MONTHYEARBSEP 05-0046, March 2005 Monthly Operating Report for Brunswick Steam Electric Plant, Unit Nos. 1 and 22005-04-13013 April 2005 March 2005 Monthly Operating Report for Brunswick Steam Electric Plant, Unit Nos. 1 and 2 BSEP 05-0039, February 2005 Monthly Operating Reports for Brunswick Steam Electric Plant Units 1 and 22005-03-14014 March 2005 February 2005 Monthly Operating Reports for Brunswick Steam Electric Plant Units 1 and 2 BSEP 05-0014, January 2005 Monthly Operating Report for Brunswick Steam Electric Plant Units 1 and 22005-02-0909 February 2005 January 2005 Monthly Operating Report for Brunswick Steam Electric Plant Units 1 and 2 BSEP 04-0167, December 2004 Monthly Operating Reports for Brunswick Steam Electric Plant, Unit Nos. 1 and 22005-01-10010 January 2005 December 2004 Monthly Operating Reports for Brunswick Steam Electric Plant, Unit Nos. 1 and 2 BSEP 04-0154, November 2004 Monthly Operating Report for Brunswick Steam Electric Plant2004-12-10010 December 2004 November 2004 Monthly Operating Report for Brunswick Steam Electric Plant BSEP 04-0147, October 2004 Monthly Operating Reports for Brunswick Units 1 and 22004-11-10010 November 2004 October 2004 Monthly Operating Reports for Brunswick Units 1 and 2 BSEP 04-0139, September 2004 Monthly Operating Report for Brunswick, Units 1 and 22004-10-13013 October 2004 September 2004 Monthly Operating Report for Brunswick, Units 1 and 2 ML0427404362004-09-15015 September 2004 August 2004 Monthly Operating Report for Brunswick Steam Electric Plant, Unit Nos. 1 and 2 BSEP 04-0107, July 2004 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 & 22004-08-11011 August 2004 July 2004 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 & 2 BSEP 04-0086, June 2004 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 and 22004-07-13013 July 2004 June 2004 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 and 2 BSEP 04-0052, April 2004 Monthly Operating Report for Brunswick Steam Electric Plant, Unit Nos. 1 and 22004-05-13013 May 2004 April 2004 Monthly Operating Report for Brunswick Steam Electric Plant, Unit Nos. 1 and 2 BSEP 04-0045, March 2004 Monthly Operating Report for Brunswick, Units 1 & 22004-04-12012 April 2004 March 2004 Monthly Operating Report for Brunswick, Units 1 & 2 BSEP 04-0041, February 2004 Monthly Operating Report for Brunswick, Units 1 and 22004-03-10010 March 2004 February 2004 Monthly Operating Report for Brunswick, Units 1 and 2 BSEP 04-0014, January 2004 Monthly Operating Report for Brunswick, Units 1and 22004-02-10010 February 2004 January 2004 Monthly Operating Report for Brunswick, Units 1and 2 BSEP 03-0172, December 2003 Monthly Operating Report for Brunswick, Units 1 and 22004-01-13013 January 2004 December 2003 Monthly Operating Report for Brunswick, Units 1 and 2 BSEP 03-0161, November 2003 Monthly Operating Report for Brunswick, Units 1 and 22003-12-11011 December 2003 November 2003 Monthly Operating Report for Brunswick, Units 1 and 2 BSEP 03-0153, October 2003 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 and 22003-11-12012 November 2003 October 2003 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 and 2 BSEP 03-0142, September 2003 Monthly Operating Report from Brunswick, Units 1 & 22003-10-14014 October 2003 September 2003 Monthly Operating Report from Brunswick, Units 1 & 2 BSEP 03-0127, August 2003 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 and 22003-09-11011 September 2003 August 2003 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 and 2 BSEP 03-0124, July 2003 Monthly Operating Reports for Brunswick Steam Electric Plant2003-08-14014 August 2003 July 2003 Monthly Operating Reports for Brunswick Steam Electric Plant BSEP 03-0108, June 2003 Monthly Operating Report for Brunswick, Units 1 & 22003-07-14014 July 2003 June 2003 Monthly Operating Report for Brunswick, Units 1 & 2 BSEP 03-0098, May 2003 Monthly Operating Report for Brunswick Units 1 and 22003-06-12012 June 2003 May 2003 Monthly Operating Report for Brunswick Units 1 and 2 BSEP 03-0073, April 2003 Monthly Operating Report for Brunswick Steam Electric Plant, Unit Nos. 1 & 22003-05-0808 May 2003 April 2003 Monthly Operating Report for Brunswick Steam Electric Plant, Unit Nos. 1 & 2 BSEP 03-0056, March 2003 Monthly Operating Report for Brunswick Units 1 & 22003-04-0909 April 2003 March 2003 Monthly Operating Report for Brunswick Units 1 & 2 BSEP 03-0043, February 2003 Monthly Operating Report for Brunswick Steam Electric Plant2003-03-0606 March 2003 February 2003 Monthly Operating Report for Brunswick Steam Electric Plant BSEP 03-0024, January 2003 Monthly Operating Report for Brunswick Units 1 & 22003-02-11011 February 2003 January 2003 Monthly Operating Report for Brunswick Units 1 & 2 BSEP 02-0204, December 2002 Monthly Operating Report for Brunswick Units 1 & 22003-01-13013 January 2003 December 2002 Monthly Operating Report for Brunswick Units 1 & 2 BSEP 02-0192, November 2002 Monthly Operating Report for Brunswick Units 1 & 22002-12-10010 December 2002 November 2002 Monthly Operating Report for Brunswick Units 1 & 2 BSEP 02-0181, October 2002 Monthly Operating Report for Brunswick Units 1 & 22002-11-14014 November 2002 October 2002 Monthly Operating Report for Brunswick Units 1 & 2 BSEP 02-0167, September 2002 Monthly Operating Report for Brunswick Units 1 & 22002-10-11011 October 2002 September 2002 Monthly Operating Report for Brunswick Units 1 & 2 BSEP-02-0155, August 2002 Monthly Operating Report for Brunswick Steam Electric Plant, Unit Nos.1 & 22002-09-10010 September 2002 August 2002 Monthly Operating Report for Brunswick Steam Electric Plant, Unit Nos.1 & 2 BSEP 02-0138, July 2002 Monthly Operating Report for Brunswick Units 1 & 22002-08-0707 August 2002 July 2002 Monthly Operating Report for Brunswick Units 1 & 2 BSEP 02-0125, June 2002 Monthly Operating Report for Brunswick Units 1 & 22002-07-12012 July 2002 June 2002 Monthly Operating Report for Brunswick Units 1 & 2 BSEP 02-0112, May 2002 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 & 22002-06-10010 June 2002 May 2002 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 & 2 BSEP 02-0096, April 2002 Monthly Operating Report for Brunswick, Units 1 & 22002-05-0909 May 2002 April 2002 Monthly Operating Report for Brunswick, Units 1 & 2 BSEP 02-0074, March 2002 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 and 22002-04-11011 April 2002 March 2002 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 and 2 BSEP 02-0058, February 2002 Monthly Operating Report for Brunswick, Units 1 & 22002-03-11011 March 2002 February 2002 Monthly Operating Report for Brunswick, Units 1 & 2 BSEP 02-0036, January 2002 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 & 22002-02-11011 February 2002 January 2002 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 & 2 BSEP 02-0001, December 2001 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 and 22002-01-10010 January 2002 December 2001 Monthly Operating Report for Brunswick Steam Electric Plant, Units 1 and 2 2005-04-13
[Table view] |
Text
CP&L AProgress Energy Company OCT 112002 SERIAL: BSEP 02-0167 U.S. Nuclear Regulatory Commission NekA : Document Control Desk Washington, DC 20555-0001 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NOS. I AND 2 DOCKET NOS. 50-325 AND 50-324/LICENSE NOS. DPR-71 AND DPR-62 SEPTEMBER 2002 MONTHLY OPERATING REPORTS Ladies and Gentlemen:
In accordance with Technical Specification (TS) 5.6.4 for the Brunswick Steam Electric Plant (BSEP), Unit Nos. 1 and 2, Carolina Power & Light (CP&L) Company is submitting the enclosed Monthly Operating Reports for September 2002. These reports are being submitted to the NRC by the 15th day of the month following the calendar month covered by the reports, as specified in TS 5.6.4.
There are no regulatory commitments being made in this submittal. Please refer questions regarding this submittal to Mr. Leonard R. Beller, Supervisor - Licensing/Regulatory Programs, at (910) 457-2073.
Sincerely, Edward T. O'Neil Manager - Regulatory Affairs Brunswick Steam Electric Plant CRE/cre
Enclosures:
- 1. BSEP, Unit No. 1 Monthly Operating Report September 2002
- 2. BSEP, Unit No. 2 Monthly Operating Report September 2002 Brunswick Nuclear Plant P 0 Box 10429 Southport, NC 28461
Document Control Desk BSEP 02-0167 / Page 2 cc (with enclosures):
U. S. Nuclear Regulatory Commission, Region II ATTN: Mr. Luis A. Reyes, Regional Administrator Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW, Suite 23T85 Atlanta, GA 30303-8931 U. S. Nuclear Regulatory Commission ATTN: Mr. Theodore A. Easlick, NRC Senior Resident Inspector 8470 River Road Southport, NC 28461-8869 U. S. Nuclear Regulatory Commission ATTN: Ms. Brenda L. Mozafari (Mail Stop OWFN 8G9) (Electronic Copy Only) 11555 Rockville Pike Rockville, MD 20852-2738 Ms. Jo A. Sanford Chair - North Carolina Utilities Commission P.O. Box 29510 Raleigh, NC 27626-0510 ElectriCities of N. C., Inc.
ATTN: Mr. Roy Donehower P. O. Box 29513 Raleigh, NC 27626-0513
BSEP 02-0167 Enclosure 1 Page 1 of 2 APPENDIX A OPERATING DATA REPORT DOCKET NO. 50-325 UNIT NAME Brunswick Steam Electric Plant, Unit No. 1 DATE October 7, 2002 COMPLETED BY Kester M. Thompson TELEPHONE (910) 457-2754 REPORTING PERIOD September 2002 (Month/Year)
YEAR TO MONTH DATE CUMULATIVE
- 1. Design Electrical Rating: 895 N/A N/A (MWe-Net) - Note 1
- 2. Maximum Dependable Capacity: 820 N/A N/A (MWe-Net)
- 3. Number of Hours the Reactor Was Critical: 551.1 5,729.7 158,705.7
- 4. Number of Hours the Generator Was On Line: 533.3 5,667.4 154,244.1
- 5. Unit Reserve Shutdown Hours: 0 0 0
- 6. Net Electrical Energy (MWH): 442,198 4,725,726 114,075,822 Note 1: License Amendment 222 for Unit 1 approved Extended Power Uprate (EPU). This amendment was implemented on June 1, 2002. As a result, the present value for Design Electrical Rating (i.e., net megawatts electric (MWe)) has been revised from 867 MWe to 895 MWe to reflect current equipment limitations and testing activities associated with the first phase of EPU implementation. The Design Electrical Rating value is subject to further revision as EPU testing and implementation activities continue.
BSEP 02-0167 Enclosure I Page 2 of 2 APPENDIX B UNIT SHUTDOWNS DOCKET NO. 50-325 UNIT NAME Brunswick Steam Electric Plant, Unit No. 1 DATE October 7, 2002 COMPLETED BY Kester M. Thompson TELEPHONE (910) 457-2754 REPORTING PERIOD September 2002 (Month/Year)
TYPE METHOD OF F: FORCED DURATION SHUTTING CAUSE/CORRECTIVE ACTIONS NO. DATE S SCHEDULED (HOURS) REASON (1) DOWN (2) COMMENTS 2 020921 S 186.1 A (see comments) 2 Unit No. 1 was shut down to replace leaking fuel bundles.
3 020930 F 0.6 A (see comments) 5 (see comments) Unit No. 1 turbine/generator was taken off-line (while the reactor remained critical) to repair a steam leak in the main steam system.
SUMMARY
- Unit No. I was shut down on September 21, 2002, for approximately eight days, to perform a scheduled fuel bundle replacement outage. On September 30, 2002, the turbine/generator was taken off-line to repair a steam leak in the main steam system. Repairs were completed and the generator synchronized to the grid in the early morning of October 1,2002.
(1) Reason (2) Method A - Equipment Failure (Explain) E - Operator Training/License Examination I - Manual 5 - Other (Explain)
B - Maintenance or Test F - Administrative 2 - Manual Trip/Scram C - Refueling G - Operational Error (Explain) 3 - Automatic Trip/Scram D - Regulatory Restriction If - Other (Explain) 4 - Continuation
t.
BSEP 02-0167 Enclosure 2 Page 1 of 2 APPENDIX A OPERATING DATA REPORT DOCKET NO. 50-324 UNIT NAME Brunswick Steam Electric Plant, Unit No. 2 DATE October 7, 2002 COMPLETED BY Kester M. Thompson TELEPHONE (910) 457-2754 REPORTING PERIOD September 2002 (Month/Year)
YEAR TO MONTH DATE CUMULATIVE
- 1. Design Electrical Rating: 867 N/A N/A (MWe-Net)
- 2. Maximum Dependable Capacity: 811 N/A N/A (MWe-Net)
- 3. Number of Hours the Reactor Was Critical: 720 6,416.9 168,086.2
- 4. Number of Hours the Generator Was On Line: 720 6,400.5 162,103.7
- 5. Unit Reserve Shutdown Hours: 0 0 0
- 6. Net Electrical Energy (MWH): 590,614 5,246,659 115,193,452
BSEP 02-0167 'V Enclosure 2 Page 2 of 2 APPENDIX B UNIT SHUTDOWNS DOCKET NO. 50-324 UNIT NAME Brunswick Steam Electric Plant, Unit No. 2 DATE October 7, 2002 COMPLETED BY Kester M. Thompson TELEPHONE (910) 457-2754 REPORTING PERIOD September 2002 (Month/Year)
TYPE METHOD OF F: FORCED DURATION SHUTTING CAUSE/CORRECTIVE ACTIONS NO. DATE S: SCHEDULED (HOURS) REASON (1) DOWN (2) COMMENTS Unit No. 2 was not required to shut down during the month of September 2002.
SUMMARY
(I) Reason (2) Method A - Equipment Failure (Explain) I - Manual B - Maintenance or Test 2 - Manual Trip/Scram C - Refueling 3 - Automatic Trip/Scram D - Regulatory Restriction 4 - Continuation E - Operator Training/License Examination 5 - Other (Explain)
F - Administrative
- - Operational Error (Explain)
H - Other (Explain)