ENS 45238
ENS Event | |
|---|---|
02:08 Jul 31, 2009 | |
| Title | Unusual Event Declared Due to a Loss of Offsite Power for Greater than 15 Minutes |
| Event Description | Unit 2 automatically tripped from 100% reactor power as a result of the over-current trip of the 2C Reactor Coolant Pump. Both station auxiliary transformers on Unit 2 subsequently tripped offline. All control rods fully inserted on the trip. Auxiliary feedwater auto-started and maintained Steam Generator water level. The unit is stable in Mode 3. The Emergency Diesel Generators auto started and loaded supplying both emergency busses with power. All systems functioned as required. There was no affect on Unit 1.
The licensee notified the NRC Resident Inspector.
At 2059 on July 30, 2009, a reactor trip of Unit 2 at Braidwood occurred. A loss of offsite power occurred and an Unusual Event was declared at 2108. NRC Headquarter Operations was notified at 2155 (ENS call # 45238). Power from System Auxiliary Transformer (SAT) (credited offsite power supply) 242-2 was restored to buses 241 and 242 (safety related buses) at 0036 on August 2, 2009. The Unusual Event was terminated at 0036 on August 2, 2009. This call is being made due to the termination of the Unusual Event declared on July 30, 2009. An Event Summary Report is required by Exelon procedures within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of termination of the Unusual Event and will be communicated to the Headquarter Operations later today. The initial event was the result of the actuation of the SAT sudden pressure relay. When the transformer tripped, a slow automatic bus transfer resulted. When the RCPs [Reactor Coolant Pump] and condensate pumps were reenergized, they tripped on overcurrent causing the reactor trip. The sudden pressure relay has subsequently tripped during testing and may have caused the initial event. The licensee reported no damage to the plant. The licensee notified the NRC Resident Inspector. Notified the R3DO (Daley), IRD (McDermott), NRR (Howe), DHS (An), and FEMA (Biscoe).
The Event Summary Report was received and documented the following technical conclusions: The Unusual Event declaration was caused by a sudden pressure relay on SAT 242-1 causing a lockout of both SATs followed by a trip of Unit 2 due to the 2C RCP tripping during the automatic bus transfer for bus 258. This led to a loss of offsite power to Unit 2. It is currently unknown why the sudden pressure relay on SAT 242-1 actuated. Troubleshooting on the sudden pressure relay is in progress. The licensee will notify the NRC Resident Inspector. Notified the R3DO (Daley). Notified the IRD (McDermott) and NRR (Howe) via e-mail. |
| Where | |
|---|---|
| Braidwood Illinois (NRC Region 3) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
| Time - Person (Reporting Time:+-3.22 h-0.134 days <br />-0.0192 weeks <br />-0.00441 months <br />) | |
| Opened: | David Braglia 22:55 Jul 30, 2009 |
| NRC Officer: | Vince Klco |
| Last Updated: | Aug 2, 2009 |
| 45238 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | A/R |
| Before | Power Operation (100 %) |
| After | Hot Standby (0 %) |
Braidwood | |
WEEKMONTHYEARENS 578392025-07-30T17:30:00030 July 2025 17:30:00
[Table view]10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 571072024-05-05T08:38:0005 May 2024 08:38:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Lowering Steam Generator Water Level ENS 553202021-06-21T05:51:00021 June 2021 05:51:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Trip on Generator Lockout Relay Trip ENS 542892019-09-23T16:06:00023 September 2019 16:06:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Lowering Steam Generator Levels ENS 534432018-06-04T14:20:0004 June 2018 14:20:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip on Lowering Steam Generator Water Level ENS 533712018-04-30T16:24:00030 April 2018 16:24:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Following Turbine Trip ENS 533582018-04-22T21:46:00022 April 2018 21:46:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Undervoltage Actuation of the Engineered Safety Feature Bus ENS 533472018-04-19T16:52:00019 April 2018 16:52:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Undervoltage Actuation of the Engineered Safety Feature Bus ENS 514502015-10-05T06:05:0005 October 2015 06:05:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Specified System Actuations ENS 503012014-07-24T00:30:00024 July 2014 00:30:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Based on Shots Fired in the Owner Controlled Area ENS 469362011-06-08T15:26:0008 June 2011 15:26:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Flooding That Potentially Affected Safety Related Equipment ENS 466942011-03-24T15:18:00024 March 2011 15:18:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unexpected Loss of Annuciators During Planned Maintenance ENS 462622010-09-20T22:04:00020 September 2010 22:04:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 461782010-08-16T07:06:00016 August 2010 07:06:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trips at Both Units ENS 456182010-01-10T01:51:00010 January 2010 01:51:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Declared Due to a Fire in the Auxiliary Building Lasting Greater than 15 Minutes ENS 452382009-07-31T02:08:00031 July 2009 02:08:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to a Loss of Offsite Power for Greater than 15 Minutes ENS 450172009-04-24T16:41:00024 April 2009 16:41:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip During Instrument Calibration ENS 447432008-12-27T20:18:00027 December 2008 20:18:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip as a Result of a Generator Trip ENS 435902007-08-23T20:30:00023 August 2007 20:30:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Manual Reactor Trip Because of Lowering Condenser Vacuum ENS 434492007-06-27T14:21:00027 June 2007 14:21:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Due to Off-Site Power Fluctuation ENS 415342005-03-28T19:59:00028 March 2005 19:59:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hydrogen Leak ENS 415352005-03-28T18:46:00028 March 2005 18:46:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Due to Generator Protection Circuitry ENS 412802004-12-22T19:07:00022 December 2004 19:07:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Rps Actuation Due to Steam Generator Low Level Signal ENS 403702003-12-03T09:36:0003 December 2003 09:36:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Plant Had an Auto Reactor Trip from 100% Power Due to Steam Generator Low Level ENS 402982003-11-05T03:32:0005 November 2003 03:32:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Braidwood 2 Afw Support System Actuation During Outage 2025-07-30T17:30:00 | |