ML030380579

From kanterella
Jump to navigation Jump to search
Technical Specifications and Bases
ML030380579
Person / Time
Site: Palisades 
Issue date: 01/22/2003
From:
Consumers Energy
To: Hood D
Document Control Desk, Office of Nuclear Security and Incident Response
References
Download: ML030380579 (75)


Text

Date Entered: Jan 22, 2003 TO:

US NUCLEAR REGULATO C

MISSION DSHOOD opy Number.

12 TRANSMITAL NUMBER:

234085 PROCEDURE NUMBER: TECH SpocS TITLE: PALISADNE PLANT TECHNICAL SPECIFICATIONS AND BASTS TRANSMITTAL: LISTED BELOW MFE NEW/REVISED PROCEDURES WHICH MUST BE IMMEDIATELY 4f NRTED INTO OR DISCARDED FROM YOUR PROCEDURE MANUAL.

Action Required Section or Description PLEASE MAKE CHANGES TECHNICAL SPECIFICATIONS BASES PER THE ATTACHED INSTRUCT~~

SIGN, DATE, AND RETURN THE A CKNO WtEDGEMENT FORM WITHIN 10 DAYS TO THE PALISADES PLANT DOCUMENT CONTROL SIGNATURE OR INITIALS DATE i L `eI Irff

TECHNICAL SPECIFICATIONS PALISADES PLANT Docket 60-255 - License DPR-20 Page Change Instructions Technical Specifications Bases Changes January 22, 2003 Revise your copy of the Palisades Technical Specification Bases by removing the Pages Identified below and Insertin-q the attached revised and additional pagqes. The revised and additional pages are identified by a revision date at the bottom of the pages and contain vertical lines in the margin indicating the areas of change.

TECHNICAL SPECIFICATIONS BASES List of Effective Pages (2 pgs), Rev 12/30/02 List of Effective Pages (2 pgs), Rev 01/22/03 Section B 3.3.1 (35 pgs), rev 5/23/02 Section B 3.3.1 (35 pgs), Rev 01=22103 Section B 3.3.3 (24 pgs), Rev 4/22/02 Section 8 3.3.3 (24 pgs), Rev 01/22/03 Section B 3.6.6 (12 pgs), Rev 7/22/02 Section B 3.6.6 (12 pgs), Rev 01/22/03

.1i PALISADES TECHNICAL SPECIFICATIONS BASES LIST OF EFFECTIVE PAGES COVERSHEET Title Page 208 - Revised 05/23/02 TABLE OF CONTENTS Page I Page Ii TECHNICAL SPECIFICATIONS BASES Pages Pages B 2.1.1 B 2.1.1-4 B 2.1.2 B 2.1.2-4 Pages B 3.0 B 3.0-14 Bases 2.0 Bases 3.0 Bases 3.1 Bases 3.2 Bases 3.3 Bases 3.4 B3.1.1 B 3.1.1-5 3.1.2-1 -63.1.2-6 B 3.1.3 B 3.1.3-4 B 3.1.4 B 3.1.4-13 B 3.1.5 B 3.1.5-7 B 3.1.6 B 3.1.6-9 B 3.1.7 B 3.1.7-6 B 3.2.1-1.- B 3.2.1-11 B 3.2.2 B 3.2.2-3 B 3.2.3 B 3.2.3-3 B 3.2.4 B 3.2.4-3 B 3.3.1 B 3.3.1-35 B 3.3.2 B 3.3.2-10 B3.3.3 B 3.3.3-24 B 3.3.4 B 3.3.4-12 B3.3.5 B 3.3.5-6 B 3.3.6 B 3.3.6-6 B 3.3.7 B 3.3.7-12 B 3.3.8 B 3.3.8-6 B 3.3.9 B 3.3.9-5 B 3.3.10 B 3.3.104 B 3.4.1 B 3.4.1-5 B 3.4.2 B 3.4.2-2 B 3.4.3 B 3.4.3-7 B 3.4.4 B 3.4.4-4 B 3.4.5 B 3.4.5-5 B 3.4.6 B 3.4.6-6 B 3.4.7 B 3.4.7-7 B 3.4.8 B 3.4.8-5 B 3.4.9 B 3.4.9-6 63.4.10 B 3.4.10-4 63.4.11 B 3.4.11-7 83.4.12 B 3.4.12-13 B 3.4.13 B 3.4.13-6 B 3.4.14 B 3.4.14-8 B 3.4.15 B 3.4.15-6 B 3.4.16 B 3.4.16-5 205 189 Revised 09/28/01 189 189 - Revised 08/09/00 189 189 - Revised 08/09/00 189 Revised 12/30/02 189 - Revised 08/09100 Revised 09/28/01 189 - Revised 08/09/00 Revised 09/28101 Revised 09/28/01 Revised 09/28/01 189-Revised 08/09/00 Revised 01/22/03 189 - Revised 02/12/01 Revised 01/22/03 189 189 189 - Revised 02/12/01 Revised 05/04/01 189 189 - Revised 08/09/00 189 189 189 189 189 189-Revised 08/09/00 189 - Revised 02/12/01 Revised 12/02/02 189 - Revised 02/12/01 189 189 189-Revised 08/09/00 Revised 07/22/02 Revised 07/22/02 189 - Revised 08/09/00 Revised 07/22/02 Revised 07/22/02 Revised 01/22/2003.

Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages I.

PALISADES TECHNICAL SPECIFICATIONS BASES LIST OF EFFECTIVE PAGES Bases 3.5 Pages Page Page Page Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Pages Revised 01/22/2003 B 3.5.1 B 3.5.1-5 B 3.5.1-6 B 3.5.1-7 B 3.5.1-8 B 3.5.2 B 3.5.2-12 B 3.5.3 B 3.5.3-4 B 3.5.4 B 3.5.4-7 B 3.5.5 B 3.5.5-5 B 3.6.1 B 3.6.1-4 B 3.6.2 B 3.6.2-8 B 3.6.3 B 3.6.3-11 B 3.6.4 B 3.6.4-3 B 3.6.5 B 3.6.5-3 B 3.6.6 B 3.6.6-12 B 3.6.7 B 3.6.7-6 B 3.7.1 B 3.7.1-4 B 3.7.2 B 3.7.2-6 B 3.7.3 B 3.7.3-5 B 3.7.4 B 3.7.4-4 B 3.7.5 B 3.7.5-9 B 3.7.6 B 3.7.6-4 B 3.7.7 B 3.7.7-9 B 3.7.8 B 3.7.8-8 B 3.7.9 B 3.7.9-3 B 3.7.10 B 3.7.10-7 B 3.7.11 B 3.7.11-5 B 3.7.12 B 3.7.12-7 B 3.7.13 B 3.7.13-3 B 3.7.14 B 3.7.14-3 B 3.7.15 B 3.7.15-2 B 3.7.16 B 3.7.16-3 B 3.7.17 B 3.7.17-3 B 3.8.1 B 3.8.1-24 B 3.8.2 B 3.8.2-4 B 3.8.3 B 3.8.3-7 B 3.8.4 B 3.8.4-9 B 3.8.5 B 3.8.5-3 B 3.8.6 B 3.8.6-6 B 3.8.7 B 3.8.7-3 B 3.8.8 B 3.8.8-3 B 3.8.9 B 3.8.9-7 B 3.8.10 B 3.8.10-3 B 3.9.1 B 3.9.1-4 B 3.9.2 B 3.9.2-3 B 3.9.3 B 3.9.3-6 B 3.9.4 B 3.9.4-4 B 3.9.5 B 3.9.5-4 B 3.9.6 B 3.9.6-3 2

Bases 3.6 Bases 3.7 189 191 189 191 Revised 04122/2002 Revised 07/22/02 Revised 04/22/2002 189 Revised 12/10/02 Revised 12/10/02 Revised 12/10/02 Revised 04/27/01 Revised 04/27/01 Revised 01/22/03 189 - Revised 11/09/00 189 - Revised 02112/01 Revised 12/02/02 Revised 12/02/02 189-Revised 08/09/00 Revised 08/01/01 189-Revised 08/09/00 Revised 07/22/02 Revised 08/01/01 Revised 07116/01 Revised 08/01/01 189 189 189 - Revised 08/09/00 189 207 207 Revised 07/22/02 189-Revised 08/09/00 Revised 11/06/01 Revised 07/22/02 189 -. Revised 08/09/00 Revised 11/06/01 189 - Revised 08/09/00 189 Revised 11/06/01 Revised 11/06/01 Revised 11106101 189 - Revised 08/09/00 189 - Revised 02/12/01 189 - Revised 08109/00 Revised 07/22/02 189-Revised 02/12/01 189 - Revised 02/27/01 Bases 3.8

<-/_

Bases 3.9 I

RPS Instrumentation B 3.3.1 B 3.3 INSTRUMENTATION B 3.3.1 Reactor Protective System (RPS) Instrumentation BASES BACKGROUND The RPS initiates a reactor trip to protect against violating the acceptable fuel design limits and breaching the reactor coolant pressure boundary during Anticipated Operational Occurrences (AOOs). (As defined In 10 CFR 50, Appendix A, "Anticipated operational occurances mean those conditions of normal operation which are expected to occur one or more times during the life of the nuclear power unit and Include but are not limited to loss of power to all recirculation pumps, tripping of the turbine generator set, isolation of the main condenser, and loss of all offsite power.') By tripping the reactor, the RPS also assists the Engineered Safety Features (ESF) systems in mitigating accidents.

The protection and monitoring systems have been designed to ensure safe operation of the reactor. This Is achieved by specifying i-miting Safety System Settings (LSSS) in terms of parameters directly monitored by the RPS, as well as LCOs on other reactor system parameters and equipment performance.

The LSSS, defined In this Specification as the Allowable Values, in conjunction with the LCOs, establish the threshold for protective system action to prevent exceeding acceptable limits during Design Basis Accidents (DBAs).

During AOOs, which are those events expected to occur one or more times during the plant life, the acceptable limits are:

The Departure from Nucleate Boiling Ratio (DNBR) shall be maintained above the Safety Limit (SL) value to prevent departure from nucleate boiling; Fuel centeriine melting shall not occur, and The Primary Coolant System (PCS) pressure SL of 2750 psia shall not be exceeded.

Maintaining the parameters within the above values ensures that the offsite dose will be within the 10 CFR 50 (Ref. 1) and 10 CFR 100 (Ref. 2) criteria during AOOs.

Palisades Nuclear Plant Revised 01/22/2003 B -3.3. 1-1

RPS Instrumentation B 3.3.1 BASES BACKGROUND Accidents are events that are analyzed even though they are not (continued) expected to occur during the plant life. The acceptable limit during accidents is that the offsite dose shall be maintained within an acceptable fraction of 10 CFR 100 (Ref. 2) limits. Different accident categories allow a different fraction of these limits based on probability of occurrence. Meeting the acceptable dose limit for an accident category is considered having acceptable consequences for that event.

The RPS Is segmented into four interconnected modules. These modules are:

Measurement channels; RPS trip units; Matrix Logic; and Trip Initiation Logic.

This LCO addresses measurement channels and RPS trip units. It also addresses the automatic bypass removal feature for those trips with Zero Power Mode bypasses. The RPS Logic and Trip Initiation Logic are addressed in LCO 3.3.2, "Reactor Protective System (RPS) Logic and Trip Initiation." The role of the measurement channels, RPS trip units, and RPS Bypasses is discussed below.

Measurement Channels Measurement channels, consisting of pressure switches, field transmitters, or process sensors and associated instrumentation, provide a measurable electronic signal based upon the physical characteristics of the parameter being measured.

With the exception of Hi Startup Rate, which employs two instrument channels, and Loss of Load, which employs a single pressure sensor, four identical measurement channels with electrical and physical separation are provided for each parameter used in the direct generation of trip signals. These are designated channels A through D.

Some measurement channels provide input to more than one RPS trip unit within the same RPS channel. In addition, some measurement channels may also be used as inputs to Engineered Safety Features (ESF) bistables, and most provide indication in the control room.

Palisades Nuclear Plant B 3.3.1-2 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES BACKGROUND Measurement Channels (continued)

(continued)

In the case of Hi Startup Rate and Loss of Load, where fewer than four sensor channels are employed, the reactor trips provided are not relied upon by the plant safety analyses. The sensor channels do however, provide trip input signals to all four RPS channels.

When a channel monitoring a parameter exceeds a predetermined setpoint, indicating an abnormal condition, the bistable monitoring the parameter in that channel will trip. Tripping two or more channels of bistable trip units monitoring the same parameter de-energizes Matrix Logic, (addressed by LCO 3.3.2) which in turn de-energizes the Trip Initiation Logic. This causes all four DC clutch power supplies to de-energize, interrupting power to the control rod drive mechanism clutches, allowing the full length control rods to insert into the core.

For those trips relied upon in the safety analyses, three of the four measurement and trip unit channels can meet the redundancy and testability of GDC 21 in 10 CFR 50, Appendix A (Ref. 1). This LCO requires, however, that four channels be OPERABLE. The fourth channel provides additional flexibility by allowing one channel to be removed from service (trip channel bypassed) for maintenance or testing while still maintaining a minimum two-out-of-three logic.

Since no single failure will prevent a protective system actuation, this arrangement meets the requirements of IEEE Standard 279-1971 (Ref. 3).

Most of the RPS trips are generated by comparing a single measurement to a fixed bistable setpoint. Two trip Functions, Variable High Power Trip and Thermal Margin Low Pressure Trip, make use of more than one measurement to provide a trip.

The required RPS Trip Functions utilize the following input instrumentation:

Variable High Power Trip (VHPT)

The VHPT uses 0 Power as its Input. 0 Power is the higher of NI power from the power range NI drawer and primary calorimetric power (AT power) based on PCS hot leg and cold leg temperatures. The measurement channels associated with the VHPT are the power range excore channels, and the PCS hot and cold leg temperature channels.

Palisades Nuclear Plant B 3.3.1-3 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES BACKGROUND Measurement Channels (continued)

Variable High Power Trio (VHPPT) (continued)

The Thermal Margin Monitors provide the complex signal processing necessary to calculate the TM/LP trip setpoint, VHPT trip setpoint and trip comparison, and Q Power calculation. On power decreases the VHPT setpoint tracks power levels downward so that it is always within a fixed increment above current power, subject to a minimum value.

On power increases, the trip setpoint remains fixed unless manually reset, at which point it increases to the new setpoint, a fixed increment above Q Power at the time of reset, subject to a maximum value. Thus, during power escalation, the trip setpoint must be repeatedly reset to avoid a reactor trip.

Hi-gh Startup Rate Trip The High Startup Rate trip uses the wide range Nuclear Instruments (NIs) to provide an input signal. There are only two wide range NI channels. The wide range channel signal processing electronics are physically mounted in RPS cabinet channels C (NI-1/3) and D (NI-2/4). Separate bistable trip units mounted within the NI-1/3 wide range channel drawer supply High Startup Rate trip signals to RPS channels A and C. Separate bistable trip units mounted within the NI-2/4 wide range channel drawer provide High Startup Rate trip signals to RPS channels B and D.

Low Primary Coolant Flow Trio The Low Primary Coolant Flow Trip utilizes 16 flow measurement channels which monitor the differential pressure across the primary side of the steam generators. Each RPS channel, A, B, C, and D, receives a signal which is the sum of four differential pressure signals. This totalized signal is compared with a setpoint in the RPS Low Flow bistable trip unit for that RPS channel.

Palisades Nuclear Plant B 3.3.1-4 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES BACKGROUND Measurement Channels (continued)

(continued)

Low Steam Generator Level Trips There are two separate Low Steam Generator Level trips, one for each steam generator. Each Low Steam Generator Level trip monitors four level measurement channels for the associated steam generator, one for each RPS channel.

Low Steam Generator Pressure Trips There are also two separate Low Steam Generator Pressure trips, one for each steam generator. Each Low Steam Generator Pressure trip monitors four pressure measurement channels for the associated steam generator, one for each RPS channel.

High Pressurizer Pressure Trip The High Pressurizer Pressure Trip monitors four pressurizer pressure channels, one for each RPS channel.

Thermal Margin Low Pressure (TM/LP) Trio The TM/LP Trip utilizes bistable trip units. Each of these bistable trip units receives a calculated trip setpoint from the Thermal Margin Monitor (TMM) and compares It to the measured pressurizer pressure signal. The TM/LP setpoint is based on o power (the higher of NI power from the power range NI drawer, or AT power, based on PCS hot leg and cold leg temperatures) pressurizer pressure, PCS cold leg temperature, and Axial Shape Index. The TMM provide the complex signal processing necessary to calculate the TM/LP trip setpoint, TM/LP trip comparison signal, and Q Power.

Palisades Nuclear Plant B 3.3.1-5 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES BACKGROUND Measurement Channels (continued)

(continued)

Loss of Load Trip The Loss of Load trip uses a single pressure switch, 63lAST-2, in the turbine auto stop oil circuit to sense a turbine trip for input to all four RPS auxiliary trip units. The Loss of Load Trip is actuated by turbine auxiliary relays 305L and 305R. Relay 305L provides input to RPS channels A and C; 305R to channels B and D.

Relays 305L and 305R are energized on a turbine trip. Their inputs are the same as the inputs to the turbine solenoid trip valve, 20ET.

If a turbine trip is generated by loss of auto stop oil pressure, auto stop oil pressure switch 63/AST-2 will actuate relays 305L and 305R and generate a reactor trip. If a turbine trip is generated by an input to the solenoid trip valve, relays 305L and 305R, which are wired in parallel, will also be actuated and will generate a reactor trip.

Containment High Pressure Trip The Containment High Pressure Trip is actuated by four pressure switches, one for each RPS channel.

Zero Power Mode Bypass Automatic Removal The Zero Power Bypass allows manually bypassing (i.e., disabling) four reactor trip functions, Low PCS Flow, Low SG A Pressure, Low SG B Pressure, and TM/LP (low PCS pressure),

when reactor power (as indicated by the wide range nuclear instrument channels) is below 104%. This bypassing is necessary to allow RPS testing and control rod drive mechanism testing when the reactor is shutdown and plant conditions would cause a reactor trip to be present.

The Zero Power Mode Bypass removal interlock uses the wide range nuclear instruments (NIs) as measurement channels.

There are only two wide range NI channels. Separate bistables are provided to actuate the bypass removal for each RPS channel. Bistables in the NI-1/3 channel provide the bypass removal function for RPS channels A and C; bistables in the NI-2/4 channel for RPS channels B and D.

Palisades Nuclear Plant B 3.3.1-6 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES BACKGROUND Several measurement instrument channels provide more than one (continued) required function. Those sensors shared for RPS and ESF functions are identified in Table B 3.3.1-1. That table provides a listing of those shared channels and the Specifications which they affect.

RPS Trip Units Two types of RPS trip units are used in the RPS cabinets; bistable trip units and auxiliary trip units:

A bistable trip unit receives a measured process signal from its instrument channel and compares It to a setpoint; the trip unit actuates three relays, with contacts In the Matrix Logic channels, when the measured signal is less conservative than the setpoint.

They also provide local trip indication and remote annunciation.

An auxiliary trip unit receives a digital Input (contacts open or closed); the trip unit actuates three relays, with contacts in the MatrixLogic channels, when the digital input is received. They also provide local trip indication and remote annunciation.

Each RPS channel has four auxiliary trip units and seven bistable trip units.

The contacts from these trip unit relays are arranged into six coincidence matrices, comprising the Matrix Logic. If bistable trip units monitoring the same parameter in at least two channels trip, the Matrix Logic will generate a reactor trip (two-out-of-four logic).

Four of the RPS measurement channels provide contact outputs to the RPS, so the comparison of an analog Input to a trip setpoint is not necessary. In these cases, the bistable trip unit is replaced with an auxiliary trip unit. The auxiliary trip units provide contact multiplication so the single input contact opening can provide multiple contact outputs to the coincidence logic as well as trip indication and annunciation.

Palisades Nuclear Plant B 3.3.1-7 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES BACKGROUND RPS Trip Units (continued)

(continued)

Trips employing auxiliary trip units include the VHPT, which receives contact inputs from the Thermal Margin Monitors; the High Startup Rate trip which employs contact inputs from bistables mounted in the two wide range drawers; the Loss of Load Trip which receives contact inputs from one of two auxiliary relays which are operated by a single switch sensing turbine auto stop oil pressure; and the Containment High Pressure (CHP) trip, which employs containment pressure switch contacts.

There are four RPS trip units, designated as channels A through D, each channel having eleven trip units, one for each RPS Function. Trip unit output relays de-energize when a trip occurs.

All RPS Trip Functions, with the exception of the Loss of Load and CHP trips, generate a pretrip alarm as the trip setpoint is approached.

The Allowable Values are specified for each safety related RPS trip Function which is credited in the safety analysis. Nominal trip setpoints are specified in the plant procedures. The nominal setpoints are selected to ensure plant parameters do not exceed the Allowable Value if the instrument loop is performing as required. The methodology used to determine the nominal trip setpoints is also provided in plant documents. Operation with a trip setpoint less conservative than the nominal trip setpoint, but within its Allowable Value, is acceptable. Each Allowable Value specified is more conservative than the analytical limit determined in the safety analysis in order to account for uncertainties appropriate to the trip Function. These uncertainties are addressed as described in plant documents. A channel is inoperable if its actual setpoint is not within its Allowable Value.

Setpoints in accordance with the Allowable Value will ensure that SLs of Chapter 2.0 are not violated during AOOs and the consequences of DBAs will be acceptable, providing the plant is operated from within the LCOs at the onset of the AOO or DBA and the equipment functions as designed.

Note that in the accompanying LCO 3.3.1, the Allowable Values of Table 3.3.1-1 are the LSSS.

Palisades Nuclear Plant B 3.3.1-8 Revised 01122/2003

RPS Instrumentation B 3.3.1 BASES BACKGROUND (continued)

Reactor Protective System Bypasses Three different types of trip bypass are utilized in the RPS, Operating Bypass, Zero Power Mode Bypass, and Trip Channel Bypass. The Operating Bypass or Zero Power Mode Bypass prevent the actuation of a trip unit or auxiliary trip unit; the Trip Channel Bypass prevents the trip unit output from affecting the Logic Matrix. A channel which is bypassed, other than as allowed by the Table 3.3.1-1 footnotes, cannot perform its specified safety function and must be considered to be inoperable.

Operating Bypasses The Operating Bypasses are initiated and removed automatically during startup and shutdown as power level changes. An Operating Bypass prevents the associated RPS auxiliary trip unit from receiving a tdp signal from the associated'measurement channel. With the bypass In place, neither the pre-trip alarm nor the trip will actuate if the measured parameter exceeds the set point. An annunciator is provided for each Operating Bypass. The RPS trips with Operating Bypasses are:

a.

High Startup Rate Trip bypass. The High Startup Rate trip Is automatically bypassed when the associated wide range channel indicates below 1E-4% RTP, and when the associated power range excore channel indicates above 13% RTP. These bypasses are automatically removed between 1 E-4% RTP and 13% RTP.

b.

Loss of Load bypass. The Loss of Load trip Is automatically bypassed when the associated power range excore channel indicates below 17% RTP. The bypass is automatically removed when the channel indicates above the set point. The same power range excore channel bistable is used to bypass the High Startup Rate trip and the Loss of Load trip for that RPS channel..

Palisades Nuclear Plant Revised 01/22/2003 B 3.3.1-9

RPS Instrumentation B 3.3.1 BASES BACKGROUND Operating Bypasses (continued)

(continued)

Each wide range channel contains two bistables set at 1 E-4% RTP, one bistable unit for each associated RPS channel. Each of the two wide range channels affect the Operating Bypasses for two RPS channels; wide range channel NI-113 for RPS channels A and C, wide range channel NI-2/4 for RPS channels B and D. Each of the four power range excore channel affects the Operating Bypasses for the associated RPS channel. The power range excore channel bistables associated with the Operating Bypasses are set at a nominal 15%, and are required to actuate between 13% RTP and 17% RTP.

Zero Power Mode (ZPM) Bypass The ZPM Bypass is used when the plant is shut down and it is desired to raise the control rods for control rod drop testing with PCS flow, pressure or temperature too low for the RPS trips to be reset. ZPM bypasses may be manually initiated and removed when wide range power is below 1 E-4% RTP, and are automatically removed if the associated wide range NI indicated power exceeds 1 E-4% RTP. A ZPM bypass prevents the RPS trip unit from actuating if the measured parameter exceeds the set point. Operation of the pretrip alarm is unaffected by the zero power mode bypass. An annunciator indicates the presence of any ZPM bypass. The RPS trips with ZPM bypasses are:

a.

Low Primary Coolant System Flow.

b.

Low Steam Generator Pressure.

c.

Thermal Margin/Low Pressure.

The wide range NI channels provide contact closure permissive signals when indicated power is below I E-4% RTP. The ZPM bypasses may then be manually initiated or removed by actuation of key-lock switches.

One key-lock switch located on each RPS cabinet controls the ZPM Bypass for the associated RPS trip channels. The bypass is automatically removed if the associated wide range NI indicated power exceeds I E-4% RTP. The same wide range NI channel bistables that provide the ZPM Bypass permissive and removal signals also provide the high startup rate trip Operating Bypass actuation and removal.

Palisades Nuclear Plant B 3.3.1 -10 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES BACKGROUND (continued)

Trip Channel Bypass A Trip Channel Bypass is used when it is desired to physically remove an individual trip unit from the system, or when calibration or servicing of a trip channel could cause an inadvertent'trip. A trip Channel Bypass may be manually initiated or removed at any time by actuation of a key lock switch. A Trip Channel Bypass prevents the trip unit output from affecting the RPS logic matrix. A light above the bypass switch indicates that the trip channel has been bypassed. Each RPS trip Unit has an associated trip channel bypass:

The key-lock trip channel bypass switch Is located above each trip unit.

The key cannot be removed when in the bypass position. Only one key for each trip parameter Is provided, therefore the operator can bypass only one channel of a given parameter at a time. During the bypass condition, system logic changes from two-out-of-four to two-out-of-three channels required for trip.

APPLICABLE SAFETY ANALYSES Each of the analyzed accidents and transients can be detected by one or more RPS Functions. The accident analysis contained in Reference 4 takes credit for most RPS trip Functions. The High Startup Rate and Loss of Load Functions, which are not specifically credited in the accident analysis are part of the NRC approved licensing basis for the plant. The High Startup Rate and Loss of Load trips are purely equipment protective, and their use minimizes the potential for equipment damage.

The-specific safety analyses applicable to each protective Function are identified below.

1.

Variable Hi-gh Power Trip (VHPT)

The VHPT provides reactor core protection against positive reactivity excursions.

The safety analysis assumes that this trip is OPERABLE to terminate excessive positive reactivity insertions during power operation and while shut down.

Palisades Nuclear Plant B 3.3.1 -11 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES APPLICABLE SAFETY ANALYSIS (continued)

2.

High Startup Rate Trip There are no safety analyses which take credit for functioning of the High Startup Rate Trip. The High Startup Rate trip is used to trip the reactor when excore wide range power indicates an excessive rate of change. The High Startup Rate trip minimizes transients for events such as a continuous control rod withdrawal or a boron dilution event from low power levels. The trip may be operationally bypassed when THERMAL POWER is

< 1 E-4% RTP, when poor counting statistics may lead to erroneous indication. It may also be operationally bypassed at

> 13% RTP, where moderator temperature coefficient and fuel temperature coefficient make high rate of change of power unlikely.

There are only two wide range drawers, with each supplying contact input to auxiliary trip units in two RPS channels.

3.

Low Primary Coolant System Flow Trip The Low PCS Flow trip provides DNB protection during events which suddenly reduce the PCS flow rate during power operation, such as loss of power to, or seizure of, a primary coolant pump.

Flow in each of the four PCS loops is determined from pressure drop from inlet to outlet of the SGs. The total PCS flow is determined, for the RPS flow channels, by summing the loop pressure drops across the SGs and correlating this pressure sum with the sum of SG differential pressures which exist at 100% flow (four pump operation at full power Tave). Full PCS flow is that flow which exists at RTP, at full power Tv,, with four pumps operating.

4, 5. Low Steam Generator Level Trip The Low Steam Generator Level trips are provided to trip the reactor in the event of excessive steam demand (to prevent overcooling the PCS) and loss of feedwater events (to prevent overpressurization of the PCS).

The Allowable Value assures that there will be sufficient water inventory in the SG at the time of trip to allow a safe and orderly plant shutdown and to prevent SG dryout assuming minimum AFW capacity.

Palisades Nuclear Plant B 3.3.1-12 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES APPLICABLE 4, 5. Low Steam Generator Level Trip (continued)

SAFETY ANALYSIS (continued)

Each SG level is sensed by measuring the differential pressure in the upper portion of the downcomer annulus in the SG. These trips share four level sensing channels on each SG with the AFW actuation signal.

6, 7. Low Steam Generator Pressure Trid The Low Steam Generator Pressure trip provides protection against an excessive rate of heat extraction from the steam generators, which would result in a rapid uncontrolled cooldown of the PCS. This trip provides a mitigation function in the event of an MSLB.

The Low SG Pressure channels are shared with the Low SG Pressure signals which isolate the steam and feedwater lines.

8.

High Pressurizer Pressure Trip The High Pressurizer Pressure trip, In conjunction with pressurizer safety valves and Main Steam Safety Valves (MSSVs), provides protection against overpressure conditions in the PCS when at operating temperature. The safety analyses assume the High Pressurizer Pressure trip is OPERABLE during accidents and transients which suddenly reduce PCS cooling (e.g., Loss of Load, Main Steam Isolation Valve (MSIV) closure, etc.) or which suddenly increase reactor power (e.g., rod ejection accident).

The High Pressurizer Pressure trip shares four safety grade instrument channels with the TM/LP trip, Anticipated Transient Without Scram (ATWS) and PORV circuits, and the Pressurizer Low Pressure Safety Injection Signal.

Palisades Nuclear Plant B 3.3.1-13 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES APPLICABLE

9.

Thermal Mar-gin/Low Pressure (TM/LP) Trip SAFETY ANALYSIS (continued)

The TM/LP trip is provided to prevent reactor operation when the DNBR is insufficient. The TM/LP trip protects against slow reactivity or temperature increases, and against pressure decreases.

The trip is initiated whenever the PCS pressure signal drops below a minimum value (Pmrn) or a computed value (Par) as described below, whichever is higher.

The TM/LP trip uses Q Power, ASI, pressurizer pressure, and cold leg temperature (TJ) as inputs.

Q Power is the higher of core THERMAL POWER (AT Power) or nuclear power. The AT power uses hot leg and cold leg RTDs as inputs. Nuclear power uses the power range excore channels as inputs. Both the AT and excore power signals have provisions for calibration by calorimetric calculations.

The ASI is calculated from the upper and lower power range excore detector signals, as explained in Section 1.1, "Definitions.*

The signal is corrected for the difference between the flux at the core periphery and the flux at the detectors.

The T" value is the higher of the two cold leg signals.

The Low Pressurizer Pressure trip limit (Pv=)is calculated using the equations given in Table 3.3.1-2.

The calculated limit (Pa,,) is then compared to a fixed Low Pressurizer Pressure trip limit (P,*). The auctioneered highest of these signals becomes the trip limit (Pldp). Php is compared to the measured PCS pressure and a trip signal is generated when the measured pressure for that channel is less than or equal to Ptdp. A pre-trip alarm is also generated when P is less than or equal to the pre-trip setting, PuV + AP.

The TM/LP trip setpoint is a complex function of these inputs and represents a minimum acceptable PCS pressure for the existing temperature and power conditions. It is compared to actual PCS pressure in the TM/LP trip unit.

Palisades Nuclear Plant B 3.3.1-14 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES APPLICABLE

10.

Loss of Load Trip SAFETY ANALYSIS (continued)

There are no safety analyses which take credit for functioning of the Loss of Load Trip.

The Loss of Load trip is provided to prevent lifting the pressurizer and main steam safety valves in the event of a turbine generator trip while at power. The trip is equipment protective. The safety analyses do not assume that this trip functions during any accident or transient. The Loss of Load trip uses a single pressure switch in the turbine auto stop oil circuit to sense a turbine trip for input to all four RPS auxiliary trip units.

11.

Containment High Pressure Trip The Containment High Pressure trip provides a reactor trip in the event of a Loss of Coolant Accident (LOCA) or Main Steam Line Break (MSLB). The Containment High Pressure trip shares sensors with the Containment High Pressure sensing logic for Safety Injection, Containment Isolation, and Containment Spray.

Each of these sensors has a single bellows which actuates two microswitches. One microswitch on each of four sensors provides an input to the RPS.

12. Zero Power Mode Bypass Removal The only RPS bypass considered In the safety analyses is the Zero Power Mode (ZPM) Bypass. The ZPM Bypass is used when the plant is shut down and it isdesired to raise the control rods for control rod drop testing with PCS flow or temperature too low for the RPS Low PCS Flow, Low SG Pressure, or Thermal Margin/Low Pressure trips to be reset. ZPM bypasses are automatically removed if the wide range NI Indicated power exceeds 1E-4% RTP.

Palisades Nuclear Plant Revised 01/22/2003 B 3.3.1-15

RPS Instrumentation B 3.3.1 BASES APPLICABLE SAFETY ANALYSIS (continued)

LC6

12. Zero Power Mode Bypass Removal (continued)

The safety analyses take credit for automatic removal of the ZPM Bypass if reactor criticality due to a Continuous Control Rod Bank Withdrawal should occur with the affected trips bypassed and PCS flow, pressure, or temperature below the values at which the RPS could be reset. The ZPM Bypass would effectively be removed when the first wide range NI channel indication reached 1 E-4% RTP. With the ZPM Bypass for two RPS channels removed, the RPS would trip on one of the un-bypassed trips.

This would prevent the reactor reaching an excessive power level.

If a reactor criticality due to a Continuous Control Rod Bank Withdrawal should occur when PCS flow, steam generator pressure, and PCS pressure (TM/LP) were above their trip setpoints, a trip would terminate the event when power increased to the minimum setting (nominally 30%) of the Variable High Power Trip. In this case, the monitored parameters are at or near their normal operational values, and a trip initiated at 30% RTP provides adequate protection.

The RPS design also includes automatic removal of the Operating Bypasses for the High Startup Rate and Loss of Load trips. The safety analyses do not assume functioning of either these trips or the automatic removal of their bypasses.

The RPS instrumentation satisfies Criterion 3 of 10 CFR 50.36(c)(2).

The LCO requires all instrumentation performing an RPS Function to be OPERABLE. Failure of the trip unit (including its output relays), any required portion of the associated instrument channel, or both, renders the affected channel(s) inoperable and reduces the reliability of the affected Functions. Failure of an automatic ZPM bypass removal channel may also impact the associated instrument channel(s) and reduce the reliability of the affected Functions.

Palisades Nuclear Plant B 3.3.1-16 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES LCO (continued)

Actions allow Trip Channel Bypass of individual channels, but the bypassed channel must be considered to be inoperable. The bypass key used to bypass a single channel cannot be simultaneously used to bypass that same parameter In other channels. This interlock prevents operation with more than one channel of the same Function trip channel bypassed. The plant is normally restricted to 7 days in a trip channel bypass, or otherwise Inoperable condition before either restoring the Function to four channel operation (two-out-of-four logic) or placing the channel in trip (one-out-of-three logic).

The Allowable Values are specified for each safety related RPS trip Function which Is credited in the safety analysis. Nominal trip setpoints are specified in the plant procedures. The nominal setpoints are selected to ensure plant parameters do not exceed the Allowable Value if the instrument loop is performing as required. Operation with a trip setpoint less conservative than the nominal trip setpoint, but within its Allowable Value, is acceptable. Each Allowable Value specified is more conservative than the analytical limit determined in the safety analysis in order to account for uncertainties appropriate to the trip Function.

These uncertainties are addressed as described in plant documents.

Neither Allowable Values nor setpoints are specified for the non-safety related RPS Trip Functions, since no safety analysis assumptions would be violated if they are not set at a particular value.

The following Bases for each trip Function identify the above RPS trip Function criteria items that are applicable to establish the trip Function OPERABILITY.

1.

Variable High Power Trip (VHPT)

This LCO requires all four channels of the VHPT Function to be OPERABLE.

The Allowable Value is high enough to provide an operating envelope that prevents unnecessary VHPT trips during normal plant operations. The Allowable Value is low enough for the system to function adequately during reactivity addition events.

Palisades Nuclear Plant B 3.3.1-17 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES LCO

1.

Variable High Power Trip (VHPT) (continued)

(continued)

The VHPT is designed to limit maximum reactor power to its maximum design and to terminate power excursions initiating at lower powers without power reaching this full power limit. During plant startup, the VHPT trip setpoint is initially at its minimum value, < 30%. Below 30% RTP, the VHPT setpoint is not required to "track" with Q Power, i.e., be adjusted to within 15% RTP. It remains fixed until manually reset, at which point it increases to

< 15% above existing Q Power.

The maximum allowable setting of the VHPT is 111% RTP.

Adding to this the possible variation in trip setpoint due to calibration and instrument error, the maximum actual steady state power at which a trip would be actuated is 115%, which is the value assumed in the safety analysis.

2.

High Startup Rate Trip This LCO requires four channels of High Startup Rate Trip Function to be OPERABLE in MODES 1 and 2.

The High Startup Rate trip serves as a backup to the administratively enforced startup rate limit. The Function is not credited in the accident analyses; therefore, no Allowable Value for the trip or operating bypass Functions is derived from analytical limits and none is specified.

The four channels of the High Startup Rate trip are derived from two wide range NI signal processing drawers. Thus, a failure in one wide range channel could render two RPS channels inoperable. It is acceptable to continue operation in this condition because the High Startup Rate trip is not credited in any safety analyses.

The requirement for this trip Function is modified by a footnote, which allows the High Startup Rate trip to be bypassed when the wide range NI indicates below 1OE-4% or when THERMAL POWER is above 13% RTP. If a High Startup Rate trip is bypassed when power is between these limits, it must be considered to be inoperable.

Palisades Nuclear Plant B 3.3.1-18 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES LCO

3.

Low Primary Coolant System Flow Trip (continued)

This LCO requires four channels of Low PCS Flow Trip Function to be OPERABLE.

This trip Is set high enough to maintain fuel integrity during a loss of flow condition. The setting is lowenough to allow for normal operating fluctuations from offsite power.

The Low PCS Flow trip setpoint of 95% of full PCS flow insures that the reactor cannot operate when the flow rate Is less than 93% of the nominal value considering instrument errors. Full PCS flow Is that flow which exists at RTP, at full power Tave, with four pumps operating.

The requirement for this trip Function is modified by a footnote, which allows use of the ZPM bypass when wide range power is below 1 E-4% RTP. That bypass is automatically removed when the associated wide range channel indicates I E-4% RTP. If a trip channel Is bypassed when power is above 1 E-4% RTP, it must be considered to be Inoperable.

4, 5. Low Steam Generator Level Trip This LCO requires four channels of Low Steam Generator Level Trip Function per steam generator to be OPERABLE.

The 25.9% Allowable Value assures that there Is an adequate water inventory in the steam generators when the reactor is critical and is based upon narrow range Instrumentation. The 25.9%

indicated level corresponds to the location of the feed ring.

6,7. Low Steam Generator Pressure Trip This LCO requires four channels of Low Steam Generator Pressure Trip Function per steam generator to be OPERABLE.

The Allowable Value of 500 psia is sufficiently below the full load operating value for steam pressure so as not to interfere with normal plant operation, but still high enough to provide the required protection in the event of excessive steam demand.

Since excessive steam demand causes the PCS to cool down, resulting In positive reactivity addition to the core, a reactor trip Is required to offset that effect.

Palisades Nuclear Plant B 3.3.1-19 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES LCO (continued)

8.

High Pressurizer Pressure Trip This LCO requires four channels of High Pressurizer Pressure Trip Function to be OPERABLE.

The Allowable Value is set high enough to allow for pressure increases in the PCS during normal operation (i.e., plant transients) not indicative of an abnormal condition. The setting is below the lift setpoint of the pressurizer safety valves and low enough to initiate a reactor trip when an abnormal condition is indicated.

9.

Thermal Margin/Low Pressure (TM/LP) Trip This LCO requires four channels of TM/LP Trip Function to be OPERABLE.

The TM/LP trip setpoints are derived from the core thermal limits through application of appropriate allowances for measurement uncertainties and processing errors. The allowances specifically account for instrument drift in both power and inlet temperatures, calorimetric power measurement, inlet temperature measurement, and primary system pressure measurement.

Other uncertainties including allowances for assembly power tilt, fuel pellet manufacturing tolerances, core flow measurement uncertainty and core bypass flow, inlet temperature measurement time delays, and ASI measurement, are included in the development of the TM/LP trip setpoint used in the accident analysis.

The requirement for this trip Function is modified by a footnote, which allows use of the ZPM bypass when wide range power is below 1 E-4% RTP. That bypass is automatically removed when the associated wide range channel indicates 1 E-4% RTP. If a trip channel is bypassed when power is above 1 E-4% RTP, it must be considered to be inoperable.

Palisades Nuclear Plant B 3.3.1-20 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES LCO

10.

Loss of Load Trip (continued)

The LCO requires four Loss of Load Trip Function channels to be OPERABLE in MODE I with THERMAL POWER'- 17% RTP.

The Loss of Load trip may be bypassed or be inoperable with THERMAL POWER < 17% RTP, since It is no longer needed to prevent lifting of the pressurizer safety valves or steam generator safety valves in the event of a Loss of Load. Loss of Load Trip unit must be considered inoperable if it Is bypassed when THERMAL POWER is above 17% RTP.

This LCO requires four RPS Loss of Load auxiliary trip units, relays 305L and 305R, and pressure switch 63lAST-2 to be OPERABLE. With those components OPERABLE, a turbine trip will generate a reactor trip. The LCO does not require the various turbine trips, themselves, to be OPERABLE.

The Nuclear Steam Supply System and Steam Dump System are capable of accommodating the Loss of Load without requiring the use of the above equipment.

The Loss of Load Trip Function is not credited in the accident analysis; therefore, an Allowable Value for the trip cannot be derived from analytical limits, and is not specified.

11.

Containment Hi-gh Pressure Trip This LCO requires four channels of Containment High Pressure Trip Function to be OPERABLE.

The Allowable Value is high enough to allow for small pressure increases in containment expected during normal operation (i.e., plant heatup) that are not Indicative of an abnormal condition.

The setting is low enough to initiate a reactor trip to prevent containment pressure from exceeding design pressure following a DBA and ensures the reactor Is shutdown before initiation of safety Injection and containment spray.

Palisades Nuclear Plant B 3.3.1-21 Revised 01/r22/2003

RPS Instrumentation B 3.3.1 BASES LCO (continued)

12.

ZPM Bypass The LCO requires that four channels of automatic Zero Power Mode (ZPM) Bypass removal instrumentation be OPERABLE.

Each channel of automatic ZPM Bypass removal includes a shared wide range NI channel, an actuating bistable in the wide range drawer, and a relay in the associated RPS cabinet. Wide Range NI channel 113 is shared between ZPM Bypass removal channels A and C; Wide Range NI channel 2/4, between ZPM Bypass removal channels B and D. An operable bypass removal channel must be capable of automatically removing the capability to bypass the affected RPS trip channels with the ZPM Bypass key switch at the proper setpoint.

APPLICABILITY This LCO requires all safety related trip functions to be OPERABLE in accordance with Table 3.3.1-1.

Those RPS trip Functions which are assumed in the safety analyses (all except High Startup Rate and Loss of Load), are required to be operable in MODES 1 and 2, and in MODES 3,4, and 5 with more than one full-length control rod capable of being withdrawn and PCS boron concentration less than REFUELING BORON CONCENTRATION.

These trip Functions are not required while in MODES 3, 4, or 5, if PCS boron concentration is at REFUELING BORON CONCENTRATION, or when no more than one full-length control rod is capable of being withdrawn, because the RPS Function is already fulfilled. REFUELING BORON CONCENTRATION provides sufficient negative reactivity to assure the reactor remains subcritical regardless of control rod position, and the safety analyses assume that the highest worth withdrawn full-length control rod will fail to insert on a trip. Therefore, under these conditions, the safety analyses assumptions will be met without the RPS trip Function.

The High Startup Rate Trip Function is required to be OPERABLE in MODES I and 2, but may be bypassed when the associated wide range NI channel indicates below I E-4% power, when poor counting statistics may lead to erroneous indication. In MODES 3, 4, 5, and 6, the High Startup Rate trip is not required to be OPERABLE. Wide range channels are required to be OPERABLE in MODES 3, 4, and 5, by LCO 3.3.9, "Neutron Flux Monitoring Channels," and in MODE 6, by LCO 3.9.2, 'Nuclear Instrumentation.

Palisades Nuclear Plant B 3.3.1-22 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES APPLICABILITY (continued)

The High Startup Rate Trip Function is required to be OPERABLE in MODES 1 and 2, but may be bypassed when the associated wide range NI channel Indicates below I E-4% power, when poor counting statistics may lead to erroneous indication. In MODES 3, 4, 5, and 6, the High Startup Rate trip is not required to be OPERABLE. Wide range channels are required to be OPERABLE in MODES 3,4, and 5, by LCO 3.3.9, "Neutron Flux Monitoring Channels," and in MODE 6, by LCO 3.9.2, "Nuclear Instrumentation."

The Loss of Load trip is required to be OPERABLE with THERMAL POWER at or above 17% RTP. Below 17% RTP, the ADVs are capable of relieving the pressure due to a Loss of Load event without challenging other overpressure protection.

The trips are designed to take the reactor subcrtical, maintaining the SLs during AOQs and assisting the ESF in providing acceptable consequences during accidents.

ACTIONS The most common causes of channel inoperability are outright failure of loop components or drift of those loop components which is sufficient to exceed the tolerance provided in the plant setpolnt analysis. Loop component failures are typically Identified by the actuation of alarms due to the channel failing to the 'safe' condition, during CHANNEL CHECKS (when the Instrument is compared to the redundant channels), or during the CHANNEL FUNCTIONAL TEST (when an automatic component might not respond properly). Typically, the drift of the loop components is found to be small and results in a delay of actuation rather than a total loss of function. Excessive loop component drift would, most likely, be identified during a CHANNEL CHECK (when the instrument is compared to the redundant channels) or during a CHANNEL CALIBRATION (when instrument loop components are checked against reference standards).

In the event a channel's trip setpoint is found nonconservative with respect to the Allowable Value, or the transmitter, instrument loop, signal processing electronics, or RPS bistable trip unit Is found Inoperable, all affected Functions provided by that channel must be declared inoperable, and the plant must enter the Condition for the particular protection Functions affected.

Palisades Nuclear Plant Revised 01122/2003 B 3.3.1-23

RPS Instrumentation B 3.3.1 BASES ACTIONS (continued)

When the number of inoperable channels in a trip Function exceeds that specified in any related Condition associated with the same trip Function, then the plant is outside the safety analysis. Therefore, LCO 3.0.3 is immediately entered if applicable in the current MODE of operation.

A Note has been added to the ACTIONS to clarify the application of the Completion Time rules. The Conditions of this Specification may be entered independently for each Function. The Completion Times of each inoperable Function will be tracked separately for each Function, starting from the time the Condition was entered.

A.1 Condition A applies to the failure of a single channel in any required RPS Function, except High Startup Rate, Loss of Load, or ZPM Bypass Removal. (Condition A is modified by a Note stating that this Condition does not apply to the High Startup Rate, Loss of Load, or ZPM Bypass Removal Functions. The failure of one channel of those Functions is addressed by Conditions B, C, or D.)

If one RPS bistable trip unit or associated instrument channel is inoperable, operation is allowed to continue. Since the trip unit and associated instrument channel combine to perform the trip function, this Condition is also appropriate if both the trip unit and the associated instrument channel are inoperable. Though not required, the inoperable channel may be bypassed. The provision of four trip channels allows one channel to be bypassed (removed from service) during operations, placing the RPS in two-out-of-three coincidence logic. The failed channel must be restored to OPERABLE status or placed in trip within 7 days.

Required Action A.1 places the Function in a one-out-of-three configuration. In this configuration, common cause failure of dependent channels cannot prevent trip.

The Completion Time of 7 days is based on operating experience, which has demonstrated that a random failure of a second channel occurring during the 7 day period is a low probability event.

Palisades Nuclear Plant B 3.3.1-24 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES ACTIONS A.1 (continued)

(continued)

The Completion Time of 7 days is based on operating experience, which has'demonstrated that a random failure of a second channel occurring during the 7 day period Is a low probability event.

B..1 Condition B applies to the failure of a single High Startup Rate trip unit or associated instrument channel.

If one trip unit or associated instrument channel fails, it must be restored to OPERABLE status prior to entering MODE 2 from MODE 3. A shutdown provides the appropriate opportunity to repair the trip function and conduct the necessary testing. The Completion Time is based on the fact that the safety analyses take no credit for the functioning of this trip.

C.1 Condition C applies to the failure of a single Loss of Load or associated instrument channel.

If one trip unit or associated Instrument channel fails, it must be restored to OPERABLE status prior to THERMAL POWER > 17% RTP following a shutdown. If the plant is shutdown at the time the channel becomes inoperable, then the failed channel must be restored to OPERABLE status prior to THERMAL POWER Z 17% RTP. For this Completion Time, "following a shutdown' means this Required Action does not have to be completed until prior to THERMAL POWER ý: 17% RTP for the first time after the plant has been in MODE 3 following entry into the Condition. The Completion Time trip assures that the plant will not be restarted with an inoperable Loss of Load trip channel.

Palisades Nuclear Plant Revised 01/22/2003 B 3.3.1-25

RPS Instrumentation B 3.3.1 BASES ACTIONS D.1 and D.2 (continued)

Condition D applies when one or more automatic ZPM Bypass removal channels are inoperable. If the ZPM Bypass removal channel cannot be restored to OPERABLE status, the affected ZPM Bypasses must be immediately removed, or the bypassed RPS trip Function channels must be immediately declared to be inoperable. Unless additional circuit failures exist, the ZPM Bypass may be removed by placing the associated "Zero Power Mode Bypass" key operated switch in the normal position.

A trip channel which is actually bypassed, other than as allowed by the Table 3.3.1-1 footnotes, cannot perform its specified safety function and must immediately be declared to be inoperable.

E.1 and E.2 Condition E applies to the failure of two channels in any RPS Function, except ZPM Bypass Removal Function. (The failure of ZPM Bypass Removal Functions is addressed by Condition D.).

Condition E is modified by a Note stating that this Condition does not apply to the ZPM Bypass Removal Function.

The Required Actions are modified by a Note stating that LCO 3.0.4 is not applicable. The Note was added to allow the changing of MODES even though two channels are inoperable, with one channel tripped.

MODE changes in this configuration are allowed because two trip channels for the affected function remain OPERABLE. A trip occurring in either or both of those channels would cause a reactor trip.

In this configuration, the protection system is in a one-out-of-two logic, and the probability of a common cause failure affecting both of the OPERABLE channels during the 7 days permitted is remote.

Required Action E.1 provides for placing one inoperable channel in trip within the Completion Time of 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. Though not required, the other inoperable channel may be (trip channel) bypassed.

Palisades Nuclear Plant B 3.3.1-26 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES ACTIONS E.1 and E.2 (continued)

(continued)

This Completion Time is sufficient to allow the operator to take all appropriate actions for the failed channels while ensuring that the risk Involved in operating with the failed channels is acceptable. With one channel of protective instrumentation bypassed or Inoperable in an untripped condition, the RPS is In a two-out-of-three logic for that function; but with another channel failed, the RPS may be operating in a two-out-of-two logic. This is outside the assumptions made in the analyses and should be corrected. To correct the problem, one of the Inoperable channels is placed in trip. This places the RPS In a one-out-of-two for that function logic. If any of the other unbypassed channels for that function receives a trip signal, the reactor will trip.

Action E.2 is modified by a Note stating that this Action does not apply to (is not required for) the High Startup Rate and Loss of Load Functions.

One channel is required to be restored to OPERABLE status within 7 days for reasons similar to those stated under Condition A. After one channel Is restored to OPERABLE status, the provisions of Condition A still apply to theremaining inoperable channel. Therefore, the channel that Is still Inoperable after completion of Required Action E.2 must be placed In trip If more than 7 days have elapsed since the initial channel failure.

EJ.1 The power range excore channels are used to generate the internal ASI signal used as an input to the TM/LP trip. They also provide input to the Thermal Margin Monitors for determination of the Q Power input for the TM/LP trip and the VHPT. If two power range excore channels cannot be restored to OPERABLE status, power is restricted or reduced during subsequent operations because of Increased uncertainty associated with inoperable power range excore channels which provide input to those trips.

The Completion Time of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> is adequate to reduce power in an orderly manner without challenging plant systems.

Palisades Nuclear Plant B 3.3.1-27 Revised 01/2242003

RPS Instrumentation B 3.3.1 BASES ACTIONS G.1, G.2.1, and G.2.2 (continued)

Condition G is entered when the Required Action and associated Completion Time of Condition A, B, C, D, E, or F are not met, or if the control room ambient air temperature exceeds 900F.

If the control room ambient air temperature exceeds 900F, all Thermal Margin Monitor channels are rendered inoperable because their operating temperature limit is exceeded. In this condition, or if the Required Actions and associated Completion Times are not met, the reactor must be placed in a condition in which the LCO does not apply.

To accomplish this, the plant must be placed in MODE 3, with no more than one full-length control rod capable of being withdrawn or with the PCS boron concentration at REFUELING BORON CONCENTRATION in 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

The Completion Time is reasonable, based on operating experience, for placing the plant in MODE 3 from full power conditions in an orderly manner and without challenging plant systems. The Completion Time is also reasonable to ensure that no more than one full-length control rod is capable of being withdrawn or that the PCS boron concentration is at REFUELING BORON CONCENTRATION.

SURVEILLANCE The SRs for any particular RPS Function are found in the SR column of REQUIREMENTS Table 3.3.1-1 for that Function. Most Functions are subject to CHANNEL CHECK, CHANNEL FUNCTIONAL TEST, and CHANNEL CALIBRATION.

SR 3.3.1.1 Performance of the CHANNEL CHECK once every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ensures that gross failure of instrumentation has not occurred. A CHANNEL CHECK is normally a comparison of the parameter indicated on one channel to a similar parameter on other channels. It is based on the assumption that instrument channels monitoring the same parameter should read approximately the same value. Significant deviations between the two instrument channels could be an indication of excessive instrument drift in one of the channels or of something even more serious. Under most conditions, a CHANNEL CHECK will detect gross channel failure; thus, it is key to verifying that the instrumentation continues to operate properly between each CHANNEL CALIBRATION.

Palisades Nuclear Plant B 3.3.1-28 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES SURVEILLANCE SR 3.3.1.1 (continued)

REQUIREMENTS (continued)

Agreement criteria are determined by the plant staff based on a combination of the channel instrument uncertainties, including indication and readability. If a channel is outside the criteria, it may be an indication that the transmitter or the signal processing equipment has drifted outside Its limits.

The Containment High Pressure and Loss of Load channels are pressure switch actuated. As such, they have no associated control room Indicator and do not require a CHANNEL CHECK.

The Frequency, about once every shift, Is based on operating experience that demonstrates the rarity of channel failure. Since the probability of two random failures in redundant channels in any 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> period is extremely low, the CHANNEL CHECK minimizes the chance of loss of protective function due to failure of redundant channels. The CHANNEL CHECK supplements less formal, but more frequent, checks of channel OPERABILITY during normal operational use of the displays associated with the LCO required channels.

SR 3.3.1.2 This SR verifies that the control room ambient air temperature Is within the environmental qualification temperature limits for the most restrictive RPS components, which are the Thermal Margin Monitors. These monitors provide Input to both the VHPT Function and the TM/LP Trip Function. The 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Frequency is reasonable based on engineering judgement and plant operating experience.

SR 3.3.1.3 A daily calibration (heat balance) Is performed when THERMAL POWER is 2: 15%. The daily calibration consists of adjusting the "nuclear power calibrate" potentiometers to agree with the calorimetric calculation if the absolute difference is k 1.5%. Nuclear power is adjusted via a potentiometer, or THERMAL POWER is adjusted via a Thermal Margin Monitor bias number, as necessary, in accordance with the daily calibration (heat balance) procedure. Performance of the daily calibration ensures that the two inputs to the Q power measurement are indicating accurately with respect to the much more accurate secondary calorimetric calculation.

Palisades Nuclear Plant Revised 01/22/2003 B 3.3.1-29

RPS Instrumentation B 3.3.1 BASES SURVEILLANCE REQUIREMENTS (continued)

SR 3.3.1.3 (continued)

The Frequency of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> is based on plant operating experience and takes into account indications and alarms located in the control room to detect deviations in channel outputs.

The Frequency is modified by a Note indicating this Surveillance must be performed within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after THERMAL POWER is > 15% RTP.

The secondary calorimetric is inaccurate at lower power levels. The 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> allows time requirements for plant stabilization, data taking, and instrument calibration.

SR 3.3.1.4 It is necessary to calibrate the power range excore channel upper and lower subchannel amplifiers such that the measured ASI reflects the true core power distribution as determined by the incore detectors. ASI is utilized as an input to the TM/LP trip function where it is used to ensure that the measured axial power profiles are bounded by the axial power profiles used in the development of the Tinet limitation of LCO 3.4.1. An adjustment of the excore channel is necessary only if reactor power is greater than 25% RTP and individual excore channel ASI differs from AXIAL OFFSET, as measured by the incores, outside the bounds of the following table:

Group 4 Rods k 128" withdrawn

-0.020 < (AO-ASI) < 0.020

-0.033 < (AO-ASI) < 0.020

-0.046 < (AO-ASI)

  • 0.020

-0.060:< (AO-ASI) s 0.020

-0.133 < (AO-ASI) < 0.080

-0.146 < (AO-ASI) < 0.080

-0.153 5 (AO-ASI) < 0.080

-0.153 < (AO-ASI) < 0.080

-0.153 < (AO-ASI) : 0.080

-0.153 < (AO-ASI) < 0.080

-0.153 < (AO-ASI) : 0.080

-0.153 < (AO-ASI) < 0.080

-0.153 5 (AO-ASI)

  • 0.080

-0.153 < (AO-ASI)

  • 0.080

-0.153 < (AO-ASI) < 0.080 Below 25% RTP any AO/ASI Group 4 Rods <128" withdrawn

-0.040 < (AO-ASI) <0.040

-0.053:5 (AO-ASI) < 0.040

-0.066 s (AO-ASI) <0.040

-0.080 < (AO-ASI) < 0.040

-0.153:5 (AO-ASI) 5 0.100

-0.153:5 (AO-ASI) <0.100

-0.153 5 (AO-ASI) 5 0.100

-0.153:5 (AO-ASI) S 0.100

-0.153 S (AO-ASI) 5 0.100

-0.153:5 (AO-ASI) S 0.100

-0.153:5 (AO-ASI) 5 0.100

-0.153:5 (AO-ASI) <0.100

-0.153:5 (AO-ASI) <0.100

-0.153:5 (AO-ASI) 5 0.100

-0.153:5 (AO-ASI) 5 0.100 difference is acceptable Table values determined with a conservative K.~ gamma constant of -9420.

Palisades Nuclear Plant

'-I Allowed Reactor Power

. 100%

< 95

< 90

< 85

< 80

< 75

< 70

< 65

< 60

< 55

< 50

< 45

< 40

< 35

< 30

< 25 B 3.3.1-30 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES SURVEILLANCE REQUIREMENTS (continued)

SR 3.3.1.4 (continued)

Below 25% RTP any difference between ASI and AXIAL OFFSET is acceptable. A Note indicates the Surveillance is not required to have been performed until 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after THERMAL POWER is k 25% RTP.

Uncertainties in the excore and incore measurement process make it impractical to calibrate when THERMAL POWER Is < 25% RTP. The 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> allows time for plant stabilization, data taking, and instrument calibration.

The 31 day Frequency is adequate, based on operating experience of the excore linear amplifiers and the slow bumup of the detectors. The excore readings are a strong function of the power produced in the peripheral fuel bundles and do not represent an integrated reading across the core. Slow changes in neutron flux during the fuel cycle can also be detected at this Frequency.

SR 3.3.1.5 A CHANNEL FUNCTIONAL TEST is performed on each RPS Instrument channel, except Loss of Load and High Startup Rate, every 92 days to ensure the entire channel will perform its Intended function when needed. For the TM/LP Function, the constants associated with the Thermal Margin Monitors must be verified to be within tolerances.

A successful test of the required contact(s) of a channel relay may be performed by the verification of the change of state of a single contact of the relay. This clarifies what is an acceptable CHANNEL FUNCTIONAL TEST of a relay. This Is acceptable because all of the other required contacts of the relay are verified by other Technical Specifications and non-Technical Specifications tests at least once per refueling interval with applicable extensions.

Any setpoint adjustment must be consistent with the assumptions of the current setpoint analysis.

The Frequency of 92 days Is based on the reliability analysis presented in topical report CEN-327, "RPS/ESFAS Extended Test Interval Evaluation" (Ref. 5).

Palisades Nuclear Plant B 3.3.1-31 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES SURVEILLANCE SR 3.3.1.6 REQUIREMENTS (continued)

A calibration check of the power range excore channels using the internal test circuitry is required every 92 days. This SR uses an internally generated test signal to check that the 0% and 50% levels read within limits for both the upper and lower detector, both on the analog meter and on the TMM screen. This check verifies that neither the zero point nor the amplifier gain adjustment have undergone excessive drift since the previous complete CHANNEL CALIBRATION.

The Frequency of 92 days is acceptable, based on plant operating experience, and takes into account indications and alarms available to the operator in the control room.

SR 3.3.1.7 A CHANNEL FUNCTIONAL TEST on the Loss of Load and High Startup Rate channels is performed prior to a reactor startup to ensure the entire channel will perform its intended function.

A successful test of the required contact(s) of a channel relay may be performed by the verification of the change of state of a single contact of the relay. This clarifies what is an acceptable CHANNEL FUNCTIONAL TEST of a relay. This is acceptable because all of the other required contacts of the relay are verified by other Technical Specifications and non-Technical Specifications tests at least once per refueling interval with applicable extensions.

The High Startup Rate trip is actuated by either of the Wide Range Nuclear Instrument Startup Rate channels. NI-1/3 sends a trip signal to RPS channels A and C; NI-214 to channels B and D. Since each High Startup Rate channel would cause a trip on two RPS channels, the High Startup Rate trip is not tested when the reactor is critical.

The four Loss of Load Trip channels are all actuated by a single pressure switch monitoring turbine auto stop oil pressure which is not tested when the reactor is critical. Operating experience has shown that these components usually pass the Surveillance when performed at a Frequency of once per 7 days prior to each reactor startup.

Palisades Nuclear Plant B 3.3.1-32 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES SURVEILLANCE SR 3.3.1.8 REQUIREMENTS (continued)

SR 3.3.1.8 is the performance of a CHANNEL CALIBRATION every 18 months.

CHANNEL CALIBRATION is a complete check of the Instrument channel including the sensor (except neutron detectors). The Surveillance verifies that the channel responds to a measured parameter within the necessary range and accuracy. CHANNEL CALIBRATION leaves the channel adjusted to account for instrument drift between successive calibrations to ensure that the channel remains operational between successive tests. CHANNEL CALIBRATIONS must be consistent with the setpoint analysis.

The bistable setpoints must be found to trip within the Allowable Values specified In the LCO and left set consistent with the assumptions of the setpoint analysis. The Variable High Power Trip setpoint shall be verified to reset properly at several indicated power levels during (simulated) power Increases and power decreases.

The as-found and as-left values must also be recorded and reviewed for consistency with the assumptions of the setpoint analysis.

As part of the CHANNEL CALIBRATION of the wide range Nuclear Instrumentation, automatic removal of the ZPM Bypass for the Low PCS Flow, TMILP must be verified to assure that these trips are available when required.

The Frequency Is based upon the assumption of an 18 month calibration interval for the determination of the magnitude of equipment drift.

This SR is modified by a Note which states that it is not necessary to calibrate neutron detectors because they are passive devices with minimal drift and because of the difficulty of simulating a meaningful signal. Slow changes in power range excore neutron detector sensitivity are compensated for by performing the daily calorimetric calibration (SR 3.3.1.3) and the monthly calibration using the Incore detectors (SR 3.3.1.4). Sudden changes in detector performance would be noted during the required CHANNEL CHECKS (SR 3.3.1.1).

Palisades Nuclear Plant B 3.3.1.-33 Revised 01/22/2003

RPS Instrumentation B 3.3.1 BASES REFERENCES

1.
2.
3.
4.

5.

10 CFR 50, Appendix A, GDC 21 10 CFR 100 IEEE Standard 279-1971, April 5,1972 FSAR, Chapter 14 CEN-327, June 2, 1986, including Supplement 1, March 3, 1989 Palisades Nuclear Plant B 3.3.1-34 Revised 01/22/2003

RPS Instrumentation B 3.3.1 Table B 3.3.1-1 (page 1 of 1)

Instruments Affecting Multiple Specifications U

=

Required Instrument Channels Affected Specifications Nuclear Instrumentation Source Range NI-1/3, Count Rate Indication @ C-150 Panel 3.3.8 (#1)

Source Range NI-1/3 & 2/4, Count Rate Signal 3.3.9 & 3.9.2 Wide Range NI-1/3 & 2/4, Flux Level I0" Bypass 3.3.1 (#3, 6, 7, 9, & 12)

Wide Range NI-1/3 & 2/4, Startup Rate 3.3.1 (#2)

Wide Range NI-1/3 & 2/4, Flux Level Indication 3.3.7 (#3) & 3.3.9 Power Range NI-5, 6, 7,' & 8, Tq 3.2.1 & 3.2.3 Power Range NI-5,_6, 7,_& 8, Q Power 3.3.1 (#1 & 9)

Power Range NI-5,6_7, & 8, ASI -

3.3.1 (#9) & 3.2.1 & 3.2.4 Power Range NI-5, 6, 7, & 8, Loss of Load/High Startup Rate Bypass 3.3.1 (#2 & 10)

PCS T-Cold Instruments "1T-01 12CA, Temperature Signal (SPI AT Power for PDIL Alarm Circuit) 3.1.6 TT-01 12CA & 0122CA, Temperature Signal (C-150) 3.3.8 (#6 & 7)

TT-0122CB, Temperature Signal (PIP AT Power for PDIL Alarm Circuit) 3.1.6 TT-01 12CA & 0122CB, Temperature Signal (LTOP) 3.4.12.b.1 TT-0112CC & 0122CD (PTR-0112 & 0122) Temperature Indication 3.3.7 (#2)

TT-0112 & 0122 CC & CD, Temperature Signal (SMM) 3.3.7 (#5)

TT-0112 & 0122 CA, CB, CC, & CD, Temperature Signal (Q Power & TMM) 3.3.1 (#1 & 9) & 3.4.1.b PCS T-Hot Instruments TT-Oi12HA, Temperature Signal (SPI AT Power for PDIL Alarm Circuit) 3.1.6 TT-0112HA & 0122HA, Temperature Signal (C-150) 3.3.8 (#4 & 5)

TT-0122HB, Temperature Signal (PIP AT Power for PDIL Alarm Circuit) 3.1.6 TT-0112 & 0122 HC & HD, Temperature Signal (SMM) 3.3.7 (#5)

TT-0112HC & 0122HD (PTR-01 12 & 0122) Temperature Indication 3.3.7 (#1)

TT-0112 & 0122 HA, HB, HC, & HD, Temperature Signal (Q Power & TMM) 3.3.1 (#1 & 9)

Thermal Margin Monitors PY-0102A, B, C, & D 3.3.1 (#1 & 9)

Pressurizer Pressure Instruments PT-0102A, B, C, & D, Pressure Signal (RPS & SIS) 3.3.1 (#8 & 9) &

3.3.3 (#1.a & 7a)

PT-0104A & B, Pressure Signal (LTOP & SDC Interlock) 3.4.12.b.1 & 3.4.14 PT-0105A & B, Pressure Signal (WR Indication & LTOP) 3.3.7 (#5) & 3.4.12.b.1 PI-0110, Pressure Indication @ C-150 Panel 3.3.8 (#2)

SG Level Instruments LT-0751 & 0752 A, B, C, & D, Level Signal (RPS & AFAS) 3.3.1 (#4 & 5) &

3.3.3 (#4.a & 4.b)

LI-0757 & 0758 A & B, Wide Range Level Indication 3.3.7 (#11 & 12)

LI-0757C & 0758C, Wide Range Level Indication 0 C-150 Panel 3.3.8 (#10 & 11)

SG Pressure Instruments PT-0751 & 0752 A, B, C, & D, Pressure Signal (RPS & SG Isolation) 3.3.1 (#6 & 7) &

3.3.3 (#2a, 2b, 7b, 7c)

PIC-0751 & 0752 C & D, Pressure Indication 3.3.7 (#13 & 14)

PI-0751E & 0752E, Pressure Indication @ C-150 Panel 3.3.8 (#8 & 9)

Containment Pressure Instruments PS-1801, 1802, 1803, & 1804, Switch Output (RPS) 3.3.1 (#11)

PS-1801, 1802A, 1803, & 1804A, Switch Output (ESF) 3.3.3 (#5.a)

PS-1801A, 1802, 1803A, & 1804, Switch Output (ESF) 3.3.3 (#5.b)

Note:

Palisades Nuclear Plant The information provided in this table Is Intended for use as an aid to distinguish those Instrument channels which provide more than one required function and to describe which specifications they affect. The information In this table should not be taken as inclusive for all Instruments nor affected specifications.

Revised 01/22/2003 B 3.3.1-35

ESF Instrumentation B 3.3.3 B 3.3 INSTRUMENTATION B 3.3.3 Engineered Safety Features (ESF) Instrumentation BASES BACKGROUND The ESF Instrumentation initiates necessary safety systems, based upon the values of selected plant parameters, to protect against violating core design limits and the Primary Coolant System (PCS) pressure boundary and to mitigate accidents.

The ESF circuitry generates the signals listed below when the monitored variables reach levels that are indicative of conditions requiring protective action. The inputs to each ESF actuation signal are also listed.

1.

Safety Injection Signal (SIS).

a.

Containment High Pressure (CHP)

b.

Pressurizer Low Pressure

2.

Steam Generator Low Pressure (SGLP);

a.

Steam Generator A Low Pressure

b.

Steam Generator B Low Pressure

3.

Recirculation Actuation Signal (RAS);

a.

Safety Injection Refueling Water Tank (SIRWT) Low Level

4.

Auxiliary Feedwater Actuation Signal (AFAS);

a.

Steam Generator A Low Level

b.

Steam Generator B Low Level

5.

Containment High Pressure Signal (CHP);

a.

Containment High Pressure - Left Train

b.

Containment High Pressure - Right Train Palisades Nuclear Plant B 3.3.3-1 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES BACKGROUND

6.

Containment High Radiation Signal (CHR);

(continued)

a.

Containment High Radiation

7.

Automatic Bypass Removal

a.

Pressurizer Pressure Low Bypass

b.

Steam Generator A Low Pressure Bypass

c.

Steam Generator B Low Pressure Bypass In the above list of actuation signals, the CHP and RAS are derived from pressure and level switches, respectively.

Equipment actuated by each of the above signals is identified in the FSAR, Chapter 7. (Ref. 1).

The ESF circuitry, with the exception of RAS, employs two-out-of-four logic. Four independent measurement channels are provided for each function used to generate ESF actuation signals. When any two channels of the same function reach their setpoint, actuating relays are energized which, in turn, initiate the protective actions. Two separate and redundant trains of actuating relays, each powered from separate power supplies, are utilized. These separate relay trains operate redundant trains of ESF equipment RAS logic consists of output contacts of the relays actuated by the SIRWT level switches arranged in a "one-out-of-two taken twice" logic.

The contacts are arranged so that at least one low level signal powered from each station battery is required to initiate RAS. Loss of a single battery, therefore, cannot either cause or prevent RAS initiation.

The ESF logic circuitry contains the capability to manually block the SIS actuation logic and the SGLP action logic during normal plant shutdowns to avoid undesired actuation of the associated equipment.

In each case, when three of the four associated measurement channels are below the block setpoint, pressing a manual pushbutton will block the actuation signal for that train. If two of the four of the measurement channels increase above the block setpoint, the block will automatically be removed.

Palisades Nuclear Plant B 3.3.3-2 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES BACKGROUND

7.

Automatic Bypass Removal (continued)

(continued)

The sensor subsystems, including individual channel actuation bistables, is addressed in this LCO. The actuation logic subsystems, manual actuation, and downstream components used to actuate the individual ESF components are addressed in LCO 3.3.4.

Measurement Channels Measurement channels, consisting of pressure switches, field transmitters, or process sensors and associated instrumentation, provide a measurable electronic signal based upon the physical characteristics of the parameter being measured.

Four identical measurement channels are provided for each parameter used in the generation of trip signals. These are designated Channels A through D. Measurement channels provide input to ESF bistables within the same ESF channel. In addition, some measurement channels may also be used as inputs to Reactor Protective System (RPS) bistables, and most provide indication in the control room.

When a channel monitoring a parameter indicates an abnormal condition, the bistable monitoring the parameter in that channel will trip.

In the case of RAS and CHP, the sensors are latching auxiliary relays from level and pressure switches, respectively, which do not develop an analog input to separate bistables. Tripping two or more channels monitoring the same parameter will actuate both channels of Actuation Logic of the associated ESF equipment.

Three of the four measurement and bistable channels are necessary to meet the redundancy and testability of GDC 21 in Appendix A to 10 CFR 50 (Ref. 2). The fourth channel provides additional flexibility by allowing one channel to be removed from service for maintenance or testing while still maintaining a minimum two-out-of-three logic.

Since no single failure will prevent a protective system actuation and no protective channel feeds a control channel, this arrangement meets the requirements of IEEE Standard 279 -1971 (Ref. 3).

Palisades Nuclear Plant B83.3.3-3 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES BACKGROUND Measurement Channels (continued)

(continued)

The ESF Actuation Functions are generated by comparing a single measurement to a fixed bistable setpoint. The ESF Actuation Functions utilize the following input instrumentation:

Safety Iniection Signal (SIS)

The Safety Injection Signal can be generated by any of three inputs: Pressurizer Low Pressure, Containment High Pressure, or Manual Actuation. Manual Actuation is addressed by LCO 3.3.4; Containment High Pressure is discussed below. Four instruments (channels A through D), monitor Pressurizer Pressure to develop the SIS actuation. Each of these instrument channels has two individually adjustable ESF bistable trip devices, one for the bypass removal circuit (discussed below) and one for SIS. Each ESF bistable trip device actuates two auxiliary relays, one for each actuation train. The output contacts from these auxiliary relays form the logic circuits addressed in LCO 3.3.4. The instrument channels associated with each Pressurizer Low Pressure SIS actuation bistable include the pressure measurement loop, the SIS actuation bistable, and the two auxiliary relays associated with that bistable. The bistables associated with automatic removal of the Pressurizer Low Pressure Bypass are discussed under Function 7.a, below.

Low Steam Generator Pressure Sigqnal (SGLP)

There are two separate Low Steam Generator Pressure signals, one for each steam generator. For each steam generator, four instruments (channels A through D) monitor pressure to develop the SGLP actuation. Each of these instrument channels has two individually adjustable ESF bistable tdp devices, one for the bypass removal circuit (discussed below) and one for SGLP.

Each Steam SGLP bistable trip device actuates an auxiliary relay.

The output contacts from these auxiliary relays form the SGLP logic circuits addressed in LCO 3.3.4. The instrument channels associated with each Steam Generator Low Pressure Signal bistable include the pressure measurement loop, the SGLP actuation bistable, and the auxiliary relay associated with that bistable. The bistables associated with automatic removal of the SGLP Bypass are discussed under Function 7.a, below.

Palisades Nuclear Plant B 3.3.3-4 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES BACKGROUND Measurement Channels (continued)

(continued)

Recirculation Actuation Sigqnal (RAS)

There are four Safety Injection Refueling Water (SIRW) Tank level instruments used to develop the RAS signal. Each of these instrument channels actuates two auxiliary relays, one for each actuation train. The output contacts from these auxiliary relays form the logic circuits addressed In LCO 3.3.4. The SIRW Tank Low Level Instrument channels associated with each RAS actuation bistable include the level instrument and the two auxiliary relays associated with that Instrument.

Auxiliary Feedwater Actuation Signal (AFAS)

There are two separate AFAS signals (AFAS channels A and B),

each one actuated on low level In either steam generator. For each steam generator, four level instruments (channels A through D) monitor level to develop the AFAS actuation signals. The output contacts from the bistables on these level channels form the AFAS logic circuits addressed in LCO 3.3.4. The Instrument channels associated with each Steam Generator Low Level Signal bistable include the level measurement loop and the Low Level AFAS bistable.

0 Containment High Pressure Actuation (CHP)

The Containment High Pressure signal is actuated by two sets of four pressure switches, one set for each train. The output contacts from these pressure switches form the CHP logic circuits addressed In LCO 3.3A4.

Palisades Nuclear Plant B 3.3.3-5 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES BACKGROUND Measurement Channels (continued)

(continued)

Containment High Radiation Actuation (CHR)

The CHR signal can be generated by either of two inputs: High Radiation or Manual Actuation. Manual Actuation is addressed by LCO 3.3.4. Four radiation monitor instruments (channels A through D), monitor containment area radiation level to develop the CHR signal. Each CHR monitor bistable device actuates one auxiliary relay which has contacts in each CHR logic train addressed in LCO 3.3.4. The instrument channels associated with each CHR actuation bistable include the radiation monitor itself and the associated auxiliary relay.

Automatic Bypass Removal Functions Pressurizer Low Pressure and Steam Generator Low Pressure logic circuits have the capability to be blocked to avoid undesired actuation when pressure is intentionally lowered during plant shutdowns. In each case these bypasses are automatically removed when the measured pressure exceeds the bypass permissive setpoint. The measurement channels which provide the bypass removal signal are the same channels which provide the actuation signal. Each of these pressure measurement channels has two bistables, one for actuation and one for the bypass removal Function. The pressurizer pressure channels include an auxiliary relay actuated by the bypass removal bistable.

The logic circuits for Automatic Bypass Removal Functions are addressed by LCO 3.3.4.

Several measurement instrument channels provide more than one required function. Those sensors shared for RPS and ESF functions are identified in Table B 3.3.1-1. That table provides a listing of those shared channels and the Specifications which they affect.

Palisades Nuclear Plant B 3.3.3-6 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES BACKGROUND Bistable Trip Units (continued)

There are four channels of bistables, designated A through D, for each ESF Function, one for each measurement channel. The bistables for all required Functions, except CHP and RAS, receive an analog input from the measurement device, compare the analog input to trip setpoints, and provide contact output to the Actuation Logic. CHP and RAS are actuated by pressure switches and level switches respectively.

The Allowable Values are specified for each safety related ESF trip Function which is credited in the safety analysis. Nominal trip setpoints are specified in the plant procedures. The nominal setpoints are selected to ensure plant parameters do not exceed the Allowable Value if the instrument'loop is performing as required. The methodology used to determine the nominal trip setpoints is also provided in plant documents. Operation with a trip setpoint less conservative than the nominal trip setpoint, but within its Allowable Value, is acceptable. Each Allowable Value specified is more conservative than the analytical limit determined in the safety analysis in order to account for uncertainties appropriate to the trip Function. These uncertainties are addressed as described in plant documents. A channel is inoperable if its actual setpoint is not within its Allowable Value.

Setpoints in accordance with the Allowable Value will ensure that Safety Limits of Chapter 2.0, "SAFETY LIMITS (SLs)," are not violated during Anticipated Operational Occurrences (AOOs) and that the consequences of Design Basis Accidents (DBAs) will be acceptable, providing the plant is operated from within the LCOs at the onset of the AOO or DBA and the equipment functions as designed. (As defined in 10 CFR 50, Appendix A, "Anticipated operational occurances mean those conditions of normal operation which are expected to occur one or more times during the life of the nuclear power unit and include but are not limited to loss of power to all recirculation pumps, tripping of the turbine generator set, isolation of the main condenser, and loss of all offsite power.")

ESF Instrument Channel Bypasses The only ESF Instrument channels with built-in bypass capability are the Low SG Level AFAS bistables. Those bypasses are effected by a key operated switch, similar to the RPS Trip Channel Bypasses. A bypassed Low SG Level channel AFAS bistable cannot perform its specified function and must be considered inoperable.

Palisades Nuclear Plant B 3.3.3-7 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES BACKGROUND (continued)

ESF Instrument Channel Bypasses (continued)

While there are no other built-in provisions for instrument channel bypasses in the ESF design (bypassing any other channel output requires opening a circuit link, lifting a lead, or using a jumper), this LCO includes requirements for OPERABILITY of the instrument channels and bistables which provide input to the Automatic Bypass Removal Logic channels required by LCO 3.3.4, "ESF Logic and Manual Initiation.*

The Actuation Logic channels for Pressurizer Pressure and Steam Generator Low Pressure, however, have the ability to be manually bypassed when the associated pressure is below the range where automatic protection is required. These actuation logic channel bypasses may be manually initiated when three-out-of-four bypass permissive bistables indicate below their setpoint. When two-out-of-four of these bistables are above their bypass permissive setpoint, the actuation logic channel bypass is automatically removed. The bypass permissive bistables use the same four measurement channels as the blocked ESF function for their inputs.

APPLICABLE SAFETY ANALYSES Each of the analyzed accidents can be detected by one or more ESF Functions. One of the ESF Functions is the primary actuation signal for that accident. An ESF Function may be the primary actuation signal for more than one type of accident. An ESF Function may also be a secondary, or backup, actuation signal for one or more other accidents.

Functions not specifically credited in the accident analysis, serve as backups and are part of the NRC approved licensing basis for the plant.

Palisades Nuclear Plant B 3.3.3-8 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES APPLICABLE ESF protective Functions are as follows.

SAFETY ANALYSES (continued) 1.-

Safety Iniection Signal (SIS)

The SIS ensures acceptable consequences during Loss of Coolant Accident (LOCA) events, including steam generator tube rupture, and Main Steam Line Breaks (MSLBs) or Feedwater Line Breaks (FWLBs) (inside containment). To provide the required protection, SIS is actuated by a CHP signal, or by two-out-of-four Pressurizer Low Pressure channels decreasing below the setpoint. SIS initiates the following actions:

a.

Start HPSI & LPSI pumps;

b.

Start component cooling water and service water pumps;

c.

Initiate service water valve operations;

d.

Initiate component cooling water valve operations;

e.

Start containment cooling fans (when coincident with a loss of offsite power);

f.

Enable Containment Spray Pump Start on CHP; and

g.

Initiate Safety Injection Valve operations.

Each SIS logic train is also actuated by a contact pair on one of the CHP initiation relays for the associated CHP train.

2.

Steam Generator Low Pressure Signal (SGLP)

The SGLP ensures acceptable consequences during an MSLB or FVVLB by Isolating the steam generator if it indicates a low steam generator pressure. The SGLP concurrent with or following a reactor trip, minimizes the rate of heat extraction and subsequent cooldown of the PCS during these events.

Palisades Nuclear Plant B 3.3.3-9 Revised 0 1/22/2003

ESF Instrumentation B 3.3.3 BASES APPLICABLE

2.

Steam Generator Low Pressure Signal (SGLP) (continued)

SAFETY ANALYSES (continued)

One SGLP circuit is provided for each SG. Each SGLP circuit is actuated by two-out-of-four pressure channels on the associated SG reaching their setpoint. SGLP initiates the following actions:

a.

Close the associated Feedwater Regulating valve and its bypass; and

b.

Close both Main Steam Isolation Valves.

3.

Recirculation Actuation Signal At the end of the injection phase of a LOCA, the SIRW" will be nearly empty. Continued cooling must be provided by the ECCS to remove decay heat The source of water for the ECCS pumps is automatically switched to the containment recirculation sump. Switchover from SIRWT to the containment sump must occur before the SIRWT empties to prevent damage to the ECCS pumps and a loss of core cooling capability. For similar reasons, switchover must not occur before there is sufficient water in the containment sump to support pump suction.

Furthermore, early switchover must not occur to ensure sufficient borated water is injected from the SIRWT to ensure the reactor remains shut down in the recirculation mode. An SIRWT Low Level signal initiates the RAS.

RAS initiates the following actions:

a.

Trip LPSI pumps (this trip can be manually bypassed);

b.

Switch HPSI and containment spray pump suction from SIRWT to Containment Sump by opening sump CVs and closing SIRWT CVs;

c.

Adjust cooling water to component cooling heat exchangers;

d.

Open HPSI subcooling valve CV-3071 if the associated HPSI pump is operating;

e.

After containment sump valve CV-3030 is opened, open HPSI subcooling valve CV-3070 if the associated HPSI pump is operating;

f.

Close containment spray valve CV-3001 if containment sump valve CV-3030 does not open.

Palisades Nuclear Plant B 3.3.3-10 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES APPLICABLE SAFETY ANALYSES (continued) 3 Recirculation Actuation Signal (continued)

The RAS signal is actuated by separate sensors from those which provide tank level indication. The allowable range of 21" to 27" above the tank floor corresponds to 1.1% to 3.3% indicated level.

Typically the actual setting is near the midpoint of the allowable range.

4 Auxiliary Feedwater Actuation Signal An AFAS initiates feedwater flow to both steam generators if a low level is indicated In either steam generator.

The AFAS maintains a steam generator heat sink during the following events:

MSLB; FW*LB; LOCA; and Loss of feedwater.

5.

Containment High Pressure Signal (CHP)

The CHP signal closes all containment isolation valves not required for ESF operation and starts containment spray (if SIS enabled), ensuring acceptable consequences during LOCAs, control rod ejection events,.MSLBs, or FWLBs (inside containment).

CHP is actuated by two-out-of-four pressure switches for the associated train reaching their setpoints. CHP initiates the following actions:

a.

Containment Spray;

b.

Safety Injection Signal;

c.

Main Feedwater Isolation; Palisades Nuclear Plant B 3.3.3-11 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES APPLICABLE SAFETY ANALYSIS (continued)

5.

Containment Hi-gh Pressure Signal (CHP) (continued)

d.

Main Steam Line Isolation;

e.

Control Room HVAC Emergency Mode; and

f.

Containment Isolation Valve Closure.

6.

Containment High Radiation Siqnal (CHR)

CHR is actuated by two-out-of-four radiation monitors exceeding their setpoints. CHR initiates the following actions to ensure acceptable consequences following a LOCA or control rod ejection event:

a.

Control Room HVAC Emergency Mode;

b.

Containment Isolation Valve Closure; and

c.

Block automatic starting of ECCS pump room sump pumps.

During refueling operations, separate switch-selectable radiation monitors initiate CHR, as addressed by LCO 3.3.6.

7.

Automatic Bypass Removal Functions The logic circuitry provides automatic removal of the Pressurizer Pressure Low and Steam Generator Pressure Low actuation signal bypasses. There are no assumptions in the safety analyses which assume operation of these automatic bypass removal circuits, and no analyzed events result in conditions where the automatic removal would be required to mitigate the event. The automatic removal circuits are required to assure that logic circuit bypasses will not be overlooked during a plant startup.

The ESF Instrumentation satisfies Criterion 3 of 10 CFR 50.36(c)(2).

Palisades Nuclear Plant B 3.3.3-12 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES LCO The LCO requires all channel components necessary to provide an ESF actuation to be OPERABLE.

The Bases for the LCO on ESF Functions are addressed below.

I1.

Safety Iniection Signal (SIS)

This LCO requires four channels of SIS Pressurizer Low Pressure to be OPERABLE in MODES 1, 2, and 3.

The setpoint was chosen so as to be low enough to avoid actuation during plant operating transients, but to be high enough to be quickly actuated by a LOCA or MSLB. The settings include an uncertainty allowance which is consistent with the settings assumed in the MSLB analysis (which bounds the settings assumed In the LOCA analysis).

2.

Steam Generator Low Pressure Signal (SGLP)

This LCO requires four channels of Steam Generator Low Pressure Instrumentation for each SG to be OPERABLE in MODES 1, 2, and 3. However, as indicated In Table 3.3.3-1, Note (a), the SGLP Function is not required to be OPERABLE in MODES 2 or 3 if all Main Steam Isolation Valves (MSIVs) are closed and deactivated and all Main Feedwater Regulating Valves (MFRVs) and MFRV bypass valves are either closed and deactivated or isolated by closed manual valves.

The setpoint was chosen to be low enough to avoid actuation during plant operation, but be close enough to full power operating pressure to be actuated quickly in the event of a MSLB. The setting includes an uncertainty allowance which is consistent with the setting used In the Reference 4 analysis.

Each SGLP logic Is made up of output contacts from four pressure bistables from the associated SG. When the logic circuit is satisfied, two relays are energized to actuate steam'and feedwater line isolation.

Palisades Nuclear Plant Revised 01/22/2003 B 3.3.3-13

ESF Instrumentation B 3.3.3 BASES LCO

2.

Steam Generator Low Pressure Signal (SGLP) (continued)

(continued)

This LCO applies to failures in the four sensor subsystems, including sensors, bistables, and associated equipment. Failures in the actuation subsystems are considered Actuation Logic failures and are addressed in LCO 3.3.4.

3.

Recirculation Actuation Signal (RAS)

This LCO requires four channels of SIRWT Low Level to be OPERABLE in MODES 1, 2, and 3.

The setpoint was chosen to provide adequate water in the containment sump for HPSI pump net positive suction head following an accident, but prevent the pumps from running dry during the switchover.

The upper limit on the Allowable Value for this trip is set low enough to ensure RAS does not initiate before sufficient water is transferred to the containment sump. Premature recirculation could impair the reactivity control Function of safety injection by limiting the amount of boron injection. Premature recirculation could also damage or disable the recirculation system if recirculation begins before the sump has enough water.

The lower limit on the SIRWT Low Level trip Allowable Value is high enough to transfer suction to the containment sump prior to emptying the SIRWT.

4.

Auxiliary Feedwater Actuation Signal (AFAS)

The AFAS logic actuates AFW to each SG on a SG Low Level in either SG.

The Allowable Value was chosen to assure that AFW flow would be initiated while the SG could still act as a heat sink and steam source, and to assure that a reactor trip would not occur on low level without the actuation of AFW.

Palisades Nuclear Plant B 3.3.3-14 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES LCO

4.

Auxiliary Feedwater Actuation Signal (AFAS) (continued)

(continued)

This LCO requires four channels for each steam generator of Steam Generator Low Level to be OPERABLE in MODES 1, 2, and 3.

5.

Containment High Pressure Signal (CHP)

This LCO requires four channels of CHP to be OPERABLE for each of the associated ESF trains (left and right) in MODES 1, 2, 3 and 4.

The setpoint was chosen so as to be high enough to avoid actuation by containment temperature or atmospheric pressure changes, but low enough to be quickly actuated by a LOCA or a MSLB in the containment.

6.

Containment High Radiation Signal (CHR)

This LCO requires four channels of CHR to be OPERABLE in MODES 1, 2,3, and 4.

The setpoint Is based on the maximum primary coolant leakage to the containment atmosphere allowed by LCO 3.4.13 and the maximum activity allowed by LCO 3.4.16. Ni6 concentration reaches equilibrium in containment atmosphere due to its short half-life, but other activity was assumed to build up. At the end of a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> leakage period the dose rate Is approximately 20 R/h as seen by the area monitors. A large leak could cause the area dose rate to quickly exceed the 20 R/h setting and initiate CHI.

7.

Automatic Bypass Removal The automatic bypass removal logic removes the bypasses which are used during plant shutdown periods, for Pressurizer Low Pressure and Steam Generator Low Pressure actuation signals.

The setpoints were chosen to be above the setpoint for the associated actuation signal, but well below the normal operating pressures.

Palisades Nuclear Plant B 3.3:3-115 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES LCO

7.

Automatic Bypass Removal (continued)

(continued)

This LCO requires four channels of Pressurizer Low Pressure bypass removal and four channels for each steam generator of Steam Generator Low Pressure bypass removal, to be OPERABLE in MODES 1, 2, and 3.

APPLICABILITY All ESF Functions are required to be OPERABLE in MODES 1, 2, and 3. In addition, Containment High Pressure and Containment High Radiation are required to be operable in MODE 4.

In MODES 1, 2, and 3 there is sufficient energy in the primary and secondary systems to warrant automatic ESF System responses to:

Close the main steam isolation valves to preclude a positive reactivity addition and containment overpressure; Actuate AFW to preclude the loss of the steam generators as a heat sink (in the event the normal feedwater system is not available);

Actuate ESF systems to prevent or limit the release of fission product radioactivity to the environment by isolating containment and limiting the containment pressure from exceeding the containment design pressure during a design basis LOCA or MSLB; and Actuate ESF systems to ensure sufficient borated inventory to permit adequate core cooling and reactivity control during a design basis LOCA or MSLB accident.

The CHP and CHR Functions are required to be OPERABLE in MODE 4 to limit leakage of radioactive material from containment and limit operator exposure during and following a DBA.

The SGLP Function is not required to be OPERABLE in MODES 2 and 3, if all MSIVs are closed and deactivated and all MFRVs and MFRV bypass valves are either closed and deactivated or isolated by closed manual valves, since the SGLP Function is not required to perform any safety functions under these conditions.

Palisades Nuclear Plant B 3.3.3-16 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES APPLICABILITY In lower MODES, automatic actuation of ESF Functions is not required, (continued) because adequate time is available for plant operators to evaluate plant conditions and respond by manually operating the ESF components.

LCO 3.3.6 addresses automatic Refueling CHR isolation during CORE ALTERATIONS or during movement of irradiated fuel.

In MODES 5 and 6, ESFAS initiated systems are either reconfigured or disabled for shutdown cooling operation. Accidents in these MODES are slow to develop and would be mitigated by manual operation of Individual components.

ACTIONS The most common causes of channel inoperability are outright failure of loop components or drift of those loop components which is sufficient to exceed the tolerance provided in the plant setpoint analysis. Loop component failures are typically identified by the actuation of alarms due to the channel failing to the "safew condition, during CHANNEL CHECKS (when the instrument is compared to the redundant channels), or during the CHANNEL FUNCTIONAL TEST (when an automatic component might not respond properly). Typically, the drift of the loop components Is found to be small and results in a delay of actuation rather than a total loss of function. Excessive loop component drift would, most likely, be Identified during a CHANNEL CHECK (when the Instrument is compared to the redundant channels) or during a CHANNEL CALIBRATION (when Instrument loop components are checked against reference standards).

Typically, the drift is small and results in a delay of actuation rather than a total loss of function. Determination of setpoint drift is generally made during the performance of a CHANNEL FUNCTIONAL TEST when the process instrument is set up for adjustment to bring it to within specification. If the actual trip setpoint is not within the Allowable Value in Table 3.3.3-1, the channel is Inoperable and the appropriate Condition(s) are entered.

In the event a channel's trip setpoint is found nonconservative with respect to the Allowable Value in Table 3.3.3-1, or the sensor, Instrument loop, signal processing electronics, or ESF bistable is found inoperable, then all affected Functions provided by that channel must be declared Inoperable and the plant must enter the Condition statement for the particular protection Function affected.

Palisades Nuclear Plant B 3.3.3-17 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES ACTIONS When the number of inoperable channels in a trip Function exceeds (continued) those specified in any related Condition associated with the same trip Function, then the plant is outside the safety analysis. Therefore, LCO 3.0.3 should be immediately entered if applicable in the current MODE of operation.

A Note has been added to clarify the application of the Completion Time rules. The Conditions of this Specification may be entered independently for each Function in Table 3.3.3-1. Completion Times for the inoperable channel of a Function will be tracked separately.

A.1 Condition A applies to the failure of a single bistable or associated instrumentation channel of one or more input parameters in each ESF Function except the RAS Function. Since the bistable and associated instrument channel combine to perform the actuation function, the Condition is also appropriate if both the bistable and associated instrument channel are inoperable.

ESF coincidence logic is normally two-out-of-four. If one ESF channel is inoperable, startup or power operation is allowed to continue as long as action is taken to restore the design level of redundancy.

If one ESF channel is inoperable, startup or power operation is allowed to continue, providing the inoperable channel actuation bistable is placed in trip within 7 days. The provision of four trip channels allows one channel to be inoperable in a non-trip condition up to the 7 day Completion Time allotted to place the channel in trip. Operating with one failed channel in a non-trip condition during operations, places the ESF Actuation Logic in a two-out-of-three coincidence logic.

If the failed channel cannot be restored to OPERABLE status in 7 days, the associated bistable is placed in a tripped condition. This places the function in a one-out-of-three configuration.

Palisades Nuclear Plant B 3.3.3-18 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES ACTIONS A.1 (continued)

(continued)

In this configuration, common cause failure of the dependent channel cannot prevent ESF actuation. The 7 day Completion Time is based upon operating experience, which has demonstrated that a random failure of a second channel occurring during the 7 day period is a low probability event.

Condition A is modified by a Note which indicates it is not applicable to the SIRWT Low Level Function.

B.1 and B.2 Condition B applies to the failure of two channels in any of the ESF Functions except the RAS Function.

With two inoperable channels, one channel actuation device must be placed in trip within the 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> Completion Time. Eight hours is allowed for this action since it must be accomplished by a circuit modification, or by removing power from a circuit component. With one channel of protective Instrumentation Inoperable, the ESF Actuation Logic Function Is in two-out-of-three logic, but with another channel inoperable the ESF may be operating with a two-out-of-two logic. This is outside the assumptions made In the analyses and should be corrected. To correct the problem, the second channel is placed in trip. This places the ESF In a one-out-of-two logic. If any of the other OPERABLE channels receives a trip signal, ESF actuation will occur.

One of the failed channels must be restored to OPERABLE status within 7 days, and the provisions of Condition A still applied to the remaining inoperable channel. Therefore, the channel that is still inoperable after completion of Required Action B.2 must be placed in trip if more than 7 days has elapsed since the channel's initial failure.

Palisades Nuclear Plant B 3.3.3-19 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES ACTIONS B.1 and B.2 (continued)

(continued)

Condition B is modified by a Note which indicates that it is not applicable to the SIRWT Low Level Function. The Required Action is also modified by a Note stating that LCO 3.0.4 is not applicable. The Note was added to allow the changing of MODES even though two channels are inoperable, with one channel tripped. MODE changes in this configuration are allowed, to permit maintenance and testing on one of the inoperable channels. In this configuration, the protection system is in a one-out-of-two logic, and the probability of a common cause failure affecting both of the OPERABLE channels during the 7 days permitted is remote.

C.1 and C.2 Condition C applies to one RAS SIRWT Low Level channel inoperable.

The SIRWT low level circuitry is arranged in a "I-out-of-2 taken twice" logic rather than the more frequently used 2-out-of-4 logic. Therefore, Required Action C.1 differs from other ESF functions. With a bypassed SIRWT low level channel, an additional failure might disable automatic RAS, but would not initiate a premature RAS. With a tripped channel, an additional failure could cause a premature RAS, but would not disable the automatic RAS.

Since considerable time is available after initiation of SIS until RAS must be initiated, and since a premature RAS could damage the ESF pumps, it is preferable to bypass an inoperable channel and risk loss of automatic RAS than to trip a channel and risk a premature RAS.

The Completion Time of 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> allowed is reasonable because the Required Action involves a circuit modification.

Required Action C.2 requires that the inoperable channel be restored to OPERABLE status within 7 days. The Completion Time is reasonable based upon operating experience, which has demonstrated that a random failure of a second channel occurring during the 7 day period is a low probability event.

Palisades Nuclear Plant B 3.3.3-20 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES ACTIONS D.1 and D.2 (continued)

If the Required Actions and associated Completion Times of Condition A, B, or C are not met for Functions 1, 2, 3, 4, or 7, the plant must be brought to a MODE in which the LCO does not apply. To achieve this status, the plant must be brought to at least MODE 3 within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and to MODE 4 within 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. The allowed Completion' Times are reasonable, based on operating experience, to reach the required plant conditions from full power conditions in an ordedy manner and without challenging plant systems.

E.1 and E.2 If the Required Actions and associated Completion Times of Condition A, B, or C are not met for Functions 5 or 6, the plant must be brought to a MODE in which the LCO does not apply. To achieve this status, the plant must be brought to at least MODE 3 within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and to MODE 5 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. The allowed Completion Times are reasonable, based on operating experience, to reach the required plant conditions from full power conditions in an orderly manner and without challenging plant systems.

SURVEILLANCE The SRs for any particular ESF Function are found in the SRs column REQUIREMENTS of Table 3.3.3-1 for that Function. Most functions are subject to CHANNEL CHECK, CHANNEL FUNCTIONAL TEST, and CHANNEL CALIBRATION.

SR 3.3.3.1 A CHANNEL CHECK is performed once every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> on each ESF input channel which is provided with an indicator to provide a qualitative assurance that the channel is working properly and that its readings are within limits. A CHANNEL CHECK is not perrormed on the CHP and SIRWT Low Level channels because they have no associated control room indicator.

Palisades Nuclear Plant B 3.3.3-21 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES SURVEILLANCE REQUIREMENTS (continued)

SR 3.3.3.1 (continued)

Performance of the CHANNEL CHECK once every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ensures that a gross failure of instrumentation has not occurred. A CHANNEL CHECK is normally a comparison of the parameter indicated on one channel to a similar parameter on other channels. It is based on the assumption that instrument channels monitoring the same parameter should read approximately the same value. Significant deviations between instrument channels could be an indication of excessive instrument drift in one of the channels or of something even more serious. CHANNEL CHECK will detect gross channel failure; thus, it is key to verifying the instrumentation continues to operate properly between each CHANNEL CALIBRATION.

Agreement criteria are determined by the plant staff based on a combination of the channel instrument uncertainties, including indication and readability. If a channel is outside the criteria, it may be an indication that the sensor or the signal processing equipment has drifted outside its limit. If the channels are within the criteria, it is an indication that the channels are OPERABLE. If the channels are normally off scale during times when Surveillance is required, the CHANNEL CHECK will only verify that they are off scale in the same direction.

Offscale low current loop channels are verified to be reading at the bottom of the range and not failed downscale.

The Frequency of about once every shift is based on operating experience that demonstrates channel failure is rare. Since the probability of two random failures in redundant channels in any 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> period is extremely low, the CHANNEL CHECK minimizes the chance of loss of protective function due to failure of redundant channels. The CHANNEL CHECK supplements less formal, but more frequent, checks of CHANNEL OPERABILITY during normal operational use of displays associated with the LCO required channels.

Palisades Nuclear Plant B 3.3.3-22 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES SURVEILLANCE REQUIREMENTS (continued)

SR 3.3.3.2 A CHANNEL FUNCTIONAL TEST is performed every 92 days to ensure the entire channel will perform its intended function when needed. A successful test of the required contact(s) of a channel relay may be performed by the verification of the change of state of a single contact of the relay. This clarifies what is an acceptable CHANNEL FUNCTIONAL TEST of a relay. This is acceptable because all of the other required contacts of the relay are verified by other Technical Specifications and non-Technical Specifications tests at least once per refueling interval with applicable extensions.

This test is required to be performed each 92 days on ESF input channels provided with on-line testing capability. It is not required for the SIRWT Low Level channels since they have no built in test capability. The CHANNEL FUNCTIONAL TEST for SIRWT Low Level channels is performed each 18 months as part of the required CHANNEL CALIBRATION.

The CHANNEL FUNCTIONAL TEST tests the individual channels using an analog test Input to each bistable.

Any setpoint adjustment shall be consistent with the assumptions of the current setpoint analysis.

The Frequency of 92 days is based on the reliability analysis presented In topical report CEN-327, "RPS/ESFAS Extended Test Interval Evaluation" (Reference 5).

SR 3.3.3.3 CHANNEL CALIBRATION is a complete check of the instrument channel, Including the sensor. The Surveillance verifies that the channel responds to a measured parameter within the necessary range and accuracy. CHANNEL CALIBRATION leaves the channel adjusted to account for Instrument drift between successive calibrations to ensure that the channel remains operational between successive surveillances. CHANNEL CALIBRATIONS must be performed consistent with the setpoint analysis.

Palisades Nuclear Plant B 3.3.3-23 Revised 01/22/2003

ESF Instrumentation B 3.3.3 BASES SURVEILLANCE SR 3.3.3.3 (continued)

REQUIREMENTS (continued)

The as found and as left values must also be recorded and reviewed for consistency with the assumptions of the extension analysis. The requirements for this review are outlined in Reference 5.

The Frequency is based upon the assumption of an 18 month calibration interval for the determination of the magnitude of equipment drift in the setpoint analysis.

REFERENCES

1.

FSAR, Chapter 7

2.

10 CFR 50, Appendix A

3.

IEEE Standard 279-1971

4.

FSAR, Chapter 14

5.

CEN-327, June 2, 1986, including Supplement 1, March 3, 1989 Palisades Nuclear Plant B 3.3.3-24 Revised 01/22/2003

Containment Cooling Systems B 3.6.6 B 3.6 CONTAINMENT SYSTEMS B 3.6.6 Containment Cooling Systems BASES BACKGROUND The Containment Spray and Containment Air Cooler systems provide containment atmosphere cooling to limit post accident pressure and temperature In containment to less than the design values. Reduction of containment pressure reduces the release of fission product radioactivity from containment to the environment, in the event of a Main Steam Line Break (MSLB) or a large break Loss of Coolant Accident (LOCA). The Containment Spray and Containment Air Cooler systems are designed to the requirements of the Palisades Nuclear Plant design criteria (Ref. 1).

The Containment Air Cooler System and Containment Spray System are Engineered Safety Feature (ESF) systems. They are designed to ensure that the heat removal capability required during the post accident period can be attained. The systems are arranged with two spray pumps and one air coolerfan powered from one diesel generator, and with one spray pump and thr ee air cooler fans powered from the other diesel generator.

The Containment Spray System was originally designed to be redundant to the Containment Air Coolers (CACs) and fans. These systems were originally designed such that either two containment spray pumps or three CACs could limit containment pressure to less than design. However, the current safety analyses take credit for one containment spray pump when evaluating cases with three CACs, and for one air cooler fan in cases with two spray pumps and both Main Steam Isolation Valve (MSIV) bypass valves closed. If an MSIV bypass valve is open, 2 service water pumps and 2 CACs are also required to be OPERABLE in addition to the 2 spray pumps for containment heat removal.

To address this dependency between the Containment Spray System and the Containment Air Cooler System the title of this Specification is "Containment Cooling Systems,3 and Includes both systems. The LCO Is written in terms of trains of containment cooling. One train of containment cooling Is associated with Diesel Generator 1-1 and Includes Containment Spray Pumps P-54B and P-54C, Containment Spray Valve CV-3001 and the associated spray header, and Air Cooler Fan V-4A. The other train of containment cooling is associated with Diesel Generator 1-2 and includes Containment Spray Pump P-54A, Containment Spray Valve CV-3002 and the associated spray header, and CACs VHX-1, VHX-2, and VHX-3 and their associated safety related fans, V-1A, V-2A, and V-3A.

Palisades Nuclear Plant B 3.6.6-1 Revised 01/22/2003

Containment Cooling Systems B 3.6.6 BASES BACKGROUND If reliance is placed solely on one spray pump and three CACs, at least (continued) two service water pumps must be OPERABLE to provide the necessary service water flow to assure OPERABILITY of the CACs. Additional details of the required equipment and its operation is discussed with the containment cooling system with which it is associated.

Containment Spray System The Containment Spray System consists of three half-capacity (50%)

motor driven pumps, two shutdown cooling heat exchangers, two spray headers, two full sets of full capacity (100%) nozzles, valves, and piping, two full capacity (100%) pump suction lines from the Safety Injection and Refueling Water Tank (SIRWT) and the containment sump with the associated piping, valves, power sources, instruments, and controls. The heat exchangers are shared with the Shutdown Cooling System. SIRWT supplies borated water to the containment spray during the injection phase of operation. In the recirculation mode of operation, containment spray pump suction is transferred from the SIRWT to the containment sump.

Normally, both Shutdown Cooling Heat Exchangers must be available to provide cooling of the containment spray flow in the event of a Loss of Coolant Accident. If the Containment Spray side (tube side) of one SDC Heat Exchanger is out of service, 100% of the required post accident cooling capability can be provided, if other equipment outages are limited (refer to Bases for Required Action C.1).

The Containment Spray System provides a spray of cold borated water into the upper regions of containment to reduce the containment pressure and temperature during a MSLB or large break LOCA event. In addition, the Containment Spray System in conjunction with the use of trisodium phosphate (LCO 3.5.5, "Trisodium Phosphate,m) serve to remove iodine which may be released following an accident. The SIRWT solution temperature is an important factor in determining the heat removal capability of the Containment Spray System during the injection phase.

Palisades Nuclear Plant B 3.6.6-2 Revised 01/22/2003

Containment Cooling Systems B 3.6.6 BASES BACKGROUND Containment Spray System (continued)

In the recirculation mode of operation, heat is removed from the containment sump water by the shutdown cooling heat exchangers.

The Containment Spray System is actuated either automatically by a Containment High Pressure (CHP) signal or manually. An automatic actuation opens the containment spray header Isolation valves, starts the three containment spray pumps, and begins the injection phase.

Individual component controls may be used to manually initiate Containment Spray. The injection phase continues until an SIRWT Level Low signal is received. The Low Level signal for the SIRWT generates a Recirculation Actuation Signal (RAS) that aligns valves from the containment spray pump suction to the containment sump. RAS opens the H PSI subcooling valve CV-3071, if the associated HPSI pump is operating. After the containment sump valve CV-3030 opens from RAS, HPSI subcooling valve CV-3070 will open, if the associated HPSI pump is operating. RAS will close containment spray valve CV-3001, If containment sump valve CV-3030 does not open. The Containment Spray System In recirculation mode maintains an equilibrium temperature between the containment atmosphere and the recirculated sump water.

Operation of the Containment Spray System in the recirculation mode Is controlled by the operator in accordance with the emergency operating procedures.

The containment spray pumps also provide a required support function for the High Pressure Safety Injection pumps as described in the Bases for specification 3.5.2. The High Pressure Safety Injection pumps alone may not have adequate NPSH after a postulated accident and the realignment of their suctions from the SIRWT to the containment sump.

Flow Is automatically provided from the discharge of the containment spray pumps to the suction of the High Pressure Safety Injection (HPSI) pumps after the change to recirculation mode has occurred, if the HPSI pump is operating. The additional suction pressure ensures that adequate NPSH Is available for the High Pressure Safety Injection pumps.

Palisades Nuclear Plant B 3.6.6-3 Revised 01/22/2003

Containment Cooling Systems B 3.6.6 BASES BACKGROUND Containment Air Cooler System (continued)

The Containment Air Cooler System includes four air handling and cooling units, referred to as the Containment Air Coolers (CACs), which are located entirely within the containment building. Three of the CACs (VHX-1, VHX-2, and VHX-3) are safety related coolers and are cooled by the critical service water. The fourth CAC (VHX-4) is not taken credit for in maintaining containment temperature within limit (the service water inlet valve for VHX-4 is closed by an SIS signal to conserve service water flow), but is used during normal operation along with the three CACs to maintain containment temperature below the design limits. The fan associated with VHX-4, V-4A, is assumed in the safety analysis as assisting in the containment atmosphere mixing function.

The DG which powers the fans associated with VHX-1, VHX-2, and VHX-3 (V-1A, V-2A and V-3A) also powers two service water pumps.

This is necessary because if reliance is placed solely on the train with one spray pump and three CACs, at least two service water pumps must be OPERABLE to provide the necessary service water flow to assure OPERABILITY of the CACs.

Each CAC has two vaneaxial fans with direct connected motors which draw air through the cooling coils. Both of these fans are normally in operation, but only one fan and motor for each CAC is rated for post accident conditions. The post accident rated 'safety related* fan units, V-1A, V-2A, V-3A, and V-4A, serve not only to provide forced flow for the associated cooler, but also provide mixing of the containment atmosphere. A single operating safety related fan unit will provide enough air flow to assure that there is adequate mixing of unsprayed containment areas to assure the assumed iodine removal by the containment spray. The fan units also support the functioning of the hydrogen recombiners, as discussed in the Bases for LCO 3.6.7, "Hydrogen Recombiners.' In post accident operation following a SIS, all four Containment air coolers are designed to change automatically to the emergency mode.

The CACs are automatically changed to the emergency mode by a Safety Injection Signal (SIS). This signal will trip the normal rated fan motor in each unit, open the high-capacity service water discharge valve from VHX-1, VHX-2, and VHX-3, and close the high-capacity service water supply valve to VHX-4. The test to verify the service water valves actuate to their correct position upon receipt of an SIS signal is included in the surveillance test performed as part of Specification 3.7.8, 'Service Water System." The safety related fans are normally in operation and only receive an actuation signal through the DBA sequencers following an SIS in conjunction with a loss of offsite power. This actuation is tested by the surveillance which verifies the energizing of loads from the DBA sequencers in Specification 3.8.1, 'AC Sources-Operating.'

Palisades Nuclear Plant B 3.6.6-4 Revised 01/22/2003

Containment Cooling Systems B 3.6.6 BASES APPLICABLE The Containment Spray System and Containment Air Cooler SAFETY ANALYSES System limit the temperature and pressure that could be experienced following either a Loss of Coolant Accident (LOCA) or a Main Steam Line Break'(MSLB). The large break LOCA and MSLB are analyzed using computer codes designed to predict the resultant containment pressure and temperature transients.

The Containment Cooling Systems have been analyzed for three accident cases (Ref. 2). All accidents analyses account for the most limiting single active failure.

1.

A Large Break LOCA,

2.

An MSLB occurring at various power levels with both MSIV bypass valves closed, and

3.

An MSLB occurring at 0% RTP with both MSIV bypass valves open.

The postulated large break LOCA is analyzed, in regard to containment ESF systems, assuming the loss of offsite power and the loss of one ESF bus, which is the Worst case single active failure, resulting in one train of Containment Cooling being rendered inoperable (Ref. 6).

The postulated MSLB Is analyzed, In regard to containment ESF systems, assuming the worst case single active failure.

The MSLB event Is analyzed at various power levels with both MSIV bypass valves closed, and at 0% RTP with both MSIV bypass valves open. Having any MSIV bypass valve open allows additional blowdown from the intact steam generator.

The analysis and evaluation show that under the worst-case scenario, the highest peak containment pressure and the peak containment vapor temperature are within the intent of the design basis. (See the Bases for Specifications 3.6.4, "Containment Pressure," and 3.6.5, "Containment Air Temperature," for a detailed discussion.) The analyses and evaluations considered a range of power levels and equipment configurations as described in Reference 2. The peak containment pressure case is the 0% power MSLB with Initial (pre-accident) conditions of 140°F and 16.2 psia. The peak temperature case Is the 102% power MSLB with initial (pre-accident) conditions of 1400F and 15.7 psia. The analyses also assume a response time delayed initiation in order to provide conservative peak calculated containment pressure and temperature responses.

Palisades Nuclear Plant B 3.6.6-5 Revised 01/22/2003

Containment Cooling Systems B 3.6.6 BASES APPLICABLE The external design pressure of the containment shell is 3 psig. This SAFETY ANALYSES value is approximately 0.5 psig greater than the maximum external (continued) pressure that could be developed if the containment were sealed during a period of low barometric pressure and high temperature and, subsequently, the containment atmosphere was cooled with a concurrent major rise in barometric pressure.

The modeled Containment Cooling System actuation from the containment analysis is based on a response time associated with exceeding the Containment High Pressure setpoint to achieve full flow through the CACs and containment spray nozzles. The spray lines within containment are maintained filled to the 735 ft elevation to provide for rapid spray initiation. The Containment Cooling System total response time of < 60 seconds includes diesel generator startup (for loss of offsite power), loading of equipment, CAC and containment spray pump startup, and spray line filling.

The performance of the Containment Spray System for post accident conditions is given in Reference 3. The performance of the Containment Air Coolers is given in Reference 4.

The Containment Spray System and the Containment Cooling System satisfy Criterion 3 of 10 CFR 50.36(c)(2).

LCO During an MSLB or large break LOCA event, a minimum of one containment cooling train is required to maintain the containment peak pressure and temperature below the design limits (Ref. 2). One train of containment cooling is associated with Diesel Generator 1-1 and includes Containment Spray Pumps P-549 and P-54C, Containment Spray Valve CV-3001 and the associated spray header, and air cooler fan V-4A. This train must be supplemented with 2 service water pumps and 2 containment air coolers if an MSIV bypass valve is open. The other train of containment cooling is associated with Diesel Generator 1-2 and includes Containment Spray Pump P-54A, Containment Spray Valve CV-3002 and the associated spray header, and CACs VHX-1, VHX-2, and VHX-3 and their associated safety related fans, V-IA, V-2A, and V-3A. To ensure that these requirements are met, two trains of containment cooling must be OPERABLE. Therefore, in the event of an accident, the minimum requirements are met, assuming the worst-case single active failure occurs.

Palisades Nuclear Plant B 3.6.6-6 Revised 01/22/2003

Containment Cooling Systems B 3.6.6 BASES LCO (continued)

The Containment Spray System portion of the containment cooling trains includes three spray pumps, two spray headers, nozzles, valves, piping, Instruments, and controls to ensure an OPERABLE flow path capable of taking suction from the SIRWT upon an ESF actuation signal and automatically transferring suction to the containment sump.

The Containment Air Cooler System portion of the containment cooling train which must be OPERABLE includes the three safety related air coolers which each consist of four cooling coil banks, the safety related fan which must be In operation to be OPERABLE, gravity-operated fan discharge dampers, Instruments, and controls to ensure an OPERABLE flow path.

CAC fans V-1A, V-2A, V-3A, and V-4A must be In operation to be considered OPERABLE. These fans only receive a start signal from the DBA sequencer; they are assumed to be In operation, and are not started by either a CHP or an SIS signal.

APPLICABILITY In MODES 1,2, and 3, a large break LOCA event could cause a release of radioactive material to containment and an increase in containment pressure and temperature requiring the operation of the containment spray trains and containment cooling trains.

In MODES 4, 5 and 6, the probability and consequences of these events are reduced due to the pressure and temperature limitations of these MODES. Thus, the Containment Spray and Containment Cooling systems are not required to be OPERABLE In MODES 4, 5 and 6.

ACTIONS A.1 Condition A Is applicable whenever one or more containment cooling trains is Inoperable. Action A.1 requires restoration of both trains to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. The 72-hour Completion Time for Condition A Is based on the assumption that at least 100% of the required post accident containment cooling capability (that assumed in the safety analyses) is available. If less than 100% of the required post containment accident cooling Is available, Condition C must also be entered.

Mechanical system LCOs typically provide a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Completion Time under conditions when a required system can perform its required safety function, but may not be able to do so assuming an additional failure.

When operating in accordance with the Required Actions of an LCO Condition, It Is not necessary to be able to cope with an additional single failure.

B 3.6.6-7 Revised 01/22/2003 Palisades Nuclear Plant

Containment Cooling Systems B 3.6.6 BASES ACTIONS A.1 (continued)

The Containment Cooling systems can provide one hundred percent of the required post accident cooling capability following the occurrence of any single active failure. Therefore, the containment cooling function can be met during conditions when those components which could be deactivated by a single active failure are known to be inoperable. Under that condition, however, the ability to provide the function after the occurrence of an additional failure cannot be guaranteed. Therefore, continued operation with one or more trains inoperable is allowed only for a limited time.

B.1 and B.2 Condition B is applicable when the Required Actions of Condition A cannot be completed within the required Completion Time. Condition A is applicable whenever one or more trains is inoperable. Therefore, when Condition B is applicable, Condition A is also applicable. (If less than 100% of the post accident containment cooling capability is available, Condition C must be entered as well.) Being in Conditions A and B concurrently maintains both Completion Time clocks for instances where equipment repair allows exit from Condition B while the plant is still within the applicable conditions of the LCO.

If the inoperable containment cooling trains cannot be restored to OPERABLE status within the required Completion Time of Condition A, the plant must be brought to a MODE in which the LCO does not apply.

To achieve this status, the plant must be brought to at least MODE 3 within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and to MODE 4 within 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. The allowed Completion Times are reasonable, based on operating experience, to reach the required plant conditions from full power conditions in an orderly manner and without challenging plant systems.

C.A Condition C is applicable with one or more trains inoperable when there is less than 100% of the required post accident containment cooling capability available. Condition A is applicable whenever one or more trains is inoperable. Therefore, when this Condition is applicable, Condition A is also applicable. Being in Conditions A and C concurrently maintains both Completion Time clocks for instances where equipment repair restores 100% of the required post accident containment cooling capability while the LCO is still applicable, allowing exit from Condition C (and LCO 3.0.3).

Palisades Nuclear Plant B 3.6.6-8 Revised 01/22/2003

Containment Cooling Systems B 3.6.6 BASES ACTIONS C.1 (continued)

Several specific cases have been analyzed In the safety analysis to provide operating flexibility for equipment outages and testing. These analyses show that action A.1 can be entered under certain circumstances, because 100% of the post accident cooling capability is maintained. These specific cases are discussed below.

One hundred percent of the required post accident cooling capability can be provided with both MSIV bypass valves closed if either;

1.

Two containment spray pumps, two spray headers, and one CAC fan are OPERABLE, or

2.

One containment spray pump, two spray headers, and three safety related CACs, are OPERABLE (at least two service water pumps must be OPERABLE If CACs are to be relied upon).

One hundred percent of the required post accident cooling capability can be provided for operation with a MSIV bypass valve open or closed if

either,
1.

Two containment spray pumps, two spray headers, and two safety related CACs, are OPERABLE (at least two service water pumps must be OPERABLE if CACs are to be relied upon), or

2.

One containment spray pump, one spray header, and three safety related CACs are OPERABLE (at least three service water pumps must be OPERABLE to provide the necessary service water flow to assure OPERABILITY of the CACs).

If the Containment Spray side (tube side) of SDC Heat Exchanger E-60B Is out of service, 100% of the required post accident cooling capability can be provided, if other equipment outages are limited. One hundred percent of the post accident cooling can be provided with the Containment Spray side of SDC Heat Exchanger E-60B out of service If the following equipment is OPERABLE: three safety related Containment Air Coolers, two Containment Spray Pumps, two spray headers, CCW pumps P-52A and P-52B, two SWS pumps, and both CCW Heat Exchangers, and if

1.

One CCW Containment Isolation Valve, CV-0910, CV-091 1, or CV-0940, is OPERABLE, and

2.

Two CCW Isolation valves for the non-safety related loads outside the containment, CV-0944A and CV-0944 (or CV-0977B), are OPERABLE.

Palisades Nuclear Plant B 3.6.6-9 Revised 01/22/2003

Containment Cooling Systems B 3.6.6 BASES ACTIONS C.1 (continued)

With less than 100% of the required post accident containment cooling capability available, the plant is in a condition outside the assumptions of the safety analyses. Therefore, LCO 3.0.3 must be entered immediately.

SURVEILLANCE SR 3.6.6.1 REQUIREMENTS Verifying the correct alignment for manual, power operated, and automatic valves, excluding check valves, in the Containment Spray System provides assurance that the proper flow path exists for Containment Spray System operation. This SR also does not apply to valves that are locked, sealed, or otherwise secured in position since these were verified to be in the correct positions prior to being secured.

This SR also does not apply to valves that cannot be inadvertently misaligned, such as check valves. This SR does not require any testing or valve manipulation. Rather, it involves verification, through a system walkdown, that those valves outside containment and capable of potentially being mispositioned, are in the correct position.

SR 3.6.6.2 Operating each safety related Containment Air Cooler fan unit for

> 15 minutes ensures that all trains are OPERABLE and are functioning properly. The 31-day Frequency was developed considering the known reliability of the fan units, the two train redundancy available, and the low probability of a significant degradation of the containment cooling train occurring between surveillances.

SR 3.6.6.3 Verifying the containment spray header is full of water to the 735 ft elevation minimizes the time required to fill the header. This ensures that spray flow will be admitted to the containment atmosphere within the time frame assumed in the containment analysis. The 31-day Frequency is based on the static nature of the fill header and the low probability of a significant degradation of the water level in the piping occurring between surveillances.

SR 3.6.6.4 Verifying a total service water flow rate of > 4800 gpm to CACs VHX-1, VHX-2, and VHX-3, when aligned for accident conditions, provides assurance the design flow rate assumed in the safety analyses will be achieved (Ref. 8). Also considered in selecting this Frequency were the Palisades Nuclear Plant B 3.6.6-10 Revised 01/22/2003

Containment Cooling Systems B 3.6.6 BASES SURVEILLANCE SR 3.6.6.4 (continued)

REQUIREMENTS known reliability of the cooling water system, the two train redundancy, and the low probability of a significant degradation of flow occurring between surveillances.

SR 3.6.6.5 Verifying that each containment spray pump's developed head at the flow test point Is greater than or equal to the required developed head ensures that spray pump performance has not degraded during the cycle. Flow and differential pressure are normal tests of centrifugal pump performance required by Section XI of the ASME Code (Ref. 5).

Since the containment spray pumps cannot be tested with flow through the spray headers, they are tested on recirculation flow. This test confirms one point on the pump design curve and Is indicative of overall performance. Such inservice inspections confirm component OPERABILITY, trend performance, and detect incipient failures by indicating abnormal performance. The Frequency of this SR is In accordance with the Inservice Testing Program.

SR 3.6.6.6 and SR 3.6.6.7 SR 3.6.6.6 verifies each automatic containment spray valve actuates to its correct position upon receipt of an actual or simulated actuation signal.

This Surveillance is not required for valves that are locked, sealed, or otherwise secured in the required position under administrative controls.

SR 3.6.6.7 verifies each containment spray pump starts automatically on an actual or simulated actuation signal. The 18-month Frequency is based on the need to perform these Surveillances under the conditions that apply during a plant outage and the potential for an unplanned transient if the Surveillances were performed with the reactor at power.

Operating experience has shown that these components usually pass the Surveillances when performed at the 18 month Frequency. Therefore, the Frequency was concluded to be acceptable from a reliability standpoint.

Where the surveillance of containment sump isolation valves is also required by SR 3.5.2.5, a single surveillance may be used to satisfy both requirements.

SR 3.6.6.8 This SR verifies each containment cooling fan actuates upon receipt of an actual or simulated actuation signal. The 18-month Frequency is Palisades Nuclear Plant Revised 01/22/2003 B 3.6.6-11

Containment Cooling Systems B 3.6.6 BASES SURVEILLANCE SR 3.6.6.8 (continued)

REQUIREMENTS based on engineering judgement and has been shown to be acceptable through operating experience. See SR 3.6.6.6 and SR 3.6.6.7, above, for further discussion of the basis for the 18 month Frequency.

SR 3.6.6.9 With the containment spray inlet valves closed and the spray header drained of any solution, low pressure air or smoke can be blown through test connections. Performance of this SR demonstrates that each spray nozzle is unobstructed and provides assurance that spray coverage of the containment during an accident is not degraded. Due to the passive design of the nozzle, a test at 10-year intervals is considered adequate to detect obstruction of the spray nozzles.

REFERENCES

1.

FSAR, Section 5.1

2.

FSAR, Section 14.18

3.

FSAR, Sections 6.2

4.

FSAR, Section 6.3

5.

ASME, Boiler and Pressure Vessel Code,Section XI

6.

FSAR, Table 14.18.1-3

7.

FSAR, Table 14.18.2-1

8.

FSAR, Table 9-1

9.

EA-MSLB-2001-01 Rev. 1, Containment Response to a MSLB Using CONTEMPT-LT/28, January 2002.

10.

EA-LOCA-2001-01 Rev. 1, Containment Response to a LOCA Using CONTEMPT-LT/28, January 2002.

Palisades Nuclear Plant B 3.6.6-12 Revised 01/22/2003