IR 05000708/2008004

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 850708-0804
ML20134N125
Person / Time
Site: North Anna, 05000708  
Issue date: 08/21/1985
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20134N123 List:
References
50-338-85-18, 50-339-85-18, NUDOCS 8509050012
Download: ML20134N125 (1)


Text

W

.

.

.

AUG 21 1985 ENCLOSURE 1 NOTICE OF VIOLATION Virginia Electric and Power Company Docket Nos. 50-338 and 50-339 North Anna Units 1 and 2 License Nos. NPF-4 and NPF-7 The following violation was identified during an inspection conducted on July 8 -

Enforcement Policy (10 CFR Part 2, Appendix C)gned in accordance with the NRC August 4,1985.

The Severity Level was assi

.

Unit 1 and Unit 2 Technical Specifications (TS) 4.8.1.1.3a specify a number of surveillance requirements that are to be performed at least once per seven days.

I and 2-PT-85, DC Distribution Systems, are the perfomance tests the licensee uses to satisfy the above requirements.

Unit 1 and Unit 2 TS 4.0.2 require, in part, that each surveillance requirement be performed within the specified interval with a maximum allowable extension not to exceed 25 percent of the surveillance interval.

Contrary to the above, the surveillance intervals for 1 and 2-PT-85 were exceeded in that the tests were performed on July 9,1985, and were not perfomed again until July 19, 1985.

This is a Severity Level V violation (Supplement 1) and applies to both Units.

Pursuant to 10 CFR 2.201, you are required to submit to this office within 30 days of the date of this Notice a written statement or explanation in reply including:

(1) admission or denial of the alleged violations; (2) the reasons for the. violations if admitted, (3) the corrective steps which have been taken and the results achieved, (4) corrective steps which will be taken to avoid further violations, and (5) the date when full compliance will be achieved.

Security or safeguards infomation should be submitted as an enclosure to facilitate withholding it from public disclosure as required by 10 CFR 2.790(d)

or 10 CFR 73.21.

Date:

8509050012 850821 ADOCK 0 % p DR

.

..g..