ENS 40372
ENS Event | |
|---|---|
20:00 Dec 3, 2003 | |
| Title | Backward Installation of Containment Loop Seal Penetration Vacuum Breakers |
| Event Description | Vacuum breakers 1WL980 and 2WL980 are installed backwards. In their current orientation, the valves will not lift from their seats to break a siphon into the corresponding unit's Ventilation Unit Condensate Drain Tank (VUCDT).
The VUCDT input line is a 6-Inch pipe. There is a loop seal between the outboard containment isolation valve and the VUCDT. Since the VUCDT is vented to the auxiliary building environment, the purpose of the loop seal is to provide a barrier between the containment atmosphere and the auxiliary building atmosphere during normal unit operations. The purpose of the vacuum breaker is to prevent siphoning water out of the loop seal. In its current configuration, the vacuum breaker will not open. The loop seal is not needed to provide a barrier between the containment atmosphere and the auxiliary building atmosphere during a large break Loss of Coolant Accident (LOCA) because valves 1(2)WL867A and 1(2)WL869B will close on a Phase B containment isolation signal on high-high containment pressure (3.2 psig in containment, accounting for instrument error). During certain small break LOCAs, however, a high-high containment isolation signal may not occur, since pressure might not reach the setpoint. In this scenario, the loop seal is needed to isolate the containment atmosphere from the auxiliary building atmosphere. Given the size of the VUCDT inlet piping, the only mechanism that could form a siphon out of the loop seal is a large flow of water that would push the air out of the top of the loop seal. In this instance, a siphon could form and pull water out of the low point of the loop seal. If this were to occur, a vent path from the containment atmosphere to the auxiliary building atmosphere would be open. However, during normal operation, there is not sufficient flow into the tank to make this a plausible scenario. For a large break LOCA, containment pressure would rise quickly to the high-high setpoint; then the inoperable VUCDT loop seal would be isolated by its containment isolation valves. For smaller LOCAs, particularly, for a rod ejection accident resulting in a LOCA, containment pressure would rise slowly- from 2.81 psig (the pressure at which the loop seal isolation function would fail), until 3.2 psig (the maximum high-high containment pressure setpoint, accounting for instrument error), the inoperable loop seal would represent a containment leak path. The rod ejection accident does result in a high level of fuel clad failure; therefore, the unisolated containment leak path represents a source of release to the environment until such time as the high-high containment pressure setpoint is reached (if it is reached). The dose consequences associated with this potential leak path have not been evaluated. Upon discovery of the incorrectly installed vacuum breakers, the containment isolation valves associated with this penetration flow path were closed to isolate the path. The Unit 2 loop seal configuration has since been modified to correct this situation. The Unit 1 loop seal configuration will be modified prior to the completion of the current end of cycle 14 refueling outage. The incorrect installation of the vacuum breakers was identified on 11/03/03, and it is being investigated on how long this condition has existed. It is possible that it has existed since construction. The licensee will notify the NRC Resident Inspector, state and local regulatory agencies.
The subject EN was made on 12/3/03. Following additional review by the licensee, this event was determined to not meet the reportability requirements of 10 CFR 50.72. The event was determined to not result in a degraded or unanalyzed condition, as the consequences of the event were determined to be bounded by transients currently analyzed and described in the Updated Final Safety Analysis Report (UFSAR). In addition, the event did not represent a failure of structures, systems, or components utilized to control the release of radiological material or to mitigate the consequences of an accident. The licensee is therefore retracting the subject EN. The licensee notified the NRC Resident Inspector. Notified R2DO (P. Fredrickson) |
| Where | |
|---|---|
| Catawba South Carolina (NRC Region 2) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+-4.37 h-0.182 days <br />-0.026 weeks <br />-0.00599 months <br />) | |
| Opened: | Don Bradley 15:38 Dec 3, 2003 |
| NRC Officer: | Jeff Rotton |
| Last Updated: | Jan 13, 2004 |
| 40372 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Catawba | |
WEEKMONTHYEARENS 579062025-09-05T13:09:0005 September 2025 13:09:00
[Table view]10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Degraded Condition ENS 561652022-10-15T15:59:00015 October 2022 15:59:00 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Reactor Vessel Head Penetration Repair Degraded ENS 552752021-05-25T21:51:00025 May 2021 21:51:00 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Unit 2 Containment Local Leak Rate and As-Found Integrated Overall Leakage Rate Exceeded Acceptance Criteria ENS 552012021-04-21T02:30:00021 April 2021 02:30:00 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Reactor Coolant System (Rcs) Pressure Boundary Degraded ENS 547072020-05-13T02:20:00013 May 2020 02:20:00 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Reactor Coolant System Pressure Boundary Degraded ENS 542332019-08-18T21:00:00018 August 2019 21:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Refueling Water Storage Tank Level Lower than Required ENS 542862019-07-06T05:56:0006 July 2019 05:56:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Both Trains of Component Cooling Water Determined Inoperable ENS 499902014-04-02T20:00:0002 April 2014 20:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Fire Related Unanalyzed Condition That Could Impact Credited Safe Shutdown Analysis ENS 483482012-09-26T19:15:00026 September 2012 19:15:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Technical Specification 3.0.3 Entered Due to Surveillance Testing Not Being Completed as Required ENS 457102010-02-19T00:15:00019 February 2010 00:15:00 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Rcs Pressure Boundary Leakage Identified on Rtd Weld ENS 439452008-01-30T17:20:00030 January 2008 17:20:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Auxiliary Feedwater Pumps Declared Inoperable Based on Postulated Main Feedwater Line Break Scenario ENS 434052007-06-05T00:08:0005 June 2007 00:08:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Fire Safe Shutdown Capability Impacted by a Breaker Coordination Issue ENS 410482004-09-17T14:00:00017 September 2004 14:00:00 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Apparent Pressure Boundary Leakage Identified on Steam Generator Bowl Drains ENS 408372004-06-23T21:00:00023 June 2004 21:00:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Related to Fire Protection Cable Separation ENS 404512004-01-15T23:50:00015 January 2004 23:50:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident Potential Gas Binding of Centrifugal Charging Pump ENS 403722003-12-03T20:00:0003 December 2003 20:00:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded, 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Backward Installation of Containment Loop Seal Penetration Vacuum Breakers ENS 403592003-11-28T03:55:00028 November 2003 03:55:00 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Component Cooling System Surge Tank Supports May Fail During a Seismic Event 2025-09-05T13:09:00 | |