ENS 53961
ENS Event | |
|---|---|
18:50 Mar 28, 2019 | |
| Title | Unusual Event Declared Due to Rcs Unidentified Leakage |
| Event Description | At 1450 EDT on March 28, 2019, the licensee observed that the Unit 1 unidentified Reactor Coolant System (RCS) leakage was greater than 10 gallons per minute (gpm) for greater than or equal to 15 minutes. The licensee declared an Unusual Event in accordance with their EAL SU 5.1. The licensee initiated a unit shutdown in accordance with their procedures and the unit was approximately 58 percent reactor power at 1507 EDT, with unit shutdown in progress. The licensee also received an alarm due to increasing Drywell Pressure at 1.7 pounds drywell pressure.
At 1600 EDT the licensee called with an update. Unit 1 was still in an Unusual Event with the unit at 37 percent power with the shutdown continuing. Drywell Pressure had decreased to 0.8 pounds. At 1603 the licensee scrammed Unit 1. Notified DHS SWO, FEMA Operations Center, DHS NICC, FEMA NWC (email), DHS Nuclear SSA (email), and FEMA NRCC SASC (email).
At 1437 EDT on March 28, 2019, with Unit 1 in Mode 1 at approximately 100 percent power, a Technical Specification-required shutdown was initiated due to indication of a leak in the drywell. Technical Specification Action 3.4.4.A, Unidentified Reactor Coolant System (RCS) leakage increase not within limit, requires RCS leakage to be reduced to within limits within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. It is expected that the leakage would not have been reduced to within limits within the required Technical Specification completion time; therefore, this event is being reported in accordance with 10 CFR 50.72(b)(2)(i). There was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified.
At 0259 EDT on March 29, 2019, the Unusual Event was terminated because RCS leakage was reduced to less than 10 gallons per minute. The most recent leakage rate measured at 0225 EDT was 3.9 gpm. The source of the leak will be identified when plant conditions allow containment entry. No elevated radiation levels were observed during this event. Drywell pressure is currently 0.0 psig. Unit 1 is in Mode 4. The licensee notified the NRC Resident Inspector. Notified R2DO (Bonser), NRR EO (Miller), IRD MOC (Grant), DHS SWO, FEMA Operations Center, DHS NICC, FEMA NWC (email), DHS Nuclear SSA (email), and FEMA NRCC SASC (email). |
| Where | |
|---|---|
| Brunswick North Carolina (NRC Region 2) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown | |
| Time - Person (Reporting Time:+-3.72 h-0.155 days <br />-0.0221 weeks <br />-0.0051 months <br />) | |
| Opened: | Derek Watson 15:07 Mar 28, 2019 |
| NRC Officer: | Jeff Herrera |
| Last Updated: | Mar 29, 2019 |
| 53961 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (58 %) |
Brunswick | |
WEEKMONTHYEARENS 573222024-09-16T16:40:00016 September 2024 16:40:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Site Access Impeded ENS 567972023-10-16T02:56:00016 October 2023 02:56:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Fire Not Verified to Be Extinguished within 15 Minutes ENS 548122020-08-04T03:12:0004 August 2020 03:12:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to a Loss of Offsite Power ENS 546032020-03-24T16:05:00024 March 2020 16:05:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification-Required Shutdown Due to Unidentified Leakage ENS 540522019-05-07T02:04:0007 May 2019 02:04:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Noue Due to Fire Lasting Longer than 15 Minutes in Turbine Building ENS 539612019-03-28T18:50:00028 March 2019 18:50:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Unusual Event Declared Due to Rcs Unidentified Leakage ENS 536092018-09-15T04:00:00015 September 2018 04:00:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration En Revision Imported Date 9/19/2018 ENS 520822016-07-13T00:39:00013 July 2016 00:39:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Alert Declared for a Fire in the Service Water Building ENS 517152016-02-07T18:26:0007 February 2016 18:26:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Scram and Alert Declaration Due to Electrical Fault Resulting in Fire/Explosion ENS 507512015-01-22T23:13:00022 January 2015 23:13:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Declared Due to Toxic Gas in the Security Diesel Building ENS 503552014-08-12T08:32:00012 August 2014 08:32:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Unusual Event for a Halon Release Near the Tsc and Eof ENS 497882014-02-03T15:03:0003 February 2014 15:03:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Toxic Gas Release That Could Affect Normal Operation ENS 497132014-01-11T00:48:00011 January 2014 00:48:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Explosion within Protected Area Boundary ENS 488902013-04-05T10:24:0005 April 2013 10:24:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to a Fire Alarm in the Stack Filter House ENS 487832013-02-26T14:00:00026 February 2013 14:00:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Toxic Gas Leak ENS 476872012-02-23T01:14:00023 February 2012 01:14:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Inoperability of Emergency Core Cooling Systems ENS 474442011-11-16T08:01:00016 November 2011 08:01:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Drywell Leakage Greater than 10 Gpm ENS 468732011-05-23T19:35:00023 May 2011 19:35:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Alert Declared Due to Halon Discharge in Emergency Diesel Generator Building ENS 459802010-06-06T15:37:0006 June 2010 15:37:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Brunswick Declared Alert Due to Halon Discharge in Emergency Diesel Generator Building ENS 457962010-03-27T02:45:00027 March 2010 02:45:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Dut to Fire Greater than 15 Minutes in Turbine Building ENS 457112010-02-19T16:11:00019 February 2010 16:11:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unsual Event Due to Carbon Dioxide Discharge in the High Pressure Coolant Injection (Hpci) Room ENS 453682009-09-20T18:00:00020 September 2009 18:00:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Inoperability of Diesel Generator ENS 432692007-04-01T14:45:0001 April 2007 14:45:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Tech Spec Required Shutdown Due to Edg Inoperability ENS 429602006-11-02T23:53:0002 November 2006 23:53:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Shutdown ENS 429552006-11-01T23:37:0001 November 2006 23:37:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge Unit 2 Declared an Unusual Event Due to Loss of Offsite Power to the 4Kv Emergency Buses ENS 419832005-09-13T03:14:00013 September 2005 03:14:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hurricane Ophelia Warning ENS 418952005-08-05T22:40:0005 August 2005 22:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Inoperability of All Emergency Diesel Generators ENS 416922005-05-12T08:11:00012 May 2005 08:11:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown, 10 CFR 50.73(a)(1), Submit an LER Technical Specification Required Shutdown Due to Loss of Emergency Bus E1 ENS 409532004-08-14T17:08:00014 August 2004 17:08:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event Emergency Declared Due to Loss of Offsite Power ENS 409512004-08-13T22:20:00013 August 2004 22:20:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event Declared Due to Hurricane Warning ENS 409052004-07-29T13:42:00029 July 2004 13:42:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Plant Entered Lco Action Statement Due to Malfunction of a Suppression Chamber-To-Drywell Vacuum Breaker. ENS 401642003-09-17T02:40:00017 September 2003 02:40:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event at Brunswick Due to Hurricane Warning 2024-09-16T16:40:00 | |