ML011430172
| ML011430172 | |
| Person / Time | |
|---|---|
| Site: | Limerick (NPF-039, NPF-085) |
| Issue date: | 05/04/2001 |
| From: | Conte R NRC/RGN-I/DRS/OSB |
| To: | Wasong A Exelon Generation Co |
| References | |
| -RFPFR 05000352/01-301 | |
| Download: ML011430172 (61) | |
Text
ES-301 Control Room Systems and Facility Walk-Through Test Outline Form ES-301-2 Facility: Limerick Generating Station Date of Examination: 05/04/2001 Exam Level:
RO Operating Test No.:
B.1 Control Room Systems System JPM Title Type Safety Code*
Function
- a. Transfer D13 from 101 to 201 DAS 6
- b. Manually Initiate Standby Liquid Control (SLC)
DAS 1
- c. Shutdown Cooling Flow Adjustments - RHRSW Hi Rad LDAS 4
- e. Main Turbine Bypass Valve Exercise Test DS 3
- f. Manually Initiate a Control Room Radiation Isolation DS 9
- g. Primary Containment N2 Make-up NS 5
B.2 Facility Walk-Through
- a. Inadvertent Opening of a Relief Valve DR 3
- b. Remote Alignment of LPCI valves for Fire Safe Shutdown DR 2
HVAC (T-229)
- Type Codes: (D)irect from bank, (M)odified from bank, (N)ew, (A)lternate path, (C)ontrol room, (S)imulator, (L)ow-Power, (R)CA NUREG-1021, Revision 8 22 of 26
ES-301 Control Room Systems and Facility Walk-Through Test Outline Form ES-301-2 Facility: Limerick Generating Station Date of Examination: 05/04/2001 Exam Level:
SRO(I)
Operating Test No.:
B.1 Control Room Systems System / JPM Title Type Safety Code*
Function
- a. Transfer D13 from 101 to 201 DAS 6
- b. Manually Initiate Standby Liquid Control (SLC)
DAS 1
- c. Shutdown Cooling Flow Adjustments - RHRSW Hi Rad LDAS 4
- e. Main Turbine Bypass Valve Exercise Test DS 3
- f. Manually Initiate a Control Room Radiation Isolation DS 9
- g. Primary Containment N2 Make-up NS 5
B.2 Facility Walk-Through
- a. Inadvertent Opening of a Relief Valve DR 3
- b. Remote Alignment of LPCI valves for Fire Safe Shutdown DR 2
- c. Bypass Refuel Floor HVAC isolations and Re-start Refuel Floor NAR 9
HVAC (T-229)
- Type Codes: (D)irect from bank, (M)odified from bank, (N)ew, (A)lternate path, (C)ontrol room, (S)imulator, (L)ow-Power, (R)CA NUREG-1021, Revision 8 22 of 26
ES-301 Control Room Systems and Facility Walk-Through Test Outline Form ES-301-2 Facility: Limerick Generating Station Date of Examination: 05/04/2001 Exam Level:
SRO(U)
Operating Test No.:
B. 1 Control Room Systems System / JPM Title Type Safety Code*
Function
- a.
Primary Containment N2 Make-up NS 5
- b.
Main Turbine Bypass Valve Exercise Test DS 3
- c.
Shutdown Cooling Flow Adjustments - RHRSW Hi Rad LDAS 4
- d.
- e.
- f.
- g.
B.2 Facility Walk-Through
- a.
Bypass Refuel Floor HVAC isolations and Re-start Refuel Floor NAR 9
HVAC (T-229)
- b.
Remote Alignment of LPCI valves for Fire Safe Shutdown DR 2
C.
NUREG-1021, Revision 8
- Type Codes: (D)irect from bank, (M)odified from bank, (N)ew, (A)lternate path, (C)ontrol room, (S)imulator, (L)ow-Power, (R)CA 22 of 26
NUCLEAR GENERATION GROUP EXELON NUCLEAR I TITLE:
TRANSFER D13 BUS FROM 101 TO 201 SUPPLY (ALTERNATE PATH)
TASK PERFORMED BY:
EVALUATOR:
EVALUATOR SIGNATURE:
DATE:
DIRECTIONS TO EVALUATOR:
- 1. Reset the simulator to IC-1 7, and take out of freeze
- 2. Start and Load to 2000 kw D13 D/G per S92.1.0, Local And Remote Manual Startup of a Diesel Generator
- 3. Adjust DG speed and voltage to result in 101 feeder amps as close as possible to zero
- 4. Take 101-D1l sync switch to OFF
- 5. Prepare a copy of $92.6.A initialed up to and including Step 4.1.5 EVALUATION METHOD:
PERFORM EVALUATION LOCATION:
SIMULATOR APPROXIMATE COMPLETION TIME:
15 MINUTES IMPORTANCE RATING(S):
SYSTEM NUMBER(S):
3.7 264000 A4.04
REFERENCES:
- 1. S92.6.A, Rev. 13, Transfer of a 4KV Safeguard Bus from 101 Safeguard Feed to 201 Safeguard Feed and Vice Versa TASK STANDARD(S):
Transfer D1 3 from the 101 to 201 without inadvertently tripping the diesel generator or interrupting power to the D13 bus per S92.6A.
LLCJPMO5I9 RevOOldoc Page 3 of 7 Page 3 of 7 I LLOJPM0519 RevOOl.doc I
NUCLEAR GENERATION GROUP EXELON NUCLEARI TASK CONDITIONS:
- 1. All prerequisites for 4 KV transfer are completed
- 2. S92.1.N, Diesel Generator Set Up for Automatic Operations and S92.9.N Routine Inspection of the Diesel Generators have been completed for D13 Diesel Generator
- 3.
D1 3 has been Started, Synchronized and Loaded to 2000 kW per S92. 1.0, Local and remote manual Startup of a Diesel Generator.
INITIATING CUES:
You are directed by Shift Supervision to transfer 4KV Safeguard Bus from 101 Safeguard Bus Feed to the 201 Safeguard bus feed using D13 Diesel Generator.
LLOJPMO5I9 RevOOlxIoc Page 4 of 7 LLOJPM0519 RevOOl.doc Page 4 of 7
NUCLEAR GENERATION GROUP EXEL ON NUCLEAR]
Critical Element(s) indicated by "'" in Performance Checklist.
PERFORMANCE CHECKLIST:
STEP STANDARD SAT/U NSAT
- 1.
Obtain a copy of $92.6.A NA (CUE: Provide prepared copy of S92.6.A)
- 2. MAINTAIN applicable Safeguard Safeguard Transformer Feeder Transformer Feeder Ammeter as close Ammeter Close to Zero to zero as possible without tripping Diesel Generator Output breaker by adjusting engine speed using 165A(B,C,D) G501/CS, "Diesel Generator Speed Governor Control Switch" (SPEED GOVERNOR).
- 3. OPEN 101 Feeder Breaker (101 101 Feeder Breaker indicates OPEN SAFEGUARDS) to appropriate 4kV and diesel generator maintains proper Safeguard Bus.
Frequency and Voltage
- 4.
PLACE 143-AX103, "101 Safeguard 101 Safeguard Transformer Load Tap Transformer Load Tap Changer" (TAP Changer is in AUTO CHANGER) in "AUTO."
Evaluator Note: The simulator does not model the 201 Safeguard Transformer. The next step must be cued.
- 5.
PLACE 143-BX103, "201 Safeguard 201 Safeguard Transformer Tap Transformer Tap Changer" Changer" (TAP CHANGER) in (TAP CHANGER) in "MANUAL."
"MANUAL."
Cue: The U2 RO reports 143-BX1 03, Safeguard Transformer is in manual
- 6.
INSERT Synchroscope Switch handle Synchroscope Switch (SYNC) for D13 into synchroscope switch (SYNC) for 201 4kV Bus Feeder breaker "ON."
appropriate 201 4kV Bus Feeder breaker AND PLACE to "ON."
- 7.
OBSERVE proper operation of N/A N/A appropriate synchroscope (SYSTEM) by verifying the following:.
- a. Synchroscope rotating.
Synchroscope rotating
- b. WHEN synchroscope is at 180 degrees, At 180 degrees both lights are fully THEN both lights are fully bright, bright LLOJPMO519 RevOOl.doc Page 5 of 7 LL OJPM0519 RevOOl.doc Page 5 of 7
NUCLEAR GENERATION GROUP EXELON NUCLEARI STEP STANDARD SAT/UNSAT
- c. WHEN synchroscope is at 0 degrees, At 0 degrees both lights are off THEN both lights are off.
- 8.
ADJUST engine speed using 165-Synchroscope is rotating slowly in the A(B,C,D)G501/CS, "Diesel Generator SLOW direction (counterclockwise)
Speed Governor Control Switch" (SPEED GOVERNOR) until the synchroscope is rotating slowly in the SLOW direction).
- 9 ADJUST diesel generator voltage using Synchronizing Running Voltmeter 170-A(B,C,D)G502/CS, "Diesel RUNNING is slightly higher (1-5 Volts)
Generator Voltage Regulator Switch" than Synchronizing Incoming (VOLTAGE REGULATOR) until Voltmeter INCOMING "Synchronizing Running Voltmeter,"
RUNNING is slightly higher than "Synchronizing Incoming Voltmeter,"
INCOMING
"*10. WHEN synchroscope (SYSTEM is within 201 Feeder Breaker (201 Safeguards) 3 degrees before 12 O'clock, THEN closed to appropriate 4kV Safeguard CLOSE 201 Feeder Breaker (201 Bus Safeguards) to appropriate 4kV Safeguard Bus II INSTRUCTOR NOTE The following interventions simulate a failure of the D13 DG voltage regulator in the RAISE direction, D13 DG OVERCURRENT alarm, and failure to trip. This will require manual action to secure the DG per the ARC.
Insert 10 Override ZEDB702C "D13 DG Voltage Control SW to RAISE" 10 seconds after 201-D13 breaker is closed Insert Annunciator Cry Wolf 121 E-5 "D13 GENERATOR OVERCURRENT" 20 D13 breaker is closed
- 11. TURN synchronizing switch to "OFF" Synchronizing switch is "OFF"
- 12. Acknowledge Annunciator 121 E-5 Annunciator E-5 Acknowledged
"*13. Shutdown D13 DG D13 DG Breaker tripped or D13 DG control placed to STOP NOTE: Either one or both steps will unload the DG. This may be performed immediately or by referencing S92.2.N, Shutdown of the Diesel Generators Cue: You have met the termination criterion for this JPM. You may stop here seconds after 201-LLOJPMO519 RevOOldoc Page 6 of 7 L LOJPM0519 Re vO01. doc Page 6 of 7
I NUCLEAR GENERATION GROUP EXELON NUCLEAR I Comment Note: Any grade of UNSAT requires a comment.
JPM Overall Rating:
SAT/UNSAT LLQJPMO519 RevOOldoc Page 7 of 7 LL OJPM0519 RevO01. doc Page 7 of 7
NUCLEAR GENERATION GROUP EXELON NUCLEARý TASK CONDITIONS:
1*. All prerequisites for 4 KV transfer are completed
- 2. S92.1.N, Diesel Generator Set Up for Automatic Operations and S92.9.N Routine Inspection of the Diesel Generators have been completed for D13 Diesel Generator
- 3.
D1 3 has been Started, Synchronized and Loaded to 2000 kW per S92.1.0, Local and remote manual Startup of a Diesel Generator.
INITIATING CUES:
You are directed by Shift Supervision to transfer 4KV Safeguard Bus from 101 Safeguard Bus Feed to the 201Safeguard bus feed using D13 Diesel Generator.
I NUCLEAR GENERATION GROUP EXELON NUCLEAR MANUALLY INITIATE SLC (Alternate Path)
TASK PERFORMED BY:
EVALUATOR:
EVALUATOR SIGNATURE:
DATE:
DIRECTIONS TO EVALUATOR:
- 1.
- 2.
- 3.
- 4.
- 5.
- 6.
7.
Reset simulator to any power IC.
Insert malfunction MCU195A, RWCU Isolation Valve (HV44-1F001) fails as-is Insert malfunction MCU002B, RWCU Isolation Valve (HV44-1F004) fails to auto close.
Insert malfunction MRP029B Insert malfunction MRP407C Arm and depress the RPS scram and ARI push buttons Place the mode switch in shutdown EVALUATION METHOD:
PERFORM EVALUATION LOCATION:
SIMULATOR APPROXIMATE COMPLETION TIME:
10 MINUTES IMPORTANCE RATING(S):
4.2/4.2 3.9/3.9 SYSTEM NUMBER(S):
211000 A4.08 211000 A4.06
REFERENCES:
S48.1.B Rev. 9.
TASK STANDARD(S):
Standby Liquid injecting into the RPV, failure of RWCU to isolate is identified, and attempt made to manually isolate RWCU.
LLOJPMO5 16 RevOO4. doc Page 3 of 7 TITLE:
LLOJPM0516 RevO04. doc Page 3 of 7
NUCLEAR GENERATION GROUP EXELON NUCLEARI TASK CONDITIONS:
- 1.
- 2.
3.
ATWS in progress on Unit 1.
SLC injection is directed by T-1 01, "RPV CONTROL" SLC is set up per S48. 1.A, Standby Liquid Control System Setup for Normal Operation INITIATING CUES:
You are directed by Shift Supervision to manually initiate the Unit 1 SLC System, per S48.1.B.
I LLUJI-'MLL51b HevOO4.doc Page 4 of 7 Page 4 of 7 I LLO)JPM0516 RevOO4.doc I
I NUCLEAR GENERATION GROUP EXELON NUCLEAR Critical Element(s) indicated by "*" in Performance Checklist.
PERFORMANCE CHECKLIST:
STEP I
STANDARD SAT/UNSAT
- 1.
Obtain a current revision of S48.1.B.
Current revision of $48.1.B obtained.
Cue:
Once the trainee demonstrates the ability to locate the current revision of the procedure, provide him/her a copy.
- 2.
SLC System set up per S48.1.A, N/A N/A Standby Liquid Control System Set Up For Normal Operation.
- 3.
SLC manual initiation is directed by T-N/A N/A 101, RPV Control.
- 4.
ENSURE 48-1 F036 "SLC Manual 48-1 F036 open.
Injection Maintenance Valve" (INBOARD), open.
- 5.
VERIFY the following SLC squib valve Indicating lights on C603 are lit for:
continuity white lights lit:
XV-48-1 F004A XV-48-1XF004A XV-48-1 F004B XV-48-1XF004B XV-48-1 F004C.
XV-48-1 FO04C
- 6.
ENSURE the following:
N/A N/A 6a.
HV-48-1 F006A "SLC Injection" HV-48-1 F006A is open.
(OUTBOARD A), open.
6b.
HV-48-1F006B "SLC Injection" HV-48-1F006B is open.
(OUTBOARD B), open
- 7.
START the following SLC injection SLC Pump A, B, and C switches to RUN pumps, by holding keylock switches in for at least one second and release.
"RUN" for at least 1 second before releasing:
1AP208 "SLC Injection Pump" 1BP208 "SLC Injection Pump" 1CP208 "SLC Injection Pump" LLOJPMO516 RevOO4.doc Page 5 of 7 Page 5 of 7 I LLOJPM0516 RevOO4.doc I
NUCLEAR GENERATION GROUP EXELON NUCLEAR STEP STANDARD SAT/UNSAT
- 8.
VERIFY squib valves have fired by loss Indicating lights on C603 extinguished for:
of the following continuity white lights:
XV48-1 F004A XV-48-1 F004A XV-48-1 F004B XV-48-1 F004B XV-48-1XF04C.
XV-48-1 F004C
- 9.
PERFORM the following to ensure N/A N/A operation of SLC injection pumps within parameters:
- 10.
VERIFY PI-48-1 R600A,B,C "Pump Indication on C603 for pump discharge Discharge Pressure" (PX), greater than pressure is greater than reactor pressure.
reactor pressure.
- 11.
VERIFY LI-48-1 R601, "SLC Tank C603 indication SLC tank level Level" (LV), lowering at a steady rate.
decreasing.
- 12.
VERIFY lowering reactivity as Available power indications show power observed by lowering power on nuclear going down.
instrumentation.
- 13.
ENSURE the following at 10C602:
N/A N/A 14a.
HV-44-1F001 "RWCU Inboard Recognize HV-44-1 F001 failed to isolate Isolation" (INBOARD), closed, and try to manually close valve. Notify CRS.
Cue:
If asked, respond as the CRS that you understand that the HV-44-1 F001 valve did not close, but you want the Operator to continue with the procedure.
"*15b.
HV-44-1F004, 'RWCU Outboard HV-44-1F004 manually isolated Isolation" (OUTBOARD), closed.
Cue:
You have met the termination criteria for this JPM, you may stop here.
I LLOJPMO51G RevOO4.doc Page 6 of 7 Page 6 of 7 I LLOJPM0516 RevOO4.doc I
I NUCLEAR GENERATION GROUP EXELON NUCLEAR Comments:
Note: Any grade of UNSAT requires a comment.
JPM Overall Rating:
SAT/UNSAT LLOJPMO5I6 RevOO4.doc Page 7 of 7 Page 7 of 7 I LL OJPM0516 RevO04. doc I
NUCLEAR GENERATION GROUP EXELON NUCLEAR TASK CONDITIONS:
- 1.
- 2.
3.
ATWS in progress on Unit 1.
SLC injection is directed by T-1 01, "RPV CONTROL" SLC is set up per S48.1.A, Standby Liquid Control System Setup for Normal Operation INITIATING CUES:
You are directed by Shift Supervision to manually initiate the Unit 1 SLC System, per $48.1.B.
NUCLEAR GENERATION GROUP EXELON NUCLEAR TITLE: SHUTDOWN COOLING FLOW ADJUSTMENTS - RHRSW Hi Rad (Alternate Path)
TASK PERFORMED BY:
EVALUATOR:
EVALUATOR SIGNATURE:
DATE:
DIRECTIONS TO EVALUATOR:
- 1. Reset simulator to IC-5 (Flooded up into Rx Well).
- 2. Adjust HV-C-51-103A (1A RHR Heat Exchanger Outlet Bypass POS) to 100%.
- 3. Ensure HV-51-1F015A (Shutdown Cooling Return Valve) is full open.
- 4. Throttle HV-C-51-1F048A (Heat Exchanger Bypass) closed to obtain 9000 gpm flow.
- 5. Close HV-51-1 F003A (Heat Exchanger Outlet).
- 6. Provide examinee with copy of S51.8.B initialed up to and including Step 4.3.16.4 EVALUATION METHOD:
PERFORM EVALUATION LOCATION:
SIMULATOR APPROXIMATE COMPLETION TIME:
15 MINUTES IMPORTANCE RATING(S):
SYSTEM NUMBER(S):
A4.09 3.1/3.1 205000
REFERENCES:
S51.8.B, Shutdown Cooling/Reactor Circulation Operation Startup and Shutdown, Rev 46 TASK STANDARD(S):
1A RHR pump tripped and 1A RHR Heat Exchanger isolated.
LLOJPM0515 Rev004.doc Page 3 of 6
NUCLEAR GENERATION GROUP EXELON NUCLEAR Tasks Conditions:
- 1.
"IA" RHR has been placed in service for Shutdown Cooling with Reactor Coolant temperature at 85 0F as read on XI-36-101 point 1.
- 2.
"OA" RHRSW pump is in service providing flow to "IA" RHR Heat Exchanger.
- 3.
Reactor level is being maintained at 494" as read on LI-42-1R605.
- 4.
HV-C-51-103A, RHR Heat Exchanger Outlet Bypass (POS), is full open and additional cooling is required to maintain reactor coolant temperature within the 75°F to 850F band.
- 5.
The Unit I Reactor Operator is performing the cooldown ST.
Initiating Cues:
The SSV has directed you to utilize S51.8.8, Shutdown Cooling Operation, to provide additional cooling to reactor coolant.
LLOJPMO51 5 RevOO4.doc Page4of 6 LLOJPM0515 Rev004.doc Page 4 of 6
NUCLEAR GENERATION GROUP EXELON NUCLEAR Critical Element(s) indicated by "*' in Performance Checklist.
PERFORMANCE CHECKLIST:
STEP STANDARD SAT/UNSAT
- 1.
Obtain a Current revision of S51.8.B N/A.
(Cue: Provide prepared copy of S51.8.B)
- 2.
If additional cooling is required, then N/A N/A PERFORM the following:
(Cue: Additional cooling is required) 2a.
OPEN HV-C-51-*F048A(B), Heat HV-C-51-1F048A handswitch to OPEN.
Exch Bypass.
2b.
OPEN HV-51-*FO03A(B), OUTLET HV-51-1F003A handswitch to OPEN.
INSTRUCTOR NOTE Insert MRM019A U1 RHR SW Return Hdr Rad Mon fails to 500 cpm.
2c.
CLOSE HV-C-51-*03A(B), POS.
Depress HV-C-51-103A controller "CLOSE" pushbutton to reduce meter output to 0%.
- 3. Respond to alarm B-4 on 011 SERV Obtain ARC B-4 on 011 SERV WTIR B.
WTR B (RHRSW HI RADIATION.)
(Cue: "I am the CRS you have just received the RHRSW HI Rad Alarm")
- 4.
Verify the high rad condition on RR12-Observe RHRSW rad recorder RR12 OR615A,B.
OR615A and determine increasing trend.
- 5.
If an actual high radiation condition is Determine recorder response is due to suspected, an actual increasing radiation condition.
- 5a.
Trip associated RHR pump.
RHR Pump "IA" handswitch taken to STOP.
5b.
Isolate shell side at 1 F047 or 182.
HV-51-1F047A keylock switch taken to CLOSE, green light on, red light off.
5c.
and 1F003, 103 or 1 F053 for the HV-51-1F003A keylock switch taken to affected loop.
CLOSE, green light on, red light off.
(Cue: Tell Operator, "You can stop here, we have met the termination criteria for this JPM.")
LLJM5 eO4.o ae5o LLOJPM0515 Rev004.doc Page 5 of 6
I NUCLEAR GENERATION GROUP EXELON NUCLEAR Comments:
Note: Any grade of UNSAT requires a comment.
JPM Overall Rating:
SAT/UNSAT LLOJPMO51 5 RevOO4.doc Page 6 of 6 LLOJPM0515 Rev04.doc Page 6 of 6
NUCLEAR GENERATION GROUP EXELON NUCLEAR; Tasks Conditions:
"1.
"IA" RHR has been placed in service for Shutdown Cooling with Reactor Coolant temperature at 850F as read on XI-36-1 01 point 1.
- 2.
"OA" RHRSW pump is in service providing flow to "IA" RHR Heat Exchanger.
- 3.
Reactor level is being maintained at 494" as read on LI-42-1 R605.
- 4.
HV-C-51-103A, RHR Heat Exchanger Outlet Bypass (POS), is full open and additional cooling is required to maintain reactor coolant temperature within the 75 0F to 85°F band.
- 5.
The Unit 1 Reactor Operator is performing the cooldown ST.
Initiating Cues:
The CRS has directed you to utilize S51.8.B, Shutdown Cooling Operation, to provide additional cooling to reactor coolant.
NUCLEAR GENERATION GROUP EXELON NUCLEARI SHIFT HPCI SUCTION FROM THE CST TO THE SUPPRESSION POOL TASK PERFORMED BY:
EVALUATOR:
EVALUATOR SIGNATURE:
DATE:
DIRECTIONS TO EVALUATOR:
- 1. Reset the Simulator to any 100% power IC.
- 2. Place HPCI in full flow test at rated flow from CST-to-CST in accordance with $55.1.D.
- 3. Place the mode switch to shutdown.
- 4. Prepare a copy of $55.1.D marked as follows: Section 4.1 initialed; Section 4.2 N/A; Section 4.3 initialed; Section 4.4 initialed up to and including Step 4.4.3 EVALUATION METHOD:
PERFORM EVALUATION LOCATION:
SIMULATOR APPROXIMATE COMPLETION TIME:
15 MINUTES IMPORTANCE RATING(S):
A4.04 3.7/3.7 SYSTEM NUMBER(S):
206000
REFERENCES:
- 1.
S55.1.D, HPCI System Full Flow Functional Test, Rev. 26, TASK STANDARD(S):
HPCI pump suction aligned to the suppression pool.
TASK CONDITIONS:
- 1. The unit has been shutdown due to decreasing hotwell and CST level.
- 2. HPCI is operating in the full flow test mode at rated flow from CST-to-CST per S55.1.D, Section 4.4. in preparation for closing the MSIVs.
INITIATING CUES:
You are directed by Shift Supervision to swap Unit 1 HPCI suction from the CST to the Suppression Pool per section 4.4.4 of $55.1.D.
TITLE:
LLOJPM0048 RV008.doc Page 3 of 5
NUCLEAR GENERATION GROUP EXELON NUCLEAR Critical Element(s) indicated by "'" in Performance Checklist.
PERFORMANCE CHECKLIST:
STEP STANDARD SAT/UNSAT
- 1.
Obtain current revision of $55.1.D N/A (CUE: Provide prepared copy of S55.1.D)
- 2.
PLACE FIC55-*R600 in "MANUAL" Flow controller in MANUAL and Turbine AND REDUCE HPCI turbine speed to Speed at 2200-2300 rpm.
nominal 2,250 rpm as indicated on SI 56-*61, "Turbine Speed".
- 3.
OPEN HV-55-*F071, "HPCI/RCIC HV-55-1F071 OPEN.
Flush Line to Suppression Pool" (TEST OUTBOARD).
- 4.
CLOSE HV-55-*F01 1, "HPCI/RCIC HV-55-1 F01 1 CLOSED.
Test Return to CST" (CONDENSATE RETURN).
- 5.
IF flow indicated on FIC-55-*R600, If Flow drops below 300, verify HV-55 "HPCI Pump Discharge Flow 1F012 indicates open.
Controller" (FL), falls below 300 gpm.
THEN VERIFY HV-55-*F012, "HPCI Min. Flow Bypass" (MIN FLOW),
opens.
- 6.
OPEN HV-55-*F041, "HPCI Pump HV-55-1 F041 OPEN.
Suction from Suppression Pool (SUPP POOL SUCTION).
- 7.
OPEN HV-55-*F042, "HPCI Pump HV-55-1F042 OPEN.
Suction from Suppression Pool (SUPP POOL SUCTION).
- 8.
ENSURE HV-55-*F004, "HPCI Pump HV-55-1F004 CLOSED.
Suction (COND TK SUCTION),
closes.
- 9.
RAISE HPCI Turbine flow, as N/A N/A required, using FIC-55-*R600, "HPCI Pump Discharge Flow Controller" (FL).
(Cue: You may stop here, you have met the N/A N/A termination criteria for this JPM I LLOJPMOO48 RVOO8.doc Page 4 of 5 Page 4 of 5 I LLOJPM0048 RV008.doc I
I NUCLEAR GENERATION GROUP EXELON NUCLEAR Comments:
Note: Any grade of UNSAT requires a comment.
JPM Overall Rating:
SAT/UNSAT I LLOJPMOO48 RVOO8.doc Page 5 of 5 Page 5 of 5 I LLOJPM0048 RV008.doc I
NUCLEAR GENERATION GROUP EXELON NUCLEAR TASK CONDITIONS:
- 1. The unit has been shutdown due to decreasing hotwell and CST level.
- 2. HPCI is operating in the full flow test mode at rated flow from CST-to-CST per $55.1.D, Section 4.4. in preparation for closing the MSIVs.
INITIATING CUES:
You are directed by Shift Supervision to swap Unit I HPCI suction from the CST to the Suppression Pool per section 4.4.4 of $55.1.D.
NUCLEAR GENERATION GROUP EXELON NUCLEAR TITLE: MAIN TURBINE BYPASS VALVE EXERCISING TASK PERFORMED BY:
EVALUATOR:
EVALUATOR SIGNATURE:
DATE:
DIRECTIONS TO SIMULATOR OPERATOR:
- 1. Reset to a 100% power IC and adjust recirc flow to obtain 99% power.
- 2. Prepare a yellow copy of ST-6-001-761-1 completed up to and including Step 4.3.3, BPV #7 EVALUATION METHOD:
PERFORM EVALUATION LOCATION:
SIMULATOR APPROXIMATE COMPLETION TIME:
20 MINUTES IMPORTANCE RATING(S):
SYSTEM NUMBER(S):
3.9/2.9 A4.06 241000
REFERENCES:
- 1.
ST-6-001-761-1, Rev. 11, Main Turbine Bypass Valve Exercising, TASK STANDARD(S):
- 8 and #9 bypass valves cycled full open then closed TASK CONDITIONS:
- 1. Unit 1 is at 99% power.
- 2. No other testing is in progress on Unit 1.
- 3. The ST is complete up to and including step 4.3.3 BPV-7
- 4. Permission to continue the ST is obtained form the CRS and RO, and all prerequisites are met INITIATING CUES:
You have been directed by the CRS to complete ST-6-001-761-1, Main Turbine Bypass Valve Exercising.
LLOJPMOO83 RevOO3. doc Page 3 of 6 LLOJPM0083 RevO03. doc Page 3 of 6
NUCLEAR GENERATION GROUP EXELON NUCLEAR Critical Element(s) indicated by "'" in Performance Checklist.
PERFORMANCE CHECKLIST:
STEP STANDARD SAT/UNSAT
- 1.
Obtain ST-6-001-761-1 in progress.
N/A (CUE: Provide examinee with yellow copy of ST-6-001-761-1 completed up to and including step 4.3.3 BPV-7.)
- 2.
PERFORM the following for one valve N/A N/A at a time:
- 3.
VERIFY READY TO SELECT light lit, READY TO SELECT green light lit on at panel 1 0C670.
1 0C670.
- 4.
POSITION BYPASS VALVE TEST BYPASS VALVE TEST selector in position selector switch to appropriate position.
- 8.
- 5.
DEPRESS AND HOLD TEST Depress and hold TEST Bypass Valve BYPASS VALVE pushbutton.
pushbutton.
- 6.
VERIFY TESTING AND DO NOT TESTING and DO NOT SELECT amber SELECT lights lit while valve is being lights lit.
exercised.
- 7.
WHEN Bypass Valve is full open, When #8 Bypass Valve indicates 100% on THEN RELEASE TEST BYPASS 10C670, then release TEST BYPASS VALVE pushbutton.
VALVE pushbutton.
- 8.
VERIFY Bypass Valve recloses AND Verify #8 Bypass Valve indicates 0%,
ENTER initials in appropriate blank in examinee enters initials in blank for BPV-8.
step 4.3.3.
- 9.
VERIFY BYPASS VALVE OPEN Acknowledge and reset BYPASS VALVE annunciator on 106 MAIN STEAM OPEN alarm.
clears.
- 10.
WHEN READY TO SELECT light lit READY TO SELECT green light lit.
AND plant conditions are stable, THEN REPEAT steps 4.3.2.1 through 4.3.2.7 for next valve to be tested.
- 11.
VERIFY READY TO SELECT light lit, READY TO SELECT green light lit on at panel 10C670.
10C670.
"*12.
POSITION BYPASS VALVE TEST BYPASS VALVE TEST selector in position selector switch to appropriate position.
- 9.
"13.
DEPRESS AND HOLD TEST Depress and hold TEST Bypass Valve BYPASS VALVE pushbutton.
pushbutton.
LLOJPMOO83 RevOO3. doc Page 4 of 6 LLOJPM0083 RevO03. doc Page 4 of 6
NUCLEAR GENERATION GROUP EXELON NUCLEAR STEP STANDARD SAT/UNSAT
- 14.
VERIFY TESTING AND DO NOT TESTING and DO NOT SELECT amber SELECT lights lit while valve is being lights lit.
exercised.
"*15.
WHEN Bypass Valve is full open, When #9 Bypass Valve indicates 100% on THEN RELEASE TEST BYPASS 10C670, then release TEST BYPASS VALVE pushbutton.
VALVE pushbutton.
- 16.
VERIFY Bypass Valve recloses AND Verify #9 Bypass Valve indicates 0%,
ENTER initials in appropriate blank in examinee enters initials in blank for BPV-9.
step 4.3.3.
- 17.
VERIFY BYPASS VALVE OPEN Acknowledge and reset BYPASS VALVE annunciator on 106 MAIN STEAM OPEN alarm.
clears.
- 18.
Verify each bypass valve completed Step 4.3.3 marked to indicate all bypass one cycle of full travel valves completed a full cycle of travel
- 19.
Position BYPASS VALVE TEST BYPASS VALVE TEST selector switch in selector switch to OFF OFF
- 20.
IF the number of Bypass Valves N/A entered for step 4.3.5.
which are OPERABLE is less than the number required in Table 5 of the Core Operating Limits Report (COLR),AND action statement C of Tech Spec 3.2.3 has not already been satisfied as determined from the LCO Log, THEN REDUCE Rx power in accordance with GP-5 Appendix 2, Section 3.1, as required, to achieve a MFLCPR of less than or equal to 0.90 AND immediately NOTIFY Reactor Engineering. Otherwise ENTER N/A for this step
- 21. IF less than four (4) Bypass Valves are N/A entered for step 4.3.6 operable, THEN CONTACT Reactor Engineering immediately Otherwise ENTER N/A for this step.
LL OJPMOO83 RevOO3. doc Page 5 of 6 LL OJPM0083 RevO03. doc Page 5 of 6
NUCLEAR GENERATION GROUP EXELON NUCLEAR_
STEP STANDARD SAT/UNSAT "23. IF the EOC-RPT trip system is N/A entered in step 4.3.7 inoperable per Tech Spec 3.3.4.2 AND the main turbine bypass system is inoperable per Tech Spec 3.7.8 AND reactor power is =25%,
THEN MCPR is UNANALYZED AND the Tech Spec actions required by Tech Spec 3.2.3.b must be followed.
Otherwise ENTER N/A for this step.
(CUE: You have met the termination criteria for this JPM and can stop here.)
Comments:
Note: Any grade of UNSAT requires a comment.
JPM Overall Rating:
SAT/UNSAT LLOJPMOO83 RevOO3. doc Page 6 of 6 LL OJPM0083 RevOO3.doc Page 6 of 6
NUCLEAR GENERATION GROUP EXELON NUCLEAR INITIATING CUES:
You have been directed by the CRS to complete ST-6-001-761-1, Main Turbine Bypass Valve Exercising.
TASK CONDITIONS:
- 1. Unit 1 is at 99% power.
- 2. No other testing is in progress on Unit 1.
- 3. The ST is complete up to and including step 4.3.3 BPV-7
NUCLEAR GENERATION GROUP EXELON NUCLEARh TITLE:
MANUALLY INITIATE A CONTROL ROOM RADIATION ISOLATION TASK PERFORMED BY:
EVALUATOR:
EVALUATOR SIGNATURE:
DATE:
DIRECTIONS TO EVALUATOR:
- 1.
Reset the simulator to IC-1 7, and take out of freeze.
- 2.
Ensure the A CREFAS fan switch is in AUTO, and the B CREFAS fan switch is in STBY.
- 3.
Ensure the A Control Room Supply and Return fans are in RUN, and the B Control Room Supply and Return fans are in AUTO.
EVALUATION METHOD:
PERFORM EVALUATION LOCATION:
SIMULATOR APPROXIMATE COMPLETION TIME:
10 MINUTES IMPORTANCE RATING(S):
SYSTEM NUMBER(S):
3.2/3.2 A4.01 290003
REFERENCES:
- 1.
$78.8.A, Manual Initiation of Control Room Radiation or Chlorine/Toxic Chemical Isolation Rev. 13 TASK STANDARD(S):
The Control Room HVAC system is operating in the Radiation Isolation Mode, with a Radiation Isolation signal present on the "A" subsystem (Channels A and C), and no Chlorine /Toxic Chemical Isolation signals present.
Page 3 of 8 I LLOJPM0024 RV007.doc
NUCLEAR GENERATION GROUP EXELON NUCLEAR TASK CONDITIONS:
"1. Control Room HVAC is in the normal operating mode per S78.1.A
- 2. The Control Room Emergency Fresh Air Supply System is lined up for automatic operation per S78.1.B.
INITIATING CUES:
You are directed by Shift Supervision to manually initiate a Control Room HVAC Radiation isolation for maintenance using the "A" subsystem only.
I LLOJPMOO24 RVOO7.doc Page 4 of 8 Page 4 of 8 I LLOJPM0024 RV007.doc I
NUCLEAR GENERATION GROUP EXELON NUCLEAR Critical Element(s) indicated by "*" in Performance Checklist.
PERFORMANCE CHECKLIST:
STEP STANDARD 3 SAT/UNSAT
- 1.
Obtain current revision of $78.8.A.
Current revision of $78.8.A obtained.
- 2.
Control Room HVAC in normal N/A N/A operating mode per S78.1.A, Placing the Control Room HVAC System into Normal Operation.
- 3.
Control Room Emergency Fresh Air N/A N/A System lined up for automatic operation per S78.1.B, Aligning the Control Room HVAC Isolation and Emergency Fresh Air Supply System for Automatic Operation.
- 4.
ENSURE keys for keylock Two keys for keylock handswitches HS handswitches HS-78-017A,C (RESET),
78-017A,,C (RESET) are obtained.
are available.
SUBSYSTEM "A" ISOLATION N/A "5.
IF no radiation isolation has been N/A initiated, THEN ensure alignment as follows:
5a.
HS-78-01OA, "A" CONT RM EMERG HS-78-010A, "A" CONT RM EMERG FRESH AIR FAN CONT 0AV127 in FRESH AIR FAN CONT 0AV127 in AUTO AUTO 5b.
HS-78-O10B, "B" CONT RM EMERG HS-78-01 OB, "B" CONT RM EMERG FRESH AIR FAN CONT 0BV127 in FRESH AIR FAN CONT 0BV127 in STANDBY STANDBY
- 6.
PLACE Control Room Isolation Valve Reset Keylock switch HS-78-017C Reset Keylock switch HS-78-017C (RESET C) is placed in "RESET" at (RESET C) to "RESET".
00C681.
- 7.
PLACE Control Room Isolation Valve Reset Keylock switch HS-78-017A Reset Keylock switch HS-78-017A (RESET A) is placed in "RESET" at (RESET A) to "RESET'.
00C681.
- 8 PLACE Control Room Isolation Valve Switch HSS-78-017C (TRIP C) arming Trip Switch HSS-78-017C (TRIP C) to collar is rotated to "RAD" at 00C681.
"RAD".
- 9.
PLACE Control Room Isolation Valve Trip Switch HSS-78-017A (TRIP A) to "RAD".
Switch HSS-78-017A (TRIP A) arming collar is rotated to "RAD" at 00C681.
LLOJPMOO24 RVOO7.doc PageS of 8 LLOJPM0024 RV007.doc Page 5 of 8
NUCLEAR GENERATION GROUP EXELON NUCLEAR STEP STANDARD SAT/UNSAT
- 10.
Acknowledge 002 VENT window B2.
002 VENT window B2 acknowledged.
"*11.
PLACE Control Room Isolation Valve Reset Keylock switch HS-78-017AC Reset Keylock switch HS-78-017C (RESET C) is placed in "AUTO" at (RESET C) to "AUTO".
00C681.
"*12.
PLACE Control Room Isolation Valve Reset Keylock switch HS-78-017A Reset Keylock switch HS-78-017A (RESET A) is placed in "AUTO" at (RESET A) to "AUTO".
00C681.
"*13.
DEPRESS AND RELEASE pushbutton Switch HSS-78-017C (TRIP C) portion of Trip switch HSS-78-017C pushbutton is depressed and released at (TRIP C).
00C681.
"*14.
DEPRESS AND RELEASE pushbutton Switch HSS-78-017A (TRIP A) portion of Trip switch HSS-78-017A pushbutton is depressed and released at (TRIP A).
00C681.
- 15.
RECORD CREFAS run time in CREFAS start data is recorded in appropriate log.
CREFAS run time log.
- 16.
ENSURE HI RAD ISLN Channel A,C HI RAD ISLN Channel A,C amber lights amber lights are Lit.
are Lit
- 17.
VERIFY CONTROL ROOM CONTROL ROOM RADIATION RADIATION ISOLATION INITIATED ISOLATION INITIATED annunciator annunciator alarmed at 002 VENT A-1 alarmed
- 18.
VERIFY CONTROL ROOM CONTROL ROOM RADIATION RADIATION ISOLATION NOT ISOLATION NOT COMPLETE COMPLETE annunciator is not alarmed annunciator is not alarmed at 002 VENT A-3, after 25 seconds
- 19.
ENSURE OA(B)VI 27, Emergency Air OAV1 27, Emergency Air Fan A, is Fan A(B), is running running
- 20.
ENSURE OA(B)V116, CONTROL CONTROL ROOM AIR SUPPLY FAN A ROOM AIR SUPPLY FAN A(B), running OAV1 16, running
- 21.
ENSURE OA(B)V121, CONTROL OAV121, CONTROL ROOM AIR ROOM AIR RETURN FAN A(B),
RETURN FAN A, running running
- 22.
VERIFY PDI-78-054, CONTROL CONTROL ROOM AIR INSIDE/
ROOM AIR INSIDE/OUTSIDE APX, OUTSIDE APX, greater than or equal to greater than or equal to.25 inches
.25 inches water water.
LLOJPMOO24 RVOO7.doc Page 6 of 8 LLOJPM0024 RV007.doc Page 6 of 8
NUCLEAR GENERATION GROUP EXELON NUCLEAR STEP STANDARD SAT/UNSAT
- 23.
IF performing subsection for N/A maintenance, then ENSURE the device positions for RAD isolations per.
(CUE: "You have met the termination criteria for the JPM. You may stop here.")
LLOJPMOO24 RVOO7.doc Page 7 of 8 LLOJPM0024 RV007.doc Page 7 of 8
I NUCLEAR GENERATION GROUP EXELON NUCLEAR Comments:
Note: Any grade of UNSAT requires a comment.
JPM Overall Rating:
SAT/UNSAT LLOJPMOO24 RVOO7.doc Page 8 of 8 LLOJPM0024 RV007.doc Page 8 of 8
NUCLEAR GENERATION GROUP EXELON NUCLEAR TASK CONDITIONS:
"1. Control Room HVAC is in the normal operating mode per S78.1.A
- 2. The Control Room Emergency Fresh Air Supply System is lined up for automatic operation per S78.1.B.
INITIATING CUES:
You are directed by Shift Supervision to manually initiate a Control Room HVAC Radiation isolation for maintenance using the "A" subsystem only.
NUCLEAR GENERATION GROUP EXELON NUCLEAR TITLE:
PRIMARY CONTAINMENT N2 MAKEUP TASK PERFORMED BY:
EVALUATOR:
EVALUATOR SIGNATURE:
DATE:
DIRECTIONS TO EVALUATOR:
- 1. Reset the simulator to IC-17, and take out of freeze
- 2.
Use Malfunction "MCP473, Drywell Air Leak" to reduce drywell pressure until the DRYWELL HI/LO PRESS alarm (107 F-2) is received at 0.1 psig. Then remove the malfunction.
- 3. Acknowledge DRYWELL HI/LO PRESS alarm EVALUATION METHOD:
PERFORM EVALUATION LOCATION:
SIMULATOR APPROXIMATE COMPLETION TIME:
10 MINUTES IMPORTANCE RATING(S):
SYSTEM NUMBER(S):
3.2 223001 A4.10
REFERENCES:
S57.3.B, Primary Containment Pressure Control And Nitrogen Make-Up, Rev 32 TASK STANDARD(S):
Establish makeup flow to drywell and monitor drywell pressure LL 0JPM0523 RevOQO. doc Page 3 of 7 LL OJPM0523 RevO00. doc Page 3 of 7
NUCLEAR GENERATION GROUP EXELON NUCLEAR TASK CONDITIONS:
- 1. Drywell pressure is 0.1 psig due to normal losses
- 2. All prerequisites for S57.3.B are completed
- 3. Makeup N2 is available and lined up for low flow service per $57.8.A INITIATING CUES:
You are directed by Shift Supervision to raise drywell pressure to between 0.2 and 0.7 psig per S57.3.B, Section 4.3.
LLUJPMW523 HevOOO. cloc Page 4 of 7 LLOJIPM0523 RevO00. doc Page 4 of 7
NUCLEAR GENERATION GROUP EXELON NUCLEAR Critical Element(s) indicated by "*" in Performance Checklist.
PERFORMANCE CHECKLIST:
STEP STANDARD SAT/UNSAT
- 1.
Obtain a copy of S57.3.1B.
S57.3.B Obtained
- 2. REFER TO $57.8.A, Placing or removing NA Liquid N2Vaporizing System In (From)
Service and Changing Flow Modes, AND ENSURE Make-up N2 available AND N2 Supply lined up for low flow service.
- 3. PLACE FIC-57-119, "Nitrogen Flow FIC-57-119, "Nitrogen Flow Controller" Controller" (FL), in "MANUAL" AND SET to (FL), in "MANUAL" AND SET to zero.
zero.
- 4. ENSURE HSS-57-196, "H2/0 2 Analyzer 10S206," in "STANDBY 10S206," in "STANDBY."
- 5. ENSURE HSS-57-126, "H2/0 2 Analyzer 10S205," in "STANDBY 10S205," in "STANDBY."
- 6. PLACE HS-57-153 to "CLOSE."
HS-57-153 closed
- 7. PLACE HS-57-187 to "CLOSE."
HS-57-187 closed INSTRUCTOR NOTE:
Activate Remote Function RPC044, Manual Stop Valve 57-1088 to close 57-1088 after being requested in the next step
- 8. CLOSE 57-1088, "N2 Makeup & Atm EO directed to close 57-1088 or Samp Return To Supp Pool Line Maint."
perform $57.3.B Step 4.3.7 (CUE: Report as EO "57-1088 is closed" or
"$57.3.B Step 4.3.7 is complete" as appropriate)
- 9. Slowly throttle OPEN HV-57-116, N2 HV-57-116 throttled open and stopped MAKE-UP for 5 seconds AND PLACE in after approximately 5 seconds "PULL TO STOP" position.
- 10. VERIFY N2 flow using XR-57-119, XR-57-119 red pen indicates flow NITROGEN PURGE, (red pen).
LLOJPMO523 RevOQO. doc Page 5 of 7 LLOJPM0523 RevOOO.doc Page 5 of 7
NUCLEAR GENERATION GROUP EXELON NUCLEAR; STEP STANDARD SAT/U NSAT
- 11. THROTTLE HV-57-116 for desired flow HV-57-116 throttled open with flow rate.
indicating on XR-57-119
- 12. RECORD start time AND Drywell NA NA pressure in RO's Unified Log, using term "N2" contained in entry for System Manager's search.
Note: The Unified Log is not simulated.
(CUE: Unified Log entry has been made)
- 13. MONITOR PI-57-121, (PX(NR))
Drywell pressure monitored on one or OR PMS 057 DRYWELL PRESSURE more of PI-57-121, (PX(NR))
OR PMS 075 DW/POOL PRESS OR PMS 057 DRYWELL VALIDATION PI-57-121 (narrow range).
PRESSURE OR PMS 075 DW/POOL PRESS VALIDATION PI-57-121 (narrow range).
- 14. CUE: "You may stop here. You have met NA NA the termination criteria for the JPM" LLOJPMO523 RevOOC. doc Page 6 of 7 LLOJPM0523 RevO00. doc Page 6 of 7
I NUCLEAR GENERATION GROUP EXELON NUCLEARi Comments:
Note: Any grade of UNSAT requires a comment.
JPM Overall Rating:
SAT/UNSAT LLUJPMO523 RevOOO. doc Page 7 of 7 LL OJPM0523 RevO00. doc Page 7 of 7
NUCLEAR GENERATION GROUP EXELON NUCLEAR TASK CONDITIONS:
"1. Drywell pressure is 0.1 psig due to normal losses
- 2.
All prerequisites for S57.3.B are completed
- 3. Makeup N2 is available and lined up for low flow service per $57.8.A INITIATING CUES:
You are directed by Shift Supervision to raise drywell pressure to between 0.2 and 0.7 psig per S57.3.B, Section 4.3.
NUCLEAR GENERATION GROUP EXELON NUCLEAR TITLE:
INADVERTENT OPENING OF A RELIEF VALVE TASK PERFORMED BY:
EVALUATOR:
EVALUATOR SIGNATURE:
DATE:
DIRECTIONS TO EVALUATOR:
None EVALUATION METHOD:
SIMULATE EVALUATION LOCATION:
PLANT APPROXIMATE COMPLETION TIME:
10 MINUTES IMPORTANCE RATING(S):
SYSTEM NUMBER(S):
/
4.1/4.2 A2.03 239002
REFERENCES:
- 1.
OT-114, Inadvertent Opening of a Relief Valve Rev. 18 TASK STANDARD(S):
Appropriate Fuses are pulled in accordance with OT-1 14.
TASK CONDITIONS:
- 1.
LGS Unit 1 is in OPCON 3.
- 2.
PSV-41 -1 F01 3K has indicated open for two minutes.
INITIATING CUES:
You are directed by Shift Supervision to pull fuses for PSV-41-1F013K in accordance with OT-114.
LLOJPMO2O4 RevOO5.doc Page 3 of 5 Page 3 of 5 I LLOJPM0204 RevOO5.doc I
I NUCLEAR GENERATION GROUP EXELON NUCLEAR Critical Element(s) indicated by "*" in Performance Checklist.
PERFORMANCE CHECKLIST:
STEP STANDARD SAT/U NSAT
- 1.
Obtain current revision of OT-1 14.
Current revision of OT-1 14 obtained.
- 2.
Obtain Fuse Pullers.
Fuse pullers in hand.
NOTE: The operator can obtain fuse puller from a variety of locations. Most likely location is the MCR PRO's desk.
(CUE: Once operator demonstrates ability to obtain fuse pullers, say "You have obtained fuse pullers.")
- 3.
PULL Fuse AA-F4 B21C-F3K at panel Fuse AA-F4 B21C-F3K at panel 10C628 1 OC628.
removed.
(Cue: Fuse is pulled.)
- 4.
PULL Fuse AA-F5 B21C-F4K at panel Fuse AA-F5 B21C-F4K at panel 10C628 1 0C628.
removed.
(Cue: Fuse is pulled.)
- 5.
PULL Fuse AA-F3 B21C-F7K at panel Fuse AA-F3 B21C-F7K at panel 10C631 10C631.
removed.
(Cue: Fuse is pulled.)
- 6.
PULL Fuse AA-F4 B21C-F8K at panel Fuse AA-F4 B21C-F8K at panel 10C631 10C631.
removed.
(Cue: Fuse is pulled.)
(Cue: After all four fuses have been removed, tell operator "You have met the termination criteria for this JPM. You can stop here.")
LLUJHMU2U4 HevOO5.doc Page 4 of 5 Page 4 of 5 I LLO)JPM0204 RevOO5.doc I
I NUCLEAR GENERATION GROUP EXELON NUCLEAR Comments:
Note: Any grade of UNSAT requires a comment.
JPM Overall Rating:
SAT/UNSAT I LLOJPMO2O4 RevOO5.doc Page 5 of 5 Page 5 of 5 I LLOJPM0204 PevOO5.doc I
NUCLEAR GENERATION GROUP EXELON NUCLEAR TASK CONDITIONS:
- 1.
LGS Unit 1 is in OPCON 3.
- 2.
PSV-41-1F013K has indicated open for two minutes.
INITIATING CUES:
You are directed by Shift Supervision to pull fuses for PSV-41-1F013K in accordance with OT-1 14.
NUCLEAR GENERATION GROUP EXELON NUCLEAR!
TITLE:
REMOTE ALIGNMENT OF LPCI VALVES FOR FIRE SAFE SHUTDOWN TASK PERFORMED BY:
EVALUATOR:
EVALUATOR SIGNATURE:
DATE:
DIRECTIONS TO EVALUATOR:
None EVALUATION METHOD:
SIMULATE EVALUATION LOCATION:
IN-PLANT APPROXIMATE COMPLETION TIME:
30 MINUTES IMPORTANCE RATING(S):
SYSTEM NUMBER(S):
3.2/3.8 AA2.14 600000 3.0/3.5 AA2.16 600000 3.1/3.6 AA2.17 600000 3.6/3.7 K4.14 203000
REFERENCES:
- 1. 2FSSG-3068W, Rev 003 TASK STANDARD(S):
Simulate proper operation of 2B RHR EMERGENCY LOCAL VALVE CONTROL PANEL X1 during fire conditions.
I LLOJPMO267 RevOOldoc Page 3 of 6 Page 3 of 6 I LLOJPM0267 RevOOI.doc I
NUCLEAR GENERATION GROUP EXELON NUCLEAR TASK CONDITIONS:
- 1. LGS Unit 2 has been scrammed and safe shutdown procedures are in progress.
- 2. Fire is reported in Unit 2 CRD Hydraulic Equipment Area (El. 253').
- 3. The 2B RHR Pump is running from the Main Control Room.
- 4. The following valves have no position indication in the MCR, can NOT be positioned normally, and need to be in the CLOSED position:
"* HV-051-2F015B "2B RHR SHUTDOWN CLG INJECTION PCIV (OUTBOARD)"
"* HV-051-2F027B "2B RHR SUPP POOL SPRAY LINE PCIV";
"* HV-C-051-2F048B "2B RHR HTX.SHELL SIDE BYPASS VLV. (HEAT EXCH BYPASS)"
INITIATING CUES:
You are directed by Shift Supervision to perform Alignment of Equipment for Manual Initiation of LPCI per 2FSSG-3068W Section 3.3.
LLOJPMO267 RevOOl.doc Page 4 of 6 LL OJPM0267 RevO01. doc Page 4 of 6
NUCLEAR GENERATION GROUP EXELON NUCLEAR Critical Element(s) indicated by "'" in Performance Checklist.
PERFORMANCE CHECKLIST:
STEP STANDARD SAT/UNSAT
- 1. Obtain current revision of 2FSSG-3068W Current revision of 2FSSG-3068W Procedure obtained
- 2. IF any of the following valves can NOT be Operator positions transfer switches on positioned normally, 20-C601-X1, '2B RHR EMERGENCY LOCAL VALVE CONTROL PANEL Xl" When operator positions transfer switches on as necessary to determine HV-051 20-C01-1, 28 RR EERGNCY2F015B, HV-051-2F027B and HV-C LOCAL VALVE CONTROL PANEL Xl",
051-2F048B valve positions.
provide valve position CUE indications as follows:
Operator recognizes HV-C-051-2F048B, "2B RHR HTX. SHELL SIDE BYPASS HSS51-215BX - Green light on, Red light off VLV (
HEAT EXCH BYPASS VLV. (HEAT EXCH BYPASS)" valve is HSS51-227BX - Green light on, Red light off open and needs to be closed.
HSS51-248BX - Green light off, Red light on
- 3. THEN position valve from 20-C601-X1, HSS51-248BX is operated to close HV 2B RHR EMERGENCY LOCAL VALVE C-051-2F048B, "28 RHR HTX. SHELL CONTROL PANEL Xl, using applicable SIDE BYPASS VLV. (HEAT EXCH Transfer Switch (18-217-370)
BYPASS)"
(Note: MOV Control Switch must also be (Note: MOV Control Switch must also operated to close the valve. Transfer switch be operated to close the valve. Transfer only aligns power to the MOV) switch only aligns power to the MOV)
(CUE: Inform operator of indications for HV C-051-2F048B valve closing "dual indication" and then closed "Green light on, Red light off' after appropriate time delay)
- 4. IF HV-51-2F017B, "2B RHR LPCI INJ N/A N/A PCIV (OUTBOARD B)" can NOT be positioned normally, THEN POSITION valve from 20-C601-X2, "2B RHR EMERGENCY LOCAL VALVE CONTROL PANEL X2", (14-283-580) using control switch.
(CUE: When requested from MCR, Inform operator that "HV-051-017B valve is positioned open normally")
- 5. NOTIFY MCR that valves are aligned for MCR personnel notified LPCI operation L L Lj)-muzolUZ R-e VUU 7.
C~o Page 5 of 6
I NUCLEAR GENERATION GROUP EXELON NUCLEAR "Comments:
Note: Any grade of UNSAT requires a comment.
JPM Overall Rating:
SAT/UNSAT I LLC)JPM0267 RevOOldoc Page 6 of 6 Page 6 of 6 I LLOJPM0267 RevO0l.doc I
NUCLEAR GENERATION GROUP EXELON NUCLEARh TASK CONDITIONS:
- 1. LGS Unit 2 has been scrammed and safe shutdown procedures are in progress.
- 2. Fire is reported in Unit 2 CRD Hydraulic Equipment Area (El. 253').
- 3. The 2B RHR Pump is running from the Main Control Room.
- 4. The following valves have no position indication in the MCR, can NOT be positioned normally, and need to be in the CLOSED position:
"* HV-051-2F015B "2B RHR SHUTDOWN CLG INJECTION PCIV (OUTBOARD)"
"* HV-051-2F027B "2B RHR SUPP POOL SPRAY LINE PCIV";
"* HV-C-051-2F048B "2B RHR HTX.SHELL SIDE BYPASS VLV. (HEAT EXCH BYPASS)"
INITIATING CUES:
You are directed by Shift Supervision to perform Alignment of Equipment for Manual Initiation of LPCI per 2FSSG-3068W Section 3.3.
NUCLEAR GENERATION GROUP EXELON NUCLEAR TITLE:
BYPASS REFUEL FLOOR HVAC ISOLATIONS AND RE-START REFUEL FLOOR HVAC (ALTERNATE PATH)
TASK PERFORMED BY:
EVALUATOR:
EVALUATOR SIGNATURE:
DATE:
DIRECTIONS TO EVALUATOR:
None EVALUATION METHOD:
SIMULATE EVALUATION LOCATION:
PLANT APPROXIMATE COMPLETION TIME:
15 MINUTES IMPORTANCE RATING(S):
3.7 SYSTEM NUMBER(S):
295032 EA1.03
REFERENCES:
- 1. T-229, Defeating Refuel HVAC Isolation Logic Rev 001 TASK STANDARD(S):
Refuel Floor HVAC started on Unit
_, with the standby exhaust fan manually started.
LL UJI'MWXe'2 HeVLJLJLJ. cloc Page 3 of 11 LL *JP-MU,..22 RevOO0. doc Page 3 of 11
NUCLEAR GENERATION GROUP EXELON NUCLEARI TASK CONDITIONS:
- 1. Unit is in OPCON 5
- 2. The refuel floor has been evacuated due to lowering cavity level on Unit
- 3. TRIP procedures require refuel floor HVAC isolation signals to be bypassed and refuel floor HVAC restored to permit access to the refuel floor for emergency seal installation
- 4. Zone 1, 2, and 3 are not connected
- 5. Refuel floor HVAC is manually secured INITIATING CUES:
You are directed by shift management to defeat refuel floor HVAC isolation signals and restore Unit refuel floor HVAC to service per T-229, DEFEATING REFUEL FLOOR HVAC ISOLATION LOGIC.
LLOJPMO522 RevOOC. doc Page 4 of 11 LL OJPM0522 RevOOO.doc Page 4 of 11
NUCLEAR GENERATION GROUP EXELON NUCLEAR Critical Element(s) indicated by "*" in Performance Checklist.
PERFORMANCE CHECKLIST:
STEP STANDARD SAT/UNSAT NOTE:
IF this JPM is the first of multiple T-200 series JPMs being performed by a single candidate THEN step #1 applies.
OTHERWISE mark step #1 N/A AND provide the following to the candidate:
- a. INITIATING CUE(S) and Task Conditions sheet
- b. CUE: "You are now in possession of the T-229 equipment container. It contains all tools and equipment required by the procedure. You are to simulate their use during performance of the procedure."
- c. PROCEDURE COPY for the appropriate unit
"*1. The following tools/equipment obtained Student obtains a copy of T-229 and from Unit 1 T-200 cabinet in OSC, the required tools and materials from BL-840 key required:
the T-200 locker (4) Electrical jumpers e
(1) Insulated screwdriver o
(1) Holding screwdriver e
(1) Flashlight (8) PA2235 keys (CUE: Provide the examinee with the procedure copy as soon as the candidate removes the plant copy from the tool box (this allows the candidate to check off items in his or her copy). After the examinee points out the materials he or she will take, say "You have that equipment and copy of T 229.")
- 2. DIRECT Dose Assessment personnel to Contact Control Room and request HP monitor offsite dose.
be directed to monitor offsite dose, or (CUE: Dose Assessment has been directed contact HP directly.
to monitor offsite dose)
LLOJPMO522 RevOQO. doc Page 5 of 11 LL OJPM0522 RevOOO.doc Page 5 of 11
IF Zones I AND III are connected, THEN PLACE the following handswitches in "NORMAL":
HS-76-151A, RF/Rx Encl Cntmt Iso Interlock, at 10C622 (Aux Equip Room).
HS-76-152A, Rx Encl/RF Floor Cntmt Iso Interlock, at 10C622 (Aux Equip Room).
HS-76-151 B, RF/Rx Encl Cntmt Iso Interlock, at 10C623 (Aux Equip Room).
HS-76-152B, Rx EncI/RF Cntmt Iso Interlock, at 10C623 (Aux Equip Room).
(CUE: Zone I and II are not connected)
(If the examinee verifies switches in the Aux Equip. Room, the cue for each switch is "The switch is in NORMAL)
NA NA LLOJPMO522 RevOOC. doc Page 6 of 11 NUCLEAR GENERATION GROUP EXELON NUCLEAR STEP STANDARD SAT/UNSAT
- 3. BYPASS REFUEL FLOOR HVAC NA NA ISOLATIONS
- 3a. INSTALL a jumper from EEE6-2 to Jacks for jumper located and jumper EEE6-3 at 10C606 installed (Aux Equip Room)
(CUE: Jumper is installed)
- 3b. INSTALL a jumper from FFF8-3 to FFF8-Jacks for jumper located and jumper 4 at 10C606 installed (Aux Equip Room)
(CUE: Jumper is installed)
"*3c. INSTALL a jumper from EEE6-2 to Jacks for jumper located and jumper EEE6-3 at 20C606 installed (Aux Equip Room)
(CUE: Jumper is installed)
- 3d. INSTALL a jumper from FFF8-3 to FFF8-Jacks for jumper located and jumper 4 at 20C606 installed (Aux Equip Room)
(CUE: Jumper is installed)
LL OJPM0522 RevOOO.doc Page 6 of 11
NUCLEAR GENERATION GROUP EXELON NUCLEAR1
[
STEP STANDARD SAT/UNSAT SIF Zones I I AND III are connected, THEN PLACE the following handswitches in NA NA "NORMAL":
"* HS-76-251A, RF/Rx Encl Cntmt Iso Interlock, at 20C622 (Aux Equip Room).
"* HS-76-252A, Rx Encd/RF Floor Cntmt Iso Interlock, at 20C622 (Aux Equip Room).
"* HS-76-251B, RF/Rx Encl Cntmt Iso Interlock, at 20C623 (Aux Equip Room).
HS-76-252B, Rx Encd/RF Cntmt Iso Interlock, at 20C623 (Aux Equip Room).
(CUE: Zone II and III are not connected)
(If the examinee verifies switches in the Aux Equip. Room, the cue for each switch is "The switch is in NORMAL)
- 4. BYPASS Low Refuel Floor Enclosure Delta P Isolation to prevent NA NA auto start of SBGTS by placing the following Refuel Floor HVAC Isolation Valve Reset Switches to "RESET":
(Note: the MCR Plant Reactor Operator (PRO) performs the next four steps. Role play as the PRO when communicating)
LLOJPMO522 RevOQO. doc Page 7 of 11 LL OJPM0522 RevOOO.doc Page 7 of 11
NUCLEAR GENERATION GROUP EXELON NUCLEAR J
LLOJPMO522 RevOOO. doc Page 8 of 11 Page 8 of 11 STEP I
STANDARD SAT/UNSAT EVALUATOR NOTE The examinee may request the next 4 steps individually, or he or she may direct the MCR Operator to "Perform T-229 Step 4.5. In the case of the latter, mark JPM steps 4a through 4d SAT, and cue the examinee "T-229 Step 4.5 is complete."
4a. HS-76-181A, HVAC RESET A, at Switch in RESET 10C681 (Main Control Room)
(CUE: HS-76-181A is in RESET) 4b. HS-76-181B, HVAC RESET B, at Switch in RESET 10C681 (Main Control Room)
(CUE: HS-76-181B is in RESET) 4c. HS-76-281A, HVAC RESET A, at Switch in RESET 20C681 (Main Control Room)
(CUE: HS-76-281A is in RESET) 4d. HS-76-281B, HVAC RESET B, at Switch in RESET 20C681 (Main Control Room)
(CUE: HS-76-281B is in RESET)
CAUTION NA NA WHEN starting fans, THEN care must be taken not to exceed load center capacity which would result in a feeder breaker trip. Prior to starting a fan, the existing load should be verified to assure that the added load will remain within limits.
An effort should be made to distribute the loads equally among the load centers.
At no time shall the resulting load exceed 50 amps on any load center as measured at 1 0C654.
(CUE: The load from the fans has been verified to be within the limits by the PRO)
LL OJPM0522 RevO00. doc
NUCLEAR GENERATION GROUP EXELON NUCLEARI STEP STANDARD SAT/UNSAT NOTE NA The Refuel Floor HVAC System on the NA affected unit should be operated IF the Refuel Floor HVAC System on the affected unit is not available, the Refuel Floor HVAC System on the unaffected unit may be operated. However, only the Unit 1 OR Unit 2 Refuel Floor HVAC System may operate, not both.
(CUE: If requested, then provide cue "You are directed to start Unit 1 Refuel Floor HVAC, and Unit 1 Refuel Floor HVAC is available)
- 5. PLACE any two of the following Refueling Any two switches are in RUN Floor Air Supply Fan handswitches to "RUN" at *0C206:
HS-76-*15A HS-76-*15B HS-76-*15C (CUE: Switch is in RUN)
(Note: Supply fans by design will not start at this point. They will start when two exhaust fans are sensed as running)
- 6. ANNOUNCE on Public Address System MCR Operator requested to make requiring all personnel to stand clear of announcement Refuel Floor Air Locks to prevent any personnel injury while starting fans.
(CUE: Communicate as the PRO, and when requested to make the announcement, say "I will make the plant announcement for starting refuel floor HVAC." Several seconds later cue the examinee "You have just heard the announcement made for starting refuel floor HVAC."
LLOJPMO522 RevOQO. doc Page 9 of 11 LL OJPM0522 RevO00. doc Page 9 of 11
NUCLEAR GENERATION GROUP EXELON NUCLEAR STEP STANDARD SAT/UNSAT I
CUE: You may stop here. You have met the termination criteria for the JPM.
1
-
Two switches placed to run Third fan placed to run after start failure of second fan f
LLOJPMO522 RevOQO. doc Page 10 of 11
- 7. PLACE any two of the following Refueling Floor Air Exhaust Fan handswitches to "RUN" at *0C206:
"* HS-76-*65A
"* HS-76-*65B
"* HS-76-*65C CUES:
1' fan: "Switch is in RUN. Red lamp lit, green lamp off".
2 nd fan: "Switch is in RUN. Green lamp lit, red lamp off".
3rd fan: "Switch is in RUN. Red lamp lit, green lamp off' "Red lamps are now lit for the supply fans selected to RUN".
"Refuel floor DP indication is approaching negative 0.3 inches" LL OJPM0522 RevO00. doc Page 10 of I I
NUCLEAR GENERA TION GROUP EXELON NUCLEAR Comments:
Note: Any grade of UNSAT requires a comment.
JPM Overall Rating:
SAT/UNSAT LLOJPMO522 RevOQO. doc Page 11 of 11 LL OJPM0522 RevO00. doc Page 11 of 11
NUCLEAR GENERATION GROUP EXELON NUCLEAR TASK CONDITIONS:
"1. Unit is in OPCON 5
- 2. The refuel floor has been evacuated due to lowering cavity level on Unit
- 3. TRIP procedures require refuel floor HVAC isolation signals to be bypassed and refuel floor HVAC restored to permit access to the refuel floor for emergency seal installation
- 4. Zone 1, 2, and 3 are not connected
- 5.
Refuel floor HVAC is manually secured INITIATING CUES:
You are directed by shift management to defeat refuel floor HVAC isolation signals and restore Unit refuel floor HVAC to service per T-229, DEFEATING REFUEL FLOOR HVAC ISOLATION LOGIC