IR 05000335/1990023

From kanterella
Jump to navigation Jump to search
Corrects 901121 Response to Violations Noted in Insp Repts 50-335/90-23 & 50-389/90-23.Corrective Actions Re Maint Personnel Training on Revised Matl Control Procedures Will Be Completed by 910228
ML17223B044
Person / Time
Site: Saint Lucie  
Issue date: 12/20/1990
From: SAGER D A
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
L-90-455, NUDOCS 9101040001
Preceding documents:
Download: ML17223B044 (7)


Text

ACCELERATEDDISTRIBUTIONDEMONSTRATIONSYSTEMREGULATORYINFORMATIONDISTRIBUTIONSYSTEM(RIDS)'CESSIONNBR:9101040001DOC.DATE:90/12/20NOTARIZED:NOFACIL:50-335St.LuciePlant,Unit1,FloridaPower&LightCo.50-389St.LuciePlant,Unit2,FloridaPower&LightCo.AUTH.NAMEAUTHORAFFILIATIONSAGER,D.A.FloridaPower&LightCo.RECIP.NAMERECIPIENTAFFILIATIONDocumentControlBranch(DocumentControlDesk)

SUBJECT: Corrects901121responsetoviolationsnotedinInspRepts50-335/90-23&50-389/90-23.Correctiveactionsremaintpersonneltrainingonrevisedmatlcontrolprocedureswillbecompletedby910228.DISTRIBUTIONCODE:IE01DCOPIESRECEIVED:LTRENCLSIZE:TITLE:General(50Dkt)-InspRept/NoticeofVioationResponseNOTES:DOCKET0500033505000389RECIPIENTIDCODE/NAMEPD2-2PDINTERNAL:ACRSAEOD/DEIIBDEDRONRRSHANKMAN,SNRR/DOEA/OEABNRR/DRIS/DXRNRR/PMAS/ILRB120$JDI=R~LE02EXTERNALEG&G/BRYCEiJH~NSXCCOPIESLTTRENCL112211111111111111111111RECIPIENTIDCODE/NAMENORRIS,JAEODAEOD/TPABNRRMORISSEAU,DNRR/DLPQ/LPEB10NRR/DREP/PEPB9DNRR/DST/DIR8E2NUDOCS-ABSTRACTOGC/HDS2RGN2FILE01NRCPDRCOPIESLTTRENCL1111111111111111111111NOTETOALL"RIDS"RECIPIENTSPLEASEHELPUSTOREDUCEWASTE!CONTACTTHEDOCUMENTCONTROLDESK,ROOMPl-37(EXT.20079)TOELIMINATEYOURNAMEFROMDISTRIBUTIONLISTSFORDOCUMENTSYOUDON'TNEEDI'OTALNUMBEROFCOPIESREQUIRED:LTTR24ENCL24 P.O.Box128,Ft.Pierce,FL34954-0128December20,1990L-90-45510CFR2.201U.S.NuclearRegulatoryCommissionAttn:DocumentControlDeskWashington,D.C.20555Gentlemen:Re:St.LucieUnitNos.1and2DocketNos.50-335&50-389CorrectionofTypographicalErrorintheResponsetoNoticeofViolationInsectionReort.90-23FloridaPowerandLightCompanyhasidentifiedatypographicalerrorintheresponsetothesubjectviolationsubmittedbyFPLletterL-90-392onNovember21,1990.Theletterincorrectlystatedinsection5.eoftheresponsethat.correctiveaction4.b.(3)wouldbecompletebyFebruary28,1990.ThecorrectiveactionstatementshouldhavereadtheactionwillbecompletebyFebruary28,1991.Attachedpleasefindacorrectedresponse.Verytrulyyours,D.AViceageresident,St.LuciePlantDAS/GRN/kwAttachmentcc:StewartD.Ebneter,RegionalAdministrator,USNRCRegionIISeniorResidentInspector,USNRC,St.LuciePlantDAS/PSLN3119101040001901220PDRADOCK05000335QPDRanFPLGroupcompanyIb)/p

ATTACHMENTRESPONSETONOTICEOFVIOLATION0FINDING010CFR50,AppendixB,CriterionV,Instructions,Procedures,andDrawings,asimplementedbyapprovedFPLTopicalQualityAssuranceReportTQAR1-76ARev.15,TQR5.0,Instructions,Procedures,andDrawings,andfurtherimplementedbyTQARAppendixCcommitmenttoANSIN18-7,1976,paragraph5.2.7,MaintenanceandModifications,requirethatmaintenanceormodificationswhichmayeffectfunctioningofsafety-relatedstructures,systems,orcomponentsshallbeperformedinamannertoensurequalityatleastequivalenttothatspecifiedinoriginaldesignbasesandrequirements,materialsspecifications,andinspectionrequirements.10CFR50,AppendixB,CriterionVIII,IdentificationandControlofMaterials,PartsandComponents,asimplementedbyapprovedFPLTopicalQualityAssuranceReport1-76A,Rev15,TQR8.0,IdentificationandControlofMaterials,Parts,andComponents,requiresthatmeasuresbedesignedtopreventtheuseofincorrectmaterials,partsorcomponents.ThisisfurtherimplementedonsitebyprocedureQI-PR/PSL-8.1,Rev11,IdentificationControlofMaterials,Parts,andComponents.Contrarytotheabove,inthetwosafety-relatedrepairexamplescitedbelow,thelicenseefailedtocontrolmaterialandensurequalityatleastequivalenttothatspecifiedinoriginaldesignbasesandrequirements,materialsspecifications,andinspectionrequirementsinthat:1~TheequipmentmanualfortheReactorProtectionSystemchannel"C"cabinetfailedtospecifyapprovedreplacementwirematerial.Asaresult,onAugust21,1990,non-authorizedwirematerialwasinstalledintheUnit2cabinetduringthereplacementofthereactorcoolantpumpmodeselectorswitch.Thelicenseedidnotestablishqualificationbyothermeans.2~OnAugust24,1990,anon-authorizedsealantwasusedona1AComponentCoolingWater(CCW)pumpshaftmechanicalsealleak.Theunapprovedsealantwasappliedtothejointafteran"0"ringatthesealretainingcollarwascompressed,causingaminorleakatthecollar-to-pumpcasingjoint."0"ringreplacementwouldhaverequiredpartialpumpdisassembly.Ineachinstance,subsequentengineeringevaluationwasrequestedafterrepaircompletionandNRCinquiry.Theseevaluationsconcludedthattherepairswereacceptable,butthiswasnotknownatthetimeoftherepair.TheCCWsystemwasinoperationduringtheevaluationbuttheRPSchannelremainedoutofserviceuntilauthorizedmaterialwasobtainedandinstalle ATTACHMENTPage2of3RESPONSEi1~FloridaPowerandLightCompany(FPL)concurswiththeviolation.2~3~Thereasonfortheviolationwaspersonnelerrorcoupledwithinadequateprocedure.Thefollowingactionsweretakentocorrectthespecificitemsofnoncompliance:a.Theimproperwirewasreplacedwithvendorrecommendedwire.4~b.ThesealantusedontheComponentCoolingWaterPumpwasevaluatedbyFPLEngineeringanddeterminedtobeacceptableforuse.Thefollowingcorrectiveactionshavebeenorwillbeimplemented:a~InterimMeasures:b.Untiltheprocedurechangescanbemadeandtrainingconductedthefollowinginterimmeasureswillbeimplemented:(1)TheMaintenanceSuperintendenthasissuedaletterdescribingtherequirementsformaterialcontrol.Allpartsormaterialusedinsafety-relatedcomponentrepairswillbeverifiedtoconformtorequirements(i.e.TechnicalManuals,drawings,procedures,procurementspecifications,orstoresmaterialidentificationsheets).IfmaterialcannotbeverifiedworkwillbestoppeduntilawrittenEngineeringdispositionisreceived.(2)TheseinstructionswillbereviewedwithallMaintenancePersonneltoensurecompliance.ProgramCorrections:(1)Theworkcontrolprocedurewillberevisedtoprovidethedetailtoproperlyimplementtheplantqualityinstruct'ons.(2)Ourprogramstocontrolchemicalsandconsumablematerialswillbereviewedandrevisedasnecessary.(3)TrainingwillbeheldforallMaintenancePersonnelontherevisedmaterialcontrolprocedure ATTACHMENTPage3of35.Correctiveactionstatus.a~b.Correctiveactions3.a.and3.b.werecompletedbeforetheendoftheinspectionperiod.Correctiveaction4.a.willbecompletebyNovember30,1990.c~d.Correctiveaction4.b.(1)willbecompletedbyDecember31,1990.CorrectiveAction4.b.(2)willbecompletebyJanuary31,1991.e.CorrectiveAction4.b.(3)willbecompletebyFebruary28,199 tlII