Thomas Alexion-ANO-1 Actions for TMI SG Tube Sever Conce rn i-'acie 1 

From:

To:

Date:

Subject:

"BENNETT, STEVE A" <SBENNE2@entergy.com>

"T'om Alexion'" <twa@nrc.gov>

9/30/02 10:14AM ANO-1 Actions for TMI SG Tube Sever Concern

Tom, See attached notes for Call tomorrow 4 iý'mas Alexion - ANO-1 Actions for TMI SG Tube Sever Concern Paae 1

Entergy Actions for TMI Tube Sever Concerns for ANO-1 ANO-1 Scope of Potential Concern

"* ANO-1 did not install Westinghouse or B &W 1-600 mechanical rolled plugs during the 1980's. Instead, ANO-1 used either welded, ribbed or explosive plugs

"* The first rolled plug was installed in the ANO-1 OTSG's in 1992 which was Alloy-690 material.

"* Review of past outage eddy current data revealed no wear indications have ever been detected at the tubesheet face

"* ANO worked with Framatome, based on the criteria presented at the Feb. 1.

2002 meeting with the NRC, to determine the susceptible plugged tube list

"* List included:

UTS plugs removed and replaced at a later date, UTS plugs installed could have leaked and another type of plug was placed in the tube to seal the water in the tube, 1-690 plugs installed was rerolled/retorqued at a later date to possibly seal in water

"* A total of 12 tubes were determined to be susceptible to possible tube swelling Entergy Planned Actions During 1R17 Outage

"* ANO has no plans to remove any plugs during 1 R1 7 All susceptible tubes have been evaluated and a total of 63 neighboring tubes will be plugged. 4 stabilizers will be installed in the upper span due to the industry operating experience events

"* Some tubes will be plugged as an extra "buffer zone" downstream of plugged tubes

"* Eddy Current Analysis will be performed on all tubes surrounding susceptible tubes to ensure no wear is seen on tubes prior to plugging/stabilizing

! C:\\WINDOWS\\TEMP\\GW}0000l.TMP Page 1 Mail Envelope Properties (3D9850F3.BC3 : 10: 15299)

Subject:

Creation Date:

From:

ANO-1 Actions for TMI SG Tube Sever Concern 9/30/02 9:27AM "BENNETT, STEVE A" <SBENNE2@entergy.com>

Created By:

SBENNE2@enterev.com Recipients nrc.gov owf4_po.OWFNDO TWA (Thomas Alexion)

Post Office owf4_po.OWFNDO Files MESSAGE TMI Tube Sever Notes.doc Mime.822 Options Expiration Date:

Priority:

Reply Requested:

Return Notification:

Concealed

Subject:

Security:

Route nrc.gov Date & Time 09/30/02 09:27AM Size 45 20480 29508 None Standard No None No Standard

[c.\\WINDOVWS\\TEM P\\GW}O00091.TM P Page 11