L-2021-182, Summary of Commitment Revisions, Emergency Diesel Generator Fuel Oil Storage Tank Cleaning Inspection Commitment Revisions

From kanterella
(Redirected from L-2021-182)
Jump to navigation Jump to search
Summary of Commitment Revisions, Emergency Diesel Generator Fuel Oil Storage Tank Cleaning Inspection Commitment Revisions
ML21259A259
Person / Time
Site: Turkey Point 
Issue date: 09/16/2021
From: Hess R
Florida Power & Light Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-2021-182
Download: ML21259A259 (5)


Text

September 16,2021 L-2021-182 U.S.Nuclear Regulatory Commission Attn.Document Control Desk Washington, D.C.20555 Re:

Turkey Point Unit3 Docket Nos.50-250 m

References:

1. L-98-012, FPLletter dated Feb02,1998, "Revised Proposed License Amendments and Request forAdditional Information (RAI)

Diesel Fuel Storage Systems."

2. NRCletter dated June9,1998,"Turkey Point Units3and 4-Issuance ofAmendments Regarding Diesel Fuel OilStorage andTransfer System(TACNos. M97376andM97377)

Thepurpose ofthis letter istoprovide asummaryofcommitment revisions associatedwiththe Turkey Point Unit3Emergency Diesel Fuel OilFuel Storage andTransfer System.

The commitments wereevaluated andrevised using theguidance provided in NEl99-04,Guidelines forManaging NRCCommitment Changes.

Enclosure 1provides theoriginal commitments.

Enclosure 2provides therevised commitments.

Enclosure 3provides thecorresponding justification forrevising these commitments.

Should youhaveanyquestions regarding this submittal, please contact Mr.RobertJ. Hess, Turkey Point Licensing

Manager, at305-246-4112.

Sincerely, v

RobertHess Licensing Manager Turkey Point Nuclear Plant Enclosures cc:

USNRCRegional Administrator, Region II USNRCProject

Manager, Turkey PointNuclear Plant USNRCSenior Resident Inspector, Turkey Point Nuclear Plant

~~ Florida Power-

& Light Company 9760S.W.344th Street Homestead, FL33035

Enclosure 1toL-2021-188 Turkey Point Units 3Emergency Diesel Generator FuelOilStorage TankCleaning Inspection andPMCommitment Updates Original Commitments 1."The proposed threetemporarystationary tanks will bemobile trailer rectangular style tanks (43ft long, 11fthigh, 8ftwide) having acapacity ofapproximately 19,000gallons each.

These tanks willbeWORKSAFE"d, orequivalent, Bi-Level steel

tanks, withcross style internal bracingwith anapproximate emptyweight of21,000Ibs."

[Ref 1,Attachment 1,

Page8of9)

2. "These trailer/tanks areprovided with tie-down capability andwill besecured by temporary measures towithstand winds ofatleast 120mph."[Ref1,Attachment 1,Page8 of9) 3."Thetemporary storage tanks will belocated insidetheprotected areainthevicinity ofthe Nuclear Plant Central Receiving Facility.

The temporary tanks will belocated greater than fifty (50) feet fromsafety related orsafe shutdown components orcircuits.

This doesnot produce anythreat tofire protection orsafe shutdown capability andtherefore represents aconfiguration that isbounded byexisting fire hazards analysis." [Ref 1,Attachment 2,Page 3of4.)

4. "Adedicated mobile tanker staged inside theprotected area to transfer fuel fromthe temporary storage tanks tothepermanentday/skid tank system.

The mobiletanker will haveanintegral transfer pumptofacilitate movementoffuel toeither ofthetwotruck fills attheUnit4EDGbuilding ordaytanktruck fills (auxiliary fill station)at the Unit3EDGs."

[Ref 1,Attachment 1,Page8of9) 5."Intheeventofahurricane, themobile tanker along withhoses portable

pumps, filters, etc.,

wouldbegaraged inside theonsite Central Facility which isdesigned towithstand winds ofatleast 120mph."[Ref 1,Attachment 1,Page9of9) 6 "Manual actions required toprovide a7-day supply offuel totheEDGscaneasily be accomplished inthe17hours ofEDGoperation provided bythe3880-gallon capacity ofa single EDGdayandskid tank."

[Ref 1,Attachment 2,Page2of4)

7. "Combing theexcess available fromtheUnit4storage tanks andthenominal volumeofthe Unit3dayandskid tanks giveatotal of12,480gallons (4300 x2+3880) ofavailable fuel to either oftheUnit3EDGs."

[Ref1,Attachment 2,Page2of4)

Enclosure 2toL-2021-188 Turkey Point Units 3Emergency Diesel Generator FuelOilStorage TankCleaning Inspection andPMCommitment Updates Revised Commitments 1."Theproposed three temporary stationary tanks will be45ft.

long, 11ft.
high, 8.5ft.

wide; havingacapacity ofapproximately 21,000gallons each.

These tanks areAdler FRACTanks aremadeof steel andwith anapproximate emptyweight of29,500lbs.

each."

2. "Engineering Evaluation (EC 294570)determined thatthetemporary tanks arecapable of withstanding windsof 120 mphwithout being secured bytie-down temporarymeasures."

3."Thetemporary storage tanks will belocated, attheTurkey Point Fossil

side, atan extension oftheTurkey PointNuclear site protected
area, justbeyond theNuclear/Fossi boundary fence.

Thetemporarytanks willberelocated inanareagreater thanfifty (50) feet fromsafety related orsafe shutdown components orcircuits.

This newlocation doesnot produce anythreat tofire protection or safe shutdown capability andtherefore represents aconfiguration that isbounded byexisting fire hazards analysis."

4. "Apumpingtruck will beprovided inside theprotected areatotransfer fuel fromthe temporary storage tanks tothepermanent day/skid tank systems.

This truck will havehoses ofsufficient length topumpfuel between theUnit3Diesel OilStorageTanks andthe temporary storage tanks aswell astotransfer fuel fromthe temporary tanks totheUnit3 EDGDayTankAlternate fill Station located atthenorth sideof the unit3EDGBuilding.

Thepumping truck will also facilitate movementoffuel toeither of thetwofills attheUnit 4EDGbuilding."

5."Intheeventofahurricane, thepumping truck along withhoses etc.,

would begaraged inside theonsite FLEXbuilding which isdesigned towithstand winds ofatleast 120 mph."

6. "Manual actions required toprovide a7-day supply offuel totheEDGscaneasilybe accomplished inthe17hours ofEDGoperation provided bythenormal operating band of 3790gallons combined capacity ofasingle EDGdayandskid tank."
7. "Combing theexcess available fromtheUnit4storage tanks andthenominal volume ofthe Unit3dayandskid tanks giveatotal of12,390 gallons (4300 x2+3790) ofavailable fuel to either oftheUnit3EDGs."

Enclosure 3toL-2021-188 Turkey Point Units 3Emergency Diesel Generator FuelOilStorage TankCleaning inspection andPMCommitment Updates Justification forRevising Commitments Page1of2 1.Therevised commitment documents theupdated style oftanks tobeusedforstorage of theDieseloil fuel. Theoriginal commitment documents thedimensions,

thestyle, the capacity andthe weight ofthetanks.

These tanks wheninplace, wouldeachhavea footprint ofapproximately 43ft.by8.5ft.,

capacity of21,000gallons andanemptyweight of29,500Ibs.

Basedon the dimensions,

style, capacity andweight, theAdler FRACstyle steel Tanks arefound to be equivalent tothepreviously approved temporary stationary style WORKSAFE" steel tanks.

2.TheAdler FRACtanks haveanempty weight of29,500lbs.

Thetanks areconstructed with only arearsetofwheels requiringto be hitched toatruck inorder tobemoved.

EC294570 determined that

thetanks, evenempty, are capable ofwithstandingwinds upto120mph.

Furthermore, ffeachtankisfilled toapproximately halfwaywithonly 10,000galoffuel, the weight isincreased by68,000lbs.

foratotalweight of97,500lbs.

pertank.

Thus, there is reasonable assurance thatthetanks will notbemoved evenintheeventofinclement weather evenwithout temporary tie-down measures.

3.Therevised commitment relocates thetemporary tanksin the vicinity oftheneighboring FPLTurkey Point Fossil Units 1and2,inanareajust northof the Turkey Point Unit3 Emergency Diesel Generator building.

Fortheduration ofthe10-year surveillance, this area will haveatemporary fence erected around itandsecurity personnel will bestationedat this

location, andassuch, this location will beconsidered anextension of theTurkeyPoint Nuclear Plant Protected Area(PA).

Therelocation ofthetemporary tanks inthevicinityof theFossil plant isless thantheprevious location oftheCentral receiving

area, which wasat least 1,000ft.

away.However,relocation ofthetemporary tanks will still beat least 50ft.

awayfromanysafety-related orfire safe-shutdown components orcircuits.

Since the new location isoutside ofthenormal PA,andthusoutside ofanyexisting fire zonesfor the

plant, thenewlocation doesnotrepresent anythreat tofire protection orsafe shutdown capability andtherefore represents aconfiguration that isbounded byexisting fire hazards analysis.

4.Therevised commitment eliminates theneedtohaveamobile fuel transfer tanker dueto theproximity ofthetemporary tankers totheEDGs.Instead, afuel transfer systemshall be available that candirectly connectbetween thetemporary tankers andtheEDGfuel supply lines asnecessary.

Thevendor will provide apumping truck withhoses ofsufficient length topumpthefuel between theUnit3DOSTandthetemporary tankers aswell astotransfer fuel toeither ofthetwotruck fills attheUnit4EDGbuilding ordaytanktruck fills (auxiliary fill station) attheUnit3EDGs.

Enclosure 3toL-2021-188 Turkey Point Units 3Emergency Diesel Generator Fuel OilStorage TankCleaning Inspection andPMCommitment Updates Justification forRevising Commitments Page2of2 5.Therevised commitment identifiestheFLEXbuilding, astherobust structure forstoring the pumping truck inthe event ofahurricane, which isdesigned towithstand winds ofatleast 120mph.Bychanging the garage

location, there isnoadditional risk addedifthepumping truck isgaraged attheFLEX building which meetsSeismic Category Irequirements.

6.Therevised commitment ensures that manualactions required toprovide a7daysupply of fuel totheEDGscaneasily beaccomplished inthe17hours ofEDGoperation evenwith lower thanthetop-off levels oftheEDG Day andskid

tanks, butwithin thenormal operating bandofacombined capacity of3,790 gallons.

WithUnit3EDGrunning atrated capacity of 2500KWwiththelower levels (of combined capacity of3,790gallons),

theruntimeof17 hours continues tobemet.

7.Therevised commitment updates thecombined capacity oftheEDGDayandskid tanks to reflect thelowering ofthetop-off levels from3880to3790 gallons. Thechanged commitment hasnotnoimpact ontheruntimeof55hours for theUnit3EDG(assuming fuel oil transfer fromUnit4)prior toreaching theTechnicalSpecification minimumvolume forUnit4fuel ofstorage tanks.