| Title | Unusual Event Declared Due to Hydrogen Leak |
| Event Description | The licensee faxed the following information:
Following the Unit 2 trip, (due to a malfunction of the generator protection circuitry), a hydrogen leak was identified on the Unit 2 main generator. The leakage was sufficient enough to cause a flammable gas release affecting normal plant operation. The Unusual Event was declared under HU6 - Hazards and Other Conditions. The State and local authorities were notified at 14:09 CST. There is NO fire, it is a hydrogen release only. The licensee said the hydrogen totalizer, which indicated a flow rate of 100 cfm, may be a probable area of leakage. The hydrogen leaked directly into the turbine building. Air samples indicated personnel breathing apparatus was not required. The licensee expects to exit from the UE once the hydrogen system was purged with CO2. Estimated timeframe is 3-6 hours. The licensee notified the NRC Resident Inspector.
The licensee terminated their Unusual Event at 16:40 CST, and the plant status is 0% power / Mode 3. The hydrogen leak was determined to be from a bushing on the main generator. The hydrogen leakage is believed to have lasted only 5 minutes. The licensee notified the State and NRC Resident Inspector. Notified R3DO (Riemer), IRD Manager (Crlenjak), NRR EO (Berkow), FEMA and DHS.
|
| Where | |
|---|---|
| Braidwood Illinois (NRC Region 3) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration | |
| Time - Person (Reporting Time:+-4.53 h-0.189 days <br />-0.027 weeks <br />-0.00621 months <br />) | |
| Opened: | Craig Ingold 15:27 Mar 28, 2005 |
| NRC Officer: | John Knoke |
| Last Updated: | Mar 29, 2005 |
| 41534 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Not Critical |
| Scram | No |
| Before | Hot Standby (0 %) |
| After | Hot Standby (0 %) |
WEEKMONTHYEARENS 503012014-07-24T00:30:00024 July 2014 00:30:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Based on Shots Fired in the Owner Controlled Area ENS 469362011-06-08T15:26:0008 June 2011 15:26:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Flooding That Potentially Affected Safety Related Equipment ENS 466942011-03-24T15:18:00024 March 2011 15:18:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unexpected Loss of Annuciators During Planned Maintenance ENS 456182010-01-10T01:51:00010 January 2010 01:51:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Declared Due to a Fire in the Auxiliary Building Lasting Greater than 15 Minutes ENS 452382009-07-31T02:08:00031 July 2009 02:08:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to a Loss of Offsite Power for Greater than 15 Minutes ENS 415342005-03-28T19:59:00028 March 2005 19:59:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hydrogen Leak 2014-07-24T00:30:00 | |