ENS 53331
ENS Event | |
|---|---|
23:00 Apr 12, 2018 | |
| Title | Potentially Degraded Items Relied on for Safety |
| Event Description | GNF-A's [Global Nuclear Fuels - Americas] Fuel Manufacturing Operation maintains a safe geometry Radwaste accumulation tank to receive certain liquid discharges from operations. During the annual shutdown work activities and routine inspections, an accumulation of material was identified in a safe geometry Radwaste accumulation tank.
The accumulation appears to have occurred due to reduced recirculation flow, an engineered feature that mixes the contents of the tank as part of a density control. The accumulation of material is an indication that the tank density control had degraded. Plant operations attempted to remove and quantify the material per normal requirements. On 4/12/18 at approximately 1900 [EDT], GNF-A determined that the material could not be quantified in a timely manner. In the absence of quantification, GNF-A has conservatively determined that this condition is a failure to meet performance requirements and is therefore reporting it within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of discovery pursuant to Part 70 Appendix A (b)(2). Additional controls on the tank geometry remained intact and at no time was an unsafe condition present. In addition, there are no sources that could result in a rapid addition of uranium to the system. Additional corrective actions, extent of condition, and extent of cause are being investigated. The licensee will be notifying their NRC Program Manager (Vukovinsky), the Radiation Protection Section at North Carolina Department of Health and Human Services, and Hanover County Emergency Management Agency. |
| Where | |
|---|---|
| Global Nuclear Fuel Wilmington, North Carolina (NRC Region 2) | |
| License number: | SNM-1097 |
| Reporting | |
| Part 70 App A (B)(2) | |
| Time - Person (Reporting Time:+16 h0.667 days <br />0.0952 weeks <br />0.0219 months <br />) | |
| Opened: | Scott Murray 15:00 Apr 13, 2018 |
| NRC Officer: | Howie Crouch |
| Last Updated: | Apr 13, 2018 |
| 53331 - NRC Website
Loading map... | |
Global Nuclear Fuel with Part 70 App A (B)(2) | |
WEEKMONTHYEARENS 562562022-12-02T20:30:0002 December 2022 20:30:00
[Table view]Part 70 App A (B)(2) Fuel Cycle Facility - Loss or Degradation of Safety Items ENS 533312018-04-12T23:00:00012 April 2018 23:00:00 Part 70 App A (B)(2) Potentially Degraded Items Relied on for Safety ENS 522512016-09-19T10:00:00019 September 2016 10:00:00 Part 70 App A (B)(2) Uf6 Scrubber Exhaust System Not Operating as Required ENS 516622016-01-19T02:00:00019 January 2016 02:00:00 Part 70 App A (B)(2) Accumulation of Uranium Oxide Powder in the Dry Scrap Recycle Furnace Off-Gas System ENS 499692014-03-28T17:30:00028 March 2014 17:30:00 Part 70 App A (B)(2), Part 70 App A (A)(4) Items Relied on for Safety Not Operable ENS 480382012-06-19T21:00:00019 June 2012 21:00:00 Part 70 App A (B)(2) Degradation of Safety Equipment ENS 480572012-02-13T13:20:00013 February 2012 13:20:00 Part 70 App A (B)(2) Mass Control Limit Exceeded ENS 466692011-03-10T14:15:00010 March 2011 14:15:00 Part 70 App A (B)(2) Malfunctioning Valve Leads to a Loss of Defense in Depth ENS 464862010-12-16T15:44:00016 December 2010 15:44:00 Part 70 App A (B)(2) Both Hf Detectors in Ghs Test Loop Failed to Be Available and Operable ENS 462442010-09-10T14:00:00010 September 2010 14:00:00 Part 70 App A (B)(2) Degradation of Safety Equipment ENS 461682010-01-25T13:50:00025 January 2010 13:50:00 Part 70 App A (B)(2) Degradation of an Item Relied on for Safety ENS 436372007-09-12T15:30:00012 September 2007 15:30:00 Part 70 App A (B)(2) Moderation Control Item Relied on for Safety Degradation 2022-12-02T20:30:00 | |