IR 05000461/2017008
| ML17150A434 | |
| Person / Time | |
|---|---|
| Site: | Clinton (NPF-062) |
| Issue date: | 05/30/2017 |
| From: | Robert Daley Engineering Branch 3 |
| To: | Bryan Hanson Exelon Generation Co, Exelon Nuclear |
| References | |
| IR 2017008 | |
| Preceding documents: |
|
| Download: ML17150A434 (21) | |
Text
May 30, 2017
SUBJECT:
CLINTON POWER STATION TRIENNIAL FIRE PROTECTION INSPECTION REPORT 05000461/2017008
Dear Mr. Hanson:
On April 21, 2017, the U.S. Nuclear Regulatory Commission (NRC) completed a Triennial Fire Protection Inspection at your Clinton Power Station. The enclosed inspection report documents the inspection results, which were discussed on April 21, 2017, with Mr. T. Stoner and other members of your staff.
The inspection examined activities conducted under your license as they relate to safety and compliance with the Commissions rules and regulations and with the conditions of your license.
The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel.
The NRC inspectors documented one finding of very-low safety significance (Green) in this report. This finding was determined to involve a violation of NRC requirements. However, because of its very-low safety significance and because the issue was entered into your Corrective Action Program, the NRC is treating the issue as a Non-Cited Violation in accordance with Section 2.3.2 of the NRC Enforcement Policy.
If you contest the violation or significance of the NCV, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555 0001; with copies to the Regional Administrator, Region III; the Director, Office of Enforcement; and the NRC resident inspector at the Clinton Power Station. This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with 10 CFR 2.390, Public Inspections, Exemptions, Requests for Withholding.
Sincerely,
/RA/
Robert C. Daley, Chief Engineering Branch 3 Division of Reactor Safety Docket No. 50-461 License No. NPF-62 Enclosure:
Inspection Report 05000461/2017008 cc: Distribution via LISTSERV
SUMMARY
Inspection Report 05000461/2017008; 03/21/2017 - 04/21/2017; Clinton Power Station;
Routine Triennial Fire Protection Baseline Inspection.
This report covers an announced Triennial Fire Protection Baseline Inspection. The inspection was conducted by Region III inspectors. One finding was identified by the inspectors. The finding was considered a Non-Cited Violation of U.S. Nuclear Regulatory Commission (NRC)regulations. The significance of most findings is indicated by their color (i.e., greater than Green, or Green, White, Yellow, Red) using Inspection Manual Chapter 0609, Significance Determination Process, dated April 29, 2015. Cross-cutting aspects were determined using Inspection Manual Chapter 0310, Aspects Within the Cross Cutting Areas. Findings for which the Significance Determination Process does not apply may be Green or be assigned a severity level after NRC management review. All violations of NRC requirements are dispositioned in accordance with the NRCs Enforcement Policy dated November 1, 2016. The NRCs program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, Reactor Oversight Process, Revision 6, dated July 2016.
Cornerstone: Mitigating Systems
- Green.
The inspectors identified a finding of very-low safety significance (Green), and an associated Non-Cited Violation of License Condition 2.C(f) for the licensee's failure to adequately implement surveillance procedures and work processes associated with fire barrier damper inspections. Specifically, the licensee failed to perform fire barrier damper inspections for 15 fire dampers once every 48 months (plus an additional 25 percent grace period) as required by the Fire Protection Program. The licensee entered the issue into their Corrective Action Program, and will inspect the fire barrier dampers during the next refueling outage.
The inspectors determined that the performance deficiency was more-than-minor because the licensee's failure to inspect the fire barrier dampers could result in not identifying degraded dampers which could affect their ability to prevent a fire from spreading from one fire area to another. The finding was of very-low safety significance because the failure to inspect the fire barrier dampers did not impact the plant's ability to reach and maintain safe-shutdown. The finding has a cross-cutting aspect in the area of Human Performance, Work Management because the licensee failed to execute a work order to inspect the fire dampers in accordance with the required frequency in Procedure CPS 9601.01 and instead improperly extended the frequency of the fire damper inspections. (Section 1R05.2b) [H.5]
REPORT DETAILS
REACTOR SAFETY
Cornerstones: Initiating Events and Mitigating Systems
1R05 Fire Protection
The purpose of the Fire Protection Triennial Baseline Inspection was to conduct a design-based, plant specific, risk-informed, onsite inspection of the licensees Fire Protection Programs defense-in-depth elements used to mitigate the consequences of a fire. The Fire Protection Program shall extend the concept of defense-in-depth to fire protection in plant areas important to safety by:
preventing fires from starting;
rapidly detecting, controlling and extinguishing fires that do occur;
providing protection for structures, systems, and components important to safety so that a fire that is not promptly extinguished by fire suppression activities will not prevent the safe-shutdown of the reactor plant; and
taking reasonable actions to mitigate postulated events that could potentially cause loss of large areas of power reactor facilities due to explosions or fires.
The inspectors evaluation focused on the design, operational status, and material condition of the reactor plants Fire Protection Program, post-fire safe-shutdown (SSD)systems, and B.5.b mitigating strategies. The objectives of the inspection were to assess whether the licensee had implemented a Fire Protection Program that:
- (1) provided adequate controls for combustibles and ignition sources inside the plant;
- (2) provided adequate fire detection and suppression capability;
- (3) maintained passive fire protection features in good material condition;
- (4) established adequate compensatory measures for out-of-service, degraded or inoperable fire protection equipment, systems or features;
- (5) ensured that procedures, equipment, fire barriers and systems exist so that the post-fire capability to safely shut down the plant was ensured;
- (6) included feasible and reliable operator manual actions when appropriate to achieve SSD; and
- (7) identified fire protection issues at an appropriate threshold and ensured these issues were entered into the licensees Problem Identification And Resolution Program.
In addition, the inspectors review and assessment focused on the licensees post-fire SSD systems for selected risk-significant fire areas. Inspector emphasis was placed on determining that the post-fire SSD capability and the fire protection features were maintained free of fire damage to ensure that at least one post-fire SSD success path was available. The inspectors review and assessment also focused on the licensees B.5.b related license conditions and the requirements of Title 10 of the Code of Federal Regulations (CFR), Part 50.54 (hh)(2). Inspector emphasis was to ensure that the licensee could maintain or restore core cooling, containment, and spent fuel pool cooling capabilities utilizing the B.5.b mitigating strategies following a loss of large areas of power reactor facilities due to explosions or fires. Documents reviewed are listed in the to this report.
The fire areas and fire zones and B.5.b mitigating strategies selected for review during this inspection are listed below and in Section 1R05.13. The fire areas and fire zones selected constituted four inspection samples and the B.5.b mitigating strategies selected constituted two inspection samples, respectively, as defined in Inspection Procedure 71111.05T.
Fire Area Fire Zone Description CB-2 CB-2 Division 2 Cable Spreading Room CB-3 CB-3e Division 2 Nuclear Systems Protection System Inverter Room CB-6 CB-6d Corridor and Miscellaneous Rooms D-4 D-4a Division 3 Diesel Generator Room
.1 Protection of Safe Shutdown Capabilities
a. Inspection Scope
For each of the selected fire areas, the inspectors reviewed the fire hazards analysis, SSD analysis, and supporting drawings and documentation to verify that SSD capabilities were properly protected.
The inspectors also reviewed the licensees design control procedures to ensure that the process included appropriate reviews and controls to assess plant changes for any potential adverse impact on the fire protection program and/or post-fire SSD analysis and procedures.
b. Findings
No findings of significance were identified.
.2 Passive Fire Protection
a. Inspection Scope
For the selected fire areas, the inspectors evaluated the adequacy of fire area barriers, penetration seals, fire doors, electrical raceway fire barriers, and fire rated electrical cables. The inspectors observed the material condition and configuration of the installed barriers, seals, doors, and cables. The inspectors reviewed approved construction details and supporting fire tests. In addition, the inspectors reviewed license documentation, such as U.S. Nuclear Regulatory Commission (NRC) Safety Evaluation Reports, and deviations from NRC Regulations and the National Fire Protection Association standards to verify that fire protection features met license commitments.
The inspectors walked down accessible portions of the selected fire areas to observe material condition and the adequacy of design of fire area boundaries (including walls, fire doors, and fire dampers) to ensure they were appropriate for the fire hazards in the area.
The inspectors reviewed the installation, repair, and qualification records for a sample of penetration seals to ensure the fill material was of the appropriate fire rating and that the installation met the engineering design.
b. Findings
Failure to Perform Required Surveillances on Multiple Fire Dampers
Introduction:
The inspectors identified a finding of very-low safety significance (Green)and an associated Non-Cited Violation (NCV) of License Condition 2.C(f) for the licensees failure to adequately implement surveillance procedures and work processes associated with fire barrier damper inspections. Specifically, the licensee failed to perform fire barrier damper inspections for 15 fire dampers once every 48 months (plus an additional 25 percent grace period) as required by the Fire Protection Program.
Description:
License Condition 2.C(f) required the licensee to fully implement and maintain in effect all provisions of the approved Fire Protection Program as described in the Final Safety Analysis Report as amended, and as approved in the Safety Evaluation Report (NUREG-0853) dated February 1982 and Supplement Numbers 1 through 8.
Section 9.5.1.4 of the Updated Final Safety Analysis Report stated, in part, that fire dampers will be subjected to periodic tests and/or inspections, as specified in plant administrative procedures. Specifically, Procedure CPS 9601.01, Fire Rated Assemblies and Penetration Sealing Devices, Section 2.1.1 required that fire dampers and associated hardware be verified operable at least once per 48 months (allowing an additional 25 percent grace period) by visual inspection.
During the inspection the inspectors requested records of fire barrier damper inspections. While providing the response the licensee determined that 15 fire barrier dampers, whose design function is to preclude a fire from one fire area from spreading to an adjacent fire area, were not inspected as required by Procedure CPS 9601.01 since November 2011. The grace period for performing the inspections had expired in November 2016. The licensee had scheduled to inspect these fire dampers in 2015, but decided to extend the frequency of these inspection out to 5 years assuming another 25 percent grace period, which would alter the effective frequency of inspection to 6 years, without evaluating and documenting the frequency extension.
The licensee entered the issue into their Corrective Action Program (CAP) as Action Request (AR) 03992372, 2017 FP Triennial: Damper Surveillances Exceeds Frequency, dated March 31, 2017, and AR 03992375, 2017 FP Triennial: DG Damper Surveillance Missed, dated March 31, 2017. The licensee immediately declared these fire dampers non-functional and verified that the fire detectors on at least one side of these fire damper locations were functional. In accordance with Procedure CPS 1893.01, Fire Protection Impairment Reporting, Appendix A, Fire Protection Functionality Requirements #8 Fire Rated Assemblies, the licensee implemented a 1-hour fire watch as a compensatory action. In addition, the licensee will perform a full inspection of these fire dampers during the next refueling outage.
Analysis:
The inspectors determined that the licensees failure to perform fire barrier damper inspections was a performance deficiency and was contrary to the Fire Protection Programs requirement of inspection within every 48 months. Specifically, the licensee failed to perform fire barrier damper inspections for 15 dampers at least once every 48 months (plus an additional 25 percent grace period).
The inspectors determined that the performance deficiency was more than minor because the finding was associated with the Mitigating Systems cornerstone attribute of Protection Against External Factors (Fire) and affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage).
In accordance with Inspection Manual Chapter (IMC) 0609, Significance Determination Process, Attachment 0609.04, Initial Characterization of Findings, Table 2, the inspectors determined the finding affected the Mitigating Systems cornerstone. The finding degraded fire protection defense-in-depth strategies, and the inspectors determined, using Table 3, that it could be evaluated using Appendix F, Fire Protection Significance Determination Process. Specifically, the licensees failure to inspect the fire barrier dampers could result in not identifying degraded dampers which could affect their ability to prevent a fire from spreading from one fire area to another.
The inspectors screened the finding using IMC 0609, Appendix F, Attachment 1, Part 1:
Fire Protection SDP Phase 1 Worksheet, dated September 20, 2013. The inspectors answered yes to Question 1.3.1, Is the reactor able to reach and maintain safe shutdown (either hot or cold) condition?, in Task 1.3.1 of IMC 0609, Appendix F. The failure to inspect these 15 fire barrier dampers did not impact the plants ability to reach and maintain safe shutdown. Even though these fire barrier dampers were declared non-functional, the fire dampers were located in areas with fire detection systems. In addition, in most of the affected areas there was a functional automatic suppression system in the area on at least one side of the barrier with the non-functional damper.
Therefore, the inspectors determined that the finding screened as having very-low safety significance (Green).
The finding has a cross-cutting aspect in the area of Human Performance, Work Management because the licensee failed to implement a process for planning, controlling, and executing work activities such that nuclear safety is the overriding priority. Specifically, the licensee staff failed to execute the work order to inspect the fire dampers in accordance with the required frequency in Procedure CPS 9601.01 and instead extended the frequency of the fire damper inspections. [H.5]
Enforcement:
License Condition 2.C(f) requires the licensee to fully implement and maintain in effect all provisions of the approved Fire Protection Program as described in the Final Safety Analysis Report as amended, and as approved in the Safety Evaluation Report (NUREG-0853) dated February 1982 and Supplement Numbers 1 through 8.
Section 9.5.1.4 of the Updated Final Safety Analysis Report stated, in part, that the fire dampers will be subjected to periodic tests and/or inspections, as specified in plant administrative procedures. Specifically, Procedure CPS 9601.01, Fire Rated Assemblies and Penetration Sealing Devices, Section 2.1.1, required that fire dampers and associated hardware shall be verified operable at least once per 48 months by visual inspection.
Contrary to the above, since November 9, 2011, the licensee failed to implement and maintain in effect all provisions of the approved Fire Protection Program. Specifically, the licensee failed to perform fire damper inspections for 15 fire dampers once every 48 months as required by Procedure CPS 9601.01. The licensee had last completed inspections of these fire dampers on November 9, 2011.
This violation is being treated as an NCV, consistent with Section 2.3.2 of the NRC Enforcement Policy because it was of very-low safety significance and was entered into the licensees CAP as AR 03992375 and AR 03992372. The licensee inspected the accessible fire dampers, implemented an hourly fire watch, and will perform a full inspection of the remaining fire dampers during the next refueling outage.
(NCV 05000461/2017008-01, Failure to Perform Required Surveillances on Multiple Fire Dampers)
.3 Active Fire Protection
a. Inspection Scope
For the selected fire areas, the inspectors evaluated the adequacy of fire suppression and detection systems. The inspectors observed the material condition and configuration of the installed fire detection and suppression systems. The inspectors reviewed design documents and supporting calculations. In addition, the inspectors reviewed license basis documentation, such as, NRC Safety Evaluation Reports, deviations from NRC Regulations, and National Fire Protection Association standards to verify that fire suppression and detection systems met license commitments.
The team observed an unannounced fire drill simulating a fire in the turbine building.
The team observed fire brigade members fight a simulated fire. The team verified that the licensee identified problems, openly discussed them in a self-critical manner at the drill debrief, and identified appropriate corrective actions.
b. Findings
No findings of significance were identified.
.4 Protection from Damage from Fire Suppression Activities
a. Inspection Scope
For the selected fire areas, the inspectors verified that redundant trains of systems required for hot shutdown would not be subject to damage from fire suppression activities or from the rupture or inadvertent operation of fire suppression systems including the effects of flooding. The inspectors conducted walkdowns of each of the selected fire areas to assess conditions such as the adequacy and condition of floor drains, equipment elevations, and spray protection.
b. Findings
No findings of significance were identified.
.5 Alternative Shutdown Capability
a. Inspection Scope
The inspectors reviewed the licensees systems required to achieve alternative SSD to determine if the licensee had properly identified the components and systems necessary to achieve and maintain safe shutdown conditions. The inspectors also focused on the adequacy of the systems to perform reactor pressure control, reactivity control, reactor coolant makeup, decay heat removal, process monitoring, and support system functions.
The inspectors conducted selected area walkdowns to determine if operators could reasonably be expected to perform the alternate SSD procedure actions and that equipment labeling was consistent with the alternate SSD procedure. The review also looked at operator training as well as consistency between the operations shutdown procedures and any associated administrative controls.
b. Findings
No findings of significance were identified
.6 Circuit Analyses
a. Inspection Scope
The inspectors verified that the licensee performed a post-fire SSD analysis for the selected fire areas and the analysis appropriately identified the structures, systems, and components important to achieving and maintaining SSD. Additionally, the inspectors verified that the licensee's analysis ensured that necessary electrical circuits were properly protected and that circuits that could adversely impact SSD due to hot shorts, shorts to ground, or other failures were identified, evaluated, and dispositioned to ensure spurious actuations would not prevent SSD.
The inspectors' review considered fire and cable attributes, potential undesirable consequences, and common power supply/bus concerns. Specific items included the credibility of the fire threat, cable insulation attributes, cable failure modes, and actuations resulting in flow diversion or loss of coolant events.
The inspectors also reviewed cable raceway drawings for a sample of components required for post-fire SSD to verify that cables were routed as described in the cable routing matrices.
The inspectors reviewed circuit breaker coordination studies to ensure equipment needed to conduct post-fire safe shutdown activities would not be impacted due to a lack of coordination. Additionally, the inspectors reviewed a sample of circuit breaker maintenance records to verify that circuit breakers for components required for post-fire SSD were properly maintained in accordance with procedural requirements.
The inspectors verified for cables that are important to SSD, but not part of the success path, and that do not meet the separation/protection requirements of Section III.G.2 of 10 CFR 50, Appendix R, that the circuit analysis considered the cable failure modes.
In addition, the inspectors have verified that the licensee has either:
- (1) determined that there is not a credible fire scenario (through fire modeling),
- (2) implemented feasible and reliable manual actions to assure SSD capability, or
- (3) performed a circuit fault analysis demonstrating no potential impact on SSD capability exists.
b. Findings
No findings of significance were identified.
.7 Communications
a. Inspection Scope
The inspectors reviewed, on a sample basis, the adequacy of the communication system to support plant personnel in the performance of alternative SSD functions and fire brigade duties. The inspectors verified that plant telephones, page systems, sound powered phones, and radios were available for use and maintained in working order. The inspectors reviewed the electrical power supplies and cable routing for these systems to verify that either the telephones or the radios would remain functional following a fire.
b. Findings
No findings of significance were identified.
.8 Emergency Lighting
a. Inspection Scope
The inspectors performed a plant walkdown of selected areas in which a sample of operator actions would be performed in the performance of alternative SSD functions.
As part of the walkdowns, the inspectors focused on the existence of sufficient emergency lighting for access and egress to areas and for performing necessary equipment operations. The locations and positioning of the emergency lights were observed during the walkdown and during review of manual actions implemented for the selected fire areas.
b. Findings
No findings of significance were identified.
.9 Cold Shutdown Repairs
a. Inspection Scope
The licensee did not credit any repairs in order to achieve cold shutdown. Therefore, no reviews were performed by the inspectors for this procedure section.
b. Findings
No findings of significance were identified.
.10 Compensatory Measures
a. Inspection Scope
The inspectors conducted a review to verify that compensatory measures were in place for out-of-service, degraded or inoperable fire protection and post-fire SSD equipment, systems, or features (e.g., detection and suppression systems, and equipment, passive fire barriers, pumps, valves or electrical devices providing safe shutdown functions or capabilities). The inspectors also conducted a review of the adequacy of short term compensatory measures to compensate for a degraded function or feature until appropriate corrective actions were taken.
b. Findings
No findings of significance were identified.
.11 Review and Documentation of Fire Protection Program Changes
a. Inspection Scope
The inspectors reviewed changes to the approved Fire Protection Program to verify that the changes did not constitute an adverse effect on the ability to safely shutdown. The inspectors also reviewed the licensees design control procedures to ensure that the process included appropriate reviews and controls to assess plant changes for any potential adverse impact on the Fire Protection Program and/or post-fire SSD analysis and procedures.
b. Findings
No findings of significance were identified.
.12 Control of Transient Combustibles and Ignition Sources
a. Inspection Scope
The inspectors reviewed the licensee's procedures and programs for the control of ignition sources and transient combustibles to assess their effectiveness in preventing fires and in controlling combustible loading within limits established in the fire hazards analysis. A sample of hot work and transient combustible control permits were also reviewed. The inspectors performed plant walkdowns to verify that transient combustibles and ignition sources were being implemented in accordance with the administrative controls.
b. Findings
No findings of significance were identified.
.13 B.5.b Inspection Activities
a. Inspection Scope
The inspectors reviewed the licensees preparedness to handle large fires or explosions by reviewing selected mitigating strategies. This review ensured that the licensee continued to meet the requirements of their B.5.b related License Conditions and 10 CFR 50.54(hh)(2) by determining that:
procedures were being maintained and adequate;
equipment was properly staged, maintained, and tested;
station personnel were knowledgeable and could implement the procedures; and
additionally, inspectors reviewed the storage, maintenance, and testing of B.5.b related equipment.
The inspectors reviewed the licensees B.5.b-related License Conditions and evaluated selected mitigating strategies to ensure they remain feasible in light of operator training, maintenance/testing of necessary equipment and any plant modifications. In addition, the inspectors reviewed previous inspection reports for commitments made by the licensee to correct deficiencies identified during performance of Temporary Instruction 2515/171 or subsequent performances of these inspections.
The B.5.b mitigating strategies selected for review during this inspection are listed below. The offsite and onsite communications, notifications/emergency response organization activation, initial operational response actions and damage assessment activities identified in Table A.3-1 of Nuclear Energy Institute 06-12, B.5.b Phase II and III Submittal Guidance, Revision 2, are evaluated each time due to the mitigation strategies scenario selected.
NEI 06-12, Revision 2, Section Licensee Strategy (Table)2.3.1 Spent Fuel Pool External Makeup (Table A.2-2)3.4.5 Makeup to the Reactor Core Isolation Cooling (RCIC) Tank (Table A.5-5)
b. Findings
No findings of significance were identified.
OTHER ACTIVITIES
4OA2 Identification and Resolution of Problems
a. Inspection Scope
The inspectors reviewed the licensees CAP procedures and samples of corrective action documents to verify that the licensee was identifying issues related to the Fire Protection Program at an appropriate threshold and entering them in the CAP. The inspectors reviewed selected samples of condition reports, design packages, and fire protection system non-conformance documents.
b. Findings
No findings of significance were identified.
4OA5 Other Activities
.1 (Closed) Unresolved Item 05000461/2014007-01, Interpretation of Requirements for
Multiple Spurious Operations During the Triennial Fire Protection Inspection in 2014 the inspectors identified an unresolved item (URI) associated with the interpretation of requirements for addressing multiple spurious operations (MSOs). Specifically, the licensees position was that addressing MSOs was a voluntary effort and not a requirement. Based on current interpretation and guidance the inspectors disagree with the licensees position.
However, during a review of the licensees analyses the inspectors did not identify any MSO scenarios that the licensee did not consider and disposition. The licensee also took the position that they could limit the analysis of MSOs to four components when evaluating a scenario. The inspectors disagreed with this position. During the 2014 inspection the inspectors requested the licensee to perform a qualitative analysis on diesel generator loading involving more than four loads. The licensee performed this analysis and showed that the additional loads were still within the margin of the diesel generator. The inspectors did not identify any additional scenarios during this inspection where the licensee did not appropriately consider and disposition all affected components. Lastly, in 2014 the inspectors discussed the determination of SSD path components in the URI. During the current inspection, the inspectors did not identify any concerns with the determination of SSD path components. The inspectors reviewed the licensees fire hazards and SSD analyses, circuit analyses, and the fire response procedures and did not identify a violation at this time. Therefore, this URI is closed.
4OA6 Management Meetings
.1
Exit Meeting Summary
On April 21, 2017, the inspectors presented the inspection results to Mr. T. Stoner, and other members of the licensee staff. The licensee acknowledged the issues presented.
The inspectors confirmed that none of the potential report input discussed was considered proprietary.
ATTACHMENT:
SUPPLEMENTAL INFORMATION
KEY POINTS OF CONTACT
Licensee
- D. Avery, Regulatory Affairs
- K. Burda, Fire Protection Engineer
- B. Kapellas, Plant Manager
- T. Krawcyk, Engineering Director
- W. Marsh, Security Director
- K. Pointer, Regulatory Affairs
- E. Rodriguez, Engineering Manager
- D. Shelton, Regulatory Assurance Manager
- T. Stoner, Site Vice President
- J. Wilson, Engineering Manager
U.S. Nuclear Regulatory Commission
- R. Daley, Branch Chief, EB3
- E. Sanchez Santiago, Resident Inspector
- W. Schaup, Senior Resident Inspector
LIST OF ITEMS
OPENED, CLOSED AND DISCUSSED
Opened and Closed
- 05000461/2017008-01 NCV Failure to Perform Required Surveillances on Multiple Fire Dampers (Section 1R05.2b)
Closed
- 05000461/2014007-01 URI Interpretation of Requirements for Multiple Spurious Operations (Section 4OA5.1)
Discussed
None LIST OF ACRONYMS USED AR Action Request CAP Corrective Action Program CPS Clinton Power Station IMC Inspection Manual Chapter MSO Multiple Spurious Operations NCV Non-Cited Violation NRC U.S. Nuclear Regulatory Commission SSD Safe Shutdown URI Unresolved Item