While performing a review of industry
OE [operating experience] concerning unfused ammeter circuits on station batteries, it was discovered that the ammeter circuits for all of the non-1E batteries are of a similar design to that described in the
OE. Also, while reviewing additional
DC circuits, it was discovered that the control circuit for the Turbine Generator Emergency
Lube Oil pump is unfused, protected only by the motor circuit breaker with a trip setting of 350 amps. The concern is that under the fire
safe shutdown rules it is postulated that a fire in one fire area can damage these circuits and cause short circuits without protection that would overheat the cables and possibly result in secondary fires in other fire areas where the cables are routed. The secondary fires could adversely affect
safe shutdown equipment and potentially cause the loss of the ability to conduct a
safe shutdown as required by
10CFR50 Appendix R. This condition is being reported in accordance with 10 CFR 50.72(b)(3)(ii)(B) as an
unanalyzed condition that significantly degrades plant safety.
Compensatory measures (fire watches) have been implemented for affected areas of the plant.
The NRC Resident Inspector has been notified.