PRIORITY1IACCELERATEDRIBSPROCI'.SSliG)REGULATORYINFORMATIONDISTRIBUTIONSYSTEM(RIDS)CCESSIONNBR:9411020260DOC.DATE:94/10/27NOTARIZED-NODOCKETFACIL:5p'-387SusquehannaSteamElectricStation,Unit1,Pennsylva050003875G-388SusquehannaSteamElectricStation,Unit2,Pennsylva05000388AUTH.NAMEAUTHORAFFILIATIONBYRAM,R.G.PennsylvaniaPower&LightCo.RECIP.NAMERECIPIENTAFFILIATIONDocumentControlBranch(DocumentControlDesk)

SUBJECT: RespondstoNRC940917ltrreviolationsnotedinInspRepts50-387/94-16&50-388/94-16.Correctiveactions:standusedtoblockFireDoor44removed&fusiblelinkassemblyverifiedtoholddooropen.DISTRIBUTIONCODE:IE01DCOPIESRECEIVED:LTR.ENCLSIZE:TITLE:General(50Dkt)-InspRept/NoticeofViolationResponseNOTES'5000387RECIPIENTIDCODE/NAMEPD1-2PDINTERNAL:ACRSAEOD/SPD/RABAEOD/~C~~~FILECENTER02NRR/DRCH/HHFBNUDOCS-ABSTRACTOGC/HDS2RGN1FILE01EXTERNAL:LITCOBRYCE,JHNRCPDRNOTESCOPIESLTTRENCL11221111111111111111'111RECIPIENTIDCODE/NAMEPOSLUSNY,CAEOD/DEIBAEOD/SPD/RRABDEDRONRR/DORS/OEABNRR/PMAS/IRCB-EOEDIRRES/HFBNOACCOPI'ESLTTRENCL1111111111111111'11VOTETOALL"RIDS"RECIPIENTS:PlEASEISELPUSTOREDUCEiVKSTE!CONTAC'I"I'IIEDOCL'ifE4TCOi'TROLDESK,ROOXfPl-37(E)iT.504.~0S3)TOI.LIXfliA1'L5'OURi'ANIL:FAOifDISfRIBU'I'IOYLIS'I'SI'ORDOCI'Nfl'.i'I'SYOUI)Oi"I'4'III)!TOTALNUMBEROFCOPIESREQUIRED:LTTR22ENCL22

PennsylvaniaPower8LightCompanyTwoNorthNinthStreet~Allentown,PA18101-1179~610/774-5151RobertG.ByramSeniorVicePresident-Nuclear610/774-7502Fax:610/774-5019ccT2789<U.S.NuclearRegulatoryCommissionAttn.:DocumentControlDeskMailStopP1-137Washington,D.C.20555SUSQUEHANNASTEAMELECTRICSTATIONREPLYTONOTICEOFVIOLATION(387/94-16-01AND387/94-16-03)DocketNos.50-38750-388

DearSir:

ThisletterprovidesPennsylvaniaPowerEcLightCompany'sresponsetotheNoticeofViolationforNRCCombinedInspectionReport50-387/94-16and50-388/94-17datedSeptember27,1994.Thenoticerequiredsubmittalofawrittenreplywithinthirty(30)daysofthedateofthelettertransmittingtheNoticeofViolation.Wetrustthatthecommissionwillfindtheattachedresponseacceptable.Verytrulyyours,tR.~rmAttachmentcc:RegionalAdministrator-RegionIMs.M.Banerjee,NRCSr.ResidentInspectorMr.C.Poslusny,Jr.,NRCSr.ProjectManager9411020260941027PDRADOCK05000387PDR1(~pi(

ATTACHMENTTOPLA4211FILER41-2PAGE1OF5REPLYTOANOTICEOFVIOLATIONViolation(387/94-16-03)10CFRPart50,AppendixB,CriterionXVI,"CorrectiveActions,"requires,inpart,thatin-casesofsignificantconditionsadversetoquality,measuresshallassurethatthecauseoftheconditionisdeterminedandcorrectiveactiontakentoprecluderepetition.Contrarytotheabove,onMarch4andMarch7,1994,thelicenseediscoveredthatfiredoor44wasblockedopenandtherequiredformNDAP-QA-0441whichauthorizesandrecognizestheconditionwasnotcompletedcontributingasignificantconditionadversetoquality.Additionally,priortotheseoccurrences,thelicenseeidentifiedseveralinstanceswherefiredoorswereblockedopenwithoutformNDAP-QA-0441beingcompleted.OnJuly20,1994,theinspectordiscoveredfiredoor44blockedopenwithouttherequiredapproval.Correctiveactionsforthesepreviouseventsdidnotprecluderepetitioninthattheinspectoridentified,again,onAugust23,1994thatfiredoor44wasblockedopenwithoutapproval.~Resense1.ReasonfortheViolationTheidentificationofstationdoorsasalsobeingfiredoorsisinadequate,andcombinedwithotherlabelingonthedoor,makesthedeterminationasafiredoordifticult.Theonlywaytoidentifyafiredoorisbythereddoorlabelwhichislocatedintheupper.cornerofthedoororbyutilizingNDAP-QA-0441,"FireProtectionSystemStatusControl."FireDoor844alsohadalabelaffixedtoitwhichstates"thisdoortoremainopen"(forventilationpurposes).Theintentwasthatfiredoor044onlybeheldopenbyitsfusiblelink.However,nonotificationwasavailableatthedoorwhichspecifiesthatthedoormaynotbeheldopenbyanymethodotherthanafusiblelin ATI'ACHMENTTOPLA-4211FILER41-2PAGE2OFS2.CorrectiveStesWhichHaveBeenTakenandtheResultsAchieveda.,ThestandusedtoblockopenFireDoor844wasremovedandthefusiblelinkassemblywasverifiedtoholdthedooropen.b.ThelabelonFireDoor844,thatstated"thisdoortoremainopen"wasremovedtoassistineliminatinglabelingconfusion.3.CorrectiveStesWhichWillBeTakentoAvoidFurtherViolationsa.Stationfiredoorswillbelabeledinlargelettersateyelevelasfollows:"FIREDOOR-DONOTBLOCKOPENWITHOUTAUTHORIZATION"b.Sitepersonnelwillbetrainedonthestatuscontrolrequirementsforstationfiredoors.TrainingofsitepersonnelwillbeconductedthroughGETTraining/RetrainingandPre-outagebriefings.4.DateofFullComlianceBasedon(2)abovePPkLisinfullcompliance.Labelingofstationfiredoors,asidentifiedin(3.a)abovewillbecompletedbyDecember31,1994.Trainingofstationpersonnelasidentifiedin(3.b)abovewillbecompletedbyApril10,199 AT1'ACHMENTTOPLAA211FILER41-2PAGE3OF58.Violalion(387/94-16-01)TechnicalSpecifications3.3.7.9,3.7.6.2and3.7.7requiresthatcontinuousfirewatchesbeestablishedwithinonehourwhenfiredetectionandsuppressionsystemsareinoperable.Contrarytotheabove,onAugust2,1994,at9:31p.m.,continuousfirewatcheswerenotestablishedwithintherequiredonehourfollowingthedeterminationthattheSimplexFireProtectionSystem(firedetectionandsuppressionsystem)wasinoperable.Specifically,foratleast10hoursfollowingtheevent,continuousfirewatcheswerenotimplemented.~ResenseReferenceLER50-387/94-012-00formoredetailsconcerningthiseventI.ReasonfortheViolationOnAugust2,1994,at2131hoursalightningstrikecausedacompletefailureoftheSimplexFireProtectionSystem.Availablepersonnelwereassignedrovingfirewatchdutiesintheaffectedareas.Continuousfirewatchescouldnotbeestablishedduetomanpowerlimitationsandtheextensivenumberofareasrequiringcoverage.Additionally,miscommunicationbetweentheSiteFireProtectionEngineerandShiASupervision,andinadequatecommunicationbetweenShiASupervisionandStationManagementcontributedtothefailuretoestablishcontinuousfirewatcheswithinonehour.ShiASupervisionaskedifhourlyfirewatcheswereacceptablegiventhesituationandtheFireProtection.Engineerrespondedthatitwas.However,ShiASupervisioninterpretedthistomeanacceptableforthedurationoftheLCO,andwhat'heFireProtectionEngineeractuallymeantbyhisresponsewasthatthiswasacceptableintheinterimuntiladditionalpersonnelwerecalledintomanthecontinuousfirewatches.InadequatecommunicationthenoccurredduringatelephoneconversationwhenShiASupervisionnotifiedStationManagementoftheevent.AssumptionsweremadebyStationManagementastotheactionplanandrecoveryeffortsfortheremainderoftheevening.Additionalquestioningand/orconversationwouldhaveledtoamoreappropriateresponse,specificallyrelatedtocontinuingeffortstostaffcontinuousfirewatchassoonaspossibl ATTACHMENTTOPLA-4211FILER41-2PAGE4OF52.ManaementExectationsa.StationManagement'sexpectationsregardingfireprotectionwascommunicatedtostationpersonnelviaaletterfromtheVicePresident-NuclearOperations.This'letterwasalsopublishedinthedepartmentalnewsletterwhichisdistributedtotheNuclearDepartment.Thisletterstatedexpectationswithrespecttofireprotectionprogramcompliance,procedureimplementation,andsystem/componentoperability.Italsoidentifiedprogrammaticshortcomings,statedactionsthatmustbeachieved,andactionsbeingtakentoachievestatedobjectives:TheletterconcludedbystatingthatSusquehannacannottoleratelessthanexcellentperformanceregardingfireprotection.-b.Additionally,Operation'sManagementissuedamemorandumtoShiftSupervisionidentifyingthefailuretomeetthecontinuousfirewatchLCOrequirementofthetechnicalspecifications,andtheirexpectationsthatrequirementsofthetechnicalspecificationsaretobeachieved.3.CorrectiveStesWhichHaveBeenTakenandtheResultsAchieveda.At0730hoursonAugust3,1994,itwasdeterminedthatcontinuousfirewatcheswererequiredandeffortswerestartedtosupportcontinuousfirewatches.Between0800and1210hoursonAugust3,1994,identificationofallfirezonesrequiringcontinuousfirewatcheswascompletedandstaffingof'thesezonesbegan.At1145hoursonAugust3,1994,theSimplexSystemwasrestored,andat1250hoursthefirewatchesestablishedforthiseventwereremoved.b.OperatingInstruction(OI-AD-013)wasissuedtoprovideshiftsupervisionguidanceintheeventofSimplexfailuresandtoassisttheoperatorthroughassessmentandcompensatorymeasuresdeemedappropriate.c.RequirementsforcontinuousfirewatcheshavebeenreevaluatedandupdatedconsistentwithTechnicalSpecifications.Thisresultedinareductioninthenumberofcontinuousfirewatchesrequired.d.AmemorandumhasbeenissuedtoOperationsshiftsupervisionemphasizingexpectationsregardingTechnicalSpecificationcompliance.(item2.b)e.Amemorandumhasbeenissuedtositepersonnel(letter)anddepartmentalpersonnel(newsletter)clarifyingexpectationsregardingfireprotection.(item2.a)

ATTACHMENTTOPLA4211FILER41-2PAGE5OF54.CorrectiveStesWhichWillBeTakentoAvoidFurtherUiolationsa.Trainadditionalon-shiftpersonneltobeabletoperformfirewatchduties.b.ProvideOperationscontrolroompersonneltrainingonSimplexsystemoperation,messagesandfailuremodesc.Reviewthiseventwithappropriateworkgroupsstressingtheimportanceofclearcommunications.d.EvaluateTechnicalSpecificationrequirementsforpostingfirewatcheswithinonehourandprocessappropriatechanges.e.AnEventReviewTeam(ERT)wasestablishedandperformedarootcauseanalysis.TheERTidentifiedseveralothercontributingfactorsinadditiontotheprimarycausesforthefailuretoestablishtherequiredfirewatchesandSimplexfailure(manpowerlimitations,extensivefirewatchareasrequiringcoverageandcommunications).TheseitemswillbedispositionedasdeterminedbytheERT.5.DateofFullComlianceBasedon(3.a)abovePALisinfullcompliance.Trainingofadditionalfirewatchesidentifiedin(4.a)abovewillbecompletedby12/31/94.Othertraining/reviewingactionidentifiedin(4.bandc)abovewillbecompletedby3/31/95.Evaluation/submittalofTechnicalSpecificationrevisions,ifnecessary,willbecompletedbyJune30,1995.