L-MT-12-035, Emergency Response Data System-Data Point Library Update

From kanterella
Jump to navigation Jump to search
Emergency Response Data System-Data Point Library Update
ML12109A280
Person / Time
Site: Monticello 
Issue date: 04/18/2012
From: O'Connor T
Northern States Power Co, Xcel Energy
To:
Office of Nuclear Reactor Regulation, Document Control Desk
References
L-MT-12-035
Download: ML12109A280 (69)


Text

April 18, 2012 Monticello Nuclear Generating Plant 2807 W County Road 75 Monticello. MN 55362 L-MT-12-035 10 CFR 50 Appendix E.Vl.3.a U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Monticello Nuclear Generating Plant Docket 50-263 Renewed Facility Operating License No. DPR-22 Emeraencv Response Data Svstem-Data Point Librarv Update Pursuant to the requirements of 10 CFR 50, Appendix El Section V1.3, "Maintaining the Emergency Response Data System," the Northern States Power Company, a Minnesota corporation (NSPM), doing business as Xcel Energy, the licensee for the Monticello Nuclear Generating Plant (MNGP), is submitting this letter to inform the NRC of updates to the Emergency Response Data System (ERDS) data point library implemented April 1, 2012. The ERDS data point library was revised to document replacement of 16 Meteorological Information and Dose Assessment System (MIDAS) computer points with Radiological Assessment System for Consequence Analysis (RASCAL) computer points. Enclosure 1 contains a summary of the revised computer points. Enclosure 2 contains a copy of the updated ERDS Data Point Library.

Summarv of Commitments r revisions to any existing commitments.

Nuclear Generating Plant Power Company-Minnesota Enclosures (2) cc:

Regional Administrator, Region Ill, USNRC Project Manager, Monticello Nuclear Generating Plant, USNRC Resident Inspector, Monticello Nuclear Generating Plant, USNRC Monticello Nuclear Generating Plant Summary of Changes to Data Point Library (I Page to follow)

L-MT-12-03 5 Page 1 of 1 Emergency Response Data System data point library (ERDS-SRS-1-10) was revised to document replacement of MlDAS computer points with RASCAL computer points as shown in the table below.

I MET1 10 MT 43M AVG DELTA TEMP A I MET140FR MT 43M-10M A DELTA AIR T 15MRUN MlDAS Computer Point MET1 13 MT 100M AVG DELTA TEMP B I MET139FR MT 100M-10M B DELTA AIR T 15MRUN RASCAL Computer Point I MET1 12 MT 100M AVG DELTA TEMP A I MET1 38FR I

MT 100M-1 OM A DELTA AIR T 1 5MRUN MET1 11 MT 43M AVG DELTA TEMP B MET141FR MT 43M-10M B DELTA AIR T 15MRUN MET1 06 MT 43M AVG WIND DIRECTA MET128FR MT 43M A WIND DIR 15MRUN I

MET1 07 MT 43M AVG WIND DIRECTB MET108 MT 100M AVG WlND DIRECTA I

MET104 MT IOOM AVG WlND SPEED A I MET120FR MT 100M A WlND SPEED 15MRUN MET129FR MT 43M B WIND DIR 15MRUN MET126FR MT 100M A WIND DIR 15MRUN MET102 MT 43M AVG WIND SPEED A MET103 MT 43M AVG WIND SPEED B MET122FR MT 43M A WIND SPEED 15MRUN MET123FR MT 43M B WIND SPEED 15MRUN MET105 MT 100M AVG WlND SPEED B MET121FR MT 100M B WlND SPEED 15MRUN MET109 MT 100M AVG WIND DIRECTB MET127FR MT 100M B WlND DIR 15MRUN p 1 2 1 STACK EFF MONITOR CH A PRM500FR STACK EFF RAD A 15MRUN PRM122 STACK EFF MONITOR CH B PRM501FR STACK EFF RAD B 15MRUN PRM123 RBV EFFLUENT MONITOR CHA PRM124 RBV EFFLUENT MONITOR CHB PRM123FR RBV EFFLUENT MONITOR CHA 15MAVG PRM124FR RBV EFFLUENT MONITOR CHB 15MAVGS Monticello Nuclear Generating Plant Process Computer System - Emergency Response Data System Data Point Library (65 Pages to follow)

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

1 I

Effective Date:

LIST OF PAGES SHEET 1

2 7

8 9

I 0 11 13 14 15 19 2 1 22 23 27 33 35 37 38 39 40 41 42 44 46 48 52 56 60 63 DESCRIPTION LIST OF PAGES NI POWER RANGE NI INTER RANGE NI SOURC RNG REAC VES LEV RCSPRESSURE MAIN FD FLOW HPCI FLOW RClC FLOW LPCl FLOW CR SPRAY FL DW ED SMP LV DW FD SMP LV EFF GAS RAD EFF LIQ RAD COND AIE RAD DW RAD MN STEAM RAD DW PRESS DW TEMP SP TEMP SP LEVEL H2 CONC 0 2 CONC CST LEVEL WlND SPEED WlND DIR STAB CLASS Contacts Data Feeder Information REVISION and DATE Revision 8, 511 2/06 Revision 8, 511 2/06 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 10, 311 511 2 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 10, 311 511 2 Revision 1 0, 311 511 2 Revision 1 0, 311 511 2 Revision 9, 5/06/09 Revision 9, 5/06/09

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library I 0 Sheet No:

2 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarmrrrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS NI POWER RNG C5 1 C400 1 AVERAGE CONSISTENT APRM READING NUCLEAR INSTRUMENTS, POWER RANGE A

NIA 0

125 NIA NIA P

12 AVERAGE OF CONSISTENT APRMS APRM UTILIZE 24 LPRMS LOCATED IN CORE HI-HI TRIP=(.58W+62%),W=%REClRC FLOW NIA NIA This point consists of either an average of all consistent APRMs or an average of in-range APRMs if there are less than the required number of consistent signals.

APRMS(Average Power Range Monitors) consist of an average of 24 LPRMs (Local Power Range Monitors). Each individual APRM signal will fail on Downscale(3%), Inop, or Bypass. HI-HI trip feed RPS SCRAM for one-out-of-three-twice logic. HI trip (.58W+50%) results in Rod Withdraw Block.

Northern States Power Company Monticello Nuclear Generating Plant Soflware Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS System (ERDS) - Data Point Library 10 Sheet No:

3 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

.Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 05106109 M01 PCS NI POWER RNG NU1196 APRM # I NUCLEAR INSTRUMENTS, POWER RANGE A

NIA 0

125 NIA NIA S

24 AVERAGE OF 24 LPRMs APRM UTILIZE 24 LPRMs LOCATED IN CORE Note A NIA HIGH & LOW SENSOR NIA NIA NIA The APRM provides overall power range monitoring, the range monitored is from approximately 3 to 100% power, The reading of APRM is the average of 24 LPRM signals and provides output signal that are proportional to average neutron flux. The output signal is recorded on reactor control console recorder and indicated on the APRM Panel indicator. Trip circuit associated with APRM channel provides trip output signals to the RMCS rod withdrawal block circuits and the RPS scram circuitry.

Note A: Three AlarmITrip Set Points:

HI-HI TRIP=(.66W+59.6%),W=%RECIRC FLOW UPSCALE TRIP=I 19.5% (MODE SWITCH IN RUN)

UPSCALE TRIP=l 8% (MODE SWITCH NOT IN RUN)

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification I

Title:

Number:

SRS

~-Yicess Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

4 DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

05/06/09 M01 PCS NI POWER RNG NU1197 APRM #4 NUCLEAR INSTRUMENTS, POWER RANGE A

NIA 0

125 N/A NIA S

24 AVERAGE OF 24 LPRMs APRM UTILIZE 24 LPRMs LOCATED IN CORE Note A NIA HIGH & LOW SENSOR NIA NIA NIA The APRM provides overall power range monitoring, the range monitored is from approximately 3 to 100% power. The reading of APRM is the average of 24 LPRM signals and provides output signal that are proportional to average neutron flux. The output signal is recorded on reactor control console recorder and indicated on the APRM Panel indicator. Trip circuit associated with APRM channel provides trip output signals to the RMCS rod withdrawal block circuits and the RPS scram circuitry.

Note A: Three AlarmITrip Set Points:

HI-HI TRIP=(.66W+59.6%),W=%RECIRC FLOW UPSCALE TRIP=I 19.5% (MODE SWITCH IN RUN)

UPSCALE TRIP=18% (MODE SWITCH NOT IN RUN)

Northern States Power Com~anv Monticello Nuclear ~enerati;~

plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

5 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 05106109 M01 PCS NI POWER RNG NU1198 APRM #2 NUCLEAR INSTRUMENTS, POWER RANGE A

NIA 0

125 NIA NIA S

24 AVERAGE OF 24 LPRMs APRM UTILIZE 24 LPRMs LOCATED IN CORE sNote A NIA HIGH & LOW SENSOR NIA NIA NIA The APRM provides overall power range monitoring, the range monitored is from approximately 3 to 100% power. The reading of APRM is the average of 24 LPRM signals and provides output signal that are proportional to average neutron flux. The output signal is recorded on reactor control console recorder and indicated on the APRM Panel indicator. Trip circuit associated with APRM channel provides trip output signals to the RMCS rod withdrawal block circuits and the RPS scram circuitry.

Note A: Three AlarmITrip Set Points:

HI-HI TRIP=(.66W+59.6%),W=%RECIRC FLOW UPSCALE TRIP=I 19.5% (MODE SWITCH IN RUN)

UPSCALE TRIP=18% (MODE SWITCH NOT IN RUN)

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

6 DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

05106109 M01 PCS NI POWER RNG NU1200 APRM #3 NUCLEAR INSTRUMENTS, POWER RANGE A

NIA 0

125 NIA NIA S

24 AVERAGE OF 24 LPRMs APRM UTILIZE 24 LPRMs LOCATED IN CORE Note A NIA HIGH & LOW SENSOR NIA NIA NIA The APRM provides overall power range monitoring, the range monitored is from approximately 3 to 100% power. The reading of APRM is the average of 24 LPRM signals and provides output signal that are proportional to average neutron flux. The output signal is recorded on reactor control console recorder and indicated on the APRM Panel indicator. Trip circuit associated with APRM channel provides trip output signals to the RMCS rod withdrawal block circuits and the RPS scram circuitry.

Note A: Three AlarmITrip Set Points:

HI-HI TRIP=(.66W+59.6%),W=%RECIRC FLOW UPSCALE TRIP=I 19.5% (MODE SWITCH IN RUN)

UPSCALE TRIP=18% (MODE SWITCH NOT IN RUN)

Northern States Power Company S

Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library DATA POINT LIBRARY REFERENCE FILE Date:

0 1/07/92 Reactor Unit:

M01 Data Feeder:

PCS NRC ERDS Parameter:

NI INTER RNG Point ID:

Plant Spec Point Desc.:

(not available)

GenericICond Desc.:

NUCLEAR INSTRUMENTS, INTERMEDIATE RANGE AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

System.

Not available to Process Computer

Northern States Power Com~anv Monticello Nuclear ~ e n e r a t i i ~

plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

8 DATA POINT LIBRARY REFERENCE FILE Date:

01 I07192 Reactor Unit:

M01 Data Feeder:

PCS NRC ERDS Parameter:

NI SOURC RNG Point ID:

Plant Spec Point Desc.:

(not available)

GenericICond Desc.:

NUCLEAR INSTRUMENTS, SOURCE RANGE AnaloglDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

Not available to Process Computer System.

Northern States Power Company Monticello Nuclear ~enerating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I -

System (ERDS) - Data Point Library 10 Sheet No:

9 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1107192 M01 PCS REAC VES LEV B21 COO1 0 RPV VALIDATED WATER LEVEL REACTOR VESSEL WATER LEVEL A

INCHES NIA

-350 350 MSSKRT 0" CORRESPONDS TO 126" ABOVE TOP OF FUEL P

28 WEIGHTED AVERAGE OF CONSISTENT LEVELS LEVEL REF LEGS - 5 HOT(IN DW) & 2 COLD

-48"=ECCS INIT, 9"=SCRAM, 48"=HI TRIP NIA

+280" TOP OF REACTOR HEAD NIA WET This point consists of either a weighted average of all consistent level indicators or an average of in-range level indicators if there are less than the required number of consistent signals. Algorithm performs temperature compensation and evaluates reference leg flashing on 7 level signals. Safeguards Levels (-50" to 50") utilize cold reference leg design outside of drywell. ECCS levels (-335" to 65") are invalidated with recirc pumps running. Other levels include 2 feedwater (0 to 60") and 1 vessel flood (-50" to 350").

Northern States Power Company SRS Process Computer System - Emergency Response Data System (ERDS) - Data Point Library DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

0111 9/93 M01 PCS RCS PRESSURE B21 C0210 RPV VALIDATED PRESSURE REACTOR COOLANT SYSTEM PRESSURE A

PSIG NIA 0.00 1500 NIA NIA P

3 WEIGHTED AVERAGE OF CONSISTENT LEVELS PRESSURE SENSED OFF LEVEL REF LEGS 1056 PSIG=SCRAM NIA HIILOW SENSOR NIA NIA This point consists of either a weighted average of all consistent pressure indicators or an average of in-range pressure level indicators if there are less than the required number of consistent signals.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

11 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1 107192 M01 PCS MAIN FD FLOW C51 C9001 SMOOTHED FEEDWATER FLOW LOOP A FEEDWATER FLOW INTO THE REACTOR SYSTEM A

MLBIHR NIA 0

4 NIA NIA P

4 SMOOTHED FW FLOW CALC FROM A NOZZLE DIP FW NOZZLE IS DOWNSTREAM OF RX FW PUMPS NIA NIA NIA HIILOW SENSOR NIA NIA NIA SMOOTHED FW FLOW LOOP A is calculated using Feedwater nozzle DIP, Pressure, and temperature. Smoothing algorithm sums 1/12 current sample + 11/12 of previous smoothed value. Sampling frequency is 5 seconds. Feedwater nozzles are located downstream of Reactor Feedwater Pumps and ahead of high pressure heaters.

Northern States Power Company SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library Sheet No:

12 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI-Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01 107192 M01 PCS MAIN FD FLOW C51 C9002 SMOOTHED FEEDWATER FLOW LOOP B FEEDWATER FLOW INTO THE REACTOR SYSTEM A

MLBIHR NIA 0

4 NIA NIA P

4 SMOOTHED FW FLOW CALC FROM B NOZZLE DIP FW NOZZLE IS DOWNSTREAM OF RX FW PUMPS NIA NIA HIILOW SENSOR NIA NIA NIA SMOOTHED FW FLOW LOOP B is calculated using Feedwater nozzle DIP, Pressure, and temperature. Smoothing algorithm sums 1/12 current sample + 11/12 of previous smoothed value. Sampling frequency is 5 seconds. Feedwater nozzles are located downstream of Reactor Feedwater Pumps and ahead of high pressure heaters.

Northern States Power Company cess Computer System - Emergency Response Data System (ERDS) - Data Point Library Sheet No:

13 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0111 9/93 MO1 PCS HPCl FLOW HPCl 00 HPCl PUMP DISCHARGE FLOW HlGH PRESSURE COOLANT INJECTION FLOW A

GPM NIA 0

3500 NIA NIA S

1 SIGNAL INPUT FROM FLOW TRANSMITTER FLOW ELEMENT ON HPCl PUMP DISHARGE NIA NIA HlGH & LOW SENSOR NIA NIA NIA HPCl is a steam turbine driven pump designed to deliver 2700 gpm over reactor pressure range of 150-1 120 psig. Flow element is located on pump disharge line ahead of the test return line to the CST tanks and injection line into "B" feedwater line. HPCI injects into feedwater line prior to the line entering containment.

Northern States Power Company Monticello Nuclear Generating Plant Soflware Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

14 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01 107192 M01 PCS RClC FLOW RCI 100 RClC PUMP DISCHARGE FLOW REACTOR CORE ISOLATION COOLING A

GPM NIA 0

500 NIA NIA S

1 SIGNAL INPUT FROM FLOW TRANSMITTER FLOW ELEMENT ON RClC PUMP DISHARGE NIA NIA HIGH & LOW SENSOR NIA NIA NIA RClC is a steam turbine driven pump designed to deliver 400 gpm over reactor pressure range of 150-1 120 psig. Flow element is located on pump disharge line ahead of the test return line to the CST tanks and injection line into "A" feedwater line. RClC injects into feedwater line prior to the line entering containment.

Northern States Power Company Monticello Nuclear ene era tin^ Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

15 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:.

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1107192 M01 PCS LPCI FLOW RHRI 00 CONTAINMENT SPRAYICOOLING A LOOP LOW PRESSURE COOLANT INJECTION FLOW A

GPM NIA 0

10000 NIA NIA S

1 SIGNAL INPUT FROM FLOW TRANSMITTER DISCHARGE OF RHR HEAT EXCHANGERS NIA NIA HIGH & LOW SENSOR NIA NIA NIA CONTAINMENT SPRAYICOOLING A LOOP flow is the RHR flow to the A loop drywell spray, torus spray and torus cooling.

Each RHR pump is approximately rated at 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.

Northern States Power Company Monticello Nuclear Generating Plant Soflware Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

16 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc. :

DATA POINT LIBRARY REFERENCE FILE 0 1107192 M01 PCS LPCl FLOW RHRIOI CONTAINMENT SPRAYICOOLING B LOOP LOW PRESSURE COOLANT INJECTION FLOW A

GPM NIA 0

10000 NIA NIA S

1 SIGNAL INPUT FROM FLOW TRANSMITTER DISCHARGE OF RHR HEAT EXCHANGERS NIA NIA HIGH & LOW SENSOR NIA NIA NIA CONTAINMENT SPRAYICOOLING B LOOP flow is the RHR flow to the B loop drywell spray, torus spray and torus cooling.

Each RHR pump is approximately rated at 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.

Northern States Power Company Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDig ital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS LPCI FLOW RHRl02 RHR LOOP A INJECT FLOW LOW PRESSURE COOLANT INJECTION FLOW A

GPM NIA 0

10000 NIA N/A s

1 SIGNAL INPUT FROM FLOW TRANSMITTER DISCHARGE OF RHR HEAT EXCHANGERS NIA NIA HIGH & LOW SENSOR NIA N/A NIA RHR LOOP A INJECT FLOW is the RHR flow to the A Recirc Loop, Reactor Head Cooling, Waste Surge Tank, and cross tie to B Loop. Each RHR pump is rated at about 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.

Northern States Power Company Monticello Nuclear ene era tin^ Plant Software Requirement Specification

Title:

Number:

I SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet NO:

18 DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmlTrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

01 107192 M01 PCS LPCl FLOW RHRl03 RHR LOOP B INJECT FLOW LOW PRESSURE COOLANT INJECTION FLOW A

GPM NIA 0

10000 NIA NIA S

1 SIGNAL INPUT FROM FLOW TRANSMITTER DISCHARGE OF RHR HEAT EXCHANGERS NIA NIA HIGH & LOW SENSOR NIA NIA NIA RHR LOOP B INJECT FLOW is the RHR flow to the B Recirc Loop and cross tie to A Loop. Each RHR pump is rated at about 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.

Northern States Power Company Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1 107192 M01 PCS CR SPRAY FL CSPl 00 CS LOOP 11 FLOW Core Spray Cooling System Flow A

GPM NIA 0

5000 NIA NIA S

1 SIGNAL INPUT FROM FLOW TRANSMITTER ON PUMP DISCHARGE LINE NIA HIGH & LOW SENSOR NIA NIA The loop A Core Spray system consists of one electric driven pump designed to deliver 3020 gpm against a system head corresponding to a reactor pressure of 130psi above containment pressure. The flow element is located on the pump discharge line just a head of the reactor vessel injection and test return lines.

Northern States Power Company SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

20 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS CR SPRAY FL CSPl 01 CS LOOP 12 FLOW CORE SPRAY COOLING SYSTEM FLOW A

GPM NIA 0

5000 NIA NIA S

1 SIGNAL INPUT FROM FLOW TRANSMITTER ON PUMP DISCHARGE LINE HIGH & LOW SENSOR NIA NIA The loop B Core Spray system consists of one electric driven pump designed to deliver 3020 gpm against a system head corresponding to a reactor pressure of 130psi above containment pressure. The flow element is located on the pump discharge line just a head of the reactor vessel injection and test return lines.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

21 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1107192 M01 PCS DW ED SMP LV PCTI 38 DW EQUIP DRAIN SUMP VOL DRYWELL FLOOR DRAIN SUMP LEVEL A

GAL NIA 164 565 NIA NIA S

1 SIGNAL INPUT FROM LEVEL TRANSMITTER DIRECTLY BELOW RX VESSEL IN DRYWELL Hl=555 NIA HIGH & LOW SENSOR NIA NIA This sump collects liquid effluent from valve stem leak-offs, Rx Recirc Pump and piping maintenance drains, reactor well bulkhead and bellows drains, reactor vessel flange leakoff and Drywell Equipment Drain Sump heat exchanger drain. Two 50 GPM pumps discharge the water to the Waste Collector Tank in the Reactor building. Sump is isolated by Group I1 Isolation or manually from control room. Sump overflows into Drywell Floor Drain Sump at 1090 Gallons.

Northern States Power Company SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library Sheet No:

22 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS DW FD SMP LV PCTI 39 DW FLOOR DRAIN SUMP VOL DRYWELL FLOOR DRAIN SUMP LEVEL A

GAL NIA 164 565 NIA NIA S

1 SIGNAL INPUT FROM LEVEL TRANSMITTER DIRECTLY BELOW RX VESSEL IN DRYWELL Hl=555 NIA HIGH & LOW SENSOR NIA NIA This sump collects liquid effluent from Drywell cooler drains, floor drains, control rod drive leakage and drains, closed cooling water piping drains, and piping and equipment maintenance vents. Two 50 GPM pumps discharge the water to the Floor Drain Collector Tank in the Reactor building.

Sump is isolated by Group II Isolation or manually from control room. Sump overflows into Drywell Equipment Drain Sump at 1090 Gallons.

Northern States Power Company SRS Process Computer System - Emergency Response Data System (ERDS) - Data Point Library 10 Sheet No:

23 DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

311 511 2 I

M01 PCS EFF GAS RAD PRM500FR STACK EFF RAD A 15MRUN RADIOACTIVITY OF RELEASED GASES A

uCI/S N/A 1

10E12 NIA NIA P I I

15 MINUTE AVERAGE OF 5 SECOND VALUES FOUR ISOKINETIC PROBES IN OFF GAS STACK I

NIA NIA I

HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library I

Sheet No:

24 I

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 M01 I

PCS EFF GAS RAD PRM501 FR STACK EFF RAD B 15MRUN RADIOACTIVITY OF RELEASED GASES A

uCIIS NIA 1

10E12 NIA NIA P

1 I

15 MINUTE AVERAGE OF 5 SECOND VALUES FOUR ISOKINETIC PROBES IN OFF GAS STACK I

NIA NIA I

HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

25 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 M01 I

PCS EFF GAS BAD PRMI 23FR RBV EFFLUENT MONITOR CHA 15MAVG RADIOACTIVITY OF RELEASED GASES A

uCI/S NIA I

10E12 NIA NIA P

1 15 MINUTE AVERAGE OF 5 SECOND VALUES ISOKINETIC PROBES IN EACH RX BLDG VENT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Com~anv SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library Sheet No:

26 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 M01 I

PCS EFF GAS RAD PRMI 24FR RBV EFFLUENT MONITOR CHB 15MAVG RADIOACTIVITY OF RELEASED GASES A

uCIIS NIA 1

10E12 NIA NIA P

1 I

15 MINUTE AVERAGE OF 5 SECOND VALUES ISOKlNETlC PROBES IN EACH RX BLDG VENT I

NIA NIA I

HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I -

System (ERDS) - Data Point Library 10 Sheet No:

27 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS EFF LIQ RAD PRMI 07 SERVICE WATER EFFLUENT RADIOACTIVITY OF RELEASED LIQUIDS A

CPS uCi/MI=((PRMI 07 in CPS)-5)*(4.3E-7)

. I I OE6 N/A NIA S

1 SIGNAL INPUT FROM MONITOR SAMPLES SW PRIOR TO SW LEAVING RX BLDG HI=20; HI-HI=31400 NIA DOWNSCALE & UPSCALE NIA NIA Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detector housed in shielded sampler. Sidestream sample is used from the service water line prior to leaving the Reactor Building. After leaving Reactor Building, line discharges into circ water discharge pipe. Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

28 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1107192 M01 PCS EFF LIQ RAD PRMI 09 RADWASTE EFFLUENT RADIOACTIVITY OF RELEASED LIQUIDS A

CPS uCi/MI=((PRMI 09 in CPS)-7)*(2.5E-6)

. I 10E6 NIA N/A S

1 SIGNAL INPUT FROM MONITOR SAMPLED PRIOR TO LEAVING RADWASTE BLDG HI=70; HI-Hl=10000000 NIA DOWNSCALE & UPSCALE, INOP NIA NIA Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detector housed in shielded sampler. Liquid is sampled prior to leaving the Radwaste Building. After leaving Radwaste Building, line discharges into discharge canal. Although Monticello has permits, Monticello maintains a policy of zero liquid radwaste releases into the river. Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company Sheet No:

29 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

,NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1 107192 M01 PCS EFF LIQ RAD PRMl 10 TB NORMAL WASTE SUMP CH A RADIOACTIVITY OF RELEASED LIQUIDS A

CPM uCi/MI=((PRMI 10 in CPM)-400)*(3.5E-9) 10 10E6 NIA NIA S

1 SIGNAL INPUT FROM MONITOR SAMPLED PRIOR TO LEAVING TURBINE BLDG HI=4000; HI-HI=3780000 NIA DOWNSCALE & UPSCALE, INOP NIA NIA Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors in dry tube in sump. Sampled prior to leaving the Turbine Building.

Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

30 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS EFF LIQ RAD PRMI 11 TB NORMAL WASTE SUMP CH B RADIOACTIVITY OF RELEASED LIQUIDS A

CPM uCi/MI=((PRMI 11 in CPM)-400)*(3.5E-9) 10 I

OE6 N/A N/A S

1 SIGNAL INPUT FROM MONITOR SAMPLED PRIOR TO LEAVING TURBINE BLDG HI=4000; HI-HI=3780000 NIA DOWNSCALE & UPSCALE, INOP N/A N/A Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors in dry tube in sump. Sampled prior to leaving the Turbine Building.

Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library Sheet No:

31 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01 107192 M01 PCS EFF LlQ RAD PRMI 12 DISCHARGE CANAL MONITOR A RADIOACTIVITY OF RELEASED LIQUIDS A

CPS uCi/MI=((PRMI 12 in CPS)-2)*(1.4E-7)

.I 10E6 NIA NIA S

1 SIGNAL INPUT FROM MONITOR 550FT DOWNSTREAM FROM DISCHARGE STRUCTURE HI=40; HI-HI=93000 NIA DOWNSCALE & UPSCALE, INOP NIA NIA Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors. Sample is drawn from 4 standpipes in canal 550 feet downstream from the discharge structure. Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

32 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS EFF LIQ RAD PRMI 13 DISCHARGE CANAL MONITOR B RADIOACTIVITY OF RELEASED LIQUIDS A

CPS uCi/MI=((PRMI 13 in CPS)-2)*(1.4E-7)

. I 10E6 NIA NIA S

1 SIGNAL INPUT FROM MONITOR 550FT DOWNSTREAM FROM DISCHARGE STRUCTURE HI=40; HI-HI=93000 NIA DOWNSCALE & UPSCALE, INOP NIA NIA Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors. Sample is drawn from 4 standpipes in canal 550 feet downstream from the discharge structure. Alarm setpoints vary with plant operation as determined by plant,chemist.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

33 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr u n i k l ~ i g States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS CND A/E RAD PRMI 18 OFF GAS CH 1

\\

CONDENSER AIR EJECTOR RADIOACTIVITY A

M RIH R NIA 1

10E6 NIA NIA S

1 SIGNAL OUTPUT FROM MONITOR SAMPLE DRAWN FROM OFF GAS LINE HI=2500; HI-HI=200000 NIA LOW NIA NIA OFF GAS CH 1 radiation monitor is positioned adjacent to a vertical sample chamber. A continuous sample is drawn from the off gas line downstream from the Steam Jet Air Ejectors and ahead of the Recombiner trains. The sample is monitored after a time delay of approximately 2 minutes to permit Nitrogen-16 and Oxygen-1 9 to decay. Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

34 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmPTrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1 107192 M01 PCS CND N E RAD PRM119 OFF GAS CH 2 CONDENSER AIR EJECTOR RADIOACTIVITY A

MRIHR NIA I

10E6 NIA NIA S

1 SIGNAL OUTPUT FROM MONITOR SAMPLE DOWNSTREAM OF STEAM JET AIR EJECT H1=2500; HI-Hl=200000 NIA LOW NIA NIA OFF GAS CH 2 radiation monitor is positioned adjacent to a vertical sample chamber. A continuous sample is drawn from the off gas line downstream from the Steam Jet Air Ejectors and ahead of the Recombiner trains. The sample is monitored after a time delay of approximately 2 minutes to permit Nitrogen-16 and Oxygen-1 9 to decay. Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company cess Computer System - Emergency Response Data System (ERDS) - Data Point Library 10 Sheet No:

35 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

Analog/Digital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS DW RAD PCTI 09 DRYWELL RADIATION CH A RADIATION LEVEL IN THE DRYWELL A

RIH R N/A I

10E8 NIA N/A S

1 SIGNAL INPUT FROM RADIATION MONITOR DRYWELL 180 DEGREE AZIMUTH AT 944' Hl=49.999, HI-Hl=35 N/A HIGH SENSOR, INOP N/A N/A Purpose is to provide estimate of core damage by measuring drywell gamma radiation fields caused by fission product leakage from the core. Each sensor is an ionization chamber with an internal U-234 source which gives IRIHR reading for operation verification. Elevation 944' is just below bottom of reactor vessel (949').

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

36 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Sply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1 107192 M01 PCS DW RAD PCTl 10 DRYWELL RADIATION CH B RADIATION LEVEL IN THE DRYWELL A

RIH R N/A 1

10E8 NIA N/A S

1 SIGNAL INPUT FROM RADIATION MONITOR DRYWELL 0 DEGREE AZIMUTH AT 944' Hl=49.999, HI-HI=35 NIA HIGH SENSOR, INOP NIA NIA Purpose is to provide estimate of core damage by measuring drywell gamma radiation fields caused by fission product leakage from the core. Each sensor is an ionization chamber with an internal U-234 source which gives 1 RIHR reading for operation verification. Elevation 944' is just below bottom of reactor vessel (949').

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification I

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I -

System (ERDS) - Data Point Library 10 Sheet No:

37 DATA POINT LIBRARY REFERENCE FILE Date:

01 I07192 Reactor Unit:

M01 Data Feeder:

PCS NRC ERDS Parameter:

MN STEAM RAD Point ID:

Plant Spec Point Desc.:

(not available)

GenericICond Desc.:

RADIATION LEVEL OF THE MAIN STEAM LINE AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

Not available to Process Computer System.

Northern States Power Company SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library Sheet No:

38 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01 I07192 M01 PCS DW PRESS D23C0010 VALIDATED DRYWELL PRESSURE DRYWELL PRESSURE A

PSlG NIA

-5 250 NIA NIA P

4 WEIGHTED AVERAGE OF CONSISTENT DW PRESS SENSING LINES FROM DRYWELL ALARMS LOW=O.I, HIGH=I.5 NIA HIGH & LOW SENSOR NIA NIA This point consists of either a weighted average of all consistent drywell pressure or an average of in-range drywell pressures if there are less than the required number of consistent singals. Four drywell pressure signals consist of one narrow range (-2 to 3), one wide range (0 to 80) and two accident (-5 to 250) ranges. Weighted averages produces average that is weighted based on instrument accuracy.

Drywell internal design pressure is 56 PSlG at 281 Degrees F.

At 2 PSIG, RPS initiates Reactor SCRAM and Primary Containment Isolation initiates Group 2 & 3.

Northern States Power Company Sheet No:

39 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS DW TEMP D23C0310 VALIDATED DRYWELL TEMPERATURE DRYWELL TEMPERATURE A

DEGF NIA 0

600 NIA NIA P

16 AVERAGE OF CONSISTENT DW TEMPERAURES 16 SENSORS AT 8 DRYWELL LOCATIONS HI=150 DEGF NIA HIGH & LOW SENSOR NIA NIA This point consists of either a weighted average bulk temperature of consistent regional temperatures or an unvalidated, non-weighted average of all in-range drywell temperatures. Regional weighting factors compensate for differences in drywell volume at the various elevations. Each location utilizes two sensors and are located in Drywell at: Elev 932' (East & West), Elev 9511(North & South), Elev 970' (East

& West), and Elev 994' (North & South).

Northern States Power Company SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library Sheet No:

40 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1107192 M01 PCS SP TEMP D23C0210 VALIDATED TORUS TEMPERATURE SUPPRESSION POOL TEMPERATURE A

DEGF NIA 30 240 NIA NIA P

16 AVERAGE OF 2 SPOTMOS (8 SENSORS EACH) 2 SENSORS IN EACH OF 8 TORUS SRV BAYS HIGH=90 NIA HIGH & LOW SENSOR, SPOTMOS INOP NIA NIA VALIDATED TORUS TEMPERATURE is the average of the inputs from two Suppression Pool Temperature Monitoring Systems (SPOTMOS). Each system generates an average of eight sensors. Each sensor is located in one of the eight bays that Safety Relief Valves discharge into.

Northern States Power Company SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS SP LEVEL G43C0015 VALIDATED TORUS WATER LEVEL SUPPRESSION POOL WATER LEVEL A

INCHES NIA

-96 180 NIA OU=ELEVATION 9101= 530,000 GALLONS P

4 WEIGHTED AVERAGE OF CONSISTENT LEVELS LEVEL TAPS OFF TORUS SHELL HIGH=2, LO=-2 NIA HIGH & LOW SENSOR NIA NIA This point consists of either a weighted average of all consistent torus water levels or an average of in-range torus water levels if there are less than the required number of consistent signals. Four torus water level signals consist of two narrow range (-1 5 to 15) and two wide range (-96 to 180).

Weighted averages produce an average that is based on instrument accuracy. HPCl suction transfer occurs at 2". Tech Specs level greater than -4" and less than 2.9".

Northern States Power Company Monticello Nuclear Generating Plant Soflware Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library I 0 Sheet No:

42 DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

0 1/07/92 M01 PCS H2 CONC PCT1 16 PCTMT H2 ANALYZER A DRYWELL OR TORUS HYDROGEN CONCENTRATION A

NIA 0

20 NIA NIA S

1 SIGNAL OUTPUT FROM H2 ANALYZER SAMPLE LINES UPPER DW,TORUS,CGCS IN & OUT NIA N/A HIGH & LOW SENSOR, SYSTEM OFF NIA NIA Analyzers are normally shutdown and values will usually read less than 0.75%. System is capable of analyzing samples from Drywell (elev 994'), Torus and Combustible Gas Control System inlet and outlet. Sample line and sample return valves close on Group 2 Isolation.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

43 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1/07/92 M01 PCS H2 CONC PCTI 17 PCTMT H2 ANALYZER B DRYWELL OR TORUS HYDROGEN CONCENTRATION A

Yo NIA 0

20 N/A NIA S

1 SIGNAL OUTPUT FROM H2 ANALYZER SAMPLE LINES UPPER DW,TORUS,CGCS IN & OUT NIA NIA HIGH & LOW SENSOR, SYSTEM OFF N/A NIA Analyzers are normally shutdown and values will usually read less than 0.75%. System is capable of analyzing samples from Drywell (elev 9947, Torus and Combustible Gas Control System inlet and outlet. Sample line and sample return valves close on Group 2 Isolation.

Northern States Power Com~anv Monticello Nuclear ~enerating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

44 DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

0 I 107192 M01 PCS 0 2 CONC PCTI 18 PCTMT 0 2 ANALYZER A DRYWELL OR TORUS OXYGEN CONCENTRATION A

NIA 0

2 5 NIA NIA S

1 SIGNAL OUTPUT FROM 0 2 ANALYZER SAMPLE LINES UPPER DW,TORUS,CGCS IN & OUT NIA NIA HIGH & LOW SENSOR, SYSTEM OFF NIA NIA Analyzers are normally shutdown and values will usually read less than 0.75%. System is capable of analyzing samples from Drywell (elev 9947, Torus and Combustible Gas Control System inlet and outlet. Sample line and sample return valves close on Group 2 Isolation. Normal operation concentrations are 2.4%.

Northern States Power Comoanv cess Computer System - Emergency Response Data System (ERDS) - Data Point Library Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01 107192 M01 PCS 0 2 CONC PCTI 19 PCTMT 0 2 ANALYZER B DRYWELL OR TORUS OXYGEN CONCENTRATION A

NIA 0

2 5 NIA NIA S

1 SIGNAL OUTPUT FROM 0 2 ANALYZER SAMPLE LINES UPPER DW,TORUS,CGCS IN & OUT NIA NIA NIA HIGH & LOW SENSOR, SYSTEM OFF NIA NIA Analyzers are normally shutdown and values will usually read less than 0.75%. System is capable of analyzing samples from Drywell (elev 994'), Torus and Combustible Gas Control System inlet and outlet. Sample line and sample return valves close on Group 2 Isolation. Normal operation concentrations are 2.4%.

Northern States Power Company ocess Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library Sheet No:

46 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 0 1107192 M01 PCS CST LEVEL CSTl 00 CST TANK LEVEL A CONDENSATE STORAGE TANK LEVEL A

FEET NIA 5

30 NIA N/A S

1 SIGNAL FROM LEVEL TRANSMITTER LEVEL TX ON WATER COLUMN IN RX BLDG HI=24'(225,600gal) LO=11.5'(108,100gal)

NIA LOW NIA NIA Condensate Storage Tank (CST) Level A is the water level in the A CST. Two CSTs exist with a tank capacity of 230,000 gallons each. Makeup condensate water is provided through 3 electric pumps from the CST tanks to various plant systems.

Each tank has suction line for Control Rod Drive, HPCI, Core Spray, RHR, and RClC systems. At 7'(65,80Ogal) receive CST Low-Low Level alarm and condensate service pumps trip. At 2'811(25, 100gal) HPCI and RClC transfer to Torus suction.

Northern States Power Company System (ERDS) - Data Point Library Sheet No:

47 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01 107192 M01 PCS CST LEVEL CSTl 01 CST TANK LEVEL B CONDENSATE STORAGE TANK LEVEL A

FEET NIA 5

30 NIA NIA S

1 SIGNAL FROM LEVEL TRANSMITTER LEVEL TX ON WATER COLUMN IN RX BLDG HI=24'(225,600gal) LO=11.5'(108,100gal)

NIA LOW NIA NIA Condensate Storage Tank (CST) Level B is the water level in the B CST. Two CSTs exist with a tank capacity of 230,000 gallons each. Makeup condensate water is provided through 3 electric pumps from the CST tanks to various plant systems.

Each tank has suction line for Control Rod Drive, HPCI, Core Spray, RHR, and RClC systems. At 7'(65,80Ogal) receive CST Low-Low Level alarm and condensate service pumps trip. At 2'8J'(25,100gal) HPCI and RClC transfer to Torus suction.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

48 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 M01 I

PCS WlND SPEED MET1 22FR MT 43M A WlND SPEED 15MRUN WlND SPEED AT THE REACTOR SITE A

MPH NIA 0

100.00 NIA NIA P

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 43 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA N/A Data is collected every five seconds, averaged every minute, I

and stored in data files as 15-minute average.

Northern States Power Company cess Computer System - Emergency Response Data System (ERDS) - Data Point Library 10 Sheet No:

49 DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

311 511 2 M01 I

PCS WlND SPEED MET1 23FR MT 43M B WlND SPEED 15MRUN WlND SPEED AT THE REACTOR SITE A

MPH NIA 0

100.00 NIA NIA P

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 43 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, I

and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

50 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 M01 I

PCS WlND SPEED MET1 20FR MT 100M A WlND SPEED 15MRUN WlND SPEED AT THE REACTOR SITE A

MPH NIA 0

100.00 NIA NIA P

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 100 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, I

and stored in data files as 15-minute average.

Northern States Power Company Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg: NIA Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 M01 I

PCS WlND SPEED MET1 21 FR MT 100M B WlND SPEED 15MRUN WlND SPEED AT THE REACTOR SITE A

MPH NIA 0

100.00 NIA NIA P

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 100 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA Data is collected every five seconds, averaged every minute, I

and stored in data files as 15-minute average.

Northern States Power Com~anv Sheet No:

52 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 M01 I

PCS WlND DIR MET1 28FR MT 43M A WIND DIR 15MRUN I

WlND DIRECTION AT THE REACTOR SITE A

DEGFR NIA 0

540.00 NIA NIA P

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 43 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, I

and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification I

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

53 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 M01 I

PCS WlND DIR MET1 29FR MT 43M B WlND DIR 15MRUN WlND DIRECTION AT THE REACTOR SITE A

DEGFR NIA 0

540.00 NIA NIA P

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 43 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, I

and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification I

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

54 DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

311 511 2 M01 I

PCS WlND DIR MET1 26FR MT IOOM A WlND DIR 15MRUN WlND DIRECTION AT THE REACTOR SITE A

DEGFR NIA 0

540.00 NIA NIA P

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT I00 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, I

and stored in data files as 15-minute average.

ERDS-SRS Sheet No:

55 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 I

M01 PCS WlND DIR MET1 27FR MT 100M B WlND DIR 15MRUN WlND DIRECTION AT THE REACTOR SITE A

DEGFR NIA 0

540.00 NIA NIA P

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 100 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, I

and stored in data files as 15-minute average.

Northern States Power Company cess Computer System - Emergency Response Data System (ERDS) - Data Point Library 10 Sheet No:

56 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

PointlD:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 M01 I

PCS STAB CLASS METl40FR MT 43M-1 OM A DELTA AIR T 15MRUN AIR STABILITY AT THE REACTOR SITE A

DEGF NIA

-9.0 9.0 NIA NIA PROC 2

AVERAGED DIFFERENTIAL PRIMARY MET AT 10 & 43 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, 1

and stored in data files as 15-minute average. This value represents the difference in temperature in degF1100ft.

Northern States Power Comoanv Monticello Nuclear ene era ti;^ plant Software Requirement Specification

Title:

Number:

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

57 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

PointlD:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 311 511 2 1

1 M01 PCS STAB CLASS MET1 41 FR MT 43M-1 OM B DELTA AIR T 1 SMRUN AIR STABILITY AT THE REACTOR SITE A

DEGF NIA

-9.0 9.0 NIA NIA PROC 2

AVERAGED DIFFERENTIAL PRIMARY MET AT 10 & 43 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, I

and stored in data files as 15-minute average. This value represents the difference in temperature in degF1100ft.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification

Title:

Number:

SRS PFOcess Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

58 DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

PointlD:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

311 511 2 1

S AB CLASS MET1 38FR MT 100M-1 OM A DELTA AIR T 15MRUN AIR STABILITY AT THE REACTOR SITE A

DEGF NIA

-9.0 9.0 NIA NIA PROC 2

AVERAGED DIFFERENTIAL PRIMARY MET AT 10 & I00 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, I

and stored in data files as 15-minute average. This value represents the difference in temperature in degF1100ft.

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Specification I

Title:

Number:

1.

SRS Process Computer System - Emergency Response Data ERDS-SRS-I-System (ERDS) - Data Point Library 10 Sheet No:

59 DATA POINT LIBRARY REFERENCE FILE Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

PointlD:

Plant Spec Point Desc.:

GenericICond Desc.:

AnalogIDigital:

Engr UnitsIDig States:

Engr Units Conversion:

Minimum lnstr Range:

Maximum lnstr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

AlarmITrip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

311 511 2 M01 PCS STAB CLASS MET1 39FR MT 100M-1 OM B DELTA AIR T 15MRUN AIR STABILITY AT THE REACTOR SITE A

DEGF NIA

-9.0 9.0 NIA NIA PROC 2

AVERAGED DIFFERENTIAL PRIMARY MET AT 10 & 100 METER HEIGHT NIA NIA HIGH & LOW SENSOR NIA NIA Data is collected every five seconds, averaged every minute, I

and stored in data files as I 5-minute average. This value represents the difference in temperature in degF1100ft.

Northern States Power Company SRS Process Computer System - Emergency Response Data ERDS-SRS System (ERDS) - Data Point Library Sheet No:

60 I.

Contacts Note: Please provide name, title, mailing address and phone number A.

Survey Coordinator (i.e. contact for later clarification of questionnaire answers):

Russell E. Van Dell Manager, Computer & Information Systems Xcel Energy, Inc.

Monticello Nuclear Generating Plant 2807 West County Road 75 Monticello, MN 55362 (763) 295-1 326 B.

Computer Hardware Specialist(s):

Nai-Tai (Nelson) Fei Senior Engineer Xcel Energy, Inc.

Monticello Nuclear Generating Plant 2807 West County Road 75 Monticello, MN 55362 (763) 271 -51 80 C.

Systems Software Specialist(s):

Bob Awde Principal Engineer Xcel Energy, Inc.

Monticello Nuclear Generating Plant 2807 West County Road 75 Monticello, MN 55362 (763) 271 -51 03 D.

Application-level Software Specialist(s):

Nai-Tai (Nelson) Fei Senior Engineer Xcel Energy, Inc.

Monticello Nuclear Generating Plant 2807 West County Road 75 Monticello, MN 55362 (763) 271 -51 80

Northern States Power Company SRS Process Computer System - Emergency Response Data System (ERDS) - Data Point Library E.

Telephone Systems Specialist(s):

David Seestrom Instrument Engineer Xcel Energy, Inc.

Monticello Nuclear Generating Plant 2807 West County Road 75 Monticello, MN 55362 (763) 295-1 376

Northern States Power Company rocess Computer System - Emergency Response Data System (ERDS) - Data Point Library Sheet No:

62 II. Selection of Data Feeders A.

How many data feeders are there (six maximum)?

One - Process Computer System B.

Identify the selected data feeders and provide the following for each:

1.

a short description of the categories of data points it will provide (e.g., met. rad.

or plant data points, by unit) and 1.2.

the rationale for selecting it if another system can also provide its categories of I

data points.

a)

It is planned to provide both plant data points and meteorological information through the single feeder.

a)b)

No other system is capable of providing requested information.

C.

Which data feeder is the site time determining feeder? This should be the feeder which is providing the majority of the data points.

Northern States Power Company cess Computer System - Emergency Response Data System (ERDS) - Data Point Library Sheet No:

63 Ill. Data Feeder lnformation Note: A new Section IV must be filled out for each feeder system selected.

General Questions A.

Identification of Data Feeder

1.

What is the name in local parlance given to this data feeder (e.g., Emergency Response lnformation System)? Please give both the acronym and the words forming it.

PCS - Process Computer System

2.

Is this the site time determining feeder?

Yes

3.

How often will this feeder transmit an update set to the ERDS (in seconds)?

60 Seconds B.

Hardwarelsoftware Environment 1,

ldentify the manufacturer and model number of the data feeder hardware.

Digital Equipment Corporation VAX-4000-108

2.

ldentify the operating system.

VAX OpenVMS V7.1

3.

What method of timekeeping is implemented on this feeder system (Daylight Savings, Standard, Greenwich)?

Daylight Savings

4.

In what time zone is this feeder located?

Central Standard Time Zone

Northern States Power Company cess Computer System - Emergency Response Data System (ERDS) - Data Point Library Sheet No:

64 C.

Data Communication Details

1.

Can this data feeder provide asynchronous serial data communication (RS-232-C) with full-modem control?

Yes

2.

Will this feeder transmit in ASCll or EBCDIC?

3.

Can this feeder transmit at a serial baud rate of 2400 bps? If not, at what baud rate can it transmit?

Yes, 2400 bps can be used.

4.

Does the operating system support XONIXOFF flow control?

Yes a)

Are any problems foreseen with the NRC using XONIXOFF to control the transmission of data?

No, however the use of SUSPEND and RESUME to control the transmission of data works better as demonstrated in testing with HaIiburtonINUS.

5.

If it is not feasible to recontigure a serial port for the ERDS linkup (i.e., change the baud rate, parity, etc.), please explain why.

Note Applicable.

6.

Do any ports currently exist for the ERDS linkup?

Yes a)

If not, is it possible to add additional ports?

Not Applicable.

Northern States Power Company SRS Process Computer System - Emergency Response Data ERDS-SRS-I -

System (ERDS) - Data Point Library 10 Sheet No:

65 b)

If yes, will the port be used solely by the ERDS or shared with other non-emergency-time users? Give details.

Port will be dedicated for ERDS.

D.

Data Feeder Physical Environment and Management I

Where is the data feeder located in terms of the TSC, EOF, and control room?

Computer Room located in Plant Administrative Building adjacent to Plant Control Room.

2.

Is the data feeder protected from loss of supply of electricity?

Yes, PCS is provided with UPS (batteries with inverter and diesel generator).

3.

Is there a human operator for this data feeder?

Yes a)

If so, how many hours a day is the feeder attended?

It is planned to have the Shift Emergency Communicator (SEC) initiate the ERDS System per Emergency Implementing Procedures. An SEC is on duty 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />slday.