ENS 41326
ENS Event | |
|---|---|
19:30 Jan 12, 2005 | |
| Title | 24 Hour Condition of License Report Regarding Halon System Actuator Port Connection Error |
| Event Description | At 1330 on January 12, 2005, station personnel identified an error in connection of pilot lines to the manual-pneumatic actuator on halon bottles required for fire suppression. The vendor was contacted to confirm the configuration. The vendor indicated that the halon bottles would not properly discharge if the pilot lines were not properly connected.
The system engineer inspected the halon systems. It was determined that five of six fire areas protected by halon systems were affected. Fire watches were implemented for the affected fire areas. Affected areas: A-27, Load Center/MG set Room, main - correct, reserve - 1 valve correct/1 valve incorrect A-17, South Electrical Penetration Room, main - correct, reserve - incorrect A-18, North Electrical Penetration Room, Main - correct, reserve - correct C-9, ESF Switchgear room 1*, main - incorrect, reserve - incorrect C-10, ESF Switchgear room 2*, main - incorrect, reserve - incorrect C-27, Control room cable trenches/chases**, bottle 1 - correct, bottle 2 - incorrect The main bank is sufficient to suppress a fire in a fire area.
The design and licensing basis for the fire protection system does not require consideration of a fire in more than one fire area at a time. No degraded fire barriers between the above fire areas were identified which would have allowed a fire to affect more than one of the fire areas at a time. Repairs were immediately initiated to correct the condition. As of 2010 CST, the repairs have been completed for the affected fire areas and restored to operable status. The licensee notified the NRC Resident Inspector.
Investigation - Informational tests conducted by the Vendor (Chemetron) and witnessed by Wolf Creek, Callaway, and NRC personnel on January 26, 2005 determined that the Halon systems would have properly actuated in the as-found incorrect configuration (port 'A' and 'B' connections reversed). The only identified difference in the actuation sequence between the tests conducted in the incorrect configuration versus the correct configuration is a delay of less than 2 seconds from the time the solenoid received the discharge signal until the first cylinder actuated. There is no regulatory or National Fire Protection Association standard or guideline that places a time requirement on this interval. This very slight time delay would have had no effect on the designed function of the Halon suppression system to extinguish a fire. Additional details are provided in the Chemetron report, 'Report on Actuation Arrangements for Halon Extinguishing System Units,' (Correspondence ULNRC 05-121) that includes the test procedure and results. Halon system function is to establish sufficient halon concentration for sufficient time to suppress a fire. This capability was not lost with the delay in actuation. Regulatory Evaluation - Guidance for reporting to the criterion of 10 CFR 50.73(a)(2)(ii) is provided in section 3.2.4 of NUREG 1022 rev 2, 'Event Reporting Guidelines 10 CFR50.72 and 50.73.' This guidance states that an LER is required for a seriously degraded principal safety barrier or an unanalyzed condition that significantly degrades plant safety. Operating License Condition 2.C(5)(c) states the following: The Operating Corporation shall maintain in effect all provisions of the approved fire protection program as described in the SNUPPS Final Safety Analysis Report for the facility through Revision 15, the Callaway site addendum through Revision 8, and as approved in the SER through Supplement 4, subject to provisions d below. Conclusion: - Based upon the information provided, the Halon suppression system would have operated to extinguish a fire. This condition is not considered reportable to the requirements of 10 CFR 50.72(b)(3)(ii)(B), 10 CFR 50.73(a)(2)(ii), nor is it a violation of the Operating License Condition 2.C(5)(c). Consistent with this conclusion, ENS notification 41326 for this event is to be retracted. The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Callaway Missouri (NRC Region 4) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Other Unspec Reqmnt | |
| Time - Person (Reporting Time:+2.3 h0.0958 days <br />0.0137 weeks <br />0.00315 months <br />) | |
| Opened: | David Lantz 21:48 Jan 12, 2005 |
| NRC Officer: | Bill Gott |
| Last Updated: | Feb 23, 2005 |
| 41326 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 41326\u003C/a\u003E - \u003Ca href=\"/Callaway\" title=\"Callaway\"\u003ECallaway\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E24 Hour Condition of License Report Regarding Halon System Actuator Port Connection Error\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 41326 - Callaway\n","link":"","lat":38.76076111111111,"lon":-91.78175833333333,"icon":"/w/images/0/06/Ameren_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 559722022-05-02T04:05:0002 May 2022 04:05:00
[Table view]Other Unspec Reqmnt, 10 CFR 50.73(a)(1), Submit an LER Invalid Specified System Actuation ENS 548062020-07-30T13:15:00030 July 2020 13:15:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition ENS 534852018-07-03T05:00:0003 July 2018 05:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition En Revision Imported Date 8/1/2018 ENS 532232018-02-20T18:25:00020 February 2018 18:25:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition All Three Auxiliary Feedwater Pumps Inoperable Due to Helb Door Being Open ENS 529052017-08-15T16:46:00015 August 2017 16:46:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Discovery of Non-Conforming Conditions During Tornado Hazards Analysis ENS 526072017-03-13T18:58:00013 March 2017 18:58:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Discovery of Non-Conforming Conditions During Tornado Hazards Analysis ENS 518742016-04-20T19:05:00020 April 2016 19:05:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Due to Essential Service Water Pressure Transient ENS 506252014-11-19T01:00:00019 November 2014 01:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Due to All Four Safety Injection Accumulators Inoperable ENS 504742014-09-19T16:34:00019 September 2014 16:34:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Due to a Postulated Hot-Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 494222013-10-09T20:00:0009 October 2013 20:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Fire Event Could Result in a Hot Short That Could Adversely Impact Safe Shutdown Equipment ENS 478852012-05-01T18:00:0001 May 2012 18:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Floor Drain Blockage Adversely Affects Asumptions of Pipe Break Analysis for Electrical Switghear Rooms ENS 477832012-03-28T20:00:00028 March 2012 20:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Degraded Condition Identified in the B Train Containment Cooler Units ENS 474262011-11-09T23:50:0009 November 2011 23:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Potential Failure of High Density Polyethylene Piping in Esw System ENS 470842011-07-21T16:00:00021 July 2011 16:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Potential Adverse Effect on Esw Train During a Postulated Control Room Fire ENS 467152011-03-31T19:32:00031 March 2011 19:32:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Identified for Inoperable Rwst Level ENS 466932011-03-24T04:54:00024 March 2011 04:54:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Pressure Transmitters Needed for Auxiliary Feedwater Suction Path Not Analyzed for Potential High Energy Line Break ENS 465972011-02-07T15:18:0007 February 2011 15:18:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition High Energy Line Break Analysis for Aux Steam to the Auxiliary Building ENS 457472010-03-05T19:25:0005 March 2010 19:25:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Steam Supply Valve Credited as Closed in Fsar Analysis Is Normally Open During Operations ENS 455712009-12-15T20:30:00015 December 2009 20:30:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Helb Configuration Calculations Not Consistent with Previous Helb Analysis ENS 445602008-10-11T05:49:00011 October 2008 05:49:00 Other Unspec Reqmnt Discovery of an After-The-Fact Notification of Unusual Event ENS 428522006-09-08T15:15:0008 September 2006 15:15:00 Other Unspec Reqmnt Discovery of After-The-Fact Emergency Condition: Inapproriate Change Made to Emergency Action Level 3J Back in 1997 Caused an Emergency, Alert, Not to Be Declared. ENS 422422006-01-04T19:45:0004 January 2006 19:45:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Related to Emergency Diesel Fuel Oil Tank Vortex Formation ENS 413262005-01-12T19:30:00012 January 2005 19:30:00 Other Unspec Reqmnt, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition 24 Hour Condition of License Report Regarding Halon System Actuator Port Connection Error ENS 412052004-09-18T22:35:00018 September 2004 22:35:00 Other Unspec Reqmnt Discovery of After-The-Fact Emergency Condition (Unusual Event) ENS 407052004-04-26T22:11:00026 April 2004 22:11:00 Other Unspec Reqmnt Technical Specifications Required Report of Steam Generator Defective Tubes ENS 403732003-12-03T18:30:0003 December 2003 18:30:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Emergency Procedure Deficiency Causes Unanalyzed Condition 2022-05-02T04:05:00 | |