ENCLOSURE

NOTICE OF DEVIATION Tennessee Valley Authority Browns Ferry 1, 2, and

Oocket Nos:

50-259, 260 and 296 License Nos:

OPR-33, 52, and

The following deviation was identified during an inspection conducted on July 27 - August 19, 1985.

Final Safety Analysis Report (FSAR) section 5.3.3.7, Standby Gas Treatment (SBGT)

System, states that the charcoal bed temperature is thermostatically controlled with high and low temperature alarms in the Control Room.

Contrary to the above, no low temperature alarm existed for the charcoal bed temperature.

No other means was established to insure the SBGT heaters were operable.

When the operability of the heaters was questioned by the inspector, train B and train C were found not to be operating properly.

t This deviation is applicable to all three units.

Please provide, in writing within

days of the date of thi s Notice, a

description of corrective actions regarding these deviations, actions taken to avoid further deviations, and the dates when these actions were or will be completed.

Security or safeguards information should be -submitted as an enclosure to facilitate withholding it from public disclosure as required by

CFR 2.790(d)

or 10 CFR 73.21.