ENS 45618
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
01:51 Jan 10, 2010 | |
| Title | Notification of Unusual Event Declared Due to a Fire in the Auxiliary Building Lasting Greater than 15 Minutes |
| Event Description | At 1925 [hrs. CST], the Main Control Room received a notification of smoke in the Auxiliary Building Ventilation Supply Plenum. Fire Brigade and the Incident Commander were dispatched. Once [they] arrived at the scene, they noted smoke in the area of the 0C VA Supply Fan and requested the fan be shutdown. The 0C VA supply fan was shutdown at 1933 hrs. The operators reported smoke and a small fire coming from the inboard bearing of the 0C VA supply fan. A CO2 fire extinguisher was used to put the fire out and cool the bearing. A total of 2 extinguishers were used. The fire was declared out at 1941 hrs. Both Units remained stable and at full power during the entire event.
There were no injuries, and no off site assistance was required. The licensee notified state and local authorities and the NRC Resident Inspector.
At 2111 CST [on] 1-9-2010, the Unusual Event was terminated. The fire is out. Both Units are stable. A fire watch is established. There are no signs of reflash. [Braidwood] no longer [meets the] Unusual Event action level threshold. The licensee has notified the NRC Resident Inspector. Notified IRD (Grant), R3DO (Stone), NRR EO (Giiter), DHS (Inzler) and FEMA (Casto). |
| Where | |
|---|---|
| Braidwood Illinois (NRC Region 3) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration | |
| Time - Person (Reporting Time:+-4.3 h-0.179 days <br />-0.0256 weeks <br />-0.00589 months <br />) | |
| Opened: | Mike Deboard 21:33 Jan 9, 2010 |
| NRC Officer: | Howie Crouch |
| Last Updated: | Jan 9, 2010 |
| 45618 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 503012014-07-24T00:30:00024 July 2014 00:30:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Based on Shots Fired in the Owner Controlled Area ENS 469362011-06-08T15:26:0008 June 2011 15:26:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Flooding That Potentially Affected Safety Related Equipment ENS 466942011-03-24T15:18:00024 March 2011 15:18:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unexpected Loss of Annuciators During Planned Maintenance ENS 456182010-01-10T01:51:00010 January 2010 01:51:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Declared Due to a Fire in the Auxiliary Building Lasting Greater than 15 Minutes ENS 452382009-07-31T02:08:00031 July 2009 02:08:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to a Loss of Offsite Power for Greater than 15 Minutes ENS 415342005-03-28T19:59:00028 March 2005 19:59:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hydrogen Leak 2014-07-24T00:30:00 | |