L-2002-070 Attachment 2 Page 96 of 230 Appendix A Cable Tray Fuel Load Calculations
L-2002-070 Attachment 2 Page 97 of 230 Heat Release Rate Cables Combustible per unit length of Reference Point Tray ID Width of Fuel Load per cable tray (kW/m)
Meter (kJ/m) (400 kW/m 2 q)
MIN0 0.502 74388.2 90.36 0.075 16143.3 13.50 235C100 (with0 C101 0.283 38195.6 50.94
,1101 0.367 42678.3 66.06 TOTAL 1.227 171405.5 220.86 M100 0.502 74388.2 90.36 2305 C100 0.075 16143.3 13.50 (without L101) C101 0.283 38195.6 50.94 TOTAL 0.860 128727.2 154.80 M120 0.610 89177.6 109.80 2307/2369 C120 0.294 36767.3 52.92 (with L120) L120 0.388 55180.6 69.84 TOTAL 1.292 181125.5 232.56 2 M120 0.610 89177.6 109.80 2307/2369 C120 0.294 36767.3 52.92 (without L120) TOTAL 0.904 125944.9 162.72 M100 0.502 74388.2 90.36 2320 C 101 0.283 38579.3 50.94 TOTAL 0.785 112967.5 141.30 M100 0.502 74388.2 90.36 2393 C101 0.243 33795.2 43.74 TOTAL 0.745 108183.4 134.10 M100 0.376 55791.2 67.68 2306 C101 0.148 20097.5 26.64 TOTAL 0.524 75888.7 94.32 M120 0.502 74388.2 90.36 2308 C 120 0.113 16752.6 20.34 TOTAL 0.615 91140.8 110.70 M102 0.037 6641.2 6.66 2245 C103 0.516 66073.0 92.88 TOTAL 0.553 72714.2 99.54 M102 0.016 2571.8 2.88 2247 C 103 0.249 39607.3 44.82 TOTAL 0.265 42179.1 47.70 M127 0.110 17057.2 19.80 2221/2225 C121 0.610 118745.1 109.80 TOTAL 0.720 135802.3 129.60 M127 0.110 17057.2 19.80 2223 C121 0.610 115916.7 109.80 TOTAL 0.720 132973.9 129.60 M127 0.016 2167.3 2.88 2227 C121 0.396 63357.2 71.28 TOTAL 0.412 65524.5 74.16
L-2002-070 Attachment 2 Page 98 of 230 Cable Tray ID C100-2305 Cable Type ,#1 2 XLPN (XLPPP)
Outside Diameter (inches) 74 0.018796 meters Insulation Material 3
Outer Jacket Thickness (mils) i 0.001524 meters Insulation Density (kg/m )
Insulation Jacket Thickness (mils) i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) *ii 0.00076 meters Jacket Material 3
Num. Conds. ...... 7. Jacket Density (kg/m )
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.009398 m 2
Total Cable Area (A3) 0.00027747 i 2 0.00011585 M Jacket Area Insulation Area 4.716E-05 m2 3
Total Volume of Jacket (M ) 3 3.53E-05 Mass of Jacket per meter (kg/m) 0.1670
) Mass of Insulation per meter (kg/m) 0.0436 Total Volume of Insulation (M 1.44E-05 Volume (ms) 4.97E-05 Total Combustible Mass per meter (kg/m) 0.2106 Total Combustible 0.1 Jacket heat of combustion energy per meter (kJ/m) 2998.3 Total Mass of Jacket (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1037.6 Total Mass of Insulation (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4035.8 Total Combustible Mass (kg)
Combustible Fuel Load per meter (kJ/m) 16143.3 Number of Cables i I Total Width of Cables 0.075
L-2002-070 Attachment 2 Page 99 of 230 Cable Tray ID C101-2305 Cable Type 2/C#12 XLPPP Outside Diameter (inches) . 5 0.0127 meters Insulation Material 3 Outer Jacket Thickness (mils) : 0.001143 meters Insulation Density (kg/Mr )
Insulation Jacket Thickness (mils) i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 3i 0.00076 meters Jacket Material 2 2 Jacket Density (kg/M )
3 Num. Conds.
Diam. Cond. (inches) . 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ................. ......
0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.00012668 M2 5.0973E-05 M Jacket Area Insulation Area 1.3474E-05 m2 Total Volume of Jacket (Mi) 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m3) 4.11 E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (Mi) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 6462.5 Number of Cables .....
Total Width of Cables 0.051
L-2002-070 Attachment 2 Page 100 of 230 Cable Tray ID C101-2305 Cable Type 2/C#12 XLPN (XLPPP)
Outside Diameter (inches) i 0.0127 meters Insulation Material 3 Outer Jacket Thickness (mils) 4..................
0.001143 meters Insulation Density (kg/m )
Insulation Jacket Thickness (mils) 15 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ..... ....... 0.00076 meters Jacket Material 3 Num. Conds. Jacket Density (kg/im )
Diam. Cond. (inches) i8O& 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ...... ........ 0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.00012668 m2 2
Jacket Area 5.0973E-05 m Insulation Area 1.3474E-05 m2 3
Total Volume of Jacket (M ) 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m3) 4.11 E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (m3) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 6462.5 Number of Cables .
Total Width of Cables 0.051
L-2002-070 Attachment 2 Page 101 of 230 Cable Tray ID CIOI-2305 Cable Type ,#16 XLPPP Outside Diameter (inches) ........... 0.013208 meters Insulation Material 3
Outer Jacket Thickness (mils) ............. 0.001143 meters Insulation Density (kg/im )
Insulation Jacket Thickness (mils) S0.000381 meters Insulation Heat of Combustion (kJ/kg) ....
Conduct. Insul. Thickness (mils) *5 0.00064 meters Jacket Material 3 ... . . .......
Num. Conds. A5O& - 0.00129 meters Jacket Density (kg/M )
Diam. Cond. (inches) Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 4 0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.00013701 m'2 Jacket Area 6.0927E-05 M Insulation Area 1.9204E-05 M2 3
Total Volume of Jacket (M )
3 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (M ) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m3) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 3998.6 Number of Cables yy Total Width of Cables 0.026
L-2002-070 Attachment 2 Page 102 of 230 Cable Tray ID CIOI-2305 Cable Type 2/C# 16 XLPPP Outside Diameter (inches) .... 0.010414 meters
.......... Insulation Material 3 Outer Jacket Thickness (mils) 4 i 0.001143 meters Insulation Density (kg/m )
Insulation Jacket Thickness (mils) 1 : 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ........ 0.00064 meters 5........ Jacket Material 3 Num. Conds. 2 2 Jacket Density (kg/m )
Diam. Cond. (inches) :::: :: 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) i 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.5178E-05 M 4.0332E-05 M2 Jacket Area Insulation Area 7.6817E-06 M 3
Total Volume of Jacket (M ) 3 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (M ) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (Mi) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 6064.0 Number of Cables :.....5........
Total Width of Cables 0.052
L-2002-070 Attachment 2 Page 103 of 230 Cable Tray ID C101-2305 2/*'*I 6 XLPN (XLPPP)
Cable Type Outside Diameter (inches) 0.010414 meters Insulation Material 3 Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/M )
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material 3
Num. Conds. 2 Jacket Density (kg/m )
Diam. Cond. (inches) 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.005207 m2 Total Cable Area (A3) 8.5178E-05 m Jacket Area 4.0332E-05 m2 Insulation Area 7.6817E-06 M 3
Total Volume of Jacket (M ) 3 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582
) 0.0071 Total Volume of Insulation (M 3 2.34E-06 Mass of Insulation per meter (kg/m)
Combustible Volume (M ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 1212.8 Number of Cables ........
Total Width of Cables 0.010 Total Width (m) 0.283 Total Energy (kJ/m) 38195.6
L-2002-070 Attachment 2 Page 104 of 230 Cable Tray ID M120-230712369 Cable Type -1 I/ #4/0l XLPP Outside Diameter (inches) 0.020904 meters Insulation Material i........ ...
3 Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m ) ......................
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ:kg :: :::
Jacket Material 60.Wf (~m F Wi i
- ipiis Conduct. Insul. Thickness (mils) 0.00140 meters 1 3 Num. Conds. Jacket Density (kg/r ) .. 441...........
Diam. Cond. (inches) 0.011684 meters Jacket Heat of Combustion (kJ/kg) 1795ti Cable Length (feet) 0.304878 meters Outside Radius 0.0104521 m Total Cable Area (A3) 0.00034321 m2 Jacket Area 7.0959E-05 m2 2
Insulation Area 5.741 E-05 M 3
Total Volume of Jacket (m ) 3 2.16E-05 Mass of Jacket per meter (kg/m) 0.1023 Total Volume of Insulation (m ) 1.75E-05 Mass of Insulation per meter (kg/m) 0.0531 3
Total Combustible Volume (m ) 3.91 E-05 Total Combustible Mass per meter (kg/m) 0.1554 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1836.4 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1263.1 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 3099.5 Combustible Fuel Load per meter (kJ/m) 74388.2 Number of Cables ..........
Total Width of Cables 0.502
L-2002-070 Attachment 2 Page 105 of 230 Cable Tray ID M120-230712369 Cable Type 5I*#l 2 MCCC Outside Diameter (inches) 0.016256 meters Insulation Material 3 Outer Jacket Thickness (mils) 0.001651 meters Insulation Density (kglm )
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/k Conduct. Insul. Thickness (mils) 0.00102 meters Jacket Material 3 Num. Conds. 1 Jacket Density (kg/m )
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.008128 m Total Cable Area (A3) 0.00020755 m2 Jacket Area 7.5753E-05 M Insulation Area 9.7936E-06 m2 3
Total Volume of Jacket (m ) 3 2.31 E-05 Mass of Jacket per meter (kg/m) 0.1092 Volume of Insulation (M ) 2.99E-06 Mass of Insulation per meter (kg/m) 0.0091 Total Total Combustible Volume (m3) 2.61 E-05 Total Combustible Mass per meter (kg/m) 0.1183 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1960.5 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 215.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2176.0 Combustible Fuel Load per meter (kJ/m) 4351.9 Number of Cables ..2..........
Total Width of Cables 0.033
L-2002-070 Attachment 2 Page 106 of 230 Cable Tray ID M120-230712369 Cable Type 3/C#12 XLPN (XLPP)
Outside Diameter (inches) X.. 0.015723
............ meters Insulation Material 3 Outer Jacket Thickness (mils) 0.001143
.45........ meters Insulation Density (kgt/M)
Insulation Jacket Thickness (mils) . 0.000381
. .*..... meters Insulation Heat of Combustion (kJ/k Conduct. Insul. Thickness (mils) .3 : 0.00076 meters Jacket Material Num. Conds. 3 Jacket Density (kg/M3)
Diam. Cond. (inches) 0 080&: 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 1i 0.304878 meters Outside Radius 0.0078613 m Total Cable Area (A3) 0.00019415 m' Jacket Area 6.6563E-05 m22 Insulation Area 2.0212E-05 m Total Volume of Jacket (m3) 3 2.03E-05 Mass of Jacket per meter (kglm) 0.0960 Total Volume of Insulation (m ) 6.16E-06 Mass of Insulation per meter (kg/m) 0.0187 Total Combustible Volume (M) 2.65E-05 Total Combustible Mass per meter (kg/m) 0.1147 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1722.7 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 444.7 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJtm) 2167.3 Number of Cables ......
...... Combustible Fuel Load per meter (kJ/m) 4334.7 Total Width of Cables 0.031
L-2002-070 Attachment 2 Page 107 of 230 Cable Tray ID M120-230712369 Cable Type 3-1/C#2 XLPP Outside Diameter (inches) .i8 i 0.014783 meters Insulation Material Outer Jacket Thickness (mils) 45 : 0.001143 meters Insulation Density (kg/m 3 )
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/k Conduct. Insul. Thickness (mils) : 0.00140 meters Jacket Material Num. Conds. ......
....... Jacket Density (kg/m 3 )
Diam. Cond. (inches) 0.006543 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.0073914 m 2
Total Cable Area (A3) 0.00017163 m Jacket Area 4.8978E-05 m2 Insulation Area 3.4847E-05 m2 3
Total Volume of Jacket (m ) 3 1.49E-05 Mass of Jacket per meter (kg/m) 0.0706 Total Volume of Insulation (m ) 1.06E-05 Mass of Insulation per meter (kg/m) 0.0322 3
Total Combustible Volume (m ) 2.56E-05 Total Combustible Mass per meter (kg/m) 0.1028 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1267.6 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 766.7 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2034.2 Combustible Fuel Load per meter (kJ/m) 6102.7 Number of Cables ...........
Total Width of Cables 0.044 Total Width (m): 0.610 Total Energy (kJIm): 89177.6
L-2002-070 Attachment 2 Page 108 of 230 Cable Tray ID C120-2307 Cable Type XLPN (XLPPP)
Outside Diameter (inches) 0.018796 meters Insulation Material Outer Jacket Thickness (mils) 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kl Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material 3
Num. Conds. 7 Jacket Density (kg/m )
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.009398 m Total Cable Area (A3) 0.00027747 m2 Jacket Area 0.00011585 m2 Insulation Area 4.716E-05 m2 3
Total Volume of Jacket (m ) 3.53E-05 Mass of Jacket per meter (kg/m) 0.1670 Total Volume of Insulation (m3) 1.44E-05 Mass of Insulation per meter (kg/m) 0.0436 Total Combustible Volume (m3) 4.97E-05 Total Combustible Mass per meter (kg/m) 0.2106 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJIm) 2998.3 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1037.6 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4035.8 Combustible Fuel Load per meter (kJ/m) 8071.7 Number of Cables comma .
Total Width of Cables 0.038
L-2002-070 Attachment 2 Page 109 of 230 Cable Tray ID C120-2307 Cable Type *#12 MCCC Outside Diameter (inches) *64
... 0.016256 meters Insulation Material E rbdn4 ...........
- iiiiii5iiiiii 0.001651 meters Insulation Density (kg/m 3) 9244 Outer Jacket Thickness (mils)
- iii~iii!
0 meters Insulation Heat of Combustion (kJ/kg 2$& ::
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils) I=============== 0.00102 meters Jacket Material i (Fauitro fIyI - k propertie iPi1C ie Num. Conds. ......... 0.002052 meters Jacket Density (kg/mi3) ..............
Diam. Cond. (inches) ............ 304878 meters Jacket Heat of Combustion (kJ/kg) .7950 Cable Length (feet)
Outside Radius 0.008128 m Total Cable Area (A3) 0.00020755 m2 Jacket Area 7.5753E-05 m2 Insulation Area 4.8968E-05 m2 Total Volume of Jacket (mi3 ) 3 2.31 E-05 Mass of Jacket per meter (kg/m) 0.1092 Total Volume of Insulation (M ) 1.49E-05 Mass of Insulation per meter (kg/m) 0.0453 Total Combustible Volume (m3) 3.8E-05 Total Combustible Mass per meter (kg/m) 0.1545 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1960.5 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1077.3 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 3037.8 Combustible Fuel Load per meter (kJ/m) 12151.4 Number of Cables i Total Width of Cables 0.065
L-2002-070 Attachment 2 Page 110 of 230 Cable Tray ID C120-2307 Cable Type ,#12 MCCC Outside Diameter (inches) .9.. 0.022606 meters Insulation Material Outer Jacket Thickness (mils) *100.002032
... meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/k Conduct. Insul. Thickness (mils) == 0.00102 meters Jacket Material Num. Conds. Jacket Density (kg/m 3)
Diam. Cond. (inches) . 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 1 0.304878 meters Outside Radius 0.011303 m Total Cable Area (A3) 0.00040136 m2 0-00013134 m2 Jacket Area Insulation Area 8-8143E-05 m2 3
Total Volume of Jacket (M ) 3 4E-05 Mass of Jacket per meter (kg/m) 0.1894 Total Volume of Insulation (m 3) 2.69E-05 Mass of Insulation per meter (kg/m) 0.0815 Total Combustible Volume (M ) 6.69E-05 Total Combustible Mass per meter (kg/m) 0.2708 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 3399.1 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1939.2 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 5338.3 Combustible Fuel Load per meter (kJ/m) 5338.3 Number of Cables .:::::::::::
Total Width of Cables 0.023
L-2002-070 Attachment 2 Page 111 of 230 Cable Tray ID C120-2307 Cable Type 5/C#16
...--...-....-.. XLPPP Outside Diameter (inches) G52 0.013208 meters Insulation Material Outer Jacket Thickness (mils) `5 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) i 0.000381 meters Insulation Heat of Combustion (kWJ/k Conduct. Insul. Thickness (mils) 25 0.00064 meters Jacket Material Num. Conds. Jacket Density (kg/m 3)
Diam. Cond. (inches) ::: : 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ........ ..........0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.00013701 m 22 Jacket Area 6.0927E-05 M 2 Insulation Area 1.9204E-05 M 3
(M )
Total Volume of Jacket 1.86E-05 Mass of Jacket per meter (kglm) 0.0878 Total Volume of Insulation (m3) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m3) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJtm) 1999.3 Combustible Fuel Load per meter (kJ/m) 5997.9 Number of Cables ..........
Total Width of Cables 0.040
L-2002-070 Attachment 2 Page 112 of 230 Cable Tray ID C1 20 -2307 Cable Type 2/C#12 XLPPP Outside Diameter (inches) : : 0.0127 meters Insulation Material C. .b.............i...........
Outer Jacket Thickness (mils) ................
- 45 0.001143 meters Insulation Density (kg/m 3) 9244 Insulation Jacket Thickness (mils)
.3D:'::,::
S0.000381 meters
.' 0.00076 meters Insulation Heat of Combustion (kJ/kg: $*0 ... .. .. ..
Conduct. Insul. Thickness (mils) Jacket Material bilyL i
- pn*per Pi ies.
Num. Conds. 2 2 Jacket Density (kg/m3) 1441 :
Diam. Cond. (inches) &O8 i 0.002052 meters Jacket Heat of Combustion (kJ/kg) .....................
Cable Length (feet) 1 0.304878 meters Outside Radius 0.00635 m 2
Total Cable Area (A3) 0.00012668 m2 Jacket Area 5.0973E-05 2 m Insulation Area 1.3474E-05 m 3
Total Volume of Jacket (mi ) 3 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (M ) 4.11 E-06 Mass of Insulation per meter (kglm) 0.0125 3
Total Combustible Volume (m ) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 1615.6 Number of Cables :
Total Width of Cables 0.013
L-2002-070 Attachment 2 Page 113 of 230 Cable Tray ID C120-2307 Cable Type XLPPP Outside Diameter (inches) 0.010414 meters Insulation Material :..:.::::::::
Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m 3) 9244 Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg 2 . . . .
Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material .oly!te.r. Fl:m.m.):* VC .iuse popetie Num. Conds. 2 Jacket Density (kg/m3) 441
-4 Diam. Cond. (inches) 0.00129 meters Jacket Heat of Combustion (kJ/kg) ......
Cable Length (feet) 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.5178E-05 m2 Jacket Area 4.0332E-05 m2 2 Insulation Area 7.6817E-06 m 3
Total Volume of Jacket (m ) 1.23E-05 Mass of Jacket per meter (kglm) 0.0582 Total Volume of Insulation (m3) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 3
Total Combustible Volume (m ) 1.46E-05 Total Combustible Mass per meter (kgtm) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJtm) 1212.8 Combustible Fuel Load per meter (kJ/m) 8489.6 Num ber of Cables ... .....
Total Width of Cables 0.073
L-2002-070 Attachment 2 Page 114 of 230 Cable Tray ID C120-2307 Cable Type 2 7*41A MCCC Outside Diameter (inches) 0.017526 meters Insulation Material Outer Jacket Thickness (mils) 0.001651 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/kg Conduct. Insul. Thickness (mils) 0.00102 meters Jacket Material Num. Conds. 7 Jacket Density (kg/m 3)
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.008763 m Total Cable Area (A3) 0.00024124 m2 Jacket Area 8.234E-05 m2 2
Insulation Area 6.8555E-05 m 3
Total Volume of Jacket (M ) 3 2.51 E-05 Mass of Jacket per meter (kg/m) 0.1187 Total Volume of Insulation (m 3) 2.09E-05 Mass of Insulation per meter (kg/m) 0.0634 Total Combustible Volume (M ) 4.6E-05 Total Combustible Mass per meter (kg/m) 0.1821 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 2131.0 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1508.3 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJfm) 3639.3 Combustible Fuel Load per meter (kJ/m) 3639.3 Number of Cables ...........
Total Width of Cables 0.018
L-2002-070 Attachment 2 Page 115 of 230 Cable Tray ID C120-2307 Cable Type ,#12 XLPN (XLPPP)
Outside Diameter (inches) : : 0.0127 meters Insulation Material Outer Jacket Thickness (mils) ............. 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) . $...... 0.000381 meters Insulation Heat of Combustion (kJ/k Conduct. Insul. Thickness (mils) .. 0.00076 meters Jacket Material Num. Conds. 2............ 2 Jacket Density (kg/m3)
Diam. Cond. (inches)
- 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ..*1 0.304878 meters Outside Radius 0.00635 m 2
Total Cable Area (A3) 0.00012668 m Jacket Area 5.0973E-05 2m2 Insulation Area 1.3474E-05 m 3
(M )
Total Volume of Jacket 3 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (M 3) 4.11E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (mi 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 1615.6 Number of Cables .. .::
Total Width of Cables 0.013
L-2002-070 Attachment 2 Page 116 of 230 Cable Tray ID C1 20-2307 Cable Type ;#16 XLPN (XLPPP)
Outside Diameter (inches) 52i 0.013208 meters Insulation Material Outer Jacket Thickness (mils) .. 0.001143 meters Insulation Density (kg/mt)
Insulation Jacket Thickness (mils)
- 0.000381 meters Insulation Heat of Combustion (kJ/k Conduct. Insul. Thickness (mils) == 0.00064 meters Jacket Material Num. Conds. AN 5 Jacket Density (kg/m3)
Diam. Cond. (inches) *O . 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 1 0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.00013701 m' Jacket Area 6.0927E-05 m'2 Insulation Area 1.9204E-05 m 3
Total Volume of Jacket (M ) 3 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (M ) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m3) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 1999.3 Number of Cables ....
Total Width of Cables 0.013 Total Width (m) 0.294 Total Energy (m) 36767.3
L-2002-070 Attachment 2 Page 117 of 230 Cable Tray ID L120-230712369 Cable Type 12/C#16 XLPSMP Outside Diameter (inches) 1 i 0.02794 meters Insulation Material Outer Jacket Thickness (mils) BQ 0.002032 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) ................* 0.000381 meters Insulation Heat of Combustion (kJWl Conduct. Insul. Thickness (mils) 25 0.00064 meters Jacket Material Num. Conds. ........ 12 Jacket Density (kg/m 3)
Diam. Cond. (inches) ..................... 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ..................... 0.304878 meters Outside Radius 0.01397 m Total Cable Area (A3) 0.00061312 M 2
Jacket Area 0.00020764 2 m2 Insulation Area 4.609E-05 M 3
Total Volume of Jacket (M ) 3 6.33E-05 Mass of Jacket per meter (kg/m) 0.2994 Total Volume of Insulation (m 3
) 1.41 E-05 Mass of Insulation per meter (kg/m) 0.0426 Total Combustible Volume (M ) 7.74E-05 Total Combustible Mass per meter (kg/m) 0.3420 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 5373.7 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1014.0 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 6387.7 Combustible Fuel Load per meter (kJ/m) 12775.4 Number of Cables ............
Total Width of Cables 0.056
L-2002-070 Attachment 2 Page 118 of 230 Cable Tray ID LI 20-230712369 Cable Type 2/C#16 INSTS Outside Diameter (inches) . .. 0.010922 meters Insulation Material Outer Jacket Thickness (mils)
.. i 0.00127 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils)
........ 0 meters Insulation Heat of Combustion (k J/!k Conduct. Insul. Thickness (mils) : 0.00076 meters Jacket Material Num. Conds. 2 2 Jacket Density (kg/mr)
Diam. Cond. (inches) i050 o0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ................... 0.304878 meters Outside Radius 0.005461 m Total Cable Area (A3) 9.369E-05 m' Jacket Area 3.851 E-05 m22 Insulation Area 9.8261E-06 M 3
Total Volume of Jacket (M ) 3 1.17E-05 Mass of Jacket per meter (kg/m) 0.0555 Total Volume of Insulation (M ) 3E-06 Mass of Insulation per meter (kg/m) 0.0091 Total Combustible Volume (m3 ) 1.47E-05 Total Combustible Mass per meter (kg/m) 0.0646 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 996.6 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 216.2 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJIm) 1212.8 Combustible Fuel Load per meter (kJ/m) 6064.1 Number of Cables :
Total Width of Cables 0.055
L-2002-070 Attachment 2 Page 119 of 230 Cable Tray ID L120-230712369 Cable Type 4/C#16 INSTS Outside Diameter (inches) 64:iiiiiiiiiiiiiii 0.0104114 meters Insulation Material Carbon. biack cross -linked pciyyle, Outer Jacket Thickness (mils) 5 0.0012"7 meters Insulation Density (kg/m 3) i 4 4 Insulation Jacket Thickness (mils) meters Insulation Heat of Combustion (kJ/kg 2$$i&
Conduct. Insul. Thickness (mils) .... 3 ........ 0.0007. 6 meters Jacket Material R6I in ~p -. .%priipert-es Num. Conds. 2
- ..ii~~~~iii.........0 .3
...... 287ii~~ii 04 Jacket Density (kg/m3) 14.1..................
Diam. Cond. (inches) 9 meters Jacket Heat of Combustion (kJ/kg) 17 :.
Cable Length (feet) S.......................
0.30487 78 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.5178E-05 m22 Jacket Area 3.6483E-05 m2 Insulation Area 9.8261E-06 m Total Volume of Jacket (mi3) 3 1.11 E-05 Mass of Jacket per meter (kg/m) 0.0526 Total Volume of Insulation (M ) 3E-06 Mass of Insulation per meter (kg/m) 0.0091 Total Combustible Volume (m3) 1.41 E-05 Total Combustible Mass per meter (kg/m) 0.0617 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 944.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 216.2 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1160.4 Combustible Fuel Load per meter (kJtm) 1160.4 Nrum ber of Cables ............. ....
Total Width of Cables 0.010
L-2002-070 Attachment 2 Page 120 of 230 Cable Tray ID L120-230712369 Cable Type 21C#16 XLPSMP(TE)
Outside Diameter (inches) 035 i 0.00889 meters Insulation Material Outer Jacket Thickness (mils) .................. 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) ... meters o0.....*.... Insulation Heat of Combustion (kJ/k(
Conduct. Insul. Thickness (mils) 3.0....... 0.00076 meters Jacket Material 2iiiiiii ii~iiiiiiiiii2 Num. Conds. Jacket Density (kg/mr3)
Diam. Cond. (inches) ,O50: 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ........1........ 0.304878 meters Outside Radius 0.004445 m 2
Total Cable Area (A3) 6.2072E-05 m Jacket Area 2.7818E-05 m2 Insulation Area 9.8261 E-06 m2 Total Volume of Jacket (m 3) 3 8.48E-06 Mass of Jacket per meter (kg/m) 0.0401 Total Volume of Insulation (M ) 3E-06 Mass of Insulation per meter (kg/m) 0.0091 Total Combustible Volume (m3) 1.15E-05 Total Combustible Mass per meter (kg/m) 0.0492 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 719.9 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 216.2 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 936.1 Combustible Fuel Load per meter (kJ/m) 936.1 Number of Cables %........
Total Width of Cables 0.009
L-2002-070 Attachment 2 Page 121 of 230 Cable Tray ID L120-230712369 Cable Type XLPSMP Outside Diameter (inches) 0.010922 meters Insulation Material Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/mr)
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/!
Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material Num. Conds. 3 Jacket Density (kg/m3)
Diam. Cond. (inches) 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.005461 m Total Cable Area (A3) 9.369E-05 m2 Jacket Area 4.5677E-05 m2 2
Insulation Area 1.1523E-05 M 3
Total Volume of Jacket (M ) 3 1.39E-05 Mass of Jacket per meter (kg/m) 0.0659 Total Volume of Insulation (m ) 3.51 E-06 Mass of Insulation per meter (kg/m) 0.0107 Total Combustible Volume (m3) 1.74E-05 Total Combustible Mass per meter (kg/m) 0.0765 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1182.1 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 253.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1435.6 Combustible Fuel Load per meter (kJ/m) 2871.3 Number of Cables :
Total Width of Cables 0.022
L-2002-070 Attachment 2 Page 122 of 230 Cable Tray ID L120-230712369 Cable Type 2/C#14 XLPSN (XLPSMP)
Outside Diameter (inches) 05 0.0127 meters Insulation Material *os.......polyethylene
- a.b.n Outer Jacket Thickness (mils)
- AS 0.001143 meters Insulation Density (kg/m 3) - .9244......
Insulation Jacket Thickness (mils) 1 ......
........ i 0.000381 meters Insulation Heat of Combustion (kJ/kg 23::
$O&:.:.
Conduct. Insul. Thickness (mils)
- 30 0.00076 meters Jacket Material (FnTo .ms P properfies Wol.ein Jacket Density (kg/m43) 1441 Num. Conds. *2 2 Diam. Cond. (inches) 0i$4 ; 0.001628 meters Jacket Heat of Combustion (kJ/kg) IMi:....
Cable Length (feet) 1% 0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.00012668m' Jacket Area 4.9957E-05m2 Insulation Area 1.1443E-05m2 Total Volume of Jacket (m 3) 1.52E-05 Mass of Jacket per meter (kg/m) 0.0720 Total Volume of Insulation (m3) 3.49E-06 Mass of Insulation per meter (kg/m) 0.0106 Total Combustible Volume (m3) 1.87E-05 Total Combustible Mass per meter (kg/m) 0.0826 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJIm) 1292.9 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 251.8 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1544.7
................................... .... Combustible Fuel Load per meter (kJ/m) 4634.0 Number of Cables . ... ..... ...........
Total Width of Cables 0.038
L-2002-070 Attachment 2 Page 123 of 230 Cable Tray ID L120-230712369 41/":.l 6 XLPSN Cable Type Outside Diameter (inches) 0.0127 Insulation Material Cr Z, .....
meters Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kglm3) .244 Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/kg 2$i.iiii..............
Conduct. Insul. Thickness (mils) 0.00051 meters Jacket Material FOR. w.i i .C pripries Num. Conds. 4 Jacket Density (kg/m 3) .. -...............
.441.
Diam. Cond. (inches) 0.00129 meters Jacket Heat of Combustion (kJ/kg) 17iO Cable Length (feet) 0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.00012668 m2 Jacket Area 4.1499E-05 m2 2
Insulation Area 1.148E-05 m 3
Total Volume of Jacket (M ) 3 1.27E-05 Mass of Jacket per meter (kg/m) 0.0598 Total Volume of Insulation (m ) 3.5E-06 Mass of Insulation per meter (kg/m) 0.0106 3
Total Combustible Volume (m ) 1.62E-05 Total Combustible Mass per meter (kg/m) 0.0704 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJlm) 1074.0 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 252.6 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1326.6 Combustible Fuel Load per meter (kJ/m) 3979.8 Num ber of Cables ...........
Total Width of Cables 0.038
L-2002-070 Attachment 2 Page 124 of 230 Cable Tray ID L120-230712369 Cable Type 2/C#16 EPDMHYP (XLPPP)
Outside Diameter (inches) ..................... 0.010414 m eters Insulation Material Outer Jacket Thickness (mils) . 45 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils)
- i : 0.000381 meters Insulation Heat of Combustion (kJ/kgI Conduct. Insul. Thickness (mils) ......2......... 0.00064 meters Jacket Material Num. Conds. ......... .......... 0.00129 meters Jacket Density (kg/m 3)
Diam. Cond. (inches) Jacket Heat of Combustion (kJ/kg)
Cable Length (feet)
- 4 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.5178E-05 m'2 Jacket Area 4.0332E-05 m Insulation Area 7.6817E-06 m2 Total Volume of Jacket (mi3 ) 3 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (M 3) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (m ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 2425.6 Number of Cables ............ ..........
Total Width of Cables 0.021
L-2002-070 Attachment 2 Page 125 of 230 Cable Tray ID L120-230712369 Cable Type 4/C#16 XLPP (XLPSMP)
..... 7. 0.01905 5....... meters Insulation Material Outside Diameter (inches)
Outer Jacket Thickness (mils) ......
........ 0.001524
...... meters Insulation Density (kglm3)
Insulation Jacket Thickness (mils) i 0.000381 meters Insulation Heat of Combustion (kJ/k Conduct. Insul. Thickness (mils) 2: : 0.00064 meters Jacket Material Num. Conds. ......... 4 Jacket Density (kg/m 3)
Diam. Cond. (inches) i i 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .......... 0.304878 meters Outside Radius 0.009525 m Total Cable Area (A3) 0.00028502 m2 Jacket Area 9.7993E-05m2 Insulation Area 1.5363E-05m2 3
Total Volume of Jacket (M )
3 2.99E-05 Mass of Jacket per meter (kg/m) 0.1413 Total Volume of Insulation (M ) 4.68E-06 Mass of Insulation per meter (kg/m) 0.0142 Total Combustible Volume (m3) 3.46E-05 Total Combustible Mass per meter (kg/m) 0.1555 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 2536.1 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 338.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2874.1 w......
Combustible Fuel Load per meter (kJ/m) 8622.3 Number of Cables .......... .
Total Width of Cables 0.057
L-2002-070 Attachment 2 Page 126 of 230 Cable Tray ID L120-230712369 Cable Type ;Pr*If' A. XLPSMP Outside Diameter (inches) 0.0127 meters Insulation Material arap etbylene cros*inked IbMa Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m 3) 9244 Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg i2i3i.! O Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material rn - iuse PVC propertie lii Ryefr Num. Conds. 2 Jacket Density (kg/m3) 1441.............
Diam. Cond. (inches) 0.001628 meters Jacket Heat of Combustion (kJ/kg) 17*O Cable Length (feet) 0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.00012668 m2 Jacket Area 4.9957E-05 m22 Insulation Area 1.1443E-05 m 3
Total Volume of Jacket (M ) 1.52E-05 Mass of Jacket per meter (kg/m) 0.0720 Total Volume of Insulation (m3) 3.49E-06 Mass of Insulation per meter (kg/m) 0.0106 Total Combustible Volume (m )
3 1.87E-05 Total Combustible Mass per meter (kg/m) 0.0826 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1292.9 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 251.8 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1544.7 Combustible Fuel Load per meter (kJ/m) 3089.4 Number of Cables i .
Total Width of Cables 0.025
L-2002-070 Attachment 2 Page 127 of 230 Cable Tray ID L120-230712369 Cable Type 4/C# 16 XLPSMP Outside Diameter (inches) 0.01905 meters
................ Insulation Material Outer Jacket Thickness (mils) ...... 0.001524 meters
..... Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) !5 0.000381 meters Insulation Heat of Combustion (kJ/kg Conduct. Insul. Thickness (mils) 25i 0.00064 meters Jacket Material 4 , 4 Jacket Density (kg/m 3)
Num. Conds.
Diam. Cond. (inches) .5 i 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ...... 0.304878 meters Outside Radius 0.009525 m Total Cable Area (A3) 0.00028502 m 2 2
Jacket Area 9.7993E-05 M 2
Insulation Area 1.5363E-05 m 3
Total Volume of Jacket (M ) 2.99E-05 Mass of Jacket per meter (kglm) 0.1413 Total Volume of Insulation (m3)3 4.68E-06 Mass of Insulation per meter (kglm) 0.0142
)
Total Combustible Volume (M 3.46E-05 Total Combustible Mass per meter (kg/m) 0.1555 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJJ/m) 2536.1 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 338.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2874.1 Combustible Fuel Load per meter (kJ/m) 8622.3 Number of Cables .
Total Width of Cables 0.057 Total Width (m) 0.388 Total Energy (kJim) 55180.6
L-2002-070 Attachment 2 Page 128 of 230 Cable Tray ID LIOI-2305 Cable Type 5Q9/ I RG-59/U COA Outside Diameter (inches) 0.018796 meters Insulation Material . .. . ..........................
Outer Jacket Thickness (mils) 0 meters Insulation Density (kg/m 3) 1441 B Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion g...... .....
Conduct. Insul. Thickness (mils) 0.00274 meters Jacket Material Iy:PW.I)u fe91r P .
Num. Conds. 1 Jacket Density (kg/m 3) 1441 B Diam. Cond. (inches) 0.000643 meters Jacket Heat of Combustion (kJ/kg) :,.*t%:".:.4.*OO W.W.
Cable Length (feet) 0.304878 meters Outside Radius 0.009398 m (PE) 2 Total Cable Area (A3) 0.00027747 M 2
Jacket Area 0 m2 Insulation Area 2.9179E-05 m Total Volume of Jacket (m3) 0 Mass of Jacket per meter (kg/m) 0.0000 Total Volume of Insulation (m3)3 8.9E-06 Mass of Insulation per meter (kg/m) 0.0421 Total Combustible Volume (M ) 8.9E-06 Total Combustible Mass per meter (kg/m) 0.0421 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 0.0 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1956.3 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1956.3 Combustible Fuel Load per meter (kJ/m) 9781.4 Number of Cables i Total Width of Cables 0.094
L-2002-070 Attachment 2 Page 129 of 230 Cable Tray ID L101-2305 Cable Type COAX COA Outside Diameter (inches) 0.018796 meters Insulation Material Outer Jacket Thickness (mils) 0 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/kg Conduct. Insul. Thickness (mils) 0.00318 meters Jacket Material Num. Conds. 1 Jacket Density (kg/m 3)
Diam. Cond. (inches) 0.000574 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.009398 m (PE)
Total Cable Area (A3) 0.00027747 m' 2
Jacket Area 0 m2 Insulation Area 3.7395E-05 m 3
Total Volume of Jacket (M ) 3 0 Mass of Jacket per meter (kg/m) 0.0000 Total Volume of Insulation (M3) 1.14E-05 Mass of Insulation per meter (kg/m) 0.0539 Total Combustible Volume (m ) 1.14E-05 Total Combustible Mass per meter (kglm) 0.0539 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 0.0 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 2507.1 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2507.1 Combustible Fuel Load per meter (kJ/m) 5014.2 Number of Cables :
Total Width of Cables 0.038
L-2002-070 Attachment 2 Page 130 of 230 Cable Tray ID L101-2305 Cable Type "#18
.-.....-...-....--. XLPSN (XLPPP)
Outside Diameter (inches) ............0.013335 meters Insulation Material Outer Jacket Thickness (mils) ............ 0.001143 meters Insulation Density (kg/m 3 )
Insulation Jacket Thickness (mils) ) 0 meters Insulation Heat of Combustion (kJ/k Conduct. Insul. Thickness (mils) ............0.00051 meters Jacket Material Num. Conds. 6 Jacket Density (kglm 3 )
Diam. Cond. (inches) 0.001024 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ............ 0.304878 meters Outside Radius 0.0066675 m 2
Total Cable Area (A3) 0.00013966 m Jacket Area 4.378E-05 m' Insulation Area 1.4666E-05 m' 3
Total Volume of Jacket (M ) 3 1.33E-05 Mass of Jacket per meter (kg/m) 0.0631
) 0.0136 Total Volume of Insulation (M 4.47E-06 Mass of Insulation per meter (kg/m)
Total Combustible Volume (m 3
) 1.78E-05 Total Combustible Mass per meter (kg/m) 0.0767 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1133.0 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJim) 322.7 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1455.7 Combustible Fuel Load per meter (kJ/m) 1455.7 Num ber of Cables ...........
Total Width of Cables 0.013
L-2002-070 Attachment 2 Page 131 of 230 Cable Tray ID L101-2305 Cable Type "#16 XLPSN Outside Diameter (inches) i 0.0127 meters Insulation Material Outer Jacket Thickness (mils) 5 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) ) 0 meters Insulation Heat of Combustion (kJ/kg Conduct. Insul. Thickness (mils) ............
. .............. 0.00051 meters Jacket Material Num. Conds.
4 Jacket Density (kg/m 3)
Diam. Cond. (inches) 5O i 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .:%:::::::::::::::::::::::::::::0.304878 meters Outside Radius 0.00635 m 2
Total Cable Area (A3) 0.00012668 m Jacket Area 4.1499E-05 2 m2 Insulation Area 1.148E-05 m 3
Total Volume of Jacket (M ) 1.27E-05 Mass of Jacket per meter (kg/m) 0.0598 Total Volume of Insulation (m3) 3.5E-06 Mass of Insulation per meter (kg/m) 0.0106 Total Combustible Volume (m3) 1.62E-05 Total Combustible Mass per meter (kg/m) 0.0704 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1074.0 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 252.6 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1326.6
.,... ....................... Combustible Fuel Load per meter (kJ/m) 2653.2 Number of Cables :
Total Width of Cables 0.025
L-2002-070 Attachment 2 Page 132 of 230 Cable Tray ID L101-2305 Cable Type XLPSN (1) (XLPPP)
Outside Diameter (inches) 0.010414 meters Insulation Material kss inked
'mrboi n .........
3 Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m ) 9244 Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg 23.,.O Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material 6oIvbM6fnFla mf ise PVC prop:rf:es Num. Conds. 2 Jacket Density (kg/m 3) 1441......
Diam. Cond. (inches) 0.00129 meters Jacket Heat of Combustion (kJ/kg) i....................
Cable Length (feet) 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.5178E-05 m' Jacket Area 4.0332E-05 m2 Insulation Area 7.6817E-06 m2 Total Volume of Jacket (in 3 ) 3 1.23E-05 Mass of Jacket per meter (kglm) 0.0582 Total Volume of Insulation (M 3) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (m ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJtm) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 2425.6 Number of Cables :
Total Width of Cables 0.021
L-2002-070 Attachment 2 Page 133 of 230 Cable Tray ID LIOI-2305 4-A1A Cable Type XLPSN (1) (XLPSMP)
Outside Diameter (inches) 0.0127 meters Insulation Material ............
Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m 3) 9244 Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg 23800 Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material in{Ftam i .kise iesi Jacket Density (kg/m 3) . ......
1441...
Num. Conds. 2 Diam. Cond. (inches) 0.001628 meters Jacket Heat of Combustion (kJ/kg) 17i80 Cable Length (feet) 0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.00012668 m2 Jacket Area 4.9957E-05 m22 Insulation Area 1.1443E-05 m Total Volume of Jacket (m 3) 1.52E-05 Mass of Jacket per meter (kg/m) 0.0720 Total Volume of Insulation (m3)3 3.49E-06 Mass of Insulation per meter (kg/m) 0.0106 Total Combustible Volume (m ) 1.87E-05 Total Combustible Mass per meter (kg/m) 0.0826 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1292.9 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 251.8 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1544.7 Combustible Fuel Load per meter (kJ/m) 4634.0 Number of Cables Total Width of Cables 0.038
L-2002-070 Attachment 2 Page 134 of 230 Cable Tray ID L101-2305 Cable Type 2/C#16 XLPSMP Outside Diameter (inches) 035............. 0.00889 meters Insulation Material Carbo""',
Outer Jacket Thickness (mils) 5A......... 0.001143 meters Insulation Density (kg/m 3) 9244 Insulation Heat of Combustion (kJ/kg . . . . . .
Insulation Jacket Thickness (mils) ....
- 0. m eters Conduct. Insul. Thickness (mils) S0.00076 meters Jacket Material C Num. Conds. 2 2 Jacket Density (kg/m 3) .. 441.............
Diam. Cond. (inches) ................... 0.00129 meters Jacket Heat of Combustion (kJ/kg) 179iO Cable Length (feet) ....... *...... 0.304878 meters Outside Radius 0.004445 m 2
Total Cable Area (A3) 6.2072E-05 m2 Jacket Area 2.7818E-05 m2 Insulation Area 9.8261E-06 m 3
Total Volume of Jacket (mi ) 3 8.48E-06 Mass of Jacket per meter (kg/m) 0.0401 Total Volume of Insulation (m ) 3E-06 Mass of Insulation per meter (kg/m) 0.0091 3
Total Combustible Volume (m ) 1.15E-05 Total Combustible Mass per meter (kglm) 0.0492 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 719.9 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 216.2 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 936.1 Combustible Fuel Load per meter (kJ/m) 2808.4 Num ber of Cables ..........
Total Width of Cables 0.027
L-2002-070 Attachment 2 Page 135 of 230 Cable Tray ID L101-2305 Cable Type #14 XLPSMP Outside Diameter (inches) ..* . 0.0127 meters Insulation Material Outer Jacket Thickness (mils) *I 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) ...i 0.000381 meters Insulation Heat of Combustion (kJ/k Conduct. Insul. Thickness (mils) .O 0.00076 meters Jacket Material Num. Conds. ...... . 2 Jacket Density (kg/m3)
Diam. Cond. (inches) ..... 0.001628 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 1: 0.304878 meters Outside Radius 0.00635 m 2
Total Cable Area (A3) 0.00012668 M2 Jacket Area 4.9957E-05 M Insulation Area 1.1443E-05 m2 3
Total Volume of Jacket (M ) 3 1.52E-05 Mass of Jacket per meter (kg/m) 0.0720 Total Volume of Insulation (m 3) 3.49E-06 Mass of Insulation per meter (kg/m) 0.0106 Total Combustible Volume (M ) 1.87E-05 Total Combustible Mass per meter (kg/m) 0.0826 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1292.9 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 251.8 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1544.7 Combustible Fuel Load per meter (kJ/m) 3089.4 Number of Cables ...........
Total Width of Cables 0.025
L-2002-070 Attachment 2 Page 136 of 230 Cable Tray ID LI 01-2305 Cable Type #16 XLPSMP Outside Diameter (inches) 4...........0.010922 meters Insulation Material ....................................
Outer Jacket Thickness (mils) S 0.001143 meters Insulation Density (kg/m3) 9244...............
Insulation Jacket Thickness (mils) : 0.000381 meters Insulation Heat of Combustion (kJ/kg 2 .. . .
Jacket Material Flan*fro - ~usePir M.1yotefiri
- propertie Conduct. Insul. Thickness (mils) 5 : 0.00064 meters Num. Conds. 3 3 Jacket Density (kgfm3) ............144.......
Diam. Cond. (inches) 5 i 0.00129 meters Jacket Heat of Combustion (kJ/kg) ......................
Cable Length (feet) ............0.304878 meters Outside Radius 0.005461 m Total Cable Area (A3) 9.369E-05 m'2 Jacket Area 4.5677E-05 m Insulation Area 1.1523E-05 m2 Total Volume of Jacket (m3) 3 1.39E-05 Mass of Jacket per meter (kg/m) 0.0659 Total Volume of Insulation (M 3) 3.51 E-06 Mass of Insulation per meter (kglm) 0.0107 Total Combustible Volume (M ) 1.74E-05 Total Combustible Mass per meter (kg/m) 0.0765 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1182.1 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 253.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1435.6 Combustible Fuel Load per meter (kJ/m) 7178.1 Number of Cables 3/4 Total Width of Cables 0.055
L-2002-070 Attachment 2 Page 137 of 230 Cable Tray ID L101-2305 Cable Type 2/C#16 TEW (XLPPP)
Outside Diameter (inches) i 41 0.010414 meters Insulation Material 1.arbo.
Outer Jacket Thickness (mils) .45
- ................0.001143 meters Insulation Density (kg/m 3) 9244 Insulation Jacket Thickness (mils) 1i 0.000381 meters iiiiiii.
Insulation Heat of Combustion (kJ/kg !23&*O!*!*!!!i!*!*
Conduct. Insul. Thickness (mils) ......... ........ 0.00064 meters Jacket Material R iM F.aPAW, kis PV *ro ie ir 2......... 2 Num. Conds. Jacket Density (kg/m 3) 1441 S Diam. Cond. (inches) iiO5O i 0.00129 meters Jacket Heat of Combustion (kJ/kg) 179iO Cable Length (feet) ...........%-..-..--1 0.304878 meters Outside Radius 0.005207 m 2
Total Cable Area (A3) 8.5178E-05 m2 Jacket Area 4.0332E-05 m2 Insulation Area 7.6817E-06 m Total Volume of Jacket (mi3 ) 3 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (M ) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (m3) 1.46E-05 Total Combustible Mass per meter (kglm) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 2425.6 Number of Cables ...........
Total Width of Cables 0.021
L-2002-070 Attachment 2 Page 138 of 230 Cable Tray ID L101-2305 Cable Type ;#16 EPDMHYP (XLPPP)
Outside Diameter (inches) 41 0.010414 meters Insulation Material Outer Jacket Thickness (mils) 5 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) S0000381 meters Insulation Heat of Combustion (kWJi!
Conduct. Insul. Thickness (mils) ............. 0.00064 meters Jacket Material Num. Conds. 2 2 Jacket Density (kg/m 3)
Diam. Cond. (inches) *O$ 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .* 0.304878 meters Outside Radius 0.005207 m 2
Total Cable Area (A3) 8.5178E-05 m Jacket Area 4.0332E-05 2 m2 Insulation Area 7.6817E-06 m Total Volume of Jacket (m3) 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m3)3 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (M ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 1212.8 Number of Cables .IBM! .NEI ,
Total Width of Cables 0.010 Total Width (m) 0.367 Total Energy (m) 42678.3
L-2002-070 Attachment 2 Page 139 of 230 Cable Tray ID M100-2305 Cable Type 3-1/C #4/0 XLPP Outside Diameter (inches) 0823i 0.020904 meters Insulation Material Outer Jacket Thickness (mils) .45i 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) . . 0 meters Insulation Heat of Combustion (kJ/ik Conduct. Insul. Thickness (mils) .... 5*.. 0.00140 meters
..... Jacket Material Num. Conds. Jacket Density (kg/m3)
Diam. Cond. (inches) 'S..": 0.011684 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters S*............
Outside Radius 0.0104521 m 2
Total Cable Area (A3) 0.00034321 m Jacket Area 7.0959E-05 m2 Insulation Area 5.741 E-05 M2 3
Total Volume of Jacket (m ) 3 2.16E-05 Mass of Jacket per meter (kg/m) 0.1023 Total Volume of Insulation (m ) 1.75E-05 Mass of Insulation per meter (kg/m) 0.0531 Total Combustible Volume (m3) 3.91E-05 Total Combustible Mass per meter (kg/m) 0.1554 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1836.4 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1263.1 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 3099.5 Combustible Fuel Load per meter (kJ/m) 74388.2 Number of Cables :2 I Total Width of Cables 0.502
L-2002-070 Attachment 2 Page 140 of 230 Cable Tray ID MIOO-2320 Cable Type 3-1/C #4/0 XLPP Outside Diameter (inches) ............0.020904 meters Insulation Material Outer Jacket Thickness (mils) 15iiiiii"ii.iiiii 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ....... 0.00140 meters Jacket Material Num. Conds. 1 Jacket Density (kg/Mr)
Diam. Cond. (inches) 0.011684 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (if) 0.304878 meters Outside Radius 0.0104521 m 2
Total Cable Area (A3) 0.0003432 m Jacket Area 7.096E-05 m2 Insulation Area 5.741E-05 m2 Total Volume of Jacket (m 3) 2.16E-05 Mass of Jacket per meter (kg/m) 0.1023 Total Volume of Insulation (m3)3 1.75E-05 Mass of Insulation per meter (kg/m) 0.0531 Total Combustible Volume (M ) 3.91 E-05 Total Combustible Mass per meter (kg/m) 0.1554 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1836.4 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1263.1 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 3099.5 Combustible Fuel Load per meter (kJ/m) 74388.2 Number of Cables ......
Total Width of Cables 0.502
L-2002-070 Attachment 2 Page 141 of 230 Cable Tray ID C101-2320 Cable Type #16 XLPPP Outside Diameter (inches) 2..... 0.013208
....... meters Insulation Material 9244. .........
Outer Jacket Thickness (mils) 5 0.001143 meters Insulation Density (kg/m 3) sk t: ..........
Insulation Jacket Thickness (mils) S0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ...... 0.00064 meters Jacket Material Num. Conds. Jacket Density (kg/m3) i1441 i;;*i* ;I :: .1 ....
Diam. Cond. (inches)
- 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .............0.304878 meters Outside Radius 0.006604 m2 Total Cable Area (A3) 0.000137 m Jacket Area 6.093E-05m2 Insulation Area 1.92E-05M 3
Total Volume of Jacket (M ) 3 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (m 3) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m ) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 7997.2 Number of Cables ....
Total Width of Cables 0.053
L-2002-070 Attachment 2 Page 142 of 230 Cable Tray ID C101-2320 Cable Type "ýIfl XLPPP Outside Diameter (inches) 0.0127 meters Insulation Material Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material Num. Conds. 2 Jacket Density (kg/rm)
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.0001267 m' Jacket Area 5.097E-05 m2 2
Insulation Area 1.347E-05 M Total Volume of Jacket (m3) 3 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m 3 0.0125
) 4.11E-06 Mass of Insulation per meter (kg/m)
Combustible Volume (M ) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 6462.5 Number of Cables :
Total Width of Cables 0.051
L-2002-070 Attachment 2 Page 143 of 230 Cable Tray ID C101-2320 Cable Type 2/C#16 XLPPP
. -4 1 4.i Insulation Material Outside Diameter (inches) 0.010414 meters 244... ...
Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) ...... 5 .... 0.000381 meters Insulation Heat of Combustion (kJ/kg) ....
4....11W.. .....
MA,........
Conduct. Insul. Thickness (mils) . .........
......... iiiiiii~iii 2......
..... 0.00064 meters Jacket Material Num. Conds. .... I.....
..... ..... 2 Jacket Density (kg/m 3)
Diam. Cond. (inches) 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 m2 Jacket Area 4.033E-05 m2 Insulation Area 7.682E-06 m2 Total Volume of Jacket (m 3) 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m3)3 2.34E-06 Mass of Insulation per meter (kgrm) 0.0071 Total Combustible Volume (m ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 7276.8 Number of Cables .
Total Width of Cables 0.062
L-2002-070 Attachment 2 Page 144 of 230 Cable Tray ID C101-2320 Cable Type 5/C#16
.. .... ....................... XLPN (XLPPP)
Outside Diameter (inches) 52: 0.013208 meters Insulation Material Outer Jacket Thickness (mils) .......4..5... . 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 1i i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ::::::::: 0.00064 meters 5:::::::: Jacket Material 3 Num. Conds. 5 5 Jacket Density (kglm )
Diam. Cond. (inches) }OiQ$ 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .. ........ 0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m' Jacket Area 6.093E-05 m2 2
Insulation Area 1.92E-05 i Total Volume of Jacket (m3) 3 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (M 3) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m ) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJim) 1999.3 Combustible Fuel Load per meter (kJ/m) 11995.8 Number of Cables ..........
Total Width of Cables 0.079
L-2002-070 Attachment 2 Page 145 of 230 Cable Tray ID C101-2320 Cable Type ,#12 XLPN (XLPPP)
Outside Diameter (inches) * : 0.0127 meters Insulation Material 3 .......... .......
Insulation Density (kglm )
Outer Jacket Thickness (mils) S 0.001143 meters ..
Insulation Jacket Thickness (mils) I 0.000381 meters Insulation Heat of Combustion (kJ/kg) . :....: :.: :: : :: : : ::.
Conduct. Insul. Thickness (mils) i .....* 0.00076 meters Jacket Material ie Num. Conds. Jacket Density (kg/m3)
Diam. Cond. (inches) ) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.00635 m 2
Total Cable Area (A3) 0.0001267 m 2
Jacket Area 5.097E-05M 2 Insulation Area 1.347E-05 m 3
Total Volume of Jacket (M )
3 1.55E-05 Mass of Jacket per meter (kglm) 0.0735 (M ) 0.0125 Total Volume of Insulation 3 4.11E-06 Mass of Insulation per meter (kg/m)
(M )
Total Combustible Volume 1.96E-05 Total Combustible Mass per meter (kglm) 0.0859 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJtm) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 4846.9 Number of Cables :I .'x. x Total Width of Cables 0.038 Total Width (m) 0.283 Total Energy(kJ/m) 38579.3
L-2002-070 Attachment 2 Page 146 of 230 Cable Tray ID M100-2393 Cable Type 3-1/C #410 XLPP SM'%"iiii.i0.020904 Outside Diameter (inches) meters Insulation Material 0- iiiiiiii0.001143 Outer Jacket Thickness (mils) meters Insulation Density (kglm 3)
............... . 0 Insulation Jacket Thickness (mils) 0 4 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) *~0.00140 meters Jacket Material 3
Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) 0.011684 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) 0.304878 meters Outside Radius 0.0104521 m Total Cable Area (A3) 0.0003432 m2 Jacket Area 7.096E-05 m2 Insulation Area 5.741 E-05 m2 3
Total Volume of Jacket (mi ) 3 2.16E-05 Mass of Jacket per meter (kg/m) 0.1023 Total Volume of Insulation (m 3
) 0.0531 1.75E-05 Mass of Insulation per meter (kg/m)
Volume (M ) 0.1554 Total Combustible 3.91 E-05 Total Combustible Mass per meter (kg/m)
Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1836.4 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1263.1 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 3099.5 Combustible Fuel Load per meter (kJ/m) 74388.2 Number of Cables :
Total Width of Cables 0.502
L-2002-070 Attachment 2 Page 147 of 230 Cable Tray ID C1 01-2393 Cable Type 2/C#12 XLPPP Outside Diameter (inches) ..................i 0.0127 m eters Insulation Material i..... 0.001143 meters Insulation Density (kg/m 3)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils) 1. 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ......... 0.00076 meters Jacket Material 3 Num. Conds. 2 2 Jacket Density (kg/m )
Diam. Cond. (inches) iiv i 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .......... ... ....0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.0001267 m2 2
Jacket Area 5.097E-05 m 2
Insulation Area 1.347E-05 M Total Volume of Jacket (M3) 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (M3) 3 4.11E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (m ) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 4846.9 Num ber of Cables ..... . .........
Total Width of Cables 0.038
L-2002-070 Attachment 2 Page 148 of 230 Cable Tray ID C101-2393 Cable Type ,#16 XLPPP Outside Diameter (inches) 2 0.013208 meters Insulation Material Outer Jacket Thickness (mils) = 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils)
- 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 2 0.00064 meters Jacket Material 3 Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) M i.. 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .. 0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m' Jacket Area 6.093E-05 m22 Insulation Area 1.92E-05 m Total Volume of Jacket (mi3 ) 3 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (M3) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m ) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 3998.6 Number of Cables . ..........
Total Width of Cables 0.026
L-2002-070 Attachment 2 Page 149 of 230 Cable Tray ID C101-2393 Cable Type 2/C#16 XLPPP Outside Diameter (inches) 0 ii 0.010414 meters Insulation Material Outer Jacket Thickness (mils) ...... 0.001143 meters
......... Insulation Density (kg/mr)
Insulation Jacket Thickness (mils) 4i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 2* 0.00064 meters Jacket Material Num. Conds. S 22* Jacket Density (kg/mr)
Diam. Cond. (inches) i 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 1........
...... 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 m2 2
Jacket Area 4.033E-05 m Insulation Area 7.682E-06 m2 3
Total Volume of Jacket (M ) 3 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m 3) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (M ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 3638.4 Num ber of Cables ........................
Total Width of Cables 0.031
L-2002-070 Attachment 2 Page 150 of 230 Cable Tray ID C101-2393 Cable Type 5/C #12 XLPN (XLPPP)
Outside Diameter (inches) 0.017272 meters Insulation Material Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kglm 3)
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material 3 Num. Conds. 5 Jacket Density (kg/m )
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.008636 m Total Cable Area (A3) 0.0002343 m 2 Jacket Area 8.16E-05 m2 3.369E-05 in2 Insulation Area Total Volume of Jacket (M3) 3 2.49E-05 Mass of Jacket per meter (kg/m) 0.1177 Total Volume of Insulation (M 3) 1.03E-05 Mass of Insulation per meter (kg/m) 0.0311 Total Combustible Volume (m ) 3.51 E-05 Total Combustible Mass per meter (kg/m) 0.1488 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 2111.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 741.1 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2853.0 Combustible Fuel Load per meter (kJ/m) 2853.0 Number of Cables ...... : ................
Total Width of Cables 0.017
L-2002-070 Attachment 2 Page 151 of 230 Cable Tray ID C101-2393 Cable Type 3#12 XLPN (XLPPP)
Outside Diameter (inches) k i 0.0127 meters Insulation Material Outer Jacket Thickness (mils) 4.- 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) .I........... 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) .3C::i:"iii::i-.::ii 0.00076 meters Jacket Material 3 Num. Conds. 2 2 Jacket Density (kglm )
Diam. Cond. (inches) ........... 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) S0.304878 meters Outside Radius 0.00635 m2 Total Cable Area (A3) 0.0001267 m 2
Jacket Area 5.097E-05 m Insulation Area 1.347E-05 m2 3
(M )
Total Volume of Jacket 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m3)3 4.11 E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (m ) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJtm) 1615.6 Combustible Fuel Load per meter (kJim) 6462.5 Number of Cables ......
Total Width of Cables 0.051
L-2002-070 Attachment 2 Page 152 of 230 Cable Tray ID C101-2393 Cable Type '#16 XLPN (XLPPP)
Outside Diameter (inches) 2 0.013208 meters Insulation Material 3 Outer Jacket Thickness (mils) = 0.001143 meters Insulation Density (kg/Mi )
Insulation Jacket Thickness (mils) 5 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) .. 0.00064 meters Jacket Material 3 Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) 5Oi 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) S0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m2 2
Jacket Area 6.093E-05 m 2
Insulation Area 1.92E-05 M 3
Total Volume of Jacket (M ) 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (Mi) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m3) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJfm) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 11995.8 Number of Cables Total Width of Cables 0.079 Total Width (m) 0.243 Total Energy (kJim) 33795.2
L-2002-070 Attachment 2 Page 153 of 230 Cable Tray ID Ml00-2306 Cable Type 3-1/C #4/0 XLPP 828iiii: 0.020904 meters Caibo..........
Outside Diameter (inches) Insulation Material Outer Jacket Thickness (mils) 4 i 0.001143 meters Insulation Density (kg/m 3)
. ........ 0 Insulation Jacket Thickness (mils) meters Insulation Heat of Combustion (kJ/kg) 14.....1......
Conduct. Insul. Thickness (mils) *6 0.00140 meters Jacket Material Num. Conds. Jacket Density (kg/mi)
Diam. Cond. (inches) .............. 0.011684 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) .............. 0.304878 meters Outside Radius 0.0104521 m Total Cable Area (A3) 0.0003432 m2 Jacket Area 7.096E-05 m2 Insulation Area 5.741 E-05 M2 3
Total Volume of Jacket (m ) 3 2.16E-05 Mass of Jacket per meter (kg/m) 0.1023 Total Volume of Insulation (m ) 1.75E-05 Mass of Insulation per meter (kglm) 0.0531 3
Total Combustible Volume (m ) 3.91 E-05 Total Combustible Mass per meter (kg/m) 0.1554 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1836.4 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1263.1 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJJ/m) 3099.5 Combustible Fuel Load per meter (kJ/m) 55791.2 Number of Cables Total Width of Cables 0.376
L-2002-070 Attachment 2 Page 154 of 230 Cable Tray ID C101-2306 Cable Type '#12 XLPPP Outside Diameter (inches) 0.0127 meters Insulation Material 3
Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m )
Insulation Jacket Thickness (mils) 15 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ........... 0.00076 meters Jacket Material 3
Num. Conds. 22 Jacket Density (kg/m )
Diam. Cond. (inches) ................. 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ..... 0.304878 meters Outside Radius 0.00635 m 2
Total Cable Area (A3) 0.0001267 m 2
Jacket Area 5.097E-05 i 2
Insulation Area 1 .347E-05 M 3
Total Volume of Jacket (mi ) 3 1.55405E-05 Mass of Jacket per meter (kg/m) 0.0735 Volume of Insulation (M ) Mass of Insulation per meter (kg/m) 0.0125 Total 4.10804E-06 Total Combustible Volume (Mi) 1.96485E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 1615.6 Number of Cables Total Width of Cables 0.013
L-2002-070 Attachment 2 Page 155 of 230 Cable Tray ID CIOI-2306 Cable Type 5/C #16 XLPPP Outside Diameter (inches) .......
S*.... %. 0.013208 meters Insulation Material 3 Outer Jacket Thickness (mils) .5 . 0.001143 meters Insulation Density (kg/M )
S....... >.:........... .. :
Insulation Jacket Thickness (mils) .....0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material Num. Conds. S5 Jacket Density (kg/m3)
Diam. Cond. (inches) ....................... 0.00129 m eters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 1....... %...0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m2 Jacket Area 6.093E-05 m' Insulation Area 1.92E-05 M 3
Total Volume of Jacket (M ) 3 1.85752E-05 Mass of Jacket per meter (kg/m) 0.0878
)
Total Volume of Insulation (M 3 5.85494E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (in ) 2.44301 E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 1999.3 Num ber of Cables ...........
Total Width of Cables 0.013
L-2002-070 Attachment 2 Page 156 of 230 Cable Tray ID C101-2306 Cable Type '#12 XLPN (XLPPP)
................ 0.0127 meters Insulation Material ........
4.
Outside Diameter (inches) 3 Insulation Density (kg/M ) ....
Outer Jacket Thickness (mils) *......... 0.001143 meters Insulation Jacket Thickness (mils) *IS 0.000381 meters Insulation Heat of Combustion (kJ/kg) ...41. .....
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material Num. Conds. ...... 2 Jacket Density (kg/M3)
Diam. Cond. (inches)
- 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ............. 0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.0001267 m2 2
2 Jacket Area 5.097E-05 m Insulation Area 1.347E-05 m2 3
Total Volume of Jacket (M ) 3 1.55405E-05 Mass of Jacket per meter (kg/m) 0.0735
)
Total Volume of Insulation (M 4.10804E-06 Mass of Insulation per meter (kg/m) 0.0125 3
Total Combustible Volume (m ) 1.96485E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 4846.9 Number of Cables i Total Width of Cables 0.038
L-2002-070 Attachment 2 Page 157 of 230 Cable Tray ID CIOI-2306 Cable Type 5/C#l 6 XLPN (XLPPP)
Outside Diameter (inches) : 0.013208 meters Insulation Material 3 Outer Jacket Thickness (mils) A= =0.001143 meters Insulation Density (kg/M )
Insulation Jacket Thickness (mils) X..5K .0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ..... ... .......... 0.00064 meters Jacket Material 3 Num. Conds. 5 .5. Jacket Density (kg/m )
Diam. Cond. (inches) ..... 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) . 0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m' Jacket Area 6.093E-05 m2 Insulation Area 1.92E-05 m2 3
Total Volume of Jacket (M ) 3 1.85752E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (M 3) 5.85494E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (M ) 2.44301 E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 7997.2 Number of Cables :
Total Width of Cables 0.053
L-2002-070 Attachment 2 Page 158 of 230 Cable Tray ID CI01-2306 Cable Type 2/C#16 XLPPP Outside Diameter (inches) * .........0.010414 meters Insulation Material Outer Jacket Thickness (mils) 45 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 15 000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material 3 Num. Conds.
2 ............ 2 Jacket Density (kg/M )
Diam. Cond. (inches) i 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) S*.....................
0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 m2 Jacket Area 4.033E-05 m2 2
Insulation Area 7.682E-06 M Total Volume of Jacket (m2) 1.22963E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (Mi)3 2.34198E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (M ) 1.46383E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 3638.4 Number of Cables S Total Width of Cables 0.031 Total Width (m) 0.148 Total Energy (kUJ/m) 20097.5
L-2002-070 Attachment 2 Page 159 of 230 Cable Tray ID M120-2308 Cable Type 3-I/C #410
... ................ XLPP Outside Diameter (inches) *.!.i..... 0.020904 meters Insulation Material 92 44.
Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kglm 3) ..
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/kg) 441....
Conduct. Insul. Thickness (mils) 66.. 0.00140 meters Jacket Material .... ..
Num. Conds. 1 Jacket Density (kg/m 3)
Diam. Cond. (inches) 0.011684 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) 0.304878 meters Outside Radius 0.0104521 m 2
Total Cable Area (A3) 0.0003432 m2 Jacket Area 7.096E-05 m Insulation Area 5.741 E-05 M2 Total Volume of Jacket (m 3) 2.16E-05 Mass of Jacket per meter (kg/m) 0.1023 Total Volume of Insulation (m3)3 1.75E-05 Mass of Insulation per meter (kg/m) 0.0531 Total Combustible Volume (M ) 3.91 E-05 Total Combustible Mass per meter (kglm) 0.1554 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1836.4 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1263.1 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 3099.5 Combustible Fuel Load per meter (kJ/m) 74388.2 Number of Cables * ..........
Total Width of Cables 0.502
L-2002-070 Attachment 2 Page 160 of 230 Cable Tray ID C120-2308 Cable Type 2/C#12 XLPN (XLPPP)
Outside Diameter (inches) 0.0127 meters Insulation Material 3 U-244ý"
Outer Jacket Thickness (mils) *4 *.................. 0.001143 meters Insulation Density (kg/im ) ........
Insulation Jacket Thickness (mils) Insulation Heat of Combustion (kJ/kg) 1441.......... .....
Conduct. Insul. Thickness (mils) . 0.00076 meters Jacket Material 3
~ Jacket Density (kg/M )
Num. Conds. 2 Diam. Cond. (inches) ...... i 0.002052 meters
- i$Q Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.00635 m 2
Total Cable Area (A3) 0.0001267 m Jacket Area 5.097E-05 m 1.347E-05 m22 Insulation Area 3
Total Volume of Jacket (m ) 3 1.55405E-05 Mass of Jacket per meter (kg/m) 0.0735
)
Total Volume of Insulation (M 4.10804E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (m3) 1.96485E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 1615.6 Number of Cables ..................:
Total Width of Cables 0.013
L-2002-070 Attachment 2 Page 161 of 230 Cable Tray ID C120-2308 Cable Type 5/C#16 XLPN (XLPPP)
... ......... 0.013208 meters Outside Diameter (inches) Insulation Material 3 24.4......
Outer Jacket Thickness (mils) S....................... 0. 03 1 meters 45 0001143 m t r Insulation Density (kg/m ) ..........
15 0.000381 metr Pot)
(*~* ~ ~ fe..........
Insulation Jacket Thickness (mils) Insulation Heat of Combustion (kJlkg) 441..
1... .... T .. ....
Conduct. Insul. Thickness (mils) S........... 0.00064 meters Jacket Material 3 Num. Conds. 55 Jacket Density (kg/im )
Diam. Cond. (inches) t::::: 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m' Jacket Area 6.093E-05 m2 Insulation Area 1.92E-05 m2 3
Total Volume of Jacket (M ) 1.85752E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (Mi) 5.85494E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m3) 2.44301 E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 1999.3 Number of Cables i Total Width of Cables 0.013
L-2002-070 Attachment 2 Page 162 of 230 Cable Tray ID C120-2308 Cable Type XLPN (XLPPP)
Outside Diameter (inches) 0.018796 meters Insulation Material 3 Outer Jacket Thickness (mils) 0.001524 meters Insulation Density (kg/M )
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJlkg)
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material 3 Num. Conds. 7 Jacket Density (kg/m )
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.009398 m Total Cable Area (A3) 0.0002775 m2 2
Jacket Area 0.0001159 m2 Insulation Area 4.716E-05 M2 Total Volume of Jacket (mi3 ) 3 3.53206E-05 Mass of Jacket per meter (kg/m) 0.1670
)
Total Volume of Insulation (M 3 1.43781 E-05 Mass of Insulation per meter (kg/m) 0.0436 Volume (M )
Total Combustible 4.96987E-05 Total Combustible Mass per meter (kg/m) 0.2106 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 2998.3 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1037.6 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4035.8 Combustible Fuel Load per meter (kJ/m) 4035.8 Number of Cables :
Total Width of Cables 0.019
L-2002-070 Attachment 2 Page 163 of 230 Cable Tray ID C120-2308 Cable Type '#12 MCCC Outside Diameter (inches) * *...- 0.016256 meters Insulation Material 3 .......... ..... .. ......
Outer Jacket Thickness (mils) ................ 0.001651 meters Insulation Density (kg/M )
Insulation Jacket Thickness (mils) .. o0. meters Insulation Heat of Combustion (kJ/kg) . : : ......: : :..= . = = = =
Conduct. Insul. Thickness (mils) 0.00102 meters Jacket Material 1 .4. .
Num. Conds. 8..::::::........ 5 Jacket Density (kg/m3)
Diam. Cond. (inches) 1 iQi 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ................ 0.304878 meters Outside Radius 0.008128 m Total Cable Area (A3) 0.0002075 M Jacket Area 7.575E-05 m2 Insulation Area 4.897E-05 m2 Total Volume of Jacket (m 3 ) 3 2.30954E-05 Mass of Jacket per meter (kg/m) 0.1092 Total Volume of Insulation (M 3) 1.49293E-05 Mass of Insulation per meter (kg/m) 0.0453 Total Combustible Volume (M ) 3.80247E-05 Total Combustible Mass per meter (kg/m) 0.1545 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1960.5 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1077.3 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 3037.8 Combustible Fuel Load per meter (kJ/m) 3037.8 Number of Cables i Total Width of Cables 0.016
L-2002-070 Attachment 2 Page 164 of 230 Cable Tray ID C120-2308 Cable Type 2/C#16 XLPPP Outside Diameter (inches) 41 0.010414 meters Insulation Material Outer Jacket Thickness (mils) 0.001143
.4............. meters Insulation Density (kg/M3)
Insulation Jacket Thickness (mils) 1 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material 3 Num. Conds. . 2...... 2 Jacket Density (kg/M )
Diam. Cond. (inches) $Q: 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 M22 Jacket Area 4.033E-05 m2 Insulation Area 7.682E-06 m 3
Total Volume of Jacket (M ) 3 1.22963E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m 3) 2.34198E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (M ) 1.46383E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 6064.0 Number of Cables i Total Width of Cables 0.052 Total Width (m) 0.113 Total Energy (kJ/m) 16752.6
L-2002-070 Attachment 2 Page 165 of 230 Cable Tray ID M102-2245 Cable Type 3/C #8 XLPP Outside Diameter (inches) 0A i 0.021488 meters Insulation Material 3 So924..
. 4..
Outer Jacket Thickness (mils) 3Q 0.001524 meters Insulation Density (kg/m ) : Z 38Jb:::
.**..'" '*"M
- "9 " j". ...
Insulation Jacket Thickness (mils) 5.......... 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00114 meters Jacket Material 3 ..
Num. Conds. 3 l 3 Jacket Density (kg/m )
Diam. Cond. (inches) S 0.003264
................ 0 meters meters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) X..:
............. 0.304878 iiiiii meters Outside Radius 0.0107442 m Total Cable Area (A3) 0.0003627 m2 Jacket Area 0.0001169 m2 2
Insulation Area 4.747E-05 m 3
Total Volume of Jacket (M ) 3 3.56348E-05 Mass of Jacket per meter (kg/m) 0.1685
)
Total Volume of Insulation (M 1.44736E-05 Mass of Insulation per meter (kg/m) 0.0439 3
Total Combustible Volume (m ) 5.01084E-05 Total Combustible Mass per meter (kg/m) 0.2124 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 3024.9 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1044.4 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4069.4 Number of Cables ................. Combustible Fuel Load per meter (kJ/m) 4069.4 Total Width of Cables 0.021
L-2002-070 Attachment 2 Page 166 of 230 Cable Tray ID M102-2245 Cable Type 3/C #12 XLPP (XLPPP)
Outside Diameter (inches) : $t i 0.015723 meters Insulation Material Outer Jacket Thickness (mils) 60 0.001524 meters 3 Insulation Density (kg/M )
9............ .. . . . . . . . . . . . . . . . . . . . .... . .
Insulation Jacket Thickness (mils) .............. 0.000381 meters Insulation Heat of Combustion (kJ/kg) .......... .........
Z...3........ f~
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Matedal .. .. . .. .. .. .
3 Num. Conds.
Diam. Cond. (inches) 3: 3 Jacket Density (kg/M )
1 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) 1: 0.304878 meters Outside Radius 0.0078613 m Total Cable Area (A3) 0.0001942 m2 Jacket Area 8.219E-05 m2 2
Insulation Area 2.021E-05 m 3
Total Volume of Jacket (M ) 3 2.50579E-05 Mass of Jacket per meter (kg/m) 0.1185 Total Volume of Insulation (M 3) 6.16206E-06 Mass of Insulation per meter (kg/m) 0.0187 Total Combustible Volume (M ) 3.122E-05 Total Combustible Mass per meter (kg/m) 0.1372 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 2127.1 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 444.7 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2571.8 Combustible Fuel Load per meter (kJ/m) 2571.8 Number of Cables .......
Total Width of Cables 0.016 Total Width (m) 0.037 Total Energy (kJ/m) 6641.2
L-2002-070 Attachment 2 Page 167 of 230 Cable Tray ID C103-2245 Cable Type 7#16 XLPPP Outside Diameter (inches) 4 0.010414 meters Insulation Material 3 Outer Jacket Thickness (mils) 001143 meters
- 4**iiiiiiiiiiii
- i.i::
O0. Insulation Density (kg/M )
Insulation Jacket Thickness (mils) M*x: 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material 17iiiii 6fl~;; ............
Num. Conds. Jacket Density (kg/m 3) .....................
Diam. Cond. (inches) ................ 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .......... 0.304878 meters Outside Radius 0.005207 m2 Total Cable Area (A3) 8.518E-05 M 2
Jacket Area 4.033E-05 m2 Insulation Area 7.682E-06 m 3
Total Volume of Jacket (m ) 3 1.22963E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (M3) 2.34198E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (M ) 1.46383E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.018 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.002 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.020 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 18192.1 Number of Cables i Total Width of Cables 0.156
L-2002-070 Attachment 2 Page 168 of 230 Cable Tray ID C103-2245 Cable Type 3#1 2 XLPPP Outside Diameter (inches) *8 0.0127 meters Insulation Material 3 Outer Jacket Thickness (mils) ............ 0.001143 meters Insulation Density (kg/M )
Insulation Jacket Thickness (mils)
- 0*0000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material 3
Num. Conds. 22 Jacket Density (kg/m )
Diam. Cond. (inches) . . 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ............... 0.304878 meters Outside Radius 0.00635 m 2 Total Cable Area (A3) 0.0001267 M 2
Jacket Area 5.097E-05 M Insulation Area 1.347E-05 m2 3
Total Volume of Jacket (M ) 3 1.55405E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (M 3) 4.10804E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (M ) 1.96485E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 19387.6 Number of Cables ......... .........
Total Width of Cables 0.152
L-2002-070 Attachment 2 Page 169 of 230 Cable Tray ID C103-2245 Cable Type 5/C#16 XLPPP Outside Diameter (inches) .......................0.013208 meters Insulation Material C..........................
Outer Jacket Thickness (mils) :: : 0.001143 meters Insulation Density (kg/mi) O ..
i.......
... 0.000381 meters Insulation Heat of Combustion (kJ/kg) 1..............
Insulation Jacket Thickness (mils) .... 0.00064 meters Jacket Material Conduct. Insul. Thickness (mils) .. ....................
3 Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) OOi43 i 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) S 0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m' Jacket Area 6.093E-05 m2 2
Insulation Area 1.92E-05 m 3
Total Volume of Jacket (M ) 3 1.85752E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (M 3) 5.85494E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (M ) 2.44301 E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.027 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.005 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.032 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 7997.2 Number of Cables .................
Total Width of Cables 0.053
L-2002-070 Attachment 2 Page 170 of 230 Cable Tray ID C103-2245 Cable Type 71C #12 XLPPP Outside Diameter (inches) o0.018792 meters Insulation Material 3 Outer Jacket Thickness (mils) ::::::::::
- :::::::::::0.001524
- meters Insulation Density (kg/M )
Insulation Jacket Thickness (mils) 1~ 0.000:381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material Num. Conds. 77 Jacket Density (kg/m3)
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.009398 m Total Cable Area (A3) 0.0002775 m22 Jacket Area 0.0001159 m 2
Insulation Area 4.716E-05 m 3
Total Volume of Jacket (M ) 3 3.53206E-05 Mass of Jacket per meter (kg/m) 0.1670 Total Volume of Insulation (M 3) 1.43781E-05 Mass of Insulation per meter (kg/m) 0.0436 Total Combustible Volume (M ) 4.96987E-05 Total Combustible Mass per meter (kg/m) 0.2106 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 2998.3 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1037.6 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4035.8 Combustible Fuel Load per meter (kJ/m) 4035.8 Number of Cables .......... ..
Total Width of Cables 0.019
L-2002-070 Attachment 2 Page 171 of 230 Cable Tray ID C103-2245 Cable Type 2- Armored Cable XLPE (XLPPP)
Outside Diameter (inches) 5 0.0127 meters Insulation Material 3
Outer Jacket Thickness (mils) .. 0.001143 meters Insulation Density (kg/m )
Insulation Jacket Thickness (mils) 5 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material 3 Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ........ 0.304878 meters Outside Radius 0.00635 m2 Total Cable Area (A3) 0.0001267 M 2 Jacket Area 5.097E-05 M2 Insulation Area 1.347E-05 m Total Volume of Jacket (Mi) 3 1.55405E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (M ) 4.10804E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (mn) 1.96485E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 0.0 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 0.0 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 0.0 Combustible Fuel Load per meter (kJ/m) 0.0 Number of Cables :.:::.:...........::. .
Total Width of Cables 0.025
L-2002-070 Attachment 2 Page 172 of 230 Cable Tray ID C103-2245 Cable Type '#12 XLPPP Outside Diameter (inches) : 0.017272 meters Insulation Material Insulation Density (kgIMr) ..................... ten e Outer Jacket Thickness (mils) ................ 0.001524 meters ..............
Insulation Jacket Thickness (mils) S 0.000381 meters Insulation Heat of Combustion (kJlkg)
Jacket Material Conduct. Insul. Thickness (mils) 0.00076 meters 3 Num. Conds. 85 Jacket Density (kg/m )
Diam. Cond. (inches) ................0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) : 0 0304878 meters Outside Radius 0.008636 m 2
Total Cable Area (A3) 0.0002343 m2 Jacket Area 9.908E-05 M 2 Insulation Area 3.369E-05 m Total Volume of Jacket (Mi) 3.02078E-05 Mass of Jacket per meter (kg/m) 0.1429 Total Volume of Insulation (Mi) 1.02701 E-05 Mass of Insulation per meter (kg/m) 0.0311 Total Combustible Volume (Mi) 4.04779E-05 Total Combustible Mass per meter (kg/m) 0.1740 Total Mass of Jacket (kg) 0.044 Jacket heat of combustion energy per meter (kJ/m) 2564.3 Total Mass of Insulation (kg) 0.009 Insulation heat of combustion energy per meter (kJ/m) 741.1 Total Combustible Mass (kg) 0.053 Combustible Fuel Load per meter per cable (kJ/m) 3305.4 Combustible Fuel Load per meter (kJ/m) 3305.4 Number of Cables ::.:..::.::
Total Width of Cables 0.017
L-2002-070 Attachment 2 Page 173 of 230 Cable Tray ID C103-2245 Cable Type 2/C#16 XLPN (XLPPP)
Outside Diameter (inches) : : 0010414 meters Insulation Material 3 Outer Jacket Thickness (mils) ............ 0.001143 meters Insulation Density (kg/M )
Insulation Jacket Thickness (mils) 1 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ...................... 0.00064 meters Jacket Material 3 Num. Conds. 2 Jacket Density (kg/M )
Diam. Cond. (inches) 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 m' Jacket Area 4.033E-05 m' Insulation Area 7.682E-06 m2 3
Total Volume of Jacket (M ) 3 1.22963E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m ) 2.34198E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (rn3 ) 1.46383E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 1212.8 Number of Cables ::::::: ...... :::::::::
Total Width of Cables 0.010
L-2002-070 Attachment 2 Page 174 of 230 Cable Tray ID C103-2245 Cable Type 5/C#16 XLPN (XLPPP)
Outside Diameter (inches) :52: 0.013208 meters Insulation Material . d......
Carbonblack ro....... e..
3 Outer Jacket Thickness (mils) 4Ii i 0.001143 meters Insulation Density (kg/M ) ..........................
Insulation Jacket Thickness (mils) 1 i 0.000381 meters Insulation Heat of Combustion (kJ/kg) ............
Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material 3 Num. Conds. 55 Jacket Density (kg/m )
Diam. Cond. (inches) &!8
................. 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ...................... 0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m' Jacket Area 6.093E-05 m' Insulation Area 1.92E-05 m2 3
Total Volume of Jacket (mi ) 3 1.85752E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (M ) 5.85494E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m3) 2.44301 E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 5997.9 Number of Cables ..........
Total Width of Cables 0.040
L-2002-070 Attachment 2 Page 175 of 230 Cable Tray ID C103-2245 Cable Type ,#12 SP Outside Diameter (inches) == 0.012802 meters Insulation Material 3 E............................................
Outer Jacket Thickness (mils) .......... 0.001143 meters Insulation Density (kg/M ) ...
Insulation Jacket Thickness (mils) 15 0.000381 meters Insulation Heat of Combustion (kJ/kg) .................... ............
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material 3 Jacket Density (kg/m ) .14......4.......... ..
Num. Conds.
Diam. Cond. (inches) . 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ............... 0.304878 meters Outside Radius 0.0064008 m Total Cable Area (A3) m2 0.0001287 2 Jacket Area 4.951 E-05 m Insulation Area 9.826E-06 m2 3
Total Volume of Jacket (M ) 3 1.50956E-05 Mass of Jacket per meter (kg/m) 0.0714 Total Volume of Insulation (M ) 2.99575E-06 Mass of Insulation per meter (kg/m) 0.0091 3 0.0805 Total Combustible Volume (m ) 1.80913E-05 Total Combustible Mass per meter (kg/m)
Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 1281.4 Total Mass of Insulation (kg) 0.003 Insulation heat of combustion energy per meter (kJ/m) 216.2 Total Combustible Mass (kg) 0.025 Combustible Fuel Load per meter per cable (kJ/m) 1497.6 Combustible Fuel Load per meter (kJ/m) 2995.2 Number of Cables i Total Width of Cables 0.026
L-2002-070 Attachment 2 Page 176 of 230 Cable Tray ID C103-2245 Cable Type 5/C #12 SP (XLPPP)
Outside Diameter (inches) . 0.016967 meters Insulation Material ...
3 ........
Outer Jacket Thickness (mils) .. *.....* 0.001524
.i..... meters Insulation Density (kg/M ) ...
Insulation Jacket Thickness (mils) 0.000381
......... meters Insulation Heat of Combustion (kJ/kg) ...
4...
Conduct. Insul. Thickness (mils) ............. 0.00076 meters Jacket Material 17.........
3 Num. Conds.
5iii~~~~~~~~~!
iiiiiii 5 Jacket Density (kg/m )
Diam. Cond. (inches) 00505 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .....1..
...... 0.304878 meters Outside Radius 0.0084836 m 2 Total Cable Area (A3) 0.0002261 m2 Jacket Area 9.306E-05 m Insulation Area 2.457E-05 M2 3
Total Volume of Jacket (M ) 3 2.83725E-05 Mass of Jacket per meter (kg/m) 0.1342 Total Volume of Insulation (M 3) 7.48938E-06 Mass of Insulation per meter (kg/m) 0.0227 Total Combustible Volume (M ) 3.58619E-05 Total Combustible Mass per meter (kg/m) 0.1569 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 2408.5 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 540.5 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2948.9 Combustible Fuel Load per meter (kJ/m) 2948.9 Number of Cables :
Total Width of Cables 0.017 Total Width (m) 0.616 Total Energy (kJ/m) 66073.0
L-2002-070 Attachment 2 Page 177 of 230 Cable Tray ID M102-2247 Cable Type 3/C #12 XLPP (XLPPP)
SI9'*d""**.-
..,.......-.-..... 0.015723 meters Outside Diameter (inches) Insulation Material Outer Jacket Thickness (mils) S0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) S0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) .I.......... 0.00076 meters Jacket Material 3 Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches)
- i 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) . 0.304878 meters Outside Radius 0.0078613 m2 Total Cable Area (A3) 0.0001942 m Jacket Area 8.219E-05 m2 2
Insulation Area 2.021 E-05 M 3
Total Volume of Jacket (M ) 3 2.51 E-05 Mass of Jacket per meter (kg/m) 0.1185 Total Volume of Insulation (m ) 6.16E-06 Mass of Insulation per meter (kglm) 0.0187 Total Combustible Volume (m3) 3.12E-05 Total Combustible Mass per meter (kg/m) 0.1372 Total Mass of Jacket (kg) 0.036 Jacket heat of combustion energy per meter (kJ/m) 2127.1 Total Mass of Insulation (kg) 0.006 Insulation heat of combustion energy per meter (kJ/m) 444.7 Total Combustible Mass (kg) 0.042 Combustible Fuel Load per meter per cable (kJ/m) 2571.8 Combustible Fuel Load per meter (kJ/m) 2571.8 Number of Cables I................
Total Width of Cables 0.016
L-2002-070 Attachment 2 Page 178 of 230 Cable Tray ID C103-2247 Cable Type 2/C#16 XLPPP Outside Diameter (inches) :11 0.010414 meters Insulation Material Outer Jacket Thickness (mils) i 0.001143 meters Insulation Density (kg/m&)
Insulation Jacket Thickness (mils) ; 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ..:......:.:::::::: 0.00064 meters Jacket Material 3 Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) i 8.! 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) : 0.304878 meters Outside Radius 0.005207 m 2
Total Cable Area (A3) 8.518E-05 m2 Jacket Area 4.033E-05 M 2
Insulation Area 7.682E-06 M Total Volume of Jacket (m3) 3 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m 3
) 0.0071 2.34E-06 Mass of Insulation per meter (kg/m)
Total Combustible Volume (m ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.018 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.002 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.020 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 2425.6 Number of Cables .
Total Width of Cables 0.021
L-2002-070 Attachment 2 Page 179 of 230 Cable Tray ID C103-2247 Cable Type ,#12 XLPPP Outside Diameter (inches) ... *.5 0.0127 meters Insulation Material Outer Jacket Thickness (mils) 05 0001143
.......... meters Insulation Density (kglm 3)
Insulation Jacket Thickness (mils) S0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) .. 0.00076 meters Jacket Material 3 Num. Conds. ............. 2 Jacket Density (kg/m )
Diam. Cond. (inches) *I0 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) : 0.304878 meters Outside Radius 0.00635 m 0.0001267 M2 Total Cable Area (A3) 2 Jacket Area 5.097E-05m22 Insulation Area 1.347E-05 mi Total Volume of Jacket (min3)3 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (M ) 4.11E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (m3) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 6462.5 Num ber of Cables ........................
Total Width of Cables 0.051
L-2002-070 Attachment 2 Page 180 of 230
.. .0 Cable Tray ID C103-2247 Cable Type 5/C#16 XLPPP Insulation Material .. .............. MO ............
Outside Diameter (inches) 052
...... 0.013208 meters :c ..%..%
......... ah.b ..
Outer Jacket Thickness (mils) 5 0.001143 meters Insulation Density (kg/mi) W4'
- 1..... ...0.000381 meters Insulation Heat of Combustion (kJ/kg)
Insulation Jacket Thickness (mils)
Jacket Material .. ...............
Conduct. Insul. Thickness (mils) 2. 0.00064 meters "'PAW"
..................... -A
.0 Y..".".0"O'b .................
Num. Conds. 5 Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg) ..........
Diam. Cond. (inches) .............
- (*i .i 0.00129 meters ..............
Cable Length (feet) .............. 0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m2 2
Jacket Area 6.093E-05 m 2
Insulation Area 1.92E-05 m 3
Total Volume of Jacket (M ) 3 1.86E-05 Mass of Jacket per meter (kglm) 0.0878 Total Volume of Insulation (M 3) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m ) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.027 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.005 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.032 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 7997.2 Number of Cables ......
Total Width of Cables 0.053
L-2002-070 Attachment 2 Page 181 of 230 Cable Tray ID C103-2247 Cable Type MCCC (XLPPP for Insul. Jacket thickness)
Outside Diameter (inches) 0.017526 meters Insulation Material z....i.....
3 Outer Jacket Thickness (mils) 0.001651 meters Insulation Density (kg/m ) 2.4.....
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/kg) .
Conduct. Insul. Thickness (mils) 0.00102 meters Jacket Material I. ::::::::::::::::::::::::::::.-..
W .: -... t*.-.-d... .......................
P, m . . . . . . . . . . .
3 Num. Conds. 7 Jacket Density (kg/m ) 1441.
0.002052 meters Jacket Heat of Combustion (kJ/kg) ......
Diam. Cond. (inches)
Cable Length (feet) 0.304878 meters Outside Radius 0.008763 m 2
Total Cable Area (A3) 0.0002412 m Jacket Area 8.234E-05 m2 2
Insulation Area 6.856E-05 M Total Volume of Jacket (m 3) 2.51 E-05 Mass of Jacket per meter (kg/m) 0.1187 Total Volume of Insulation (m3) 3 2.09E-05 Mass of Insulation per meter (kg/m) 0.0634 Total Combustible Volume (M ) 4.6E-05 Total Combustible Mass per meter (kglm) 0.1821 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 2131.0 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1508.3 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 3639.3 Combustible Fuel Load per meter (kJ/m) 10917.8 Number of Cables ..........
Total Width of Cables 0.053
L-2002-070 Attachment 2 Page 182 of 230 Cable Tray ID C103-2247 Cable Type 5/C #12 XLPPP Outside Diameter (inches) 68 0.017272 meters Insulation Material Outer Jacket Thickness (mils) iG 0001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) I 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) Jacket Material 3 Num. Conds. Jacket Density (kglm )
Diam. Cond. (inches) f00 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) . . 0.304878 meters Outside Radius 0.008636 m Total Cable Area (A3) 0.0002343 m2 9.908E-05 m2 Jacket Area 2
Insulation Area 3.369E-05 M 3
Total Volume of Jacket (M ) 3.02E-05 Mass of Jacket per meter (kg/m) 0.1429 3
Total Volume of Insulation (m 3) 1.03E-05 Mass of Insulation per meter (kg/m) 0.0311 Total Combustible Volume (M ) 4.05E-05 Total Combustible Mass per meter (kg/m) 0.1740 Total Mass of Jacket (kg) 0.044 Jacket heat of combustion energy per meter (kJ/m) 2564.3 Total Mass of Insulation (kg) 0.009 Insulation heat of combustion energy per meter (kJ/m) 741.1 Total Combustible Mass (kg) 0.053 Combustible Fuel Load per meter per cable (kJ/m) 3305.4 Combustible Fuel Load per meter (kJ/m) 3305.4 Number of Cables .... ...
Total Width of Cables 0.017
L-2002-070 Attachment 2 Page 183 of 230 Cable Tray ID C103-2247 Cable Type XLPN (XLPPP)
Outside Diameter (inches) 0.010414 meters Insulation Material Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material 3 Num. Conds. 2 Jacket Density (kglm )
Diam. Cond. (inches) 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.005207 m2 Total Cable Area (A3) 8.518E-05 m Jacket Area 4.033E-05 m2 2
Insulation Area 7.682E-06 m Total Volume of Jacket (m 3) 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m3) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 3
Total Combustible Volume (m ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJim) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Number of Cables ...
........... Combustible Fuel Load per meter (kJ/m) 1212.8 Total Width of Cables 0.010
L-2002-070 Attachment 2 Page 184 of 230 Cable Tray ID C103-2247 Cable Type #12 XLPPP Outside Diameter (inches) 4 0.018796 meters Insulation Material Outer Jacket Thickness (mils) ............ 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) S 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ............. 0.00076 meters Jacket Material 3 Num. Conds. 7~~~~~~~~~~ 7 Jacket Density (kglm )
Diam. Cond. (inches) :0$ 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) i 0.304878 meters Outside Radius 0.009398 m 2
Total Cable Area (A3) 0.0002775 m 0.000,1159 M2 Jacket Area 2 Insulation Area 4.716E-05 M Total Volume of Jacket (mi3 ) 3.53E-05 Mass of Jacket per meter (kg/m) 0.1670 Total Volume of Insulation (m3)3 1.44E-05 Mass of Insulation per meter (kg/m) 0.0436 (M )
Total Combustible Volume 4.97E-05 Total Combustible Mass per meter (kg/m) 0.2106 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 2998.3 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1037.6 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJim) 4035.8 Combustible Fuel Load per meter (kJ/m) 4035.8 Num ber of C ables ............
Total Width of Cables 0.019
L-2002-070 Attachment 2 Page 185 of 230 Cable Tray ID C103-2247 Cable Type 2/C #12 SP Outside Diameter (inches) 050 ~ 0.012802 meters Insulation Material Outer Jacket Thickness (mils) 5i.. ii 0.001143 meters Insulation Density (kg/m3)
Insulation Jacket Thickness (mils) 4i i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ::.:.... 0.00076 meters Jacket Material Num. Conds. 2 2 Jacket Density (kg/mi)
Diam. Cond. (inches) ; . 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ...................... 0.304878 meters Outside Radius 0.0064008 m Total Cable Area (A3) 0.0001287 m' 2
Jacket Area 5.134E-05 m 2
Insulation Area 1.347E-05 M 3
Total Volume of Jacket (M )
3 1.57E-05 Mass of Jacket per meter (kg/m) 0.0740 Total Volume of Insulation (M ) 4.11 E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (m) 1.98E-05 Total Combustible Mass per meter (kg/m) 0.0865 Total Mass of Jacket (kg) 0.023 Jacket heat of combustion energy per meter (kJ/m) 1328.6 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 1625.1 Combustible Fuel Load per meter (kJ/m) 3250.2 Number of Cables ...........
Total Width of Cables 0.026 Total Width (m) 0.249 Total Energy (kJim) 39607.3
L-2002-070 Attachment 2 Page 186 of 230 Cable Tray ID Ml 27-222112225 Cable Type 3/C #8
%.-.% XLPP Outside Diameter (inches) 8 .6 0.021488 meters Insulation Material Outer Jacket Thickness (mils) .................. 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) ................. 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) Al ......
- ....* 0.00114 meters Jacket Material Num. Conds. 3 3 Jacket Density (kg/m 3 )
Diam. Cond. (inches) S0.003264 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) ...... .... 0.304878 meters Outside Radius 0.0107442 m Total Cable Area (A3) 0.0003627 m2 Jacket Area 0.0001169 m2 Insulation Area 4.747E-05 M2 Total Volume of Jacket (m3) 3.56E-05 Mass of Jacket per meter (kg/m) 0.1685 Total Volume of Insulation (m3) 3 1.45E-05 Mass of Insulation per meter (kg/m) 0.0439 Total Combustible Volume (m ) 5.01E-05 Total Combustible Mass per meter (kg/m) 0.2124 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 3024.9 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1044.4 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4069.4 Combustible Fuel Load per meter (kJ/m) 4069.4 Number of Cables i4iii Total Width of Cables 0.021
L-2002-070 Attachment 2 Page 187 of 230 Cable Tray ID M127-222112225 Cable Type 31C #12 XLPP (XLPPP)
Outside Diameter (inches) O6 : 0.015723 meters Insulation Material Outer Jacket Thickness (mils) G 0.001524 meters Insulation Density (kg/m) .. . . . . . . . . . . i;i Insulation Jacket Thickness (mils) S0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) :: : 0.00076 meters Jacket Material C...
a....... ..... . ...
Num. Conds. Jacket Density (kg/m3)
Diam. Cond. (inches) S0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) : 0.304878 meters Outside Radius 0.0078613 m Total Cable Area (A3) 0.0001942 m' 2
Jacket Area 8.219E-05 m 2
Insulation Area 2.021 E-05 M 3
Total Volume of Jacket (M ) 3 2.51 E-05 Mass of Jacket per meter (kg/m) 0.1185 Total Volume of Insulation (m 3) 6.16E-06 Mass of Insulation per meter (kg/m) 0.0187 Total Combustible Volume (M ) 3.12E-05 Total Combustible Mass per meter (kg/m) 0.1372 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 2127.1 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 444.7 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2571.8 Combustible Fuel Load per meter (kJ/m) 2571.8 Number of Cables Total Width of Cables 0.016
L-2002-070 Attachment 2 Page 188 of 230 Cable Tray ID M127-222112225 Cable Type 4 - 1/C #210 XLPN (XLPPP)
Outside Diameter (inches) 712 0.018085 meters Insulation Material Outer Jacket Thickness (mils) :................. 0.001143 meters Insulation Density (kg/m 3 )
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ......... 5....... 0.00140 meters Jacket Material 3 Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) ...................... 0.009266 m eters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) 1 0.304878 meters Outside Radius 0.0090424 m 2
Total Cable Area (A3) 0.0002569M 2 Jacket Area 6.084E-05M 2
Insulation Area 4.68E-05M 3
Total Volume of Jacket (M ) 3 1.85E-05 Mass of Jacket per meter (kg/m) 0.0877 (M )
Total Volume of Insulation 3 1.43E-05 Mass of Insulation per meter (kg/m) 0.0433 (M )
Total Combustible Volume 3.28E-05 Total Combustible Mass per meter (kg/m) 0.1310 Total Mass of Jacket (kg) 0.027 Jacket heat of combustion energy per meter (kJ/m) 1574.4 Total Mass of Insulation (kg) 0.013 Insulation heat of combustion energy per meter (kJ/m) 1029.6 Total Combustible Mass (kg) 0.040 Combustible Fuel Load per meter per cable (kJ/m) 2604.0 Number of Cables ..... Combustible Fuel Load per meter (kJ/m) 10416.1 Total Width of Cables 0.072 Total Width (m) 0.110 Total Energy (kJim) 17057.2
L-2002-070 Attachment 2 Page 189 of 230 Cable Tray ID C121-222112225 Cable Type 2/C#16 XLPPP Outside Diameter (inches) .................. 0.010414 meters Insulation Material :::::::::::::::::::
- ::::::::::::4::::::
Outer Jacket Thickness (mils) ................. 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) i............. 0.000381 meters Insulation Heat of Combustion (kJ/kg) : :::::::::::::::
Conduct. Insul. Thickness (mils) 2 : 0.00064 meters Jacket Material 3 Num. Conds. Jacket Density (kg/m ) 1441, Diam. Cond. (inches) O 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0..................
.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 m2 2
Jacket Area 4.033E-05 m2 Insulation Area 7.682E-06 m 3
Total Volume of Jacket (m ) 3 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m ) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 3
Total Combustible Volume (M ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.018 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.002 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.020 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 14553.7 Number of Cables .. ...
Total Width of Cables 0.125
L-2002-070 Attachment 2 Page 190 of 230 Cable Tray ID C121-222112225 Cable Type 5/C #10 XLPPP Outside Diameter (inches) 0.018796 meters Insulation Material Outer Jacket Thickness (mils) 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material 3 Num. Conds. 5 Jacket Density (kg/m )
Diam. Cond. (inches) 0.002588 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.009398 m Total Cable Area (A3) 0.0002775 m2 Jacket Area 0.0001096 m2 Insulation Area 4.01 E-05 m2 3
Total Volume of Jacket (mi ) 3 3.34E-05 Mass of Jacket per meter (kg/m) 0.1580 Total Volume of Insulation (M ) 1.22E-05 Mass of Insulation per meter (kg/m) 0.0371 Total Combustible Volume (m3) 4.56E-05 Total Combustible Mass per meter (kg/m) 0.1951 Total Mass of Jacket (kg) 0.048 Jacket heat of combustion energy per meter (kJ/m) 2836.1 Total Mass of Insulation (kg) 0.011 Insulation heat of combustion energy per meter (kJ/m) 882.2 Total Combustible Mass (kg) 0.059 Combustible Fuel Load per meter per cable (kJ/m) 3718.4 Combustible Fuel Load per meter (kJ/m) 3718.4 Number of Cables ......... ..........
Total Width of Cables 0.019
L-2002-070 Attachment 2 Page 191 of 230 Cable Tray ID C121-222112225 Cable Type "7/I4419 XLPN (XLPPP)
Outside Diameter (inches) 0.018796 meters Insulation Material Outer Jacket Thickness (mils) 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material 3 Num. Conds. 7 Jacket Density (kg/m )
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.009398 m Total Cable Area (A3) 0.0002775 m2 Jacket Area 0.0001159 m2 4.71 6E-05 m Insulation Area 3
Total Volume of Jacket (M )
3 3.53E-05 Mass of Jacket per meter (kg/m) 0.1670 Total Volume of Insulation (m ) 1.44E-05 Mass of Insulation per meter (kg/m) 0.0436 Total Combustible Volume (m3) 4.97E-05 Total Combustible Mass per meter (kg/m) 0.2106 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 2998.3 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1037.6 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4035.8 Combustible Fuel Load per meter (kJ/m) 4035.8 Number of Cables Total Width of Cables 0.019
L-2002-070 Attachment 2 Page 192 of 230 Cable Tray ID C121-222112225 Cable Type 2/C#12 XLPPP Outside Diameter (inches) G : 0.0127 meters Insulation Material 3
Outer Jacket Thickness (mils) i 0.001143 meters Insulation Density (kglm )
Insulation Jacket Thickness (mils) S0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) .... 000076 meters 3..0......... Jacket Material 2.......2 3 Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) *O i$ 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) S0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.0001267 m' Jacket Area 5.097E-05 mm22 1.347E-05 Insulation Area 3
Total Volume of Jacket (M ) 3 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m 3) 4.11 E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (M ) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJIm) 1319.2 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 19387.6 Number of Cables :::...................
Total Width of Cables 0.152
L-2002-070 Attachment 2 Page 193 of 230 Cable Tray ID C121-222112225 Cable Type 5/C #12 XLPN (XLPPP)
Outside Diameter (inches) a6b 0.017272 meters Insulation Material Outer Jacket Thickness (mils) 0 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) } 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ....
- 3 ... i 0.00076 meters Jacket Material 3 Num. Conds. 5 5 Jacket Density (kglm )
Diam. Cond. (inches) *0 i 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ...1..
........ 0.304878 meters Outside Radius 0.008636 m Total Cable Area (A3) 0.0002343 m' 2
Jacket Area 9.908E-05 m Insulation Area 3.369E-05 m2 Total Volume of Jacket (m3) 3 3.02E-05 Mass of Jacket per meter (kg/m) 0.1429 Total Volume of Insulation (m 3) 1.03E-05 Mass of Insulation per meter (kg/m) 0.0311 Total Combustible Volume (M ) 4.05E-05 Total Combustible Mass per meter (kg/m) 0.1740 Total Mass of Jacket (kg) 0.044 Jacket heat of combustion energy per meter (kJtm) 2564.3 Total Mass of Insulation (kg) 0.009 Insulation heat of combustion energy per meter (kJ/m) 741.1 Total Combustible Mass (kg) 0.053 Combustible Fuel Load per meter per cable (kUJ/m) 3305.4 Combustible Fuel Load per meter (kUJ/m) 13221.5 Number of Cables i Total Width of Cables 0.069
L-2002-070 Attachment 2 Page 194 of 230 Cable Tray ID C121-222112225 Cable Type XLPPP Outside Diameter (inches) 0.013208 meters Insulation Material Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00064 meters Jacket Material Num. Conds. 5 Jacket Density (kg/m3 Diam. Cond. (inches) 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.006604 m 0.000137 m 2 Total Cable Area (A3) 2 Jacket Area 6.093E-05 m Insulation Area 1.92E-05 m2 3
Total Volume of Jacket (M ) 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (m3) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m3) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.027 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.005 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.032 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 3998.6 Number of Cables ::::: :
Total Width of Cables 0.026
L-2002-070 Attachment 2 Page 195 of 230 Cable Tray ID C121-222112225 Cable Type 2/C #12 - Armored Cable XLPE (XLPPP)
Outside Diameter (inches) : 0.0127 meters Insulation Material Outer Jacket Thickness (mils) : 0.001143 meters Insulation Density (kg/m3) ... ....S...................................... .....
Insulation Jacket Thickness (mils) ..................... 0.000381 m eters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ! 0.00076 meters Jacket Material . ..
Num. Conds. 2 2 Jacket Density (kg/m3n .. 441.........
Diam. Cond. (inches) :.. 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .....
- ....... . 0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.0001267 m2 2
Jacket Area 5.097E-05 M Insulation Area 1.347E-05 m 2 3
Total Volume of Jacket (m ) 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m3) 4.11 E-06 Mass of Insulation per meter (kg/m) 0.0125 3
Total Combustible Volume (m ) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 0.0 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 0.0 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 0.0 Combustible Fuel Load per meter (kJ/m) 0.0 Number of Cables i Total Width of Cables 0.038
L-2002-070 Attachment 2 Page 196 of 230 Cable Tray ID C121-222112225 Cable Type 21C#16 XLPN (XLPPP)
Outside Diameter (inches) .................. 0.010414 meters Insulation Material Outer Jacket Thickness (mils) 5 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 2S 0.00064 meters Jacket Material Num. Conds. Jacket Density (kglm3)
Diam. Cond. (inches) iO iQ$ 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 1 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 m2 Jacket Area 4.033E-05 m2 2
Insulation Area 7.682E-06 M 3
Total Volume of Jacket (M ) 3 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (M 3) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (M ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJim) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 1212.8 Number of Cables Total Width of Cables 0.010
L-2002-070 Attachment 2 Page 197 of 230 Cable Tray ID C121-222112225 Cable Type 7/C #12 XLPPP Outside Diameter (inches) 74 0.018796 meters Insulation Material Outer Jacket Thickness (mils) B0* 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 1 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) i0 0.00076 meters Jacket Material 3 Num. Conds. Jacket Density (kg/in )
Diam. Cond. (inches) ::::::::***::::: 0.002052 meters Jacket Heat of Combustion (kJ/kg) 0.304878 m eters
- i~!iiii~~iiiii**;i;;!**iiii*i Cable Length (feet)
Outside Radius 0.009398 m Total Cable Area (A3) 0.0002775 m' Jacket Area 0.0001159 m2 2
Insulation Area 4.716SE-05 M Total Volume of Jacket (M3) 3.53E-05 Mass of Jacket per meter (kg/m) 0.1670 Total Volume of Insulation (m3) 1.44E-05 Mass of Insulation per meter (kg/m) 0.0436 3
Total Combustible Volume (m ) 4.97E-05 Total Combustible Mass per meter (kg/m) 0.2106 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 2998.3 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1037.6 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4035.8 Combustible Fuel Load per meter (kJ/m) 8071.7 Number of Cables ..........
Total Width of Cables 0.038
L-2002-070 Attachment 2 Page 198 of 230 Cable Tray ID C121-222112225 Cable Type 5/C #12 XLPPP Outside Diameter (inches) -68' 0.017272 meters Insulation Material Outer Jacket Thickness (mils) S. 60 ...: ...+ . 0.001524 meters
.........:.: Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 1, : 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) .......... ............... 0.00076
................... meters Jacket Material 3 Num. Conds. 5i 5 Jacket Density (kg/m )
Diam. Cond. (inches) ................... %-.-.- 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .......... ......... 0.304878 meters Outside Radius 0.008636 m Total Cable Area (A3) 0.0002343 m' Jacket Area 9.908E-05 m2 Insulation Area 3.369E-05 M2 3
Total Volume of Jacket (M ) 3 3.02E-05 Mass of Jacket per meter (kg/m) 0.1429 Total Volume of Insulation (in ) 1.03E-05 Mass of Insulation per meter (kg/m) 0.0311 Total Combustible Volume (m3) 4.05E-05 Total Combustible Mass per meter (kg/m) 0.1740 Total Mass of Jacket (kg) 0.044 Jacket heat of combustion energy per meter (kJ/m) 2564.3 Total Mass of Insulation (kg) 0.009 Insulation heat of combustion energy per meter (kJ/m) 741.1 Total Combustible Mass (kg) 0.053 Combustible Fuel Load per meter per cable (kJ/m) 3305.4 Combustible Fuel Load per meter (kJ/m) 9916.1 Number of Cables ............ ...........
Total Width of Cables 0.052
L-2002-070 Attachment 2 Page 199 of 230 Cable Tray ID C121-222112225 Cable Type 2/C #12 XLPN Outside Diameter (inches) ..........
- 5 0.0127 meters Insulation Material Outer Jacket Thickness (mils) 5 0.001143 meters Insulation Density (kglm 3)
Insulation Jacket Thickness (mils) 1* 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) .30 0.00076 meters Jacket Material Num. Conds. 2 2 Jacket Density (kg/m3)
Diam. Cond. (inches) S0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) S 0.304878 meters Outside Radius 0.00635 m 2
Total Cable Area (A3) 0.0001267 m Jacket Area 5.097E-05 m2 2
Insulation Area 1.347E-05 M 3
Total Volume of Jacket (M ) 3 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (M 3) 4.11 E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (M ) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 8078.2 Number of Cables .........:..........
Total Width of Cables 0.064
L-2002-070 Attachment 2 Page 200 of 230 Cable Tray ID C121-222112225 Cable Type 5/C #16 XLPN (XLPPP) i .52 0.013208 meters Insulation Material Outside Diameter (inches)
Outer Jacket Thickness (mils) 4; 0.001143 meters Insulation Density (kg/m 3) Caronblak 1~ ............
Insulation Jacket Thickness (mils) ........ 0.000381
.... meters Insulation Heat of Combustion (kJ/kg) ... .ii ii Conduct. Insul. Thickness (mils) 25 0.00064 meters Jacket Material 3 Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches)
- 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) *1... 0.304878
......... meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m2 2
Jacket Area 6.093E-05 m 2
Insulation Area 1.92E-05 M Total Volume of Jacket (m 3) 3 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (M3) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m ) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.027 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.005 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.032 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 17993.7 Number of Cables .. ..........
Total Width of Cables 0.119
L-2002-070 Attachment 2 Page 201 of 230 Cable Tray ID C121-222112225 Cable Type 7/C #12 MCCC (XLPPP for Insul. Jacket thicl Outside Diameter (inches) .........
6........ 0.017526 meters Insulation Material 3 Outer Jacket Thickness (mils) i5 0.001651 meters Insulation Density (kg/M )
Insulation Jacket Thickness (mils) S................. 0 00 m e er meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 40 0.00102 meters Jacket Material 7 7 3 Jacket Density (kg/m )
Num. Conds.
Diam. Cond. (inches) ........... 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) . 0.304878 meters Outside Radius 0.008763 m 2
Total Cable Area (A3) 0.0002412 m2 Jacket Area 8.234E-05m 2
Insulation Area 6.856E-05 M 3
Total Volume of Jacket (M ) 2.51 E-05 Mass of Jacket per meter (kg/m) 0.1187 Total Volume of Insulation (Mi)3 2.09E-05 Mass of Insulation per meter (kg/m) 0.0634 Total Combustible Volume (M ) 4.6E-05 Total Combustible Mass per meter (kg/m) 0.1821 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 2131.0 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1508.3 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 3639.3 Combustible Fuel Load per meter (kJ/m) 14557.0 Number of Cables %..%%
Total Width of Cables 0.070 Total Width (m) 0.801 0.61 m Tray width used Total Energy (kJim) 118745.1
L-2002-070 Attachment 2 Page 202 of 230 Cable Tray ID M1 27-2223 Cable Type 3/C #8 XLPP Outside Diameter (inches) ........... 0.021488 meters Insulation Material 6h,
...................... .... P.Py Outer Jacket Thickness (mils) 5G.:i.iK 0.001524 meters Insulation Density (kg/ma) :-9 -2.A:-'
Insulation Jacket Thickness (mils) == 0.000381 meters Insulation Heat of Combustion (kJ/kg) .................. .............................
Conduct. Insul. Thickness (mils) 0.00114 meters
..... Jacket Material Num. Conds. 3 Jacket Density (kg/m3 ...............
Diam. Cond. (inches) 0.003264 meters Jacket Heat of Combustion (kJ/kg) ......................
Cable Length (ft) 0.304878 meters Outside Radius 0.0107442 m Total Cable Area (A3) 0.0003627 m' 2
0.0001169 m Jacket Area Insulation Area 4.747E-05 M Total Volume of Jacket (m3) 3.56E-05 Mass of Jacket per meter (kg/m) 0.1685 Total Volume of Insulation (m3) 1.45E-05 Mass of Insulation per meter (kg/m) 0.0439 Total Combustible Volume (ma) 5.01E-05 Total Combustible Mass per meter (kg/m) 0.2124 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 3024.9 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1044.4 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4069.4 Combustible Fuel Load per meter (kJ/m) 4069.4 Number of Cables :
Total Width of Cables 0.021
L-2002-070 Attachment 2 Page 203 of 230 Cable Tray ID M127-2223 Cable Type 3/C #12 XLPP (XLPPP)
Outside Diameter (inches) B1: 0.015723 meters Insulation Material Outer Jacket Thickness (mils) 30 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) .......... 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) = 0.00076 meters Jacket Material Num. Conds. 3 3 Jacket Density (kg/m 3)
Diam. Cond. (inches) *i8Oi 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) .. ....... 0.304878 meters Outside Radius 0.0078613 m Total Cable Area (A3) 0.0001942 m' 2
Jacket Area 8.219E-05M 2
Insulation Area 2.021 E-05 m Total Volume of Jacket (m 3) 3 2.51 E-05 Mass of Jacket per meter (kg/m) 0.1185 Total Volume of Insulation (M ) 6.16E-06 Mass of Insulation per meter (kg/m) 0.0187 Total Combustible Volume (m3) 3.12E-05 Total Combustible Mass per meter (kg/m) 0.1372 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 2127.1 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJJ/m) 444.7 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2571.8 Combustible Fuel Load per meter (kJ/m) 2571.8 Number of Cables ...........
Total Width of Cables 0.016
L-2002-070 Attachment 2 Page 204 of 230 Cable Tray ID M127-2223 Cable Type 4- 1/C#2/0 XLPN (XLPPP)
Outside Diameter (inches) T12i 0.018085 meters Insulation Material 3
Outer Jacket Thickness (mils) meters .0.001143 Insulation Density (kglm )
Insulation Jacket Thickness (mils) .......... 0 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) S0.00140 meters Jacket Material Num. Conds. I Jacket Density (kg/m 3 )
Diam. Cond. (inches) 0.009266 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (ft) 0.304878 meters Outside Radius 0.0090424 m Total Cable Area (A3) 0.0002569 m2 Jacket Area 6.084E-05 m2 2
Insulation Area 4.68E-05 M Total Volume of Jacket (Mi) 1.85E-05 Mass of Jacket per meter (kg/m) 0.0877 Total Volume of Insulation (Mi) 1.43E-05 Mass of Insulation per meter (kg/m) 0.0433 Total Combustible Volume (m3) 3.28E-05 Total Combustible Mass per meter (kg/m) 0.1310 Total Mass of Jacket (kg) 0.027 Jacket heat of combustion energy per meter (kJ/m) 1574.4 Total Mass of Insulation (kg) 0.013 Insulation heat of combustion energy per meter (kJ/m) 1029.6 Total Combustible Mass (kg) 0.040 Combustible Fuel Load per meter per cable (kJ/m) 2604.0 Combustible Fuel Load per meter (kJ/m) 10416.1 Number of Cables :.: 4............
Total Width of Cables 0.072 Total Width (m) 0.110 Total Energy (kJIm) 17057.2
L-2002-070 Attachment 2 Page 205 of 230 Cable Tray ID C121-2223 Cable Type ,#16 XLPPP Outside Diameter (inches) i 0.010414 meters Insulation Material Outer Jacket Thickness (mils) 5 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) $5 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 2S 0.00064 meters Jacket Material 3
Num. Conds. : 2 Jacket Density (kg/m )
.... 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Diam. Cond. (inches)
Cable Length (feet) .............. 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 m' Jacket Area 4.033E-05 m2 Insulation Area 7.682E-06 m2 3
Total Volume of Jacket (M ) 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m3 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 3
Total Combustible Volume (m ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.018 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.002 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.020 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 13340.8 Number of Cables ...... ..........
Total Width of Cables 0.115
L-2002-070 Attachment 2 Page 206 of 230 Cable Tray ID C121-2223 Cable Type S#10 XLPPP Outside Diameter (inches) 4 0.018796 meters Insulation Material Outer Jacket Thickness (mils) 0 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils)
- 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils)
- 0.00076 meters Jacket Material 3 Num. Conds. Jacket Density (kg/im )
Diam. Cond. (inches) Q1i 0.002588 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) . 0.304878 meters Outside Radius 0.009398 m Total Cable Area (A3) 0.0002775 m2 Jacket Area 4.01 E-05 m 0.0001096 2 m2 Insulation Area Total Volume of Jacket (m 3) 3.34E-05 Mass of Jacket per meter (kg/m) 0.1580 Total Volume of Insulation (m3) 1.22E-05 Mass of Insulation per meter (kg/m) 0.0371 Total Combustible Volume (m3) 4.56E-05 Total Combustible Mass per meter (kglm) 0.1951 Total Mass of Jacket (kg) 0.048 Jacket heat of combustion energy per meter (kJ/m) 2836.1 Total Mass of Insulation (kg) 0.011 Insulation heat of combustion energy per meter (kJIm) 882.2 Total Combustible Mass (kg) 0.059 Combustible Fuel Load per meter per cable (kJ/m) 3718.4 Combustible Fuel Load per meter (kJ/m) 3718.4 Number of Cables i Total Width of Cables 0.019
L-2002-070 Attachment 2 Page 207 of 230 Cable Tray ID C121-2223 Cable Type Alf*9~- XLPN (XLPPP)
Outside Diameter (inches) 0.018796 meters Insulation Material Outer Jacket Thickness (mils) 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material 3
Num. Conds. 7 Jacket Density (kg/m )
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.009398 m Total Cable Area (A3) 0.0002775 m'2 Jacket Area 0.0001159 m 2
Insulation Area 4.71 6E-05 M Total Volume of Jacket (m 3) 3 3.53E-05 Mass of Jacket per meter (kg/m) 0.1670 Total Volume of Insulation (m
) 1.44E-05 Mass of Insulation per meter (kg/m) 0.0436 Total Combustible Volume (m3
) 4.97E-05 Total Combustible Mass per meter (kg/m) 0.2106 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJim) 2998.3 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1037.6 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4035.8 Combustible Fuel Load per meter (kJ/m) 4035.8 Number of Cables
- Total Width of Cables 0.019
L-2002-070 Attachment 2 Page 208 of 230 Cable Tray ID C1 21-2223 Cable Type 4ý -9 XLPPP Outside Diameter (inches) 0.0127 meters Insulation Material .6 k:
3 Outer Jacket Thickness (mils) 0.001143 meters Insulation Density (kg/m ) .................... .. ........ . ...... ... . . . .. . .
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material ......
.. 1 ...
I..................
Num. Conds. 2 Jacket Density (kg/mr3 Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.00635 m2 Total Cable Area (A3) 0.0001267 m 2
Jacket Area 5.097E-05m Insulation Area 1.347E-05m 2 3
Total Volume of Jacket (M ) 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m3) 4.11E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (M3) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 17772.0 Number of Cables i Total Width of Cables 0.140
L-2002-070 Attachment 2 Page 209 of 230 Cable Tray ID C121-2223 Cable Type #12 XLPN (XLPPP)
Outside Diameter (inches) 68 *6 0.017272 meters Insulation Material 3
Outer Jacket Thickness (mils) I 0.001524 meters Insulation Density (kg/m )
Insulation Jacket Thickness (mils) S0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) .J 0.00076 meters Jacket Material 3 Num. Conds. 5 5 Jacket Density (kglm )
Diam. Cond. (inches) S0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .. 0.....
0.304878 meters Outside Radius 0.008636 m Total Cable Area (A3) 0.0002343 m22 Jacket Area 9.908E-05 im 2
Insulation Area 3.369E-05 i 3
Total Volume of Jacket (m ) 3 3.02E-05 Mass of Jacket per meter (kg/m) 0.1429 Total Volume of Insulation (M 3) 1.03E-05 Mass of Insulation per meter (kg/m) 0.0311 Total Combustible Volume (m ) 4.05E-05 Total Combustible Mass per meter (kg/m) 0.1740 Total Mass of Jacket (kg) 0.044 Jacket heat of combustion energy per meter (kJ/m) 2564.3 Total Mass of Insulation (kg) 0.009 Insulation heat of combustion energy per meter (kJ/m) 741.1 Total Combustible Mass (kg) 0.053 Combustible Fuel Load per meter per cable (kJ/m) 3305.4 Combustible Fuel Load per meter (kJ/m) 13221.5 Number of Cables ..........
Total Width of Cables 0.069
L-2002-070 Attachment 2 Page 210 of 230 Cable Tray ID C121-2223 Cable Type #16
.................. XLPPP Outside Diameter (inches) 5 0.013208 meters Insulation Material Outer Jacket Thickness (mils) I 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) . 0.00064 meters Jacket Material 3
Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) -. ** 0.00129 meters Cable Length (feet) 1 0.304878 meters Outside Radius 0.006604 m Jacket Heat of Combustion (kJ/kg)
Total Cable Area (A3) 0.000137 m'2 Jacket Area 6.093E-05 im Insulation Area 1.92E-05 m2 Total Volume of Jacket (m 3) 3 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (M ) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m3) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.027 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.005 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.032 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 3998.6 Number of Cables ........................
Total Width of Cables 0.026
L-2002-070 Attachment 2 Page 211 of 230 Cable Tray ID C121-2223 Cable Type 2/C #12 - Armored Cable XLPE (XLPPP)
Outside Diameter (inches) ........ 0.0127 meters Insulation Material Outer Jacket Thickness (m ils) . 5.*..;. 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) ......... ........... 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 3-0 0.00076 meters Jacket Material 3
Num. Conds. 2 2 Jacket Density (kg/m )
Diam. Cond. (inches) Ci0 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.0001267 m2 2
Jacket Area 5.097E-05 m Insulation Area 1.347E-05 M 3
Total Volume of Jacket (m ) 3 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m ) 4.11 E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (m3) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 0.0 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 0.0 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 0.0 Combustible Fuel Load per meter (kJ/m) 0.0 Number of Cables Total Width of Cables 06038
L-2002-070 Attachment 2 Page 212 of 230 Cable Tray ID C121-2223 Cable Type ;#16 XLPN (XLPPP)
Outside Diameter (inches) 1
....-..........-... 0.010414 meters Insulation Material a..ff c..PRI P .. ........
e..............e
........ 4 Outer Jacket Thickness (mils) 15 0.001143 meters Insulation Density (kglm3)
Insulation Jacket Thickness (mils) S0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) :: 0.00064 meters Jacket Material ....441.......
3 Num. Conds. 2 2 Jacket Density (kg/M ) Rw~
Diam. Cond. (inches) *08- 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 1*,%............. 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 m' 2
Jacket Area 4.033E-05 m 2
Insulation Area 7.682E-06 M Total Volume of Jacket (m3) 3 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (M 3) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (m ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Number of Cables .: ... .......... Combustible Fuel Load per meter (kJ/m) 1212.8 Total Width of Cables 0.010
L-2002-070 Attachment 2 Page 213 of 230 Cable Tray ID C121-2223 7/r' 44V)
Cable Type XLPPP Outside Diameter (inches) 0.018796 meters Insulation Material 9244fl Outer Jacket Thickness (mils) 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg) .14 41........... .................
Conduct. Insul. Thickness (mils) 0.00076 meters Jacket Material 3
Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.009398 m Total Cable Area (A3) 0.0002775 m2 Jacket Area 0.0001159 m22 Insulation Area 4.716E-05 m Total Volume of Jacket (m 3) 3.53E-05 Mass of Jacket per meter (kg/m) 0.1670 Total Volume of Insulation (m3)3 1.44E-05 Mass of Insulation per meter (kg/m) 0.0436 Total Combustible Volume (M ) 4.97E-05 Total Combustible Mass per meter (kg/m) 0.2106 Total Mass of Jacket (kg) 0.1 Jacket heat of combustion energy per meter (kJ/m) 2998.3 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1037.6 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 4035.8 Combustible Fuel Load per meter (kJ/m) 8071.7 Number of Cables ;
Total Width of Cables 0.038
L-2002-070 Attachment 2 Page 214 of 230 Cable Tray ID C121-2223 Cable Type 5/C #12 XLPPP Outside Diameter (inches) 06 i 0.017272 meters Insulation Material
.... 60.. 0.001524
....... meters Insulation Density (kg/m 3) iiiiiii... ye ..Wii Outer Jacket Thickness (mils) :
...i Insulation Jacket Thickness (mils) i i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) *M,:::::::::::::::::
0.00076 meters Jacket Material ...................... i fft::c : t. .........
P:: ............
Num. Conds. 5 5 Jacket Density (kg/m3)
Diam. Cond. (inches) .... 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) S0.304878 meters Outside Radius 0.008636 m Total Cable Area (A3) 0.0002343 m' 2
Jacket Area 9.908E-05 m2 Insulation Area 3.369E-05 m 3
Total Volume of Jacket (M ) 3 3.02E-05 Mass of Jacket per meter (kg/m) 0.1429 Total Volume of Insulation (M ) 1.03E-05 Mass of Insulation per meter (kg/m) 0.0311 Total Combustible Volume (m3) 4.05E-05 Total Combustible Mass per meter (kg/m) 0.1740 Total Mass of Jacket (kg) 0.044 Jacket heat of combustion energy per meter (kJ/m) 2564.3 Total Mass of Insulation (kg) 0.009 Insulation heat of combustion energy per meter (kJ/m) 741.1 Total Combustible Mass (kg) 0.053 Combustible Fuel Load per meter per cable (kJ/m) 3305.4 Combustible Fuel Load per meter (kJ/m) 9916.1 Number of Cables ........... ...........
Total Width of Cables 0.052
L-2002-070 Attachment 2 Page 215 of 230 Cable Tray ID C121-2223 Cable Type #12 XLPN (XLPPP)
Outside Diameter (inches) ............. 0.0127 meters Insulation Material Outer Jacket Thickness (mils) = 0.001143 meters Insulation Density (kg/m 3) ................. iil.....
Insulation Jacket Thickness (mils) i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) . 0.00076 meters Jacket Material ab94.1 la -t4s.e........ potye........enem Num. Conds. 2 2 Jacket Density (kg/m 3)
Diam. Cond. (inches) : 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ............0.304878 meters Outside Radius 0.00635 m Total Cable Area (A3) 0.0001267 m2 Jacket Area 5.097E-05 M 2
Insulation Area 1.347E-05 M 3
Total Volume of Jacket (M ) 3 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m ) 4.11E-06 Mass of Insulation per meter (kglm) 0.0125 Total Combustible Volume (m) 1.96E-05 Total Combustible Mass per meter (kglm) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 8078.2 Number of Cables .... ......
Total Width of Cables 0.064
L-2002-070 Attachment 2 Page 216 of 230 Cable Tray ID C121-2223 Cable Type '#16 XLPN (XLPPP)
Outside Diameter (inches) : 0.013208 meters Insulation Material Outer Jacket Thickness (mils) 5 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) . 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) .......... 0.00064 meters Jacket Material Num. Conds. 5 5 Jacket Density (kg/m3n Diam. Cond. (inches)
- 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) S0.304878 meters Outside Radius 0.006604 m 2
Total Cable Area (A3) 0.000137 m Jacket Area 6.093E-05 m2 Insulation Area 1.92E-05 m2 3
Total Volume of Jacket (M ) 3 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 0.0178 Total Volume of Insulation (m ) 5.85E-06 Mass of Insulation per meter (kglm)
Total Combustible Volume (m3) 2.44E-05 Total Combustible Mass per meter (kglm) 0.1056 0.027 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Jacket (kg) 0.005 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Mass of Insulation (kg) 0.032 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Total Combustible Mass (kg)
Combustible Fuel Load per meter (kJ/m) 17993.7 Number of Cables i Total Width of Cables 0.119
L-2002-070 Attachment 2 Page 217 of 230 Cable Tray ID C121-2223 Cable Type 7/C #12 MCCC (XLPPP for Insul. Jacket th Outside Diameter (inches) .M69.: 0.017 '526 meters Insulation Material 3 Outer Jacket Thickness (mils) S0.001E1651 meters Insulation Density (kg/M )
Insulation Jacket Thickness (mils) ............
- 0 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00 )102 meters Jacket Material Num. Conds. .......
- 7. S7*...
..... 7 Jacket Density (kg/m3)
Diam. Cond. (inches) 0.00 2052
... meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ........... 0.304f4878 meters Outside Radius 0.008763 m Total Cable Area (A3) 0.0002412 m2 Jacket Area 8.234E-05 m2 Insulation Area 6.856E-05 m2 3
Total Volume of Jacket (M ) 2.51 E-05 Mass of Jacket per meter (kg/m) 0.1187 3
Total Volume of Insulation (m ) 2.09E-05 Mass of Insulation per meter (kg/m) 0.0634 3
Total Combustible Volume (m ) 4.6E-05 Total Combustible Mass per meter (kg/m) 0.1821 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 2131.0 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 1508.3 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m) 3639.3 Number of Cables .. .......... Combustible Fuel Load per meter (kJ/m) 14557.0 Total Width of Cables 0.070 Total Width (m) 0.778 C0.61 m Tray width used Total Energy (kJ/m) 115916.7
L-2002-070 Attachment 2 Page 218 of 230 Cable Tray ID M127-2227 Cable Type 3/C#12 XLPP Outside Diameter (inches) £ii69 0.015723 meters Insulation Material Outer Jacket Thickness (mils) i 0.001143 meters Insulation Density (kg/mr)
Insulation Jacket Thickness (mils) i i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) i 0.00076 meters Jacket Material Num. Conds. 3 3 Jacket Density (kg/m 3)
Diam. Cond. (inches) Oi eO ;0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) - 0.304878 meters Outside Radius 0.0078613 m Total Cable Area (A3) 0.0001942 m2 2
Jacket Area 6.656E-05 M2 Insulation Area 2.021 E-05 m2 Total Volume of Jacket (m3) 3 2.03E-05 Mass of Jacket per meter (kg/m) 0.0960 Total Volume of Insulation (M ) 6.16E-06 Mass of Insulation per meter (kg/m) 0.0187 Total Combustible Volume (m3 2.65E-05 Total Combustible Mass per meter (kg/m) 0.1147 Total Mass of Jacket (kg) 0.0 Jacket heat of combustion energy per meter (kJ/m) 1722.7 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 444.7 Total Combustible Mass (kg) 0.0 Combustible Fuel Load per meter per cable (kJ/m) 2167.3 Combustible Fuel Load per meter (kJ/m) 2167.3 Num ber of Cables ........... ............
Total Width of Cables 0.016
L-2002-070 Attachment 2 Page 219 of 230 Cable Tray ID C121-2227 Cable Type ,#16 XLPPP Outside Diameter (inches) 41...........
0.010414 meters Insulation Material is..... 43lck
.C.a.rb...o...n ri...
Outer Jacket Thickness (mils) *I 0.001143 meters Insulation Density (kg/m 3) .........:.........
Insulation Jacket Thickness (mils) i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 2:*.:.:.:0.00064 meters Jacket Material Jacket Density (kg/m 3) ..
- 4...........1M Num. Conds. .... 0.00129 meters Diam. Cond. (inches) i 0.304878 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet)
Outside Radius 0.005207 m 2
Total Cable Area (A3) 8.51 BE-05 m 2
Jacket Area 4.033E-05 i 2
Insulation Area 7.682E-06 m Total Volume of Jacket (m3) 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m33) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (m ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.018 Jacket heat of combustion energy per meter (kJtm) 1043.8 Total Mass of Insulation (kg) 0.002 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.020 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 3638.4 Number of Cables :
Total Width of Cables 0.031
L-2002-070 Attachment 2 Page 220 of 230 Cable Tray ID Cl 21-2227 Cable Type 2/C#12 XLPPP Outside Diameter (inches) 0. 0127
............................ m eters Insulation Material Outer Jacket Thickness (mils) A 0 .001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) S 00.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 3 0.00076 meters Jacket Material Num. Conds. 2i 2 Jacket Density (kg/m3)
Diam. Cond. (inches) i 0002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) -.-
i 0.304878 meters Outside Radius 0.00635 m 2
Total Cable Area (A3) 0.0001267 m 2
Jacket Area 5.097E-05m 2
Insulation Area 1.347E-05 M Total Volume of Jacket (mi3 ) 3 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m ) 4.11 E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (m )
3 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 17772.0 Number of Cables .4 Total Width of Cables 0.140
L-2002-070 Attachment 2 Page 221 of 230 Cable Tray ID Cl121-2227 Cable Type 5/C#16 XLPPP Outside Diameter (inches) 52 0.013208 meters Insulation Material Outer Jacket Thickness (mils) 4i* 0.001143 meters Insulation Density (kglm3)
Insulation Jacket Thickness (mils) .. 0.000381
.......... meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 2: 0.00064 meters Jacket Material 3
Num. Conds. Jacket Density (kg/m )
Diam. Cond. (inches) V*O* i 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ; 0.304878 meters Outside Radius 0.006604 m 2
Total Cable Area (A3) 0.000137 m Jacket Area 6.093E-05 m2 2
Insulation Area 1.92E-05 m Total Volume of Jacket (m3) 3 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 Total Volume of Insulation (M 3) 5.85E-06 Mass of Insulation per meter (kg/m) 0.0178 Total Combustible Volume (m
) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.1056 Total Mass of Jacket (kg) 0.027 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Insulation (kg) 0.005 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Combustible Mass (kg) 0.032 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Combustible Fuel Load per meter (kJ/m) 1999.3 Number of Cables :
Total Width of Cables 0.013
L-2002-070 Attachment 2 Page 222 of 230 Cable Tray ID C121-2227
- .#12 XLPPP Cable Type 0.018796 meters 74........... Insulation Material Outside Diameter (inches) 3
. 0.001524 meters Insulation Density (kg/m )
Outer Jacket Thickness (mils) 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Insulation Jacket Thickness (mils)
..
- 0.00076 meters Jacket Material Conduct. Insul. Thickness (mils)
Num. Conds. 7 7 Jacket Density (kg/m3 S0.002052 meters Jacket Heat of Combustion (kJ/kg)
Diam. Cond. (inches)
Cable Length (feet) S 0.304878 meters Outside Radius 0.009398 m Total Cable Area (A3) 0.0002775 m'2 Jacket Area 0.0001159 m Insulation Area 4.716E-05 m2 3
Total Volume of Jacket (M ) 3.53E-05 Mass of Jacket per meter (kg/m) 0.1670 Mass of Insulation per meter (kg/m) 0.0436 Total Volume of Insulation (m
- 3) 1.44E-05 (m3) Total Combustible Mass per meter (kg/m) 0.2106 Total Combustible Volume 4.97E-05 Jacket heat of combustion energy per meter (kJ/m) 2998.3 Total Mass of Jacket (kg) 0.1 1037.6 Total Mass of Insulation (kg) 0.0 Insulation heat of combustion energy per meter (kJ/m) 4035.8 Total Combustible Mass (kg) 0.1 Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 4035.8 Number of Cables ...
Total Width of Cables 0.019
L-2002-070 Attachment 2 Page 223 of 230 Cable Tray ID C121-2227 Cable Type 5/C #12 XLPN (XLPPP)
Outside Diameter (inches) : 68 0.017272 meters Insulation Material 3
Outer Jacket Thickness (mils) 0 0.001524 meters Insulation Density (kg/m )
Insulation Jacket Thickness (mils) 1$ 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 3 : 0.00076 meters Jacket Material 3
Num. Conds. 5 5 Jacket Density (kg/m )
Diam. Cond. (inches) &:: :: 0.002052 meters Jacket Heat of Combustion (kJ/kg)
I::::::::::::::::*:::::::::::::::::
0.304878 m eters Cable Length (feet)
Outside Radius 0.008636 m 2
Total Cable Area (A3) 0.0002343 i 2
Jacket Area 9.908E-05 m 2
Insulation Area 3.369E-05 M Total Volume of Jacket (M3) 3 3.02E-05 Mass of Jacket per meter (kg/m) 0.1429 Total Volume of Insulation (m ) 1.03E-05 Mass of Insulation per meter (kg/m) 0.0311 Total Combustible Volume (m3) 4.05E-05 Total Combustible Mass per meter (kg/m) 0.1740 Total Mass of Jacket (kg) 0.044 Jacket heat of combustion energy per meter (kJ/m) 2564.3 0.009 Insulation heat of combustion energy per meter (kJ/m) 741.1 Total Mass of Insulation (kg) 0.053 Combustible Fuel Load per meter per cable (kJ/m) 3305.4 Total Combustible Mass (kg)
Combustible Fuel Load per meter (kJ/m) 13221.5 Number of Cables . . ...........
Total Width of Cables 0.069
L-2002-070 Attachment 2 Page 224 of 230 Cable Tray ID C121-2227 Cable Type 3#16 XLPN (XLPPP)
Outside Diameter (inches) ............. 0.010414 meters Insulation Material Outer Jacket Thickness (mils) : 0.001143 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils)
- 0.000381 meters Insulation Heat of Combustion (kJ/kg)
....... 0.00064 meters Conduct. Insul. Thickness (mils)
Num. Conds.
........ ...ii 2 Jacket Material 3 Jacket Density (kg/m )
Diam. Cond. (inches) ~ i 0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) . 0.304878 meters Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 m2 2
Jacket Area 4.033E-05 m Insulation Area 7.682E-06 m2 3
Total Volume of Jacket (M ) 3 1.23E-05 Mass of Jacket per meter (kg/m) 0.0582 Total Volume of Insulation (m 3) 2.34E-06 Mass of Insulation per meter (kg/m) 0.0071 Total Combustible Volume (M ) 1.46E-05 Total Combustible Mass per meter (kg/m) 0.0653 Total Mass of Jacket (kg) 0.018 Jacket heat of combustion energy per meter (kJ/m) 1043.8 Total Mass of Insulation (kg) 0.002 Insulation heat of combustion energy per meter (kJ/m) 169.0 Total Combustible Mass (kg) 0.020 Combustible Fuel Load per meter per cable (kJ/m) 1212.8 Combustible Fuel Load per meter (kJ/m) 1212.8 Number of Cables ii Total Width of Cables 0.010
L-2002-070 Attachment 2 Page 225 of 230 Cable Tray ID C121-2227 Cable Type '#12 XLPPP Outside Diameter (inches) 8 0,017272 meters Insulation Material Outer Jacket Thickness (mils) 0 0.001524 meters Insulation Density (kg/m 3)
Insulation Jacket Thickness (mils) S0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) ............. 0.00076 meters Jacket Material 3
Num. Conds. ...... .. 5 Jacket Density (kg/m )
Diam. Cond. (inches) ......... 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) ..............0.304878 meters Outside Radius 0.008636 m Total Cable Area (A3) 0.0002343 m2 2
Jacket Area 9.908E-05 m Insulation Area 3.369E-05 m2 3
Total Volume of Jacket (M ) 3 3.02E-05 Mass of Jacket per meter (kg/m) 0.1429 Total Volume of Insulation (m 3) 1.03E-05 Mass of Insulation per meter (kg/m) 0.0311 Total Combustible Volume (M ) 4.05E-05 Total Combustible Mass per meter (kg/m) 0.1740 Total Mass of Jacket (kg) 0.044 Jacket heat of combustion energy per meter (kJ/m) 2564.3 Total Mass of Insulation (kg) 0.009 Insulation heat of combustion energy per meter (kJ/m) 741.1 Total Combustible Mass (kg) 0.053 Combustible Fuel Load per meter per cable (kJ/m) 3305.4 Combustible Fuel Load per meter (kJ/m) 3305A Number of Cables :
Total Width of Cables 0.017
L-2002-070 Attachment 2 Page 226 of 230 Cable Tray ID C121-2227 Cable Type 2/C #12 XLPN (XLPPP)
Outside Diameter (inches) ........
- .i .... 0.0127 meters Insulation Material ................ . ........
o...t...e..
Outer Jacket Thickness (mils) 5 0.001143 meters Insulation Density (kg/m 3) .
Insulation Jacket Thickness (mils) ...........
1M......... 0000381 meters Insulation Heat of Combustion (kJ/kg) ............ ...
Conduct. Insul. Thickness (mils) ............ 0.00076 meters Jacket Material 3
............ e i ....
Num. Conds. 2 2 Jacket Density (kg/m )
Diam. Cond. (inches)
- 0002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .. ........ 0.304878 meters Outside Radius 0.00635 m2 Total Cable Area (A3) 0.0001267 m Jacket Area 5.097E-05 m2 2
Insulation Area 1.347E-05 M Total Volume of Jacket (m3) 3 1.55E-05 Mass of Jacket per meter (kg/m) 0.0735 Total Volume of Insulation (m3 ) 4.11 E-06 Mass of Insulation per meter (kg/m) 0.0125 Total Combustible Volume (m ) 1.96E-05 Total Combustible Mass per meter (kg/m) 0.0859 Total Mass of Jacket (kg) 0.022 Jacket heat of combustion energy per meter (kJ/m) 1319.2 Total Mass of Insulation (kg) 0.004 Insulation heat of combustion energy per meter (kJ/m) 296.4 Total Combustible Mass (kg) 0.026 Combustible Fuel Load per meter per cable (kJ/m) 1615.6 Combustible Fuel Load per meter (kJ/m) 1615.6 Number of Cables .i............
Total Width of Cables 0.013
L-2002-070 Attachment 2 Page 227 of 230 Cable Tray ID C121-2227 Cable Type 5/C #16 XLPN (XLPPP)
Outside Diameter (inches) 52 0.013208 meters Insulation Material Outer Jacket Thickness (mils) 4 0001143 meters Insulation Density (kglm 3)
Insulation Jacket Thickness (mils) 1i 0.000381 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 2 0.00064 meters Jacket Material Num. Conds. 5 5 Jacket Density (kg/m3 Diam. Cond. (inches) CLV~0* i0.00129 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) .................... 0.304878 meters Outside Radius 0.006604 m Total Cable Area (A3) 0.000137 m2 Jacket Area 6.093E-05 m2 Insulation Area 1.92E-05 m2 Total Volume of Jacket (m3) 1.86E-05 Mass of Jacket per meter (kg/m) 0.0878 0.0178 Total Volume of Insulation (m3)3 5.85E-06 Mass of Insulation per meter (kg/m) 0.1056 Total Combustible Volume (M ) 2.44E-05 Total Combustible Mass per meter (kg/m) 0.027 Jacket heat of combustion energy per meter (kJ/m) 1576.8 Total Mass of Jacket (kg) 0.005 Insulation heat of combustion energy per meter (kJ/m) 422.5 Total Mass of Insulation (kg) 0.032 Combustible Fuel Load per meter per cable (kJ/m) 1999.3 Total Combustible Mass (kg) 1999.3 Combustible Fuel Load per meter (kJ/m)
Number of Cables .....
Total Width of Cables 0.013
L-2002-070 Attachment 2 Page 228 of 230 Cable Tray ID C121-2227 4* -*1.
Cable Type MCCC Outside Diameter (inches) 0.017526 meters Insulation Material 3 Outer Jacket Thickness (mils) 0.001651 meters Insulation Density (kg/m )
Insulation Jacket Thickness (mils) 0 meters Insulation Heat of Combustion (kJ/kg)
Conduct. Insul. Thickness (mils) 0.00102 meters Jacket Material 2 Num. Conds. 7 Jacket Density (kglm )
Diam. Cond. (inches) 0.002052 meters Jacket Heat of Combustion (kJ/kg)
Cable Length (feet) 0.304878 meters Outside Radius 0.008763 m Total Cable Area (A3) 0.0002412 m2 Jacket Area 8.234E-05 m2 2
Insulation Area 6.856E-05 M 3
Total Volume of Jacket (M ) 3 2.51 E-05 Mass of Jacket per meter (kglm) 0.1187 Total Volume of Insulation (M 3) 2.09E-05 Mass of Insulation per meter (kg/m) 0.0634 (M ) 0.1821 Total Combustible Volume 4.6E-05 Total Combustible Mass per meter (kglm)
Total Mass of Jacket (kg) 0.036 Jacket heat of combustion energy per meter (kJJ/m) 2131.0 Total Mass of Insulation (kg) 0.019 Insulation heat of combustion energy per meter (kJ/m) 1508.3 Total Combustible Mass (kg) 0.056 Combustible Fuel Load per meter per cable (kJ/m) 3639.3 Combustible Fuel Load per meter (kJ/m) 14557.0 Number of Cables .... .......
Total Width of Cables 0.070 Total Width (m) 0.396 Total Energy (kJim) 63357.2
L-2002-070 Attachment 2 Page 229 of 230 Appendix B Thermal Material Properties used to Calculated Temperature Response of Target Cable Tray System to Incident Heat Flux BL. Thermal Conductivity The thermal conductivity for steel as a function of temperature is shown in Table B1.
Because the failure threshold for the cable jacket material is less than 400 'C, the thermal conductivity of the copper and PVC jacket material are essentially temperature independent in this analysis.
Copoer [Holman. 19901: 386 W/m-0 C PVC [Marks, 1996]: 0. 17 W/m-°C Table BI - Temperature Dependent Thermal Conductivity of Steel [Abrams, 1978]
T m )C)
KCT ((C) k (W/mO)
(°C)(/mOC T (OC)
T(C k (W/mOC) T ( 0°C C) k (W/m-oC) 20.0 46.02 316.0 42.75 649.0 32.84 816.0 29.03 38.0 46.02 371.0 41.04 677.0 32.1 843.0 27.15 73.0 46.4 427.0 39.45 704.0 31.42 871.0 26.40 149.0 45.73 482.0 37.82 732.0 30.92 899.0 26.73 204.0 44.76 538.0 36.44 760.0 30.45 927.0 26.78 260.0 43.84 593.0 34.73 788.0 30.0 1038.0 27.74 B2. Thermal Heat Capacity The thermal heat capacity for steel as a function of temperature is shown in Table B2.
The thermal heat capacity for PVC as a function of temperature over the range of interest is shown in Table B3. The heat capacity for copper is essentially constant of the temperature range expected in the cable core.
Copper [Holman. 1990]: 383 J/kg-°C
L-2002-070 Attachment 2 Page 230 of 230 Table B2 - Temperature Dependant Heat Capacity of Steel [Abrams, 1978]
T (°C) ( C (J/kg-°C)
T (°C) { C (J/kg-°C)
T (°C) Cp (J/kg-°C)
T (°C) %
(J/kg-°C) 20.0 467 316.0 558 649.0 777 816.0 568 38.0 471 371.0 580 677.0 810 843.0 535 73.0 484 427.0 606 704.0 1098 871.0 522 149.0 501 482.0 641 732.0 1410 899.0 533 204.0 518 538.0 690 760.0 1012 927.0 568 260.0 536 593.0 736 788.0 727 1038.0 584 Table B3 - Temperature Dependant Heat Capacity of PVC [Marks, 1996]
B3. Density The density for the steel, PVC, and copper is constant of the temperature range considered.
Steel [Abrams, 1978]: 7800.0 kg/m3 Copper [Holman, 1990]: 8954.0 kg/m3 3
PVC [Johnson, 1994]: 1500.0 kg/m