L-03-043, February 2003 Monthly Operating Report for Beaver Valley Power Station, Units 1 & 2

From kanterella
(Redirected from L-03-043)
Jump to navigation Jump to search
February 2003 Monthly Operating Report for Beaver Valley Power Station, Units 1 & 2
ML030770726
Person / Time
Site: Beaver Valley
Issue date: 03/10/2003
From: Bezilla M
FirstEnergy Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-03-043
Download: ML030770726 (5)


Text

FENOC E .Nucl1ear F',rstEnZ Cpan ,oa Beaver Valley PowerStation P. 0. Box 4 Shippingport,PA 15077 L-03-043 March 10, 2003 Beaver Valley Power Station Unit 1 - Docket No. 50-334, License No. DPR-66 Unit 2 - Docket No. 50-412, License No. NPF-73

--- Monthly-Operating-Report U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

Monthly In accordance with NRC Generic Letter 97-02, "Revised Contents of the "Monthly Operating Operating Report", and Unit 1 and 2 Technical Specification 6.9.4, the Report" is submitted for Unit 1 and Unit 2 for the month of February, 2003.

Respectfully, Vice-President DTJ/cmg Enclosures cc: NRC Regional Office King of Prussia, PA

UNIT SHUTDOWNS DOCKET NO. 50-334 UNIT NAME BVPS Unit#1 DATE March 3, 2003 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: February 2003 No. Date Type Duration Reason Method of Cause / Corrective Actions (Y/M/D) F: Forced (Hours) (1) Shutting S: Scheduled Down (2) Comments 1 03/02/24 F 58.8 H 3 The Unit experienced an automatic reactor trip and safety injection due to low main steam pressure when the "C"Main Steam Isolation Valve failed closed. Carpenters erecting scaffolding for the upcoming refueling outage in the area of this valve

-pu"nctureada"u-pt6iIedisk-6nbrn-of tw actuator air operating cylinders that hold the valve in the open position. Puncture of the rupture disk vented the instrument air pressure resulting in closure of the valve.

The rupture disks were replaced in each of the two actuator air cylinders for this valve.

(1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B- Maintenance or Test 2 - Manual Trip I Scram C- Refueling 3 - Automatic Trip / Scram D- Regulatory Restriction 4 - Continuation E- Operator Training / License Examination 5 - Other (Explain)

F - Administrative G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

__The Unit.began the-report period operating -at a .nominal -value-of l00% output until-1 548 hour0.00634 days <br />0.152 hours <br />9.060847e-4 weeks <br />2.08514e-4 months <br />s-on 2/24/03, when the Unit experienced an automatic reactor trip and safety injection due to low main steam pressure when the "C" Main Steam Isolation Valve failed closed. Per the Emergency Plan, an Unusual Event was also declared at 1600 hours0.0185 days <br />0.444 hours <br />0.00265 weeks <br />6.088e-4 months <br /> on 2/24/03. With the plant stable in Mode 3, the Unusual Event was terminated at 1735 hours0.0201 days <br />0.482 hours <br />0.00287 weeks <br />6.601675e-4 months <br /> on 2/24/03. Following evaluation of the trip and repair of the valve, Mode 2 was entered at 2001 hours0.0232 days <br />0.556 hours <br />0.00331 weeks <br />7.613805e-4 months <br /> on 2/26/03. The reactor was taken critical at 2039 hours0.0236 days <br />0.566 hours <br />0.00337 weeks <br />7.758395e-4 months <br /> and Mode 1 was entered at 2129 hours0.0246 days <br />0.591 hours <br />0.00352 weeks <br />8.100845e-4 months <br /> on 2/26/03. The Unit was synchronized to the electrical grid at 0238 hours0.00275 days <br />0.0661 hours <br />3.935185e-4 weeks <br />9.0559e-5 months <br /> on 2/27/03 and power e*calation was begun. Due to elevated and increasing motor bearing temperatures on the running "A" Main Feedwater Pump, an attempt was made to start the "B" Main Feedwater Pump when the 4KV feeder breaker to the "D" 4KV Bus tripped on overcurrent at 1301 hours0.0151 days <br />0.361 hours <br />0.00215 weeks <br />4.950305e-4 months <br /> on 2/27/03. Output was immediately reduced from approximately 57% to approximately 45% as the "A" Main Feedwater Pump remained in service. During the course of the next several hours, output was allowed to reduce from approximately 45% to as low as 36% due to core end of life reactivity management before stabilizing out at approximately 39% output at 2000 hours0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> on 2/27/03. The Unit continued to operate at approximately 39% output while motor bearing temperatures on the "A" Main Feedwater Pump were reduced and stabilized. From 2100 hours0.0243 days <br />0.583 hours <br />0.00347 weeks <br />7.9905e-4 months <br /> on 2/28/03 to 0250 hours0.00289 days <br />0.0694 hours <br />4.133598e-4 weeks <br />9.5125e-5 months <br /> on 3/1/03, power was escalated to approximately 58% (one Main Feedwater Pump operation) while evaluation of the bus trip continued.

OPERATING DATA REPORT DOCKET NO.: 50-334 UNIT NAME: BVPS UNIT #1 REPORT DATE: 03/03/03 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962

"* Note: Rated thermal power at FEBRUARY 2003 la. REPORTING PERIOD: "* BVPS-1 was uprated from 2652 MWt*

1. DESIGN ELECTRICAL RATING (Net MWeN: 835
  • to 2689 MWt on 10/20/01. Net *

"* MDC was also uprated from *

-2.-_M=. _DEPENDABLE.CAPACITY_(Net Me): -821 __ 810 _MWe _to 821 MWe..

  • THIS MONTH YEAR TO DATE CUMULATIVE 3a. HOURS IN REPORTING PERIOD: 672.0 1416.0 235200.0
3. NO. OF ERS. REACTOR WAS CRITICAL: 619.2 1363.2 161954.7
4. SERVICE HOURS GENERATOR ON LINE: 613.2 1357.2 159469.2 UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0 5.
6. NET ELECTRICAL ENERGY GEN. (MWH): 488471.0 1113361.0 119769368.0
7. GROSS ELECT. ENERGY GEN. (MWH): 519301.0 1180381.0 127849971.0
8. GROSS THERMAL ENERGY GEN. (MWH): 1573244.0 3571420.0 393842729.5
9. UNIT AVAILABILITY FACTOR (M): 91.3 95.8 69.2 UNIT CAPACITY FACTOR (MDC) (%): 88.5 95.8 64.7 10.
11. UNIT FORCED OUTAGE RATE (Ms): 8.8 4.2 15.6

UNIT SHUTDOWNS DOCKET NO. 50-412 UNIT NAME BVPS Unit #2 DATE March 3,2003 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: February 2003 No. Date Type Duration Reason Method of Cause / Corrective Actions (Y/M/D) F: Forced (Hours) (1) Shutting S: Scheduled Down (2) Comments NONE.

(1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2- Manual Trip / Scram C - Refueling 3- Automatic Trip I Scram D - Regulatory Restriction 4- Continuation E - Operator Training / Ucense Examination 5- Other (Explain)

F - Administrative G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output for the entire report period.

OPERATING DATA REPORT DOCKET NO.: 50-412 UNIT NAME: BVPS UNIT #2 REPORT DATE: 03/03/03 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962

"* Notes: Rated thermal power at

  • la. REPORTING PERIOD: FEBRUARY 2003 "* BVPS-2 was uprated from 2652 MWt*
i. DESIGN ELECTRICAL RATING (Net MWe): 836
  • to 2689 Mwt on 10/30/01. Net *

"* MDC was also uprated from *

.- MAX.°DEPENDABLE CAPACITY-(Net MWe): 831 *_820 MWe to 831 MWe. _

  • THIS MONTH YEAR TO DATE CUMULATIVE 3a. HOURS IN REPORTING PERIOD: 672.0 1416.0 133983.0
3. NO. OF HRS. REACTOR WAS CRITICAL: 672.0 1416.0 110971.1
4. SERVICE HOURS GENERATOR ON LINE: 672.0 1416.0 110242.5
5. UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0
6. NET ELECTRICAL ENERGY GEN. (MWH): 567210.0 1198299.0 86380702.0
7. GROSS ELECT. ENERGY GEN. (MWH): 596151.0 1258389.0 91290434.0
8. GROSS THERMAL ENERGY GEN. (MWH): 1804094.0 3801982.0 278401593.0
9. UNIT AVAILABILITY FACTOR M6): 100.0 100.0 82.3
10. UNIT CAPACITY FACTOR (MDC) M6): 101.6 101.8 77.6
11. UNIT FORCED OUTAGE RATE M6): 0.0 0.0 9.6