IR 05000219/2002011

From kanterella
Jump to navigation Jump to search
IR 05000219-02-011; on 12/16/2002 - 1/10/2003; Oyster Creek Nuclear Generating Station; Triennial Fire Protection Inspection Report
ML030240554
Person / Time
Site: Oyster Creek
Issue date: 01/24/2003
From: Linville J
Division of Reactor Safety III
To: Skolds J
AmerGen Energy Co
References
-RFPFR, FOIA/PA-2003-0358 IR-02-011
Download: ML030240554 (23)


Text

ary 24, 2003

SUBJECT:

OYSTER CREEK NUCLEAR GENERATING STATION - TRIENNIAL FIRE PROTECTION INSPECTION REPORT 50-219/02-011

Dear Mr. Skolds:

On January 10, 2003, the NRC completed a triennial fire protection inspection at your Oyster Creek Nuclear Generating Station. The enclosed report documents the inspection findings that were discussed on January 10, 2003, with Mr. E. Harkness and other members of your staff.

This inspection examined activities conducted under your license as they relate to safety and compliance with the Commissions rules and regulations, and with the conditions of your license. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel.

No findings of significance were identified.

In accordance with 10 CFR 2.790 of the NRCs Rules of Practice, a copy of this letter and its enclosure will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARs) component of NRCs document system (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

We appreciate your cooperation. Please contact me at (610) 337-5129, if you have any questions regarding this letter.

Sincerely,

/RA/

James C. Linville, Chief Electrical Branch Division of Reactor Safety Docket No: 50-219 License No: DPR-16

Mr. John Enclosure: NRC Inspection Report 50-219/02-011 cc w/encl:

AmerGen Energy Company - Correspondence Control Deck Vice President - Oyster Creek Licensing - Vice President, Exelon Corporation Director-Licensing Manager, Regulatory Assurance New England Coalition Staff BNE Manager, State of New Jersey N. Cohen, Coordinator - Unplug Salem Campaign E. Gbur, Coordinator - Jersey Shore Nuclear Watch E. Zobian, Coordinator - Jersey Shore Anti Nuclear Alliance

Mr. John