selected Supply Support Cont Fan Cooler 2-2 CCW 2K-3282-12 Not Selected Supply Support Cont Fan Cooler 2-1 CCW 2K-3283-12 414-53R VT-3 2

Supply Support Page 267

AIt ASME Sec. X1 t;6,,..,ategory i--A JI PROGAM PLN,`-.

Di blCan nd I e

IOev.S ITEM PARTS EXAMINED Cont Fan Cooler 2-5 CCW Return Support Cont Fan Cooler 2-4 CCW Return Support Cont Fan Cooler 2-3 CCW Return Support Cont Fan Cooler 2-2 CCW Return Support Cont Fan Cooler 2-1 CCW Return Support Cont Fan Cooler 2-1 CCW Return Support CCW Pump 2-1 Recirc Support CCW Pump 2-2 Recirc Support CCW Surge Tank Conn Header B Support CCW Surge Tank Conn Header A Support CCW Surge Tank Conn Header A Support CCW Surge Tank Conn Header A Support CCW Surge Tank Conn Header A Support CCW Surge Tank Conn Header A Support WELD/COMP NO.

ISi DWG.

NDE PER. LINE-TOTL RELIEF REQ.

CONIP/LINE 2K-3284-12 2K-3285-12 2K-3286-12 2K-3287-12 2K-3288-12 2K-3288-12 2K-1i16-6 2K-1i17-6 2K-121-6 2K-123-6 2K-123-6 2K-123-6 2K-123-6 2K-123-6 Not Selected Not Selected Not Selected Not Selected 76-IR 76-2R 23-17R Not Selected Not Selected 25-IV 25-SR 404-18R 404-21R 404-22R Vr-3 VT-3 vr-3 Vr-3 Vr-3 Page 268 K-K-i VT-3 VT-3 VT-3 NOTES

ASME Sec. XI C*-1ategory F-A I

IA 1,A-I M

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

CCW Surge Tank Conn 2K-123-6 404-23R VT-3 2

Header A Support CCW Surge Tank Conn 2K-123-6 404-25R VT-3 3

Header A Support CCW Surge Tank Conn 2K-123-6 404-8R VT-3 I

Header A Support CCW Surge Tank Conn 2K-123-6 413-182R VT-3 2

Header A Support CCW Surge Tank Conn 2K-123-6 50-46V VT-3 3

Header A Support CCW Pump 2-3 Recirc Support 2K-157-6 Not Selected RC Pumps Therm Barrier CCW 2K-1357-6 72-43SL VT-3 2

Return Hdr Support RC Pumps Therm Barrier CCW 2K-1357-6 7-28V VT-3 3

Return Hdr Support RC Pumps Therm Barrier CCW 2K!7-2340-6 7-32R VT-3 I

Return Hdr Support RC Pumps Therm Barrer CCW 2KI7-2340-6 7-33R VT-3 2

Return Hdr Support RC Pumps Therm Barrier CCW 2K 17-2340-6 7-34R VT-3 3

Return Hdr Support RC Pumps Therm Barrier CCW 2KI7-2340-6 7-68R VT-3 I

Return Hdr Support RC Pumps Therm Barrier CCW 2K17-2340-6 7-70R VT-3 2

Return f-dr Support RC Pumps Therm Barrier CCW 2K17-2340-6 7-71R VT-3 3

Return Hdr Support Page 269

"ASME Sec. XI Co edClategory F-A A

A ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

RC Pumps Therm Barrier CCW 2K 17-2340-6 7-76R VT-3 I

Return H~dr Support RC Pumps Therm Barrier CCW 2K 17-2340-6 7-95R VT-3 2

Return Hdr Support RC Pumps Therm Barrier CCW 2K17-2340-6 72-41SL VT-3 2

Return Hdr Support RC Pumps Therm Barrier CCW 2K 17-2340-6 72-42SL VT-3 3

Return lIdr Support RC Pumps Therm Barrier CCW 2K 17-2340-6 7-27R VT-3 2

Return Hdr Support Aux Feedwater Pps Condensate 2K-380-10 35S-3 I R VT-3 3

Suction Support Aux Feedwater Pps Condensate 2K-380-10 35S-32R VT-3 I

Suction Support Aux Feedwater Pps Condensate 2K-380-10 414-147R V'-3 2

Suction Support Aux Feedwater Pps Condensate 2K-380-10 414-149R VT-3 3

Suction Support Aux Feedwater Pps Condensate 2K-380-10 414-150R V'-3 1

Suction Support Aux Feedwater Pps Condensate 2K-380-10 414-174A VT-3 2

Suction Support Aux Feedwater Pps Condensate 2K-380-10 414-207R VT-3 3

Suction Support Aux Feedwater Pps Condensate 2K-380-10 414-208R V'-3 1

Suction Support Aux Feedwater Pps Condensate 2K-380-10 414-225R Vr-3 2

Suction Support Page 270

ASME Sec. XI C(*b-Category F-A DiablCavon2ndInt V

ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

1Sl DWG.

NDE PER. LINE-TOTL RELIEF NOTES REQ.

Aux Feedwater Pps Condensate 2K-380-10 414-30R VT-3 3

Suction Support Aux Feedwater Pps Condensate 2K-380-10 414.424R VT-3 1

Suction Support Aux Feedwater Pps Condensate 2K-380-10 42-3R V'-3 2

Suction Support Raw Water Storage Resv Disch 2K-1862-8 35N-87A VT-3 3

Remainder of Inoe counted as Unit I Hldr Support Raw Water Storage Resv Disch 2K-1862-8 35N-32R VT-3 I

Hdr Support Aux Saltwater Pps Units I & 2 2G1-933-24 28-66R VT-3 2

Crosstie Support Component Cooling Water HX 2-2G1-713-24 No Supports I Outlet (support)

Component Cooling Water HX 2-2GI-714-24 No Supports 2 Outlet (support)

Auxiliary Saltwater Pump 2-1 2G1-687-24 28-38R VT-3 3

Discharge Support Auxiliary Saltwater Pump 2-1 2G1-687-24 28-46R V'-3 1

Discharge Support Auxiliary Saltwater Pump 2-1 2G1-687-24 28-62R VT-3 2

Discharge Support Auxiliary Saltwater Pump 2-1 2GI-687-24 28-63R V'-3 3

Discharge Support Auxiliary Saltwater Pump 2-1 2G 1-687-24 28-69R VT-3 1

Discharge Support Auxiliary Saltwater Pump 2-1 2GI-687-24 286-2R VT-3 2

Discharge Support Page 271

ASME Sec. XI C 6.Aategory F-A IIPRORAM PLA Diabo av 2dI ntrvl ev*2 ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. L1NE-TOTL RELIEF REQ.

Auxiliary Saltwater Pump 2-1 Discharge Support Auxiliary Saltwater Pps Discharge Crosstie Support Auxiliary Saltwater Pps Discharge Crosstie Support Auxiliary Saltwater Pps Discharge Crosstie Support Auxiliary Saltwater Pps Discharge Crosstie Support Auxiliary Saltwater Pps Discharge Crosstie Support Auxiliary Saltwater Pump 2-2 Discharge Auxiliary Saltwater Pump 2-1 Discharge Support Auxiliary Saltwater Pump 2-1 Discharge Support Auxiliary Saltwater Pump 2-1 Discharge Support Auxiliary Saltwater Pump 2-1 Discharge Support Auxiliary Saltwater Pump 2-I Discharge Support Auxiliary Saltwater Pump 2-1 Discharge Support Auxiliary Saltwater Pump 2-2 Discharge Support 2GI-687-24 2G 1-676-24 2GI-676-24 2GI-676-24 2G I-676-24 2G 1-676-24 2G1-680-24 2G2-6159-24 2G2-6159-24 2G2-6159-24 2G2-6159-24 2G2-6159-24 202-6159-24 2G2-6158-24 VT-3 Vr-3 VT-3 VT-3 V'-3 V'-3 286-67R 28-60R 28-64R 28-65R 28-67R 28-68R Not Selected 414-788R 414-789R 414-790R 414-787R 414-786R 288-90R Not Selected VT-3 VT-3 VT-3 Vr-3 3

2 3

2 3

2 3

    • Inspected with Unit I Line 6159 Page 272 K-i NOTES

ASME Sec. Xl Code Catt,.Y.jAugmented Exams IS ROGRM PAN I

iia o a

S n

ntra Rv ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISl DWG.

NDE PER. LINE-TOTL RELIEF REQ.

UNIT I RC Pump I-I Flywheel 100%

RC Pump 1-1 Flywheel RC Pump 1-1 Flywheel Inner Half Radius UI: 1l5-1 UT I

Schedule may vary due to pump maintenance requirements RC Pump 1-2 Flywheel 100%

RC Pump 1-3 Flywheel 100%

RC Pump 1-4 Flywheel 100%

RC Pump 1-2 Flywheel RC Pump 1-3 Flywheel RC Pump 1-4 Flywheel RC Pump 1-2 Flywheel Inner Half Radius RC Pump 1-3 Flywheel Inner Half Radius RC Pump 1-4 Flywheel Inner Half Radius UI 1.5-1 UT 3

U1.15-1 UT 2

Ul I5-1 UT 3

Schedule may vary due to pump maintenance requirements Schedule may vary due to pump maintenance requirements Schedule may vary due to pump maintenance requirements Page 273 NOTES

AbMr-beC. Al LoUUU o L,.

UU..

ISIPRGRAMPLAN Diabl Canon 2n intrval ev.

ITEM PARTS EXAMINED COM P/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

UNIT 2 RC Pump 2-1 Flywheel. 100%

RC Pump 2-2 Flywheel 100%

RC Pump 2-3 Flywheel 100%

RC Pump 2-1 Flywheel RC Pump 2-2 Flywheel RC Pump 2-3 Flywheel RC Pump 2-1 Flywheel Inner Half Radius RC Pump 2-2 Flywheel Inner Half Radius RC Pump 2-3 Flywheel Inner Half Radius U2. 1.5-1 UT 2

U2 15-1 UT 2

U2 15-1 UT Schedule may vary due to pump maintenance requirements Schedule may vary due to pump maintenance requirements Schedule may vary due to pump maintenance requirements Page 274 K-i I

NOTES

ASME Sec. XI Code Cate~o4 Augmented Exams IS POGAMPAN Diabl Cng ndInervl ev-ITEM PARTS EXAMINED COMP/LINE WELD/COMP NO.

ISI DWG.

NDE PER. LINE-TOTL RELIEF REQ.

RC Pump 2-4 Flywheel 100%

RC Pump 2-4 Flywheel RC Pump 2-4 Flywheel Inner Half Radius U2 15-I UT 3

Schedule may vary due to pump maintenance requirements NOTE. RC pump flywheel examinations are conducted in accordance with DCPP technical specifications 5 5 7, "Reactor Coolant Pump Flywheel Inspection Program" Refer to WCAP-14535A for technical justification, see AR# A0500491 Page 275 KJ I

NOTES

\\

S ASME Sec. Xl Code Cma~ory Pressure Tests I

POGAM PAN Diabl Cnvo ndIntra Rv DESCRIPTION SHEET#N FRQ.

EXAM RELIEF REQ CLASS I Reactor Coolant System and Connected Piping Excess Letdown between 8166 & 8167 8

12 14 14 Pressurizer Auxiliary Spray Alternate Charging RItR & SI to Cold Legs Charging Injection Inside Cont.

Safety Injection Inside Cont, From 8905A-D to 8949A-D RIIR Between 8702 & 8701 17 18 19,20 20 R, I R, I R, I R, I R, I R, I R, I R, I VT-2 PRS-IA,B,C, PRS-IE and F apply throughout this table RI VT-2 PRS-IC,RI VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 PRS-IC, RI PRS-IC, RI PRS-1C, RI PRS-IC, RI PRS-IC, RI PRS-IC, RI Page 276

<-V TEST #

K-i NOTES 2

3 I

ASME Sec. X1 Code CL_,r Pressure Tests ISI PROG AMPA Diablo anvn2dItevlRv DESCRIPTION SHEET #

FRQ.

EXAM RELIEF REQ CLASS 2 Steam Generators and Connected Piping Auxiliary Feedwater Pumps X-2 & X-3 Discharge Auxiliary Feedwater Pump X-I Discharge RCS Loops I & 4 Hot Leg Sample Lines Pressurizer Sample Lines XS Ltdn HX & piping from 8167 to tICV-123 RCP Hi Press Seal Water out & XS Ltdn HX outlet piping Charging Pumps Discharge Piping Recip Chg Pump & Disch Piping to 8475 Alt Charging Between 8483, 8147 & 8379A Charging Injection 8803A & B to 8801A & B Charging Injection 8801A & B to 8820 3,5,6 3

3 8,22 10,22 12 12 12, 14, 18 14 14 18 18 P,I P, I P, I P, I P, I P, I P, I P, I P, I P, I P, I P, I PRS-1 E and F apply throughout this table VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid, Extend exam to 8105 per A0308932 System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid Page 277 TEST #

NOTES

ASME Sec. XI Code &,,

6 ry Pressure Tests i ROGRM LA Dialo anon ndInevlR

.2 SIIEET#

FRQ.

EXAM RELIEF REQ 13 14 15 15a 16 17 18 19 20 21 22 23 24 25 Charging Pumps & Suction Piping 14, 18 Regenerative HX and Letdown Piping 13 Boric Acid Pumps Disch Piping 14, 15 Boric Acid Pumps Disch Piping Between 8104 and 8445 14 Boric Acid Tanks to Pump Disch Iso Valves 15 Accumulator Injection Loops 1.4, Sample Lines to 9352A-D, Test & Fill lines to 8878A-D 17,22 Accumulator, RHR & Charging Test Lines 17-19 RWST & Supply to RHR, Cont Spray, SI, Refueling Wtr Purification Pumps &Recirc Line 18-20 & 23, to RHR HX 24 RWST Supply to Chg Pp Suction, 8805A & B to 8924 18 Safety Injection Pump Discharge to 8802A & B and Cold Legs 19 Safety Injection Pumps Discharge to Hot Legs from 8802A & B to 8904A-D 19 RHR Pumps and Discharge Piping 18-23 RHR Hot Leg injection from 8703 to 8740A & B 20 Spray Additive Tank and Unisolable piping 23 P, I P, I P, I P, I P, I P, I P, I P, I P, I P, I P, I P, I P, I P, I System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 Page 278 TEST #

DESCRIPTION K>

NOTES System Contains Boric Acid System Contains Boric Acid, Extend exam to 8974A per A0308932 System Contains Boric Acid System Contains Boric Acid System Contains Boric Acid

ASME Sec. Xl Code Cegory Pressure Tests

.-S ROGR+/-AM PANk "Diabloa' n*

nndI ntevalRe.

2 DESCRIPTION SHEETN FRQ.

EXAM RELIEF REQ 26 27 28 29 30 31 32 33 34 35 36 37 38 39 RWST Supply to Eductors 23 Cont Spray Pump Disch Piping to 9015A & B 23 Cont Spray Pump Disch Piping from 9015A & B to 9006A & B 23 Cont Spray Ring Piping, Spec S3 23 CCW Supply & Return to Cont Fan Coolers, RCPs and XS Letdown Heat Exchanger 27, 29, 31, 32 Steam Generator Nitrogen Supply 6

RX Vessel Level Indication and Vent System 9

Class 2 Containment Penetrations for Non-Safety Related Systems Operating Under 50 PSI 10 PZR Relief Tank Nitrogen Supply 10 Primary Water Supply to PZR Relief Tank 10 Accumulator Tanks Nitrogen Supply Header 17 Accumulators Sample Header 22 Fuel Transfer Tube to Refueling Canal 24,42 Auxiliary Steam Containment Penetration 40 P, I P, I P, I I*

P, I P, I P, I P, I P, I P, I P,

P, I P, I VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2*

VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 Page 279 TEST N NOTES System Contains Boric Acid PRS-5, RI

  • Satisfied by Open Flowpath Test PRS-3 System Contains Boric Acid PRS-2, R I
  • Test may be satisfied by LLRT at 50# with check for thru wall leaks System Contains Boric Acid PRS-4, RI
  • Visual Inspection of O-Ring in Lieu of Pressure Test

ASME sec. A lL;oae u._ry rressure m w, 3.31POGRAMPLAN DESCRIPTION SHEET #

FRQ.

EXAM RELIEF REQ Firewater Supply Before Containment Refueling Canal Water Inlet Reactor Coolant Drain Tank Nitrogen Sup Reactor Coolant Drain Pumps Discharge Header Inside Cont Instrument Air Supply Header Service Air Penetration Header 41 42 42 42 45 45 P,

P, P.

P, P.

P, VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 System Contains Boric Acid System Contains Boric Acid Page 280 TEST #

KJ 40 41 42 43 44 45 NOTES

"ASME Sec. Xl Code Cat,,fory Pressure Tests IS POGAMPAN D

iabo an 2d ntralRv2 DESCRIPTION SHEET#4 FRQ.

EXAM RELIEF REQ CLASS 3 Motor Driven Auxiliary Feedwater Pumps Discharge, Chemical Injection & Recirc Piping Motor Driven Auxiliary Feedwater Pumps Discharge Piping Cross Tie Turbine Driven Auxiliary Feedwater Pump Discharge Piping Condensate Storage Tank & Suction Lines to Auxiliary Feedwater & makeup Water Pumps Turbine Driven Auxiliary Feedwater Pump Steam Supply, Exhaust & Drains Component Cooling Water System Class 3 Component Cooling Water inside containment Fire Water Transfer Tank Makeup Water Transfer Pumps Discharge to CCW & Spent Fuel Pit System Makeup Water Transfer Pumps Discharge to SFP (MU-803 to SFP)

Auxiliary Saltwater Pumps Supply to CCW Heat Exchangers Diesel Engine Jacket Water Cooling System 3

3 3

3,33 6

25-32 29 33 33,36 24,34 35 37 P, I P, I P, I P, I P, I P, I P, I P, I P, I P, I P, I P, I PRS-1E and F apply throughout this table VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 VT-2 Page 281 TEST #

NOTES la 2

3 4

5 6

7 8

9 10

ASME Sec. Xl Code C,_

ry Pressure Tests TEST #

DESCRIPTION SHEET#

FRQ.

EXAM RELIEF NOTES REQ II Spent Fuel Pool Cooling System 24 P, I VT-2 12 Raw Water Storage Reservoir to Auxiliary Feedwater Pumps Suction 3, 36, P, I VT-2 38,39 13 Raw Water Storage Reservoir to Auxiliary Feedwater Pumps from FCV-436 & 437 to FW-3 P, I VT-2 349 & 353 Page 282