Finding | |
|---|---|
| Title | Inadequate Acceptance Criteria in the Insulation Resistance Test Procedure |
| Description | The inspectors identified a finding of very low safety significance (Green) and associated NCV of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the failure to have adequate acceptance criteria in a testing procedure. Specifically, the minimum acceptable insulation resistance for transformers as specified in Procedure CPS 8440.01 did not meet the minimum vendor recommended values in accordance with the vendor manual. The licensee entered this concern into its Corrective Action Program as IR 01596730 and IR 01598375. The performance deficiency was determined to be more than minor because it was associated with the Mitigating Systems cornerstone attribute of design control and affected the cornerstone objective of ensuring capability and reliability of systems that respond to initiating events to prevent undesirable consequences. The finding screened as very low safety significance (Green), because the inspectors answered No to all Mitigating Systems Screening questions in Exhibit 2 of Appendix A of IMC 0609. The inspectors identified the finding had a cross-cutting aspect in the area of problem identification and resolution, associated with the corrective action program component because the licensee failed to ensure issues potentially impacting nuclear safety are promptly identified. P.1(a). [Section 4OA3.2.b (2) |
| Site: | Clinton |
|---|---|
| Report | IR 05000461/2013009 Section 4OA3 |
| Date counted | Dec 31, 2013 (2013Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71153 |
| Inspectors (proximate) | A Boland A Dahbur B Bonser C Phillips J Mcghee |
| Violation of: | 10 CFR 50 Appendix B Criterion V |
| CCA | P.1, Identification |
| INPO aspect | PI.1 |
| ' | |
Finding - Clinton - IR 05000461/2013009 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Clinton) @ 2013Q4
Self-Identified List (Clinton)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||