IR 05000335/2010009
| ML103070200 | |
| Person / Time | |
|---|---|
| Site: | Saint Lucie (DPR-067) |
| Issue date: | 11/03/2010 |
| From: | Rich D NRC/RGN-II/DRP/RPB3 |
| To: | Nazar M Florida Power & Light Co |
| References | |
| EA-09-321 IR-10-009 | |
| Download: ML103070200 (27) | |
Text
November 3, 2010
SUBJECT:
ST. LUCIE NUCLEAR PLANT, Unit 1 - NRC INSPECTION PROCEDURE 95002 SUPPLEMENTAL INSPECTION REPORT 05000335/2010009
Dear Mr. Nazar:
On September 30, 2010, the U.S. Nuclear Regulatory Commission (NRC) staff completed a supplemental inspection pursuant to Inspection Procedure 95002, Inspection for One Degraded Cornerstone or any Three White Inputs in a Strategic Performance Area, at your St. Lucie Nuclear Plant, Unit 1. The enclosed inspection report documents the inspection results and closure of this finding, which were discussed at the exit meeting on October 1, 2010, with Mr. R.
Anderson and other members of your staff. As a result, the NRC determined the performance at St. Lucie Unit 1 to be in the Licensee Response Column of the Reactor Oversight Process Action Matrix, as of October 1, 2010.
As required by the NRC Reactor Oversight Process Action Matrix, this supplemental inspection was performed because a finding of Yellow safety significance was identified in the 4th quarter of 2009. This issue was documented previously in NRC Inspection Report 05000335/2010007 and 05000389/2010007. The NRC staff was informed on April 28, 2010, of your staffs readiness for this inspection.
The objectives of this supplemental inspection were to provide assurance that: (1) the root causes and the contributing causes for the risk-significant issues were understood, (2) the extent of condition and extent of cause of the issues were identified, and (3) corrective actions were or will be sufficient to address and preclude repetition of the root and contributing causes.
This inspection also included an independent NRC review of the extent of condition and extent of cause for the Yellow finding and an assessment of whether any safety culture component caused or significantly contributed to the issue. The inspection consisted of examination of activities conducted under your license as they related to safety, compliance with the Commissions rules and regulations, and the conditions of your operating license.
The inspectors determined that your staff performed a comprehensive evaluation of the subject Yellow finding associated with the component cooling water (CCW) system air intrusion event.
Your staffs evaluation identified root causes of the issue to be: (1) decision making by the organization was insufficient due to inadequate knowledge and skills related to risk significant decisions, conservative assumptions and timely communication between departments, (2) the
organization missed several opportunities to promptly identify, fully analyze and resolve in a timely manner the air intrusion event, (3) inadequate fleet/site procedures resulted in the failure to recognize the condition and significance of the event in a timely manner, (4) management did not effectively implement policies and procedures, which resulted in a reluctance to challenge issues and recognize the significance of the 2008 event and a repeat of the event in 2009, (5)
less than adequate design of the containment air compressor system resulted in recurrent air intrusion events, and (6) less than adequate maintenance resulted in a similar 2009 CCW system air intrusion event. The inspectors determined that your staff proposed appropriate corrective actions to upgrade operability determinations of degraded conditions, improve the effectiveness of the corrective action program, improve procedural guidance in several areas, and address deficiencies related to safety culture.
Based on the results of this inspection, one finding of very low safety significance (Green) was identified. The finding was determined to involve a violation of NRC requirements. However, because of the very low safety significance of the issue and because it was entered into your corrective action program, the NRC is treating the issue as a non-cited violation (NCV)
consistent with the NRC Enforcement Policy. If you contest the NCV in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the Nuclear Regulatory Commission, ATTN.: Administrator, Commission, Washington DC 20555-0001; and the NRC Resident Inspector at the St. Lucie Nuclear Plant. In addition, if you disagree with the cross-cutting aspect assigned to any finding in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your disagreement, to the Regional Administrator, Region II, and the NRC Resident Inspector at the St. Lucie Nuclear Plant.
In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter, its enclosure, and your response (if any) will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRC's document system, Agencywide Documents Access and Management System (ADAMS).
ADAMS is accessible from the NRC Website at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).
Sincerely,
/RA/
Daniel W. Rich, Chief Reactor Projects Branch 3 Division of Reactor Projects
Docket No. 50-335 License No. DPR-67
Enclosure:
Inspection Report 05000335/2010009 w/ Attachment: Supplemental Information
__ ML103070200_________
X SUNSI REVIEW COMPLETE OFFICE RII:DRP RII:DRP RII:DRP RII:DRP HQ RII:DRP
SIGNATURE
/RA by E-mail/
/RA by E-mail/
/RA by E-mail/
/RA by E-mail/
/RA by E-mail/
/RA/
NAME SNinh TMorrissey AAlen JNadel KMartin DRich
DATE 10/19/2010 10/29/2010 10/19/2010 10/19/2010 10/19/2010 10/29/2010
E-MAIL COPY?
YES NO YES NO YES NO YES NO YES NO YES NO YES NO
REGION II==
Docket No.:
50-335
License No.:
Report No:
Licensee:
Florida Power & Light Company (FP&L)
Facility:
St. Lucie Nuclear Plant, Unit 1
Location:
Jensen Beach, FL 34957
Dates:
September 27 - September 30, 2010
Inspectors:
Thomas Morrissey, Senior Resident Inspector, Crystal River (Team Lead)
Son Ninh, Senior Project Engineer, Region II Alejandro Alen, Reactor Inspector, Region II Jared Nadel, Resident Inspector, Surry Kamishan, Martin, Human Factors Engineer, HQ
Approved by:
D. Rich, Chief, Reactor Projects Branch 3 Division of Reactor Projects
Enclosure
SUMMARY OF FINDINGS
Inspection Report (IR) 05000335/2010009; 9/27/2010-9/30/2010; St. Lucie Nuclear Plant, Unit 1; Supplemental Inspection - Inspection Procedure (IP) 95002.
This supplemental inspection was conducted by a senior resident inspector, a senior project engineer, a resident inspector, a reactor inspector and a human factors engineer. One Green non-cited violation (NCV) was identified. The significance of most findings is indicated by their color (i.e., Green, White, Yellow, or Red) using the NRC Inspection Manual Chapter (IMC) 0609,
"Significance Determination Process" (SDP). Findings for which the SDP does not apply may be Green or be assigned a severity level after NRC management review. The NRC's program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, "Reactor Oversight Process," Revision 4, dated December 2006.
Cornerstone: Mitigating Systems
The NRC staff performed this supplemental inspection in accordance with IP 95002, Inspection for One Degraded Cornerstone or any Three White Inputs in a Strategic Performance Area, to assess the licensees evaluation associated with air intrusion into Unit 1 component cooling water (CCW) system in 2008 and 2009. The NRC staff previously characterized this issue as having Yellow safety significance, as documented in NRC IR 05000335/2010007 and 05000389/2010007.
The inspectors determined that the St. Lucie staff performed a comprehensive evaluation of the subject Yellow finding associated with the CCW system air intrusion event. The St. Lucie staffs evaluation identified root causes of the issue to be: (1) decision making by the organization was insufficient due to inadequate knowledge and skills related to risk significant decisions, conservative assumptions and timely communication between departments, (2) the organization missed several opportunities to promptly identify, fully analyze and resolve in a timely manner the air intrusion event, (3) inadequate fleet/site procedures resulted in the failure to recognize the condition and significance of the event in a timely manner, (4) management did not effectively implement policies and procedures, which resulted in a reluctance to challenge issues and recognize the significance of the 2008 event and a repeat of the event in 2009, (5)less than adequate design of containment air compressor system resulted in recurrent air intrusion events, and (6) less than adequate maintenance resulted in a similar 2009 air intrusion event.
The inspectors determined that the root cause evaluations for the CCW system air intrusion events were thorough and broad in scope. The evaluation appropriately determined the root and contributing causes, addressed the extent of condition and extent of cause, determined if safety culture contributed to the issue, and established and scheduled corrective actions that were sufficient to address the causes and prevent recurrence of the air intrusion event.
The inspection team performed an independent extent of condition and extent of cause review and a focused review utilizing a safety culture expert as it related to the root cause evaluations.
Overall, the team concluded that the licensees root cause evaluation and corrective actions, completed and planned, were sufficient to prevent recurrence. The root cause evaluation appropriately considered safety culture. The team did not identify any concerns associated with the safety conscious work environment at St. Lucie.
As a result of the NRC conclusion that the licensee appropriately addressed the above issues, the Yellow finding associated with air intrusion into Unit 1 CCW system will be considered in assessing plant performance for a total of four quarters in accordance with the guidance in IMC 0305, Operating Reactor Assessment Program.
NRC-Identified
& Self-Revealing Findings
Cornerstone: Mitigating Systems
- Green.
The inspectors identified a non-cited violation of 10 CFR 50.65 (a)(2) for failure to demonstrate that the performance of the 2B Emergency Diesel Generator (EDG) and 1C Auxiliary Feedwater Pump (AFW) systems was effectively controlled by preventative maintenance (PM) such that these systems remained capable of performing their intended functions. The 2B EDG and the 1C AFW pump exceeded Maintenance Rule (a)(2) performance criteria since February 27 and May 30, 2010, respectively, and the goal setting and monitoring plans were not established as required by paragraph (a)(1)of the Maintenance Rule. This issue was entered into the licensees corrective action program as AR 581307581307
The finding was determined to be of greater than minor significance because it was associated with the Equipment Performance attribute of the Mitigating Systems Cornerstone, and adversely affected the cornerstone objective of ensuring availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. More specifically, the licensee failed to demonstrate that the performance of the 2B EDG and the 1C AFW pump was effectively controlled through appropriate PM. According to NRC Inspection Manual Chapter 0609, Attachment 4,
Phase I, Initial Screening and Characterization of Findings, this finding was determined to be of very low safety significance because it did not lead to an actual loss of a safety system function or screen as potentially risk significant due to a seismic, flooding, or severe weather initiating event. The cause of this finding was directly related to the cross-cutting aspect of Human Performance H.4(b) for the failure to follow the maintenance rule procedural requirements which resulted in the goal setting and monitoring plan not being established in a timely manner per 10 CFR part 50.65.
Licensee-Identified Violations
None
REPORT DETAILS
OTHER ACTIVITIES
4OA3 Follow-up of Events and Notices of Enforcement Discretion
(Discussed) Licensee Event Report (LER) 05000335/2010-001-00 Air Intrusion from 1A Containment Instrument Air Compressor into Unit 1 Component Cooling Water
This LER describes the 2008 St. Lucie Unit 1 component cooling water (CCW) air intrusion event that resulted in the NRC-identified Yellow inspection finding. During the review of the root cause evaluation (RCE) and the LER, the inspectors determined that the LER did not list all the reportability requirements that applied to this issue.
Additionally, the RCE documents that the air intrusion event resulted in the inoperability of both trains of CCW. The LER was not as conclusive with respect to operability. The inspectors discussed this issue with the licensee who agreed with a need for an LER revision. The licensee documented this issue in the corrective action program.
4OA4 Supplemental Inspection
.01 Inspection Scope
This supplemental inspection was conducted using Inspection Procedure (IP) 95002 to assess the licensees RCE associated with a Yellow inspection finding that resulted in a degraded mitigating systems cornerstone in the reactor safety strategic performance area. The inspection objectives were to:
- provide assurance that the root and contributing causes of risk-significant issues were understood;
- provide assurance that the extent of condition and extent of cause of risk-significant issues were identified and to independently assess the extent of condition and extent of cause of individual and collective risk-significant issues;
- independently determine if safety culture components caused or significantly contributed to the risk significant issues; and
- provide assurance that the licensees corrective actions for risk-significant issues were or will be sufficient to address the root and contributing causes and to preclude repetition.
The licensee entered the Degraded Cornerstone Column of the NRCs Action Matrix as described in NRC Inspection Manual Chapter (IMC) 0305, Operating Reactor Assessment Program, in the fourth quarter of 2009 as a result of one inspection finding of substantial safety significance (Yellow). The finding was associated with the failure to identify and correct a condition adverse to quality involving a CCW system air intrusion event that occurred in October 2008. This NRC identified finding was initially documented in NRC Component Design Basis Inspection (CDBI) inspection report (IR)05000335/2009006 and 05000389/2009006 as an apparent violation of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action. A Regulatory Conference was held with the licensee on February 19, 2010 to discuss the issue. The NRC determined the final significance to be Yellow as documented in NRC IR 05000335/2010007 and 05000389/2010007.
The licensee staff informed the NRC on April 28, 2010 that they were ready for the supplemental inspection. In preparation for the inspection, the licensee performed a root cause evaluation (action request 403656) to identify weaknesses that existed in various organizations which allowed air intrusion into the Unit 1 CCW system in 2008 and a less significant air intrusion event in 2009. The licensees root cause team was made up of experienced licensee employees, industry peers and root cause consultants.
The inspectors reviewed the licensees RCE in addition to other evaluations conducted in support and as a result of the RCE. The inspectors reviewed corrective actions that were taken or planned to address the identified causes. The inspectors held discussions with licensee personnel to ensure that the root and contributing causes and the contribution of safety culture components were understood and corrective actions taken or planned were appropriate to address the causes and preclude repetition. The inspectors also independently assessed the extent of condition and extent of cause of the identified issues. In addition, the inspectors performed an assessment of whether any safety culture components caused or significantly contributed to the issues. The team included an NRC safety culture expert.
.02 Evaluation of the Inspection Requirements
02.01 Problem Identification
a.
IP 95002 requires that the inspection staff determine that the licensees evaluation of the issue documents who identified the issue (i.e., licensee-identified, self-revealing, or NRC-identified) and the conditions under which the issue was identified
The inspectors verified the licensees RCE documented the issue as NRC-identified during the 2009 NRC Component Design Basis Inspection (CDBI) (NRC IR 05000335/2009006 and 05000389/2009006).
b.
IP 95002 requires that the inspection staff determine that the licensees evaluation of the issue documents how long the issue existed and prior opportunities for identification
The licensees RCE identified that the original Unit 1 CCW design was vulnerable to air intrusion that could result in the inoperability of both trains. This design has been in place since initial plant startup. The CCW system remained vulnerable to air intrusion until after the November 2009 air intrusion event when the makeup supply was isolated from the Unit 1 containment instrument air compressors. The licensee later installed a permanent modification on the makeup supply to provided double isolation with a tell tale vent valve in between. The RCE also documented the missed opportunities to use industry operating experience to identify the vulnerability of the Unit 1 CCW system to air intrusion.
c.
IP 95002 requires that the inspection staff determine that the licensees evaluation documents the plant specific risk consequences, as applicable, and compliance concerns associated with the issues both individually and collectively
The NRC determined this issue to be a Yellow finding as documented in NRC IR 05000335/2010007 and 05000389/2010007. The inspectors verified that the licensees evaluation documented the plant specific risk consequences. The RCE documented a conditional core damage probability between 1E-4 and 6E-4 which was consistent with the NRCs safety significance determination. The NRC inspectors did not identify any significant concerns with the licensees evaluation.
d. Findings
No findings were identified
02.02 Root Cause, Extent of Condition, and Extent of Cause Evaluation
a.
IP 95002 requires that the inspection staff determine that the licensee evaluated the issue using a systematic methodology to identify the root and contributing causes
The licensee used the following systematic methods to complete the RCE.
- event and causal factor charting;
- hazard-barrier-target analysis;
- management oversight and risk tree (MORT) analysis; and
- fault tree analysis.
The inspectors determined that the licensee evaluated the issue using systematic methodology to identify root and contributing causes.
b.
IP 95002 requires that the inspection staff determine that the licensees RCE was conducted to a level of detail commensurate with the significance of the issue
The licensees RCE included a broad timeline of events that extended back to original construction. The RCE utilized several systematic methods as discussed above to identify all root and contributing causes. Using a dedicated team of experienced licensee employees and industry experts, the licensee identified six root causes and four contributing causes. The inspectors concluded that the level of detail in the licensees RCE was appropriate for the safety significance of the issue.
c.
IP 95002 requires that the inspection staff determine that the licensees RCE included a consideration of prior occurrences of the issue and knowledge of Operating Experience (OE)
The licensees RCE included an evaluation of internal and external OE. The licensees review of the St. Lucie corrective action database did not find any issues associated with CCW system gas intrusion prior to the 2008 air intrusion event. The RCE included previous OE that was mainly focused on gas intrusion of emergency core cooling systems. The licensee recognized that the station failed to apply this information to vulnerable systems beyond those referenced in the OE. Based on the licensees detailed evaluation and conclusions, the inspectors determined that the licensees RCE included a consideration of prior occurrences of the problem and knowledge of prior OE.
d.
IP 95002 requires that the inspection staff determine that the licensees RCE addresses the extent of condition and extent of cause of the issues
The licensees RCE documented two conditions associated with the CCW air intrusion event that required an extent of condition review. One condition was related to the inadequate interface between safety related/non-safety related or risk/non-risk significant systems. The licensee has actions to assess the identified systems that include a gas/fluid interface to the acceptance criteria of Generic Letter 2008-01, Managing Gas Accumulation in Emergency Core Cooling, Decay Heat Removal, and Containment Spray Systems. The second condition is related to the inadequate corrective action screening for mid level condition reports. The licensee performed an independent review of station equipment issues documented in condition reports that were coded as significance level/investigating type 3C and 3D that were initiated over the last five years to verify they were coded correctly and were properly screened for operability. Condition reports issued over the previous year that were coded as 2C equipment related were also reviewed.
For each of the six root causes and four contributing causes the licensee performed an extent of cause review. The inspectors found that the corrective actions associated with each extent of cause were sufficiently broad to address the extent of cause.
The inspectors concluded that the licensees RCE addressed the extent of condition and the extent of cause of the issue.
e. Findings
No findings were identified
02.03 Corrective Actions
a.
IP 95002 requires that the inspection staff determine that
- (1) the licensee specified appropriate corrective actions for each root and/or contributing cause, or
- (2) an evaluation that states why no actions are necessary
After the 2009 CCW system air intrusion event, the licensee took actions to isolate the CCW makeup supply to the containment air compressor system to stop/prevent further air intrusion into the CCW system. The licensees RCE documented six root causes and four contributing causes for the CCW system air intrusion event. The inspectors reviewed completed and planned corrective actions for each root cause and contributing cause to determine whether they were specific, measurable, and timely. The inspectors did not identify any significant concerns with the licensees corrective actions.
b.
IP 95002 requires that the inspection staff determine that the licensee prioritized corrective actions with consideration of risk significance and regulatory compliance
After the 2009 CCW system air intrusion event, the licensee took immediate actions to isolate the CCW makeup supply to the containment air compressor system to stop/prevent further air intrusion into the CCW system. The inspectors reviewed the licensees schedule for completion of corrective action for each identified root and contributing cause and determined that the licensee appropriately prioritized corrective actions with consideration of risk significance and regulatory compliance.
c.
IP 95002 requires that the inspection staff determine that the licensee established a schedule for implementing and completing the corrective actions
The inspectors determined that all the corrective action specified in the RCE have either been completed or scheduled.
d.
IP 95002 requires that the inspection staff determine that the licensee developed quantitative and/or qualitative measures of success for determining the effectiveness of the corrective actions to preclude repetition
As documented in the RCE, the licensee established measures for determining the effectiveness of the corrective actions. These measures included the following:
- On a quarterly basis, Engineering will assess condition reports that identify gas intrusion events and present result to the management review committee (MRC) and corrective action review board (CARB).
- On a monthly basis, engineering performance improvement will assess completed operability screenings for quality and consistency with site expectations.
- On a monthly basis, fleet performance improvement will assess the quality of a sample of screened condition reports based on the requirements of the sites corrective action procedures.
- On a monthly basis, operations will assess the quality of operational decision making (ODM) documents.
- On a monthly basis, fleet performance improvement will attend issue screening team (IST)/MRC/CARB meetings to assess performance.
The licensee staff entered these action items into their corrective action program to ensure that these effectiveness reviews and enhanced monitoring would be performed.
The inspectors determined that quantitative and qualitative measures of success had been developed for determining the effectiveness of the corrective actions to preclude repetition.
e.
IP 95002 requires that the inspection staff determine that the licensees planned or completed corrective actions adequately address a Notice of Violation (NOV) that was the basis for the supplemental inspection, if applicable
The NRC staff issued an NOV to the licensee; however, the NRC has concluded that
information regarding the reason for the violation, the corrective actions taken and
planned to correct the violation and prevent recurrence and the date when full
compliance will be achieved is already adequately addressed on the docket in the
St. Lucie FPL 3 Meeting Summary, dated February 26, 2010 (ML100601170). This
inspection requirement was not applicable.
f. Findings
No findings were identified.
02.04 Independent Assessment of Extent of Condition and Extent of Cause
a. Inspection Scope
IP 95002 requires that the inspection staff perform a focused inspection to independently assess the validity of the licensees conclusions regarding the extent of condition and extent of cause of the issue. The objective of this requirement is to independently sample performance, as necessary, within the key attributes of the cornerstone that is related to the subject issue to ensure that the licensees evaluation regarding the extent of condition and extent of cause is sufficiently comprehensive.
The inspection team conducted an independent extent of condition and extent of cause review of the issues associated with the Yellow finding. The Yellow finding ultimately revealed significant and broad organizational issues associated with the stations commitment to achieving a high level of human performance with nuclear safety as the highest priority. The organization failed to recognize or understand the significance of the 2008 gas intrusion event and its impact to the CCW system. The RCE revealed inadequacies in operating, alarm response, maintenance, operability determination and corrective action procedures. The inspection teams independent review focused on the primary root causes associated with the yellow finding in addition to the licensees identified contributing causes that involved more specific aspects of the broader root causes.
The inspection team assessed whether the licensees extent of condition and extent of cause evaluations sufficiently identified and bounded all organizational issues. The team also assessed whether the licensees extent of condition and extent of cause evaluations sufficiently determined the actual extent of similar organizational issues that potentially existed in other station departments, programs, and processes.
In conducting this independent review, the inspection team interviewed station management and personnel, reviewed program and process documentation, and reviewed existing station program monitoring and improvement efforts, including review of corrective action documents. Based on the root and contributing causes identified by the licensee, the inspection team focused the review on the following attributes of the programs and processes:
- program and process expectations with regard to operability determinations to verify the determination was justified;
- maintenance program administration to identify equipment with a history of recurring problems and verification of appropriate corrective actions ;
- human performance with regard to work practices; and
- adequacy of licensee technical evaluation (corrective action program evaluations, engineering evaluations, operability determinations).
b.
Assessment
The inspection team determined that the licensee conducted a comprehensive extent of condition and extent of cause review that sufficiently identified most relevant areas. The team did not identify any substantive extent of condition and extent of cause issues that the licensee was not aware of and had not already identified with corrective action plans in place.
The inspectors reviewed several operability evaluations and, although no present operability concerns were identified, several examples of incomplete documentation of operability evaluations were identified. The teams observations below were discussed with the licensee and have been entered into the licensees corrective action program.
- The inspectors noted that a past operability determination associated with a 2B EDG air receiver leak (AR 00479521) focused on the leak rate affect on the air-start system capability to start the EDG and did not consider the affects of a seismic event on the structural integrity of the degraded air receiver. When the inspectors questioned the licensee, the licensee identified that a seismic event would have negligible effects on further propagating the current cracks due to the structural anchorage of the air receivers being at the bottom of the tank and that design basis earthquake loads were negligible compared with the tanks pressure forces. The inspectors agreed with the licensees evaluation. However, the inspectors noted that although seismic loads were negligible, seismic loads should have been included in the past operability determination.
- Inspectors found multiple examples over the last ten years, including several recent examples, where operability determinations for CCW system piping through wall leaks did not thoroughly document the basis for the operability conclusion. The inspectors noted that operability reports did not explain the appropriateness of the chosen volumetric non-destructive examination (NDE) utilized to determine structural integrity. Several operability determinations did not document the degradation mechanism or list the relevant site OE. Also, some operability determinations did not justify the use of non-safety, non-seismic make-up sources, including consideration of required manual actions and design basis events.
During the teams review of the licensees 10 CFR 50.65 (Maintenance Rule (MR))
program, the team identified two safety significant systems (2B emergency diesel generator (EDG) and 1C auxiliary feed water (AFW) pump) where goal setting and monitoring were not established as required by paragraph a(1) of 10 CFR 50.65 in a timely manner.
c. Findings
Introduction:
The inspectors identified a Green non-cited violation (NCV) of 10 CFR 50.65(a)(2) for failure to demonstrate that the 2B EDG and the 1C AFW pump performance was being effectively controlled through the preventative maintenance (PM)program, or to place the system in 10 CFR 50.65(a)(1) status due to increased EDG and AFW pump unavailability and maintenance rule functional failures, respectively, beyond the established performance criteria.
Description:
The inspectors reviewed condition reports (CRs) 2010-1510, 2010-10145, 2010-14355, and 2010-16485 associated with Unit 1 AFW pumps. These CRs documented 1C AFW valve MV-08-03 failed to open due to trip solenoid coil binding caused by corrosion on January 21, 2010, as a MR functional failure (MRFF) and a maintenance preventable functional failure (MPFF); Unit 1 AFW valve MV-09-11 failed to stroke open during electrical testing under 0-EMP-80.07 due to degradation of 72/C auxiliary contact on April 18, 2010, as a MRFF; Unit 1 AFW Valve MV-09-11 failed to close during performance of surveillance testing under 1-OSP-09.02C on May 30, 2010, as a MRFF and a MPFF. The inspectors determined that this was the third functional failure of the train which exceeded the reliability criteria of < 2 functional failures in an 18 month period. On June 25, 2010, 1C AFW pump failed to achieve normal operating speed during surveillance test 1-OSP-09.01C due to corrosion debris from atmospheric dump valve (ADV) operation interfering with governor valve operation. This was classified as a MRFF.
The inspectors also reviewed CRs 2010-5305 and 2010-16503 associated with 2B EDG.
The inspectors determined that 2B EDG exceeded unavailability criteria of 160 hours0.00185 days <br />0.0444 hours <br />2.645503e-4 weeks <br />6.088e-5 months <br /> on February 27, 2010 because the air receivers were found to be degraded and repairs took several days to declare the EDG back in service.
Procedure NAP-415, Maintenance Rule Program Administration, requires the licensee to monitor and measure the effectiveness of maintenance in accordance with 10 CFR 50.65. NAP-415, section 4.3.2, Unavailability Monitoring, states, in part, that the
Maintenance Rule Expert Panel (MREP) shall meet within 30 days of the identification of exceeding the unavailability performance criteria. When performance criteria are exceeded and a determination is made that the goal setting and monitoring are required, then either the CR is supplemented or a new CR is initiated, the MREP is notified, and the MR (a)(1) plan is prepared. The completed plan is then reviewed and approved by the MREP and concurrence is obtained from the Plant Manager. Completion of this process is required within 30 days from the initiation of the MR (a)(1) CR.
Section 4.3.3, Condition Monitoring of NAP-415, also states, in part, that the MREP should meet within ten
- (10) days of the identification of exceeding the condition monitoring performance criteria. In all cases, the MREP shall approve the evaluation within 30 days from designation of the CR as a MRFF exceeding the condition monitoring performance criteria.
The inspectors determined that the 2B EDG and the 1C AFW pump exceeded Maintenance Rule (a)(2) performance criteria since February 27 and May 30, 2010, respectively, and goal setting and monitoring plan were not established as required by paragraph a(1) of the Maintenance Rule in a timely manner. On August 24, 2010 in support of the IP 95002 inspection, the NRC requested a list and short description of systems that have been classified MR (a)(1) since 2008. During the course of fulfilling this request, the licensee identified that they had not had a MREP to review the above equipment issues. The MREP meeting was held on September 23, 2010 to approve these systems MR (a)(1)status. The development of the required goals and monitoring plan is in progress and expected to be completed by October 6, 2010. The licensee initiated AR 581307581307to document these issues.
Analysis:
The licensees failure to effectively monitor 2B EDG and 1C AFW pump unavailability and maintenance rule functional failures and to determine the impact on 10 CFR 50.65(a)(2) performance criteria was considered a performance deficiency. The performance deficiency was determined to be more than minor because it was associated with the Equipment Performance attribute of the Mitigating Systems Cornerstone and adversely affected the cornerstone objective of ensuring availability and reliability of systems designed to respond to initiating events to prevent undesirable consequences. More specifically, the licensee failed to demonstrate effective control of the 2B EDG and 1C AFW pump through appropriate PM. In accordance with NRC inspection manual chapter (IMC) 0609.04, Phase I - Initial Screening and Characterization of Findings, this finding was determined to be of very low safety significance (Green) because it did not lead to an actual loss of a system safety function or screen as potentially risk significant due to a seismic, flooding, or severe weather initiating event. The cause of this finding was directly related to the cross-cutting aspect of Human Performance H.4(b), work practices, for the failure to follow the maintenance rule procedural requirements which resulted in the goal setting and monitoring plan not being established in a timely manner per 10 CFR part 50.65.
Enforcement:
10 CFR 50.65, Requirements for monitoring the Effectiveness of Maintenance of Nuclear Power Plants, paragraph (a)(2) states, in part, that the monitoring specified in paragraph (a)(1) is not required where it has been demonstrated the performance or condition of a system, structures and components (SSC) is being effectively controlled through the performance of appropriate PM such that the SSC remain capable of performing its intended function. Paragraph (a)(1) requires, in part, that licensee shall monitor the performance or condition of SSC within the scope of the rule against licensee-established goals in a manner sufficient to provide reasonable assurance the SSC are capable of fulfilling their intended safety functions. Contrary to the above, on September 23, 2010, the licensee failed to demonstrate that the performance or condition of Unit 2 EDG and Unit 1 AFW systems had been effectively controlled through the conduct of appropriate scheduled PM without the approved goal setting and monitoring plan requirements specified in 10 CFR 50.65 paragraph (a)(1)being implemented. However, because this finding was of very low safety significance (Green) and has been entered in the licensees corrective action program as AR 581307581307 this violation is being treated as an NCV consistent with the NRC Enforcement Policy. This NCV is identified as 05000335, 389/2010009-01, Failure to adequately monitor performance of the 2B EDG and 1C AFW pump as required by 10 CFR 50.65.
02.05 Safety Culture Consideration
1. Safety Culture Component Evaluation
a. Inspection Scope
IP 95002 requires that the inspection team perform a focused inspection to independently determine that the licensees RCE appropriately considered whether any safety culture component caused or significantly contributed to any risk significant issue.
The inspection team reviewed condition reports, procedures and conducted interviews with licensee personnel to determine if the licensee properly considered whether any safety culture component caused or contributed to the issues. The team included a safety culture expert in conducting these interviews.
b.
Assessment
As part of the root cause evaluation for the issue, the licensee evaluated the identified root and contributing causes against the safety culture components that could have contributed to the issues. The licensees root cause evaluation included a discussion of the 13 safety culture components as described in Regulatory Issue Summary 2006-013, Information on the Changes Made to the Reactor Oversight Process to More Fully Address Safety Culture, (ADAMS Accession No. ML061880341) as they applied to the YELLOW CCW air intrusion event.
The inspection team independently confirmed that the licensees RCE appropriately identified safety culture components that contributed to the issues. For each of the identified prevalent and contributing safety culture components, the inspection team confirmed that the licensee established corrective actions to address the issues.
c. Findings
No findings of significance were identified.
2. To independently determine if safety culture components caused or significantly
contributed to the individual risk-significant performance issues
a. Inspection Scope
During the inspection, inspectors independently assessed the relationship between safety culture aspects and the Yellow finding through the use of focus groups and interviews as well as reviewing self-assessment documents provided by the licensee.
The inspectors interviewed a total of 69 individuals on site which included ten focus groups and 14 scheduled individual management interviews. Plant staff members interviewed were randomly selected from the Security, Operations, Radiation Protection, Chemistry, Maintenance, and Engineering organizations. Individuals involved in the root cause analysis of the event were also included. This included contractors as well as FPL employees.
As a result of the documents reviewed as part of the inspection, the focus groups and
interviews were designed to gather information on the safety culture of St. Lucie with
more questions asked concerning specific safety culture components. The questions
covered the following general areas:
Safety Conscious Work Environment Safety Policies Continuous Learning Environment Problem Identification and Resolution Human Performance and Organizational Change Management
The areas that were the target of questions during the inspection covered specifically the following topics:
Accountability Training Benchmarking Knowledge Transfer Decision Making Resources Work Control Work Practices Corrective Action Program (CAP)
b. Assessment
The inspectors did not identify concerns related to St. Lucies safety conscious work environment (SCWE). The inspectors determined that plant staff members felt they were personally responsible for nuclear safety and were comfortable in raising safety concerns to supervisors, management, and using the CAP. Individuals felt personally responsible for nuclear safety at the site and perceived the current management reinforced this message. Plant staff members were also well aware of the availability of alternate reporting channels including the Employee Concerns Program (ECP) and directly to the NRC. During the inspection, it was concluded that it is a common perception of plant staff that resource management limits various areas which affect safety culture throughout the organization. These areas include training, staffing resources, decision making, activities related to benchmarking with other sites, and maintenance activities. The overall view of the staff is that conditions in these areas are improving under the new management. The inspectors determined that work control and work practices have started to improve under new management specifically with the decision making process as it pertains to nuclear safety. Concerning the CAP, the inspectors determined that the changes to the root cause analysis process and apparent cause evaluation process, and prioritizing of the issues entered into the CAP program have been communicated effectively and that this is slowly improving the overall CAP process. The inspectors interviews with upper management showed that management was largely aware of the perceptions of the plant staff. Some plant staff voiced concerns with management communication of organizational changes and changes to staffing plans. Overall it was determined that the components of safety culture discussed above did contribute to the Yellow finding associated with the licensees failure to implement adequate corrective actions associated with the 2008 CCW air intrusion event.
c. Findings
No findings were identified.
02.06 Evaluation of IMC 0305 Criteria for Treatment of Old Design Issues
The licensee did not request credit for self-identification of an old design issue; therefore, the risk-significant issue was not evaluated against the IMC 0305 criteria for treatment of an old design issue.
4OA6 Exit Meeting
On October 1, 2010, the inspectors presented the inspection results to Mr. R. Anderson, Site Vice President, and other members of his staff, who acknowledged the findings. The inspectors confirmed that proprietary information was not retained after the inspection.
SUPPLEMENTAL INFORMATION
KEY POINTS OF CONTACT
Licensee Personnel
- R. Anderson, Site Vice President
- B. Hughes, Plant General Manager
- L. Nicholson, Director of Licensing
- M. Hicks, Site Excellent Team Director
- S. Duston, Training Manager
- M. Moore, Performance Improvement Manager
- E. Katzman, Licensing Manager
- J. Hamm, Engineering Manager
- M. Haskin, Maintenance Manager
- D. Huey, Work Control Manager
- R. Lingle, Operations Manager
- A. Day, Chemistry Manager
- C. Martin, Radiation Protection Manager
- J. Kramer, Safety Manager
- C. Nale, Fleet Corrective Action Coordinator
- K. Thompson, Mechanical Lead Engineer
- A. Roderick, Nuclear Engineering Supervisor
- P. Rasmus, Nuclear Operations Supervisor
- P. Barnes, Nuclear Engineering Supervisor
- M. Dryden, Licensing Supervisor
- D. Cecchett, Licensing Engineering
- A. Terezakis, Nuclear Operations Supervisor
- M. Bladek, Assistant Operations Manager
- M. Baughman, Training Supervisor
- K. Gatto, Mechanical Supervisor
- J. Schaffer, Nuclear Safety Culture Project Lead
- C. Buehrig, Maintenance Rule Expert Coordinator
- T. Sansers, Component Program Group Supervisor
- S. Gambill, System Engineering Electrical Supervisor
- P. Atkinson, BOP System Engineering Supervisor
NRC Personnel
- D. Rich, Chief, Branch 3, Division of Reactor Projects
LIST OF ITEMS
OPENED, CLOSED AND DISCUSSED
Open and
Closed
- 05000335, 389/2010009-01 NCV Failure to adequately monitor performance of
the 2B EDG and 1C AFW pump as required by 10
CFR 50.65 (Section 4OA4)
Closed
Failure to Identify and Correct a Condition Adverse to Quality (Section 4OA4)
Discussed
LER 2010-001-00
LER
Air Intrusion from 1A Containment Instrument Air Compressor into Unit 1 Component Cooling Water (Section 4OA3)