L-2002-070, Part 2 of 2, St. Lucie, Unit 1 - FPL Response to Request for Additional Information for 10CFR50 Appendix R K1 Exemption Clarification/Request, Appendix a Cable Tray Fuel Load Calculations
| ML021410013 | |
| Person / Time | |
|---|---|
| Site: | Saint Lucie (DPR-067) |
| Issue date: | 05/15/2002 |
| From: | Jernigan D Florida Power & Light Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| L-2002-070 | |
| Download: ML021410013 (135) | |
Text
L-2002-070 Page 96 of 230 Appendix A Cable Tray Fuel Load Calculations
L-2002-070 Page 97 of 230 Heat Release Rate Cables Combustible per unit length of Reference Point Tray ID Width of Fuel Load per cable tray (kW/m)
Meter (kJ/m)
(400 kW/m2 q)
MIN0 0.502 74388.2 90.36 235C100 0.075 16143.3 13.50 (with0 C101 0.283 38195.6 50.94
,1101 0.367 42678.3 66.06 TOTAL 1.227 171405.5 220.86 M100 0.502 74388.2 90.36 2305 C100 0.075 16143.3 13.50 (without L101)
C101 0.283 38195.6 50.94 TOTAL 0.860 128727.2 154.80 M120 0.610 89177.6 109.80 2307/2369 C120 0.294 36767.3 52.92 (with L120)
L120 0.388 55180.6 69.84 TOTAL 1.292 181125.5 232.56 2
M120 0.610 89177.6 109.80 2307/2369 C120 0.294 36767.3 52.92 (without L120)
TOTAL 0.904 125944.9 162.72 M100 0.502 74388.2 90.36 2320 C 101 0.283 38579.3 50.94 TOTAL 0.785 112967.5 141.30 M100 0.502 74388.2 90.36 2393 C101 0.243 33795.2 43.74 TOTAL 0.745 108183.4 134.10 M100 0.376 55791.2 67.68 2306 C101 0.148 20097.5 26.64 TOTAL 0.524 75888.7 94.32 M120 0.502 74388.2 90.36 2308 C 120 0.113 16752.6 20.34 TOTAL 0.615 91140.8 110.70 M102 0.037 6641.2 6.66 2245 C103 0.516 66073.0 92.88 TOTAL 0.553 72714.2 99.54 M102 0.016 2571.8 2.88 2247 C 103 0.249 39607.3 44.82 TOTAL 0.265 42179.1 47.70 M127 0.110 17057.2 19.80 2221/2225 C121 0.610 118745.1 109.80 TOTAL 0.720 135802.3 129.60 M127 0.110 17057.2 19.80 2223 C121 0.610 115916.7 109.80 TOTAL 0.720 132973.9 129.60 M127 0.016 2167.3 2.88 2227 C121 0.396 63357.2 71.28 TOTAL 0.412 65524.5 74.16
L-2002-070 Page 98 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area C100-2305
,#1 2 74 0.018796 meters i
0.001524 meters i
0.000381 meters
- ii 0.00076 meters 7.
XLPN (XLPPP)
Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg) 0.002052 meters 0.304878 meters 0.009398 m 0.00027747 i 2 0.00011585 M2 4.716E-05 m2 Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (ms)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 3.53E-05 1.44E-05 4.97E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.1670 0.0436 0.2106 2998.3 1037.6 4035.8 16143.3 Number of Cables i
I Total Width of Cables 0.075
L-2002-070 Page 99 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2305 2/C#12
. 5 0.0127 meters 0.001143 meters i
0.000381 meters 3i 0.00076 meters 2
2 0.002052 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/Mr 3 )
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/M 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.00635 m 0.00012668 M 5.0973E-05 M 2
1.3474E-05 m2 Total Volume of Jacket (Mi)
Total Volume of Insulation (m3)
Total Combustible Volume (Mi)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.051 1.55E-05 4.11 E-06 1.96E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 6462.5
L-2002-070 Page 100 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2305 2/C#12 i
0.0127 meters 4..................
0.001143 meters 15 0.000381 meters
....... 0.00076 meters i8O&
0.002052 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/im
- 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.00635 m 0.00012668 m2 2
5.0973E-05 m 1.3474E-05 m2 Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.051 1.55E-05 4.11 E-06 1.96E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 6462.5
L-2002-070 Page 101 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
CIOI-2305
,#16
........... 0.013208 meters 0.001143 meters S0.000381 meters
- 5 0.00064 meters A5O& - 0.00129 meters 4
0.304878 meters XLPPP Insulation Material Insulation Density (kg/im3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/M3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.006604 m 0.00013701 m' 6.0927E-05 M 2
1.9204E-05 M2 Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables yy Total Width of Cables 0.026 1.86E-05 5.85E-06 2.44E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 3998.6
L-2002-070 Page 102 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
CIOI-2305 2/C# 16 0.010414 meters 4
i 0.001143 meters 1
- 0.000381 meters 5........
0.00064 meters 2
2
- 0.00129 meters i
0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (Mi)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Number of Cables
- .....5........
Total Width of Cables 0.052 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 8.5178E-05 M 4.0332E-05 M2 7.6817E-06 M 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 6064.0
L-2002-070 Page 103 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2305 2/*'*I 6 0.010414 0.001143 0.000381 0.00064 meters meters meters meters 2
0.00129 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.005207 m 8.5178E-05 m2 4.0332E-05 m2 7.6817E-06 M Total Volume of Jacket (M3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.010 Total Width (m)
Total Energy (kJ/m) 0.283 38195.6 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 1212.8
L-2002-070 Page 104 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
M120-230712369
-1 I/ #4/0l 0.020904 0.001143 0
0.00140 1
meters meters meters meters 0.011684 meters 0.304878 meters XLPP Insulation Material i........
Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ:kg ::
Jacket Material 60.Wf
(~m F Wi i
- i piis Jacket Density (kg/r
- 3)
.. 441...........
Jacket Heat of Combustion (kJ/kg) 1795ti Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.0104521 m 0.00034321 m2 7.0959E-05 m2 2
5.741 E-05 M Total Volume of Jacket (m3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 2.16E-05 1.75E-05 3.91 E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.502 0.1023 0.0531 0.1554 1836.4 1263.1 3099.5 74388.2
L-2002-070 Page 105 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
M120-230712369 5I*#l 2 0.016256 meters 0.001651 meters 0
meters 0.00102 meters 1
0.002052 meters 0.304878 meters MCCC Insulation Material Insulation Density (kglm3)
Insulation Heat of Combustion (kJ/k Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.008128 m 0.00020755 m2 7.5753E-05 M 9.7936E-06 m2 Total Volume of Jacket (m3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 2.31 E-05 2.99E-06 2.61 E-05 0.0 0.0 0.0 Number of Cables
..2..........
Total Width of Cables 0.033 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.1092 0.0091 0.1183 1960.5 215.5 2176.0 4351.9
L-2002-070 Page 106 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
M120-230712369 3/C#12 X.. 0.015723 meters
.45........
0.001143 meters
. 0.000381 meters
.3
- 0.00076 meters 3
0 080&: 0.002052 meters 1i 0.304878 meters XLPN (XLPP)
Insulation Material Insulation Density (kgt/M
- 3)
Insulation Heat of Combustion (kJ/k Jacket Material Jacket Density (kg/M3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.0078613 m 0.00019415 m' 6.6563E-05 m2 2.0212E-05 m2 Total Volume of Jacket (m3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.031 2.03E-05 6.16E-06 2.65E-05 0.0 0.0 0.0 Mass of Jacket per meter (kglm)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJtm)
Combustible Fuel Load per meter (kJ/m) 0.0960 0.0187 0.1147 1722.7 444.7 2167.3 4334.7
L-2002-070 Page 107 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area M120-230712369 3-1/C#2
.i8 i 0.014783 meters 45
- 0.001143 meters 0
meters 0.00140 meters XLPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/k Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg) 0.006543 meters 0.304878 meters 0.0073914 m 0.00017163 m 2 4.8978E-05 m2 3.4847E-05 m2 Total Volume of Jacket (m3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.49E-05 1.06E-05 2.56E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0706 0.0322 0.1028 1267.6 766.7 2034.2 6102.7 Number of Cables Total Width of Cables 0.044 Total Width (m):
Total Energy (kJIm):
0.610 89177.6
L-2002-070 Page 108 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2307 0.018796 0.001524 0.000381 0.00076 7
meters meters meters meters 0.002052 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kl Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.009398 m 2
0.00027747 m 0.00011585 m2 4.716E-05 m2 Total Volume of Jacket (m3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables comma.
Total Width of Cables 0.038 3.53E-05 1.44E-05 4.97E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJIm)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.1670 0.0436 0.2106 2998.3 1037.6 4035.8 8071.7
L-2002-070 Page 109 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2307
- 12
- 64 0.016256 meters
- iiiiii5iiiiii 0.001651 meters
- iii~iii!
0 meters I===============
0.00102 meters 0.002052 meters 304878 meters MCCC Insulation Material E rbdn4 Insulation Density (kg/m 3) 9244 Insulation Heat of Combustion (kJ/kg 2$&
Jacket Material fIyI i (Fauitro i
- k ie Pi1C propertie Jacket Density (kg/mi3)
Jacket Heat of Combustion (kJ/kg)
.7950 Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.008128 m 2
0.00020755 m 7.5753E-05 m2 4.8968E-05 m2 Total Volume of Jacket (mi3)
Total Volume of Insulation (M3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 2.31 E-05 1.49E-05 3.8E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables i
Total Width of Cables 0.065 0.1092 0.0453 0.1545 1960.5 1077.3 3037.8 12151.4
L-2002-070 Page 110 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2307
,#12
.9..
0.022606 meters
- 10 0.002032 meters 0
meters
==
0.00102 meters 0.002052 meters 1
0.304878 meters MCCC Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/k Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius 0.011303 m Total Cable Area (A3) 0.00040136 m2 Jacket Area 0-00013134 m2 Insulation Area 8-8143E-05 m2 Total Volume of Jacket (M3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.023 4E-05 2.69E-05 6.69E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.1894 0.0815 0.2708 3399.1 1939.2 5338.3 5338.3
L-2002-070 Page 111 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2307 5/C#16 G52 0.013208 meters
`5 0.001143 meters i
0.000381 meters 25 0.00064 meters 0.00129 meters
.................. 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kWJ/k Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.006604 m 0.00013701 m2 6.0927E-05 M 2
1.9204E-05 M 2
Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.040 1.86E-05 5.85E-06 2.44E-05 0.0 0.0 0.0 Mass of Jacket per meter (kglm)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJtm)
Combustible Fuel Load per meter (kJ/m) 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 5997.9
L-2002-070 Page 112 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C1 20 -2307 2/C#12 0.0127 meters
- 45 0.001143 meters S0.000381 meters
.3D:'::,::
.' 0.00076 meters 2
2
&O8 i 0.002052 meters 1
0.304878 meters XLPPP Insulation Material C.
.b.............i..........
Insulation Density (kg/m 3) 9244 Insulation Heat of Combustion (kJ/kg:
$* 0 Jacket Material bilyL Pi i
pn*per ies.
Jacket Density (kg/m3) 1441 Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.00635 m 2
0.00012668 m 5.0973E-05 m2 1.3474E-05 m2 Total Volume of Jacket (mi
- 3)
Total Volume of Insulation (M 3)
Total Combustible Volume (m3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.013 1.55E-05 4.11 E-06 1.96E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kglm)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 1615.6
L-2002-070 Page 113 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2307 0.010414 0.001143 0.000381 0.00064 meters meters meters meters 2
0.00129 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3) 9244 Insulation Heat of Combustion (kJ/kg 2
Jacket Material
.oly!te.r.
Fl:m.m.):*
.iuse VC popetie Jacket Density (kg/m3) 441
-4 Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.005207 m 8.5178E-05 m2 4.0332E-05 m2 7.6817E-06 m2 Total Volume of Jacket (m3)
Total Volume of Insulation (m3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Num ber of Cables Total Width of Cables 0.073 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kglm)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kgtm)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJtm)
Combustible Fuel Load per meter (kJ/m) 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 8489.6
L-2002-070 Page 114 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2307 7*41A 2
0.017526 0.001651 0
0.00102 7
meters meters meters meters 0.002052 meters 0.304878 meters MCCC Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.008763 m 0.00024124 m2 8.234E-05 m2 6.8555E-05 m 2
Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.018 2.51 E-05 2.09E-05 4.6E-05 0.0 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJfm)
Combustible Fuel Load per meter (kJ/m) 0.1187 0.0634 0.1821 2131.0 1508.3 3639.3 3639.3
L-2002-070 Page 115 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2307
,#12 0.0127 meters 0.001143 meters 0.000381 meters 0.00076 meters 2............ 2 0.002052 meters
..*1 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/k Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.00635 m 2
0.00012668 m 5.0973E-05 m2 1.3474E-05 m2 Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (mi 3
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.013 1.55E-05 4.11E-06 1.96E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 1615.6
L-2002-070 Page 116 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C1 20-2307
- 16 52i 0.013208 meters 0.001143 meters 0.000381 meters
==
0.00064 meters AN 5
- O
. 0.00129 meters 1
0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/mt)
Insulation Heat of Combustion (kJ/k Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.006604 m 0.00013701 m' 6.0927E-05 m' 1.9204E-05 m2 Total Volume of Jacket (M3)
Total Volume of Insulation (M3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.013 Total Width (m)
Total Energy (m) 1.86E-05 5.85E-06 2.44E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (k J/m) 0.294 36767.3 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 1999.3
L-2002-070 Page 117 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L120-230712369 12/C#16 1
i 0.02794 meters BQ 0.002032 meters 0.000381 meters 25 0.00064 meters 12 0.00129 meters 0.304878 meters XLPSMP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJWl Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.01397 m 2
0.00061312 M 0.00020764 m2 4.609E-05 M 2
Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.056 6.33E-05 1.41 E-05 7.74E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.2994 0.0426 0.3420 5373.7 1014.0 6387.7 12775.4
L-2002-070 Page 118 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
LI 20-230712369 2/C#16 0.010922 meters i
0.00127 meters 0
meters 0.00076 meters 2
2 i050 o0.00129 meters
................... 0.304878 meters INSTS Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (k J/!k Jacket Material Jacket Density (kg/mr)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.005461 m 9.369E-05 m' 3.851 E-05 m2 9.8261E-06 M 2
Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.055 1.17E-05 3E-06 1.47E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJIm)
Combustible Fuel Load per meter (kJ/m) 0.0555 0.0091 0.0646 996.6 216.2 1212.8 6064.1
L-2002-070 Page 119 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L120-230712369 4/C#16 64:iiiiiiiiiiiiiii 0.01041 5
0.0012"
- ..ii~~~~iii......... 0.3 87ii~~ii 04
....3........
0.0007.
2 2
S.......................
0.30487 14 7
6 meters meters meters meters 9 meters 78 meters INSTS Insulation Material Carbon. biack cross -linked pciyyle, Insulation Density (kg/m 3) i 4 4 Insulation Heat of Combustion (kJ/kg 2$$i&
Jacket Material R6I in ~p
.%priipert-es Jacket Density (kg/m3) 14.1..................
Jacket Heat of Combustion (kJ/kg) 17 Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.005207 m 8.5178E-05 m2 3.6483E-05 m2 9.8261E-06 m2 Total Volume of Jacket (mi3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Nrum ber of Cables Total Width of Cables 0.010 1.11 E-05 3E-06 1.41 E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJtm) 0.0526 0.0091 0.0617 944.2 216.2 1160.4 1160.4
L-2002-070 Page 120 of 230 Cable Tray I D Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L120-230712369 21C#16 035 i 0.00889 meters 0.001143 meters 0.....*....
o meters 3.0.......
0.00076 meters 2iiiiiii ii~iiiiiiiiii 2
,O50: 0.00129 meters 1........ 0.304878 meters XLPSMP(TE)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/k(
Jacket Material Jacket Density (kg/mr3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.004445 m 2
6.2072E-05 m 2.7818E-05 m2 9.8261 E-06 m2 Total Volume of Jacket (m 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.009 8.48E-06 3E-06 1.15E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0401 0.0091 0.0492 719.9 216.2 936.1 936.1
L-2002-070 Page 121 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L120-230712369 0.010922 meters 0.001143 meters 0.000381 meters 0.00064 meters 3
0.00129 meters 0.304878 meters XLPSMP Insulation Material Insulation Density (kg/mr)
Insulation Heat of Combustion (k J/!
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.005461 m 9.369E-05 m2 4.5677E-05 m2 2
- 1. 1523E-05 M Total Volume of Jacket (M3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.39E-05 3.51 E-06 1.74E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.022 0.0659 0.0107 0.0765 1182.1 253.5 1435.6 2871.3
L-2002-070 Page 122 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L120-230712369 2/C#14 05 0.0127 meters AS 0.001143 meters 1
i 0.000381 meters 30 0.00076 meters
- 2 2
0i$4
- 0.001628 meters 1%
0.304878 meters XLPSN (XLPSMP)
Insulation Material
- a.b.n
- os.......
polyethylene Insulation Density (kg/m 3)
-.9244......
Insulation Heat of Combustion (kJ/kg 23::
$O&:.:.
Jacket Material Wol.ein (FnTo.ms P properfies Jacket Density (kg/m43) 1441 Jacket Heat of Combustion (kJ/kg)
IMi:....
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.00635 m 0.00012668m' 4.9957E-05m2 1.1443E-05m2 Total Volume of Jacket (m 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.038 1.52E-05 3.49E-06 1.87E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJIm)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0720 0.0106 0.0826 1292.9 251.8 1544.7 4634.0
L-2002-070 Page 123 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L120-230712369 41/":.l 6 0.0127 0.001143 0
0.00051 meters meters meters meters 4
0.00129 meters 0.304878 meters XLPSN Insulation Material Z, r C
Insulation Density (kglm3)
.244 Insulation Heat of Combustion (kJ/kg 2$i.iiii..............
Jacket Material FOR.
w.i i
.C pripries Jacket Density (kg/m 3)
.441.
Jacket Heat of Combustion (kJ/kg) 17iO Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.00635 m 0.00012668 m2 4.1499E-05 m2 1.148E-05 m2 Total Volume of Jacket (M3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Num ber of Cables Total Width of Cables 0.038 1.27E-05 3.5E-06 1.62E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJlm)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0598 0.0106 0.0704 1074.0 252.6 1326.6 3979.8
L-2002-070 Page 124 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L120-230712369 2/C#16 0.010414 m eters 45 0.001143 meters i
- 0.000381 meters
......2.........
0.00064 meters 0.00129 meters 4
0.304878 meters EPDMHYP (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kgI Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.005207 m 8.5178E-05 m' 4.0332E-05 m2 7.6817E-06 m2 Total Volume of Jacket (mi
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.021 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 2425.6
L-2002-070 Page 125 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L120-230712369 4/C#16
- 7.
5.......
0.01905 meters 0.001524 meters i
0.000381 meters 2:
0.00064 meters 4
i i
0.00129 meters 0.304878 meters XLPP (XLPSMP)
Insulation Material Insulation Density (kglm3)
Insulation Heat of Combustion (kJ/k Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.009525 m 0.00028502 m2 9.7993E-05m2 1.5363E-05m2 Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) w -,......
Number of Cables Total Width of Cables 0.057 2.99E-05 4.68E-06 3.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.1413 0.0142 0.1555 2536.1 338.0 2874.1 8622.3
L-2002-070 Page 126 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L120-230712369
- Pr*If' A.
0.0127 0.001143 0.000381 0.00076 meters meters meters meters 2
0.001628 meters 0.304878 meters XLPSMP Insulation Material ara IbMa cros*inked p etbylene Insulation Density (kg/m 3) 9244 Insulation Heat of Combustion (kJ/kg i2i3i.! O Jacket Material Ryefr lii rn
- iuse PVC propertie Jacket Density (kg/m3) 1441.............
Jacket Heat of Combustion (kJ/kg) 17*O Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.00635 m 2
0.00012668 m 4.9957E-05 m2 1.1443E-05 m2 Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.025 1.52E-05 3.49E-06 1.87E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0720 0.0106 0.0826 1292.9 251.8 1544.7 3089.4
L-2002-070 Page 127 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L120-230712369 4/C# 16 0.01905 meters 0.001524 meters
!5 0.000381 meters 25i 0.00064 meters 4
4
.5 i 0.00129 meters 0.304878 meters XLPSMP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius 0.009525 m Total Cable Area (A3) 0.00028502 m 2 2
Jacket Area 9.7993E-05 M Insulation Area 1.5363E-05 m2 Total Volume of Jacket (M3)
Total Volume of Insulation (m3)
Total Combustible Volume (M3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.057 Total Width (m)
Total Energy (kJim) 2.99E-05 4.68E-06 3.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kglm)
Mass of Insulation per meter (kglm)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.388 55180.6 0.1413 0.0142 0.1555 2536.1 338.0 2874.1 8622.3
L-2002-070 Page 128 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
LIOI-2305 5Q9/ I 0.018796 0
0 0.00274 1
meters meters meters meters 0.000643 meters 0.304878 meters RG-59/U COA Insulation Material Insulation Density (kg/m 3) 1441 B Insulation Heat of Combustion g......
Jacket Material Iy:P fe91r W.I)u P
Jacket Density (kg/m 3) 1441 B Jacket Heat of Combustion (kJ/kg)
- ,.*t%:".:.4.*OO W.W.
Outside Radius 0.009398 m 2
Total Cable Area (A3) 0.00027747 M Jacket Area Insulation Area 0 m2 2.9179E-05 m2 Total Volume of Jacket (m3)
Total Volume of Insulation (m3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.094 0
8.9E-06 8.9E-06 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
(PE) 0.0000 0.0421 0.0421 0.0 1956.3 1956.3 9781.4
L-2002-070 Page 129 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L101-2305 0.018796 0
0 0.00318 1
meters meters meters meters 0.000574 meters 0.304878 meters COAX COA Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius 0.009398 m Total Cable Area (A3) 0.00027747 m' Jacket Area Insulation Area 0 m2 3.7395E-05 m2 Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.038 0
1.14E-05 1.14E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kglm)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
(PE) 0.0000 0.0539 0.0539 0.0 2507.1 2507.1 5014.2
L-2002-070 Page 130 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L101-2305
"#18
............ 0.013335 meters 0.001143 meters
)
0 meters
............ 0.00051 meters 6
0.001024 meters 0.304878 meters XLPSN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/k Jacket Material Jacket Density (kglm3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.0066675 m 2 0.00013966 m 4.378E-05 m' 1.4666E-05 m' Total Volume of Jacket (M 3 )
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Num ber of Cables Total Width of Cables 0.013 1.33E-05 4.47E-06 1.78E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJim)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0631 0.0136 0.0767 1133.0 322.7 1455.7 1455.7
L-2002-070 Page 131 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L101-2305
"#16 i
0.0127 meters 5
0.001143 meters
)
0 meters
............ 0.00051 meters 4
5O i 0.00129 meters
.:%:::::::::::::::::::::::::::::0.304878 meters XLPSN Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.00635 m 0.00012668 m2 4.1499E-05 m2 1.148E-05 m2 Total Volume of Jacket (M3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.025 1.27E-05 3.5E-06 1.62E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0598 0.0106 0.0704 1074.0 252.6 1326.6 2653.2
L-2002-070 Page 132 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L101-2305 0.010414 0.001143 0.000381 0.00064 meters meters meters meters 2
0.00129 meters 0.304878 meters XLPSN (1) (XLPPP)
Insulation Material
'mrboi kss inked n
Insulation Density (kg/m 3) 9244 Insulation Heat of Combustion (kJ/kg 23.,.O Jacket Material 6oIvbM6fnFla mf ise PVC prop:rf:es Jacket Density (kg/m 3) 1441......
Jacket Heat of Combustion (kJ/kg) i....................
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.005207 m 8.5178E-05 m' 4.0332E-05 m2 7.6817E-06 m2 Total Volume of Jacket (in
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Number of Cables Total Width of Cables 0.021 Mass of Jacket per meter (kglm)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJtm)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 2425.6
L-2002-070 Page 133 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
LIOI-2305 4-A1 A 0.0127 0.001143 0.000381 0.00076 meters meters meters meters 2
0.001628 meters 0.304878 meters XLPSN (1) (XLPSMP)
Insulation Material Insulation Density (kg/m 3) 9244 Insulation Heat of Combustion (kJ/kg 23800 Jacket Material in{Ftam i.kise iesi Jacket Density (kg/m 3) 1441...
Jacket Heat of Combustion (kJ/kg) 17i80 Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.00635 m 0.00012668 m2 4.9957E-05 m2 1.1443E-05 m2 Total Volume of Jacket (m 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.038 1.52E-05 3.49E-06 1.87E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0720 0.0106 0.0826 1292.9 251.8 1544.7 4634.0
L-2002-070 Page 134 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L101-2305 2/C#16 035.............
0.00889 meters 5A.........
0.001143 meters
- 0.
m eters S0.00076 meters 2
2 0.00129 meters 0.304878 meters XLPSMP Insulation Material Carbo""',
Insulation Density (kg/m 3) 9244 Insulation Heat of Combustion (kJ/kg Jacket Material C
Jacket Density (kg/m 3) 441.............
Jacket Heat of Combustion (kJ/kg) 179iO Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.004445 m 2
6.2072E-05 m 2.7818E-05 m2 9.8261E-06 m2 Total Volume of Jacket (mi3)
Total Volume of Insulation (m 3)
Total Combustible Volume (m
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Num ber of Cables Total Width of Cables 0.027 8.48E-06 3E-06 1.15E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kglm)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0401 0.0091 0.0492 719.9 216.2 936.1 2808.4
L-2002-070 Page 135 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L101-2305
- 14 0.0127 meters
- I 0.001143 meters
...i 0.000381 meters
.O 0.00076 meters 2
0.001628 meters 1:
0.304878 meters XLPSMP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/k Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.00635 m 0.00012668 M 2
4.9957E-05 M 2
1.1443E-05 m2 Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.52E-05 3.49E-06 1.87E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.025 0.0720 0.0106 0.0826 1292.9 251.8 1544.7 3089.4
L-2002-070 Page 136 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
LI 01-2305
- 16 4...........
0.010922 meters S
0.001143 meters 0.000381 meters 5
0.00064 meters 3
3 5
i 0.00129 meters
............ 0.304878 meters XLPSMP Insulation M aterial Insulation Density (kg/m3) 9244...............
Insulation Heat of Combustion (kJ/kg 2
Jacket Material M.1yotefiri Flan*fro
- ~usePir propertie Jacket Density (kgfm3)
............144.......
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.005461 m 9.369E-05 m' 4.5677E-05 m2 1.1523E-05 m2 Total Volume of Jacket (m3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.39E-05 3.51 E-06 1.74E-05 0.0 0.0 0.0 Number of Cables 3/4 Total Width of Cables 0.055 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kglm)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0659 0.0107 0.0765 1182.1 253.5 1435.6 7178.1
L-2002-070 Page 137 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L101-2305 2/C#16 i 41 0.010414 meters
.45
- ................0.001143 meters 1i 0.000381 meters 0.00064 meters 2.........
2 iiO5O i 0.00129 meters
%-..-..--1 0.304878 meters TEW (XLPPP)
Insulation Material 1.arbo.
Insulation Density (kg/m 3) 9244 Insulation Heat of Combustion (kJ/kg !23&*O!*!*!!!i!*!*
iiiiiii.
Jacket Material R
i M F.aPAW, kis PV
- ro ir ie Jacket Density (kg/m 3) 1441 S Jacket Heat of Combustion (kJ/kg) 179iO Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.005207 m 2
8.5178E-05 m 4.0332E-05 m2 7.6817E-06 m2 Total Volume of Jacket (mi
- 3)
Total Volume of Insulation (M3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.021 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kglm)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 2425.6
L-2002-070 Page 138 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
L101-2305
- 16 41 0.010414 meters 5
0.001143 meters S0000381 meters
............. 0.00064 meters 2
2
- O$
0.00129 meters
.* 0.304878 meters EPDMHYP (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kWJi!
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.005207 m 2
8.5178E-05 m 4.0332E-05 m2 7.6817E-06 m2 Total Volume of Jacket (m3)
Total Volume of Insulation (m3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables
.IBM!.NEI,
Total Width of Cables 0.010 Total Width (m)
Total Energy (m) 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.367 42678.3 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 1212.8
L-2002-070 Page 139 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
M100-2305 3-1/C #4/0 0823i 0.020904 meters
.45i 0.001143 meters 0
meters 5*..
0.00140 meters
'S..": 0.011684 meters S*............
0.304878 meters XLPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/ik Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area 0.0104521 m 2
0.00034321 m 7.0959E-05 m2 5.741 E-05 M2 Total Volume of Jacket (m3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables
- 2 I Total Width of Cables 0.502 2.16E-05 1.75E-05 3.91E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.1023 0.0531 0.1554 1836.4 1263.1 3099.5 74388.2
L-2002-070 Page 140 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (if)
MIOO-2320 3-1/C #4/0
............ 0.020904 15iiiiii"ii.iiiii 0.001143 0
0.00140 1
meters meters meters meters 0.011684 meters 0.304878 meters XLPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/Mr)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (m3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.502 2.16E-05 1.75E-05 3.91 E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0104521 m 2
0.0003432 m 7.096E-05 m2 5.741E-05 m2 0.1023 0.0531 0.1554 1836.4 1263.1 3099.5 74388.2
L-2002-070 Page 141 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2320
- 16 2..... 0.013208 meters 5
0.001143 meters S0.000381 meters 0.00064 meters 0.00129 meters
............. 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg) 9244.
sk t:
i1441 i;;*i* ;I
.1 Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.053 1.86E-05 5.85E-06 2.44E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m2 6.093E-05m2 1.92E-05M 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 7997.2
L-2002-070 Page 142 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2320
"ýIfl 0.0127 0.001143 0.000381 0.00076 meters meters meters meters 2
0.002052 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/rm)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.55E-05 4.11E-06 1.96E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.051 0.00635 m 0.0001267 m' 5.097E-05 m2 2
1.347E-05 M 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 6462.5
L-2002-070 Page 143 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2320 2/C#16 4.i 1
-4 5....
2......
.... I.....
.........iiiiiii~iii 0.010414 meters 0.001143 meters 0.000381 meters 0.00064 meters 2
0.00129 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.062 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kgrm)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 2
8.518E-05 m 2
4.033E-05 m 7.682E-06 m2 244...
4....11W..
MA,........
0.0582 0.0071 0.0653 1043.8 169.0 1212.8 7276.8
L-2002-070 Page 144 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2320 5/C#16 52:
0.013208 meters
.......4..5....
0.001143 meters 1i i
0.000381 meters 5::::::::
- 0.00064 meters 5
5
}OiQ$
0.00129 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kglm3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.079 1.86E-05 5.85E-06 2.44E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJim)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m' 6.093E-05 m2 1.92E-05 i 2
0.0878 0.0178 0.1056 1576.8 422.5 1999.3 11995.8
L-2002-070 Page 145 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2320
,#12
- 0.0127 meters S
0.001143 meters I
0.000381 meters i.....*
0.00076 meters
)
0.002052 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kglm3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg) ie Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M 3 )
Total Volume of Insulation (M 3 )
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.55E-05 4.11E-06 1.96E-05 0.0 0.0 0.0 Mass of Jacket per meter (kglm)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kglm)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJtm)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables I.'x.
x Total Width of Cables 0.038 Total Width (m) 0.283 Total Energy (kJ/m) 38579.3 0.00635 m 0.0001267 m2 5.097E-05M 2 1.347E-05 m2 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 4846.9
L-2002-070 Page 146 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
M100-2393 3-1/C #410 SM'%"iii i.i 0.020904 0- iiiiiiii0.001143
. 0 4 0
- ~0.00140 meters meters meters meters 0.011684 meters 0.304878 meters XLPP Insulation Material Insulation Density (kglm3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3 )
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (mi
- 3)
Total Volume of Insulation (m
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.502 2.16E-05 1.75E-05 3.91 E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0104521 m 0.0003432 m2 2
7.096E-05 m 5.741 E-05 m2 0.1023 0.0531 0.1554 1836.4 1263.1 3099.5 74388.2
L-2002-070 Page 147 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C1 01-2393 2/C#12
..................i 0.0127 m eters i.....
0.001143 meters
- 1.
0.000381 meters
......... 0.00076 meters 2
2 iiv i 0.002052 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m
- 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (M3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Num ber of Cables Total Width of Cables 0.038 1.55E-05 4.11E-06 1.96E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 m2 2
5.097E-05 m 2
1.347E-05 M 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 4846.9
L-2002-070 Page 148 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2393
,#16 2
0.013208 meters
= 0.001143 meters 0.000381 meters 2
0.00064 meters M i.. 0.00129 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (mi 3 )
Total Volume of Insulation (M3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.026 1.86E-05 5.85E-06 2.44E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m' 6.093E-05 m2 1.92E-05 m 2
0.0878 0.0178 0.1056 1576.8 422.5 1999.3 3998.6
L-2002-070 Page 149 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2393 2/C#16 0
ii 0.010414 meters 0.001143 meters 4i 0.000381 meters 2*
0.00064 meters S
2*
2 i
0.00129 meters 1........
0.304878 meters XLPPP Insulation Material Insulation Density (kg/mr)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/mr)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (m3)
Total Combustible Volume (M3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Num ber of Cables Total Width of Cables 0.031 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 8.518E-05 m2 2
4.033E-05 m 7.682E-06 m2 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 3638.4
L-2002-070 Page 150 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2393 5/C #12 0.017272 0.001143 0.000381 0.00076 meters meters meters meters 5
0.002052 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kglm 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (M3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.017 2.49E-05 1.03E-05 3.51 E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.008636 m 0.0002343 m2 2
8.16E-05 m 3.369E-05 in2 0.1177 0.0311 0.1488 2111.8 741.1 2853.0 2853.0
L-2002-070 Page 151 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2393 3#12 k
i 0.0127 meters 4.-
0.001143 meters
.I........... 0.000381 meters
.3C::i:"iii::i-.::ii 0.00076 meters 2
2 0.002052 meters S0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kglm3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius 0.00635 m Total Cable Area (A3) 0.0001267 m2 Jacket Area 5.097E-05 m2 Insulation Area 1.347E-05 m2 Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.051 1.55E-05 4.11 E-06 1.96E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJtm)
Combustible Fuel Load per meter (kJim) 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 6462.5
L-2002-070 Page 152 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2393
'#16 2
0.013208 meters
= 0.001143 meters 5
0.000381 meters 0.00064 meters 5Oi 0.00129 meters S0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/Mi
- 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m
- 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (Mi)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.079 Total Width (m)
Total Energy (kJim) 1.86E-05 5.85E-06 2.44E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJfm)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.243 33795.2 0.006604 m 0.000137 m2 6.093E-05 m2 2
1.92E-05 M 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 11995.8
L-2002-070 Page 153 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
Ml00-2306 3-1/C #4/0 828iiii: 0.020904 meters 4
i 0.001143 meters 0
meters
- 6 0.00140 meters 0.011684 meters 0.304878 meters XLPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/mi)
Jacket Heat of Combustion (kJ/kg)
Caibo..........
14.....1......
Outside Radius 0.0104521 m Total Cable Area (A3) 0.0003432 m2 2
Jacket Area 7.096E-05 m 2
Insulation Area 5.741 E-05 M Total Volume of Jacket (m3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.376 2.16E-05 1.75E-05 3.91 E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kglm)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJJ/m)
Combustible Fuel Load per meter (kJ/m) 0.1023 0.0531 0.1554 1836.4 1263.1 3099.5 55791.2
L-2002-070 Page 154 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2306
'#12 0.0127 meters 0.001143 meters 15 0.000381 meters 0.00076 meters 22 0.002052 meters
..... 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (mi
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (Mi)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.013 1.55405E-05 4.10804E-06 1.96485E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 m2 5.097E-05 i 2
2 1.347E-05 M 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 1615.6
L-2002-070 Page 155 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
CIOI-2306 5/C #16 S*....
%. 0.013208 meters
. 5 0.001143 meters S....
.....0.000381 meters 0.00064 meters S5 0.00129 m eters 1.. %...
0.304878 meters XLPPP Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M3)
Total Combustible Volume (in
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Num ber of Cables Total Width of Cables 0.013 1.85752E-05 5.85494E-06 2.44301 E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m2 6.093E-05 m' 1.92E-05 M 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 1999.3
L-2002-070 Page 156 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C101-2306
'#12 0.0127 meters 0.001143 meters
- IS 0.000381 meters 0.00076 meters
...... 2 0.002052 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/M3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.038 1.55405E-05 4.10804E-06 1.96485E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 2
0.0001267 m2 5.097E-05 m2 1.347E-05 m2
- 4.
4
- 1.
0.0735 0.0125 0.0859 1319.2 296.4 1615.6 4846.9
L-2002-070 Page 157 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
CIOI-2306 5/C#l 6 0.013208 meters A=
=0.001143 meters X..5K
.0.000381 meters 0.00064 meters
.5.
5 0.00129 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/M 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m
- 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.053 1.85752E-05 5.85494E-06 2.44301 E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m' 6.093E-05 m2 1.92E-05 m2 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 7997.2
L-2002-070 Page 158 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
CI01-2306 2/C#16 0.010414 meters 45 0.001143 meters 15 000381 meters 0.00064 meters 2............
2 i
0.00129 meters S*.....................
0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/M3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m2)
Total Volume of Insulation (Mi)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables S
Total Width of Cables 0.031 1.22963E-05 2.34198E-06 1.46383E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Total Width (m)
Total Energy (kUJ/m) 0.005207 m 8.518E-05 m2 4.033E-05 m2 7.682E-06 M 2
0.0582 0.0071 0.0653 1043.8 169.0 1212.8 3638.4 0.148 20097.5
L-2002-070 Page 159 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
M120-2308 3-I/C #410
- .!.i..... 0.020904 0.001143 0
66..
0.00140 1
meters meters meters meters 0.011684 meters 0.304878 meters XLPP Insulation Material Insulation Density (kglm3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (m3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.502 2.16E-05 1.75E-05 3.91 E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kglm)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0104521 m 2
0.0003432 m 7.096E-05 m 2
5.741 E-05 M2
...9 2 4 4.
441....
0.1023 0.0531 0.1554 1836.4 1263.1 3099.5 74388.2
L-2002-070 Page 160 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2308 2/C#12 0.0127 meters
- 4 0.001143 meters 0.00076 meters
~
2
- i$Q i 0.002052 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/im3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/M
- 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m
- 3)
Total Volume of Insulation (M3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.013 1.55405E-05 4.10804E-06 1.96485E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 m2 2
5.097E-05 m 1.347E-05 m 2 U-244ý"
1441..........
0.0735 0.0125 0.0859 1319.2 296.4 1615.6 1615.6
L-2002-070 Page 161 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2308 5/C#16 0.013208 meters S.......................
- 0.
03 1 m t r 45 0001143 meters 15 0.000381 metr S...........
0.00064 meters 55 t:::::
0.00129 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJlkg)
Jacket Material Jacket Density (kg/im
- 3)
Jacket Heat of Combustion (kJ/kg) 2 4.4................
Pot)
(*~*
~
~
fe 1...
441..
T......
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (Mi)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.013 1.85752E-05 5.85494E-06 2.44301 E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m' 6.093E-05 m2 1.92E-05 m2 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 1999.3
L-2002-070 Page 162 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2308 0.018796 0.001524 0.000381 0.00076 7
meters meters meters meters 0.002052 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJlkg)
Jacket Material Jacket Density (kg/m
- 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (mi 3 )
Total Volume of Insulation (M3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.019 3.53206E-05 1.43781 E-05 4.96987E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.009398 m 2
0.0002775 m2 0.0001159 m2 4.716E-05 M2 0.1670 0.0436 0.2106 2998.3 1037.6 4035.8 4035.8
L-2002-070 Page 163 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C120-2308
'#12 0.016256 meters 0.001651 meters
- 0.
o meters 0.00102 meters 8..::::::........
5 1
iQ i 0.002052 meters 0.304878 meters MCCC Insulation Material Insulation Density (kg/M
- 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 2.30954E-05 1.49293E-05 3.80247E-05 0.0 0.0 0.0 Number of Cables i
Total Width of Cables 0.016 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.008128 m 0.0002075 M 7.575E-05 m2 4.897E-05 m2
- ..=
= =
1
.4.
0.1092 0.0453 0.1545 1960.5 1077.3 3037.8 3037.8
L-2002-070 Page 164 of 230 Cable Tray ID C120-2308 Cable Type 2/C#16 Outside Diameter (inches) 41 0.010414 meters Outer Jacket Thickness (mils)
.4.............
0.001143 meters Insulation Jacket Thickness (mils) 1 0.000381 meters Conduct. Insul. Thickness (mils) 0.00064 meters Num. Conds.
2......
2 Diam. Cond. (inches)
$Q: 0.00129 meters Cable Length (feet) 0.304878 meters Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area XLPPP Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/M
- 3)
Jacket Heat of Combustion (kJ/kg) 0.005207 m 8.518E-05 M2 4.033E-05 m2 7.682E-06 m 2
Total Volume of Jacket (M3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.052 1.22963E-05 2.34198E-06 1.46383E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 6064.0 Total Width (m)
Total Energy (kJ/m) 0.113 16752.6
L-2002-070 Page 165 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
M102-2245 3/C #8 0A i
0.021488 meters 3Q 0.001524 meters 5.......... 0.000381 meters 0.00114 meters 3
l 3
S 0.003264 meters 0
m eters X..:
iiiiii 0.304878 meters XLPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m
- 3)
Jacket Heat of Combustion (kJ/kg)
So 924..
. 4..
- Z 38Jb:::
.**..'" '*"M
- "9 " j".
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.021 3.56348E-05 1.44736E-05 5.01084E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0107442 m 0.0003627 m2 0.0001169 m2 4.747E-05 m2 0.1685 0.0439 0.2124 3024.9 1044.4 4069.4 4069.4
L-2002-070 Page 166 of 230 Cable Tray ID M102-2245 Cable Type 3/C #12 Outside Diameter (inches)
$t i
0.015723 meters Outer Jacket Thickness (mils) 60 0.001524 meters Insulation Jacket Thickness (mils) 0.000381 meters Conduct. Insul. Thickness (mils) 0.00076 meters Num. Conds.
3:
3 Diam. Cond. (inches) 1 0.002052 meters Cable Length (ft) 1:
0.304878 meters XLPP (XLPPP)
Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Matedal Jacket Density (kg/M
- 3)
Jacket Heat of Combustion (kJ/kg) 9............
Z...3........
f ~
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 2.50579E-05 6.16206E-06 3.122E-05 0.0 0.0 0.0 Number of Cables Total Width of Cables 0.016 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Total Width (m)
Total Energy (kJ/m) 0.0078613 m 0.0001942 m2 8.219E-05 m2 2.021E-05 m2 0.1185 0.0187 0.1372 2127.1 444.7 2571.8 2571.8 0.037 6641.2
L-2002-070 Page 167 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2245 7#16 4
0.010414 meters
- 4**iiiiiiiiiiii
- i.i::
O0. 001143 meters M*x:
0.000381 meters 0.00064 meters 0.00129 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/M 3 )
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg) 17iiiii 6fl~;;
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.156 1.22963E-05 2.34198E-06 1.46383E-05 0.018 0.002 0.020 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 8.518E-05 M 2
4.033E-05 m2 7.682E-06 m2 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 18192.1
L-2002-070 Page 168 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2245 3#1 2
- 8 0.0127 meters 0.001143 meters 0*0000381 meters 0.00076 meters 22 0.002052 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/M 3 )
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.152 1.55405E-05 4.10804E-06 1.96485E-05 0.022 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 M 2
5.097E-05 M 2
1.347E-05 m2 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 19387.6
L-2002-070 Page 169 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2245 5/C#16
....................... 0.013208 meters 0.001143 meters 0.000381 meters 0.00064 meters OOi43 i 0.00129 meters S
0.304878 meters XLPPP Insulation Material Insulation Density (kg/mi)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
C..........................
O.....
i.......
1..............
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.053 1.85752E-05 5.85494E-06 2.44301 E-05 0.027 0.005 0.032 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m' 6.093E-05 m2 1.92E-05 m2 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 7997.2
L-2002-070 Page 170 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2245 71C #12 o0.018792
- :::: :: :::::0.001524 1 ~ 0.000:381 0.00076 77 meters meters meters meters 0.002052 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 3.53206E-05 1.43781E-05 4.96987E-05 0.1 0.0 0.1 Number of Cables Total Width of Cables 0.019 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.009398 m 0.0002775 m2 0.0001159 m2 4.716E-05 m2 0.1670 0.0436 0.2106 2998.3 1037.6 4035.8 4035.8
L-2002-070 Page 171 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2245 2 - Armored Cable 5
0.0127 meters 0.001143 meters 5
0.000381 meters 0.00076 meters 0.304878 meters XLPE (XLPPP)
Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (Mi)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (mn)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.55405E-05 4.10804E-06 1.96485E-05 0.022 0.004 0.026 Number of Cables Total Width of Cables 0.025 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 M 2
5.097E-05 M 2
1.347E-05 m2 0.0735 0.0125 0.0859 0.0 0.0 0.0 0.0
L-2002-070 Page 172 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2245
'#12 0.017272 meters 0.001524 meters S
0.000381 meters 0.00076 meters 85
................ 0.002052 meters 0 0304878 meters XLPPP Insulation Material Insulation Density (kgIMr)
Insulation Heat of Combustion (kJlkg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg) ten e Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (Mi)
Total Volume of Insulation (Mi)
Total Combustible Volume (Mi)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.017 3.02078E-05 1.02701 E-05 4.04779E-05 0.044 0.009 0.053 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.008636 m 0.0002343 m2 9.908E-05 M 2
3.369E-05 m 2
0.1429 0.0311 0.1740 2564.3 741.1 3305.4 3305.4
L-2002-070 Page 173 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2245 2/C#16 0010414 0.001143 1
0.000381 0.00064 meters meters meters meters 2
0.00129 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/M3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (rn
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.010 1.22963E-05 2.34198E-06 1.46383E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 8.518E-05 m' 4.033E-05 m' 7.682E-06 m2 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 1212.8
L-2002-070 Page 174 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2245 5/C#16
- 52:
0.013208 meters 4Ii i 0.001143 meters 1
i 0.000381 meters 0.00064 meters 55
&!8 0.00129 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Carbonblack ro.......
d e..
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (mi3)
Total Volume of Insulation (M3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.85752E-05 5.85494E-06 2.44301 E-05 0.0 0.0 0.0 Number of Cables Total Width of Cables 0.040 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m' 6.093E-05 m' 1.92E-05 m2 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 5997.9
L-2002-070 Page 175 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2245
,#12
==
0.012802 meters 0.001143 meters 15 0.000381 meters 0.00076 meters 0.00129 meters 0.304878 meters SP Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
E............................................
.14......4..........
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.026 1.50956E-05 2.99575E-06 1.80913E-05 0.022 0.003 0.025 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0064008 m 0.0001287 m2 4.951 E-05 m 2
9.826E-06 m2 0.0714 0.0091 0.0805 1281.4 216.2 1497.6 2995.2
L-2002-070 Page 176 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2245 5/C #12 0.016967 meters
.i.....
0.001524 meters 0.000381 meters
..... 0.00076 meters 5
iiiiiii iii~~~~~~~~~!
5 00505 0.00129 meters 1..
.. 0.304878 meters SP (XLPPP)
Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg) 4...
17.........
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 2.83725E-05 7.48938E-06 3.58619E-05 0.0 0.0 0.0 Number of Cables Total Width of Cables 0.017 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Total Width (m)
Total Energy (kJ/m) 0.0084836 m 0.0002261 m 2
9.306E-05 m 2
2.457E-05 M2 0.1342 0.0227 0.1569 2408.5 540.5 2948.9 2948.9 0.616 66073.0
L-2002-070 Page 177 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
M102-2247 3/C #12 SI9'*d""**.-
0.015723 meters S0.001524 meters S0.000381 meters
.I..........
0.00076 meters i 0.002052 meters 0.304878 meters XLPP (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables I................
Total Width of Cables 0.016 2.51 E-05 6.16E-06 3.12E-05 0.036 0.006 0.042 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kglm)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0078613 m 0.0001942 m2 8.219E-05 m2 2.021 E-05 M 2
0.1185 0.0187 0.1372 2127.1 444.7 2571.8 2571.8
L-2002-070 Page 178 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2247 2/C#16
- 11 0.010414 meters i
0.001143 meters 0.000381 meters
..:......:.:::::::: 0.00064 meters i 8.! 0.00129 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m&)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.021 1.23E-05 2.34E-06 1.46E-05 0.018 0.002 0.020 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 2
8.518E-05 m 2 4.033E-05 M 2
7.682E-06 M 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 2425.6
L-2002-070 Page 179 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2247
,#12
- .5 0.0127 meters 05 0001143 meters S0.000381 meters 0.00076 meters 2
- I0 0.002052 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kglm 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (min3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
N um ber of Cables Total Width of Cables 0.051 1.55E-05 4.11E-06 1.96E-05 0.022 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 2
0.0001267 M2 5.097E-05m2 1.347E-05 mi 2
0.0735 0.0125 0.0859 1319.2 296.4 1615.6 6462.5
L-2002-070 Page 180 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2247 5/C#16 052 0.013208 meters 5
0.001143 meters 1.....
... 0.000381 meters
- 2.
0.00064 meters 5
- (*i
.i 0.00129 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/mi)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.053 1.86E-05 5.85E-06 2.44E-05 0.027 0.005 0.032 Mass of Jacket per meter (kglm)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m2 2
6.093E-05 m 1.92E-05 m2
- c ah.b MO
...0 W 4'
-A
"'PAW" Y..".".0"O'b
.0 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 7997.2
L-2002-070 Page 181 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2247 0.017526 0.001651 0
0.00102 7
meters meters meters meters 0.002052 meters 0.304878 meters MCCC (XLPPP for Insul. Jacket thickness)
Insulation Material z....i.....
Insulation Density (kg/m 3) 2.4.....
Insulation Heat of Combustion (kJ/kg)
Jacket Material I.
W t -d P, m Jacket Density (kg/m 3) 1441.
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (m3)
Total Combustible Volume (M 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.053 2.51 E-05 2.09E-05 4.6E-05 0.0 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kglm)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.008763 m 2
0.0002412 m 2
8.234E-05 m 2
6.856E-05 M 0.1187 0.0634 0.1821 2131.0 1508.3 3639.3 10917.8
L-2002-070 Page 182 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2247 5/C #12 68 0.017272 meters i G 0001524 meters I
0.000381 meters f00 0.002052 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kglm3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (m3)
Total Combustible Volume (M3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 3.02E-05 1.03E-05 4.05E-05 0.044 0.009 0.053 Number of Cables Total Width of Cables 0.017 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.008636 m 0.0002343 m2 9.908E-05 m2 2
3.369E-05 M 0.1429 0.0311 0.1740 2564.3 741.1 3305.4 3305.4
L-2002-070 Page 183 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2247 0.010414 0.001143 0.000381 0.00064 meters meters meters meters 2
0.00129 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kglm3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.010 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJim)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 2 8.518E-05 m 4.033E-05 m2 2
7.682E-06 m 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 1212.8
L-2002-070 Page 184 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2247
- 12 4
0.018796 meters 0.001524 meters S
0.000381 meters 0.00076 meters 7~~~~~~~~~~
7
- 0$ 0.002052 meters i
0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kglm3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (mi
- 3)
Total Volume of Insulation (m3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Num ber of C ables Total Width of Cables 0.019 3.53E-05 1.44E-05 4.97E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJim)
Combustible Fuel Load per meter (kJ/m) 0.009398 m 2 0.0002775 m 0.000,1159 M2 2
4.716E-05 M 0.1670 0.0436 0.2106 2998.3 1037.6 4035.8 4035.8
L-2002-070 Page 185 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C103-2247 2/C #12 050
~ 0.012802 meters 5i..i i 0.001143 meters 4i i 0.000381 meters 0.00076 meters 2
2
. 0.002052 meters 0.304878 meters SP Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/mi)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.026 1.57E-05 4.11 E-06 1.98E-05 0.023 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Total Width (m)
Total Energy (kJim) 0.0064008 m 0.0001287 m' 2
5.134E-05 m 2
1.347E-05 M 0.0740 0.0125 0.0865 1328.6 296.4 1625.1 3250.2 0.249 39607.3
L-2002-070 Page 186 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
Ml 27-222112225 3/C #8 8
.6 0.021488 meters 0.001524 meters 0.000381 meters Al 0.00114 meters 3
3 S0.003264 meters
.... 0.304878 meters XLPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i4iii Total Width of Cables 0.021 3.56E-05 1.45E-05 5.01E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0107442 m 2
0.0003627 m 0.0001169 m2 2
4.747E-05 M 0.1685 0.0439 0.2124 3024.9 1044.4 4069.4 4069.4
L-2002-070 Page 187 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
M127-222112225 31C #12 O6
- 0.015723 meters G
0.001524 meters S0.000381 meters
- 0.00076 meters S0.002052 meters 0.304878 meters XLPP (XLPPP)
Insulation Material Insulation Density (kg/m)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
...................... i; i C a...........
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.016 2.51 E-05 6.16E-06 3.12E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0078613 m 0.0001942 m' 2
8.219E-05 m 2
2.021 E-05 M 0.1185 0.0187 0.1372 2127.1 444.7 2571.8 2571.8
L-2002-070 Page 188 of 230 Cable Tray I D Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
M127-222112225 4 - 1/C #210 712 0.018085 meters
- ................. 0.001143 meters 0
meters 5.......
0.00140 meters 0.009266 m eters 1
0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.072 1.85E-05 1.43E-05 3.28E-05 0.027 0.013 0.040 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Total Width (m)
Total Energy (kJim) 0.0090424 m 0.0002569M 2 6.084E-05M 2
4.68E-05M 2
0.0877 0.0433 0.1310 1574.4 1029.6 2604.0 10416.1 0.110 17057.2
L-2002-070 Page 189 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 2/C#16 0.010414 meters 0.001143 meters i.............
0.000381 meters 2 :
0.00064 meters O
0.00129 meters 0..................
.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius 0.005207 m Total Cable Area (A3) 8.518E-05 m2 2
Jacket Area 4.033E-05 m Insulation Area 7.682E-06 m2 Total Volume of Jacket (m3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.125 1.23E-05 2.34E-06 1.46E-05 0.018 0.002 0.020 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
- 4::::::
- 1441, 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 14553.7
L-2002-070 Page 190 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 5/C #10 0.018796 meters 0.001524 meters 0.000381 meters 0.00076 meters 5
0.002588 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (mi
- 3)
Total Volume of Insulation (M3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.019 3.34E-05 1.22E-05 4.56E-05 0.048 0.011 0.059 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.009398 m 2
0.0002775 m 0.0001096 m2 2
4.01 E-05 m 0.1580 0.0371 0.1951 2836.1 882.2 3718.4 3718.4
L-2002-070 Page 191 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 "7/I 4419 0.018796 0.001524 0.000381 0.00076 meters meters meters meters 7
0.002052 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M 3 )
Total Volume of Insulation (m 3 )
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.019 3.53E-05 1.44E-05 4.97E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.009398 m 0.0002775 m2 2
0.0001159 m 4.71 6E-05 m2 0.1670 0.0436 0.2106 2998.3 1037.6 4035.8 4035.8
L-2002-070 Page 192 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 2/C#12 G :
0.0127 meters i 0.001143 meters S0.000381 meters 3..0.........
000076 meters 2.......
2
- O i$ 0.002052 meters S0.304878 meters XLPPP Insulation Material Insulation Density (kglm 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.152 1.55E-05 4.11 E-06 1.96E-05 0.022 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJIm)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 m' 2
5.097E-05 m 1.347E-05 m 2 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 19387.6
L-2002-070 Page 193 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 5/C #12 a6b 0.017272 meters 0
0.001524 meters
}
0.000381 meters
- 3 i 0.00076 meters 5
5
- 0 i 0.002052 meters 1..
0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kglm3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.069 3.02E-05 1.03E-05 4.05E-05 0.044 0.009 0.053 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJtm)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kUJ/m)
Combustible Fuel Load per meter (kUJ/m) 0.008636 m 0.0002343 m' 2
9.908E-05 m 3.369E-05 m2 0.1429 0.0311 0.1740 2564.3 741.1 3305.4 13221.5
L-2002-070 Page 194 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 0.013208 0.001143 0.000381 0.00064 meters meters meters meters 5
0.00129 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3 Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.026 1.86E-05 5.85E-06 2.44E-05 0.027 0.005 0.032 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m 2 2
6.093E-05 m 1.92E-05 m2 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 3998.6
L-2002-070 Page 195 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 2/C #12 - Armored Cable 0.0127 meters 0.001143 meters 0.000381 m eters 0.00076 meters 2
2 0.002052 meters
. 0.304878 meters XLPE (XLPPP)
Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3n Jacket Heat of Combustion (kJ/kg)
S..
.. 441.........
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (m3)
Total Combustible Volume (m
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.038 1.55E-05 4.11 E-06 1.96E-05 0.022 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 2
0.0001267 m2 5.097E-05 M 1.347E-05 m2 0.0735 0.0125 0.0859 0.0 0.0 0.0 0.0
L-2002-070 Page 196 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 21C#16 0.010414 meters 5
0.001143 meters i
0.000381 meters 2S 0.00064 meters iO iQ$ 0.00129 meters 1
0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kglm3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.010 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJim)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 2
8.518E-05 m 2
4.033E-05 m 2
7.682E-06 M 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 1212.8
L-2002-070 Page 197 of 230 Cable Tray I D Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 7/C #12 74 0.018796 meters B0*
0.001524 meters 1
0.000381 meters i 0 0.00076 meters
- 0.002052 meters
- i~!iiii~~iiiii**;i;;!**iiii*i 0.304878 m eters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/in3 )
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.038 3.53E-05 1.44E-05 4.97E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.009398 m 0.0002775 m' 0.0001159 m2 2
4.716SE-05 M 0.1670 0.0436 0.2106 2998.3 1037.6 4035.8 8071.7
L-2002-070 Page 198 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 5/C #12
-68' 0.017272 meters 60 0.001524 meters S.
.........:.:...:... +.
1, :
0.000381 meters 0.00076 meters 5i 5
0.002052 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (in 3 )
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 3.02E-05 1.03E-05 4.05E-05 0.044 0.009 0.053 Number of Cables Total Width of Cables 0.052 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.008636 m 0.0002343 m' 2
9.908E-05 m 2
3.369E-05 M 0.1429 0.0311 0.1740 2564.3 741.1 3305.4 9916.1
L-2002-070 Page 199 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 2/C #12
- 5 0.0127 meters 5
0.001143 meters 1*
0.000381 meters
.30 0.00076 meters 2
2 S0.002052 meters S
0.304878 meters XLPN Insulation Material Insulation Density (kglm3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.064 1.55E-05 4.11 E-06 1.96E-05 0.022 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 2
0.0001267 m 5.097E-05 m2 2
1.347E-05 M 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 8078.2
L-2002-070 Page 200 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 5/C #16 i
.52 0.013208 meters 4;
0.001143 meters 0.000381 meters 25 0.00064 meters 0.00129 meters
- 1 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Caronblak 1~............
....ii ii Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (M3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.86E-05 5.85E-06 2.44E-05 0.027 0.005 0.032 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.119 0.006604 m 0.000137 m2 6.093E-05 m2 2
1.92E-05 M 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 17993.7
L-2002-070 Page 201 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-222112225 7/C #12 6........
0.017526 meters i5 0.001651 meters 0
0 meters S.................
0 m e er 40 0.00102 meters 7
7 0.002052 meters 0.304878 meters MCCC (XLPPP for Insul. Jacket thicl Insulation Material Insulation Density (kg/M3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m
- 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (Mi)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.070 Total Width (m)
Total Energy (kJim) 2.51 E-05 2.09E-05 4.6E-05 0.0 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.801 0.61 m Tray width used 118745.1 0.008763 m 2
0.0002412 m 8.234E-05m 2
2 6.856E-05 M 0.1187 0.0634 0.1821 2131.0 1508.3 3639.3 14557.0
L-2002-070 Page 202 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
M1 27-2223 3/C #8 0.021488 5G.:i.iK 0.001524
==
0.000381 0.00114 meters meters meters meters 3
0.003264 meters 0.304878 meters XLPP Insulation Material Insulation Density (kg/ma)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3 Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (m3)
Total Combustible Volume (ma)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.021 3.56E-05 1.45E-05 5.01E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0107442 m 0.0003627 m' 0.0001169 m2 4.747E-05 M 6h, P.P y
- -9 -2. A:-'
0.1685 0.0439 0.2124 3024.9 1044.4 4069.4 4069.4
L-2002-070 Page 203 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
M127-2223 3/C #12 B1: 0.015723 meters 30 0.001524 meters 0.000381 meters
=
0.00076 meters 3
3
- i8Oi 0.002052 meters 0.304878 meters XLPP (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius 0.0078613 m Total Cable Area (A3) 0.0001942 m' 2
Jacket Area 8.219E-05M Insulation Area 2.021 E-05 m2 Total Volume of Jacket (m 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.016 2.51 E-05 6.16E-06 3.12E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.1185 0.0187 0.1372 2127.1 444.7 2571.8 2571.8
L-2002-070 Page 204 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (ft)
M127-2223 4-1/C#2/0 T12i 0.018085
.0.001143 0
S0.00140 I
meters meters meters meters 0.009266 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kglm 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (Mi)
Total Volume of Insulation (Mi)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables 4............
Total Width of Cables 0.072 Total Width (m)
Total Energy (kJIm) 1.85E-05 1.43E-05 3.28E-05 0.027 0.013 0.040 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.110 17057.2 0.0090424 m 2
0.0002569 m 2
6.084E-05 m 2
4.68E-05 M 0.0877 0.0433 0.1310 1574.4 1029.6 2604.0 10416.1
L-2002-070 Page 205 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223
,#16 i
0.010414 meters 5
0.001143 meters
$5 0.000381 meters 2S 0.00064 meters 2
0.00129 meters
.............. 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (m3 Total Combustible Volume (m
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.23E-05 2.34E-06 1.46E-05 0.018 0.002 0.020 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.115 0.005207 m 8.518E-05 m' 4.033E-05 m2 7.682E-06 m2 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 13340.8
L-2002-070 Page 206 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223 S#10 4
0.018796 meters 0
0.001524 meters 0.000381 meters 0.00076 meters Q1i 0.002588 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/im 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.019 3.34E-05 1.22E-05 4.56E-05 0.048 0.011 0.059 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kglm)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJIm)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.009398 m 2
0.0002775 m 2
0.0001096 m 4.01 E-05 m2 0.1580 0.0371 0.1951 2836.1 882.2 3718.4 3718.4
L-2002-070 Page 207 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223 Alf* 9~-
0.018796 0.001524 0.000381 0.00076 7
meters meters meters meters 0.002052 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 3.53E-05 1.44E-05 4.97E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJim)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.019 0.009398 m 0.0002775 m' 0.0001159 m2 2
4.71 6E-05 M 0.1670 0.0436 0.2106 2998.3 1037.6 4035.8 4035.8
L-2002-070 Page 208 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C1 21-2223 4ý -9 0.0127 0.001143 0.000381 0.00076 meters meters meters meters 2
0.002052 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/mr3 Jacket Heat of Combustion (kJ/kg)
.6 k:
... I..................
.. 1...
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m3)
Total Combustible Volume (M3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.140 1.55E-05 4.11E-06 1.96E-05 0.022 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 m2 5.097E-05m 2
1.347E-05m 2 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 17772.0
L-2002-070 Page 209 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223
- 12 68 *6 0.017272 meters I
0.001524 meters S0.000381 meters
.J 0.00076 meters 5
5 S0.002052 meters 0.....
0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kglm3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.069 3.02E-05 1.03E-05 4.05E-05 0.044 0.009 0.053 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.008636 m 0.0002343 m 2
9.908E-05 im 2
3.369E-05 i 2 0.1429 0.0311 0.1740 2564.3 741.1 3305.4 13221.5
L-2002-070 Page 210 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area C121-2223
- 16 5
0.013208 meters I
0.001143 meters i 0.000381 meters 0.00064 meters 0.00129 meters 1
0.304878 meters 0.006604 m 0.000137 m' 6.093E-05 im 2
1.92E-05 m2 XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Total Volume of Jacket (m 3)
Total Volume of Insulation (M3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.86E-05 5.85E-06 2.44E-05 0.027 0.005 0.032 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.026 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 3998.6
L-2002-070 Page 211 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (m ils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223 2/C #12 - Armored Cable 0.0127 meters
. 5.*..;.
0.001143 meters 0.000381 meters 3-0 0.00076 meters 2
2 Ci0 0.002052 meters 0.304878 meters XLPE (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (m
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 06038 1.55E-05 4.11 E-06 1.96E-05 0.022 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 m2 2
5.097E-05 m 1.347E-05 M 0.0735 0.0125 0.0859 0.0 0.0 0.0 0.0
L-2002-070 Page 212 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223
- 16 1
0.010414 meters 15 0.001143 meters S0.000381 meters 0.00064 meters 2
2
- 08-0.00129 meters 1*,%.............
0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kglm3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/M3)
Jacket Heat of Combustion (kJ/kg) a..ff c..PRI P
e..............e 4
.... 441.......
Rw~
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.010 1.23E-05 2.34E-06 1.46E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 8.518E-05 m' 2
4.033E-05 m 2
7.682E-06 M 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 1212.8
L-2002-070 Page 213 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223 7/r' 44V) 0.018796 0.001524 0.000381 0.00076 meters meters meters meters 0.002052 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3 )
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m 3)
Total Volume of Insulation (m3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 3.53E-05 1.44E-05 4.97E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.038 0.009398 m 0.0002775 m2 0.0001159 m2 4.716E-05 m2 9244fl
.1 4 4 1..........
0.1670 0.0436 0.2106 2998.3 1037.6 4035.8 8071.7
L-2002-070 Page 214 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223 5/C #12 06 i 0.017272 meters 60..
0.001524 meters i i 0.000381 meters
- M, :::::::::::::::::
0.00076 meters 5
5 0.002052 meters S0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 3.02E-05 1.03E-05 4.05E-05 0.044 0.009 0.053 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.052 0.008636 m 0.0002343 m' 2
9.908E-05 m 3.369E-05 m2 iiiiiii...
ye..Wii
...i
...................... i fft:
- t.
P::
- c 0.1429 0.0311 0.1740 2564.3 741.1 3305.4 9916.1
L-2002-070 Page 215 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223
- 12
............. 0.0127 meters
= 0.001143 meters i 0.000381 meters 0.00076 meters 2
2
- 0.002052 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg) iil.....
ab la
-t4s.e........
potye........enem
- 94. 1 Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M 3 )
Total Volume of Insulation (m 3 )
Total Combustible Volume (m)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.064 1.55E-05 4.11E-06 1.96E-05 0.022 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kglm)
Total Combustible Mass per meter (kglm)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 m2 5.097E-05 M 2
1.347E-05 M 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 8078.2
L-2002-070 Page 216 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223
'#16 0.013208 meters 5
0.001143 meters 0.000381 meters 0.00064 meters 5
5 0.00129 meters S0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3n Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables i
Total Width of Cables 0.119 1.86E-05 5.85E-06 2.44E-05 0.027 0.005 0.032 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kglm)
Total Combustible Mass per meter (kglm)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m2 6.093E-05 m2 1.92E-05 m2 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 17993.7
L-2002-070 Page 217 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2223 7/C #12
.M69.:
0.017 S0.001E 0.00 S7*...
7...... 7 0.00 0.304f
'526 1651 0
)102 meters meters meters meters 2052 meters 4878 meters MCCC (XLPPP for Insul. Jacket th Insulation Material Insulation Density (kg/M 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M 3)
Total Volume of Insulation (m3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.070 Total Width (m) 0.778 C Total Energy (kJ/m) 115916.7 2.51 E-05 2.09E-05 4.6E-05 0.0 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.61 m Tray width used 0.008763 m 0.0002412 m2 8.234E-05 m2 6.856E-05 m2 0.1187 0.0634 0.1821 2131.0 1508.3 3639.3 14557.0
L-2002-070 Page 218 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
M127-2227 3/C#12
£ii69 0.015723 meters i
0.001143 meters i
i 0.000381 meters i
0.00076 meters 3
3 Oi eO ;0.002052 meters 0.304878 meters XLPP Insulation Material Insulation Density (kg/mr)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius 0.0078613 m 2
Total Cable Area (A3) 0.0001942 m2 Jacket Area 6.656E-05 M2 Insulation Area 2.021 E-05 m2 Total Volume of Jacket (m3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (m3 Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Num ber of Cables Total Width of Cables 0.016 2.03E-05 6.16E-06 2.65E-05 0.0 0.0 0.0 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.0960 0.0187 0.1147 1722.7 444.7 2167.3 2167.3
L-2002-070 Page 219 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2227
,#16 41...........
0.010414 meters
- I 0.001143 meters i 0.000381 meters 2:*.:.:.: 0.00064 meters 0.00129 meters i 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
.C.a.rb...o...n 43lck is.....
ri...
- 4...........1M Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (m3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.031 1.23E-05 2.34E-06 1.46E-05 0.018 0.002 0.020 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJtm)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 2
8.51 BE-05 m 4.033E-05 i 2
7.682E-06 m2 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 3638.4
L-2002-070 Page 220 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
Cl 21-2227 2/C#12
- 0. 0127 m eters A
0.001143 meters S
0 0.000381 meters 3
0.00076 meters 2i 2
i 0002052 meters
-.-i 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (mi 3 )
Total Volume of Insulation (m 3 )
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables
.4 Total Width of Cables 0.140 1.55E-05 4.11 E-06 1.96E-05 0.022 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 m2 5.097E-05m 2 2
1.347E-05 M 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 17772.0
L-2002-070 Page 221 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
Cl121-2227 5/C#16 52 0.013208 meters 4i*
0.001143 meters
.. 0.000381 meters 2:
0.00064 meters V*O* i 0.00129 meters 0.304878 meters XLPPP Insulation Material Insulation Density (kglm3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (M3)
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 1.86E-05 5.85E-06 2.44E-05 0.027 0.005 0.032 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.013 0.006604 m 0.000137 m2 6.093E-05 m2 1.92E-05 m2 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 1999.3
L-2002-070 Page 222 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2227
- .#12 74...........
0.018796 meters 0.001524 meters 0.000381 meters 0.00076 meters 7
7 S0.002052 meters S
0.304878 meters XLPPP Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3 Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m 3)
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 3.53E-05 1.44E-05 4.97E-05 0.1 0.0 0.1 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.019 0.009398 m 0.0002775 m' 0.0001159 m2 4.716E-05 m2 0.1670 0.0436 0.2106 2998.3 1037.6 4035.8 4035.8
L-2002-070 Page 223 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2227 5/C #12
- 68 0.017272 meters 0
0.001524 meters 1$
0.000381 meters 3
- 0.00076 meters 5
5
- 0.002052 meters I::::::::::::::::*:::::::::::::::::
0.304878 m eters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.069 3.02E-05 1.03E-05 4.05E-05 0.044 0.009 0.053 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.008636 m 0.0002343 i 2
9.908E-05 m2 2
3.369E-05 M 0.1429 0.0311 0.1740 2564.3 741.1 3305.4 13221.5
L-2002-070 Page 224 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2227 3#16 0.010414 meters
- 0.001143 meters 0.000381 meters 0.00064 meters
...ii 2
~ i 0.00129 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m
- 3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables ii Total Width of Cables 0.010 1.23E-05 2.34E-06 1.46E-05 0.018 0.002 0.020 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.005207 m 8.518E-05 m2 2
4.033E-05 m 7.682E-06 m2 0.0582 0.0071 0.0653 1043.8 169.0 1212.8 1212.8
L-2002-070 Page 225 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2227
'#12 8
0,017272 meters 0
0.001524 meters S0.000381 meters
............. 0.00076 meters 5
0.002052 meters
.............. 0.304878 meters XLPPP Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg)
Outside Radius 0.008636 m Total Cable Area (A3) 0.0002343 m2 Jacket Area 9.908E-05 m2 Insulation Area 3.369E-05 m2 Total Volume of Jacket (M
- 3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.017 3.02E-05 1.03E-05 4.05E-05 0.044 0.009 0.053 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.1429 0.0311 0.1740 2564.3 741.1 3305.4 3305A
L-2002-070 Page 226 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2227 2/C #12
- .i 0.0127 meters 5
0.001143 meters 1M.........
0000381 meters 0.00076 meters 2
2 0002052 meters
........ 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kg/m 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3)
Jacket Heat of Combustion (kJ/kg) o...t...e..
i e Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (m 3 )
Total Combustible Volume (m 3 )
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables
.i...
Total Width of Cables 0.013 1.55E-05 4.11 E-06 1.96E-05 0.022 0.004 0.026 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.00635 m 0.0001267 m2 2
5.097E-05 m 2
1.347E-05 M 0.0735 0.0125 0.0859 1319.2 296.4 1615.6 1615.6
L-2002-070 Page 227 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2227 5/C #16 52 0.013208 meters 4
0001143 meters 1i 0.000381 meters 2
0.00064 meters 5
5 CLV~0* i0.00129 meters 0.304878 meters XLPN (XLPPP)
Insulation Material Insulation Density (kglm 3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kg/m3 Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (m3)
Total Volume of Insulation (m3)
Total Combustible Volume (M3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg)
Number of Cables Total Width of Cables 0.013 1.86E-05 5.85E-06 2.44E-05 0.027 0.005 0.032 Mass of Jacket per meter (kg/m)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kg/m)
Jacket heat of combustion energy per meter (kJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m) 0.006604 m 0.000137 m2 2
6.093E-05 m 1.92E-05 m2 0.0878 0.0178 0.1056 1576.8 422.5 1999.3 1999.3
L-2002-070 Page 228 of 230 Cable Tray ID Cable Type Outside Diameter (inches)
Outer Jacket Thickness (mils)
Insulation Jacket Thickness (mils)
Conduct. Insul. Thickness (mils)
Num. Conds.
Diam. Cond. (inches)
Cable Length (feet)
C121-2227 4* -*1.
0.017526 0.001651 0
0.00102 meters meters meters meters 7
0.002052 meters 0.304878 meters MCCC Insulation Material Insulation Density (kg/m3)
Insulation Heat of Combustion (kJ/kg)
Jacket Material Jacket Density (kglm2)
Jacket Heat of Combustion (kJ/kg)
Outside Radius Total Cable Area (A3)
Jacket Area Insulation Area Total Volume of Jacket (M3)
Total Volume of Insulation (M
- 3)
Total Combustible Volume (M
- 3)
Total Mass of Jacket (kg)
Total Mass of Insulation (kg)
Total Combustible Mass (kg) 2.51 E-05 2.09E-05 4.6E-05 0.036 0.019 0.056 Mass of Jacket per meter (kglm)
Mass of Insulation per meter (kg/m)
Total Combustible Mass per meter (kglm)
Jacket heat of combustion energy per meter (kJJ/m)
Insulation heat of combustion energy per meter (kJ/m)
Combustible Fuel Load per meter per cable (kJ/m)
Combustible Fuel Load per meter (kJ/m)
Number of Cables Total Width of Cables 0.070 Total Width (m)
Total Energy (kJim) 0.396 63357.2 0.008763 m 0.0002412 m2 8.234E-05 m2 2
6.856E-05 M 0.1187 0.0634 0.1821 2131.0 1508.3 3639.3 14557.0
L-2002-070 Page 229 of 230 Appendix B Thermal Material Properties used to Calculated Temperature Response of Target Cable Tray System to Incident Heat Flux BL.
Thermal Conductivity The thermal conductivity for steel as a function of temperature is shown in Table B1.
Because the failure threshold for the cable jacket material is less than 400 'C, the thermal conductivity of the copper and PVC jacket material are essentially temperature independent in this analysis.
Copoer [Holman. 19901:
PVC [Marks, 1996]:
386 W/m-0 C
- 0. 17 W/m-°C Table BI - Temperature Dependent Thermal Conductivity of Steel [Abrams, 1978]
T KCT
((C) k m
)C)
T (OC) k T (0C) k
(°C)(/mOC (W/mO)
T(C (W/mOC)
T °C (W/m-oC) 20.0 46.02 316.0 42.75 649.0 32.84 816.0 29.03 38.0 46.02 371.0 41.04 677.0 32.1 843.0 27.15 73.0 46.4 427.0 39.45 704.0 31.42 871.0 26.40 149.0 45.73 482.0 37.82 732.0 30.92 899.0 26.73 204.0 44.76 538.0 36.44 760.0 30.45 927.0 26.78 260.0 43.84 593.0 34.73 788.0 30.0 1038.0 27.74 B2.
Thermal Heat Capacity The thermal heat capacity for steel as a function of temperature is shown in Table B2.
The thermal heat capacity for PVC as a function of temperature over the range of interest is shown in Table B3. The heat capacity for copper is essentially constant of the temperature range expected in the cable core.
Copper [Holman. 1990]:
383 J/kg-°C
L-2002-070 Page 230 of 230 Table B2 - Temperature Dependant Heat Capacity of Steel [Abrams, 1978]
Table B3 - Temperature Dependant Heat Capacity of PVC [Marks, 1996]
B3.
Density The density for the steel, PVC, and copper is constant of the temperature range considered.
Steel [Abrams, 1978]:
Copper [Holman, 1990]:
PVC [Johnson, 1994]:
7800.0 kg/m3 8954.0 kg/m3 1500.0 kg/m3 T (°C)
(
C T (°C) { C T (°C)
Cp T (°C)
(J/kg-°C)
(J/kg-°C)
(J/kg-°C)
(J/kg-°C) 20.0 467 316.0 558 649.0 777 816.0 568 38.0 471 371.0 580 677.0 810 843.0 535 73.0 484 427.0 606 704.0 1098 871.0 522 149.0 501 482.0 641 732.0 1410 899.0 533 204.0 518 538.0 690 760.0 1012 927.0 568 260.0 536 593.0 736 788.0 727 1038.0 584