Suppls Response to 920413 Ltr Re Violations Noted in Insp Rept 50-335/92-04.Corrective Actions:Crew Boxes in Plant Will Be Inspected on Periodic Basis to Improve Probability That Flammable Liquids Properly Stored
ML17227A404
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 04/29/1992
From: GOLDBERG J H
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
L-92-125, NUDOCS 9205050009
Download: ML17227A404 (6)


Text

ACCELERATEDDISTRIBUTIONDEMONSTRATIONSYSTEMREGULATORYINFORMATIONDISTRIBUTIONSYSTEM(RIDS)ACESSIONNBR:9205050009DOC.DATE:92/04/29NOTARIZED:NOFACIL:50-335St.LuciePlant,Unit1,FloridaPower&LightCo.AUTH.NAME.AUTHORAFFILIATIONGOLDBERG,J.H.Florida,Power&LightCo.RECIP.NAMERECIPIENTAFFILIATIONDocumentControlBranch(DocumentControl'Desk)

SUBJECT: Supplsresponseto920413ltrreviolationsnotedinInspRept50-335/92-04.Correctiveactions:crewboxesinplantwillbeinspectedonperiodicbasistoimproveprobabilitythatflammableliquidsproperlystored.DISTRIBUTIONCODE:IEOIDCOPIES,RECEIVED:LTR1ENCLQSIZE:TITLE:General(50Dkt)-InspRept/NoticeofViolationResponseNOTES:DOCKETN05000335RDARECIPIENTIDCODE/NAMEPD2-2PDINTERNAL:ACRSAEOD/DEIIBDEDRONRR/DLPQ/LHFBPTNRR/DOEA/OEABNRR/DST/DIR8E2NUDOCS-ABSTRACTOGC/HDS3RGN2FILE01EXTERNAL:EG&G/BRYCE,J.H.NSICCOPIESLTTRENCL112211111.111111111111111RECIPIENTIDCODE/NAMENORRIS,JAEODAEOD/DSP/TPABNRRMORISSEAU,DNRR/DLPQ/LPEB10NRR/DREP/PEPB9HNRR/PMAS/ILRB12OEDIRREG"'2NRCPDRCOPIESLTTRENCL11111111111111111111DDDNOTETOALL"RIDS"RECIPIENTS:PLEASEHELPUSTOREDUCEiVASTE!CONTACTTHEDOCUMENTCONTROLDESK,ROOiIPl-37(EXT.20079)TOELlbIINATEYOURNAiv1EFROMDISTRIBUTIONLISTSFORDOCUMENTSYOUDON'TNEED!ALNUMBEROFCOPIESREQUIRED:LTTR23ENCL23DDS,

>t P.O.Box14000,JunoBeach,FL33408.0420FPLAPR291992L-92-12510CFR2-201U.S.NuclearRegulatoryCommissionAttn:DocumentControlDeskWashington,D.C.20555Re:St.LucieUnit1DocketNo.50-335ReplytoNoticeofViolationInsectionReort92-04-RevisedFloridaPowerandLightCompany(FPL)hassupplementedtheresponsetothesubjectinspectionreportsubmittedbyFPLletterL-92-99onApril13,1992.Theattachedreplacestheoriginalresponsetothenoticeofviolation.Verytrulyyours,tqjIJ.H.GoldbergPresident-NuclearDivisionJHG/JWH/kwAttachmentcc:StewartD.Ebneter,RegionalAdministrator,USNRCRegionIISeniorResidentInspector,USNRC,St.LuciePlantDAS/PSL4683-9292050500099c~04c~5'DRADOCK05000335PDR

-eRe:St.LucieUnit1'ocketNo.50-335ReplytoNoticeofViolationInsectionReort92-04-RevisedVIOLATION:Unit1TechnicalSpecifications(TS)6.8.1.frequiresthatwrittenproceduresshallbeestablished,implemented,andmaintainedcoveringfireprotectionprogramimplementation.ThisrequirementisimplementedinpartbyadministrativeprocedureAP0010434,Rev23,PlantFireProtectionGuidelines.AP0010434paragraph8.2.3listedthesafety-relatedareaswherecombustiblesmaybestored.Storageofcombustibles=inthecablespreadingroomswasnotincluded.Contrarytotheabove,onJanuary28,1992,twoplasticpintspraybottlesof91percentisopropylalcoholwereobservedstoredunattendedinanopencrewboxintheUnit1cablespreadingroom.Thesespraybottleshadattachedmaterialsafetydatasheetsnumbered"1552.500,1549"statingthatthematerialwasflammableandmustbetransferredtoasafetycanandstoredinaflame-proofcabinet.Whennotified,thelicenseeimmediatelyremovedtheealcoholtoanon-safety-relatedarea.IRESPONSE2.Thereasonfortheviolationwaspersonnelerror.Stepstakentocorrectthenon-compliance:a)Theflammablematerialwasimmediatelyremovedfromthecablespreadingroom,transferredtoasafetycan,.andstoredinaflame-proofcabinet.3~b)Allothercrewboxesandworkareaswereinspectedtoensureflammablematerialswereproperlystored.Thisinspectionrevealedseveraladditionalinstancesofimproperlystoredflammablematerial.Thesematerialswereremovedfromtheboxesandstoredasrequired.Stepstakentoavoidafurtherviolation:a)ThePlantFireProtectionDepartmentheldatrainingclassattheelectricalmaintenanceforeman/supervisormeetinginFebruary1992.Thetrainingsessionfocussedonthehandlingandstorageofflammableorcombustibleliquidsandtheplantchemicalcontrolprogram.AplantwideefforttoreachotheraffecteddepartmentswasperformedbytheFireProtectionDepartmenttoemphasizetheimportanceoffireprotectionrequirement ~:

Re:St.LucieUnit1DocketNo.50-335ReplytoNoticeofViolationInsectionReort92-04-Revisedb)c)d)Thiseventwillbediscussedatthenextelectricalmaintenancein-house-eventstrainingclass.'histrainingisscheduledforthesecondquarterof1992.Areainspectionworkdescriptionsnowincludeachecktoensurethatflammableliquidsarestoredinsafetycansandflame-proofcabinets.Plantwideemphasiswillbeplacedonchemicalcontrolthroughregularlyscheduledsafetymeetings.e)Crewboxesintheplantwillbeinspectedonaperiodicbasistoimprovetheprobabilitythatflammableliquidsareproperlystored.4.FullcompliancewasachievedonJanuary28,1992.