aj Progress Energy Serial: HNP-03-067 JUN 1 2 2003 United States Nuclear Regulatory Commission ATTENTION: Document Control Desk Washington, DC 20555 SHEARON HARRIS NUCLEAR POWER PLANT DOCKET NO. 50-400/LICENSE NO. NPF-63 MONTHLY OPERATING REPORT

Dear Sir or Madam:

In accordance with Technical Specification 6.9.1.5 for Progress Energy Carolinas, Inc's (alternately known as Carolina Power and Light Co.) Harris Nuclear Plant, the report of operating statistics and shutdown experience for the month of May 2003 is provided.

Sincerely, John R. Caves Supervisor, Licensing and Regulatory Programs Harris Nuclear Plant SGR/sgr Enclosure c:

Mr. J. B. Brady (NRC Senior Resident Inspector, HNP)

Mr. L. A. Reyes (NRC Regional Administrator, Region II)

Mr. C. P. Patel (NRC Project Manager, HNP)

Progress Energy Carolinas, Inc.

Harris Nuclear Plant P.O. Box 165 New Hill, NC 27562

OG 

United States Nuclear Regulatory Commission Page 2 bc:

Mr. Tom C. Bell Mr. Stephen Carr Mr. W. F. Conway Mr. G. W. Davis Mr. R. J. Duncan II Mr. K. N. Haffis Mr. C. S. Hinnant Mr. H. L. James Mr. R. D. Martin Mr. T. C. Morton Mr. W. S. Orser Mr. J. Scarola Mr. J. M. Taylor Mr. B. C. Waldrep Mr. W. G. Wendland (American Nuclear Insurers)

Licensing Files (2)

Nuclear Records

Enclosure to Serial HNP-03-067 Page 1 of 3 OPERATING DATA REPORT DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE 050 400 Shearon Harris Nuclear Power Plant June 5, 2003 Charles L. George (919) 362-2937 REPORTING PERIOD

1. Design Electrical Rating:

(MWe-Net)

2.

Maximum Dependable Capacity:

(MWe-Net)

3. Number of Hours the Reactor Was Critical:
4.

Number of Hours the Generator Was On Line:

5.

Unit Reserve Shutdown Hours:

6.

Net Electrical Energy (MWH):

May 2003 (Month/Year)

MONTH 941.7 900.0 322.3 270.2 0.0 YEAR TO DATE N/A N/A 3,081.4 3,029.3 0.0 CUMULATIVE N/A N/A 121,060.5 119,978.2 0.0 2,768,458.0 101,330,971.0 200,220.0

Enclosure to Serial HNP-03-067 Page 2 of 3 DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE II APPENDIX B UNIT SHUTDOWNS 050400 Shearon Harris Ndclear Power Plant June 5, 2003 Charles L. George (919) 362-2937 REPORTING PERIOD May 2003 (Month/Year)

TYPE METHOD OF DATE F: FORCED DURATION SHUTrING CAUSE/CORRECTIVE ACTIONS NO.

(yymmdd)

S: SCHEDULED (HOURS)

REASON (1)

DOWN (2)

COMMENTS03-001 030426 S

423.1 C.

1 Shutdown for scheduled refueling outage.03-002 030518 F

34.3 A

3 Automatic Turbine/Reactor trip during startup.

Investigation determined that the turbine trip was caused by a failed turbine speed sensor. Corrective maintenance was performed and the unit was returned

.to service.03-003 030520 F

16.4 A

2 Mahual Reactor trip during startup due to a loss of Feedwater supply. The event was initiated by a failed intdrnal oil pump in the fluid speed coupling of the A-Condensate Booster Pump, which tripped the A-Main Feed Pump. The failed fluid speed coupling was replaced and the unit returned to service.

Enclosure to Serial HNP-03-067 Page 3 of 3

SUMMARY

The unit was shutdown for most hf the reporting period for a planned refueling outage. While starting up from the outage, the plant experienced two plant trips. The first event was an automatic Turbine/Reactor trip caused by failure of the Main Turbine speed sensor. The second event was a manual reactor trip that was initiated due to a loss of the operating Feedwater train. Failure of the A-Condensate Booster Pump tripped the A-Main Feed Pump, resulting in a loss of makeup to the Steam Generators.

(1) Reason:

A - Equipment Failure (Explain)

B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training/License Examination F - Administrative G - Operational Error (Explain)

H - Other (Explain)

(2) Method:

1 - Manudl 2 - Manual Trip/Scram 3 - Autornatic Trip/Scram 4 - Continuation 5 - Other (Explain)